IEEE-Grounding-Transformers (1).ppt

download IEEE-Grounding-Transformers (1).ppt

of 45

Transcript of IEEE-Grounding-Transformers (1).ppt

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    1/45

    11February, 2007

    Medford,Oregon

    March 2011

    Medford, Oregon

    Grounding Transformers

    John S. Levine, P.E.

    Levine Lectronic and Lectric, !nc.

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    2/45

    •  It is used to provide a ground path onIt is used to provide a ground path oneither an ungrounded Wye or a Deltaeither an ungrounded Wye or a Delta

    connected systemconnected system•  The relatively low impedance path to ground The relatively low impedance path to ground

    maintains the system neutral at ground potentialmaintains the system neutral at ground potential

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    3/45

    • On Ungrounded systems you canOn Ungrounded systems you can

    have overvoltages of 6 to 8 timeshave overvoltages of 6 to 8 times

    normal with arcing faultsnormal with arcing faults

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    4/45

    •Plot of transient overvoltage for an arcingPlot of transient overvoltage for an arcing

    ground faultground fault

    !rcing "round #aults!rcing "round #aults

     Intermittent or $estri%eIntermittent or $estri%e

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    5/45

    •Intermittent ground fault:Intermittent

    ground fault:  ! restri%ing ground fault can create a! restri%ing ground fault can create ahigh fre&uency oscillator '$() circuit*+ independent of ( and ) values+high fre&uency oscillator '$() circuit*+ independent of ( and ) values+

    causing high transient overvoltages,causing high transient overvoltages,

     – i,e, restri%ing due to ac voltage waveform or loose wire caused -yi,e, restri%ing due to ac voltage waveform or loose wire caused -y

    vi-rationvi-ration

    V V

    480V Delta Source

    3Ø Load

    Cb bC

    R fe

    faS

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    6/45

    CONTROL OF TRANSIENT OVERVOLTAGE

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    7/45

    • It supports the voltage on aIt supports the voltage on a

    faulted phasefaulted phase

     – If a single linetoground fault occurs on anIf a single linetoground fault occurs on anungrounded or isolated system+ no return pathungrounded or isolated system+ no return pathe.ists and no current /owse.ists and no current /ows

     –  The system will continue to operate -ut the The system will continue to operate -ut the

    other two unfaulted lines will rise in in voltageother two unfaulted lines will rise in in voltage-y the s&uare root of 0+ possi-ly overstressing-y the s&uare root of 0+ possi-ly overstressing

    the transformer insulation+ and otherthe transformer insulation+ and othercomponents+ -y 102components+ -y 102

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    8/45

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    9/45

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    10/45

    • Provides a metering point to measureProvides a metering point to measure

    faultsfaults

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    11/45

      ! typical e.ample is a Wind #arm, Theyutili3e grounding transformers for faultprotection on ungrounded lines

     When a ground fault occurs on a collector ca-le causes the

    su-station circuit -rea%er to open+ the wind tur-ine string -ecomesisolated

     Tur-ines do not always detect the fault and the generators continue toenergi3e the ca-le,

    4oltages -etween the unfaulted ca-le and the ground rise -y the102

     The transformer+ placed on the tur-ine string+ provides the groundpath

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    12/45

     A typia! e"amp!e is a #ind Farm$

    #%en t%e feeder &rea'er

    Opens( t%e o!!etor &us and

    t%e step up transformer de!ta

    onneted )V *indings

    re!y on t%e Grounding

    Transformer for t%eir ground

    pat% and +o!tage support$

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    13/45

     Two di5erent constructions

    ZIG ZAG (Zn)

    WYE CONNECTED

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    14/45

    •What if no neutral e.ists 'i,e, delta systems*7What if no neutral e.ists 'i,e, delta systems*7 – ! grounding transformer is installed 'either a 3ig3ag or! grounding transformer is installed 'either a 3ig3ag or

    a wyedelta* from all three phases to create an articiala wyedelta* from all three phases to create an articial

    neutral for grounding purposesneutral for grounding purposes onlyonly,,

    HRG

    Broken Delta

    Grounding

    Transformers

    Wye-Delta

    Grounding

    Transformers

    HRGHRG

    Zig-Zag

    Grounding

    Transformer

    CØBØAØ AØ BØ CØAØ BØ CØ

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    15/45

    •  The 3ig3ag transformer contains si. coilson three cores, The rst coil on each coreis connected contrariwise to the second

    coil on the ne.t core,•  The second coils are then all tied

    together to form the neutral and thephases are connected to the primary

    coils,• 9ach phase+ therefore+ couples with each

    other phase and the voltages cancel out 

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    16/45

    Typia! #ye onnetion *it%

    Neutra! end of *indings onnetedToget%er 

     A , C

    Symmetria! t%ree p%ase soure

     A , C

    Vetor diagram of

    &a!aned system

     A

    ,

    C

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    17/45

    T%e -ig.-ag onnetion %as /

    *indings on ea% !eg$

     A

    ,

    C

    a

    &

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    18/45

    C

    ,

     A

    &

    aEa% !eg of t%e -ig.-ag

    Connetion is onneted

    to a *inding from anot%er *%i%is out of p%ase

    ,

    C

     A

    &

    a

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    19/45

    C0

     A0

    ,0

    T%e resu!ting -ig.-ag onnetion

    Is p%ase s%ifted *it% respet to t%e

    inoming t%ree p%ase soure

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    20/45

    • (imits circulation of triplen harmonics

      ' 0 rd+ 6th+ :th+ etc*

    • )an -e used without a Deltaconnected or ;legged core

    • 9limination of secondary windingresults in smaller footprint+ lowercost '

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    21/45

    • Includes a Delta or Wye connectedsecondary

    • Utili3es > or ; legged core when Wyeconnected secondary is specied

    • ?ultifunctional+ provides -enet ofau.iliary power

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    22/45

    • Primary 4oltage• Phase to Phase

    continuous primarycurrent 'or $ated %4!*

    • )ontinuous @eutralcurrent

    • !vaila-le #ault )urrentand Duration

    • Impedance as a 2 oras an ohmsAphasevalue

    • Primary Windingconnection

    • Becondary connection

    • Casic overallconstruction

    1no* t%e &asi parameters

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    23/45

    •  This is the system voltage to whichthe grounded winding is to -econnected,

    • Dont forget to specify the CI( also,

    • In some cases the CI( will -e dictated-y e&uipment considerations+ such as

    1;= %4 CI( on 0>,; %4 wind farms-ecause of the limitation of deadfront connectors

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    24/45

    •  The Transformer must -e si3ed to carrythe rated continuous+ phasetophasecurrent without e.ceeding its temperature

    limit•  The higher the current+ the larger and

    more costly the transformer

    •  Typical values can -e as low as ; amps to

    as high as a few hundred

    • Include any au.iliary loading re&uirements

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    25/45

    • Is dened as 0E the PhasetoPhasecurrent 'Fero Be&uence )urrent*

    • It is the value that is e.pected to /owin the neutral circuit without trippingprotective circuits

    • Used to design for thermal capacity

    of the transformer

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    26/45

    • Used to determine the short timeheating resulting from a fault on thesystem which returns through the

    transformer•  Typical ranges run from a few

    hundred to a few thousand amps

    • Duration is e.pressed in seconds 'i,e,>== amps for 1= seconds*

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    27/45

    • )an -e e.pressed as either a percentage oras an ohmic value

    • 9ither should -e chosen such that the un

    faulted phase voltages are within thetemporary overvoltage capa-ility of•  The Transformer

    • !ssociated e&uipment 'i,e, arresters+ terminalconnectors+ etc,*

    •  Typical values can -e as low as 82 and asmuch as 1==2

    • ?ust -e determined -y the system designer

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    28/45

    • Fig Fag or "rounded Wye

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    29/45

    • Bpecify the secondary voltageand connection for primary Wyeconnected transformers

    • Bpecify si3e of au.iliary loadingto -e connected

    • If two winding with no secondaryload+ advise if the delta windingcan -e G-uriedH 'not -roughtout* or if only one -ushing is to-e -rought out for grounding tothe tan% or testing

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    30/45

    • )ompartmentalpad mount or unitsu-station design

    • Indoor or outdoor• #luid type '?ineralOil+ Bilicone+ or9nvirotemp #$0*

    • Bite 9levation or9nvironmentalconditions

    • )onnectivity• Dead #ront or (ive

    #ront

    • Bpade terminals

    • )overmounted orsidewall

    • 9.posed or enclosed

    •  Temperature $ise• 6; degrees )

    • ;; degrees )• ;;A6; deg, )

    • Bpecial )oatingre&uirements

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    31/45

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    32/45

    06= degree coolingducts

    "ound #oi$"ound #oi$

    Radia! fores are e2ua!i0ed during s%ort iruits 3 o+er!oads

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    33/45

    #rucifor% tac&ed core contruction#rucifor% tac&ed core contruction

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    34/45

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    35/45

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    36/45

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    37/45

     The following transformers are The following transformers are

    for reference only to let you -efor reference only to let you -eaware of di5erent typeaware of di5erent type

    transformers for di5erenttransformers for di5erent

    applications,applications,

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    38/45

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    39/45

    • ! Bcott T Transformer is a! Bcott T Transformer is a

    transformer that is designed fortransformer that is designed for

    converting < phase current to 0converting < phase current to 0

    phase current or viceversa,phase current or viceversa,

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    40/45

    • !n autotransformer is a transformer that only!n autotransformer is a transformer that only

    have one winding with taps, @o isolation ishave one winding with taps, @o isolation isprovided -etween the primary and secondary,provided -etween the primary and secondary,

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    41/45

    • ! Cuc%Coost! Cuc%Coost

    transformer is onetransformer is onethat is designedthat is designedto lower '-uc%* orto lower '-uc%* orraise '-oost* theraise '-oost* thevoltage in thevoltage in the

    range of ;2 torange of ;2 to

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    42/45

    • ! drive isolation! drive isolationtransformer is onetransformer is onethat is typically usedthat is typically usedon !) or D) Driveon !) or D) Drivesystems, It typicallysystems, It typically

    has the samehas the sameprimary andprimary andsecondary voltagessecondary voltagesand is used forand is used for

    isolation, Inisolation, Inaddition youaddition youtypically have atypically have ashield to attenuateshield to attenuateline to ground noise,line to ground noise,

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    43/45

    • ! constant voltage transformer is one in! constant voltage transformer is one in

    which the secondary stays constant withwhich the secondary stays constant with

    large swings on the primary voltage,large swings on the primary voltage,

     This is accomplished -y operating the This is accomplished -y operating theprimary in a saturated mode so evenprimary in a saturated mode so even

    when the primary voltage dips you canwhen the primary voltage dips you can

    still maintain a constant output, Typicalstill maintain a constant output, Typical

    input may -e 8=2 to 11=2 with theinput may -e 8=2 to 11=2 with theoutput maintaining 12 voltageoutput maintaining 12 voltage

    regulation,regulation,

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    44/45

    A copy of thisA copy of this

     presentation presentation

    can be foundcan be found

    at:at:

    www.L-3.comwww.L-3.com

    or more information and

  • 8/18/2019 IEEE-Grounding-Transformers (1).ppt

    45/45

    www. PacificCrestTrans.com

    or more information and!"e#i$#ation !%eet!

    http://c/POWERPNT/SAMPLES/webpage.ppthttp://c/POWERPNT/SAMPLES/webpage.ppt