ICF Finish System€¦ · TAFS Over ICFs Cutaway Base Detail- Height Adjuster Head/Sill- Bucksaver...

22
DS193 ICF Finish System 100% Textured Acrylic Finishing Systems (TAFS) For Use Over Insulating Concrete Forms (ICF) ICF Finish System Installation Details

Transcript of ICF Finish System€¦ · TAFS Over ICFs Cutaway Base Detail- Height Adjuster Head/Sill- Bucksaver...

  • DS193

    ICF Finish System 100% Textured Acrylic Finishing Systems (TAFS) For Use Over Insulating Concrete Forms (ICF)

    ICF Finish System Installation Details

  • TABLE OF CONTENTS

    TAFS®OVER INSULATING CONCRETE FORMS

    NOTE

    DETAIL

    TAFS Over ICFs CutawayBase Detail- Height Adjuster

    Head/Sill- Bucksaver Rough Buck ICF 0.0.06ICF 0.0.05ICF 0.0.04ICF 0.0.03ICF 0.0.02ICF 0.0.01

    Base Detail- Tapered Cut Form

    ICF 0.0.07

    Base Detail- Cut Form

    Base Detail- EPS TrimBase Detail- Without Inspection Strip

    DRYVIT MAKES NO REPRESENTATION REGARDINGCONFORMITY OF ITS SUGGESTIONS TO MODEL BUILDINGCODES, ENGINEERING CRITERIA, SPECIFIC APPLICATIONS ORPROJECT LOCATIONS. ALL COMPONENTS INDICATED INILLUSTRATIONS, AS WELL AS OTHERS THAT MAY BEREQUIRED FOR THE INTEGRITY OF THE SYSTEM SHALL BEDESIGNED, DETAILED AND ENGINEERED BYREPRESENTATIVES OF THE ARCHITECT, OWNER ORCONTRACTOR TO BE IN CONFORMANCE WITH MODEL CODES,ARCHITECTURAL AND ENGINEERING REQUIREMENTSPERTAINING TO SPECIFIC BUILDING PROJECTS.

    DRYVIT MAKES NO WARRANTY, EXPRESSED ORIMPLIED, AS TO THE ARCHITECTURAL DESIGN,ENGINEERING, OR WORKMANSHIP OF PROJECTSUTILIZING DRYVIT SYSTEMS OR PRODUCTS.

    THE LIABILITIES OF DRYVIT SHALL BE ASSTATED IN THE DRYVIT STANDARDWARRANTY. CONTACT DRYVIT FOR A FULLAND COMPLETE COPY OF THIS WARRANTY.

    with EPS TrimHead/Sill- Wood Rough Buck

    with EPS TrimICF 0.0.08

    Head/Sill- Bucksaver Rough Buck ICF 0.0.09Head/Sill- Wood Rough Buck ICF 0.0.10

    ICF 0.0.11Head/Sill- Flange MountICF 0.0.12Head/Sill- Recessed

    ICF 0.0.13A/C PenetrationICF 0.0.14Eave Detail- Recessed Top PlateICF 0.0.15Eave Detail- Exposed Top PlateICF 0.0.16Eave Detail- Steel Roof RaftersICF 0.0.17Sloped Roof/Wall IntersectionICF 0.0.18Transition to Existing WallICF 0.0.19Transition Across ColumnICF 0.0.20Parapet Termination

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

  • Cutaway

    ICF 0.0.01

    TAFS OVER ICFs®

    BY OTHERS

    DRYVIT TAFS

    BY OTHERS

    DRYVIT TAFS OVERADDITIONAL LAYER OF EPS

    Dryvit TAFSOver ICF

    ICF

    DRYVIT BASE COAT

    DRYVIT REINFORCING MESH

    DRYVIT BASE COAT

    DRYVIT FINISH

    ICF

    DRYVIT ADHESIVE

    EXPANDED POLYSTYRENEINSULATION BOARD (MIN. 1")

    DRYVIT BASE COAT

    DRYVIT REINFORCING MESH

    DRYVIT BASE COAT

    DRYVIT FINISH

    Dryvit TAFSOver AdditionalLayer of EPSOver ICF

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

    DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS

    NOTE:1.

  • DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™ ORSTANDARD PLUS™ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DOCUMENTS

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT DRYFLEX

    BASE COAT

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    WATERPROOFING MEMBRANE

    & DRAINAGE / PROTECTION

    BOARD AS SPEC'D

    DRYFLEX TO BE LAPPED OVER

    WATERPROOFING AT GRADE

    LEVEL MIN 6"

    DRYVIT FINISH

    BURIED WEB FORM UNIT

    SEE DETAIL BELOW

    ELEV. OF TERMITE INSPECTION

    STRIP ABOVE FIN. GRADE

    6" TO 8" AS PER CODE

    TEMPORARY PLYWOOD

    FORM FASTENED TO WEBS

    PRIOR TO CONCRETE PLACEMENT

    TO CREATE INSPECTION STRIP

    HEIGHT ADJUSTER (3-3/8")

    2.

    1. NOTE:

    DETAIL RECOMMENDED WHEN ANINSPECTION STRIP IS REQUIREDBY LOCAL JURISDICTION OR BYPEST CONTROL OPERATORS

    MINOR CRACKING IS POSSIBLE INTHE FINISHED EXTERIOR SURFACEAT ICF/CONCRETE TRANSITIONS

    3.

    FORM SPACE TO BE EQUAL

    TO HEIGHT ADJUSTER AT

    OPPOSITE SIDE OF FORM

    APPLY REINFORCED DRYVIT

    DRYFLEX® BASE COAT OVERINSPECTION STRIP EXTENDING

    MIN. 6" OVER ICF ABOVE AND

    BELOW, AND MIN. 12" FROM

    GRADE

    Base Detail - Height Adjuster

    ICF 0.0.02

    TAFS OVER ICFs®

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

  • ICF 0.0.03

    TAFS OVER ICFs

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

    SEE DETAIL BELOW

    CUT SECTION OF FORM

    4" MIN. OR AS REQUIRED

    BY CODE

    APPLY REINFORCED DRYVIT

    DRYFLEX® BASE COAT OVERINSPECTION STRIP EXTENDING

    MIN. 6" OVER ICF ABOVE AND

    BELOW, AND MIN. 12" FROM GRADE

    ELEV. OF TERMITE INSPECTION

    STRIP ABOVE FIN. GRADE

    6" TO 8" AS PER CODE

    WATERPROOFING MEMBRANE

    & DRAINAGE / PROTECTION

    BOARD AS SPEC'D

    DRYFLEX TO BE LAPPED OVER

    WATERPROOFING AT GRADE

    LEVEL MIN 6"

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE

    COAT

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT DRYFLEX

    BASE COAT

    TEMPORARY PLYWOOD

    FORM FASTENED TO WEBS

    PRIOR TO CONCRETE PLACEMENT

    TO CREATE INSPECTION STRIP

    DRYVIT FINISH

    BURIED WEB FORM UNIT

    DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™ ORSTANDARD PLUS™ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DOCUMENTS

    MINOR CRACKING IS POSSIBLE INTHE FINISHED EXTERIOR SURFACEAT ICF/CONCRETE TRANSITIONS

    DETAIL RECOMMENDED WHEN ANINSPECTION STRIP IS REQUIREDBY LOCAL JURISDICTION OR BYPEST CONTROL OPERATORS

    1. NOTE:

    2.

    3.

    Base Detail - Cut Form

    ®

  • ICF 0.0.04

    TAFS OVER ICFs

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

    DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™ ORSTANDARD PLUS™ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DOCUMENTS

    MINOR CRACKING IS POSSIBLE INTHE FINISHED EXTERIOR SURFACEAT ICF/CONCRETE TRANSITIONS

    DETAIL RECOMMENDED WHEN ANINSPECTION STRIP IS REQUIREDBY LOCAL JURISDICTION OR BYPEST CONTROL OPERATORS

    1. NOTE:

    2.

    3.

    4" MIN. OR AS REQUIRED BY CODE

    CUT SECTION OF FORM

    WITH 45° TAPER

    APPLY REINFORCED DRYVIT

    DRYFLEX® BASE COAT OVERINSPECTION STRIP EXTENDING MIN. 6"

    OVER ICF ABOVE AND BELOW,

    AND MIN. 12" FROM GRADE

    BURIED WEB FORM UNIT

    ELEV. OF TERMITE INSPECTION

    STRIP ABOVE FIN. GRADE

    6" TO 8" AS PER CODE

    WATERPROOFING MEMBRANE

    & DRAINAGE / PROTECTION

    BOARD AS SPEC'D

    DRYFLEX TO BE LAPPED

    OVER WATERPROOFING AT

    GRADE LEVEL MIN 6"

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    DRYVIT COMPATIBLE SEALANT

    EPS FILLER MIN 1" ATTACHED

    TO ICF WITH DRYVIT ADHESIVE

    DRYVIT FINISH

    Base Detail - Tapered Cut Form

    ®

  • ICF 0.0.05

    TAFS OVER ICFs

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

    BURIED WEB FORM UNIT

    APPLY REINFORCED DRYVIT

    DRYFLEX BASE COAT MIN.

    12" FROM GRADE

    WATERPROOFING MEMBRANE

    & DRAINAGE / PROTECTION

    BOARD AS SPEC'D

    DRYFLEX TO BE LAPPED

    OVER WATERPROOFING AT

    GRADE LEVEL MIN 6"

    MIN 6:12 SLOPE ON ALL

    PROJECTING SURFACES

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT DRYFLEX®BASE COAT

    EPS SHAPE

    DRYVIT FINISH

    DRYVIT ADHESIVE

    SEE DETAIL 1, 2, & 3 WHENPROTECTION FROM WOODBORING INSECTS ISDETERMINED TO BENECESSARY

    NOTE:1. DRYVIT RECOMMENDS THAT GROUND

    FLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™ ORSTANDARD PLUS™ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATEDON CONTRACT DOCUMENTS

    2.

    Base Detail - EPS Trim

    ®

  • ICF 0.0.06

    TAFS OVER ICFs

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

    DRYVIT FINISH

    BURIED WEB FORM UNIT

    WATERPROOFING MEMBRANE

    & DRAINAGE / PROTECTION

    BOARD AS SPEC'D

    DRYFLEX TO BE LAPPED

    OVER WATERPROOFING AT

    GRADE LEVEL MIN 6"

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT DRYFLEX®BASE COAT (MIN. 6" ON EACH SIDE

    OF ICF JOINT)

    APPLY REINFORCED DRYVIT

    DRYFLEX BASE COAT MIN. 12"

    FROM GRADE

    DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™ ORSTANDARD PLUS™ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATEDON CONTRACT DOCUMENTS

    1. NOTE:

    SEE DETAIL 1, 2, & 3 WHENPROTECTION FROM WOODBORING INSECTS ISDETERMINED TO BENECESSARY

    2.

    Base Detail - Without Inspection Strip

    ®

  • ICF 0.0.07

    TAFS OVER ICFs

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

    VINYL BUCK SYSTEM

    DRYVIT FINISH

    DRYVIT ADHESIVE

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    BURIED WEB FORM UNIT

    FLANGE MOUNT WINDOW

    MIN 1/2" DRYVIT COMPATIBLE

    SEALANT AND CLOSED CELL

    BACKER ROD (TYP.)

    MIN 6:12 SLOPE ON ALL

    PROJECTING SURFACES

    DRYVIT COLOR PRIME™ ORDEMANDIT® ON SURFACES TO

    RECEIVE SEALANT

    DRYVIT AQUAFLASH SYSTEM OR

    DRYVIT FLASHING TAPE™ EXTENDED OVER ENTIRE SILL AND

    ONTO FRONT FACE OF VERTICAL WALL

    ATTACH EPS SHAPE WITH

    VERTICAL NOTCHED TROWEL

    ADHESIVE PATTERN

    MIN 6:12 SLOPE ON ALL

    PROJECTING SURFACES

    MIN 1/2" DRYVIT COMPATIBLE

    SEALANT AND CLOSED CELL

    BACKER ROD (TYP.)

    DRYVIT AQUAFLASHâ SYSTEM ORDRYVIT BACKSTOPâ NT AND GRID TAPE

    ALONG HEAD & JAMBS EXTENDED

    TO THE INSIDE FACE OF THE WALL

    EPS SHAPE

    1/2" GYPSUM BRD.

    Head/Sill - Bucksaver Rough Buck With EPS Trim

    ®

    DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS

    THIS DETAIL ISRECOMMENDED FOR USEIN COMBUSTIBLECONSTRUCTION ONLY.

    NOTE:1. 2.

  • ICF 0.0.08

    FLANGE MOUNT WINDOW

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    MIN 1/2" DRYVIT COMPATIBLE

    SEALANT AND CLOSED CELL

    BACKER ROD (TYP.)

    DRYVIT COLOR PRIME™ ORDEMANDIT® ON SURFACES TO

    RECEIVE SEALANT

    ATTACH EPS SHAPE WITH

    VERTICAL NOTCHED TROWEL

    ADHESIVE PATTERN

    DRYVIT AQUAFLASH SYSTEM OR

    DRYVIT FLASHING TAPE™EXTENDED OVER ENTIRE SILL AND

    ONTO FRONT FACE OF VERTICAL WALL

    MIN 1/2" DRYVIT COMPATIBLE

    SEALANT AND CLOSED CELL

    BACKER ROD (TYP.)

    DRYVIT AQUAFLASHâ SYSTEMOR DRYVIT BACKSTOPâ NT AND

    GRID TAPE™ ALONG HEAD & JAMBS

    EXTENDED TO THE INSIDE

    FACE OF THE WALL

    2"x12" ROUGH BUCK

    W/ SILL GASKET

    PRESSURE TREATED

    AS SPECIFIED

    2"X4" INSIDE & OUTSIDE FACE

    TO PERMIT CONCRETE

    PLACEMENT

    DRYVIT ADHESIVE

    MIN 6:12 SLOPE ON ALL

    PROJECTING SURFACES

    DRYVIT FINISH

    EPS SHAPE

    BURIED WEB FORM UNIT

    MIN 6:12 SLOPE ON ALL

    PROJECTING SURFACES

    1/2" GYPSUM BRD.

    DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS

    THIS DETAIL ISRECOMMENDED FOR USEIN COMBUSTIBLECONSTRUCTION ONLY.

    NOTE:1. 2.

    Head/Sill - Wood Rough Buck With EPS TrimTAFS OVER ICFs

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

    ®

  • ICF 0.0.09

    COLOR PRIME™ OR DEMANDIT® ONSURFACES TO RECEIVE SEALANT

    MIN. 1/2" DRYVIT COMPATIBLE

    SEALANT AND CLOSED CELL

    BACKER ROD (TYP.)

    Head/Sill - Bucksaver Rough Buck

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    CONTINUOUS TO INSIDE FACE

    OF THE OPENING

    SEALANT

    METAL FLASHING EXTENDED

    TO INSIDE FACE OF WALL

    1/2" GYPSUM BRD.

    VINYL BUCK SYSTEM

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    TRIM VINYL BUCKSAVER BACK

    FROM OUTSIDE FACE OF THE FORM

    TO ALLOW FOAM TO DRYVIT COATING

    CONTACT

    BURIED WEB FORM UNIT

    DRIP

    EPS ATTACHED WITH

    DRYVIT AP ADHESIVE™

    DRYVIT FINISH

    DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS

    THIS DETAIL ISRECOMMENDED FOR USEIN COMBUSTIBLECONSTRUCTION ONLY.

    NOTE:1. 2.

    TAFS OVER ICFs

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

    ®

  • ICF 0.0.10

    SEALANT

    METAL FLASHING EXTENDED

    TO INSIDE FACE OF FRAMING

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    CONTINUOUS TO INSIDE FACE

    OF THE OPENING

    2"X3" INSIDE & OUTSIDE FACE

    TO PERMIT CONCRETE

    PLACEMENT

    Head/Sill - Wood Rough Buck

    BURIED WEB FORM UNIT

    DRYVIT FINISH

    DRIP

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    EPS ATTACHED WITH

    DRYVIT AP ADHESIVE™

    COLOR PRIME™ OR DEMANDIT® ONSURFACES TO RECEIVE SEALANT

    MIN. 1/2" DRYVIT COMPATIBLE

    SEALANT AND CLOSED CELL

    BACKER ROD (TYP.)

    1/2" GYPSUM BRD.

    RECESSED 2"x6" BUCK

    DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS

    THIS DETAIL ISRECOMMENDED FOR USEIN COMBUSTIBLECONSTRUCTION ONLY.

    NOTE:1. 2.

    TAFS OVER ICFs

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

    ®

  • ICF 0.0.11

    MIN. 1/2" DRYVIT COMPATIBLE

    SEALANT AND CLOSED CELL

    BACKER ROD (TYP.)

    ATTACH EPS SHAPE WITH

    VERTICAL NOTCHED TROWEL

    ADHESIVE PATTERN

    DRYVIT AQUAFLASH SYSTEM OR

    DRYVIT FLASHING TAPE™EXTENDED OVER ENTIRE SILL AND

    ONTO FRONT FACE OF VERTICAL WALL

    MIN 6:12 SLOPE ON ALL

    PROJECTING SURFACES

    Head/Sill - Flange Mount

    DRYVIT ADHESIVE

    BURIED WEB FORM UNIT

    MIN. 1/2" DRYVIT COMPATIBLE

    SEALANT AND CLOSED CELL

    BACKER ROD (TYP.)

    FLANGE MOUNT WINDOW

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    MIN 6:12 SLOPE ON ALL

    PROJECTING SURFACES

    DRYVIT COLOR PRIME™ ORDEMANDIT® ON SURFACES TO

    RECEIVE SEALANT

    DRYVIT AQUAFLASHâ SYSTEM ORDRYVIT BACKSTOPâ NT AND GRID TAPE

    ALONG HEAD & JAMBS EXTENDED

    TO THE INSIDE FACE OF THE WALL

    DRYVIT FINISH

    EPS SHAPE

    1/2" GYPSUM BRD.

    DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS

    NOTE:1.

    TAFS OVER ICFs

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

    ®

  • ICF 0.0.12

    METAL FLASHING EXTENDED

    TO INSIDE FACE OF WALL

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    CONTINUOUS TO INSIDE FACE

    OF THE OPENING

    Head/Sill - Recessed

    SEALANT

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    COLOR PRIME™ OR DEMANDIT® ONSURFACES TO RECEIVE SEALANT

    MIN. 1/2" DRYVIT COMPATIBLE

    SEALANT AND CLOSED CELL

    BACKER ROD (TYP.)

    1/2" GYPSUM BRD.

    BURIED WEB FORM UNIT

    DRYVIT FINISH

    EPS ATTACHED WITH

    DRYVIT AP ADHESIVE™

    DRIP

    DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS

    NOTE:1.

    TAFS OVER ICFs

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

    ®

  • TAFS OVER ICFs

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

    ®

    ICF 0.0.13

    2" x 4" BLOCKING FOR STEEL

    INSERT FASTENING POINT

    AS SPEC'D BY A.C.

    INSTALLATION

    PTAC SLEEVE INSERT

    AS SPEC'D

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    WRAPPED TO THE INSIDE FACE

    OF THE FRAMING

    DRYVIT COMPATIBLE SEALANT

    AND CLOSED CELL BACKER ROD (TYP.)

    DRYVIT COMPATIBLE SEALANT AND

    CLOSED CELL BACKER ROD (TYP.) WITH

    DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

    MIN. 1/2" DIMENSION BETWEEN

    ICF AND PTAC SLEEVE

    METAL FLASHING EXTENDED

    TO INSIDE FACE OF WALL

    SEALANT

    BURIED WEB FORM UNIT

    A/C Penetration

    DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS

    NOTE:1.

  • ICF 0.0.14

    ALUM. SOFFIT

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    WRAPPED OVER TOP PLATE

    DRYVIT FINISH

    BURIED WEB FORM UNIT

    2"x6" RECESSED PLATE

    ON SILL GASKET ANCHORED

    TO CONCRETE PER LOCAL

    CODE REQMT.

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    1/2" GYPSUM BRD.

    Eave Detail - Recessed Top Plate

    DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS

    NOTE:1.

    TAFS OVER ICFs

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

    ®

  • ICF 0.0.15

    ALUM. SOFFIT

    BURIED WEB FORM UNIT

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    DRYVIT FINISH

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    WRAPPED OVER TOP PLATE

    2"x12" EXPOSED PLATE

    ON SILL GASKET ANCHORED

    TO CONCRETE PER LOCAL

    CODE REQMT.

    Eave Detail - Exposed Top Plate

    1/2" GYPSUM BRD.

    DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS

    NOTE:1.

    TAFS OVER ICFs

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

    ®

  • ICF 0.0.16

    DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS

    NOTE:1.

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    WRAPPED OVER TOP OF

    CONCRETE BEARING

    BURIED WEB FORM UNIT

    STEEL ROOF FRAMING

    CONCRETE POURED

    FLUSH WITH TOP OF FORM

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    1/2" GYPSUM BRD.

    Eave Detail - Steel Roof Rafters

    ALUM. SOFFIT

    DRYVIT FINISH

    TAFS OVER ICFs

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

    ®

  • DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS

    NOTE:1.

    ICF 0.0.17

    DRYVIT COMPATIBLE SEALANT

    AND CLOSED CELL BACKER ROD

    DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

    BURIED WEB FORM UNIT

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    FLASHING FASTENED TO CONCRETE

    INSTALLED IN A WEATHERBOARD

    FASHION AS PER NATIONAL

    ROOFING CONTRACTORS

    ASSOCIATION (NRCA)

    Sloped Roof/Wall Intersection

    MIN. 3/4"

    MIN. 2 1/2"

    MIN. 4"

    2. SHINGLES SHOULD BEINSTALLED PER NRCAGUIDELINES TO OVERLAP STEPFLASHINGS AND EXTEND ALLTHE WAY TO THE VERTICALWALL

    ROOFING PAPER

    ROOF RAFTER

    DRYVIT FINISH

    TAFS OVER ICFs

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

    ®

  • DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS

    NOTE:1.

    ICF 0.0.18

    THE JOINT BETWEEN THE TWOWALLS MAY OR MAY NOT BE ASTRUCTURAL CONNECTION WITHDOWELS AS SPEC'D BY THESTRUCTURAL ENGINEER

    IT IS THE RESPONSIBILITY OF THEDESIGNER AND CONTRACTOR TODESIGN AND CONSTRUCT THEWALLS SO THE EXTERIOR FINISHOF BOTH THE ICF WALL AND THECMU WALL ARE IN THE SAMEPLANE

    DRYVIT FINISH

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    DRYVIT EIFS

    BACK WRAP EPS SECTION

    WITH MESH AND BASE COAT

    DRYVIT DEMANDIT® ORCOLOR PRIME™ ON SURFACES TO

    RECEIVE SEALANT WITH BACKER ROD

    SEE DETAIL BELOW

    3.

    2.

    DRYVIT DEMANDIT OR COLOR PRIME

    ON SURFACES TO RECEIVE SEALANT

    EXSTG. CONCRETE

    BLOCK WALL

    DRYVIT COMPATIBLE SEALANT

    AND CLOSED CELL BACKER ROD

    Transition to Existing Wall

    3/4"

    TAFS OVER ICFs

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

    ®

  • DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS

    NOTE:1.

    ICF 0.0.19

    STEEL COLUMN ANCHORED

    IN PLACE

    WOOD BLOCKING

    NELSON STUDS CAST

    INTO CONCRETE

    EPS INSERT

    BURIED WEB FORM UNIT

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    DRYVIT FINISH

    DRYVIT AP ADHESIVE™

    Transition Across Column

    1/2" GYPSUM BRD.

    PLAN VIEW

    TAFS OVER ICFs

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

    ®

  • DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS

    NOTE:1.

    ICF 0.0.20

    DRYVIT REINFORCING MESH

    EMBEDDED IN DRYVIT BASE COAT

    BURIED WEB FORM UNIT

    DRYVIT BASE COAT WRAPPED

    ONTO CONCRETE

    ROOFING AS SPEC'D

    ROOFING MEMBRANE LAPPED

    OVER PARAPET BLOCK

    Parapet Termination

    WOOD SPACER

    DRYVIT FINISH

    PARAPET CAP

    SEALANT

    MIN. 2 1/2" OVERLAP

    RETAINING CLIP

    TAFS OVER ICFs

    ©

    The architecture, engineering, and design of the project using the

    Dryvit products is the responsibility of the project's design

    professional. All systems must comply with local building codes and

    standards. This detail is for general information and guidance only

    and Dryvit specifically disclaims any liability for the use of this detail

    and for the architecture, design, engineering or workmanship of any

    project. The project design professional determines, in its sole

    discretion, whether this detail or a functionally equivalent detail is

    best suited for the project. Use of a functionally equivalent detail does

    not violate Dryvit's warranty. This detail is subject to change without

    notice. Contact Dryvit to ensure you have the most recent version.

    Dryvit Systems, Inc. 1969

    Issued: 10/2016

    ®

    Sheets and ViewsModel

    ICF TOC.pdfSheets and ViewsModel

    TAFs ICF 0.0.02.pdfSheets and ViewsModel

    TAFs ICF 0.0.03.pdfSheets and ViewsModel

    TAFs ICF 0.0.04.pdfSheets and ViewsModel

    TAFs ICF 0.0.05.pdfSheets and ViewsModel

    TAFs ICF 0.0.06.pdfSheets and ViewsModel

    TAFs ICF 0.0.07.pdfSheets and ViewsModel

    TAFs ICF 0.0.08.pdfSheets and ViewsModel

    TAFs ICF 0.0.09.pdfSheets and ViewsModel

    TAFs ICF 0.0.10.pdfSheets and ViewsModel

    TAFs ICF 0.0.11.pdfSheets and ViewsModel

    TAFs ICF 0.0.12.pdfSheets and ViewsModel

    TAFs ICF 0.0.13.pdfSheets and ViewsModel

    TAFs ICF 0.0.14.pdfSheets and ViewsModel

    TAFs ICF 0.0.15.pdfSheets and ViewsModel

    TAFs ICF 0.0.16.pdfSheets and ViewsModel

    TAFs ICF 0.0.17.pdfSheets and ViewsModel

    TAFs ICF 0.0.18.pdfSheets and ViewsModel

    TAFs ICF 0.0.19.pdfSheets and ViewsModel

    TAFs ICF 0.0.20.pdfSheets and ViewsModel