IEEE-Grounding-Transformers (1).ppt
-
Upload
maribel-benites -
Category
Documents
-
view
233 -
download
1
Transcript of IEEE-Grounding-Transformers (1).ppt
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
1/45
11February, 2007
Medford,Oregon
March 2011
Medford, Oregon
Grounding Transformers
John S. Levine, P.E.
Levine Lectronic and Lectric, !nc.
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
2/45
• It is used to provide a ground path onIt is used to provide a ground path oneither an ungrounded Wye or a Deltaeither an ungrounded Wye or a Delta
connected systemconnected system• The relatively low impedance path to ground The relatively low impedance path to ground
maintains the system neutral at ground potentialmaintains the system neutral at ground potential
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
3/45
• On Ungrounded systems you canOn Ungrounded systems you can
have overvoltages of 6 to 8 timeshave overvoltages of 6 to 8 times
normal with arcing faultsnormal with arcing faults
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
4/45
•Plot of transient overvoltage for an arcingPlot of transient overvoltage for an arcing
ground faultground fault
!rcing "round #aults!rcing "round #aults
Intermittent or $estri%eIntermittent or $estri%e
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
5/45
•Intermittent ground fault:Intermittent
ground fault: ! restri%ing ground fault can create a! restri%ing ground fault can create ahigh fre&uency oscillator '$() circuit*+ independent of ( and ) values+high fre&uency oscillator '$() circuit*+ independent of ( and ) values+
causing high transient overvoltages,causing high transient overvoltages,
– i,e, restri%ing due to ac voltage waveform or loose wire caused -yi,e, restri%ing due to ac voltage waveform or loose wire caused -y
vi-rationvi-ration
V V
480V Delta Source
3Ø Load
Cb bC
R fe
faS
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
6/45
CONTROL OF TRANSIENT OVERVOLTAGE
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
7/45
• It supports the voltage on aIt supports the voltage on a
faulted phasefaulted phase
– If a single linetoground fault occurs on anIf a single linetoground fault occurs on anungrounded or isolated system+ no return pathungrounded or isolated system+ no return pathe.ists and no current /owse.ists and no current /ows
– The system will continue to operate -ut the The system will continue to operate -ut the
other two unfaulted lines will rise in in voltageother two unfaulted lines will rise in in voltage-y the s&uare root of 0+ possi-ly overstressing-y the s&uare root of 0+ possi-ly overstressing
the transformer insulation+ and otherthe transformer insulation+ and othercomponents+ -y 102components+ -y 102
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
8/45
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
9/45
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
10/45
• Provides a metering point to measureProvides a metering point to measure
faultsfaults
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
11/45
! typical e.ample is a Wind #arm, Theyutili3e grounding transformers for faultprotection on ungrounded lines
When a ground fault occurs on a collector ca-le causes the
su-station circuit -rea%er to open+ the wind tur-ine string -ecomesisolated
Tur-ines do not always detect the fault and the generators continue toenergi3e the ca-le,
4oltages -etween the unfaulted ca-le and the ground rise -y the102
The transformer+ placed on the tur-ine string+ provides the groundpath
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
12/45
A typia! e"amp!e is a #ind Farm$
#%en t%e feeder &rea'er
Opens( t%e o!!etor &us and
t%e step up transformer de!ta
onneted )V *indings
re!y on t%e Grounding
Transformer for t%eir ground
pat% and +o!tage support$
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
13/45
Two di5erent constructions
ZIG ZAG (Zn)
WYE CONNECTED
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
14/45
•What if no neutral e.ists 'i,e, delta systems*7What if no neutral e.ists 'i,e, delta systems*7 – ! grounding transformer is installed 'either a 3ig3ag or! grounding transformer is installed 'either a 3ig3ag or
a wyedelta* from all three phases to create an articiala wyedelta* from all three phases to create an articial
neutral for grounding purposesneutral for grounding purposes onlyonly,,
HRG
Broken Delta
Grounding
Transformers
Wye-Delta
Grounding
Transformers
HRGHRG
Zig-Zag
Grounding
Transformer
CØBØAØ AØ BØ CØAØ BØ CØ
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
15/45
• The 3ig3ag transformer contains si. coilson three cores, The rst coil on each coreis connected contrariwise to the second
coil on the ne.t core,• The second coils are then all tied
together to form the neutral and thephases are connected to the primary
coils,• 9ach phase+ therefore+ couples with each
other phase and the voltages cancel out
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
16/45
Typia! #ye onnetion *it%
Neutra! end of *indings onnetedToget%er
A , C
Symmetria! t%ree p%ase soure
A , C
Vetor diagram of
&a!aned system
A
,
C
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
17/45
T%e -ig.-ag onnetion %as /
*indings on ea% !eg$
A
,
C
a
&
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
18/45
C
,
A
&
aEa% !eg of t%e -ig.-ag
Connetion is onneted
to a *inding from anot%er *%i%is out of p%ase
,
C
A
&
a
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
19/45
C0
A0
,0
T%e resu!ting -ig.-ag onnetion
Is p%ase s%ifted *it% respet to t%e
inoming t%ree p%ase soure
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
20/45
• (imits circulation of triplen harmonics
' 0 rd+ 6th+ :th+ etc*
• )an -e used without a Deltaconnected or ;legged core
• 9limination of secondary windingresults in smaller footprint+ lowercost '
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
21/45
• Includes a Delta or Wye connectedsecondary
• Utili3es > or ; legged core when Wyeconnected secondary is specied
• ?ultifunctional+ provides -enet ofau.iliary power
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
22/45
• Primary 4oltage• Phase to Phase
continuous primarycurrent 'or $ated %4!*
• )ontinuous @eutralcurrent
• !vaila-le #ault )urrentand Duration
• Impedance as a 2 oras an ohmsAphasevalue
• Primary Windingconnection
• Becondary connection
• Casic overallconstruction
1no* t%e &asi parameters
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
23/45
• This is the system voltage to whichthe grounded winding is to -econnected,
• Dont forget to specify the CI( also,
• In some cases the CI( will -e dictated-y e&uipment considerations+ such as
1;= %4 CI( on 0>,; %4 wind farms-ecause of the limitation of deadfront connectors
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
24/45
• The Transformer must -e si3ed to carrythe rated continuous+ phasetophasecurrent without e.ceeding its temperature
limit• The higher the current+ the larger and
more costly the transformer
• Typical values can -e as low as ; amps to
as high as a few hundred
• Include any au.iliary loading re&uirements
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
25/45
• Is dened as 0E the PhasetoPhasecurrent 'Fero Be&uence )urrent*
• It is the value that is e.pected to /owin the neutral circuit without trippingprotective circuits
• Used to design for thermal capacity
of the transformer
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
26/45
• Used to determine the short timeheating resulting from a fault on thesystem which returns through the
transformer• Typical ranges run from a few
hundred to a few thousand amps
• Duration is e.pressed in seconds 'i,e,>== amps for 1= seconds*
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
27/45
• )an -e e.pressed as either a percentage oras an ohmic value
• 9ither should -e chosen such that the un
faulted phase voltages are within thetemporary overvoltage capa-ility of• The Transformer
• !ssociated e&uipment 'i,e, arresters+ terminalconnectors+ etc,*
• Typical values can -e as low as 82 and asmuch as 1==2
• ?ust -e determined -y the system designer
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
28/45
• Fig Fag or "rounded Wye
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
29/45
• Bpecify the secondary voltageand connection for primary Wyeconnected transformers
• Bpecify si3e of au.iliary loadingto -e connected
• If two winding with no secondaryload+ advise if the delta windingcan -e G-uriedH 'not -roughtout* or if only one -ushing is to-e -rought out for grounding tothe tan% or testing
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
30/45
• )ompartmentalpad mount or unitsu-station design
• Indoor or outdoor• #luid type '?ineralOil+ Bilicone+ or9nvirotemp #$0*
• Bite 9levation or9nvironmentalconditions
• )onnectivity• Dead #ront or (ive
#ront
• Bpade terminals
• )overmounted orsidewall
• 9.posed or enclosed
• Temperature $ise• 6; degrees )
• ;; degrees )• ;;A6; deg, )
• Bpecial )oatingre&uirements
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
31/45
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
32/45
06= degree coolingducts
"ound #oi$"ound #oi$
Radia! fores are e2ua!i0ed during s%ort iruits 3 o+er!oads
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
33/45
#rucifor% tac&ed core contruction#rucifor% tac&ed core contruction
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
34/45
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
35/45
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
36/45
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
37/45
The following transformers are The following transformers are
for reference only to let you -efor reference only to let you -eaware of di5erent typeaware of di5erent type
transformers for di5erenttransformers for di5erent
applications,applications,
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
38/45
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
39/45
• ! Bcott T Transformer is a! Bcott T Transformer is a
transformer that is designed fortransformer that is designed for
converting < phase current to 0converting < phase current to 0
phase current or viceversa,phase current or viceversa,
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
40/45
• !n autotransformer is a transformer that only!n autotransformer is a transformer that only
have one winding with taps, @o isolation ishave one winding with taps, @o isolation isprovided -etween the primary and secondary,provided -etween the primary and secondary,
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
41/45
• ! Cuc%Coost! Cuc%Coost
transformer is onetransformer is onethat is designedthat is designedto lower '-uc%* orto lower '-uc%* orraise '-oost* theraise '-oost* thevoltage in thevoltage in the
range of ;2 torange of ;2 to
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
42/45
• ! drive isolation! drive isolationtransformer is onetransformer is onethat is typically usedthat is typically usedon !) or D) Driveon !) or D) Drivesystems, It typicallysystems, It typically
has the samehas the sameprimary andprimary andsecondary voltagessecondary voltagesand is used forand is used for
isolation, Inisolation, Inaddition youaddition youtypically have atypically have ashield to attenuateshield to attenuateline to ground noise,line to ground noise,
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
43/45
• ! constant voltage transformer is one in! constant voltage transformer is one in
which the secondary stays constant withwhich the secondary stays constant with
large swings on the primary voltage,large swings on the primary voltage,
This is accomplished -y operating the This is accomplished -y operating theprimary in a saturated mode so evenprimary in a saturated mode so even
when the primary voltage dips you canwhen the primary voltage dips you can
still maintain a constant output, Typicalstill maintain a constant output, Typical
input may -e 8=2 to 11=2 with theinput may -e 8=2 to 11=2 with theoutput maintaining 12 voltageoutput maintaining 12 voltage
regulation,regulation,
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
44/45
A copy of thisA copy of this
presentation presentation
can be foundcan be found
at:at:
www.L-3.comwww.L-3.com
or more information and
-
8/18/2019 IEEE-Grounding-Transformers (1).ppt
45/45
www. PacificCrestTrans.com
or more information and!"e#i$#ation !%eet!
http://c/POWERPNT/SAMPLES/webpage.ppthttp://c/POWERPNT/SAMPLES/webpage.ppt