IF102E Installation, Operation & Maintenance Manual Models 075 and 150

download IF102E Installation, Operation & Maintenance Manual Models 075 and 150

of 26

Transcript of IF102E Installation, Operation & Maintenance Manual Models 075 and 150

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    1/26

    IF102E

    Installation, Operation& Maintenance Manual

    Models 075 and 150 Coro-Flo Pumps

    Frame MountANSI Flange (FF) and DIN Flange (FD)

    Direct MountANSI Flange (DLF) and DIN Flange (DLD)Warning: (1) Periodic inspection and maintenance of Corken products is essential.(2) Inspection, maintenance and installation of Corkenproducts must be made only by experienced, trained and qualified personnel. (3)Maintenance, use and installation of Corken productsmust comply with Corken instructions, applicable laws and safety standards (suchas NFPA Pamphlet 58 for LP-Gas and ANSI K61.1-1972 for Anhydrous Ammonia). (4) Transfer of toxic, dangerous, flammable or

    explosive substances using Corken products is at usersrisk and equipment should be operated only by qualified personnel according toapplicable laws and safety standards.

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    2/26

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    3/26

    Always include the model number and serial number when ordering parts.

    Model No.

    Serial No.

    Date Purchased

    Date Installed

    Purchased From

    Installed By

    2

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    4/26

    Table of Contents

    Principles of the Coro-FloPump ................................................................................................................................. 4Exclusive Features of Your Coro-FloPump .............................................................................

    .................................... 4Installation of Your Coro-FloPump .............................................................................................................................. 5Inlet Piping Should Include theFollowing ................................................................................................................... 5Outlet Piping Should Include theFollowing ................................................................................................................ 5

    Bypass System Must Include the

    Following ............................................................................................................... 5Design Criteria for Underground TankApplications....................................................................................................... 6

    Pump Foundation for Frame MountedModels ........................................................................................................... 6

    Level

    Base................................................................................................................................................................... 6

    Coupling Alignment for Frame MountedModels ........................................................................................................ 6

    DriverInstallation .......................................................................................................................................................

    . 6

    Wire SizingChart ........................................................................................................................................................ 7Operation of Your Coro-FloPump............................................................................................................................... 7Filling New Cylinders andTanks ............................................................................

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    5/26

    ........................................................ 8Preventative Maintenance Program for Your Coro-FloPump ..................................................................................... 8Repair and Service on Your Coro-FloPump ................................................................................................................ 9Seal Replacement

    Instructions.................................................................................................................................... 10

    Appendix A:

    Model Number and Mounting Identification Codes for 075-Model Coro-FloPumps............................................ 15

    Model Number and Mounting Identification Codes for 150-Model Coro-FloPumps............................................ 16Appendix B: Material and Operating Specifications for 075- and 150-Model Coro-Flo

    Pumps ...............................17Appendix C:

    Performance Curves for 075-Model Coro-FloPumps ............................................................................................ 18

    Performance Curves for 150-Model Coro-FloPumps ............................................................................................ 19Appendix D: Outline Dimensions for 075- and 150-Model Coro-FloPumps ............................................................ 20

    Appendix E: Parts Details for 075- and 150-Model Coro-FloPumps ....................................................................... 22Appendix F: Installation Tips for 075- and 150-Model Coro-FloPumps ................................................................... 24Appendix G: TroubleshootingGuide ............................................................................................................................ 31Appendix H: Extended StorageProcedures ................................................................................................................ 33

    3

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    6/26

    Principles of the Coro-Flo Pump

    The Corken Coro-Flo pump is a special type of pumpknown as a turbine or regenerative pump. The liquidflows into the inlet nozzle and into the passagewayon each side of an impeller (the rotating element) and

    is recirculated constantly between the vanes or teethof the impeller and this passageway as the impellerrotates. The fluid makes a complete revolution in thepump case and is diverted through the outlet flange.The horsepower required to drive the pump increasesas the differential pressure increases, but the capacitydecreases at the same time. Differential pressure is thedifference between the pressure at the inlet of the pumpand at the outlet of the pump.

    The impeller is the only moving part and has no contactwith the casing. Consequently, practically no wear occursto the impeller, even when pumping volatile liquids such as

    LP-gas or ammonia which have little lubricating qualities.

    Exclusive Features of YourCoro-Flo Pump

    The pumping of volatile liquids is one of the mostdifficult of all pumping applications. Unlike otherpumping applications, more attention must be givento the design, manufacture, installation and operationof the pump.

    INLET

    High strengthmetric fasteners.

    Case and cover ofASTM A536 ductileiron, providingmaximum thermalshock protection.

    Self-aligning, free-floating,precision machinedimpeller, incorporatingproprietary design,

    optimizes flow andprovides quiet nonpulsatingtransfer.

    Maximum sealingprovided by a singlebalanced, precisionlapped, mechanical seal.

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    7/26

    OUTLETDesigned for easeof service. Sealcan be replaced inminutes by simplyremoving the cover.

    In addition to being a pump type especially suited for

    handling volatile liquids, your Coro-Flo pump has anumber of features which help to make it more easilyoperated and maintained.

    The Coro-Flo pumps of this series are manufactured tobe directly connected to an electric motor (direct mount)or with their own frame for connection by means of aflexible coupling (frame mount).

    UNDERWRITERS LABORATORIES, INC. has testedand inspected the Coro-Flo pumps of this series andhas listed them for use in the handling of LP-gas andammonia fluids. The nameplate on the pump includes the

    UL registration along with other certifications.

    DUCTILE IRON has been used in the manufacture of thispump for parts under pressure.

    THE IMPELLER floats on a shaft and may be replacedeasily without disturbing the piping or driver by simplyremoving the cover. No special tools are needed.

    THE MECHANICAL SEAL ASSEMBLY may be easily replacedby removing the cover and impeller without disturbing thepiping or driver. No special tools are needed.

    PRESSURE GAUGE CONNECTIONS, 1/4" FNPT, areprovided on the inlet and outlet nozzles.

    ANSI and DIN 300# flangesprovide optimal leak control andenhances structural integrity.

    Pressure gauge connectionshelp simplify analysis ofsystem performance.

    Heavy-duty ball bearings are ratedfor continuous duty service andprovide maximum life.

    Three mounting options available:direct drive with coupling, beltdrive, and direct mounted with Cfaceelectric motor.

    4

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    8/26

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    9/26

    Installation of Your Coro-Flo Pump

    NOTE: Must be installed in a well ventilated area.

    THE INSTALLATION OF A CORO-FLO pump is simple.However, in order for the pump to deliver optimumperformance, the principles discussed in this book should be

    followed. The piping details are furnished to illustrate methodsproved by hundreds of installations. Your own needs mayrequire slight variations, but every effort should be made tofollow the recommendations identified in this manual.

    For more detailed piping recommendations, refer to pages2429. For outline dimensional drawings, refer to AppendixD (pages 20 & 21).

    For the transfer of flammable liquids like LPG, the pumpassembly must be installed according to the applicablelocal safety and health regulations. The installer and/orthe user must take into account the following:

    Potential risk due to local conditions regarding the installationand operation (e.g. poor ventilation and additional risks dueto other elements in the vicinity, etc.). Qualification of the personnel. Type of liquid being transferred. Specificsafety measures to be applied (e.g. gasdetection, automatic shut-off valves, personal protectionequipment etc.).The following table shows the weight of the bare pumpfor each model. For handling a bare pump, lifting slingsshould be placed around the inlet and outlet flange

    neck of the pump. Web slings are preferred over metalslings to minimize damage to the paint.

    ModelShipping Weightlb kgFrame Mount 63 28.6Direct Mount 75 34.0

    NO PUMP CAN DISCHARGE MORE LIQUID THAN ITRECEIVES, so the location and the inlet piping must begiven careful attention. If the inlet piping is inadequate tosupply the demand of the pump, you may expect trouble!

    The inlet line size should be the same size as the pumpsuction or next size larger. Pressure loss between thestorage tank and the pump should be minimized.

    THE PUMP SHOULD BE LOCATED AS CLOSE TO THESTORAGE TANK as possible on above ground tanks. Thecomplete inlet line, including the vertical line from thetank, should not exceed 12 feet (3.6 m) in length. Thebottom of the tank should be at least two feet (0.6 m)above the pump inlet nozzle, and four feet (1.2 m) shouldbe considered standard.

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    10/26

    The inlet should include the following:

    1.The tank excess flow valve (EFV) should have a flowrate of 1-1/2 to 2 times the capacity of the pump. Donot use an EFV without knowing its flow capacity.2.

    Pressure gauge at pump suction nozzle.3. The tank shutoff valve should be a full port ball valveor an internal valve.4.A strainer of the Y type with a 20 mesh screen shouldbe on the inlet line of the pump.5.A flexible connection should be used on the pumpinlet or outlet to accommodate piping strains.6. An eccentric swage should be used at the pump inletnozzle to change line size (flat side up).7.The inlet line must be level or slope downward to the

    pump.The outlet piping should include the following:

    1.A pressure gauge should be installed in the openingprovided on the outlet nozzle or in the outlet pipingnear the pump. This pressure gauge will tell you thecomplete story of the operation inside your pump. Besure you have one installed.2.A hydrostatic relief valve must be installed in theoutlet piping.3.

    If the outlet piping exceeds 50 feet (15.2 m) in length, acheck valve should be installed near the pump outlet.The bypass system must include the following:

    1.The pump bypass system must be installed.Without this system, the pump has little chance ofperforming.2.A CORKEN B166 BYPASS VALVE (a special valve tovent the pump of vapors and to act as a differentialrelief valve) is ideal.3.

    The bypass line should rise uninterrupted to anopening in the vapor section of the storage tank. Thetank fitting should be either an excess flow valve or avapor return valve; it should never be a filler valve or aback check valve.4.To meet Underwriters Laboratories (UL) specifications,an external bypass valve must be connected in thepiping between the pump discharge nozzle and thesupply tank for pump recirculation. When bypassingthe full output of the pump, the external bypass valve

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    11/26

    must limit the differential pressure to 125 pounds persquare inch.5

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    12/26

    Design Criteria for UndergroundTank Applications:

    Minimize suction frictional losses:-Locate pump as close as possible to the tanks liquidoutlet connection.

    -Eliminate strainer since the tank itself acts as a sumpto collect foreign materials.-Use full-port ball valves or low restrictive valves.-Use 2-inch (51 millimeter) pipe. Minimize the net static suction lift to 14 feet (4.3 m)maximum. Use vapor eliminator valves. Use back-pressure check valves downstream the pump. Limit the capacity of the pump to a maximum of 1.5percent of the tanks capacity. For example, with a

    1,000-gallon (3,785 liter) tank, limit the capacity of thepump to 15 gallons per minute (56.8 liters per minute).Pump foundation for frame mounted models

    The pump assembly must be securely attached to aconcrete foundation using all the available holes in thepump assembly footing. The total weight of the concretefoundation should be approximately twice the weight ofthe pump assembly. The foundation must be level anddeep enough to get below the ground frost line in thelocation. There are many ways to construct a foundation,and the example in figure 1 is only a suggestion.

    Figure 1

    Level base

    After the concrete has set, check the pump base for level.Drive metal shims under the base near the anchor boltsas below. Tighten anchor bolts and recheck the base forlevel (see figure 2).

    Figure 2

    Coupling alignment for frame mount models

    The coupling must be properly aligned to give quiet, longlifeservice to the pump and driver. The pump and drivershafts are carefully aligned at the factory but shouldalways be checked after the pump is installed and beforethe initial operation.

    Place a straight edge across coupling halves, top andside; both positions must line up to be correct.

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    13/26

    If misalignment exists, adjust the shims between thepump base and the foundation until exact alignment isaccomplished (see figure 3).

    Figure 3

    Driver installation

    A qualified electrician, in accordance with all the localstandards and regulations, must undertake the electricalinstallation. The wire size chart on page 7, figure 4indicates the minimum standards for wire sizes.

    Improper motor wiring may cause you to experienceexpensive motor difficulties from low voltage. If you suspectyou have low voltage, call your power company. Wiring yourmotor for the voltage you have available is important. Be sureyour motor is connected to the proper voltage. Connectingto improper voltage will completely destroy your motor.

    With explosion-proof motor applications in humid climates,the normal breathing and alternating temperatures of themotor (warm during operation and cold when stopped) willoften cause moist air to be drawn into the motor housing.This moist air will condense and may eventually addenough free water to the inside of the motor to cause it tofail. To prevent this, make a practice of running the motorand pump at least once a week on a dry day for an houror so (pump through the bypass system). This allows themotor to heat and vaporize the condensed moisture. Nomotor manufacturer will guarantee an explosion-proof ortotally enclosed motor against damage from moisture.

    ENGINE DRIVERS require special consideration; themanufacturer's instructions must be followed. When theCoro-Flo pump is equipped with an engine from thefactory, the engine speed should normally not exceed 3,600rpm. Excessive engine speed will overload the engine andcause early failure. The engine loses 3 percent of its powerfor every 1,000 feet above sea level, so if your installation isat a higher altitude than normal, consult the factory.

    6

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    14/26

    Motor Recommended Wire Size, AWGHp Motor Phase VoltsApproximateFull LoadAmperesLength of Run in Feet0100 to 200 to 300

    Pump must rotate clockwise when viewed from the motor. If not, switch any two ofthe three incoming 3 phase lines.3 1 115 34.0 6 4 2230 17.0 12 8 83 230 9.6 12 12 12460 4.8 12 12 125 1 115 56.0 4 1 1/0230 28.0 10 6 43 230 15.2 12 12 10460 7.6 12 12 127-1/2 1 230 40.0 8 6 43 230 22.0 10 10 8460 11.0 12 12 12

    10 3 230 28 8 6 4460 14 12 12 1015 3 230 42 6 4 4460 21 10 10 820 3 230 54 6 6 4460 27 10 10 10Motor Recommended Wire Size, AWGHp Motor Phase VoltsApproximateFull LoadAmperesLength of Run in Feet0100 to 200 to 300

    Pump must rotate clockwise when viewed from the motor. If not, switch any two ofthe three incoming 3 phase lines.3 1 115 34.0 6 4 2230 17.0 12 8 83 230 9.6 12 12 12460 4.8 12 12 125 1 115 56.0 4 1 1/0230 28.0 10 6 43 230 15.2 12 12 10460 7.6 12 12 127-1/2 1 230 40.0 8 6 43 230 22.0 10 10 8460 11.0 12 12 12

    10 3 230 28 8 6 4460 14 12 12 1015 3 230 42 6 4 4460 21 10 10 820 3 230 54 6 6 4460 27 10 10 10Figure 4: Wire Size Chart for Wiring Electric Motor1

    1Each country may use a different form of wire size measurement (AWG, SWG, mm2etc.). The above wiring size chart is based on the United StatesNational Electrical Code (NEC) guidelines for America Wire Gauge (AWG) sizes.

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    15/26

    These wire sizes and distances are based on nominal supplied voltages.Additional derating is necessary when the voltage is less than that shown. Consultyour local standards and regulation for specific wiring requirements.

    Operation of Your Coro-Flo Pump

    It is absolutely essential that the operator be fully informedof the pumps recommended operation procedures and

    safety precautions. See Appendix B & C, pages 1719 foroperating specifications and performance. The operatormust be made aware of the specific risks generated bythe product handled and be familiar with the purpose andfunction of all piping, valves, and instrumentation, etc. ofthe installation.

    The following steps should be performed for the initialpumping operation:

    1.Close shutoff valve on the end of the delivery hose.2.

    Open the storage tank bottom shutoff valve.3. Open the shutoff valve in the pump bypass system.4.Check the motor for the proper voltage (see instructionsunder driver installation).5.Record pressure gauge readings on suction of pump.6.Start the pump and circulate liquid through thebypass system.7.Adjust the B166 bypass valve by turning the adjustingscrew counterclockwise until the pump pressure

    gauge shows nearly the same pressure it did beforeyou started the pump. Screw the adjusting screwclockwise until the pressure gauge indicates therequired pressure or until the pump starts to losedischarge pressureyou will know this by the rapidfluctuating of the pointerthen back the adjustingscrew out a turn or two until the pressure gauge againindicates a steady pressure. Lock the lock nut andpermit the pump to circulate liquid for a half hour ormore. If the motor overload protection device stopsthe motor during this period, this indicates the bypasssystem valve is set too high and should be readjustedby turning the adjusting screw out until the motor will

    run for this period.When properly installed and operated, Coro-Flo pumpsshould not exceed a 80 dBA noise level at a distance ofone meter (3.281 ft.) from the surface of the pump.

    7

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    16/26

    Item to Check Daily MonthlyThreeMonthsSixMonths1. Visual Inspection; leaks, hoses, pipes, etc.2. Clean Inlet Strainer Screen

    3. Inspect Drive Coupling and Guard4. Lubricate Pumps Bearing15. Lubricate Motors Bearing26. Performance Test7. Re-tighten Bolts8. Inspect Motor Starter Points

    Figure 5: Preventive Maintenance Chart for Coro-Flo Pumps1If the pump runs continuously, it should be lubricated more frequently.

    2Follow the motor manufacturers recommendations.

    Filling New Cylinders and Tanks

    All new containers are full of air and since air will not liquefyunder reasonable filling pressures, it must be purged. Toensure proper gas supply to burners and carburetors,purging air from new containers is essential.

    Some cylinders are difficult to fill because they areequipped with a fill tube that extends down into the liquidportion of the container. If possible, these cylindersshould be refitted so the incoming liquid enters thevapor section of the cylinder. If refitting is impossibleor impractical, rock the cylinder as it is being filled so

    that liquid will splash up into the vapor section. Thiswill help keep the cylinder filling pressure down to areasonable limit. A properly fitted cylinder and fillingmanifold will permit filling a cylinder at no more than 50to 60 psi differential pressure. When the pump is new,it is recommended to record the flow rate, dischargepressure and suction pressure.

    Preventive Maintenance Programfor Coro-Flo Pumps

    Purpose

    By following an effective preventive maintenanceprogram, unscheduled downtime can be eliminated. Thisprogram should be used by the Operation Manager toget a maximum utilization of manpower and equipmentas well as to prevent possible unsafe situations and/orproduction delays due to equipment breakdown.

    Scope

    The Preventive Maintenance chart in figure 5 includesthe items to be regularly checked and inspected

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    17/26

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    18/26

    5.Lubricate motor bearing:Follow the recommendations of the electric motormanufacturer for the type of grease to use and thelubrication frequency.

    6. Performance test:

    A.While transferring liquid with the pump, checkthe pressure at the pumps inlet port. Thepressure drop in the inlet piping should not begreater than 3 pounds per square inch.B.While transferring liquid with the pump, close thedischarge valve(s) so the full flow will be directedback to the storage tank through the bypassvalve. Then slowly close the valve downstream ofthe bypass valves. The discharge pressure of thepump should increase to the maximum differentialpressure of the pump at no flow conditions (see

    pages 18 & 19, Appendix C: Performance Curves).C.If the maximum differential pressure is notobtained, the pump should be serviced. Visuallyinspect the pumps impeller (refer to instructionson pages 1014).Replace the impeller if damaged, broken, warpedor worn.

    A uniform wear of the impeller will not be visuallydetected. If the impeller has no visible damages,it can be re-used. The impellers wear canbe compensated by removing the adjustment

    shims on the pumps cover. Remove one shimat a time, tighten the pumps cover and assurethat the pumps shaft rotates. If the pump islocked, re-install the last shim and make sure theshaft rotates easily. For additional help, refer toAppendix G, page 31 Troubleshooting Guide.

    7.Re-tighten all hold down bolts.8. Inspect motor starter contact points:This must be performed by an authorized and qualifiedelectrician, based on the electric motor manufacturersguidelines.

    9.See Appendix H, page 33 for extended storageprocedures.Repair and Service on YourCoro-Flo Pump

    All repairs to the pump must be performed byqualified personnel in a safe manner, utilizing toolsand/or equipment that are free of hazards, andfollows the applicable safety codes of practice set

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    19/26

    by the local authorities having jurisdiction. Makesure the system pressure has been relieved beforeattempting any repair to the pump.

    After a long service life, repairs are limited to replacingthe impeller or mechanical seal.

    The only wearing part influencing the pumping action

    is the impeller, so we suggest the pump be given anefficiency test before any attempt is made to repair it.The trouble may lie in the piping system rather than in thepump. If the pump will still produce as much differentialpressure when circulating through the bypass systemas it did when new, you can be sure that your problemis in the system and not with the pump. If the pumpdoes not produce as much pressure as it did originally,remove the cover and inspect the impeller. If visualinspection indicates the impeller is in good condition,remove the thin shim gasket and replace the cover. Manytimes this procedure will adjust for slight impeller wear.If the impeller is badly worn or damaged, it should be

    replaced. For additional help, refer to Appendix G, page31, Troubleshooting Guide.

    REPLACING THE IMPELLER is a matter of removing thecover and removing the old impeller from the shaft. Ifthe old impeller is tight on the shaft, threaded bolt holesare provided in the impeller to use for pulling. The newimpeller must be a good slip fit on the shaft; it shouldfloat on the shaft, so it may be necessary to lightlysand the shaft. Clean the pump prior to reassembly (referto pages 1014).

    REPLACING THE MECHANICAL SEAL is simple and

    replacement parts are immediately available.

    The pumps can be configured with various types of sealsand O-rings. Selection of the seals and O-ring materialsare based on the product that is being transferred.The most compatible seals and O-ring materials mustbe selected. Consult the factory or distributor forrecommendations if the pump is not handling theproduct for which it was initially purchased. The modelcode in the identification plate of the pump indicates thematerials in the pump. Refer to pages 1517, Appendix Aand B, for the material in your pump.

    9

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    20/26

    Seal Replacement Instructions for 075 and 150-Model Coro-Flo Pumps

    Caution

    Bleed all pressure from the pump and piping before starting to install your newseal assembly.

    Cleanliness

    The smallest amount of dirt on your new seal can prevent a proper seal and causepremature failure. Keep all parts,tools and your hands clean while installing the seal. Avoid touching the smoothlapped faces of the carbon rotor orseal seat. For LP-gas, anhydrous ammonia and similar liquids, you are trying toseal a fluid that is 5 to 10 times thinnerthan water! Your new seal needs every chance it can get, so keep it clean.

    Workmanship

    Your CORKEN pump is a precision piece of equipment with very close clearances.

    Treat it as such. Never useexcessive force during disassembly or assembly.

    DISASSEMBLY:STEP 1Cover/head removal: Remove thecover/head screws and pull the cover/head and case O-ring from the case.Older models will have a clearanceshim/s as well. NOTE: This is a closetolerance fit so if the cover/head doesnot slide out easily, use two flatheadscrewdrivers to slowly pry the cover/

    head away from the pump casing.

    STEP 2Retainer ring, impeller and impellerkey removal: Using a pick or smallflathead screwdriver, pry off the retainerring and remove the impeller. NOTE:This retainer ring does not apply toolder models prior to serial number226858AG. If the impeller does not slideoff the shaft freely, insert two cover/headscrews in the threaded holes provided

    and gently pull outward as shown.

    NOTE: Being forceful with the removalcould warp the impeller or damage thecase O-ring groove so use care duringthis step. Lastly, remove the impellerkey. If the impeller key does not slideoff the shaft freely, use side cutters, apick or a small screwdriver to pry thekey up and out of the pump shaft.

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    21/26

    STEP 3Retainer ring removal: NOTE: Sealassembly shown is an old design andlooks slightly different than our currentdesign listed on the front cover of thisbooklet. Using a flathead screwdriveror pick, pry up and pull out on the

    retainer ring to remove it from thegroove and slide off the shaft. Makesure you do not damage the shaftwhile removing the retainer ring.

    10

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    22/26

    STEP 4Seal sub assembly removal: Slidethe seal sub assembly (seal and sealsleeve) off the shaft. Next, remove theseal sleeve O-ring from the shaft.

    NOTE: Seal assembly shown is an

    old design and looks slightly differentthan our current design listed on thefront cover of this booklet.

    STEP 5Seal housing removal: Using a 90pick or hook tool inserted behindthe face of the seal housing, slowlypull out around the circumferenceof the seal housing until you canremove it from the pump casingwith your fingers.

    STEP 6Seal housing O-ring removal andbearing inspection: Using a pick,remove the old seal housing O-ringinside the pump casing. Clean theO-ring groove and shaft and removeany burrs around the keyway. Thepump shaft bearings should bechecked by applying up and down orin and out movement. Since the sealassembly resides on the pump shaft,

    excess movement may cause a sealleak. In addition, check the bearingsfor any roughness while turningthe shaft. Change the bearings ifroughness or movement is present.

    STEP 7Seal seat removal: The seal seatis located inside of the seal housingand must be removed using a pick orsmall screwdriver by gently prying theseal seat out evenly around the inner

    circumference of the seal housingassembly. NOTE: The seal housingassembly should be cleaned beforeinserting the new seal seat.

    11

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    23/26

    ASSEMBLYSTEP 8Verify contents of your new 31891X_6 seal assembly and cleanpump shaft before installation.

    NOTE: Install two locator pins into

    the seal sleeve assembly beforeproceeding to STEP 9. Refer to theold seal sleeve for proper location ofthe locator pins.

    STEP 9Assembling seal housing assemblyand seal seat: Make certain thelocator pin is installed inside thehole on the seal housing. Clean sealhousing assembly inside and outbefore inserting the new seal seat.

    Place a light coat of oil on the sealseat O-ring. Insert the seal seat withthe notch pointing down and in linewith the locator pin in the back of theseal housing assembly. To protectseal seat during installation, place thesmall cardboard disk found in the sealassembly package on top of the sealseat. Make sure the cardboard diskis clean. Using your fingers, gentlypush on the cardboard disc to installthe seal seat inside the seal housing.Make sure the locator pin is aligned

    with the notch in the seal seat.

    STEP 10Installation of seal housing O-ringand seal housing: Apply a thin coatof oil to the new seal housing O-ringand install. NOTE: Insert the O-ringinto the groove of the pump casingand hold in place with one finger.

    With a pick or small screwdriver, useyour other hand to seat the O-ring

    using a circular motion. Apply a thincoat of oil to the seal housing andpress evenly into the pump casinguntil it snaps into place.

    12

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    24/26

    STEP 11Installation of seal sleeve O-ring:

    Clean pump shaft and install thenew seal sleeve O-ring. Make surethe O-ring is seated on the shoulder

    of pump shaft.

    STEP 12Assembly of seal and seal sleeve:

    Apply a thin coat of oil to the carbonface and the O-ring behind thecarbon and insert the seal sleeveinto the seal by aligning the locatingpin on the seal sleeve with the notch/hole on the seal. NOTE: The current

    and previous seal assemblies areshown to the right. Although some ofthe installation photos show the olddesign, the assembly instructions arethe same for the current design.

    Current design: Part #3189-1X_6 Previous design: Part #5264-X_6

    STEP 13Installation of seal: Before installingyour new seal, make sure yourhands are clean. Small debris or

    contamination may cause your sealto leak. Align the seal drive pin withthe pump shaft keyway and slide theseal assembly onto the shaft until theseal assembly snaps into place.

    NOTE: Although some of theinstallation photos show the old sealdesign, the assembly instructions arethe same for the current seal design.

    Push inwardSTEP 14

    Installation of first retainer ring:

    Install the first retainer ring on the shaftnear the seal sleeve. NOTE: In order toseat the retainer ring inside the retainerring groove, you may use the impellerto compress the seal assembly. Placethe impeller on the shaft backwards(hub side in) and push inward until theretainer ring snaps into the groove on

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    25/26

    the pump shaft. After the retainer ringhas been seated into the groove, youwill need to remove the impeller. Forquick removal, insert one of the cover/head bolts into the impeller and pull.

    NOTE: Although some of the installationphotos show the old seal design, the

    assembly instructions are the same forthe current seal design.

    13

  • 8/14/2019 IF102E Installation, Operation & Maintenance Manual Models 075 and 150

    26/26

    STEP 15Installation of impeller key: Installthe new impeller key into the keywayslot located at the end of the pumpshaft. For proper installation, installthe impeller with the hub side out.The impeller must slide on the shaft

    freely. If the shaft does not slidefreely, carefully remove any burrsfrom the impeller key and/or keywaywith a small file. Remove all fillingsfrom the pump shaft and casing.

    NOTE: Although some of theinstallation photos show the old sealdesign, the assembly instructions arethe same for the current seal design.

    STEP 16

    Securing impeller and impeller key(second retainer ring): Make certainthe impeller is pushed back to thepump casing. To ensure the impellerand impeller key stay in place, thesecond retainer ring should now beinstalled in the groove located at theend of the pump shaft. For ease ofremoval, it is best to overlap one sideof the open end of the retainer ringinto the keyway opening.

    STEP 17Cover/head installation: Replacethe cover/head O-ring, case clearanceshim (necessary for older pumpmodels), and cover/head and torqueeach bolt to 60 ftlbs. Be certain theCorken label on the cover/head ishorizontal and/or upright. On oldermodels, it may be necessary to installmore than one clearance shim if thepump will not turn after installationof the cover/head. After assemblingthe pump, ensure the pump impeller

    turns freely by rotating the pump