IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose...
Transcript of IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose...
![Page 1: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/1.jpg)
IEEE Boston Section- February 19, 2019John Teixeira, National Grid
IEEE 1366- Reliability Indices
![Page 2: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/2.jpg)
Some Important Definitions
![Page 3: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/3.jpg)
3National Grid
1. To foster uniformity in the development of distribution service reliability indices and to aid in consistent reporting practices among utilities.
2. To provide guidance for new personnel in the reliability area and to provide tools for internal as well as external comparisons.
Purpose of IEEE-1366
![Page 4: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/4.jpg)
4National Grid
Customer:
“A metered electrical service point for which an active bill account is established at a specific location.”
Sounds like common sense.
Just remember:
A Three-decker is three customers.
An apartment building may be 100 customers.
Load doesn’t matter.
Population doesn’t matter.
What’s a customer
![Page 5: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/5.jpg)
5National Grid
Interruption:
“The total loss of electric power on one or more normally energized conductors to one or more customers connected to the distribution portion of the system.”
Does not include “Power Quality” issues (sags, swells, etc.)
Part power?
Loss of “power” not “voltage”?
Outage:
“The loss of ability of a component to deliver power.”
Interruption vs. Outage
Distinction:
Interruption refers to CUSTOMERS
Outage refers to EQUIPMENT
![Page 6: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/6.jpg)
6National Grid
Momentary Interruption:
“The brief loss of power delivery to one or more customers caused by the opening and closing operation of an interrupting device.”
Each recloser operation is a separate momentary interruption
Sustained Interruption:
“Any interruption not classified as a part of a momentary event. That is, any interruption that lasts more than five minutes.”
Some companies and/or jurisdictions may use one minute or some other interval.
Momentary vs. Sustained Interruption
The original intent was probably to exclude interruptions restored by automatic operation
![Page 7: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/7.jpg)
7National Grid
Interruption Duration:
“The time period from the initiation of an interruption until service has been restored to the affected customers.”
Step Restoration:
“The process of restoring all interrupted customers in stages over time.”
Duration and Step Restoration
![Page 8: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/8.jpg)
8National Grid
CI = Customers Interrupted
CMI = Customer Minutes Interrupted
CS = Customers Served (IEEE 1366 call this NT)
Fundamental Factors
![Page 9: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/9.jpg)
CAIDI and Her Sisters
![Page 10: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/10.jpg)
10National Grid
SAIFI (System Average Interruption Frequency Index):
How often the average customer experiences an interruption
SAIDI (System Average Interruption Duration Index)
The total number of minutes (or hours) of interruption the average customer experiences
CAIDI (Customer Average Interruption Duration Index)
The average time required to restore service
Be careful with this one. The numbers can be deceiving.
The Big Three- SAIFI, SAIDI, CAIDI
![Page 11: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/11.jpg)
11National Grid
Sustained interruptions only (no momentary)
Usually applied over a specified time period (typically one year)
Usually applied over a specified customer base (typically an entire system, state, town, feeder, etc.)
Averages can be deceiving.
If the average system SAIFI is 0.5. That’s pretty good.
But if 90% of customers had no interruptions and 10% had 5, is that good?
Comments on the Big Three
![Page 12: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/12.jpg)
The Building Blocks-Calculating CI and CMI
![Page 13: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/13.jpg)
13National Grid
CI and CMI provide the basis for calculating the indices
Typical Distribution Feeder- Calculate CI and CMI
![Page 14: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/14.jpg)
14National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
Total Customers Served= 1525
Customers Served by Branch
![Page 15: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/15.jpg)
15National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
X
Fault Occurs
Simple Fault
![Page 16: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/16.jpg)
16National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
X
Open
Fault Occurs
Fuse Opens
10 Customers out for 90 minutes
CI = 10
CMI = (10) * (90) = 900 CMI
Simple Fault
![Page 17: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/17.jpg)
17National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
Fault Occurs
Recloser Operation
![Page 18: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/18.jpg)
18National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
Open2 reclose operations
Fault Occurs
Station recloser trips and recloses twice at 10 sec. intervals
Recloser locks out (stays open)
2 hours to restore (120 minutes)
Recloser Operation
![Page 19: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/19.jpg)
19National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
Open2 reclose operations
CI = 1525
Momentary interruptions do not count
Duration = 120 minutes
CMI = (1525) * (120) = 180,000 CMI
Recloser Operation
![Page 20: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/20.jpg)
20National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
1. Fault occurs on fused branch
Recloser With Fuse Save
![Page 21: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/21.jpg)
21National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
Trips
1. Fault occurs on fused branch
2. Line recloser trips
Recloser With Fuse Save
![Page 22: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/22.jpg)
22National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
10 sec reclose
1. Fault occurs on fused branch
2. Line recloser trips
3. Line recloser closes in 10 seconds
Recloser With Fuse Save
![Page 23: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/23.jpg)
23National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
Successful reclose
Opens
1. Fault occurs on fused branch
2. Line recloser trips
3. Line recloser closes in 10 seconds
4. Fuse opens
Recloser With Fuse Save
![Page 24: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/24.jpg)
24National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
Successful reclose
Opens
1. Fault occurs on fused branch
2. Line recloser trips
3. Line recloser closes in 10 seconds
4. Fuse opens
5. 45 minutes to restore
Recloser With Fuse Save
![Page 25: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/25.jpg)
25National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
Successful reclose
Opens
CI = 15
Momentary interruptions do not count
Duration = 45 minutes
CMI = (15) * (45) = 675 minutes
Recloser With Fuse Save
![Page 26: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/26.jpg)
26National Grid
![Page 27: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/27.jpg)
27National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
Step Restoration
![Page 28: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/28.jpg)
28National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
1. Fault occurs
Step Restoration
![Page 29: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/29.jpg)
29National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
Open
1. Fault occurs
2. Station recloser/breaker opens and locks out
Step Restoration
![Page 30: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/30.jpg)
30National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
CloseOpen
1. Fault occurs
2. Station recloser/breaker opens and locks out
3. 20 Minutes later:
Open Switch
Close breaker
Step Restoration
![Page 31: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/31.jpg)
31National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
Closed
1. Fault occurs
2. Station recloser/breaker opens and locks out
3. 20 Minutes later:
Open Switch
Close breaker
4. 60 minutes later
Close switch
All customers restored
Step Restoration
![Page 32: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/32.jpg)
32National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
Step Restoration
![Page 33: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/33.jpg)
33National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
Open
CI = 1525 (the entire circuit)
Duration = 20 minutes
CMI = (1525) * (20) = 30,500 minutes
Step 1
![Page 34: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/34.jpg)
34National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
CloseOpen
CI = 515
Duration = 60 minutes
CMI = (515) * (60) = 30,900 minutes
Step 2
![Page 35: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/35.jpg)
35National Grid
CI = 1525
Event Total
CS = 10
CS = 500
CS = 15
CS = 1000
![Page 36: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/36.jpg)
36National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
CI = 1525 (each customer experienced only 1 interruption)
CMI = (step 1) + (step 2)
Event Total
![Page 37: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/37.jpg)
37National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
CI = 1525 (each customer experienced only 1 interruption)
CMI = (30,500) + (30,900)
Event Total
![Page 38: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/38.jpg)
38National Grid
CS = 10
CS = 500
CS = 15
CS = 1000
CI = 1525 (each customer experienced only 1 interruption)
CMI = (30,500) + (30,900) = 61,400 minutes
Event Total
![Page 39: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/39.jpg)
Calculating SAIFI, SAIDI and CAIDI
![Page 40: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/40.jpg)
40National Grid
4 events in our universe:
Assume that this is the only feeder in our system
Calculate SAIFI, SAIDI, and CAIDI
Total of All Events
Event Type CI CMI
1 Fuse Branch 10 900
2 Feeder Outage 1,525 180,000
3 Fuse Save 15 675
4 Step Restoration 1,525 61,400
Total 3,075 242,975
![Page 41: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/41.jpg)
41National Grid
CS = 1,525
CI = 3,075
CMI = 242,975
Calculate: SAIFI, SAIDI, CAIDI
= CICS = 30751525 = 2.02= CMI = 2429751525 = 159
= SAIDISAIFI = 1592.02 = 79= = 2429753075 = 79
![Page 42: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/42.jpg)
42National Grid
Four Feeders
Let’s Expand Our Universe
Feeder CS CI CMI1 1,525 3,075 242,975 2 2,200 3,000 120,000 3 800 875 50,000 4 2,000 200 15,000
![Page 43: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/43.jpg)
43National Grid
Four Feeders
Maybe this is an entire utility, maybe it’s a town or district
Let’s Expand Our Universe
Feeder CS CI CMI1 1,525 3,075 242,975 2 2,200 3,000 120,000 3 800 875 50,000 4 2,000 200 15,000
Total 6,525 7,150 427,975
![Page 44: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/44.jpg)
44National Grid
CS = 6,525
CI = 7,150
CMI = 427,975
Calculate: SAIFI, SAIDI, CAIDI
= CMI = 4279756525 = 66= CICS = 71506525 = 1.10
= = 4279757150 = 60 = SAIDISAIFI = 661.10 = 60
![Page 45: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/45.jpg)
Some Lesser Known Cousins
![Page 46: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/46.jpg)
46National Grid
CAIFI: Customer Average Interruption Frequency Index
CTAIDI: Customer Total Average Interruption Duration Index
Similar to SAIFI and SAIDI EXCEPT Only includes customers that actually experienced an interruption
CAIFI and CTAIDI
CAIFI = CITotalnumberofdistinctcustomersinterruptedCTAIDI = CMITotalnumberofdistinctcustomersinterrupted
![Page 47: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/47.jpg)
47National Grid
Why?
Let’s say that a company’s overall reliability is:
SAIDI = 90 minutes
SAIFI = 1.5
But half the company is served by a secondary network that hasn’t and an interruption in the past ten years.
Is that important?
Averages can deceive
CAIFI and CTAIDI
![Page 48: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/48.jpg)
48National Grid
CEMIn: Customers Experiencing Multiple Interruptions
CELID: Customers Experiencing Long Interruption Durations
Intended to give a view of the relative number of customers with reliability below some threshold
These are both measured in PERCENT
CEMIn and CELID
CEMIn = TotnumofcustomersthatexperiencednormoresustainedinterruptionsCSCELID = TotnumcustomersthatexperiencedSormorehoursdurationCS
![Page 49: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/49.jpg)
49National Grid
MAIFI: Momentary Average Interruption Frequency Index
MAIFIE: Momentary Average Interruption Event Frequency Index
CEMSMIn: Customers Experiencing Multiple Sustained Interruption and Momentary
Interruption Events
Momentary: MAIFI, MAIFIE, CEMSMIn
![Page 50: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/50.jpg)
50National Grid
MAIFI: Momentary Average Interruption Frequency Index- Similar to SAIFI
MAIFIE: Momentary Average Interruption Event Frequency Index- Excludes momentaries associated with a sustained interruption (counts events)
CEMSMIn: Customers Experiencing Multiple Sustained Interruption and Momentary
Interruption Events- Similar to CEMIn
Momentary: MAIFI, MAIFIE, CEMSMIn
![Page 51: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/51.jpg)
51National Grid
ASIFI: Average System Interruption Frequency Index
ASIDI: Average System Interruption Duration Index
Similar to SAIFI and SAIDI but based on kVA rather than customers
Load Based: ASIFI, ASIDI
ASIDI = ConnectedkVAdurationofloadinterruptedTotalconnectedkVAserved = kVA)(MinuteskVAASIFI = TotalconnectedkVAofloadinterruptedTotalconnectedkVAserved = kVAkVA
![Page 52: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/52.jpg)
Lies, Damn Lies, and Statistics
![Page 53: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/53.jpg)
53National Grid
Ckt. A
Ckt. B
#2#1 #3
#5 #6
#4
#7
CS=100
CS=100 CS=100
CS=100CS=100
CS=100
Norm. Open
Simple two feeder system
CS = 600
Seven switches
Effect of Distribution Automation
![Page 54: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/54.jpg)
54National Grid
Assume:
No automation
Manual switching time: 20 minutes
Repair time: 60 minutes
Ckt. A
Ckt. B
#2#1 #3
#5 #6
#4
#7
CS=100
CS=100 CS=100
CS=100CS=100
CS=100
Norm. Open
![Page 55: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/55.jpg)
55National Grid
Ckt. A
Ckt. B
#2#1 #3
#5 #6
#4
#7
CS=100
CS=100 CS=100
CS=100CS=100
CS=100
Norm. Open
Time Action Cust out
0:00Fault
200#2 open auto
![Page 56: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/56.jpg)
56National Grid
Ckt. A
Ckt. B
#2#1 #3
#5 #6
#4
#7
CS=100
CS=100 CS=100
CS=100CS=100
CS=100
Close
Time Action Cust out
0:00Fault
200#2 open auto
0:20#3 open manually
100#4 close manually
![Page 57: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/57.jpg)
57National Grid
Ckt. A
Ckt. B
#2#1 #3
#5 #6
#4
#7
CS=100
CS=100 CS=100
CS=100CS=100
CS=100
Open
Time Action Cust out
0:00Fault
200#2 open auto
0:20#3 open manually
100#4 close manually
1:20
#3 close manually
0#2 close manually#4 open manually
![Page 58: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/58.jpg)
58National Grid
![Page 59: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/59.jpg)
59National Grid
Assume:
Distribution Automation
Repair time: 60 minutes
Ckt. A
Ckt. B
#2#1 #3
#5 #6
#4
#7
CS=100
CS=100 CS=100
CS=100CS=100
CS=100
Norm. Open
![Page 60: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/60.jpg)
60National Grid
Ckt. A
Ckt. B
#2#1 #3
#5 #6
#4
#7
CS=100
CS=100 CS=100
CS=100CS=100
CS=100
Close
Time Cust out
0:00
Fault
100#2 opens auto#3 opens auto#4 closes auto
![Page 61: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/61.jpg)
61National Grid
Time Cust out
0:00
Fault
100#2 opens auto#3 opens auto#4 closes auto
1:00 #2 close manually 0#4 open manually
Ckt. A
Ckt. B
#2#1 #3
#5 #6
#4
#7
CS=100
CS=100 CS=100
CS=100CS=100
CS=100
Open
![Page 62: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/62.jpg)
62National Grid
Without Automation
2 Steps
CS = 600
With Automation
1 Step
CS = 600
Compare CAIDI (How quickly the utility restores power)
StepDuration
(Min) CI CMI
1 20 200 4,000
2 60 100 6,000
Total 80 10,000
StepDuration
(Min) CI CMI
1 60 100 6,000
Total 60 6,000
CAIDI = CMICI = 10000200 = 50 CAIDI = CMICI = 6000100 = 60
![Page 63: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/63.jpg)
63National Grid
Without Automation
2 Steps
CS = 600
With Automation
1 Step
CS = 600
Compare CAIDI (How quickly the utility restores power)
StepDuration
(Min) CI CMI
1 20 200 4,000
2 60 100 6,000
Total 80 10,000
StepDuration
(Min) CI CMI
1 60 100 6,000
Total 60 6,000
CAIDI = CMICI = 10000200 = 50 CAIDI = CMICI = 6000100 = 60SAIFI = CICS = 200600 = 0.67SAIDI = CMICS = 10000600 = 17
SAIFI = CICS = 100600 = 0.17SAIDI = CMICS = 6000600 = 10
![Page 64: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/64.jpg)
64National Grid
ASAI: Average Service Availability Index
Usually expressed as a decimal or a percent
Availability: ASAI
ASAI = CustomerHoursServiceAvailableCustomerHoursServiceDemand
![Page 65: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/65.jpg)
65National Grid
What’s a good available number?
How many think:
0.99?
0.999?
0.9999?
ASAI
![Page 66: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/66.jpg)
66National Grid
What’s a good available number?
How many think:
0.99? – Two 9’s
0.999? – Three 9’s
0.9999? – Four 9’s
ASAI
![Page 67: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/67.jpg)
67National Grid
ASAI
ASAIAnnual Hours
Hours Available
SAIDI Hours
SAIDI Minutes
0.99 8,760 8,672 87.6 5,256
![Page 68: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/68.jpg)
68National Grid
ASAI
ASAIAnnual Hours
Hours Available
SAIDI Hours
SAIDI Minutes
0.99 8,760 8,672 87.6 5,256
0.999 8,760 8,751 8.8 526
![Page 69: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/69.jpg)
69National Grid
You better have something better than “three 9’s”
ASAI
ASAIAnnual Hours
Hours Available
SAIDI Hours
SAIDI Minutes
0.99 8,760 8,672 87.6 5,256
0.999 8,760 8,751 8.8 526
0.9999 8,760 8,759 0.9 53
![Page 70: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/70.jpg)
Some days are diamond,Some days are stone
![Page 71: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/71.jpg)
71National Grid
Usually reliability is reported two ways:
• Including ALL events
• Excluding MAJOR events
Why?
What level of service is reasonable and economical?
Storms/Major Events
![Page 72: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/72.jpg)
72National Grid
Definitions vary by utility, regulator, and/or others
Some typical definitions:
• Named Storms
• Declaration of Emergency
• Worst x% of Days
• Specifically exclusion by regulators
• “Not our fault”
IEEE-1366:
2.5 β Method
What’s a major event?
![Page 73: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/73.jpg)
73National Grid
0
200
400
600
800
1000
1200
1400
Freq
uenc
y
Bin
SAIDI by day
Frequency
Background
Eight years of data from one utility
Vast majority of days are at one end
But there are outliers
![Page 74: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/74.jpg)
74National Grid
Background
Ln (SAIDI) is a reasonable bell curve (“log-normal distribution”)
0100200300400500600700800900
1000
Freq
uenc
y
Bin
Natural Log (SAIDI) by day
Frequency
![Page 75: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/75.jpg)
75National Grid
For complete discussion see IEEE-1366
• The method relies on calculating SAIDI/day
• It determines a threshold (SIADI/day) above which a day is classified as a MAJOR EVENT DAY (MED)
• That Threshold is defined as:
2.5 β Method
= .
![Page 76: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/76.jpg)
76National Grid
Don’t be Intimidated!
.
![Page 77: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/77.jpg)
77National Grid
Don’t be Intimidated!
.
![Page 78: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/78.jpg)
78National Grid
Don’t be Intimidated!
.
![Page 79: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/79.jpg)
79National Grid
Don’t be Intimidated!
.
![Page 80: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/80.jpg)
80National Grid
Basically, two and a half standard deviations on an average!
Don’t be Intimidated!
.
![Page 81: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/81.jpg)
81National Grid
Step 1: Don’t Panic!
Step 2:
In a table:
Collect daily SAIDI for five years
Days with no interruptions will be excluded
Calculate Ln(SAIDI) for each day
Find α
Find β
Calculate TMED
Calculating TMED
= .
![Page 82: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/82.jpg)
82National Grid
α is the average of Ln(SAIDI)
β is the standard deviation of Ln(SAIDI)
It’s easier than it sounds
Calculating α and β
![Page 83: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/83.jpg)
83National Grid
Typically use 5 years worth of data
Calculate CMI and SAIDI for each day
Develop the Spreadsheet Date SAIDI/day (min) ln(SAIDI/day)
Dec 1, 1993 26.974 3.295
Dec 2, 1993 0.956 -0.046
Dec 3, 1993 0.131 -2.033
Dec 4, 1993 1.292 0.256
Dec 5, 1993 4.25 1.447
Dec 6, 1993 0.119 -2.127
Dec 7, 1993 0.13 -2.042
Dec 8, 1993 12.883 2.556
Dec 9, 1993 0.226 -1.487
Dec 10, 1993 13.864 2.629
Dec 11, 1993 0.015 -4.232
Dec 12, 1993 1.788 0.581
Dec 13, 1993 0.41 -0.891
Dec 14, 1993 0.007 -4.967
Dec 15, 1993 1.124 0.117
Dec 16, 1993 1.951 0.668
Dec 17, 1993 0.329 -1.112
Dec 19, 1993 0.281 -1.268
Dec 20, 1993 1.81 0.593
Dec 21, 1993 0.25 -1.388
Dec 22, 1993 0.021 -3.876
Dec 23, 1993 1.233 0.209
Dec 24, 1993 0.996 -0.004
Dec 25, 1993 0.162 -1.818
Dec 26, 1993 0.288 -1.244
Dec 27, 1993 0.535 -0.626
Dec 28, 1993 0.291 -1.234
Dec 29, 1993 0.6 -0.511
Dec 30, 1993 1.75 0.56
Dec 31, 1993 3.622 1.287
Date SAIDI/day (min) ln(SAIDI/day)
![Page 84: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/84.jpg)
84National Grid
Typically use 5 years worth of data
Calculate CMI and SAIDI for each day
Develop the SpreadsheetDate SAIDI/day (min) ln(SAIDI/day)
Dec 1, 1993 26.974 3.295Dec 2, 1993 0.956 -0.046Dec 3, 1993 0.131 -2.033Dec 4, 1993 1.292 0.256Dec 5, 1993 4.25 1.447Dec 6, 1993 0.119 -2.127
. . .
. . .
. . .Dec 30, 1993 1.75 0.56Dec 31, 1993 3.622 1.287
![Page 85: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/85.jpg)
85National Grid
Typically use 5 years worth of data
Calculate CMI and SAIDI for each day
Calculate α and β
Develop the SpreadsheetDate SAIDI/day (min) ln(SAIDI/day)
Dec 1, 1993 26.974 3.295Dec 2, 1993 0.956 -0.046Dec 3, 1993 0.131 -2.033Dec 4, 1993 1.292 0.256Dec 5, 1993 4.25 1.447Dec 6, 1993 0.119 -2.127
. . .
. . .
. . .Dec 30, 1993 1.75 0.56Dec 31, 1993 3.622 1.287
Average= -0.557Standard Dev= 1.91
![Page 86: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/86.jpg)
86National Grid
α = -0.557
β = 1.91
TMED = 66.7 Minutes
This TMED is used to evaluate the next year
For 2019, Calculate TMED using 2014 – 2018 data
Calculate TMED
= .
![Page 87: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/87.jpg)
87National Grid
TMED is 66.7
Any day where SAIDI >66.7 is a Major Event Day
Apply TMEDDate SAIDI/Day
Jan 1, 1994 0.24Jan 2, 1994 0.014Jan 3, 1994 0.075Jan 4, 1994 2.649Jan 5, 1994 0.666Jan 6, 1994 0.189Jan 7, 1994 0.009Jan 8, 1994 1.117Jan 9, 1994 0.111
Jan 10, 1994 8.683Jan 11, 1994 0.277Jan 12, 1994 0.057Jan 13, 1994 0.974Jan 14, 1994 0.15Jan 15, 1994 0.633Jan 16, 1994 0.434Jan 17 1994 5.7Jan 18, 1994 0.109Jan 19, 1994 0.259Jan 20, 1994 1.142Jan 21, 1994 0.262Jan 22, 1994 0.044Jan 23, 1994 0.243Jan 24, 1994 5.932Jan 25, 1994 2.698Jan 26, 1994 5.894Jan 27, 1994 0.408Jan 28, 1994 237.493Jan 29, 1994 2.73Jan 30, 1994 8.11Jan 31, 1994 0.046
![Page 88: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/88.jpg)
88National Grid
TMED is 66.7
Any day where SAIDI >66.7 is a Major Event Day
Jan. 28 is a Major Event Day
Apply TMEDDate SAIDI/Day
Jan 1, 1994 0.24Jan 2, 1994 0.014Jan 3, 1994 0.075Jan 4, 1994 2.649Jan 5, 1994 0.666Jan 6, 1994 0.189Jan 7, 1994 0.009Jan 8, 1994 1.117Jan 9, 1994 0.111
Jan 10, 1994 8.683Jan 11, 1994 0.277Jan 12, 1994 0.057Jan 13, 1994 0.974Jan 14, 1994 0.15Jan 15, 1994 0.633Jan 16, 1994 0.434Jan 17 1994 5.7Jan 18, 1994 0.109Jan 19, 1994 0.259Jan 20, 1994 1.142Jan 21, 1994 0.262Jan 22, 1994 0.044Jan 23, 1994 0.243Jan 24, 1994 5.932Jan 25, 1994 2.698Jan 26, 1994 5.894Jan 27, 1994 0.408
Jan 28, 1994 237.493Jan 29, 1994 2.73Jan 30, 1994 8.11Jan 31, 1994 0.046
Date SAIDI/Day Jan 28, 1994 237.493
![Page 89: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/89.jpg)
89National Grid
An Actual Dataset
Day Events CI CMI CS SAIDI Natural Log SAIDI1/12/2011 2 362 20198 12496 1.6164 0.48022/25/2011 1 1 86 12517 0.0069 -4.98053/1/2011 1 7 469 12512 0.0375 -3.2838
3/22/2011 1 2 127 12512 0.0102 -4.59034/13/2011 1 9 630 12516 0.0503 -2.98905/2/2011 1 6 80 12532 0.0064 -5.05405/4/2011 1 6 1542 12532 0.1230 -2.09525/6/2011 2 214 10908 12532 0.8704 -0.1388
5/11/2011 1 23 5428 12532 0.4331 -0.83675/12/2011 1 4 608 12532 0.0485 -3.02595/19/2011 1 616 30619 12532 2.4433 0.89335/21/2011 1 35 6440 12532 0.5139 -0.66585/24/2011 1 174 15611 12532 1.2457 0.21975/27/2011 1 3 234 12532 0.0187 -3.98076/4/2011 1 20 4000 12565 0.3183 -1.14466/6/2011 1 1564 79764 12565 6.3481 1.84826/9/2011 2 4 421 12565 0.0335 -3.3960
6/22/2011 1 15 5115 12565 0.4071 -0.8987
![Page 90: IEEE 1366- Reliability Indicessite.ieee.org/.../IEEE-1366-Reliability-Indices-2-2019.pdfreclose Opens 1. Fault occurs on fused branch 2. Line recloser trips 3. Line recloser closes](https://reader034.fdocuments.us/reader034/viewer/2022043007/5f93fcbdbbb0cb28e0515733/html5/thumbnails/90.jpg)
90National Grid
Basically, two and a half standard deviations on an average!
Don’t be Intimidated!
.