I-LINE II Catalogue 2008

download I-LINE II Catalogue 2008

of 111

description

Catalog

Transcript of I-LINE II Catalogue 2008

  • Schneider busway from 800 to 6000 A

    I-LINE II

    Catalogue 2008

  • 1Schneider Electric

    Contents

    Introduction 3

    Presentation and description 19

    Catalogue numbers and dimensions 35

    Design guide 81

    Installation guide 95

    In decentralised distribution, Schneider busway hits the high note!With Schneider busway, you play all the right notes!Schneider busway, in total harmony with the environment!Schneider busway, fortissimo throughout the range!Schneider busway, a display of advantages!Schneider busway, every one to their music!Schneider busway, hits the right notes!With the Schneider busway tools and services, let us compose your project!

    Panorama of Schneider busway rangeGeneralStraight lengthsFittingsSupports and fixingsSpecial fittingsPlug-in units

    Catalogue number coding

    I-LINE II Copper Busway (CFC)Straight lengthsStraight length componentsElbowsFlanged endsCable Tap BoxSupports and fixings

    I-LINE II Copper Contact Busway (BFC)Straight lengthsStraight length componentsElbowsFlanged endsCable Tap BoxSupports and fixings

    Plug-in units

    CharacteristicsDesigning with I-LINE II busbar trunking systemHarmonic currentsFire resistanceMeasurements and meteringDirect current

    Layout adviceHorizontal distributionRising mainsReception, handling and storageTesting and CommissioningMaintenance

    346810121617

    20262829313233

    36

    383941515455

    585961666970

    72

    828488909294

    9699100102104108

  • K9CE010102 Schneider Electric

  • K9CE01010

    PD

    2023

    82

    3Schneider Electric

    Intr

    oduc

    tion

    In decentralised distribution,Schneider busway hits the high note!

    Schneider busway on its second world tour More than 50 years of experience, with hundreds of thousands of installations in operation throughout the world. Full KEMA type test certification (IEC60439) for each and every ampere rating of busway.

    A total coordination with the Schneider Electric systemBusway is a part of a comprehensive offering of Schneider Electric products designed to operate together. This concept covers all low and medium voltage electrical distribution components. The result is an optimised electrical installation with even higher performance through full electrical, mechanical and communication compatibility.With the new range, you get a complete, tested distribution solution that complies with standards. It is perfectly suited to traditional applications (factories, warehouses, etc.) and to the distribution of electrical power from the incoming transformer on through to all types of loads in offices, commercial premises, laboratories, etc.

    Schneider Busway Guangzhou was initially set up by Square D, USA in 1997, and now is a professional busbar trunking manufacturer, product including I-LINE II and Canalis series, mainly supplying to the Asia Pacific and Middle East market.

    More than 50,000 km of Schneider busbar trunking has been sold around the world.

    Square D facility in Oxford, Ohio U.S.A. is an ISO 9001 and ISO 14001 registered busbar trunking manufacturing facility.

    Schneider Buway (Guangzhou) Ltd. is certified having ISO 9001 quality management system, ISO 14001 environment management system and OHSAS 18001 occupational health and safety management system.

    I-LINE busbar trunking system was first introduced by Square D in 1961 in its production facility in Oxford, Ohio U.S.A. As one of the major brands of the Schneider Electric, Square D has acquired worldwide recognition in a variety of busway applications.

    Dijon Factory was set up in 1972, manufacturing Canalis Busbar trunking system, ISO 9001 and ISO 14001 certified.

    Canlis Factory, Dijon, France

    Schneider Busway Factories

  • K9CE010204 Schneider Electric

    Intr

    oduc

    tion

    With Schneider busway, you play all the right notes!

    Distribution systems Schneider Electric offers different distribution systems to fit your operating needs.

    Centralised distribution

    For all continuous processes: cement plants, oil and gas, petrochemicals, steel, paper, etc. Centralised distribution offers: continuity of service, combined distribution of power, control and monitoring circuits, supervision, etc.

    Our solutions: Prisma Plus and Okken switchboards.

    Decentralised distribution

    For manufacturing industries: mechanical, textiles, lumber injection moulding, electronics, pharmaceuticals, livestock, etc. Decentralised distribution lets you: design installations without layout details, upgrade without shutting down production, get systems up and running sooner thanks to faster installation, generate savings depending on the number of loads.

    Our solutions: Prisma Plus switchboards, Schneider busbar trunking.

    Combined distribution

    Where the advantages of both centralised and decentralised distribution are required. Commercial and service buildings: offices, stores, hospitals, exhibition halls, etc. Infrastructures: airports, telecommunications, internet data centres, tunnels, etc. Industrial facilities: pharmaceuticals, food processing, etc.

    Our solutions: Prisma Plus and Okken switchboards, Schneider busbar trunking.

  • K9CE01020

    DD

    2056

    58

    5Schneider Electric

    Intr

    oduc

    tion

    With Schneider busway, you play all the right notes!

    The Schneider busway decentralised distribution concept

    Electrical power available at all points, throughout the installation.

    Exclusive features of the Schneider Electric systemTotal coordination of the Schneider Electric system provides maximum safety of life and property, continuity of service, upgradeability and ease of installation.

    Product characteristics are checked by calculations and tests carried out in our laboratories and certified in independent international recognized laboratories.

    A competitive installation.Simplicity, upgradeability, safety and continuity of service and operation.

    Savings start with installationWith plug-in points, Schneider busbar trunking reduces installation costs.Given the low cost of adding new circuits, savings increase as the number of loads increases, a natural consequence of the growth of your business.

    Upgradeable during operationIn decentralised distribution, evolving operating requirements and costs are integrated right from the start. The addition, relocation or replacement of load equipment can be carried out quickly, without de-energising the supply trunking or shutting down operation, The cost of making such changes is greatly reduced: loads are located close to supply points, plug-in points are always available, plug-in units can be reused or new ones added quickly for load relocation or replacement needs.

    Reusable in the event of major changesWhen making major modifications to your installation, the existing trunking can be easily dismantled and reused.

    Schneider busbar trunking

  • K9CE010306 Schneider Electric

    Intr

    oduc

    tion

    Schneider busway, in total harmony with the environment!

    Safety of life and property With Schneider Busway, no toxic emission in case of fireThe busbar trunking has a low combustible load. Its construction uses very little consumable material and is halogen free.In the event of a fire, the busbar trunking does not emit any gas or toxic smoke.

    The busbar trunking helps prevent the propagation of a fire through partition walls and floors.

    Halogen-sensitive applications Public buildings (infrastructures, hospitals, schools, etc.), Buildings with evacuation difficulties (high-rises, ships, etc.) and service-activity buildings, Sensitive processes (production of electronic components, etc.).

    Schneider Busway contains no PVCsWhen PVCs burn, they produce large amounts of smoke that can be a serious safety hazard. Reduced visibility: risk of panic, complicates rescue work, Smoke toxicity: hydrogen chloride gas (highly toxic), carbon monoxide (danger of asphyxiation).

    Schneider Busway reduces the risk of exposure to electromagnetic fieldsAccording to the WHO (World Health Organisation), exposure to electromagnetic fields can be a health hazard starting at levels as low as 0.2 micro-Teslas and could represent a long-term risk of cancer. Some countries have created standards that stipulate limits

    All electrical conductors generate magnetic fields proportional to the distance between them. The design of Schneider busbar trunking with tightly spaced conductors in a metal enclosure helps to considerably reduce radiated electromagnetic fields.The electromagnetic field characteristics of Schneider busbar trunking are well-defined and measurements show that they are far below potentially dangerous levels.

    Example:Consequences of a fire in a 100 m2 office with electrical distribution by cables.200 kg of cables (i.e. 20 kg of PVC) produces: 4400 m3 of smoke, 7.5 m3 of hydrochloric acid, 3.7 kg of corroded steel.

    Health

  • K9CE01030 7Schneider Electric

    Intr

    oduc

    tion

    Schneider busway, in total harmony with the environment!

    Environment Schneider Busway is fully recyclable Schneider Busway busbar trunking can be reused.Schneider Busway busbar trunking is designed for a long service life and can easily be dismantled, cleaned and reused. All packaging materials can be recycled (cardboard or recyclable polyethylene film). All Schneider Busway products are designed for safe end-of-life recycling. PVC, on the other hand, requires neutralisation of the hydrochloric acid produced using lime and generates dioxins that are extremely toxic.

    Schneider Busway helps conserve natural resourcesThe depletion of raw materials (copper, plastics, etc.) is one of our ongoing concerns. For this reason, we have optimised the used of all materials used to make our busbar trunking: Reduction of dangerous or polluting materials. Reduction in the weight of insulating materials, Reduction in the use of plastics for improved fire performance: less energy released during combustion, thereby limiting propagation and facilitating extinction (lower calorific value).

    Example:1 kg of PVC generates 1 kg of waste.

    Conservation of natural resources

    Schneider Busway reduces your line losses by 20 %Schneider Busway divides your consumption of plastic by a factor of fourThe cost of an electrical installation includes the initial investment for the equipment and its installation, the cost of maintenance and the cost of energy losses during operation.The concept of decentralised distribution is a way to merge all the circuits in one and thus to reduce to the maximum the low cross-section lengths and the weight of insulating materials.

    Example: 34m of 250A Schneider busbar trunking eqipped with 7 sets of 25A load.

  • K9CE01040

    Application1. Transformer/ Switchboard connection2. Horizontal distribution, from the substation to the loads in workshop3. Vertical distribution, from the substation to the loads of each high rise floor4. Lighting application, in Park place, supermarket, exhibition center, metro ect.

    1

    2

    3

    4

    PD

    2023

    84

    8 Schneider Electric

    Intr

    oduc

    tion

    Schneider busway, fortissimo throughout the range!

  • K9CE01040

    1 2

    3 4

    Lighting application

    Horizontal distribution

    Vertical distribution

    Transformer/ Switchboard connection

    9Schneider Electric

    Intr

    oduc

    tion

    Schneider busway, fortissimo throughout the range!

  • K9CE0201010 Schneider Electric

    Intr

    oduc

    tion

    Schneider busway, a display of advantages!

    The compact size of Schneider busway means it takes up very little space in the building: used as a rising main, it takes up only a minimum of space, used for horizontal distribution, it fits easily into the buildings structure (false floors, false ceilings, service shafts, etc).

    Changes in direction have been designed to optimise the space taken up, contrary to an equivalent installation using cables which requires large bending radii.

    Tap-off units, complete with protective devices, are fitted along the entire length of the busbar trunking thus reducing the floor area taken up by the electrical distribution switchboards.

    A compact solution

    A simple and economical system

    The design study is easy to perform as it does not require a detailed layout of each load. Equipment choice is pre-determined and optimised.

    Installing the busbar trunking requires 2 or 3 people only, for a time equivalent to that for installing cableways. The time normally needed for laying cables is therefore saved.

    Connection to the MV/LV substation is made using a quick fitting joint block. The plug-in units can be prepared in the workshop thus reducing on-site time. Their connection to the busbar trunking is done in a single plugging-in operation.For those ratings more than 500A, it is done by bolt-on operation.

    Installing busbar trunking lengths can be done as and when building work progresses, thus optimising on-site work and allowing possible unexpected events to be anticipated in advance.

    It is also important to note that busbar trunking is a factory tested solution, meaning the time needed for inspecting connections is reduced (visual inspection of tightening torque).

  • K9CE02010 11Schneider Electric

    Intr

    oduc

    tion

    Complete safety Busbar trunking temperature rise and short-circuit withstand are known and independent of the installation. Coordination of the Schneider Electric system results in complete control of the electrical network.

    Installation standards IEC 60 364 chapter 5.523.6 stipulate that above 4 parallel cables, it is preferable to use busbar trunking. Paralleling many cables leads to uneven distribution of currents and the risk of abnormal temperature rise.

    The busbar trunking and plug-in units are designed to guarantee the safety of personnel and equipment: Fully silver-plated cooper contact solution. bolted connections with tightening torque guaranteed by torque nuts. foolproof system to avoid the risk of assembly errors.

    Its metal enclosure and high protection degree protect the busbar trunking from all external aggressions (corrosion, rodents, etc).

    Operating continuity

    Seismic Compliance

    When working on the electrical installation, the busbar trunking provides immediate readability of the electrical circuit thus allowing the appropriate zone to be quickly identified.Plug-in units(

  • K9CE02020

    Key projectsPentronas Towers (Malaysia)Hong Kong International Financial Center (Hong Kong)Shanghai Jin Mao Building (China)Emirates Palace (UAE)Grand Indonesia Building (Indonesia)Dubai International Finance Center (UAE)Al Shira'a Tower (Kuwait)Beverly Hill Tower (Qatar)Al Safwa Tower (Saudi Arabia)Robinson Cybergate Center Tower (Philippines)Mita Koyamacho High-rise Apartment (Japan)International Commerce Centre (Hongkong)

    Congresss Conference Building (Egypt)......

    Key projectsCarrefour supermarket(World wide)

    Guangzhou International Exhibition Centre(China) Convention & Exhibition Centre(Hong Kong)Asia World Expo(Hong Kong)Central World Mall(Thailand)Siam paragon (Thailand)Abu Dhabi National Exhibition Center( UAE)Mall of Arabia (Saudi Arabia)Melbourne Convention Centre (Australia)Mall of the Emirates (UAE)National Convention Centre (Vietnam)Queensgate shopping Mall (New Zealand)

    National Olympic Stadium (Guangzhou, China)Panda Distribution Facility (Saudi Arbia)Las Vegas Sands (Macau)......

    12 Schneider Electric

    Intr

    oduc

    tion

    Schneider busway, everyone to their music!

    Key points

    Fire barrier.

    Halogen free.

    Small size.

    Operating continuity.

    Office and Hotel buildings

    Key points

    Halogen free.

    Distribution and metering.

    Able to be evolved.

    Sprinklers.

    Shopping centres and Exhibition centres

  • K9CE02020

    Key projectsGeneral Motors (World wide)Hitachi Semiconductor manufacturing (China)Chartered Semiconductor manufacturing (Singapore)Maruti Suzuki (India)

    Jabil Plant (India)Nikon Factory (Thailand)

    Intel Plant (Malaysia)Infineon Plant (Malaysia)

    Bosch (Korea)Seagate Factory (Singapore)ST Microelectronics (Singapore)Ansell Lanka (PVT) Limited (Sri Lanka)......

    Key projectsBank of China Tower (Hongkong)

    China Construction Bank (China)

    Citibank Hongkong (Hong Kong)

    Maybank (Malaysia)

    Commercial Bank (Qatar)

    Saudi Telecom Company (Saudi Arabia)Bharti data Centre (India)HSBC Bank HQ (Babrain)......

    13Schneider Electric

    Intr

    oduc

    tion

    Schneider busway, everyone to their music!

    Key points

    Operating continuity.

    Able to be evolved.

    Low voltage drops.

    Network readability.

    Industry buildings

    Key points

    Operating continuity.

    High tap-off density.

    Able to be evolved.

    Network compactness and readability.

    Data centers and Banks

  • K9CE02020

    Key projectsThree Gorges Power Station(China)Wind Farm(China)ExxonMobil Chemical plant(Malaysia) Hysco Steel(India)Shell Chemical plant (Malaysia)Petro Rabigh(Saudi Arabia) ......

    Key projectsBeijing Capital New International Airport(China)Suvarnabhumi Airport (Thailand)

    Tan Son Nhat Airport(Vietnam)India Ahmedabad Airport(Inida)Cairo Airport(Egypt)Dubai Airport(UAE)Jebel Ail Airport(UAE)......

    Schneider Busway, everyone to their music!

    Key points

    Operating continuity.

    Able to be evolved.

    Low voltage drops.

    Network readability.

    Energy

    Key points

    Halogen free.

    Distribution and metering.

    Able to be evolved.

    Sprinklers.

    Airport

    PD

    2023

    91P

    D20

    2387

    14 Schneider Electric

    Intr

    oduc

    tion

  • K9CE02020

    Key projectsThe first affiliated Hospital, Guangzhou(China)Angkor International Hospital(Thailand)Al-Maidan Hospital(Kuwait)Beijing 301 Hospital(China)Mina Hosptital (Saudi Arabia)Dammam Hospital (Saudi Arabia)......

    Key projectsGuangzhou Metro(China)Singapore Metro

    Madrid Metro (Spain)

    London Metro (UK)

    ......

    Schneider Busway, everyone to their music!

    Key points

    Fire barrier.

    Halogen free.

    Small size.

    Operating continuity.

    Hospital

    Key points

    Halogen free.

    Distribution and metering.

    Able to be evolved.

    Sprinklers.

    Metro

    PD

    3950

    77-6

    8

    15Schneider Electric

    Intr

    oduc

    tion

  • K9CE0204016 Schneider Electric

    Intr

    oduc

    tion

    Schneider busway, hits the right notes!

    IEC Certification ASTA / ASEFA /KEMA / IECEE / CNAL UL Certification CCC approved ISO 9001, ISO14001 OHS18001 Six Sigma Program

    Quality - Accreditations

  • K9CE02040

    PD

    2023

    96

    17Schneider Electric

    Intr

    oduc

    tion

    With the Schneider busway tools and services, let us compose your project!

    Work-out your solution together

    Our teams are available to provide customers with technical assistance throughout the installation of their projects.

    Design of electrical distribution architectures: design of decentralised transport and distribution systems, technical and financial optimisation of busbar trunking design projects, transformer / switchboard link, installation coordination and discrimination.

    Full installation drawings: 3D drawings with corresponding parts lists, 2D drawing with dimensions, detailed connection drawings.

    Site supervision and commissioning assistance.

    Training for designers and contractors.

    Project launch

    Technical support

    BRASS drawing

    Autocad drawing

    Production

    Project management

    On-site instruction and installation

    After-sales service

  • K9CE02040

    Horizontal distribution

    Vertical distribution

    18 Schneider Electric

    Intr

    oduc

    tion

    With the Schneider busway tools and services, let us compose your project!

    Schneider Electric offers a comprehensive design software.The BRASS software, edited by Schneider Electric, was developed to help you design I-LINE II busbar trunking runs.

    BRASS, a comprehensive toolThe BRASS software allows you to quickly design the best layout for your project.It allows: the material needed to be easily chosen a list of catalogue numbers and their exact quantities to be defined

    BRASS gives you all the help you need

    State-of-the-art softwareThe advanced BRASS design software enables you design from the routing to component detail in a more accurate, convenient and quicker way.

  • K9CE02040 19Schneider Electric

    Presentation 20Panorama of Schneider Busway range 20Lighting distribution 20Power distribution 22

    I-LINE II from 800 to 6000 A 24

    Description 26

    General 26

    Straight lengths 28

    Fittings 29

    Supports and fixings 31

    Special fittings 32

    Plug-in units 33

    Presentation and description

    Pres

    enta

    tion

    Des

    crip

    tion

  • K9CE1100020 Schneider Electric

    Pres

    enta

    tion

    Presentation

    Canalis

    Panorama of Schneider Busway rangeLighting distribution

    Range Canalis KDP Canalis KBA Canalis KBB

    Run componentsDegree of protection IP55 IP55 IP55Number of circuits 1 1 1 or 2Rating 20 A 25 and 40 A 25 and 40 ATap-off intervals 1200 - 1350 - 1500 - 2400 - 2700 and 3000 mm 500 - 1000 and 1500 mm 500 and 1000 mmStandard lengths 24 and 192 meters 2 and 3 meters 2 and 3 metersFinish - Galvanised steel Galvanised steelMaximum distance between fixing points 0,70 meter 3 meters 5 meters

    KDP-KBA-KBB tap-off units

    Rating 10 and 16 A 10 and 16 A 10 and 16 A

  • K9CE11000 21Schneider Electric

    Pres

    enta

    tion

    Panorama of Schneider Busway rangeLighting distribution

    Range Canalis KDP Canalis KBA Canalis KBB

    Run componentsDegree of protection IP55 IP55 IP55Number of circuits 1 1 1 or 2Rating 20 A 25 and 40 A 25 and 40 ATap-off intervals 1200 - 1350 - 1500 - 2400 - 2700 and 3000 mm 500 - 1000 and 1500 mm 500 and 1000 mmStandard lengths 24 and 192 meters 2 and 3 meters 2 and 3 metersFinish - Galvanised steel Galvanised steelMaximum distance between fixing points 0,70 meter 3 meters 5 meters

    KDP-KBA-KBB tap-off units

    Rating 10 and 16 A 10 and 16 A 10 and 16 A

    Presentation

    Canalis

    Panorama of Schneider Busway rangeLighting distribution

  • K9CE1100022 Schneider Electric

    Pres

    enta

    tion

    Presentation Panorama of Schneider Busway rangePower distribution

    Canalis

    Range Canalis KS Canalis KS rising mains I-LINE II Copper busway I-LINE II Copper contact busway

    Run componentsDegree of protection IP52/54 IP52/54 IP40 / 54 / 55 / 65 / 66 IP40 / 41 / 54 / 65 / 66Polarity 3L + N + PE 3L + N + PE 3L + N+PE / 3L+ PE ; 3L + N+PE / 3L+ PE ; Rating 100, 160, 250, 400, 500, 630, 800 100, 160, 250, 400, 500, 630, 800 800 - 6000A 800 - 5000ATap-off intervals 1000 mm on each face 500 mm 610mm/1220mm 610mm/1220mmStandard lengths 3 and 5 meters Defined by the floor pitch 10 Feet 10 FeetFinish White RAL 9001 White RAL 9001 ANSI 49 ANSI 49Maximum distance between fixing points 3 meters Defined by the floor pitch 10Ft 10Ft

    Tap-off units

    Rating Plug-in 25 to 400 A 25 to 400 A 15 to 500 A 15 to 500 ABolt-on 630A to 1600 A 630A to 1600 A

  • K9CE11000 23Schneider Electric

    Pres

    enta

    tion

    Presentation Panorama of Schneider Busway rangePower distribution

    I-LINE II

    Range Canalis KS Canalis KS rising mains I-LINE II Copper busway I-LINE II Copper contact busway

    Run componentsDegree of protection IP52/54 IP52/54 IP40 / 54 / 55 / 65 / 66 IP40 / 41 / 54 / 65 / 66Polarity 3L + N + PE 3L + N + PE 3L + N+PE / 3L+ PE ; 3L + N+PE / 3L+ PE ; Rating 100, 160, 250, 400, 500, 630, 800 100, 160, 250, 400, 500, 630, 800 800 - 6000A 800 - 5000ATap-off intervals 1000 mm on each face 500 mm 610mm/1220mm 610mm/1220mmStandard lengths 3 and 5 meters Defined by the floor pitch 10 Feet 10 FeetFinish White RAL 9001 White RAL 9001 ANSI 49 ANSI 49Maximum distance between fixing points 3 meters Defined by the floor pitch 10Ft 10Ft

    Tap-off units

    Rating Plug-in 25 to 400 A 25 to 400 A 15 to 500 A 15 to 500 ABolt-on 630A to 1600 A 630A to 1600 A

  • K9CE1150024 Schneider Electric

    Pres

    enta

    tion

    Run sections Plug-in units Elbow Fittings Connection fittings Fixing supports

    Rating: 12 ratings are available, from 800A to 6000A Standard length: 10 feet, 6 feet, 4 feet None-standard length: minimum length 406mm

    All I-LINE plug-in units are compatible with I-LINE II busbar trunking system Category: plug-in unit with MCCB, plug-in unit with fusible switch Plug-in unit with Merlin Gerlins MCCB, ampere rating from 15A to 1000A Plug-in unit with Square Ds MCCB, ampere rating from 15A to 1600A Plug-in unit with fusible switch, ampere rating from 30A to 1600A

    Standard elbow: Flatwise elbow Edgewise elbow Non-standard elbow: Double elbow Offset elbow Elbow plus flanged end Elbow in special angle Elbow in special length

    Supply connections allow the busbar trunking to be connected to the switchboards busbar or to the transformer. Flanged end Qwik Flanged end cable connection, transport current between cable and busbar trunking. End cable tap box Center cable tap box

    Vertical support Fix hanger Spring hanger Horizontal support Flatwise hanger Edgewise hanger

    I-LINE II from 800 to 6000 AHigh Power transport and distribution

    Presentation

    I-LINE II

  • K9CE11500 25Schneider Electric

    Pres

    enta

    tion

    Run sections Plug-in units Elbow Fittings Connection fittings Fixing supports

    Rating: 12 ratings are available, from 800A to 6000A Standard length: 10 feet, 6 feet, 4 feet None-standard length: minimum length 406mm

    All I-LINE plug-in units are compatible with I-LINE II busbar trunking system Category: plug-in unit with MCCB, plug-in unit with fusible switch Plug-in unit with Merlin Gerlins MCCB, ampere rating from 15A to 1000A Plug-in unit with Square Ds MCCB, ampere rating from 15A to 1600A Plug-in unit with fusible switch, ampere rating from 30A to 1600A

    Standard elbow: Flatwise elbow Edgewise elbow Non-standard elbow: Double elbow Offset elbow Elbow plus flanged end Elbow in special angle Elbow in special length

    Supply connections allow the busbar trunking to be connected to the switchboards busbar or to the transformer. Flanged end Qwik Flanged end cable connection, transport current between cable and busbar trunking. End cable tap box Center cable tap box

    Vertical support Fix hanger Spring hanger Horizontal support Flatwise hanger Edgewise hanger

    I-LINE II

    I-LINE II from 800 to 6000 AHigh Power transport and distribution

    Presentation

  • K9CE1200026 Schneider Electric

    Des

    crip

    tion

    Description

    The I-LINE II busbar trunking is intended for high power distribution and transport in industrial, commercial and tertiary buildings. Assembly of prefabricated sections that adapt to all run configurations.

    General

    Straight Length

    Joint Pak

    I-LINE II

    12 ratings are available, from 800A to 6000A Silver plated copper contact Conductors full-length insulated using Mylar film, class B, 130C Available polarities: 3L +PE, 3L +N+PE Maximum rated voltage: 1000 Volts Insulation voltage: 1000 Volts

    Compact Size, Sandwich Structure, totally enclosed housing Universal Installation, no need to consider de-rating factor, regardless of the mounting position. The accumulation of dirt on exposed bus bars and possibility of accidental contact with bus bar are greatly reduced. No Chimney effectContinuous air spaces inside I-line busway housing are closed off with special barriers to help prevent the spread of smoke and gases in the event of a fire in the area of the busway installation. This standard internal barrier allows busway to extend through wall or floors without creating open space for a chimney effect fire path. Improve systems ventilation, satisfy higher ampere rating Less space required for installation, investment saving

    The I-LINE II busbar trunking is suitable for applications containing harmonics by taking into account the appropriate derating factor. See Harmonic currents in the Design guide.

    Joint-Pak is standard on I-LINE II system. It allows for quick removal of lengths from the busbar trunking runs for load shifting or maintenance. It also can be removed and relocated on the opposite end of the length for the last minutes job changes Single bolt connection makes installation faster Belleville washer provides equal pressure across the complete joint contact area to assure proper electrical contact Double, Silver plated surface contact ensure a good current continuity. Adjustable range: +/- 3mm

    VIST-TITE BoltThe double head design, introduced by Square D in 1967, allows the customer to tighten the joint to the proper torque using a standard spanner. The outer head will break off when the correct torque is achieved. A second bolt head remains to allow for joint maintenance or busbar relocation. No need to purchase a replacement bolt. For maintenance of the joint or when busway is relocated, the VISIT-TITE bolt should be tightened to 70 lb-ft (95Nm) with a torque wrench

    Electro-galvanized steel, better anti-corrosion. Paint: Epoxy electrostatic powder finish Color: ANSI 49 gray, special color are optional upon customers request.

    Housing

  • K9CE12000 27Schneider Electric

    Des

    crip

    tion

    GeneralDescription

    I-LINE II

    Earthing Bus

    I-line II is furnished with the integral earthing bus as standard. The earthing bus is the bus housing itself and completely encloses the bus sandwich. It is rated at 50% capacity. The earthing bus is Continuous bonding between top and bottom bus.

    Internal Aluminum/copper earthing bus is optional.

    Schneider believes an earthing conductor is extremely important, to provide the maximum amount of protection for a distribution system in todays ever expanding electrical systems. With our design, we have given the maximum amount of protection in an economical package.

    Conductor

    Copper (Copper busway) 99.97% purity of copper Silver plated copper in full length minimize surface oxygenation, assure low surface contact resistance and low voltage drop

    Insulation

    Two layers surrounding each bus bar Class B, 130C, Vendor certified polyester film (DuPont Mylar) Excellent dielectric performance Over 40 years of application record without failure Class F is optional upon request Halogen free, safe in fire

    Degree of Protection

    Schneider offers the I-LINE II bus bar trunking system in a variety of housing constructions to meet your application and needs.

    Feeder type IP40-IP66Riser type IP40-IP54 Plug-in type IP40-IP54

    Aluminum with copper contact (Copper contact busway) Use silver-plated Bi-metal cladding on Aluminum conductor through high current and high pressure. Special process enabling molecular fusion of Copper and Aluminum through the use of very high pressure and temperature. All of connection zone are silver to silver.

    Integral Earth Bus Internal Earth Bus

  • K9CE1200028 Schneider Electric

    Des

    crip

    tion

    FeederTransport the current without plug-in opening. All straight lengths and fittings of feeder trunking are fully compatible, rating for rating, with straight lengths of plug-in trunking. 12 ratings are available, from 800A to 6000A Minimum length 406 mm Polarity: 3L+N+PE, 3L+PE system 100% neutral capacity, 50% earth bus capacity

    Straight lengthsDescription

    Straight section

    RiserPlug-in opening (PIO) on one side, only 4, 6, 10ft available

    Maximum 2 PIO for 6 feet riser element

    Maximum 4 PIO for 6 feet plug-in element

    Maximum 1 PIO for 4 feet riser element

    Maximum 2 PIO for 4 feet plug-in element

    Maximum 3 PIO for 10 feet riser element

    Maximum 6 PIO for 10 feet plug-in element

    Plug-inPlug-in opening on both sides, only 4, 6, 10ft available

    I-LINE II

    N N N

    N N N

    N NNN

    N NNN

    N

    N

  • K9CE12000 29Schneider Electric

    Des

    crip

    tion

    FittingsDescription

    I-LINE II

    Simple changes of direction

    Changes of direction

    Elbows - Types LF, LE and T

    Double elbows - Types OF, OE DR and DL

    type OE, edgewise offset

    type DR, double right elbow

    type DL, double left elbow

    type OF, flatwise offset

    to go up or down, to turn right or left Standard angle: 90 Special angles : 91- 179

    flat or edgewise, to move the run ais upwards, downwards, to the right or to the left without having to bend the busbar trunking:

    type LE, edgewise elobw

    type T, flatwise tee

    type LF, flatwise elobw

  • K9CE1200030 Schneider Electric

    Des

    crip

    tion

    FittingsDescription

    I-LINE II

    Connetions to swithboards and transformers

    Connetions to cable

    Type FE, standard flanged end

    Type QF, qwik flanged end

    type LEFE, edgewise elbow plus flanged end

    type LFFE, flatwise elbow plus flanged end

    type ETB, end cable tap box

    type CTB, center cable tap box

    Cable Tap Box cable connection , transport current between cable and busbar trunking

    Flanged ends - Type FEThey allow the busbar trunking to be connected to a switchboards busbar, or to the terminals of an transformer, generator set, etc.

    They come complete with a mounting plate fitted: either directly to the roof of the switchboard, or via the intermediary of a protective cover.

    Vertical or horizontal incoming busbar trunking.

  • K9CE12000 31Schneider Electric

    Des

    crip

    tion

    I-LINE II

    Supports and fixingsDescription

    Horizontal Supports

    Vertical Supports

    The horizontal type hanger allow the busbar trunking to be fixed and ajusted along its length, as well as absorbing its movements.

    The spring hanger has the following advantages:.

    Fix hanger

    Spring hanger

    spring adjustment to ensure distribution of the load at each floor avoids the transmission of buiding forces to the busbar trunking (expansion and vibration)

    type HFF, flatwise hanger

    type HFE, edgewise hanger

    type HFVS1, spring hanger

    type HFV, fix hanger, for all ratings.

    type HFVS2, spring hanger

    type HFVS8, spring hanger

  • K9CE1200032 Schneider Electric

    Des

    crip

    tion

    I-LINE II

    Special fittingsDescription

    Reducer

    Expansion Joint

    An Expansion Fitting should be used under the following conditions: whenever a busway run crosses a building expansion; when a long straight run of busway does not contain any elbows or both ends of the run ar fixed. No need for riser 38mm expansion allowable more detail in page 99

    Connect the high power and low power run Best way to save investment Standard reducer is non-fusible, reducer with fuse/MCCB is optional

    The end closure protects and insulates the conductor ends and is fitted to the last section.

    End closure

    Connection accessory

    type EJ, absorb horizontal expansion

    type R

    Flexible linkfor the connection between the conducting plates, to reduce the vibration from the transformer.

    Connection platesthe conductors of flanged ends are connected via connection plates to the switchboard busbars.

  • K9CE12000 33Schneider Electric

    Des

    crip

    tion

    Plug-in UnitsDescription

    I-LINE II

    CompatibilityAll plug-in units are compatible with I-LINE II busbar trunking system, regardless whether they bear MCCB or fusible switch.

    Plug-in device mountingPlug-in units are positioned along the busbar trunking length by notches in the busbar trunking housing top which accept the mounting hooks of the plug-in unit. This aligns the plug-in unit jaws with the plug-in opening. After the unit is positioned on the busway, it is allowed to swing down into the plug-in opening where the plug-in jaws make contact with the bus bars. This is accomplished in hook-swing.

    Plug-in JawsThe plug-in jaws contact to the bus bars directly with the silver plated cooper contact. The contact surface is fully silver plated to ensure a proper contact force and low contact resistance.

    EarthingEarthing established at first and switched off at last as to protect worker against electrical contact shock.All plug-in devices incorporate an earthing spring which cuts through the paint and forms an equipment earth between the housing and the body of the device before the phase jaws make contact with the busbars.

    Interlock30 A to 250 A plug-in devices are interlocked with the busway housing to prevent installation or removal of the unit when the disconnect is turned ON.All devices incorporates an interlock to prevent the door over the disconnect from being opened when the unit is ON. This door interlock can be defeated from outside the unit.

    Operating handleThe side operating handle in the PIU makes the heavy duty switch more convenient and safer. When the PIU is installed in the high position, you can easily operate the PIU on the group by the side handle.

    Protection functionSchneider Plug-in unit equipped with Schneider original protection unit, which can provide complete overload protection, short circuit protection and earthing malfunction protection. The maximum interrupting is 150KA.

    Transparent shield over Line side parts - that means safety & visible

    Product features of I-LINE II Plug-in Unit

  • K9CE1200034 Schneider Electric

    Des

    crip

    tion

    Plug-in Units

    I-LINE II

    Description

    Category of I-LINE Plug-in unit Plug-in Unit with Merlin Gerlins MCCB, ampere rating from 15A to 1000A Plug-in Unit with Square Ds MCCB, ampere rating from 15A to 1600A Plug-in with Fusible Switch, ampere rating from 30A to 1600A

    Plug-in Unit with Merlin Gerins MCCB Plug-in typePNS (15-250A), PBNS (350-500A) Bolt-on typePTNS (630-1000A) (different for horizontal/vertical mounting) Fitted with Compact NSEN/ NSES/ NSEH/ NSD / NSN / NSH / NSL(on request) available for 3-pole and 4 pole configurations available for earth leakage current protection (Vigi)

    Plug-in unit with Square D MCCB Plug-in typePF(15-100A), PK(125-250A), PB(250-400A) Bolt-on typePT(500-1600A) (different for horizontal/vertical mounting) 3 Poles only PIU enclosure not interchangeable with PIU enclosure for MG breaker

    Plug-in unit Square D Fusible Plug-in typePQ(30-200A), PS(125-250A), PBQ(250-400A) Bolt-on typePTQ(500-1600A) (different for horizontal/vertical mounting) equipped with UL/IEC fuse base

    Category of I-LINE Plug-in Unit

    Plug-in Unit with Merlin Gerins MCCB

    Plug-in Unit with Square Ds MCCB

    Plug-in Unit with Square D fusible breaker

  • K9CE20000 Schneider Electric 35

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Catalogue numbers and dimensions

    Catalogue number coding 36

    I-LINE II Copper Busway (CFC) Straight lengths 38Straight length components 39Elbows 41Double elbows 43Offset elbows 44Elbow plus flanged end 45Internal Grounding Elbows 46Flanged ends 51Cable Tap Box 54Supports and fixings 55

    I-LINE II Copper Contact Busway (BFC) Straight lengths 58Straight length components 59Elbows 61Double elbows 63offset 64Elbow plus flanged end 65Flanged ends 66Cable Tap Box 69Supports and fixings 70Plug-in units 72

  • K9CE20000Schneider Electric36

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Catalogue-number coding

    Catalogue Numbering System Generic v Discrete

    Catalogue-number composition (I-LINE II Copper Busway)

    One letter designating the application.Busbar material CodeCopper CType CodeFeeder FRiser plug-in RPlug-in PStandard CodeIEC CI-LINE II 2Polarity Code3L + PE 33L + N + IGB (integral earth) 53L + N + ING (internal earth) 6Rating Code800 081000 101250 121350 131600 162000 202500 253000 303200 324000 405000 506000 60Type of PE CodeAL GCU GGDimension of component Two letters identifying the type of component.Type CodeGeneric CodeElbow ELFlange End FEQwik Flange End QFExpension Joint EJEnd Tap Box ETBCenter Tap Box CTBFlat Tee TUnfused Reducer RDiscrete CodeEdgewise Elbow LEFlatwise Elbow LFEdgewise Offset Elbow OEFlatwise Offset Elbow OFDouble Left Elbow DLDouble Right Elbow DRFlange End Edgewise Elbow LEFEFlange End Flatwise Elbow LFFEFlange End - Double left FEDLFlange End - Double right FEDRStraight Length - Feeder/Plug-in/Riser STPhase Transition PTDegree of Pretection CodeIP40 --IP54 M54IP55*** M55IP65*** M65IP66*** M66*** Available for feeder system only

    Catalogue numbers and dimensions

    CC2GM

    Generic catalogue # describes all the features of busway (e.g. copper, ampere rating, IP rating, 3/4 poles etc except length. Hence it is not for describing individual pieces of busway but rather for quotation/contract/invoicing purposes. The unit is 1 piece (for fittings) or 1 feet (straights)

    Discrete catalogue # describes all the features of busway including length of the individual pieces. With the discrete catalogue number itself, it tells the detailed length of busway and is sufficient enough for production purposes. We also call this as BOM (Bill of Materials)

    I-LINE II Copper Busway

  • K9CE20000 Schneider Electric 37

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Catalogue-number coding

    Catalogue Numbering System Generic v Discrete

    Catalogue-number composition (I-LINE II Copper Contact Busway)

    Catalogue numbers and dimensions

    BC2GM

    I-LINE II Copper Contact Busway

    One letter designating the application.Busbar material CodeBimetal BType CodeFeeder FRiser plug-in RPlug-in PStandard CodeIEC CI-LINE II 2 One digit indicating the trunking polarityPolarity Code3L + PE 33L + N + IGB (integral earth) 5Rating Code800 081000 101250 121350 131600 162000 202500 253200 324000 405000 50Type of PE CodeAL GDimension of component Two letters identifying the type of component.Type CodeGeneric CodeElbow ELFlange End FEQwik Flange End QFExpension Joint EJEnd Tap Box ETBCenter Tap Box CTBFlat Tee TUnfused Reducer RDiscrete CodeEdgewise Elbow LEFlatwise Elbow LFEdgewise Offset Elbow OEFlatwise Offset Elbow OFDouble Left Elbow DLDouble Right Elbow DRFlange End Edgewise Elbow LEFEFlange End Flatwise Elbow LFFEFlange End - Double left FEDLFlange End - Double right FEDRStraight Length - Feeder/Plug-in/Riser STPhase Transition PTDegree of Pretection CodeIP40 --IP54 M54IP55*** M55IP65*** M65IP66*** M66*** Available for feeder system only

  • K9CE2102038 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Catalogue numbers and dimensions

    Straight feeder lengths

    Straight lengths

    Type Length Cat. no.

    3L + PE 3L + N + IGB 3L + N + INGFixed 10 Feet CFC23G10STM CFC25G10STM CFC26GG10STM

    Made to measure 16 inches ~119 inches CFC23G**STM CFC25G**STM CFC26**GG**STM

    Straight lengths with plug-in openings

    Type Length N u m b e r o f opening

    Cta.no

    3L+PE 3L+N+IGB 3L+N+ING

    Plug-in 4 feet 12 CPC23G4S2M CPC25G4S2M CPC26GG4S2M

    6 feet 12 CPC23G6S2M CPC25G6S2M CPC26GG6S2M

    22 CPC23G6S4M CPC25G6S4M CPC26GG6S4M

    10 feet 12 CPC23G10S2M CPC25G10S2M CPC26GG10S2M

    22 CPC23G10S4M CPC25G10S4M CPC26GG10S4M

    32 CPC23G10S6M CPC25G10S6M CPC26GG10S6M

    Riser 4 feet 11 CRC23G4S1M CRC25G4S1M CRC26GG4S1M

    6 feet 11 CRC23G6S1M CRC25G6S1M CRC26GG6S1M

    21 CRC23G6S2M CRC25G6S2M CRC26GG6S2M

    10 feet 11 CRC23G10S1M CRC25G10S1M CRC26GG10S1M

    21 CRC23G10S2M CRC25G10S2M CRC26GG10S2M

    31 CRC23G10S3M CRC25G10S3M CRC26GG10S3M

    Trunking cross-section

    Rating (A) Type 800 1000 1250 1350 1600 2000 2500 3000 3200 4000 5000 6000

    Weight

    (kg/m)

    3L + PE Feeder 14.8 18.0 20.5 25.0 27.2 31.4 43.3 57.6 63.5 70.3 87.9 108.9

    Plug-in 17.3 21.1 23.7 28.1 30.4 34.5 46.5 60.7 65.2 76.1 91.1 111.2

    3L + N + IGB Feeder 17.8 21.7 24.9 31.0 33.9 40.9 58.1 71.0 76.9 87.6 108.0 134.8

    Plug-in 20.3 24.8 28.0 34.1 37.1 44.0 61.2 74.1 80.1 93.9 111.2 137.9

    3L + N + ING Feeder 20.4 24.3 27.9 34.9 38.2 45.9 65.3 79.0 85.8 98.1 119.8 150.4

    Plug-in 22.9 27.4 31.0 38.0 41.4 49.0 68.4 82.1 89.0 104.4 123.0 153.5

    W(mm) 98 98 110 136 148 171 237 323 387 412 599 638

    Figure A A A A A A A B B B C C

    OrderingComplete the catalogue number by replacing by the rating and protection degree.

    Example: Generic catalogue number of 1000A straight feeder, 3L+N+PE : CFC2510GM54

    Discrete catalogue number of a 10feet 1000A straight feeder, 3L+N+PE.CFC2510G10STM54

    Rating

    Rating **

    Protection degree

    Protection degree

    I-LINE II Copper Busway

    (1) See the Trunking cross-section table below.

    **= the length of the straight feeder. If the number is larger than 10, the unit is inch. otherwise, the unit is feet.

  • K9CE21020

    ABCN

    NCBA

    DD

    2108

    07

    DD

    2108

    08

    DD

    2108

    11

    39Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    OrderingComplete the catalogue number by replacing by the rating and protection degree.

    Example: Generic catalogue number of 1000A expansion joint, 3L+N+PE :CFC2510GEJM54

    Discrete catalogue number of a standard 1000A expansion joint,3L+N+PE:CFC2510GEJM54

    Rating

    Rating

    Protection degree

    Protection degree

    Catalogue numbers and dimensions

    Straight length components

    Type Length(mm)

    Height(mm)

    Width (mm)800 1000 1250 1350 1600 2000 2500 3000 3200 4000 5000 6000

    Fixed 1016 508 343 343 343 343 442 442 492 492 594 594 819 819

    I-LINE II Copper Busway

    Type Length(mm)

    Cat. no.3L+PE 3L+N+IGB 3L+N+ING

    Fixed 966 CFC23G38PTM CFC25G38PTM CFC26GG38PTM

    Type Cat. no.3L+PE 3L+N+IGB 3L+N+ING

    Fixed CFC23GEJM CFC25GEJM CFC26GGEJM

    Unfused Reducer

    Phase transition

    Type Length(mm)

    Cat. no.

    3L+PE 3L+N+IGB 3L+N+INGFixed 610 CFC23GRM CFC25GRM CFC26GGRM

    Note: Replace R with below code. For example, CFC2520GR10M54.

    Bolt sideAmpere Rating 400 600 800 1000 1250 1350 1600 2000 2500 3000 3200 4000

    800 - R4 - R6 - - - - - - - - - -1000 - R4 - R6 - R8 - - - - - - - - -1250 - R4 - R6 - R8 -R10 - - - - - - - -1350 - - R6 - R8 -R10 -R12 - - - - - - -1600 - - R6 - R8 -R10 -R12 - R13 - - - - - -2000 - - - R8 -R10 -R12 - R13 - R16 - - - - -2500 - - - -R10 -R12 - R13 - R16 - R20 - - - -3000 - - - -R10 -R12 - R13 - R16 - R20 - R25 - - -3200 - - - - -R12 - R13 - R16 - R20 - R25 - R30 - -4000 - - - - - - R13 - R16 - R20 - R25 - R30 - -5000 - - - - - - - R16 - R20 - R25 - R30 - R32 -6000 - - - - - - - - - R25 - R30 - R32 - R40Note: MCCB reducers are available. Contact us for details.

    Expansion Joint

  • K9CE21020

    DD

    2108

    13

    40 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Catalogue numbers and dimensions

    Straight length components

    I-LINE II Copper Busway

    Wall and floor flange (WF)

    End closureType Rating

    (A)Dimension (mm) Cat. no.A

    End closure 800 110 ACF38EC1000 110 ACF38EC1250 123 ACF43EC1350 148 ACF53EC1600 161 ACF58EC2000 184 ACF67EC2500 250 ACF93EC3000 336 ACF13EC3200 399 ACF15EC4000 425 ACF17EC5000 612 ACF24EC6000 650 ACF25EC

    Note: please add the suffix M for higher protection degree. For example, ACF38ECM54

    Rating(A)

    Straight Length Flanged End Cat. noA(mm) Y W Y W

    800 211 152 203 254 381 ACF38WF1000 211 152 203 254 381 ACF38WF1250 224 152 203 254 381 ACF43WF1350 249 178 203 279 381 ACF53WF1600 262 203 203 305 381 ACF58WF2000 285 229 203 356 381 ACF67WF2500 351 279 203 483 533 ACF93WF3000 437 381 203 483 533 ACF13WF3200 500 432 203 584 533 ACF15WF4000 526 457 203 584 533 ACF17WF5000 713 660 203 813 533 ACF24WF6000 751 686 203 813 533 ACF25WF

    Flatwise Elbow Wall thickness (mm)Rating(A)

    100 200 300 400 500 600W(mm) Y(mm)

    800 203 229 279 330 381 432 4831000 203 229 279 330 381 432 4831250 203 254 305 356 407 457 5081350 203 305 356 406 457 508 5591600 203 305 356 406 457 508 5592000 203 356 406 457 508 559 6102500 203 432 483 533 584 635 6863000 203 559 610 660 711 762 8133200 203 660 711 762 813 864 9144000 203 686 737 787 838 889 9405000 203 940 991 1041 1092 1143 11946000 203 1016 1067 1118 1168 1219 1270

    Edgewise Elbow Wall thickness (mm)Rating(A)

    100 200 300 400 500 600Y(mm) W(mm)

    800 150 305 356 406 457 509 5591000 150 305 356 406 457 509 5591250 150 305 356 406 457 509 5591350 176 305 356 406 457 509 5591600 203 305 356 406 457 509 5592000 229 305 356 406 457 509 5592500 279 305 356 406 457 509 5593000 381 305 356 406 457 509 5593200 432 305 356 406 457 509 5594000 457 305 356 406 457 509 5595000 660 305 356 406 457 509 5596000 686 305 356 406 457 509 559

  • K9CE22010 41Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Catalogue numbers and dimensions

    Elbows

    Type Rating (A)

    Cat. no3L+PE 3L+N+IGB

    Standard 800 CFC2308GLFM11M CFC2508GLFM11M1000 CFC2310GLFM11M CFC2510GLFM11M1250 CFC2312GLFM11M CFC2512GLFM11M1350 CFC2313GLFM12M CFC2513GLFM12M1600 CFC2316GLFM12M CFC2516GLFM12M2000 CFC2320GLFM12M CFC2520GLFM12M2500 CFC2325GLFM14M CFC2525GLFM14M3000 CFC2330GLFM15M CFC2530GLFM15M3200 CFC2332GLFM16M CFC2532GLFM16M4000 CFC2340GLFM17M CFC2540GLFM17M5000 CFC2350GLFM21M CFC2550GLFM21M6000 CFC2360GLFM21M CFC2560GLFM21M

    Made to measure

    All CFC23GLFSBM CFC25GLFSBM

    =+

    DimensionType Rating (A) Dimension (mm)

    A B

    Standard (min)800 279 2791000 279 2791250 279 2791350 305 3051600 305 3052000 305 3052500 356 3563000 381 3813200 406 4064000 432 4325000 533 5336000 533 533

    Made to measure All min ~ 1219 min ~ 1219

    I-LINE II Copper Busway

    Flatwise elbows with made to measure angles

    Flatwise elbow

    Type Rating Angle (W)

    Cat. no3L+PE 3L+N+IGB

    Made to measure All 91 ~ 179 CFC23

    GLFOASBAM CFC25GLFOASBAM

    =+, A=A+angleOA - special angle

    OrderingComplete the catalogue number by replacing by the rating and protection degree.

    Example: Generic catalogue number of 1000A flatwise elbow, 3L+N+PE CFC2510GELM54

    Discrete catalogue number of a 24 inch, 1000A flatwise elbow, 3L+N+PE: CFC2510G24LFS13B11M54

    S - the elbow side without joint pakB - the elbow side with joint pak

    Rating

    Rating

    Protection degree

    Protection degree

    - the length of the elbow side with joint pak - the length of the elbow side without joint pak - the total length of elbow

  • K9CE2201042 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Type Rating (A)

    Cat. no3L+PE 3L+N+IGB

    Standard 800 CFC2308GLEM11M CFC2508GLEM11M1000 CFC2310GLEM11M CFC2510GLEM11M1250 CFC2312GLEM11M CFC2512GLEM11M1350 CFC2313GLEM11M CFC2513GLEM11M1600 CFC2316GLEM11M CFC2516GLEM11M2000 CFC2320GLEM11M CFC2520GLEM11M2500 CFC2325GLEM11M CFC2525GLEM11M3000 CFC2330GLEM11M CFC2530GLEM11M3200 CFC2332GLEM11M CFC2532GLEM11M4000 CFC2340GLEM11M CFC2540GLEM11M5000 CFC2350GLEM11M CFC2550GLEM11M6000 CFC2360GLEM11M CFC2560GLEM11M

    Made to measure

    All CFC23GLESBM CFC25GLESBM

    =+

    Catalogue numbers and dimensions

    Elbows

    Edgewise elbows

    Edgewise elbows with made to measure angles

    DimensionType Rating (A) Dimensions (mm)

    A BStandard(min) All 279 279Made to measure All min ~ 1219 min ~ 1219

    I-LINE II Copper Busway

    Type Rating Angle (W)

    Cat. no3L+PE 3L+N+IGB

    Made to measure

    All 91~179 CFC23GLESBAM CFC25GLESBAM

    =+, A=A+angle

    A

    B

    Flatwise TeeType Rating

    (A)Cat. no3L+PE 3L+N+IGB

    Standard 800 CFC2308G33TS11B11S11M CFC2508G33TS11B11S11M1000 CFC2310G33TS11B11S11M CFC2510G33TS11B11S11M1250 CFC2312G33TS11B11S11M CFC2512G33TS11B11S11M1350 CFC2313G36TS12B12S12M CFC2513G36TS12B12S12M1600 CFC2316G36TS12B12S12M CFC2516G36TS12B12S12M2000 CFC2320G36TS12B12S12M CFC2520G36TS12B12S12M2500 CFC2325G42TS14B14S14M CFC2525G42TS14B14S14M3000 CFC2330G45TS15B15S15M CFC2530G45TS15B15S15M3200 CFC2332G48TS16B16S16M CFC2532G48TS16B16S16M4000 CFC2340G51TS17B17S17M CFC2540G51TS17B17S17M5000 CFC2350G63TS21B21S21M CFC2550G63TS21B21S21M6000 CFC2360G63TS21B21S21M CFC2560G63TS21B21S21M

    Made to measure

    All CFC23GTSBSM CFC25GTSBSM

    =++Dimension

    Type Rating (A) Dimension (mm)A B C

    Standard (min)800 279 279 2791000 279 279 2791250 279 279 2791350 305 305 3051600 305 305 3052000 305 305 3052500 356 356 3563000 381 381 3813200 406 406 4064000 432 432 4325000 533 533 5336000 533 533 533

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1219

  • K9CE22020

    A

    B

    C

    43Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Catalogue numbers and dimensions

    Double elbows

    Double left elbow

    I-LINE II Copper Busway

    Type Rating (A)

    Cat. no3L+PE 3L+N+IGB

    Made to measure

    800 CFC2308GDLBCSM CFC2508GDLBCSM1000 CFC2310GDLBCSM CFC2510GDLBCSM1250 CFC2312GDLBCSM CFC2512GDLBCSM1350 CFC2313GDLBCSM CFC2513GDLBCSM1600 CFC2316GDLBCSM CFC2516GDLBCSM2000 CFC2320GDLBCSM CFC2520GDLBCSM2500 CFC2325GDLBCSM CFC2525GDLBCSM3000 CFC2330GDLBCSM CFC2530GDLBCSM3200 CFC2332GDLBCSM CFC2532GDLBCSM4000 CFC2340GDLBCSM CFC2540GDLBCSM5000 CFC2350GDLBCSM CFC2550GDLBCSM6000 CFC2360GDLBCSM CFC2560GDLBCSM

    =++DimensionType Rating (A) Dimension (mm)

    A B C

    Standard (min)800 279 279 1781000 279 279 1781250 279 279 1781350 305 279 2031600 305 279 2032000 305 279 2032500 356 279 2793000 381 279 2793200 406 279 3304000 432 279 3305000 533 279 4576000 533 279 457

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1016

    B

    C

    A

    Double right elbowType Rating

    (A)Cat. no3L+PE 3L+N+IGB

    Made to measure

    800 CFC2308GDRBCSM CFC2508GDRBCSM1000 CFC2310GDRBCSM CFC2510GDRBCSM1250 CFC2312GDRBCSM CFC2512GDRBCSM1350 CFC2313GDRBCSM CFC2513GDRBCSM1600 CFC2316GDRBCSM CFC2516GDRBCSM2000 CFC2320GDRBCSM CFC2520GDRBCSM2500 CFC2325GDRBCSM CFC2525GDRBCSM3000 CFC2330GDRBCSM CFC2530GDRBCSM3200 CFC2332GDRBCSM CFC2532GDRBCSM4000 CFC2340GDRBCSM CFC2540GDRBCSM5000 CFC2350GDRBCSM CFC2550GDRBCSM6000 CFC2360GDRBCSM CFC2560GDRBCSM

    =++DimensionType Rating (A) Dimension (mm)

    A B C

    Standard (min)800 279 279 1781000 279 279 1781250 279 279 1781350 305 279 2031600 305 279 2032000 305 279 2032500 356 279 2793000 381 279 2793200 406 279 3304000 432 279 3305000 533 279 4576000 533 279 457

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1016

    OrderingComplete the catalogue number by replacing by the rating and protection degree.Example: Generic catalogue number of 1000A double left elbow, 3L+N+PE:CFC2510GELM54

    Rating

    Rating

    Protection degree

    Protection degreeS - the elbow side without joint pakB - the elbow side with joint pakC or O - the straight feeder of the elbow

    - the total length of elbow - the length of the elbow side with joint pak - the length of straight feeder - the length of the elbow side without joint pak

    Discrete catalogue number of a 29 inch, 1000A double left elbow, 3L+N+PE:CFC2510G29DLB11C07S11M54

  • K9CE22020

    A

    B

    C

    A

    B

    44 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Catalogue numbers and dimensions

    Offset elbows

    Flatwise offset elbow

    Edgewise offset elbow

    I-LINE II Copper Busway

    Type Rating (A)

    Cat. no3L+PE 3L+N+IGB

    Made to measure

    800 CFC2308GOFSOBM CFC2508GOFSOBM1000 CFC2310GOFSOBM CFC2510GOFSOBM1250 CFC2312GOFSOBM CFC2512GOFSOBM1350 CFC2313GOFSOBM CFC2513GOFSOBM1600 CFC2316GOFSOBM CFC2516GOFSOBM2000 CFC2320GOFSOBM CFC2520GOFSOBM2500 CFC2325GOFSOBM CFC2525GOFSOBM3000 CFC2330GOFSOBM CFC2530GOFSOBM3200 CFC2332GOFSOBM CFC2532GOFSOBM4000 CFC2340GOFSOBM CFC2540GOFSOBM5000 CFC2350GOFSOBM CFC2550GOFSOBM6000 CFC2360GOFSOBM CFC2560GOFSOBM

    =++

    Type Rating (A)

    Cat. no3L+PE 3L+N+IGB

    Made to measure

    800 CFC2308GOESOBM CFC2508GOESOBM1000 CFC2310GOESOBM CFC2510GOESOBM1250 CFC2312GOESOBM CFC2512GOESOBM1350 CFC2313GOESOBM CFC2513GOESOBM1600 CFC2316GOESOBM CFC2516GOESOBM2000 CFC2320GOESOBM CFC2520GOESOBM2500 CFC2325GOESOBM CFC2525GOESOBM3000 CFC2330GOESOBM CFC2530GOESOBM3200 CFC2332GOESOBM CFC2532GOESOBM4000 CFC2340GOESOBM CFC2540GOESOBM5000 CFC2350GOESOBM CFC2550GOESOBM6000 CFC2360GOESOBM CFC2560GOESOBM

    =++

    DimensionType Rating (A) Dimension (mm)

    A B C

    Standard (min)800 279 279 1021000 279 279 1021250 279 279 1021350 305 305 1021600 305 305 1022000 305 305 1522500 356 356 2793000 381 381 3563200 406 406 4064000 432 432 4065000 533 533 5846000 533 533 635

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1016

    DimensionType Rating (A) Dimension (mm)

    A B C

    Standard (min) All 279 279 152

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1016

  • K9CE22020 45Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    B

    A

    Catalogue numbers and dimensions

    Elbow plus Flanged end

    Flatwise elbow flanged end

    Edgewise elbow flanged end

    I-LINE II Copper Busway

    Type Rating (A)

    Cat. no

    3L+PE 3L+N+IGB

    Made to measure

    800 CFC2308GLFFE*FM CFC2508GLFFE*FM1000 CFC2310GLFFE*FM CFC2510GLFFE*FM1250 CFC2312GLFFE*FM CFC2512GLFFE*FM1350 CFC2313GLFFE*FM CFC2513GLFFE*FM1600 CFC2316GLFFE*FM CFC2516GLFFE*FM2000 CFC2320GLFFE*FM CFC2520GLFFE*FM2500 CFC2325GLFFE*FM CFC2525GLFFE*FM3000 CFC2330GLFFE*FM CFC2530GLFFE*FM3200 CFC2332GLFFE*FM CFC2532GLFFE*FM4000 CFC2340GLFFE*FM CFC2540GLFFE*FM5000 CFC2350GLFFE*FM CFC2550GLFFE*FM6000 CFC2360GLFFE*FM CFC2560GLFFE*FM

    =+

    * = B or S. B - elbow side with joint pak, S - elbow side without joint pakDimensionType Rating (A) Dimension (mm)

    A B

    Standard (min)800 204 2791000 204 2791250 204 2791350 204 3051600 229 3052000 229 3052500 254 3563000 305 3813200 330 4064000 356 4325000 457 5336000 457 533

    Made to measure All min ~ 1219 min ~ 1219

    Type Rating (A)

    Cat. no3L+PE 3L+N+IGB

    Made to measure

    800 CFC2308GLEFE*FM CFC2508GLEFE*FM1000 CFC2310GLEFE*FM CFC2510GLEFE*FM1250 CFC2312GLEFE*FM CFC2512GLEFE*FM1350 CFC2313GLEFE*FM CFC2513GLEFE*FM1600 CFC2316GLEFE*FM CFC2516GLEFE*FM2000 CFC2320GLEFE*FM CFC2520GLEFE*FM2500 CFC2325GLEFE*FM CFC2525GLEFE*FM3000 CFC2330GLEFE*FM CFC2530GLEFE*FM3200 CFC2332GLEFE*FM CFC2532GLEFE*FM4000 CFC2340GLEFE*FM CFC2540GLEFE*FM5000 CFC2350GLEFE*FM CFC2550GLEFE*FM6000 CFC2360GLEFE*FM CFC2560GLEFE*FM

    =+

    * = B or S. B - elbow side with joint pak, S - elbow side without joint pakDimensionType Rating (A) Dimension (mm)

    A B

    Standard (min)800 152 2791000 152 2791250 152 2791350 152 2791600 152 2792000 152 2792500 152 2793000 152 2793200 152 2794000 152 2795000 152 2796000 152 279

    Made to measure All min ~ 1219 min ~ 1219

  • K9CE2202046 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Catalogue numbers and dimensions

    Internal Grounding Elbows

    Flatwise Elbow

    Edgewise Elbow

    I-LINE II Copper Busway

    Type Rating (A)

    Cat. no1a 1b

    Standard 800 CFC2608GG22LFIS11B11M CFC2508GG22LFOS11B11M1000 CFC2610GG22LFIS11B11M CFC2510GG22LFOS11B11M1250 CFC2612GG22LFIS11B11M CFC2512GG22LFOS11B11M1350 CFC2613GG24LFIS12B12M CFC2513GG24LFOS12B12M1600 CFC2616GG24LFIS12B12M CFC2516GG24LFOS12B12M2000 CFC2620GG24LFIS12B12M CFC2520GG24LFOS12B12M2500 CFC2625GG28LFIS14B14M CFC2525GG28LFOS14B14M3000 CFC2630GG30LFIS15B15M CFC2530GG30LFOS15B15M3200 CFC2632GG32LFIS16B16M CFC2532GG32LFOS16B16M4000 CFC2640GG34LFIS17B17M CFC2540GG34LFOS17B17M5000 CFC2650GG42LFIS21B21M CFC2550GG42LFOS21B21M6000 CFC2660GG42LFIS21B21M CFC2560GG42LFOS21B21M

    Made to measure

    All CFC26GGLFISBM CFC25GGLFOSBM

    =+

    Type Rating (A)

    Cat. no2a 2b

    Standard 800 CFC2608GG22LEIS11B11M CFC2508GG22LEOS11B11M1000 CFC2610GG22LEIS11B11M CFC2510GG22LEOS11B11M1250 CFC2612GG22LEIS11B11M CFC2512GG22LEOS11B11M1350 CFC2613GG22LEIS11B11M CFC2513GG22LEOS11B11M1600 CFC2616GG22LEIS11B11M CFC2516GG22LEOS11B11M2000 CFC2620GG22LEIS11B11M CFC2520GG22LEOS11B11M2500 CFC2625GG22LEIS11B11M CFC2525GG22LEOS11B11M3000 CFC2630GG22LEIS11B11M CFC2530GG22LEOS11B11M3200 CFC2632GG22LEIS11B11M CFC2532GG22LEOS11B11M4000 CFC2640GG22LEIS11B11M CFC2540GG22LEOS11B11M5000 CFC2650GG22LEIS11B11M CFC2550GG22LEOS11B11M6000 CFC2660GG22LEIS11B11M CFC2560GG22LEOS11B11M

    Made to measure

    All CFC26GGLEISBM CFC25**GGLEOSBM

    =+

    DimensionType Rating (A) Dimension (mm)

    A B

    Standard (min)800 279 2791000 279 2791250 279 2791350 305 3051600 305 3052000 305 3052500 356 3563000 381 3813200 406 4064000 432 4325000 533 5336000 533 533

    Made to measure All min ~ 1219 min ~ 1219

    Flatwise elbows with made to measure anglesType Rating

    (A)Angle (W)

    3L+N+INGGround bar inside Ground bar outside

    Standard (min) All 91 ~ 179 CFC26GGLFIOASBAM CFC26**GGLFOOASBAM

    =+, A=A+angle

    DimensionType Rating (A) Dimension (mm)

    A B

    Standard (min) All 279 279

    Made to measure All min ~ 1219 min ~ 1219

    EL1NL2L3

    EL1L2L3N

    #'',&)3"

    B

    S

    B

    A

    1a

    EL1N

    L2L3

    EL1L2L3N

    B

    S

    #'',&/3"

    A

    B

    1b

    EL1

    NL2L3

    EL1L2L3N

    CFC2608GG22LEIS11B11

    B

    S

    A

    B

    2a

    EL1N

    L2L3

    EL1L2L3N

    CFC2608GG22LEOS11B11

    B

    S

    A

    B

    2b

  • K9CE22020 47Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Catalogue numbers and dimensions

    Internal Grounding Elbows

    Tee - Feeder

    Double left elbow

    I-LINE II Copper Busway

    Type Rating (A)

    Cat. no3a 3b

    Made to measure

    800 CFC2608GGDLIBCSM CFC2608GGDL0BCSM1000 CFC2610GGDLIBCSM CFC2610GGDL0BCSM1250 CFC2612GGDLIBCSM CFC2612GGDL0BCSM1350 CFC2613GGDLIBCSM CFC2613GGDL0BCSM1600 CFC2616GGDLIBCSM CFC2616GGDL0BCSM2000 CFC2620GGDLIBCSM CFC2620GGDL0BCSM2500 CFC2625GGDLIBCSM CFC2625GGDL0BCSM3000 CFC2630GGDLIBCSM CFC2630GGDL0BCSM3200 CFC2632GGDLIBCSM CFC2632GGDL0BCSM4000 CFC2640GGDLIBCSM CFC2640GGDL0BCSM5000 CFC2650GGDLIBCSM CFC2650GGDL0BCSM6000 CFC2660GGDLIBCSM CFC2660GGDL0BCSM

    =++

    DimensionType Rating (A) Dimension (mm)

    A B C

    Standard (min)800 279 279 2791000 279 279 2791250 279 279 2791350 305 305 3051600 305 305 3052000 305 305 3052500 356 356 3563000 381 381 3813200 406 406 4064000 432 432 4325000 533 533 5336000 533 533 533

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1219

    DimensionType Rating (A) Dimension (mm)

    A B C

    Standard (min)800 279 279 1781000 279 279 1781250 279 279 1781350 305 279 2031600 305 279 2032000 305 279 2032500 356 279 2793000 381 279 2793200 406 279 3304000 432 279 3305000 533 279 4576000 533 279 457

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1016

    Type Rating Cata. no3L+PE+ING

    Standard800 CFC2608GG33TS11B11S11M1000 CFC2610GG33TS11B11S11M1250 CFC2612GG33TS11B11S11M1350 CFC2613GG36TS12B12S12M1600 CFC2616GG36TS12B12S12M2000 CFC2620GG36TS12B12S12M2500 CFC2625GG42TS14B14S14M3000 CFC2630GG45TS15B15S15M3200 CFC2632GG48TS16B16S16M4000 CFC2640GG51TS17B17S17M5000 CFC2650GG63TS21B21S21M6000 CFC2660GG63TS21B21S21M

    Made to measure All CFC26**GGTSBSM=++

    EL1

    NL2L3

    EL1L2L3N

    CFC2608GG29DLIS11C07B11

    S

    B

    A

    C

    B

    3a

    CFC2608GG29DLIB11C07S11

    EL1N L2L3

    EL1L2L3N

    B

    S

    A

    C

    B

    3a

    CFC2608GG29DLOS11C07B11

    EL1N

    L2L3

    EL1L2L3N

    S

    B

    A

    C

    B

    3b

    CFC2608GG29DLOB11C07S11

    EL1N

    L2L3

    EL1L2L3N

    B

    S

    A

    C

    B

    3b

  • K9CE2202048 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Catalogue numbers and dimensions

    Internal Grounding Elbows

    Double Right elbow

    Flatwise offset elbow

    I-LINE II Copper Busway

    Type Rating (A)

    Cat. no

    4a 4b

    Made to measure

    800 CFC2608GGDRIBCSM CFC2608GGDROBCSM1000 CFC2610GGDRIBCSM CFC2610GGDROBCSM1250 CFC2612GGDRIBCSM CFC2612GGDROBCSM1350 CFC2613GGDRIBCSM CFC2613GGDROBCSM1600 CFC2616GGDRIBCSM CFC2616GGDROBCSM2000 CFC2620GGDRIBCSM CFC2620GGDROBCSM2500 CFC2625GGDRIBCSM CFC2625GGDROBCSM3000 CFC2630GGDRIBCSM CFC2630GGDROBCSM3200 CFC2632GGDRIBCSM CFC2632GGDROBCSM4000 CFC2640GGDRIBCSM CFC2640GGDROBCSM5000 CFC2650GGDRIBCSM CFC2650GGDROBCSM6000 CFC2660GGDRIBCSM CFC2660GGDROBCSM

    =++

    Type Rating (A)

    Cat. no6a 6b

    Made to measure

    800 CFC2608GGOFISOBM CFC2608GGOFOSOBM1000 CFC2610GGOFISOBM CFC2610GGOFOSOBM1250 CFC2612GGOFISOBM CFC2612GGOFOSOBM1350 CFC2613GGOFISOBM CFC2613GGOFOSOBM1600 CFC2616GGOFISOBM CFC2616GGOFOSOBM2000 CFC2620GGOFISOBM CFC2620GGOFOSOBM2500 CFC2625GGOFISOBM CFC2625GGOFOSOBM3000 CFC2630GGOFISOBM CFC2630GGOFOSOBM3200 CFC2632GGOFISOBM CFC2632GGOFOSOBM4000 CFC2640GGOFISOBM CFC2640GGOFOSOBM5000 CFC2650GGOFISOBM CFC2650GGOFOSOBM6000 CFC2660GGOFISOBM CFC2660GGOFOSOBM

    =++

    DimensionType Rating (A) Dimension (mm)

    A B C

    Standard (min)800 279 279 1781000 279 279 1781250 279 279 1781350 305 279 2031600 305 279 2032000 305 279 2032500 356 279 2793000 381 279 2793200 406 279 3304000 432 279 3305000 533 279 4576000 533 279 457

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1016

    DimensionType Rating (A) Dimension (mm)

    A B C

    Standard (min)800 279 279 1021000 279 279 1021250 279 279 1021350 305 305 1021600 305 305 1022000 305 305 1522500 356 356 2793000 381 381 3563200 406 406 4064000 432 432 4065000 533 533 5846000 533 533 635

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1016

    EL1L2L3N

    EL1N

    L2L3

    B

    S

    CFC2608GG29DRIB11C07S11

    C

    B

    A

    4a

    EL1N

    L2L3S

    EL1L2L3N

    B

    CFC2608GG29DRIS11C07B11

    AC

    B

    4a

    EL1N

    L2L3

    S

    CFC2608GG29DROS11C07B11

    C A

    4b

    EL1L2L3N

    B

    B

    B

    EL1N

    L2L3

    EL1L2L3N

    S

    CFC2608GG29DROB11C07S11

    AC

    B

    4b

    EL1

    N

    L2L3

    EL1

    N

    L2L3

    B

    S

    CFC2608GG26OFIS11O04B11

    A

    B

    C

    6a

    EL1

    N

    L2L3

    B

    S

    EL1

    N

    L2L3

    CFC2608GG26OFOS11O04B11

    A

    B

    C

    6b

  • K9CE22020 49Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Catalogue numbers and dimensions

    Internal Grounding Elbows

    Edgewise offset elbow

    Flange end flatwise elbow

    I-LINE II Copper Busway

    Type Rating (A)

    Cat. no

    5a 5b

    Made to measure

    800 CFC2608GGOEISOBM CFC2608GGOEOSOBM1000 CFC2610GGOEISOBM CFC2610GGOEOSOBM1250 CFC2612GGOEISOBM CFC2612GGOEOSOBM1350 CFC2613GGOEISOBM CFC2613GGOEOSOBM1600 CFC2616GGOEISOBM CFC2616GGOEOSOBM2000 CFC2620GGOEISOBM CFC2620GGOEOSOBM2500 CFC2625GGOEISOBM CFC2625GGOEOSOBM3000 CFC2630GGOEISOBM CFC2630GGOEOSOBM3200 CFC2632GGOEISOBM CFC2632GGOEOSOBM4000 CFC2640GGOEISOBM CFC2640GGOEOSOBM5000 CFC2650GGOEISOBM CFC2650GGOEOSOBM6000 CFC2660GGOEISOBM CFC2660GGOEOSOBM

    =++

    Type Rating (A)

    Cat. no7a 7b

    Made to measure

    800 CFC2608GGLFIFE*FM CFC2608GGLFOFE*FM1000 CFC2610GGLFIFE*FM CFC2610GGLFOFE*FM1250 CFC2612GGLFIFE*FM CFC2612GGLFOFE*FM1350 CFC2613GGLFIFE*FM CFC2613GGLFOFE*FM1600 CFC2616GGLFIFE*FM CFC2616GGLFOFE*FM2000 CFC2620GGLFIFE*FM CFC2620GGLFOFE*FM2500 CFC2625GGLFIFE*FM CFC2625GGLFOFE*FM3000 CFC2630GGLFIFE*FM CFC2630GGLFOFE*FM3200 CFC2632GGLFIFE*FM CFC2632GGLFOFE*FM4000 CFC2640GGLFIFE*FM CFC2640GGLFOFE*FM5000 CFC2650GGLFIFE*FM CFC2650GGLFOFE*FM6000 CFC2660GGLFIFE*FM CFC2660GGLFOFE*FM

    =+

    * = B or S. B - elbow side with joint pak, S - elbow side without joint pak

    DimensionType Rating (A) Dimension (mm)

    A B C

    Standard (min) All 279 279 152

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1016

    DimensionType Rating (A) Dimension (mm)

    A B

    Standard (min)800 204 279 1000 204 279 1250 204 279 1350 204 305 1600 229 305 2000 229 305 2500 254 356 3000 305 381 3200 330 406 4000 356 432 5000 457 533 6000 457 533

    Made to measure All min ~ 1219 min ~ 1219

    EL1

    NL2

    L3

    EL1

    NL2

    L3

    S

    B

    CFC2608GG28OEIS11O06B11

    A

    B

    C

    5a

    EL1

    N

    L2L3

    S

    B EL1

    N

    L2L3

    CFC2608GG28OEOS11O06B11

    A

    B

    C

    5b

    L1L2

    L3N

    E

    SEL1N

    L2L3

    CFC2608GG19LFIFES11F08

    B

    A

    7a

    L1L2

    L3N

    E

    B

    EL1N

    L2L3

    CFC2608GG19LFIFEB11F08

    B

    A

    7a

  • K9CE2202050 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Catalogue numbers and dimensions

    Internal Grounding Elbows

    Flange end edgewise elbow

    I-LINE II Copper Busway

    Type Rating (A)

    Cat. no

    8a 8b

    Made to measure

    800 CFC2608GGLEIFE*FM CFC2608GGLEOFE*FM1000 CFC2610GGLEIFE*FM CFC2610GGLEOFE*FM1250 CFC2612GGLEIFE*FM CFC2612GGLEOFE*FM1350 CFC2613GGLEIFE*FM CFC2613GGLEOFE*FM1600 CFC2616GGLEIFE*FM CFC2616GGLEOFE*FM2000 CFC2620GGLEIFE*FM CFC2620GGLEOFE*FM2500 CFC2625GGLEIFE*FM CFC2625GGLEOFE*FM3000 CFC2630GGLEIFE*FM CFC2630GGLEOFE*FM3200 CFC2632GGLEIFE*FM CFC2632GGLEOFE*FM4000 CFC2604GGLEIFE*FM CFC2640GGLEOFE*FM5000 CFC2650GGLEIFE*FM CFC2650GGLEOFE*FM6000 CFC2660GGLEIFE*FM CFC2660GGLEOFE*FM

    =+

    * = B or S. B - elbow side with joint pak, S - elbow side without joint pak

    DimensionType Rating (A) Dimension (mm)

    A B

    Standard (min) All 152 279

    Made to measure All min ~ 1219 min ~ 1219

    EL1

    NL2L3

    S

    E

    L1

    L2

    L3

    N

    CFC2608GG17LEIFES11F06

    B

    A

    8a

    S

    L1

    L2

    L3

    N

    E

    EL1N

    L2L3

    CFC2608GG17LEOFES11F06

    B

    A

    8b

  • K9CE24010 51Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Rating (A) Dimension (mm)A B C D

    800 162 81 - -1000 162 81 - -1250 162 81 - -1350 178 89 - -1600 203 102 - -2000 254 127 - -2500 378 127 - -3000 378 127 - -3200 480 121 119 -4000 480 121 119 -5000 705 117 118 1186000 705 117 118 118

    Catalogue numbers and dimensions

    Flanged ends

    I-LINE II Copper Busway

    Type Rating (A)Cat. no3L+PE 3L+N+IGB 3L+N+ING

    Satandard all CFC23 G10FE*M CFC25G10FE*M CFC26GG10FE*M

    Made to measure

    800 CFC2308GFE*M CFC2508GFE*M CFC2608GFE*M1000 CFC2310GFE*M CFC2510GFE*M CFC2610GFE*M1250 CFC2312GFE*M CFC2512GFE*M CFC2612GFE*M1350 CFC2313GFE*M CFC2513GFE*M CFC2613GFE*M1600 CFC2316GFE*M CFC2516GFE*M CFC2616GFE*M2000 CFC2320GFE*M CFC2520GFE*M CFC2620GFE*M2500 CFC2325GFE*M CFC2525GFE*M CFC2625GFE*M3000 CFC2330GFE*M CFC2530GFE*M CFC2630GFE*M3200 CFC2332GFE*M CFC2532GFE*M CFC2632GFE*M4000 CFC2340GFE*M CFC2540GFE*M CFC2640GFE*M5000 CFC2350GFE*M CFC2550GFE*M CFC2650GFE*M6000 CFC2360GFE*M CFC2560GFE*M CFC2660GFE*M

    * =B with joint pak, S without joint pakDimensionType Rating (A) Dimension (mm)

    A

    Standard All 254

    Made to measure All min ~ 1219

    Flanged Collar and Cutout and Drill ing Template 800A-6000A Feeder

    Rating (A)

    N Holes Dimension (mm)E F G H J K W

    800 10 98 - 130 187 254 296 3351000 10 98 - 130 187 254 296 3351250 10 98 - 130 187 254 296 3351350 10 98 - 145 203 254 296 3351600 10 98 - 171 229 254 296 3352000 10 98 - 222 279 254 296 3352500 16 88 87 346 403 406 451 4873000 16 88 87 346 403 406 451 4873200 18 88 87 448 505 406 451 4874000 18 88 87 448 505 406 451 4875000 22 88 87 673 730 406 451 4876000 22 88 87 673 730 406 451 487

    Cutout

    Flanged Collar

    Flanged Collar

    8 Dia.(Holes)

    Flanged end

    OrderingComplete the catalogue number by replacing by the rating and protection degree.Example: Generic catalogue number of 1000 A flanged end, 3L+N+PE BFC2510GFEM54

    Discrete catalogue number example of a 12 inch, 1000A flanged end, 3L+N+PE: BFC2510G12FEBM54

    Rating

    Rating *

    Protection degree

    Protection degree - the length of the straight feeder of flanged end

    * = B or S. B - with joint pak, S - without joint pak

  • K9CE2401052 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Rating (A) Dimension (mm)S T U

    800 76 92 971000 76 92 971250 76 92 971350 76 92 971600 76 92 972000 76 92 972500 127 169 1733000 127 169 1733200 127 169 1734000 127 169 1735000 127 169 1736000 127 169 173

    Rating (A) Figure Dimension (mm)A B C D

    800 1 64 - - -100 1 64 - - -1250 1 76 - - -1350 1 102 - - -1600 1 114 - - -2000 1 137 - - -2500 4 203 - - 1273000 2 114 289 60 -3200 2 127 353 99 -4000 2 152 378 73 -5000 3 114 565 111 -6000 3 152 604 73 -

    Rating (A) Catalogue No. No. of Pieces required per phase& neutral

    800 FLEX508 21000 FLEX510 31250 FLEX512 31350 FLEX513 41600 FLEX516 42000 FLEX520 52500 FLEX525 73000 FLEX530 83200 FLEX532 84000 FLEX540 105000 FLEX550 136000 FLEX560 15

    Catalogue numbers and dimensions

    Flanged ends

    Figure 1

    Flanged Collar

    4-pole with Earth Bus (Bottom View)

    4-pole with Earth Bus 3-pole with Earth Bus

    Flanged end termination details

    Physical Data

    Figure 2

    Figure 3

    Figure 4

    I-LINE II Copper Busway

    Flexible link

  • K9CE24010 53Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Rating (A) Figure Dimension (mm)A B C D

    800 1 64 - - -1000 1 64 - - -1250 1 76 - - -1350 1 102 - - -1600 1 114 - - -2000 1 137 - - -2500 4 165 - - 1273000 2 114 289 60 -3200 2 127 353 86 -5000 3 114 565 111 -6000 3 152 604 73 -

    Rating (A) Dimension (mm)A B X Y Z

    800 650 432 267 458 1901000 650 432 267 458 1901250 650 432 267 458 1901350 650 432 267 458 1901600 650 432 267 458 1902000 650 432 267 458 1902500 650 445 279 458 1903000 650 533 364 458 1903200 650 584 428 458 1904000 650 610 453 458 1905000 650 813 641 458 1906000 650 838 679 458 190

    Catalogue numbers and dimensions

    Flanged ends

    Figure 1

    Figure 3

    Figure 2

    Figure 4

    I-LINE II Copper Busway

    Qwik Fange (Indoor Only)

    CL

    A

    D3271

    Type Rating (A)Cat. no3L+PE 3L+N+IGB

    Satandard800 CFC2308GQF CFC2508GQF1000 CFC2310GQF CFC2510GQF1250 CFC2312GQF CFC2512GQF1350 CFC2313GQF CFC2513GQF1600 CFC2316GQF CFC2516GQF2000 CFC2320GQF CFC2520GQF2500 CFC2325GQF CFC2525GQF3000 CFC2330GQF CFC2530GQF3200 CFC2332GQF CFC2532GQF4000 CFC2340GQF CFC2540GQF5000 CFC2350GQF CFC2550GQF6000 CFC2360GQF CFC2560GQF

    Note: please add the suffix M for higher protection degree. For example, CFC2508GQFM54

    CL

    A

    3271

    B

    CA A

    B

    A A AC C

  • K9CE26030

    D

    DD

    2023

    77D

    D20

    2381

    DD

    2023

    77

    54 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Catalogue numbers and dimensions

    Cable Tap Box

    Type Rating (A)

    Cat. no.3L+PE 3L+N+IGB 3L+N+IGB

    Standard all CFC23GETB*M CFC25GETB*M CFC26GGETB*MMade to measure

    800 CFC2308GETB*M CFC2508GETB*M CFC2608GGETB*M1000 CFC2310GETB*M CFC2510GETB*M CFC2610GGETB*M1250 CFC2312GETB*M CFC2512GETB*M CFC2612GGETB*M1350 CFC2313GETB*M CFC2513GETB*M CFC2613GGETB*M1600 CFC2316GETB*M CFC2516GETB*M CFC2616GGETB*M2000 CFC2320GETB*M CFC2520GETB*M CFC2620GGETB*M2500 CFC2325GETB*M CFC2525GETB*M CFC2625GGETB*M3000 CFC2330GETB*M CFC2530GETB*M CFC2630GGETB*M3200 CFC2332GETB*M CFC2532GETB*M CFC2632GGETB*M4000 CFC2340GETB*M CFC2540GETB*M CFC2640GGETB*M5000 CFC2350GETB*M CFC2550GETB*M CFC2650GGETB*M6000 CFC2360GETB*M CFC2560GETB*M CFC2660GGETB*M

    Type Ampere rating

    Cat. no.3L+PE 3L+N+IGB 3L+N+ING

    Standard all CFC23GETB*M CFC25GETB*M CFC26GGETB*M

    Cable Tap Box - End

    I-LINE II Copper Busway

    Cable Tap Box - Center

    DimensionType Rating

    (A)Lugs per PH&N

    Earth lugs Dimension (mm)

    240 mm2 150 mm2 240mm2 A B C D

    Standard (Min)

    800 3 3 - 740 279 406 2541000 3 3 - 740 279 406 2541250 4 4 - 740 279 406 2541350 4 4 - 740 279 406 2541600 5 5 - 740 378 406 2542000 6 6 - 740 378 406 2542500 7 7 - 1000 530 660 2543000 9 - 9 1000 530 660 2543200 10 - 10 1000 530 660 2544000 11 - 11 1000 530 660 2545000 14 - 14 1000 756 660 2546000 17 - 17 1000 756 660 254

    Made to measure All min min min min ~ 1219

    DimensionType Rating (A) Lugs per PH&N Earth lugs Dimension (mm)

    240 mm2 150 mm2 A B C D

    Standard (Min)

    800 3 3 889 356 406 1851000 3 3 889 356 406 1851250 4 4 889 356 406 1851350 4 4 889 356 406 1851600 5 5 889 356 406 1852000 6 6 889 356 406 1852500 7 7 1059 508 447 261

    OrderingComplete the catalogue number by replacing by the rating and protection degree.Example: Generic catalogue number of 1000 A end cable tap box, 3L+N+PE:CFC2510GETBM54

    Discrete catalogue number example of a 10 inch, 1000A end cable tap box, 3L+N+PE: CFC2510G10ETBBM54

    Rating

    Rating *

    Protection degree

    Protection degree - the length of the straight feeder of end cable tap box

    * = B or S. B - with joint pak, S - without joint pak

    Note: please contact us for the ratings not shown above

  • K9CE26030 55Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Catalogue numbers and dimensions

    Supports and fixings

    Flatwise horizontal hanger

    Edgewise horizontal hanger

    Type Rating(A)

    Dimension (mm) Cat. no.A (mm) B (mm)

    Flatwise horizontal hanger 800 186 148 HF38F1000 186 148 HF38F1250 199 161 HF43F1350 225 186 HF53F

    1600 237 199 HF58F

    2000 260 222 HF67F

    2500 326 288 HF93F

    3000 412 374 HF13F

    3200 475 437 HF15F

    4000 501 463 HF16F

    5000 688 650 HF24F

    6000 726 688 HF25F

    Type Rating(A)

    Dimension (mm) Cat. no.A (mm)

    Edgewise horizontal hanger 800 212 HF43E1000 212 HF43E1250 212 HF43E1350 250 HF58E

    1600 250 HF58E

    2000 276 HF67E

    2500 339 HF93E

    3000 438 HF13E

    3200 501 HF15E

    4000 527 HF16E

    5000 714 HF24E

    6000 752 HF26E

    I-LINE II Copper Busway

  • K9CE2603056 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Catalogue numbers and dimensions

    Supports and fixings

    Vertical fixed hanger

    Vertical spring hanger

    Type Rating(A) Cat. no.Vertical Spring hanger 800 HFVS1

    1000 HFVS11250 HFVS11350 HFVS11600 HFVS22000 HFVS22500 HFVS23000 HFVS83200 HFVS84000 HFVS85000 HFVS86000 HFVS8

    Type Rating(A) Cat. no.Vertical fixed hanger all HFV

    I-LINE II Copper Busway

  • K9CE26030 57Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

  • K9CE2101058 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Catalogue numbers and dimensions

    Straight lengths

    Type Length L Cat. no.3L + PE 3L + N + IGB 3L + N + ING

    Fixed 10 Feet BFC23G10STM BFC25G10STM BFC26G10STM

    Made to measure 16 inches ~119 inches BFC23G**STM BFC25G**STM BFC26G**STM

    Type Length Number of opening

    Cta.no

    3L+PE 3L+N+IGB 3L+N+ING

    Plug-in 4 feet 12 BPC23G4S2M BPC25G4S2M BPC26G4S2M

    6 feet 12 BPC23G6S2M BPC25G6S2M BPC26G6S2M22 BPC23G6S4M BPC25G6S4M BPC26G6S4M

    10 feet 12 BPC23G10S2M BPC25G10S2M BPC26G10S2M

    22 BPC23G10S4M BPC25G10S4M BPC26G10S4M

    32 BPC23G10S6M BPC25G10S6M BPC26G10S6M

    Riser 4 feet 11 BRC23G4S1M BRC25G4S1M BRC26G4S1M6 feet 11 BRC23G6S1M BRC25G6S1M BRC26G6S1M

    21 BRC23G6S2M BRC25G6S2M BRC26G6S2M

    10 feet 11 BRC23G10S1M BRC25G10S1M BRC26G10S1M21 BRC23G10S2M BRC25G10S2M BRC26G10S2M31 BRC23G10S3M BRC25G10S3M BRC26G10S3M

    I-LINE II Copper Contact Busway

    Straight feeder lengths

    Straight lengths with plug-in openings

    OrderingComplete the catalogue number by replacing by the rating and protection degree.

    Example: Generic catalogue number of 1000A straight feeder, 3L+N+PE : BFC2510GM54

    Discrete catalogue number of a 10feet 1000A straight feeder, 3L+N+PE.BFC2510G10STM54

    Rating

    Rating **

    Protection degree

    Protection degree

    **= the length of the straight feeder. If the number is larger than 10, the unit is inch. otherwise, the unit is feet.

    Trunking cross-section

    Rating (A) Type 800 1000 1250 1350 1600 2000 2500 3200 4000 5000

    Weight

    (kg/m)

    3L + PE Feeder 13.0 14.2 15.9 16.5 18.0 20.5 28.4 33.2 44.8 50.4

    Plug-in 15.8 17.3 18.8 19.6 21.2 23.6 31.5 36.3 47.0 53.6

    3L + N + IGB Feeder 14.0 15.6 17.8 18.6 20.5 23.5 33.5 39.7 51.8 60.1

    Plug-in 17.2 18.8 21.0 21.7 23.7 26.6 36.6 42.8 55.0 63.2

    W(mm) 98 120 148 161 186 225 323 412 566 650

    Figure A A A A A A B B C C

  • K9CE21010 59Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    I-LINE II Copper Contact Busway

    Catalogue numbers and dimensions

    Straight length components

    Type Length(mm)

    Height(mm)

    Width (mm)800 1000 1250 1350 1600 2000 2500 3200 4000 5000

    Fixed 1016 508 343 343 343 343 442 442 492 594 819 819

    Phase transition

    Type Length(mm)

    Cat. no.3L+PE 3L+N+IGB 3L+N+ING

    Fixed 966 BFC23G38PTM BFC25G38PTM BFC26GG38PTM

    Type Cat. no.3L+PE 3L+N+IGB 3L+N+ING

    Fixed BFC23GEJM BFC25GEJM BFC26GEJM

    Bolt sideAmpere Rating 400 630 800 1000 1250 1350 1600 2000 2500 3200 4000800 R04 R06 - - - - - - - -1000 R04 R06 R08 - - - - - - - -1250 R04 R06 R08 R10 - - - - - - -1350 - R06 R08 R10 R12 - - - - - -1600 - R06 R08 R10 R12 R13 - - - - -2000 - - R08 R10 R12 R13 R16 - - - -2500 - - - R10 R12 R13 R16 R20 - - -3200 - - - - R12 R13 R16 R20 R25 - -4000 - - - - - R13 R16 R20 R25 R32 -5000 - - - - - - R16 R20 R25 R32 R40Note: MCCB reducers are available. Contact us for details.

    Type Length(mm)

    Cat. no.3L+PE 3L+N+IGB 3L+N+ING

    Fixed 610 BFC23GRM BFC25GRM BFC26GRM

    Note: Replace R with below code. For example, BFC2520GR10M54.

    Unfused Reducer

    OrderingComplete the catalogue number by replacing by the rating and protection degree.

    Example: Generic catalogue number of 1000A expansion joint, 3L+N+PE :BFC2510GEJM54

    Discrete catalogue number of a standard 1000A expansion joint,3L+N+PE:BFC2510GEJM54

    Rating

    Rating

    Protection degree

    Protection degree

    Expansion Joint

    ABCN

    NCBA

  • K9CE2101060 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Catalogue numbers and dimensions

    Straight length components

    I-LINE II Copper Contact Busway

    Wall and floor flange (WF)

    End closureType Rating

    (A)Dimension (mm) Cat. no.A

    End closure 800 110 ACF38EC1000 132 ACF47EC1250 161 ACF58EC1350 174 ACF63EC1600 199 ACF73EC2000 237 ACF88EC2500 336 ACF13EC3200 425 ACF17EC4000 578 ACF22EC5000 663 ACF26EC

    Note: please add the suffix M for higher protection degree. For example, ACF38ECM54

    Rating(A)

    Straight Length Flanged End Cat. noA(mm) Y W Y W

    800 211 152 229 254 381 ACF38WF1000 233 174 229 276 381 ACF47WF1250 262 203 229 305 381 ACF58WF1350 275 203 229 330 381 ACF63WF1600 300 229 229 356 381 ACF73WF2000 338 279 229 432 533 ACF88WF2500 437 381 229 483 533 ACF13WF3200 526 457 229 584 533 ACF17WF4000 679 620 229 722 533 ACF22WF5000 764 711 229 813 533 ACF26WF

    Flatwise Elbow Wall thickness (mm)Rating(A)

    100 200 300 400 500 600W(mm) Y(mm)

    800 203 229 279 330 381 432 483 1000 203 305 356 406 457 508 559 1250 203 305 356 406 457 508 559 1350 203 330 381 432 483 533 584 1600 203 356 406 457 508 559 610 2000 203 432 483 533 584 635 686 2500 203 559 610 660 711 762 813 3200 203 686 737 787 838 889 940 4000 203 1016 1067 1118 1168 1219 1270 5000 203 1016 1067 1118 1168 1219 1270

    Edgewise Elbow Wall thickness (mm)Rating(A)

    100 200 300 400 500 600Y(mm) W(mm)

    800 152 305 356 406 457 509 559 1000 178 305 356 406 457 509 559 1250 203 305 356 406 457 509 559 1350 203 305 356 406 457 509 559 1600 229 305 356 406 457 509 559 2000 279 305 356 406 457 509 559 2500 381 305 356 406 457 509 559 3200 457 305 356 406 457 509 559 4000 711 305 356 406 457 509 559 5000 711 305 356 406 457 509 559

  • K9CE21010 61Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    OrderingComplete the catalogue number by replacing by the rating and protection degree.

    Example: Generic catalogue number of 1000A flatwise elbow, 3L+N+PE BFC2510GELM54

    Discrete catalogue number of a 24 inch, 1000A flatwise elbow, 3L+N+PE: BFC2510G24LFS13B11M54

    S - the elbow side without joint pakB - the elbow side with joint pak

    I-LINE II Copper Contact Busway

    Catalogue numbers and dimensions

    Elbows

    Type Rating (A)

    Cat. no3L+PE 3L+N+IGB 3L+N+ING

    Standard 800 BFC2308GLFM11M BFC2508GLFM11M BFC2608GLFM11M1000 BFC2310GLFM11M BFC2510GLFM11M BFC2610GLFM11M1250 BFC2312GLFM12M BFC2512GLFM12M BFC2612GLFM12M1350 BFC2313GLFM12M BFC2513GLFM12M BFC2613GLFM12M1600 BFC2316GLFM13M BFC2516GLFM13M BFC2616GLFM13M2000 BFC2320GLFM13M BFC2520GLFM13M BFC2620GLFM13M2500 BFC2325GLFM15M BFC2525GLFM15M BFC2625GLFM15M3200 BFC2332GLFM17M BFC2532GLFM17M BFC2632GLFM17M4000 BFC2340GLFM21M BFC2540GLFM21M BFC2640GLFM21M5000 BFC2350GLFM22M BFC2550GLFM22M BFC2650GLFM22M

    Made to measure

    All BFC23GLFSBM BFC25GLFSBM BFC26GLFSBM

    =+

    DimensionType Rating (A) Dimension (mm)

    A B

    Standard (min)800 279 2791000 279 2791250 305 3051350 305 3051600 330 3302000 330 3302500 381 3813200 432 4324000 533 5335000 559 559

    Made to measure All min ~ 1219 min ~ 1219

    Flatwise elbows with made to measure angles

    Type Rating Angle (W)

    Cat. no3L+PE 3L+N+IGB 3L+N+ING

    Made to measure All 91 ~ 179 BFC23

    GLFOASBAM BFC25GLFOASBAM BFC26GLFOASBAM

    =+, A=A+angleOA - special angle

    - the length of the elbow side with joint pak - the length of the elbow side without joint pak - the total length of elbow

    Rating

    Rating

    Protection degree

    Protection degree

    Flatwise elbow

  • K9CE2101062 Schneider Electric

    Cat

    alog

    ue n

    umbe

    rs

    Dim

    ensi

    ons

    Type Rating (A)

    Cat. no3L+PE 3L+N+IGB 3L+N+I