CURRENT TRANSFORMERSC
UR
RE
NT
TR
AN
SF
OR
ME
RS
PHONE (614) 889-6152TECH. ASSISTANCE (614) 876-8308
FAX # (614) 876-85384970 Scioto Darby Rd. Hilliard, Ohio 43026Div. Morlan & Associates, Inc.
57
Manufactured to meet the requirements of ANSI/IEEE C57.13
Designed for outdoor service.Suitable for operating meters, instruments, relays and control devices.Insulation Level ...............15.5kV, 110kV BIL per C57.13Frequency ...............................................................60HzWeight .........................................Approximately 40 Lbs.
JCK-5C are manufactured utilizing state of the art Automated Pressure Gelation (APG) processes and Hydrophobic Cycloaliphatic Epoxy (HCEP) for the entire line of 15kV outdoor current transformers. Insulation levels meet or exceed those specified in IEEE C57.13 and CSA CAN3-C13. Dimensions meet IEEE C12.11. Superior designs, HCEP epoxy, and APG processes, are combined to produce the highest quality and reliability available in the industry for outdoorapplications.
CATALOG NUMBER
CURRENT RATIORELAY CLASS
60HzMETERING CLASS
60HzRATING FACTOR
SINGLE RATIO JCK-5C 15kV, 110kV BIL
755C152001 5:5 C40 0.3 B-0.5 3.0
755C152002 10:5 C40 0.3 B-0.5 3.0
755C152003 15:5 C40 0.3 B-0.5 3.0
755C152004 20:5 C40 0.3 B-0.5 3.0
755C152005 25:5 C40 0.3 B-0.5 3.0
755C152006 30:5 C40 0.3 B-0.5 3.0
755C152007 40:5 C40 0.3 B-0.5 3.0
755C152008 50:5 C40 0.3 B-0.5 3.0
755C152009 75:5 C40 0.3 B-0.5 3.0
755C152010 100:5 C40 0.3 B-0.5 3.0
755C152011 150:5 C40 0.3 B-0.5 3.0
755C152012 200:5 C40 0.3 B-0.5 3.0
755C152013 300:5 C40 0.3 B-0.5 3.0
755C152014 400:5 C40 0.3 B-0.5 3.0
755C152015 600:5 C40 0.3 B-0.5 2.0
755C152016 800:5 C40 0.3 B-0.5 1.5
755C152017 1000:5 C40 0.3 B-0.5 1.2
755C152018 1200:5 C40 0.3 B-0.5 1.0
OUTDOOR CURRENT TRANSFORMER MODEL JCK-5C
FEATURES
SPECIFICATIONS 15KV CLASS
CURRENT TRANSFORMERSC
UR
RE
NT
TR
AN
SF
OR
ME
RS
PHONE (614) 889-6152TECH. ASSISTANCE (614) 876-8308
FAX # (614) 876-85384970 Scioto Darby Rd. Hilliard, Ohio 43026Div. Morlan & Associates, Inc.
58
10.88
10.000.440.44 X 0.88 SLOTS
12.378.18
0.66
9.50
2.00
4.000.50
1.000.75
13.81
GRD. CONNECTION0.44 HOLE
3.50
ALUMINUM LV JUNCTION BOX
4.73 3.63
DIM “A”
1.00
5.381.05
1" NPT BOTH SIDES
0.19
0.560.56H1 H2
TOP VIEW
FRONT VIEW RIGHT SIDE VIEW
All Dimensions In Inches
DIM. A RATIO
0.25" 5:5-250:5 A
0.50" 300:5-1200:5 A
DIMENSIONS MODEL JCK-5C