Versatech Recloser Manual

40
PSP8620311 Rev.C 1 VERSA-TECH ® Single-Phase Recloser for Distribution Systems Installation, Operation and Maintenance Manual IMPORTANT! Keep this manual readily available for future reference. Electric Shock Hazard. All parts of recloser are energized. Contact with in service recloser will cause death or severe injury. Before contacting or servicing the equipment, or working on the electrical system, isolate and ground the recloser from the electrical system. Verify recloser is de-energized by testing with properly rated hot sticks and/or rubber gloves and volt meter. ! DANGER 8100 Churchill Avenue Leeds, Alabama 35094 (205) 699-0840 www.hubbellpowersystems.com For Firmware Revision 3 and Higher NOTE: Hubbell has a policy of continuous product improvement. We reserve the right to change design and specifications without notice. ©Copyright 2011 Hubbell Incorporated

description

Versatech V1 Recloser Manual

Transcript of Versatech Recloser Manual

Page 1: Versatech Recloser Manual

PSP8620311Rev.C

1

VERSA-TECH®

Single-Phase Recloserfor Distribution Systems

Installation, Operation andMaintenance Manual

IMPORTANT!Keep this manual readily

available for future reference.

Electric Shock Hazard. All parts of recloser are energized.

Contact with in service recloser will cause death or severe injury.

Before contacting or servicing the equipment, or working on the electrical system, isolate and ground the recloser from the electrical system. Verify recloser is de-energized by testing with properly rated hot sticks and/or rubber gloves and volt meter.

! DANGER

8100 Churchill AvenueLeeds, Alabama 35094(205) 699-0840www.hubbellpowersystems.com

For Firmware Revision 3 and Higher

NOTE: Hubbell has a policy of continuous product improvement. We reserve the right to change design and specifications without notice. ©Copyright 2011 Hubbell Incorporated

Page 2: Versatech Recloser Manual

PSP8620311Rev. C

2

Warnings

IMPORTANTThese installation, operation and maintenance instructions do not claim to cover all details or variations in equipment. Nor do they provide for all possible conditions encountered while installing, operating or maintain-ing this equipment. If further information is desired or needed to address any particular installation, operation or maintenance problem not covered in this document, contact your authorized factory representative.

The information in this document does not relieve the user from exercising good judgment in selecting equip-ment for suitability of application. Nor does it relieve the user from using sound practices in installation, opera-tion and maintenance of the equipment purchased.

Note: Because Hubbell has a policy of continuous product improvement, we reserve the right to change de-sign and specifications without notice. Should a conflict arise between the general information in this docu-ment and the contents of drawings or supplementary material, or both, the latter shall take precedence.

QUALIFIED PERSONFor the purpose of this manual, a qualified person is:

(a) familiar with the installation, construction or operation of the subject equipment and the hazards involved with its installation, operation and maintenance.

(b) trained to de-energize, clear, ground, and tag circuits and equipment in accordance with established safety practices.

(c) trained in the proper care and use of protective equipment such as rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc., in accordance with established utility safety practices.

(d) trained to render first aid.

Electrical equipment contains hazardous voltages. Con-tact with these hazards will cause death, severe personal injury or damage equipment.

Only qualified personnel shall install, operate and maintain this equipment. Always properly ground equipment and lock out electric power (de-en-ergize) before maintenance. Using non-specified/unauthorized parts or components to repair equipment, or tampering with safety devices/systems will result in dangerous conditions which can cause death, severe personal injury or damage to equipment. Take note of and follow all safety instructions contained in this installation, operation and maintenance manual.

SUMMARYThe information in this document does not claim to cover all details or variations in equipment, nor to provide for every possible contingency encountered with installation, operation, or maintenance. Should further infor-mation be needed or problems arise that are not covered sufficiently, contact your factory representative.

The contents of this document are not part of, nor do they modify, any prior or existing agreement, commit-ment or relationship. Hubbell Power Systems, Inc. terms and conditions of sale constitute the entire obliga-tion of Hubbell Power Systems, Inc. The warranty in the terms and conditions of sale is the sole warranty of Hubbell Power Systems, Inc. Any statements in this document do not create new warranties or modify any existing warranty.

! DANGER

Page 3: Versatech Recloser Manual

PSP8620311Rev.C

3

7 — Testing

Minimum Trip Value

Sequence Coordination

Operations to Lockout

Manual Closing Delay Time

Time-Current Curve Selection

Time-Current Curve Modifiers

Minimum Response Time

Reclose Time

Reset Time

Cold Load Time

Record Manual Close

Time Stamp

Operations Counter

Fault History

Fault Energy Accumulator

Scratchpad Memory

8 — Maintenance

Overview

Connecting Local Radio

Installing Remote Radio

Remote Radio Power

Radio Operation

9 — Trouble Shooting

High-Potential Withstand Test

Minimum-Trip Current Test

Sequence of Operation Test

Section Subject Page Number

1 — Overview

Safety Information

Ratings and Specifications

Installation Alternatives

Catalog Number Matrix

Dimensions - Pole/Structure Mount

Dimensions - Crossarm Mount

2 — Installation Requirements

User Supplied Requirements

Hardware Torque Specifications

3 — Receiving and Handling

Inspection

Unpacking

Components

Storage

4 — Installation

Installation Options

Installation Preparation

Pole/Structure Surface Mounting

Crossarm Mounting

Connections

Place Recloser in Service

5 — Recloser Operation

Overview

Automatic

Manual

Non-Reclosing

Operations Counter

Lockout Beacon

6 — Control Programming

Overview

Customer Supplied Requirements

Software Installation

Connecting Recloser to PC

Programming Settings

Viewing Diagnostics

Viewing Scratchpad

Radio Setup

Security

Storing Information

5

9

10

11

16

17

Contents

Section Subject Page Number

32

34

36

Page 4: Versatech Recloser Manual

PSP8620311Rev. C

4

Contents

Tables & Figures....................................................Page Number

Table 1-1 Recloser Catalog Number Matrix........................................6Table 2-1 Hardware Torque Specifications .........................................9Table 9-1 Trouble Shooting Guide ....................................................33

Figure 1-1 Pole/Structure Face Mounting ............................................6Figure 1-2 Crossarm Mounting ...........................................................6Figure 3-1 Components .....................................................................10Figure 4-1 Pole/Structure Face Mounting ..........................................11Figure 4-2 Crossarm Mounting .........................................................11Figure 4-3 Bypass Arrangement ........................................................11Figure 4-4 Program/Installation Tag .................................................12Figure 4-5 Pole/Structure Mount Assembly Detail .............................13Figure 4-6 Pole/Structure Mount Installation ....................................13Figure 4-7 Recloser in Sling .............................................................13Figure 4-8 Crossarm Assembly Detail ...............................................14Figure 4-9 Crossarm Mount Installation ............................................14Figure 5-1 Feature Position ..............................................................16Figure 6-1 Connecting Local Radio ...................................................17Figure 6-2 Settings Tab of Programmer Software .............................20Figure 6-3 Real Time Monitoring Tab of Programmer Software ........24Figure 6-4 Events and Data Log Tab of Programmer Software ..........25Figure 6-5 Radio Setup Tab of Programmer Software .......................26Figure 6-5 Scratchpad Tab of Programmer Software ........................27Figure 7-1 Recloser attached to high potential test set ......................29Figure 7-2 Recloser attached to high current test set ........................30Figure 8-1 Battery bayonet in the recloser .........................................31Figure 8-2 Battery bayonet partially removed from recloser ..............31

Page 5: Versatech Recloser Manual

PSP8620311Rev.C

5

! WARNING

Signal WordsThe signal words “DANGER,” “WARNING” and “CAUTION” (along with their assigned symbol) throughout this manual indicate the degree of hazard the user may encounter. These symbols and words are defined as:

DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.

WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.

! WARNING

! CAUTION

CAUTION

1 — Overview

IntroductionThis manual is to guide you through the programming, installation, opera-tion and maintenance of the VERSA-TECH® single-phase recloser. This manual does not claim to cover all situations that may arise during installation. If additional informa-tion is needed, contact your factory representative. Nor does this manual supersede your company’s estab-lished guidelines and practices for similar equipment. Take note of and heed all danger, warning and cautions contained in this document.

▲ ProductThe products covered by this manual are the VERSA-TECH® single-phase reclosers for medium voltage electri-cal distribution circuits.

These products are designed for distribution circuits only at their rated capacities. They cannot be field mod-ified for capacities other than what was shipped with the units.

FunctionThis product is a single-phase re-closer designed to provide a means for interrupting, sectionalizing and isolating faults on electrical distribu-tion systems.

CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.

Qualified PersonOnly qualified trained and competent personnel that understand proper safety procedures must select, install and service this equipment.

Read and understand these instruc-tions before installing, operating or maintaining this equipment.

This guide is not a substitute for adequate training and experience in safety procedures for this type of equipment.

All parts of recloser are energized.

Contact with components will cause severe personal injury, death, or property damage.

Only qualified personnel should work on or around this equipment after becoming thor-oughly familiar with this document and other publications regarding this equipment.

This equipment is not intended to protect hu-man life.

Can cause death, severe personal injury, and/or equipment damage

Follow all locally approved procedures and safety practices when installing or operating this equipment.

Do not place the recloser in service until all settings have been programmed and verified.Failure to comply can result in recloser misoperation, equipment damage, and personal injury.

Refer to sections 6 and 7 of this manual for control programming and operation.

Handle position does not indicate de-energized recloser enclosure controls or circuit.

Contact with these components will cause severe personal injury, death, or property damage.Before contacting or servicing the equipment, or working on the electrical system, isolate and ground the recloser from the electrical system. Verify recloser is de-energized by testing with properly rated hot sticks and/or rubber gloves and volt meter.

Safety Information! DANGER

! DANGER

! DANGER

! CAUTION

Page 6: Versatech Recloser Manual

PSP8620311Rev. C

6

1 — Overview

Ratings and Specifications

Rated Maximum Voltage ................................................................................................27kVRated Continuous Current .............................................................................................400AFault Make Capacity ........................................................................................................8kAFault Make Capacity Peak ..........................................................................................20.7kAFault Break Capacity ........................................................................................................8kAMechanical Operations ................................................................................................30,0003 Second Withstand Current ............................................................................................8kATransformer Magnetizing Current ....................................................................................14ACable Charging Current ...................................................................................................25ALine Charging Current .......................................................................................................5ALightning Impulse Withstand ........................................................................................125kV60Hz, 1-Minute Withstand Voltage .................................................................................60kVMaximum Terminal Pad Load kg (pounds)................................................................. 14 (30)Operating Temperature .......................................................................................-40C to 60CWeight kg (pounds) .....................................................................................................25 (55)

Figure 1-1 Pole/Structure Face Mounting Figure 1-2 Crossarm Mounting

Installation Alternatives

Table 1-1 Recloser Catalog Number Matrix

Catalog Numbering System PostionTo build your Versa-Tech® Recloser, add features from

the matrix to this base number:

1 2 3 4 5 6 Catalog No. PSC 8 6 2 1 1 X X X Voltage Rating 27kV 2 Maximum Interrupt 8kA 1 Minimum Fault Trip 30A 1 Pole/Structure Mount 1 Crossarm Mount 2 No Connectors 1 PG (Parallel Groove) Clamps (2) 2 Captive Hardware 3 No Remote Radio 1 Standard Performance Remote Digi Radio 2 High Performance SiFlex Remote Radio 3

Page 7: Versatech Recloser Manual

PSP8620311Rev.C

7

VACUUM INTERRUPTER

2-HOLE NEMAPAD (STANDARD)TYPICAL

2-HOLE NEMAPAD (STANDARD)TYPICAL

NON-RECLOSELEVER

OPERATING LEVER

LOCKOUT INDICATORBEACON AND COUNTER

MOUNTING HOLES FOR5/8" (15mm) BOLTS11" (27.9cm) CENTERTO CENTER NOMINAL.

17.1 12.4

2.0

11.0

4.2

29.5

RS-232 PROGRAMMING PORT

LEAKAGE DISTANCE - 39.4"LOCKOUT INDICATOR BEACONAND COUNTER

OPERATING LEVER

BATTERY PACK(HOT STICK REPLACEABLE)

15.8

8.7

22.0

15.0

Dimensions - Pole/Structure mounting

1 — Overview

Side View

Front View

Back View

Page 8: Versatech Recloser Manual

PSP8620311Rev. C

8

ADJUSTABLE3" - 9-1/2"

ADJUSTABLE5-1/8" - 10-1/4"TYPICAL

OPERATING LEVER

LOCKOUT INDICATOR BEACONAND COUNTER

2-HOLE NEMAPAD (STANDARD)TYPICAL

VACUUM INTERRUPTER

LEAKAGE DISTANCE - 39.4"

LOCKOUT INDICATOR BEACONAND COUNTERNON-RECLOSE LEVER

28.0

31.1

4.0

10.6

24.9

8.712.7

14.0

Dimensions - Crossarm mounting

1 — Overview

Side ViewFront View

Page 9: Versatech Recloser Manual

PSP8620311Rev.C

9

2 — Installation Requirements

Table 2-1 Hardware Torque Specifications

User Supplied RequirementsThe following is required for installa-tion. Be sure to have these items on hand before beginning installation.

Safety Equipment (PPE)• Hard hat• Steel-toe work boots• Appropriate eye protection per your

company’s policy• Other safety equipment as required by

your company’s policies

Hardware• 5⁄8 inch (16 mm) galvanized thru-bolts

(or equivalent) long enough to pass through the center of the utility pole, plus 3 inches (75 mm)

• Curved galvanized washers for the 5⁄8 inch (16 mm) thru-bolts

• Galvanized nuts for 5⁄8 inch (16 mm) thru-bolts

• Flat galvanized washers for 1⁄2 inch (12 mm) and 5⁄8 inch (16 mm)) lag screws

Electrical• Terminal pad connectors (if not or-

dered with switch)• Connector sealing paste (CHANCE ZLN

or equivalent)• Surge arresters and wire (if needed)

Options• BP3 By-Pass Switch (for appropriate

Cat. No., see Catalog Section 14B)• Jumper Wire, 400 Amp minimum

capacity• M3 Disconnect Switch (for appropriate

Cat. No., see Catalog Section 14B)

Hubbell Power Systems, Inc. Supplied RequirementsAll necessary components and hard-ware specific to the installation of the VERSA-TECH® recloser ordered are included.

Carefully check the components and hardware items against those listed in Section 3.

Contact your factory representative if any parts are missing.

User Supplied Hardware

Item ft-lb N•m Notes

5⁄8 inch (16 mm) thru-bolts N/A N/A Company standards apply

5⁄8 inch (16 mm) lag screws N/A N/A Company standards apply

Terminal connectors N/A N/A Company standards apply

Hubbell Supplied Hardware

Item ft-lb N•m Notes

3/8 inch Crossarm Mount bolts N/A N/A Company standards apply

3/8 inch Insulator Mount bolts 15 20

1/2 inch Terminal bolts 60 81

Hardware Torque Specifica-tionsIt is the installing personnel’s re-sponsibility to be sure all threaded fasteners are installed with the correct torque. All user supplied hardware is to be torqued according to company standards. Recloser and connector hardware torque specifications are listed in Table 2-1.

Page 10: Versatech Recloser Manual

PSP8620311Rev. C

10

3 — Receiving & Handling

Inspection1.Inspect the packaging for obvious

shipping damage.2.Open and thoroughly inspect the product

for hidden damage.3.Note any damage on the “Bill of Lading”

prior to accepting the delivery.4.Check the material nameplate against the

shipping list to ensure the correct material has been received. In case of shortage or incorrect material, immediately notify your factory representative or customer service.

Note: Documentation of visible shipping damage can determine the outcome of any damage claim. Notifying the carrier of concealed damage within 15 days is essential to resolving or minimizing unsettled claims. Immediately file your claim and notify your factory representative.

NOTE:When batteries are removed for more than seven days, the time stamp chip will stop keeping time. If time stamp feature is required, the time stamp can be reset before placing the recloser in service. (See Section 7.)

StorageIf the recloser is not going to be put into service immediately, re-pack all compo-nents in the factory package to minimize storage damage and to ensure good op-erating conditions in the future. Hubbell Power Systems recommends that the recloser be stored indoors or under cover, off the ground, not subject to direct sun, rain or snow.

During storage longer than six months, the battery bayonet must be removed from the recloser. If the storage area temperature exceeds 100°F, remove the batteries and store in a cool, dry area.

Unpacking1. Locate the programming CD that is

enclosed with this manual. Take care to protect the disk from damage. The disk should be in the custody of the personnel who will be responsible for the programming of the recloser.

2. Carefully remove all items from the packaging. Exercise caution and do not drop the unit or strike the skirted end on anything as this may damage the vacuum interrupter or mechanism.

3. Refer to Figure 3-1 to familiarize yourself with all components.

Figure 3-1 Components

Mounting Fasteners

PG Clamps

Battery Bayonet

Insulator

MountingBracket

Radio(optional)

Instructionsand CD

Page 11: Versatech Recloser Manual

PSP8620311Rev.C

11

4 — Installation

Installation OptionsVERSA-TECH® single-phase reclos-ers are designed for outdoor pole or structure mounting and application on overhead electrical distribution systems. The energized recloser is insulated from the pole/structure by a polymer insulator.

The VERSA-TECH® Single Phase Elec-tronic Recloser is available in two basic mounting configurations:1. Pole/Structure mounting (see Fig. 4-1)

2. Crossarm mounting (see Fig. 4-2).

Refer to the catalog number of the unit. The seventh (7th) character position indicates the mounting arrangement, e.g., the "1" in the seventh position of C862111XXX indicates a Pole/Structure mounting. A “2” in this position indicates Crossarm mounting, e.g., C862112XXX.

Figure 4-1 Pole/Structure Mounting

Figure 4-2 Crossarm Mounting

Figure 4-3 Bypass Arrangement

Hubbell Power Systems recommends the use of a by-pass switch in parallel with the recloser. This arrangement allows the unit to be easily taken out of the circuit for service, should the need arise. It also allows all connections to be made without picking up load current with the jumper connections (see Fig. 4-3).

LIGHTNING ARRESTERS NOTE:Hubbell Power Systems recommends placing appropriately rated lightning arresters as close as possible on both the source and load sides of the recloser. (Refer to Ohio Brass catalog.)

Page 12: Versatech Recloser Manual

PSP8620311Rev. C

12

! CAUTION

! WARNING

! CAUTION

! WARNING

Do not place the recloser in service until all set-tings have been programmed and verified.

Failure to comply can result in recloser misoperation, equipment damage, and personal injury.

Refer to sections 6 and 7 of this manual for control programming and operation.

Follow all appropriate OSHA and company work rules in the installation of this equipment. All clearances, cover-up and personal protec-tive equipment must be used. Failure to follow these instructions may result in damage to equipment, personal injury or death.

Figure 4-4 – Program/Installation Tag

Installation Preparation1. Program the unit with the desired

parameters as outlined in Section 6 of this manual. Record the settings on the supplied tag and attach the tag to the operating handle for reference during installation (Fig. 4-4).

2. Prior to installation, verify vacuum interrupter integrity by applying 50/60 Hz 40kV AC across the open contacts for 60 seconds. (See Section 8.)

4 — Installation

The unit must be mounted horizontally as il-lustrated in this manual. Failure to mount in this attitude may result in improper operation of the interrupter.

Do not store or lay the recloser in mud, snow or water.

This could contaminate the insulation over the interrupter leading to electrical flashover at the system voltage.

A clean, dry storage environment is recommended.

Hubbell Versa-Tech® Single Phase RecloserComplete this tag when unit is programmed and tie to the operating handle of the unit.

This unit has been programmed to the following settings by: _______________ Date: _____________ Operations to Lockout: 1 2 3 4Minimum Trip (Amps): ___________ Reset Time (sec): ____________ Min. Response Time (mSec): __________ Cold Load Time: ____________ Sequence Coordination Enabled ❑      Min. Response Enabled for Operation 1 2 3 4

Operation #1: TCC1 TCC2 TCC1 Curve: _____________ Modifier: _____________Operation #2: Reclose Time 1 (sec): ____ Curve: TCC1 TCC2 TCC2 Curve: _____________ Modifier: _____________Operation #3: Reclose Time 2 (sec): ____ Curve: TCC1 TCC2

Operation #4: Reclose Time 3 (sec): ____ Curve: TCC1 TCC2

Location for Installation: _______________________________________________________________

Installed by: ______________________________________________ Date: _____________________

Page 13: Versatech Recloser Manual

PSP8620311Rev.C

13

4 — Installation

Pole/Structure Surface Mounting1. Refer to Figure 4-5 for assembly detail

and Table 2-1 for torque specifications. Assemble the insulator (1) to the

rectangular steel adapter plate (2) using two 3/8" X 1" bolts and split lock washers (3) as shown.

Assemble the mounting bracket (4) to the opposite end of the insulator (1) using two 3/8" X 1" bolts, flat washers and split lock washers (5) as shown.

Attach the insulator/bracket/adapter plate to the four threaded bosses on the flat side of the body of the recloser as shown. Use four ss 3/8" X 1-1/4" bolts, flat washers and split lock washers (6).

Do not attach to the 4 threaded holes on the top of the body. These attachment holes are used only on the crossarm mounting arrangement.

2. Determine the mounting location on the pole. The pole mount uses 2 bolts, 5/8" diameter on 12" centers.

3. Drill the appropriate holes through the pole.

4. Install the bolt in the top hole.

Note: The head of the bolt must be on the side of the pole where the recloser will be mounted. Install the nut and washers on the back side. Leave approximately 2" of bolt exposed under the head for the keyhole slot in the mounting bracket.

5. Using a nylon sling, sling the unit as shown in Figure 4-7. CAUTION: Do not use a metal sling or chain as this may damage the unit.

6. Using suitable means, lift the unit into position.

CAUTION: Do not allow recloser to impact or collide with pole or other objects as it is lifted and installed.

7. Ensure the top bolt engages the small portion of the “keyhole” slot.8. Install the bottom bolt/washers and nut.9. Tighten the hardware per Table 2-1.

Figure 4-6 Pole/Structure Mount Installation

Figure 4-7 Recloser in Sling

Figure 4-5 Pole/Structure Mount Assembly Detail

1

2

6

4

5

3

Page 14: Versatech Recloser Manual

PSP8620311Rev. C

14

4 — Installation

Crossarm MountingThis configuration is intended for application to a double crossarm structure.

This is the preferred arrangement if three units are to be mounted.

1. Remove the four 3/8" X 5/8" bolts from top mounting flange (8) and use to fill the four holes on the cover (9).

2. Refer to Figure 4-8 for assembly detail and Table 2-1 for torque specifications.

Orient the insulator (1) so the skirts will shed water towards the rectangular steel adapter plate (2) and assemble using two 3/8" X 1" bolts and split lock washers (3) as shown.

Assemble the mounting bracket (4) to the opposite end of the insulator (1) using two 3/8" X 1" bolts, split lock washers and flat washers (5) as shown.

Attach the insulator/bracket/adapter plate to the four threaded bosses on the top of the body of the recloser as shown. Use four ss 3/8" X 1-1/4" bolts, flat washers and lock washers (6).

3.Using a nylon sling, sling the unit as shown in Figure 4-7.

CAUTION: Do not use a metal sling or chain as this may damage the unit.

4.Using suitable means, lift the unit into position.

5. Install the back plate (7), and four 3/8" X 7-1/2" carriage bolts/lock washers/ and square nuts. Adjust the bolt spacing as necessary to fit the crossarm arrangement.

6.Tighten the hardware per Table 2-1.

Figure 4-8 Crossarm Assembly Detail

Figure 4-9 Crossarm Mount Installation

1

2

6

3

4

5

7

8

9

Page 15: Versatech Recloser Manual

PSP8620311Rev.C

15

! WARNING

! WARNING

! WARNING

Connections1.Wire brush the jumper conductors and

terminal pads.2.Apply contact aid, such as CHANCE ZLN

to the contact surfaces. Install the recloser end of the jumpers. Tighten the terminal bolts per Table 2-1. if used.

3.Make sure the recloser handle is in the open position and the contacts are open.

4.Connect the jumpers to the power source. Tighten the terminal bolts per Table 2-1.

CAUTION: Avoid applying side loads to vacuum interrupter end of recloser when making connections to terminal pads.

Place recloser into service

1.Using appropriately rated hot stick, pull the red non-reclosing lever to the down position.

2.Using appropriately rated hot stick, install the battery pack by inserting; align the pins in the slots, push and turn clockwise to lock in place.

3.Ensure all connections are tight and properly connected.

4.Using an appropriately rated hot stick, close the unit by pushing the yellow lever to the extreme up position and release. You should hear the unit close.

5.Using an appropriately rated hot stick, open the by-pass switch.

6.Push the red non-reclosing lever to the up position. The unit is now in normal operating mode.

Open the recloser before making final connections.

Failure to comply can result in an electrical arc which can cause death, personal injury or equipment damage.

Before making any connections to the power line, pull the red non-re-closing lever down and open the recloser by pulling the yellow handle to the down position.

Do not open the by-pass switch while the recloser is open.

Failure to comply can result in an electrical arc which can cause death, personal injury or equipment damage.

Do not ground the recloser.

Grounding the recloser can result in recloser misoperation, equipment damage and personal injury.

4 — Installation

Electric Shock Hazard. All parts of recloser are energized.

Contact with in service recloser will cause death or se-vere injury.

Before contacting or servicing the equipment, or working on the electrical system, isolate and ground the recloser from the electri-cal system. Verify recloser is de-energized by testing with properly rated hot sticks and/or rubber gloves and volt meter.

! DANGER

Page 16: Versatech Recloser Manual

PSP8620311Rev. C

16

Overview

The VERSA-TECH® Recloser is a unique and patented approach to recloser design. The interrupter, drive mechanism, control, and housing are raised to the system potential. The entire assembly is then insulated from ground using a standard polymer post insulator. This approach allows a compact simplified design and also eliminates the potential for an insulation breakdown failure.

The fault interruption occurs in the recloser’s vacuum interrupter. This vacuum interrupter has state of the art contacts utilizing axial magnetic fields to interrupt in diffuse mode for maximum interrupter life. The vacuum interrupter is supported by an insulating support housing with bonded silicone rubber over-molding for maximum weather resistance.

The drive for the vacuum interrupter is provided by a mechanism with a magnetic actuator. The actuator has a rare-earth neodymium magnet, which provides the latching and holding force for the vacuum interrupter in the closed position. A spring provides the pressure to hold the vacuum interrupter in the open position. Together the rare-earth magnet and the spring arrangement allow the mechanism to be stable in the open or closed position without the need for external power. To open the vacuum interrupter a coil on the magnetic actuator is pulsed in one direction. To close the same coil is pulsed in the other direction. Energy to open and close the recloser is provided by a set of capacitors.

The control for the recloser is provided by a microprocessor based electronic circuit. The control is designed to allow complete flexibility and user choice of minimum trip, time-current curves and sequencing parameters. User access to all parameters is provided through an RS-232 serial connection. Current sensing for the control occurs through a 1000:1 current transformer.

No external transformer power for the recloser is required. Power for the control and the mechanism is converted from fault or load current using two power current transformers. The open and close capacitors needed to drive the recloser are charged by the load or fault current through the power current transformers. Using this approach the recloser will continue to open and close as necessary without the need for external power or even the hot-stick replaceable lithium battery pack. The low self-discharge

5 — Recloser Operation

lithium batteries are only required for closing the recloser after lockout or manual open.

Automatic Operation

The VERSA-TECH® Recloser, when in the closed position, operates automatically per the programmed user settings.

Manual Operating Handle

Refer to Figure 5-1 for Manual Operating Handle location. The manual operating handle is designed to allow manual operation of the recloser with a hotstick. If the manual handle operating handle is rotated 90 degrees counter-clockwise to the down (open) position the recloser will open and interrupt the distribution circuit. If the recloser has load current of 1A or more the recloser control will electronically trip the magnetic actuator and interrupt the load current. If the load current is less than 1A, pulling the manual handle down will manually pull open the mechanism and the vacuum interrupter opening the recloser.

Closing the recloser after a manual open or automatic lockout can be done by moving the manual operating handle clockwise 90 degrees to the up (closed) position. This will activate the electronic control, which will initiate the close sequence. Before the recloser is closed the close capacitor is charged to the required level from the lithium batteries. When it reaches the necessary charge level, the magnetic actuator closes the recloser. This process from movement of the handle until the recloser closes may take a few seconds.

Non-Reclosing Lever

Refer to Figure 5-1 for Non-Reclosing Lever location. The handle is shown in normal or up position. In this position the recloser will follow the automatic sequence it has been programmed for. When the handle is rotated 90 degrees clockwise to the down position, the recloser will trip using TCC1 and lockout on any current above the minimum trip. The Non-Reclosing lever does not interfere with the Manual Operating Handle.Cold load time takes precedence over the Non-Reclosing lever function

To turn on the radio without adequate load current, pull down the non-reclosing lever and then push it up. The radio then will automatically shut off after 10 minutes of communications inactivity to minimize battery drain.

Operations Counter

Refer to Figure 5-1 for Counter location. Operations counter is an electromechanical counter, which counts open operations both manual and automatic initiated by the control. Manually opening the recloser when load current is less than 1A will not increment the counter.

Lockout Beacon

Refer to Figure 5-1 for Beacon location. The Lockout Beacon is a unique feature, which is designed to aid the utility lineman in identifying a locked out recloser. This high intensity sunlight visible amber LED will flash once every 3 seconds when the recloser has sequenced to lockout. The beacon will continue to flash every 3 seconds until the lineman closes the recloser or 4 hours have passed. After 4 hours the flashing beacon will automatically shutoff. The lithium batteries provide the power for the beacon. The duty cycle for the flashing beacon is chosen to have a negligible effect on battery life.

The beacon is also utilized when the recloser is manually opened. The beacon will continue to flash until the recloser is closed or 60 seconds has passed.

Hot Line Tag

When this function is enabled through the user interface the user will be able to use the Non-Reclose handle for either Non-Reclose mode or instantanious trip in Hot Line Tag mode.

Figure 5-1 Feature position

Manual Operating Handle Non-Reclosing

Lever

Lockout Beacon

Operations Counter

Page 17: Versatech Recloser Manual

PSP8620311Rev.C

17

6 — Control Programming

Overview

The VERSA-TECH® Recloser can be fitted with an optional radio which will allow settings, diagnostics and scratchpad to be viewed remotely while the unit is in service. The radios will also allow settings, timestamp and scratchpad to be changed while the recloser remains in service. Remote radio communications are accomplished using two 900MHz spread spectrum radios. The first is a USB powered local radio that is attached to a laptop or other personal computing running recloser programmer software. The second is a recloser powered remote radio module which is adapted to the serial port on the recloser.

Connecting Local Radio

The local radio (Catalog No. PSC8620062) is controlled and powered by connecting a USB cable between the module and a personal computer as shown in Figure 6-1. Communication with the local radio is accomplished through the recloser programmer software (see section 6) provided with the recloser.

Remote Radio Power

When the VERSA-TECH® Recloser is in service with a load current of 10 A or more, the attached remote radio is on and powered from the recloser's internal current transformers. If the recloser is not in service or the load current is less than 10 amps, the radio is off and must be powered from the recloser's internal batteries. To turn on the radio, pull down the non-reclosing handle and then push it up. The radio then will automatically shut off after 10 minutes of communications inactivity to minimize battery drain. If the Non-Reclosing Lever is left in the down position without the ample 10A of load current, wireless communications will time out in 60 minutes.

Figure 6-1 Connecting Local Radio

Radio Operation

The radios communicate with each other on a 900MHz channel which utilizes frequency hopping to minimize interference from other radio frequency sources. The radio transmit power is 4mW which allows line of sight communication at distances up to 500 feet. The radios use a two-part addressing scheme to help ensure that messages from only authorized sources are passed to a recloser.

First, all VERSA-TECH® Recloser local and remote radios have a unique user transparent address which goes out with each communication. The recloser local radio will accept messages only from a remote radio with the same address. This helps prevent other 900MHz radios from making unauthorized communications with VERSA-TECH® Reclosers.

Second, each remote radio is programmed with a unique fixed radio communications address. This address allows users to differentiate between multiple reclosers all within a 500-foot transmit/receive range. The remote radio will discard any message that does not include its unique radio communications address. The local radio has provisions through the recloser programmer software (see Section 6) which permits selecting any recloser's remote radio communications address.

Customer Supplied Requirements

• Personal computer with Microsoft® Windows® XP or Windows® 7 32-bit operating system, a CD-ROM Drive and an RS-232 serial port and cable if a direct conection is desired.• ***ALL digital transmission can be accomplished with the wireless radio pair in this recloser version**

Software Installation

Recloser programming software must be installed on the computer proir to use. Installation software is provided with each recloser on a CD-ROM.

Connecting Recloser to PC

The customer supplied DB9 Male/Female serial cable is used to directly connect the recloser to a PC (hardwired).Wireless communications can be established utilizing the appropriate remote/local radio combination.

To Establish Communications

Opening of the software interface automatically launches a scan for compatible devices directly connected or within range (hard wired or wirelessly respectively).

Page 18: Versatech Recloser Manual

PSP8620311Rev. C

18

6 — Control Programming

NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice.

Quick Start Guide for Local Radio PSC8620062

Before using the Local Radio for the first time, the Windows® device drivers will have to be installed. The following steps illustrate the process.

1. Locate Versa-Tech™ Recloser CD Software included with recloser packaging.

2. Connect the USB plug to USB port on the radio.4. Connect the other end of the USB cord to USB port on the PC/laptop.

5. “Found New Hardware” Wizard should start.

6. At the “Can Windows connect to Win- dows Update to search for software?” window, select “No, not at this time” and click <NEXT>

7. Insert CD into CD drive. Found New Hardware wizard should automatically continue, if not, click <NEXT>.

8. Click Finish.

9. “Found New Hardware” Wizard should start again. This time it is adding the USB port.

10. Repeat Steps 6 to 8 above.

Page 19: Versatech Recloser Manual

PSP8620311Rev.C

19

6 — Control Programming

11. Click NEXT.

12. Click FINISH.

13. Computer should state “New hard- ware is installed and ready to use.”

To determine which COM port the lo-cal radio is using, as assigned by your computer, perform these steps:

1. Right click on “My Computer.”

2. Select “Properties.”

3. Select the “Hardware” Tab.

4. Click the “Device Manager” Button.

5. Click the “+” icon next to Ports.

6. In the Ports section it will state “HPS Local Radio (COM X)”. The “X” is the port number it is using. This number will be used during programming.

Before attempting to communicate with the recloser radios each time, be sure to:

1. Attach antenna to radio unit.

2. Know or determine the COM port the local radio is using as outlined above.

3. See Recloser Installation, Operation and Maintenance Manual for program- ming software setup and communica- tion with reclosers through remote radios.

Page 20: Versatech Recloser Manual

PSP8620311Rev. C

20

Windows 7 Local Radio Quick Start Guide!!! DO not connect radio before inserting the CD !!!

1) Insert Versa Tech recloser CD part number PSP8620063__C into your computer2) Connect the local radio to the computer with the provided USB cable. Windows will attempt to automatically install drivers using the found hardware wizard.

If this driver installation process does not continue automatically: 3) Open the Device Manager by going to Start Menu>Right click on “Computer”>Select “Manage”

4) Click on the device manager and locate “HPS Local Radio”5) Right click on “HPS Local Radio” then select “Update Driver Software”

6 — Control Programming

Settings Tab

Page 21: Versatech Recloser Manual

PSP8620311Rev.C

21

6) Select “Browse my computer for driver software” & select the Drive the disk is in. Click Next.

7) Pop-up will say “Cannot verify publisher,” choose “Install anyway”; Driver will be installed.

6 — Control Programming

Settings Tab

Page 22: Versatech Recloser Manual

PSP8620311Rev. C

22

8) Repeat from Step 3 to 7 for an item called “USB Serial Port”; drivers are now installed.

NOTE The installer must run twice. Once to install the radio driver itself and then again to install the USB Serial Port

6 — Control Programming

Settings Tab

Page 23: Versatech Recloser Manual

PSP8620311Rev.C

23

6 — Control Programming

Once a device list is compiled and returned, select and activate a device by double clicking its COM port name OR select it by clicking its COM port name and then clicking the connect button to activate the connection. Doing so will automatically connect your computer to that device and query its settings values from the control memory.

Programming Settings

The Recloser Settings Tab appears when the Recloser Programmer Software is loaded and opened. See Figure 6-2. At this point, changes to the settings can be made as required for the recloser’s particular application. When settings changes are complete, the “Write Settings To Recloser” button will allow the settings displayed to be stored in the recloser. Notice that settings fields that are not identical to what is actually stored in control memory are displayed in red until they are committed to memory. From this point forward the recloser will use these new stored settings. These settings can be checked at any time by clicking the “Read Settings From Recloser” button

Figure 6-2

Settings Tab

Page 24: Versatech Recloser Manual

PSP8620311Rev. C

24

6 — Control Programming

Minimum Trip Value

The Minimum Trip Value is the minimum current sensed that will cause the Recloser to trip. This current is programmable from 30A to 800A in 10A increments. The control will begin counting towards meeting the selected time current curve when there is a half cycle of current above this threshold. The current level is measured by sampling and finding its peak value. The sample frequency for current measurement is 488.128 usec. This gives approximately 32 samples per 60Hz cycle. High frequencies are filtered by requiring at least 4 samples of current per half cycle in addition to a current sample above the fault threshold. This method will reject frequencies greater than 400Hz.

Sequence Coordination

The sequence coordination feature, if enabled, will prevent unnecessary operations of the recloser when used in a series arrangement upstream from other fault interrupting devices. If the recloser senses current above the minimum trip level for a duration shorter than the programmed control response time, the recloser will internally advance its software count one operation without tripping. This action allows an upstream recloser to stay in proper sequence when faults are cleared by a downstream recloser. False counting is avoided by applying hysteresis to the minimum trip threshold. The current must increase above the minimum threshold and then decrease to 87.5% of the trip threshold before a count is registered. The count is remembered for the reset time.

Non Reclose Vs. Hot Line Tag

In this version of the recloser, the non reclose handle can be selected to be used as a conventional non reclose utilizing TCC1 or as a Hot Line Tag (HLT) utilizing an instantaneous trip. This is accomplished by selecting the proper radio button on the main “Settings” tab of the software. The Non-Reclose/Hot Line Tag option will place the recloser in traditional Non-Reclose using whichever curve is selected as TCC1. IF however the handle is cycled once more within 30 seconds (meaning returned to normal operation and then back to the down position), the device will be placed into Hot Line Tag (HLT) mode with an accompanying characteristic pulsed strobe of the beacon to indicate such. If the Hot Line Tag Only mode is selected, the Non Reclose handle will always function only with an instantaneous (HLT) response.Operations to Lockout

The control can be set to 1,2,3, or 4 operations before the recloser goes to lockout.

Manual Closing Delay Time

The time from when the manual handle is activated until the recloser begins closing the circuit can be programmed from 0 to 30 seconds. The actual delay may be a few seconds longer than the time programmed.

Time-Current Curve Selection

The control can be set to utilize two different time current curves TCC1 and TCC2. TCC1 and TCC2 can be set separately to use one of 11 different time current curves. See Reference Bulletin 10-0501 through 10-0522. Each of the 4 possible operations can be set to use either TCC1 or TCC2.

Time-Current Curve Modifiers

Each of the 11 time current curves can be modified for greater coordination flexibility. By selecting Mod1, Mod2 or Mod3, the shape of the time-current curve can be modified as shown in Reference Bulletin 10-05-11 through 10-05-22.

Minimum Response Time

Minimum response time is used to achieve coordination between fault interrupting devices where fault levels would cause two devices in series to both trip. When minimum response is enabled, tripping is inhibited until the minimum response time programmed is less than or equal to the fault current time. The minimum response time is programmable from 0 to 250 milliseconds in 1 millisecond steps and can be enabled on operation 1,2,3, or 4.

Reclose Time

Reclose Time is the amount of time from when the recloser interrupts the over-current until the recloser attempts to close the circuit again. Each of the three possible reclose intervals is separately programmable from 0.25 to 60 seconds in 0.05 second increments.

Reset Time

Reset time is the amount of time from the last reclose until the present count of operations completed is reset to zero. When the recloser goes to lockout, this count is also reset to zero. Reset time is programmable from 1 to 240 seconds in 1-second increments.

Cold Load Time

During this programmed interval, the control will be in one operation to lockout mode and overcurrent timing will use TCC2. Cold load pickup is active after the recloser has been opened manually or has been in lockout mode. If no overcurrent is present during this interval, the control will reset. Cold Load Time

is programmable from 0 to 300 seconds in 1 second increments. Setting the cold load time to 0 inhibits cold load pickup. Cold load time takes precedence over the Non-Reclosing lever function

Record Manual Close

When enabled, this feature causes the recloser to store in the Event History the time and date of manual closes as well as over-current operations. When disabled, only over-current operations are stored.

Time Stamp

The recloser has a built in time stamp circuit which records the time and date following each recloser operation. The time stamp time can be read using the “Get Time” button in the recloser programmer software (see section 6). The time stamp time can be updated by using the “Set Time” button. The time is updated by reading the time and date from the host computer and sending them to the recloser to be stored.

Note: Make sure that the host computer has the accurate time and date before using the “Set Time” feature.

The time stamp utilizes one of 3 power sources to maintain correct time. When the recloser is in service internal current transformer power is used. When the recloser is open or not in service the main lithium batteries are used. If both of these power sources are unavailable the control has a capacitor backup circuit, which can power the time stamp for up to 7 days.

Note: Once the time stamp has been set, it is important that the lithium battery bayonet not be removed for more than 7 days. If the time stamp loses power, the recloser will continue to function correctly, but the times and dates stored for recloser operations will be incorrect.

Settings Tab

Page 25: Versatech Recloser Manual

PSP8620311Rev.C

25

To disconnect

Click the “Disconnect” buttonA “Rescan” for newly connected (within range) or different devices can now be performed by clicking the “Rescan all Ports” button.

Address of both local and remote radio must match for Digi radio use. (above)

Addresses of remote and local SiFlex radios do not have to match. (below)

Note the status indicators at the bottom of the form window. Here you will find indications for….CommunicationsCom : Successful CommunicationsRXD : Receive (data)NR : Non RecloseHLT : Hot Line TagLine : Rated Line frequency F/W Rev. : Recloser control firmware versionLocal Radio : Present Local Radio AddressRemote Radio : Present Remote Radio AddressSIG : Radio signal strength indicationRecloser Time : Present time programmed into Recloser S/N : Recloser serial numberAndA last action confirmation window (lower right of the main form)

6 — Control Programming

Settings Tab

Page 26: Versatech Recloser Manual

PSP8620311Rev. C

26

6 — Control Programming

Settings TabButton Functions General Form Controls

Read Settings From Recloser

Extracts currently programmed settings values from the recloser control’s memory

Write Settings To Recloser Programs the recloser’s control with currently displayed settings valuesRecloser Settings Profile

Recloser Settings Profile Load From

Opens a window where previously stored settings can be retrieved from a known directory or location

Save To File

Opens a window where a particular directory or location can be browsed to and selected in which to store currently displayed settings values

Generate Full Recloser report

Generates full report including all settings, Scratchpad, and fault historyCan be exported as .txt or .xml fileRescan All PortsPerforms a scan of the system for any “within range” or directly connected devicesConnect/DisconnectEstablishes or disconnects digital communications, wireless or hardwired

Page 27: Versatech Recloser Manual

PSP8620311Rev.C

27

6 — Control Programming

Real Time Monitoring

Instantaneous Current Monitoring

The real time monitoring features are automatically updated following a successful connection. The last hour rolling average and the peak values can be reset using the appropriate reset buttons for each (Figure 6-3). These value fields return the instantaneous RMS current value updated approximately every 2 seconds.

Figure 6-3

Page 28: Versatech Recloser Manual

PSP8620311Rev. C

28

6 — Control Programming

Events and Data LogViewing Diagnostic Events and Data Log

The recloser also has some built in diagnostic features, which can be read by selecting the Events and Data Log Tab as shown in Figure 6-4. This field will display the recloser operations count, the energy of interrupted faults, and the hourly log data field. Separately, the resettable operations counter can be reset and the data log erased by clicking the appropriate buttons. In addition to the fault history previously available, there is now a viewing window for an hourly log (Load Profile). Due to required upload times options are given for the last week, last 2 weeks or entire log (45 DAYS) to be retrieved. This log will be included in the full report generation only after it has been separately downloaded. The Generate Full Recloser Report will not include the hourly log unless it has been previously downloaded. Sequence coordination events will be registered and marked as such in the events log.

Figure 6-4

Page 29: Versatech Recloser Manual

PSP8620311Rev.C

29

6 — Control Programming

Radio Setup and Security

Password Protection for Settings Changes

The recloser comes with password security for settings changes. When changing the settings with the “Write Settings To Recloser” button, a correct password must be given one time per session. The default from the factory is lower case "password". To change the password, click on the “Change Password” button and follow the on screen prompts. Check the “Auto Update Recloser State Every 2 Seconds” box to enable automatic polling for instantaneous current monitoring. Click the “Set Recloser Time” button to synchronize the internal clock with the clock in the connected computer. See Figure 6-5. The “Flash Beacon” button can be used to manually flash the beacon in order to identify a recloser that you are actively connected to.

Figure 6-5

Page 30: Versatech Recloser Manual

PSP8620311Rev. C

30

6 — Control Programming

Scratchpad

Viewing the Scratchpad The recloser has a convenient scratchpad built in to its non-volatile memory. The memory can store 256 characters of information in text form. The scratchpad is accessed by selecting the Scratchpad Tab as shown in Figure 6-6. The “Load From Recloser” button will show the current text stored in the recloser. The text information can be changed in the text box and stored using the “Save To Recloser” button. This feature could contain any information pertinent to the maintenance or tracking of the recloser such as a source substation name, a physical address, install date, counter when installed, ect.

Figure 6-6

Page 31: Versatech Recloser Manual

PSP8620311Rev.C

31

6 — Control Programming

Firmware UpgradeUpgrading the Firmware

Versa-Tech® firmware upgrade procedure 

-Have the latest HPS supplied firmware version .a43 file saved in a known location on the computer being used to perform the upgrade -Establish wireless communications by opening the User Interface Version 2.41 or later -Double click on the appropriate COM Port to establish communications with the recloser you wish to upgrade -Click on the “Firmware upgrade” Tab -Click the “Load File” button -Select the supplied .a43 file from the known location where it was stored. -Click the “Start” button -Enter a valid security password and click OK. -Allow the upgrade to continue to completion -You should receive a “Successful, Device is operational. Press OK.” Confirmation directly above the progress meter.

***While upgrading the control firmware wirelessly, system coordination from this device will be interrupted for 2-3 seconds while the nonvolatile memory sector is written to. If left unbypassed and in the circuit during this time, any faults that occur on the load side of the recloser could be passed back upstream to a source side protective device. Bypassing the recloser may be preferred by some utilities.

Page 32: Versatech Recloser Manual

PSP8620311Rev. C

32

! CAUTION

! WARNING

7 — Testing

High Potential Withstand TestApplying AC 50/60 Hz voltage across the open contacts of the recloser will test the dielectric integrity of the vacuum interrupter. The AC voltage should be applied at 40kV which is 2/3 of the rated maximum withstand for 60 seconds.

1.Open the recloser.2.Connect the test voltage across the

recloser open contacts by attaching one end of the test transformer to each of the 2-hole NEMA input pads (see Figure 7-1).

3.Ensure both ends have adequate electrical clearance from each other and from any ground.

4.Verify the recloser can hold the voltage across the open contacts for 60 seconds.

During high potential withstand tests, self extinguishing momentary breakdowns can occur which do not indicate significant loss of vacuum.

Hazardous voltages are present during testing. Severe personal injury or death can occur from contact with recloser or high voltage transformer during tests.

Recloser and high voltage transformer must be in a grounded test cage or similar protective barrier to prevent accidental contact with energized equipment.

X-rays may be emitted from open vacuum interrupter contacts dur-ing high potential withstand tests.

X-rays may be hazardous to your health.

Maintain a minimum of 3 meters distance from recloser during this high potential with-stand test.

X-rays emitted by testing at voltages up to 40kV are negligible at the minimum 3 meters distance, but higher test voltages may result in hazardous x-ray emission.

Figure 7-1 Recloser attached to high potential test set

AC High Potential Test Set

Page 33: Versatech Recloser Manual

PSP8620311Rev.C

33

7 — Testing

Minimum Trip Current Test

The minimum trip current test can be used to check programmed minimum trip settings as well as recloser control functionality.

1.Close the recloser contacts.2.Connect a low voltage high current test

set across the contacts by attaching one end of the test set to each of the 2-hole NEMA input pads (see Figure 7-2).

3.Ensure both ends have adequate electrical clearance from each other and from any ground.

4.Attach an ammeter to monitor the current into the recloser. Slowly increase the current. Note and compare the ammeter reading when the recloser trips to the programmed minimum trip value. Figure 7-2 Recloser attached to high current test set

Sequence of Operation Test

The sequence of operation test can be used to check the programmed number of fast and delayed trip settings as well as operations to lockout

1.Close the recloser contacts.2.Connect a low voltage high current

test set across the closed contacts by attaching one end of the test set to each of the 2-hole NEMA input pads (see Figure 9-2).

3.Ensure both ends have adequate electrical clearance from each other and from any ground.

4.Attach an ammeter to monitor the current into the recloser. Apply a test current above the minimum trip value and compare recloser response to programmed settings.

High CurrentTest Set

Ammeter

Page 34: Versatech Recloser Manual

PSP8620311Rev. C

34

! WARNING

! WARNING

8 — Maintenance

Service Requirements

The VERSA-TECH® Recloser has been designed for a minimum mechanical life of 30,000 operations. No routine maintenance is required.

Battery Replacement

The batteries are made of a very stable lithium chemistry, which is designed with a low self discharge that they can func-tion correctly for up to 10 years. Hubbell Power Systems is recommending that users replace the batteries on an 8 year cycle.

Figures 8-1 and 8-2 show the battery bayonet and placement in the recloser. The battery bayonet was designed to be replaced using a hot stick while the recloser is in service. The battery bayonet utilizes a twist lock design. It is easily removed by pushing in slightly and turning.

The date of manufacture of the battery bayonet is stamped on its end casting. The date format is "XXXX" where the first two numbers represent the month and the second two numbers represent the year.

Figure 8-1 Battery bayonet in the recloser

Figure 8-2 Battery bayonet partially removed from recloser

Fire, explosion, leakage and severe burn hazard.

Do not recharge or disassemble batteries. Batteries should not be exposed to temperatures above 212 degrees F. Do not incinerate batteries or expose them to water. Do not short (+) and (-) terminals of batteries. When discarding batteries, insulate the (+) and (-) terminals with insulating tape.

High voltage electric contact hazard.Can cause severe injury or death.

The recloser housing and the battery bayonet are energized when the re-closer is in service. Follow all of your utility's recommended safety practices for working with energized apparatus of this voltage class. Use appropriate length grip-all clamp stick or appropriately rated rubber gloves and personal protective equipment.

Battery Disposal

Litihium batteries are neither specifi-cally listed nor exempted from the Federal Environmental Protection Agency (EPA) hazardous waste regulations as promul-gated by the Resource Conservation and Recovery Act (RCRA). The only metal of possible concern in a lithium battery is lithium that is not a listed or characteristic toxic hazardous waste. Waste lithium batter-ies can be considered a reactive hazardous waste if there is a significant amount of un-reacted, or unconsumed lithium remaining in the spent battery. The key to disposing of a lithium battery as a non-hazardous waste is to guarantee that it is fully or mostly discharged. Once it is discharged it can be disposed of as non-hazardous waste.

Page 35: Versatech Recloser Manual

PSP8620311Rev.C

35

Cleaning Instructionsfor Versa-Tech® Recloser

Battery Bayonet PSC8620068

1. Clean battery contact surfaces, recloser sleeve, and recloser battery contact surface with DeoxIT wipes per instructions on bag.

2. Apply protective coating to battery contact surfaces and recloser contact surface with DeoxIT Gold wipes per instructions on bag.

Recloser contact sleeve

Recloser battery contactin base of tube

Battery contact surfaces

8 — Maintenance

Page 36: Versatech Recloser Manual

PSP8620311Rev. C

36

9 — Trouble Shooting

The following table presents possible symp-toms, their possible cause(s) and likely corrective action(s). These do not cover all possible problems. If you are unable to correct a problem using this trouble shooting guide, contact your factory representative.

Table 9-1 Trouble Shooting Guide

Recloser does a) Handle not in full closed position a) Make sure handle fully closed (up)

not close b) Batteries low b) Replace batteries

Recloser does a) Non-reclosing lever is down a) Move non-reclosing lever to up position

not automatically

reclose

Recloser a) Damaged mechanism a) Consult factory representative

does not open

Programming a) Bad cable a) See Section 6 for cable specification

software does not b) Bad cable connection b) Ensure good connection for cable on both ends

communicate with c) Communication port unselected or c) Ensure port is selected and connected cable

recloser incorrectly selected matches port selected

Corrective Action(s)Possible Cause(s)Symptom

Page 37: Versatech Recloser Manual

PSP8620311Rev.C

37

NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice.

Return KitPackaging Instructions: Versa-Tech® Recloser

SPECIAL INSTRUCTIONS (MUST be done for proper shipment):1. Components must be packaged exactly as shown above. Return Kit includes: Foam inserts, cardboard tubes, the outer carton (same as the Return Kit was shipped in) and Class 9 Material Label.

Recloser with battery bayonet must be shipped per Department of Transportation (DOT) rules for lithium batteries. Lithium batteries are considered a Class 9 material for shipment.

2. Ensure the battery bayonet containing the batteries is returned in the original shipping container (corrugated box indicated in Photo D above, but not provided in the Return Kit) or in the receptacle of the Versa-Tech recloser (indicated in Photo C above).

3. On the outer carton, apply the Class 9 label (provided in the return kit) on the same side of the carton imprinted with "LITHIUM BATTERIES PACKED WITH EQUIPMENT UN 3091".

Battery Bayonetoriginal corrugated box(NOT in Return Kit)

Photo ABottom foam insert

Photo BShort cardboard tube

Long cardboard tube

Photo CBattery Bayonet receptacle

Foam inserts Photo DTop foam insert

Page 38: Versatech Recloser Manual

PSP8620311Rev. C

38

Notes

Page 39: Versatech Recloser Manual

PSP8620311Rev.C

39

Notes

Page 40: Versatech Recloser Manual

PSP8620311Rev. C

40

8100 Churchill AvenueLeeds, Alabama 35094(205) 699-0840www.hubbellpowersystems.com

PSP8620311Rev.C