I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
-
Upload
jim-sumire-salazar -
Category
Documents
-
view
540 -
download
72
Transcript of I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
1/68
E96-443-
Rail Mounted Termination AssemblAnalog Inpu
(NRAI0
Bailey®®
Instructio
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
2/68
I-E96-443-1D
Preface
This manual describes analog input rail mounted terminationassemblies. A termination assembly is the transition betweeninput/output plant instrumentation wiring or cabling and theINFI 90 OPEN® distributed control system.
The name Termination Assembly or TA has been assigned todifferentiate the in-line, rail mounted characteristics of thistype of field termination from the Termination Unit or TU andthe Termination Module or TM.
® INFI 90 OPEN is a registered trademark of Elsag Bailey Process Automation.
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
3/68
I-E96-443-1D
®
List of Effective Pages
Total number of pages in this instruction is 59, consisting of the following:
Page No. Ch an ge Dat e
Preface OriginalList of Effective Pages Original
iii through vii Original1-1 through 1-9 Original2-1 through 2-9 Original3-1 through 3-7 Original4-1 through 4-2 Original5-1 through 5-4 Original
6-1 through 6-1 Original7-1 through 7-2 Original8-1 through 8-2 Original
A-1 through A-7 OriginalB-1 through B-4 OriginalC-1 through C-2 OriginalD-1 through D-1 Original
Index-1 through Index-2 Original
When an update is received, insert the latest changed pages and dispose of the super-seded pages.
NOTE: On an update page, the changed text or table is indicated by a vertical bar in the outer mar-
gin of the page adjacent to the changed area. A changed figure is indicated by a vertical bar in theouter margin next to the figure caption. The date the update was prepared will appear beside the
page number.
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
4/68
Table of Contents
Page
I-E96-443-1D ii
SECTION 1 - INTRODUCTION....................................................................................................1-1
OVERVIEW ..................................................................................................................1-1()ASI02.........................................................................................................................1-1IMFBS01 ...............................................................................................................1-2
IMASI03.................................................................................................................1-2INTENDED USER.........................................................................................................1-2EQUIPMENT DESCRIPTION .........................................................................................1-2
FEATURES...................................................................................................................1-3INSTRUCTION CONTENT / HOW TO USE ....................................................................1-3EQUIPMENT APPLICATION ..........................................................................................1-3GLOSSARY OF TERMS AND ABBREVIATIONS .............................................................1-4REFERENCE DOCUMENTS..........................................................................................1-5ELSAG BAILEY CANADA REFERENCE DOCUMENTS...................................................1-6NOMENCLATURE ........................................................................................................1-7
SPECIFICATIONS.........................................................................................................1-7
SECTION 2 - DESCRIPTION AND OPERATION........................................................................2-1INTRODUCTION...........................................................................................................2-1FUNCTIONAL OPERATION ...........................................................................................2-1DIP SWITCH FUNCTIONALITY......................................................................................2-3DIP SWITCH SETTINGS ...............................................................................................2-4PHYSICAL OPERATION ................................................................................................2-5
SECTION 3 - INSTALLATION....................................................................................................3-1INTRODUCTION...........................................................................................................3-1SPECIAL HANDLING ....................................................................................................3-1UNPACKING AND INSPECTION....................................................................................3-1LOCATION CONSIDERATIONS .....................................................................................3-1
SAFETY CONSIDERATIONS .........................................................................................3-1SETUP AND PHYSICAL INSTALLATION ........................................................................3-2
Typical Elsag Bailey Termination Cabinet Arrangement..........................................3-2Explanation ...........................................................................................................3-2
CUSTOM OR SPECIAL .................................................................................................3-4 WIRING CONNECTIONS AND CABLING .......................................................................3-4OTHER EQUIPMENT INTERFACE ................................................................................3-7
PRE-OPERATING ADJUSTMENTS................................................................................3-7
SECTION 4 - CALIBRATION.......................................................................................................4-1INITIAL CALIBRATION..................................................................................................4-1CHECKOUT .................................................................................................................4-2
IN-SERVICE CALIBRATION..........................................................................................4-2
SECTION 5 - TROUBLESHOOTING...........................................................................................5-1INTRODUCTION...........................................................................................................5-1ERROR MESSAGES AND CORRECTIVE ACTION..........................................................5-1PROBLEM DETERMINATION AND VERIFICATION PROCEDURES................................5-1
TROUBLESHOOTING GUIDE .......................................................................................5-1
SECTION 6 - MAINTENANCE........................................................................................... .........6-1INTRODUCTION...........................................................................................................6-1MAINTENANCE SCHEDULE.........................................................................................6-1
http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
5/68
iv I-E96-443-1D
Table of Contents (continued)
Page
®
SECTION 6 - MAINTENANCE (continued)
PREVENTATIVE MAINTENANCE PROCEDURES .......................................................... 6-1CORRECTIVE MAINTENANCE PROCEDURES.............................................................. 6-1
SECTION 7 - REPAIR/REPLACEMENT PROCEDURES ...........................................................7-1INTRODUCTION .......................................................................................................... 7-1PROCEDURES............................................................................................................. 7-1
SECTION 8 - SUPPORT SERVICES..........................................................................................8-1INTRODUCTION .......................................................................................................... 8-1INSTRUCTION SUBSCRIPTION.................................................................................... 8-1REPLACEMENT PARTS................................................................................................ 8-1
APPENDIX A - APPLICATION EXAMPLES ..............................................................................A-1()ASI02, IMFBS01 AND IMASI03 .................................................................................. A-1
Two Wire 4-20 mA with System Common Reference............................................... A-1Four Wire 4-20 mA with System Common Reference.............................................. A-1Four Wire 4-20 mA No System Common Reference ................................................ A-2Single Ended Voltage with System Common Reference........................................... A-2Differential Voltage with No System Common Reference.........................................A-3
()ASI02 AND AMFBS01 ONLY.......................................................................................A-3 Two Wire 4-20 mA Isolated.................................................................................... A-3Four Wire 4-20 mA Isolated................................................................................... A-4
Differential Voltage (or mV) Isolated....................................................................... A-4 Thermocouple Isolated........................................................................................... A-5
RTD Isolated.......................................................................................................... A-5Special or Custom Signal.......................................................................................A-6
IMFBS01 ONLY............................................................................................................ A-6IMFBS01 Smart Transmitter.................................................................................. A-6
IMASI03 ONLY.............................................................................................................A-7IMASI03 Thermocouple ......................................................................................... A-7IMASI03 RTD ........................................................................................................ A-7
APPENDIX B - NRAI0_ PART DRAWING ................................................................................. B-1NRAI0_ PART DRAWING ..............................................................................................B-1
APPENDIX C - SPECIFICATION SHEETS................................................................................C-1SPECIFICATION SHEETS ............................................................................................C-1
APPENDIX D - CONDITIONER AND ISOLATOR PART DRAWING ........................................ D-1CONDITIONER AND ISOLATOR PART DRAWING .........................................................D-1
http://06sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://07sectxx.pdf/http://07sectxx.pdf/http://07sectxx.pdf/http://08sectxx.pdf/http://08sectxx.pdf/http://08sectxx.pdf/http://08sectxx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://bappendx.pdf/http://bappendx.pdf/http://cappendx.pdf/http://cappendx.pdf/http://dappendx.pdf/http://dappendx.pdf/http://06sectxx.pdf/http://dappendx.pdf/http://dappendx.pdf/http://cappendx.pdf/http://cappendx.pdf/http://bappendx.pdf/http://bappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://08sectxx.pdf/http://08sectxx.pdf/http://08sectxx.pdf/http://08sectxx.pdf/http://07sectxx.pdf/http://07sectxx.pdf/http://07sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
6/68
List of Figures
No. Title Page
I-E96-443-1D v
1-1. Nomenclature ........................................................................................................1-7
2-1. Printed Circuit Board Layout .................................................................................2-22-2. Typical Circuit Schematic ......................................................................................2-3
2-3. DIP Switch Codes...................................................................................................2-42-4. Printed Circuit Board Switch Legend......................................................................2-52-5. NRAI01 to () ASI02 or IMFBS01..............................................................................2-5
2-6. NRAI0_ to IMASI03 ................................................................................................2-73-1. Standard Equipment Location Numbering System .................................................3-23-2. Cabinet Interior, Front View with Side Walls Folded Out.........................................3-33-3. Cabinet Cross Section, Hardware and Zone Identification.......................................3-43-4. System Side Wiring Connections and Board Power Distribution .............................3-53-5. NRAI0_ and NRAO01 with NRCS01’s......................................................................3-64-1. Conditioner and Isolator, Calibration Potentiometer Locations (Top View)...............4-1
4-2. Conditioner & Isolator Pin Location and Identification (Bottom View)......................4-15-1. Troubleshooting Guide...........................................................................................5-2
5-2. Troubleshooting Guide (continued) ........................................................................5-35-3. Troubleshooting Guide (continued) ........................................................................5-47-1. Mounting Foot Release...........................................................................................7-2
A-1. Two Wire 4-20 mA with System Common Reference .............................................. A-1 A-2. Four Wire 4-20 mA with System Common Reference ............................................. A-1 A-3. Four Wire 4-20 mA No System Common Reference................................................ A-2
A-4. Single Ended Voltage with System Common Reference .......................................... A-2 A-5. Differential Voltage with No System Common Reference ........................................ A-3 A-6. Two Wire 4-20 mA Isolated.................................................................................... A-3 A-7. Four Wire 4-20 mA Isolated .................................................................................. A-4 A-8. Differential Voltage (or mV) Isolated....................................................................... A-4 A-9. Thermocouple Isolated.......................................................................................... A-5 A-10. RTD Isolated......................................................................................................... A-5
A-11. Special or Custom Signal ...................................................................................... A-6
A-12. IMFBS01 Smart Transmitter................................................................................. A-6 A-13. IMASI03 Thermocouple......................................................................................... A-7 A-14. IMASI03 RTD........................................................................................................ A-7B-1. NRAI01 Analog Input Manufacturing Drawing, Sheet 1 of 4................................... B-1
B-2. NRAI01 Analog Input Schematic Diagram, Sheet 2 of 4 ......................................... B-2B-3. NRAI01 Analog Input Part List, Sheet 3 of 4 .......................................................... B-3B-4. Analog Input Termination Assembly Connection Details, Sheet 4 of 4 ................... B-4C-1. Input Assignment and Configuration Data Sheet for NRAI0 (Front)........................ C-1C-2. Input Assignment and Configuration Data Sheet for NRAI0 (Back) ........................ C-2D-1. Analog Device ....................................................................................................... D-1
http://01sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://07sectxx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://bappendx.pdf/http://bappendx.pdf/http://bappendx.pdf/http://bappendx.pdf/http://cappendx.pdf/http://cappendx.pdf/http://dappendx.pdf/http://dappendx.pdf/http://cappendx.pdf/http://cappendx.pdf/http://bappendx.pdf/http://bappendx.pdf/http://bappendx.pdf/http://bappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://07sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://01sectxx.pdf/
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
7/68
vi I-E96-443-1D
No. Title Page
List of Tables
®
1-1. Glossary of Terms and Abbreviations..................................................................... 1-4
1-2. Reference Documents ............................................................................................ 1-51-3. Elsag Bailey Canada Reference Documents............................................................ 1-61-4. General Specifications ........................................................................................... 1-7
1-5. Mechanical and Input Specifications...................................................................... 1-81-6. Connection, Configuration, Power Requirement and Option Data........................... 1-9
2-1. NRAI0_, Cable & () ASI02/IMFBS01 Pin-out and Conductor Use Chart ..................2-62-2. NRAI0_, Cable & IMASI03 Pin-out and Conductor Use Chart ................................. 2-84-1. Conditioner and Isolator Calibration Procedure......................................................4-2
7-1. Termination Assembly Replacement ...................................................................... 7-18-1. Spare Parts List..................................................................................................... 8-2
http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://04sectxx.pdf/http://07sectxx.pdf/http://08sectxx.pdf/http://08sectxx.pdf/http://07sectxx.pdf/http://04sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
8/68
I-E96-443-1D vi
Safety Summary
GENERALWARNINGS
Units marked with EN-BC-606 must have alignment keys (AMP P/N
58327-1 Inter-Contact Plug) installed between contacts 15(S) and16(T) of the pre-terminated cable.
Improperly set DIP switches may result in equipment damage.Please read the instructions carefully before making connections or
applying power.
When voltage inputs are routed to the ()ASI02 or IMFBS01 slavemodules, the high impedance input will retain the signal in the event
of an open circuit. Bleeding resistors must be installed if timely badquality alarming is desired.
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
9/68
®
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
10/68
OVERVIEW
I-E96-443-1D 1 - 1
SECTION 1 - INTRODUCTION
OVERVIEW
This instruction is divided into 4 major sections, coveringoperation, installation, calibration. and troubleshooting of the
Analog Input Termination Assembly (NRAI0_). Each topic within these sections is divided into sub-sections with infor-mation specific to a particular application.
The analog input termination assembly is available in severa variations. The symbol _ (underscore) is used when referring toa feature that is common to all variations. When it is necessaryto refer to a particular model, a specific number is used. Referto NOMENCLATURE in this section for more information.
The NRAI0_ can be used with any of the ()ASI02, IMFBS01 orIMASI03 slave modules. The available capabilities and alterna-tives vary depending on which slave module is being used
The ASI02 slave is available in Network 90 and INFI 90 OPENform factors. They are functionally identical so far as the ter-mination assembly is concerned and are grouped by the () pre-fix.
A complete listing of product instructions for associated slaveand master modules is in REFERENCE DOCUMENTS .
The NRAO01 Analog Output Termination Assembly is comple-mentary to the NRAI0_. Refer to the documents listed in
ELSAG BAI LEY CANADA REFERENCE DOCUMENTS for com-plete information.
()ASI02
The ()ASI02 has 15 input channels to digitize voltage signalsfor use within the INFI 90 OPEN system. The NRAI0_ providesa corresponding 15 channels of field terminations. Each chan-nel of the NRAI0_ has socket pins for optional signal condition-ers and isolators.
When a channel of the NRAI0_ is being used in the straight
through mode (no isolator or conditioner), passive signal prep-aration for the analog input slave is performed. DIP switchesare used to select the signal preparation.
A broad range of conditioners and isolators are available forinstalled use in one or more channels in place of the jumper
boards supplied as standard. All conditioners and isolatorshave a common DIP switch setting. Refer to Figure 2-4 andFigures A-6, A-7, A-8, A-9, and A-10.
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
11/68
INTRODUCTION
INTENDED USER
1 - 2 I-E96-443-1D
®
IMFBS01
The IMFBS01 slave has the functionality of the ()ASI02 slave, but includes Elsag Bailey field bus (smart transmitter) sup-port.
When the smart transmitters are used in the analogpoint-to-point mode there is no functional change versus the()ASI02.
NOTE: Signal isolators do not pass the field bus FSK protocol and
therefore should not be installed when Elsag Bailey field bus com-
munication is required. Refer to Figure A-12.
IMASI03
The IMASI03 enhanced slave module has 16 isolated inputs,each individually able to digitize a broad range of signal types.
The use of the optional isolators is not generally required.
The NRAI0_ performs passive signal conditioning for theenhanced analog input slave module. DIP switches are used toselect the required conditions. Low level, thermocouple andRTD inputs are routed straight through to the slave. Refer toFigures A-13 and A-14.
The NRAI02 includes cold junction compensation and must beused when thermocouple inputs to the IMASI03 are required.
INTENDED USER
This manual is intended for use by:
• Prospective customers to answer their questions about thehardware design flexibility of the INFI 90 OPEN analoginputs.
• Instrument engineers or technicians for installation, optionand programming details.
• Maintenance personnel for ongoing use of the assemblies.
EQUIPMENT DESCRIPTION
The NRAI0_ consists of screw clamp terminations for 16 input channels, mounted onto a printed circuit board and installedin an extruded plastic channel, 109 mm (4 1/2 inches) wideand 610 mm (24 inches) long. The channel has mounting feet that can attach to standard DIN rails (U or C).
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
12/68
INTRODUCTION
FEATURES
I-E96-443-1D 1 - 3
FEATURES
The NRAI0_ features:
• In-line, cage clamp terminal blocks for all wiring connec-tions.
• DIP switch programming.
• Full power distribution with current limiting or fusing when necessary.
• Socket pins for optional signal conditioners and isolators.
• Connection to slave modules via pre-terminated cables.
Ribbon cable headers provide for connection to the NRCS01 which supports connection to NDCS03, NDIS02 or IISAC01
control stations and indicators. Refer to Figure 3-5, NRAI0_and NRAO01 with NRCS01's.
INSTRUCTION CONTENT / HOW TO USE
This manual has been arranged, indexed, and cross referencedto provide easy movement between related topics.
Most users will only need to refer to Section 2 - DESCRIPTIONAND OPERAT ION for the functional operation and use of theNRAI0_.
Control system design engineers should review Section 3 -
INSTALLATION before the detailed hardware design stage of aproject.
Personnel responsible for system maintenance and repairshould read and understand Section 5 - TROUBLESHOOTINGand Section 6 - MAINTENANCE when mis-operation is sus-pected. Section 7 - REPAIR/REPLACEMENT PROCEDURESand Section 8 - SUPPORT SERVICES should be referred toprior to replacing and returning any failed units.
Other than setting the DIP switches, the base NRAI0_ requiresno calibration unless the optional signal conditioners and iso-lators are installed. Refer to Section 4 - CALIBRATION .
EQUIPMENT APPLICATION
The NRAI0_ is intended to be used in systems:
• Using the digital termination assemblies,
• Requiring terminal block (screw clamp) connectiontechnology,
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
13/68
INTRODUCTION
GLOSSARY OF TERMS AND ABBREVIATIONS
1 - 4 I-E96-443-1D
®
• Requiring signal isolation,
• Having small numbers of signal ranges not supported by the ()ASI02, or
• Needing NDCS03/IISAC01 support with ASI/ASO slave
modules,
The NRAI01 is supported by the ()ASI02, IMFBS01 or IMASI03slave modules. The NRAI02, with cold junction compensation,is used if direct thermocouple inputs to the IMASI03 aredesired.
System cable part number L700741-1-(length) is required for
the ()ASI02 or IMFBS01 slave modules.
System cable part number L700743-1-(length) is required for the IMASI03 slave module.
GLOSSARY OF TERMS AND ABBREVIATIONS
Table 1-1. Glossary of Terms and Abbreviat ions
Term Definition
() (empty parenthesis) Used when statements are applicable to all variations of the unit.
_ (underscore) Used when a character may vary but there are differences between variations
that must be considered.
- (dash) Space holder, character not relevant to this instruction.
Cold Junction
Compensation
The measurement of the temperature and subsequent elimination of the millivolt
signals created between thermocouple wires and the terminal blocks they areconnected to.
Control Station Panel mounted array providing operator access to a software based manual/
automatic transfer station. Includes: process variable, set point and control out-
put indication, mode switching between manual/automatic/ratio or cascade and
bypass (backup) for the control output from the slave module.
DIP Dual Inline Pin arrangement.
DIP Switch Printed circuit board mounted miniature switch for the selection of specific func-
tionality.
DIN Deutsche Industrie Normen, German industrial standards and accepted global
standard.
Expander Bus Parallel communication bus between the Elsag Bailey master and I/O slave mod-
ules.
Field Bus A digital serial communication system connecting one or more smart transmitters
to the distributed control system.
Four Wire A transmitting device having two conductors dedicated to the measured signal
while receiving its power via two other conductors.
Isolator A device providing electrical isolation between its input, output and ground.
Jumper Board A printed circuit board having the single function of making a direct electrical con-
nection between two or more contacts.
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
14/68
INTRODUCTION
REFERENCE DOCUMENTS
I-E96-443-1D 1 - 5
REFERENCE DOCUMENTS
Mounting Rail A formed metal strip having standardized dimensions (DIN) that allow the mount-
ing of a wide variety of devices from various manufacturers.
Point-To-Point Wiring The process of manually connecting two or more electrical contact points with
single conductor wires.
Pre-Terminated Cable A multi conductor cable having pre-installed connectors, usually at both ends,
permitting efficient connection of large numbers of electrical signals in a reduced
time.
RTD Resistance Temperature Detector; a temperature sensitive resistor.
Screw Clamp Type of terminal requiring no ring or spade lug, providing high locking force and
excellent vibration resistance without damaging the conductor.
Signal Conditioner Electronic module that converts one signal range or type to another signal range
or type.
Slave Module A self contained module that accepts and responds to all instructions received
from a master module via the expander bus.
Socket Pin A spring-loaded socket that mounts directly into a printed circuit board to allow
easy removal and replacement of the installed device.
Straight Through Mode No signal conditioning or isolation being performed.
Terminal Block The mouldings and associated metal parts that form an insulated assembly for
the termination and/or continuation of electrical wiring.
Termination Assembly Field wire terminating devices featuring in-line terminal blocks and rail mounting.
Termination Module A cage mounted printed circuit board providing high density field wire termina-
tions.
Termination Unit A surface mounted printed circuit board providing field wiring terminations using
screw terminals.
Thermistor Like the RTD, a temperature sensitive resistor. Composed of sintered semicon-
ductor material which is best described as sensitive.
Two Wire A system in which the power to a transmitting device and the signal from thatsame device are carried by the same pair of wires.
Table 1-1. Glossary of Terms and Abbreviat ions (continued)
Term Definition
Tab le 1-2. Reference Documents
Document
NumberDocument
I-E93-902-1 Digital Control Station (NDCS03).
I-E93-906-7 Multi-Function Controller (NMFC03).I-E93-906-12 Multi-Function Controller (NMFC04).
I-E93-906-13 Multi-Function Controller (NMFC05).
I-E93-912-10 Analog Slave Input Module (NASI02).
I-E96-116 Digital Indicating Station (NDIS02).
I-E96-117 Analog Control Station (IISAC01).
I-E96-200 Function Code Application Manual.
I-E96-201 Multi-Function Processor (IMMFP01).
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
15/68
INTRODUCTION
ELSAG BAILEY CANADA REFERENCE DOCUMENTS
1 - 6 I-E96-443-1D
®
ELSAG BAILEY CANADA REFERENCE DOCUMENTS
I-E96-202 Multi-Function Processor (IMMFP02).
I-E96-203 Multi-Function Processor (IMMFP03).
I-E96-211 Multi-Function Controller (IMMFC03).
I-E96-212 Multi-Function Controller (IMMFC04).
I-E96-213 Function Controller (IMMFC05).
I-E96-301 Analog Slave Input Module (IMASI03).
I-E96-302 Field Bus Slave Module (IMFBS01).
I-E96-304 Analog Slave Input Module (IMASI02).
I-E96-500 Site Planning, Preparation and Equipment Installation.
Tab le 1-2. Reference Documen ts (continued)
Document
NumberDocument
Table 1-3. Elsag Bai ley Cana da Reference Docum ents
Document
NumberDocument
I-E97-443-3 Digital Input Termination Assembly (NRDI0_).
I-E97-443-4 Digital Output Termination Assembly (NRDO01).
I-E97-443-5 Relay Output Termination Assembly (NRDO02).
I-E97-443-2 Analog Output Termination Assembly (NRAO01).
HARDWARE/COMMUNICATIONS CHECKOUT
DOCUMENT.
DL700783_,SHTS 1-4
Analog Input Termination Assembly Part Drawing.
DL700837 Conditioner and Isolator Part Drawing.
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
16/68
INTRODUCTION
NOMENCLATURE
I-E96-443-1D 1 - 7
NOMENCLATURE
SPECIFICATIONS
Figure 1-1. Nomenclature
Table 1-4. General Specif ications
Nomenclature
(Part No.) (Model)
NRAI0_
(L700783-_) (990598)
Name Analog Input Termination Assembly.
Environmental
Operating Temperature
Relative Humidity
0°C to 70°C
(32 deg. F to 158°F)
5% - 90% up to 55°C (131°F) (non-condensing).
5% - 40% up to 70°C (158°F) (non-condensing).
Elsag Bailey equipment should be operated and stored in a non-corrosive
environment.
Cooling Requirements No cooling is necessary when enclosed in cabinets and operated within the
stated environmental limits.
Certification All assemblies are CSA certified as process control equipment (C22.2 No.142)
for use in ordinary (non-hazardous) locations.
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
17/68
S P E C I F I C A T I ON S
1 -8
I -E 9 6 -4 4 3 -1 D
Table 1-5. Mechanical and Input Specif ications
Nomenclature
(Part No.)
(Model)
Name
Dimensions
mm (inches) Mounting
Slave
Connecti-
vity
Cable
Type
Cable
Key
Slot
Loc’n
I/O
Quan
-tity
Input
Specifications
Length Width Height Height
on Rail
Input Slave Option
condit
mount
NRAI01
(L700783-1)
(990598)
Analog Input
Termination
Assembly
610
(24)109
(4.29)
74.6
(2.95)
82.6
(3.26)
DIN U
(35 mm)
or DIN C
(32 mm)
Rail
NASI02
IMASI02
IMFBS01
L700741-
(Length)
Round
Cable
15/16
or S/T
15 Refer to Product
Specification or
Instruction
I-E93-912-10 (NASI02)
I-E96-302 (IMFBS02)
I-E96-304 (IMASI02)
Refer
COND
TOR P
consu
Engin
inform
Gener
240 V
protec
transf
Worst
IEEE
to +85
Potted
enviro*
IMASI03
L700743-
(Length)
Round
Cable
16 Refer toProduct
Specification or
Instruction
I-E96-301
(IMASI03)
Them
be use
more
condit
be red
**NRAI02
(L700783-2)
(N/A) Analog
Input
Termination
Assembly With
Themistors
**
IMASI03
**
L700743-
(Length)
Round
Cable
***16 ***
Refer to Product
Specification or
Instruction
I-E96-301
(IMASI03)
***
Most c
would
isolate
Custo
could
first 15
* No cold junction compensation for thermocouple conversion by the IMASI03.
** Can be used with NASI02, IMSI02 and IMFBS01 if desired, L700741-1 cable must be used.*** 15 inputs and same specifications as with NRAI01 when used with NASI02, IMSI02 or IMFBS01 slave modules.
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
18/68
S P E C I F I C A T I ON S
I -E 9 6 -4 4 3 -1 D
1 -9
Table 1-6. Connection, Configurat ion, Pow er Requirement an d Option Data
Nomenclature
(Part No.)
(Model)
Name
Wire Size
(Qty./Size)
Connections
Number of Blocks per
Electrical Point
Switch Settings +24 Vdc Current Requirements
Field Power Shield S1 to S16
System versus
Field Powered
S17 to S32 ***
Signal
Preparation
Total
Assembly
S1 to S16 Conditioners
and Isolator=C1 =C2
NRAI0_
(700783-_)
(990598)
Analog Input
Termination
Assembly
#14-#22
AWG
(1 / #14)
(2 / #16)
(3 / #18)
(5 / #20)
(7 / #22)
2
(+’ve)
2
(-’ve)
1
(C
compen-
sation)
1(SH
shield)
4
(+24 V)
4
(COM)
3 One single
pole double
throw switch
per input
selects two
wire signal
versus 24 Vdc
system power
to the
+ terminal:
C1 = two wiresignal
C2 = 24 Vdc to
+ terminal
Two single
pole double
throw
switches per
input.
Pole 1 selects
current to
voltage (250
ohm resistor)
conversion:
1C1 =resistor in.
Pole 2 selects
system
common
reference:
2C1 = floating
input,
2C2 = system
common
reference
used.
Minimum
4mA
Typical
300 mA
Maximum
900 mA
0 MA
(field
powered)
Typical
15 mA**
Maximum
24 mA**
Typical
40mA**
Maximum
60 mA**
(4-20 mA
2 wire only)
* When conditioners and isolators are used, set S1 to S16 = C1, S17 to S32 = 1C1, 2C2.** The values shown are for a single input channel. All 15 or 16 channels must be summed to arrive at the total power requirements.*** The function of S32 pole 1 is reversed on REV.A boards only.
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
19/68
®
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
20/68
INTRODUCTION
I-E96-443-1D 2 - 1
SECTION 2 - DESCRIPTION AND OPERATION
INTRODUCTION
This section provides sufficient information to allow users tounderstand the use of the assembly, document instrumenta-tion wiring connections, determine and document DIP switchconfigurations, and perform basic problem solving.
There is a considerable variety of hardware combinations pos-sible. Detailed descriptions and diagrams are used to illustrateas many combinations as possible.
FUNCTIONAL OPERATION
The NRAI0_ consists of a circuit repeated 16 times. The first 15
circuits have socket pins for the optional isolators and condi-tioners. Removable jumper boards, P/N WTL 990756, are pro-
vided with the base unit. Optional jumper boards, P/N WTL990757, are available to provide input protection againstsurges as defined by IEEE C37.90a - 1974 Surge WithstandCapability (SWC) Tests. The sixteenth circuit, which is onlyused with the IMASI03 slave module, has no socket pins.
Refer to Figures 2-5, 2-6 and 3-5 for cable connection details.
Refer to Figure 3-4 for power, common, and shield drain con-nection details.
24 Vdc power is distributed along two paths. The presence opower on each path is indicated by an LED being on g r een On the first path DS1 indicates that power is available for two
wire devices, the power leaving the termination assembly beingcurrent limited to about 170 mA per channel by 150 Ω resis-tors. The second power path is routed through fuse F1 tosocket pin 3 of the 15 conditioner and isolator mounting posi-tions, with DS2 indicating the fuse status.
The total power requirements are determined by summingindividual power requirements for each input channel per
Table 1-6.
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
21/68
DESCRIPTION AND OPERATION
FUNCTIONAL OPERATION
2 - 2 I-E96-443-1D
®
FIELD SIDE SYSTEM SIDE
REFER TO SECTION 3 - INSTALLATION
CIRCUIT NO. 1 -
TERMINAL BLOCKS FOR
dc COMMON - REFER TO FIGURE 3-4.
CIRCUIT NO. 2 +TERMINAL BLOCKS FOR
24 Vdc POWER.
CIRCUIT NO. 3REFER TO FIGURE 3-4.
CIRCUIT NO. 4P3 RIBBON CABLE
CIRCUIT NO. 5REFER TO FIGURE 3-5.
CIRCUIT NO. 6
CIRCUIT NO. 7 P4RIBBON CABLE
REFER TO FIGURE 3-5.
CIRCUIT NO. 8
USER’S
INSTRUMENTATION
WIRING ON THIS SIDE
SEE DETAILS IN
FIGURE 2-2 AND
APPENDIX A - APPLICA-
TION EXAMPLES
LOCATION
LABELS AND
BRIEF
INSTRUCTIONS
P1
CARD EDGE CONNECTION FOR
PRE-TERMINATED CABLE TO SLAVE
MODULE REFER TO FIGURES 2-5
AND 2-6.
CIRCUIT NO. 9 SH TERMINAL BLOCKS FOR
SHIELD DRAIN.
CIRCUIT NO. 10
CIRCUIT NO. 11 P5 RIBBON CABLE - REFER TO FIGURE 3-5.
CIRCUIT NO. 12
CIRCUIT NO. 13
P6 RIBBON CABLE - REFER TO FIGURE 3-5.
CIRCUIT NO. 14
CIRCUIT NO. 15
CIRCUIT NO. 16
Figure 2-1. Printed Circuit Board Lay out
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
22/68
DESCRIPTION AND OPERATION
DIP SWITCH FUNCTIONALITY
I-E96-443-1D 2 - 3
NOTES:
1. The NN refers to circuit numbers 1 to 16.
2. The dual +'ve and -'ve terminals are supplied to allow indepen-
dent marshalling. Refer to Figures A-1 through A-14 for examples.
3. The C terminal becomes the third or compensating lead of an
RTD or thermocouple cold junction compensation.
4. The SH terminal is for cable shields.
5. The terminal is used with the optional surge withstand
jumper board.
DIP SWITCH FUNCTIONALITY
S1 C1 sets the input for 4-wire transmitter operation and S1C2 is for 2-wire transmitter operation.
S17 1C1 allows voltage inputs. S17 1C2 connects a precisionresistor for conversion from 4 to 20 mA dc to 1 to 5 Vdc. S17
2C1 is for differential inputs. S17 2C2 provides a system com-mon reference.
When voltage inputs are routed to the ()ASI02 OR IMFBS01slave modules, consideration of the effect of an open circuit isnecessary. The high impedance of the input circuit will holdthe residual voltage indefinitely and the fault monitoringinherent in the system will not be triggered.
Figure 2-2. Typical Circui t Schema tic
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
23/68
DESCRIPTION AND OPERATION
DIP SWITCH SETTINGS
2 - 4 I-E96-443-1D
®
If the voltage input has an elevated zero, such as a 1-5 Vdc sig-nal, a bleeding resistor installed between the extra +ve and -veterminals will drain the voltage to 0 Vdc and a Bad Quality alarm will be triggered. A 4.7 MΩ, 1/4 W resistor is recom-mended for this application. Refer to Figures A-4 and A-5.
If the voltage input has 0 Vdc as a valid part of its signal rangeor if it is desirable to f a i l h i g h , special consideration isrequired. Please consult your Elsag Bailey system engineer, or refer to Section 8 - SUPPORT SERVICES .
The IMASI03 slave and the optional signal isolators have built-in open circuit detection so no special consideration isrequired for them.
If conditioners and isolators are used, the switch settings must be set for 4-wire, voltage, and system common reference (S1C1, S17 1C1 and S17 2C2).
DIP SWITCH SETTINGS
Figure 2-3. DIP Sw itch Codes
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
24/68
DESCRIPTION AND OPERATION
PHYSICAL OPERATION
I-E96-443-1D 2 - 5
The settings are summarized on the P.C. board artwork asfollows:
Examples of all commonly used settings are shown in Figure A-1 to Figure A-14.
PHYSICAL OPERATION
The analog input termination assembly can be connected to a variety of slaves and other hardware options. The following fig-ures detail connection to the slave modules. Refer to OTHEREQUIPMENT INTERFACE in Section 3 and Figure 3-5 for
additional information concerning connection to other devicessuch as the NRCS01 for NDCS03 and IISAC01 support.
Figure 2-4. Printed Circuit Board Sw itch Legend
Figure 2-5. NRAI01 to () ASI02 or IMFBS01
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
25/68
DESCRIPTION AND OPERATION
PHYSICAL OPERATION
2 - 6 I-E96-443-1D
®
NOTES:
1. Traces A to S on the slave, or even numbers on the NRAI, are
on the component side.
2. Traces 1 to 15 on the slave, or odd numbers on the NRAI are on
the solder side.
NOTES: The following traces on the NRAI01 Termination Assembly
are not used when the ()ASI02 or IMFBS01 slave modules are
employed:
1. 1 and 2 are the thermistors for cold junction compensation.
2. 5, 6, 11, 12, 17, 18, 23, 24, 29, 30, 35, 36, 41, 42 and 47 are the
compensation conductors for RTD and TC inputs.
3. 48, 49 and 50 are for analog input channel 16.
Table 2-1. NRAI0_, Cable & () ASI02/ IMFBS01 Pin-out and
Condu ctor Use Cha rt
Slave
Signal
Slave
Trace
NRAI01
Trace
NRAI01
Signal
AI-1-
AI-2-
AI-3-
AI-4-
AI-5-
AI-6-
AI-7-
AI-8-
AI-9-
AI-10-
AI-11-
AI-12-
AI-13-
AI-14-AI-15-
AI-1+
AI-2+
AI-3+
AI-4+
AI-5+
AI-6+
AI-7+
AI-8+
AI-9+
AI-10+
AI-11+
AI-12+
AI-13+AI-14+
AI-15+
1
2
3
4
5
6
7
8
9
10
11
12
13
1415
A
B
C
D
E
F
H
J
K
L
M
N
PR
S
4
7
10
13
16
19
22
25
28
31
34
37
40
4347
3
8
9
14
15
20
21
26
27
32
33
38
3944
45
AI-1-
AI-2-
AI-3-
AI-4-
AI-5-
AI-6-
AI-7-
AI-8-
AI-9-
AI-10-
AI-11-
AI-12-
AI-13-
AI-14-AI-15-
AI-1+
AI-2+
AI-3+
AI-4+
AI-5+
AI-6+
AI-7+
AI-8+
AI-9+
AI-10+
AI-11+
AI-12+
AI-13+AI-14+
AI-15+
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
26/68
DESCRIPTION AND OPERATION
PHYSICAL OPERATION
I-E96-443-1D 2 - 7
The NRAI02 must be used if thermocouple inputs to theIMASI03 are desired.
Figure 2-6. NRAI0_ to IMASI03
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
27/68
DESCRIPTION AND OPERATION
PHYSICAL OPERATION
2 - 8 I-E96-443-1D
®
Table 2-2. NRAI0_, Cable & IMASI03 Pin-out and
Condu ctor Use Char t
IMASI03
Signal
IMASI03
Trace
NRAI02
Trace
NRAI02
Signal
RTD -
AI 1 +
AI 1 COM
AI 2 -
AI 3 +
AI 3 COM
AI 4 -
AI 5 +
AI 5 COM
AI 6 -
AI 7 +
AI 7 COM
AI 8 -
AI 9 +AI 9 COM
AI 10 -
AI 11 +
AI 11 COM
AI 12 -
AI 13 +
AI 13 COM
AI 14 -
AI 15 +
AI 15 COM
AI 16 -
RTD +
AI 1 -
AI 2 COMAI 2 +
AI 3 -
AI 4 COM
AI 4 +
AI 5 -
AI 6 COM
AI 6 +
AI 7 -
AI 8 COM
AI 8 +
AI 9 -
AI 10 COM
AI 10 +
AI 11 -AI 12 COM
AI 12 +
AI 13 -
AI 14 COM
AI 14 +
AI 15 -
AI 16 COM
AI 16 +
1
2
3
4
5
6
7
8
9
10
11
12
13
1415
16
17
18
19
20
21
22
23
24
25
26
27
2829
30
31
32
33
34
35
36
37
38
39
40
41
4243
44
45
46
47
48
49
50
1
3
5
7
9
11
13
15
17
19
21
23
25
2729
31
33
35
37
39
41
43
45
47
49
2
4
68
10
12
14
16
18
20
22
24
26
28
30
32
3436
38
40
42
44
46
48
50
RTD -
AI 1 +
AI 1 COM
AI 2 -
AI 3 +
AI 3 COM
AI 4 -
AI 5 +
AI 5 COM
AI 6 -
AI 7 +
AI 7 COM
AI 8 -
AI 9 +AI 9 COM
AI 10 -
AI 11 +
AI 11 COM
AI 12 -
AI 13 +
AI 13 COM
AI 14 -
AI 15 +
AI 15 COM
AI 16 -
RTD +
AI 1 -
AI 2 COMAI 2 +
AI 3 -
AI 4 COM
AI 4 +
AI 5 -
AI 6 COM
AI 6 +
AI 7 -
AI 8 COM
AI 8 +
AI 9 -
AI 10 COM
AI 10 +
AI 11 -AI 12 COM
AI 12 +
AI 13 -
AI 14 COM
AI 14 +
AI 15 -
AI 16 COM
AI 16 +
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
28/68
DESCRIPTION AND OPERATION
PHYSICAL OPERATION
I-E96-443-1D 2 - 9
NOTES:
1. On the IMASI03, traces 1 to 25 are on the component side.
2. Traces 26 to 50 are on the solder side.
3. On the NRAI0_, odd numbered traces are on the component
side.
4. Even numbered traces are on the solder side.
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
29/68
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
30/68
INTRODUCTION
I-E96-443-1D 3 - 1
SECTION 3 - INSTALLATION
INTRODUCTION
This section explains the standard Elsag Bailey installationpractices as well as providing the basic information for thoseinstallations where special mounting is required.
SPECIAL HANDLING
Preassembled termination cabinets should be handled in
accordance with the instructions found in the S i t e Pl a n n i n gPr e p a r a t i o n a n d E qu i pm en t I n s t a l l a t i o n I n s t r u c t i o n .
Loose termination assemblies are shipped in foam paddedcardboard cartons. No special handling is required.
UNPACKING AND INSPECTION
The termination assemblies should be inspected for damageand/or broken components. Although the assemblies are indi-
vidually packaged in foam padded boxes, some bending ofcomponents may occur during shipment. Most of these typesof problems can be corrected by the user. Physical breakageshould be reported to the shipping company.
The Elsag Bailey part drawing is listed in ELSAG BAIL EY CANADA REFERENCE DOCUMENTS in Section 1, and should be
obtained if detailed inspection of components is necessary.
LOCATION CONSIDERATIONS
As with all electrical connections, the termination assembliesshould be mounted in environments that are relatively freefrom conductive dusts and corrosive gases. Refer to I SA Env ir o nme n t a l S t a n d a r d S 7 1 .0 4 -1 9 8 5 . The severity level should
be no worse than a good G2.
The assemblies have no exposed hazardous conductors and nospecial enclosures are needed.
SAFETY CONSIDERATIONS
No special safety considerations are necessary.
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
31/68
INSTALLATION
SETUP AND PHYSICAL INSTALLATION
3 - 2 I-E96-443-1D
®
SETUP AND PHYSICAL INSTALLATION
Typical Elsag Bailey Termination Cabinet Arrangement
The termination assemblies are oriented vertically on the DIN
mounting rails. The assemblies are inverted when field wiringis to be on the right hand side.
The vertical orientation allows field instrumentation wire or cable entering via the top or bottom of a cabinet, to be directly routed to the appropriate terminal block.
The most accessible areas, at the front of each side, and at thecentre of the facing surface, are available for field I/O wiring.Fifteen cm (six inches) of support space is available next to thedoor on each side. If desired, plastic wire trays can be installed
with five cm (two inches) allowed between the plastic tray andthe field terminals for wire tag visibility.
The standard Elsag Bailey cabinet has 10 divisions from top to bottom called rows and 4 location designations A to D, startingat the front left, called zones. Zones C and D are eliminated
when front access (wall mounting) cabinet options are used.Refer to Figure 3-2. Cabinet Interior and Figure 3-3. Cabinet Cross Section, for a diagrammatic representation.
The vertically oriented rail mounting system, combined withthe variable lengths of the assemblies, has led to a modifica-tion of the standard equipment location numbering system.Positions are used rather than rows and each zone has beensubdivided into (for example) A and A1. An example of the
complete location numbering system is below.
Explanation
Figure 3-1. Stand ard Equipment Location Numbering Sys tem
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
32/68
INSTALLATION
SETUP AND PHYSICAL INSTALLATION
I-E96-443-1D 3 - 3
Figure 3-2. Cabin et Interior, Front View w ith Side Walls Folded Out
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
33/68
INSTALLATION
CUSTOM OR SPECIAL
3 - 4 I-E96-443-1D
®
CUSTOM OR SPECIAL
The assemblies can be mounted on rails in almost any enclo-sure and orientation. When sufficient mounting width is avail-able, horizontal orientation may be used.
Figure 3-2 is an approximate scale representation of a stan-dard Elsag Bailey cabinet showing relative sizes of assembliesand the position numbering that would be used. Zone A shows3 type NRAI0_ input assemblies, zone B1 shows 3 typeNRAO01 output assemblies.
WIRING CONNECTIONS AND CABLING
Each terminal block is clearly marked with black lettering on a white clip-on tag. Several connections have compound termi-nal blocks connected by printed circuit board traces. Thesecompound blocks allow the jumping of wires while maintain-
Figure 3-3. Cabinet Cross Section, Hard w are and Zone Identi f ication
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
34/68
INSTALLATION
WIRING CONNECTIONS AND CABLING
I-E96-443-1D 3 - 5
ing a single wire in any one clamp. All terminal block functionsare uniquely marked. The cage clamp technology provides afast and secure means of wiring connection such that crimpedlugs or ferrules are not necessary.
In addition to the pre-terminated cable to the slave, three wir-
ing connections are required on the system side of the termi-nation assembly. When the optional jumper boards, P/N WTL990757 are used, a fourth connection is required.
A nominal +24 Vdc and dc common signal zero reference arerequired. Refer to Table 1-6. Connection, Configuration, PowerRequirements and Option Data for voltage tolerance, currentrequirements and necessary dc common grounding character-istics.
Figure 3-4. System Side Wiring Connections and B oard Pow er Distr ibu tion
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
35/68
INSTALLATION
WIRING CONNECTIONS AND CABLING
3 - 6 I-E96-443-1D
®
Field instrument cable shielding is drained by connecting thesystem side SH terminals to an appropriate ground with suffi-ciently low impedance to drain the EMF noise expected fromthe plant environment.
The fourth connection is between the terminal and chassis
ground to provide a low impedance path to ground for theunwanted incoming surges induced onto the input signal con-ductors.
Figure 3-5. NRAI0_ an d NRAO01 w ith NRCS01’s
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
36/68
INSTALLATION
OTHER EQUIPMENT INTERFACE
I-E96-443-1D 3 - 7
OTHER EQUIPMENT INTERFACE
The supplied jumper boards can be replaced with either theoptional conditioners and isolators or custom designed daugh-ter boards allowing considerable interface flexibility. Refer toFigure A-11.
The NRAI0_ can be interfaced to NDCS03, IISAC01 andNDIS0_ via the NRCS01 Termination Assembly. Refer to Figure3-5. When the IMASI03 is employed, keep in mind that theNDCS03 and IISAC01 can only accommodate 1-5 volt signalsfor direct bar graph display in the bypass mode.
PRE-OPERATING ADJUSTMENTS
Every used input should be reviewed and DIP switches setand/or conditioners or isolators installed as required.
The converters and isolators are pre-calibrated by the manu-facturer. However, for maximum accuracy, the calibrationshould be checked as outlined in Section 4 during initiainstallation and periodically as outlined in Section 6.
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
37/68
®
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
38/68
INITIAL CALIBRATION
I-E96-443-1D 4 - 1
SECTION 4 - CALIBRATION
INITIAL CALIBRATION
The base NRAI0_ Termination Assembly requires no calibra-tion. Proper setting of the DIP switches and proper configura-tion of the associated slave and processor modules isnecessary.
The optional conditioners and isolators are calibrated by themanufacturer.
Should the calibration of the conditioners drift with time, theycan be adjusted using the potentiometers located beneath thetop label.
It is recommended that a bench or test set up be used whendoing the re-calibration of the conditioners and isolators.
Peel back the top label, and refer to Figure 4-1.
Figure 4-1. Condit ioner and Isolator,
Cal ibra tion Potentiometer Locations (Top View )
Figure 4-2. Condit ioner & Is olator Pin Location and Identi f ication (Bottom View )
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
39/68
CALIBRATION
CHECKOUT
4 - 2 I-E96-443-1D
®
CHECKOUT
All termination assemblies are factory checked for short cir-cuits, open circuits, and functional components (DIP switches,etc.).
Termination assemblies installed in cabinet assemblies or racks by Elsag Bailey are 100% checked in conjunction withtheir respective slave modules. Refer to the Hardware/Com-munications Checkout Document listed in ELSAG BAILEY CANADA REFERENCE DOCUMENT S in Section 1.
IN-SERVICE CALIBRATION
In-service calibration is not recommended.
Table 4-1. Condit ioner and Isolator Cal ibration Procedu re
1 Determine the desired input type and span and obtain test equipment able to sim-
ulate 0 and 100% input.
1.1 Ensure that the model being used is appropriate for the desired input span.
2 Connect power supply, signal source and voltmeter as outlined in Figure 4-2.
3 Set the signal source at zero (0%) input; adjust the zero potentiometer until 1 volt(or 0 volts, depending on output range) is seen at the output.
4 Set the signal source to full scale (100%) input; adjust the span potentiometer until
5 volts (or 10 volts, depending on output range) is seen at the output.
5 Repeat steps 3 and 4 as required.
6 Set the signal source to 3 volts; check that the output is 12 mA (or 3 volts depend-
ing on output range). The isolator should be replaced if half scale accuracy is not
acceptable.
7 The conditioner or isolator is now ready for installation on to the termination
assembly.
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
40/68
INTRODUCTION
I-E96-443-1D 5 - 1
SECTION 5 - TROUBLESHOOTING
INTRODUCTION
As an essentially passive device, it is unlikely that the termina-tion assembly will be the source of an equipment failure. Verifythat the procedures outlined in Section 6 have been per-formed.
Any personnel performing troubleshooting should be familiar with both the hardware and software aspects of the systemand related field devices.
ERROR MESSAGES AND CORRECTIVE ACTION
Error messages pertaining to system inputs and outputs are
reported within the status bytes and error codes of the appli-cable controller or processor module. Refer to the REFERENCE DOCUMENT S in Section 1 of this manual to determinethe appropriate controller or processor module instruction
book.
When operator interface stations are provided, the I90 Statusdisplays, which translate the module status bytes into textmessages, allow operators or maintenance personnel to iden-tify specific point malfunctions.
PROBLEM DETERMINATION AND VERIFICATION PROCEDURES
In an industrial setting there may be a variety of causes forequipment malfunction. The age of a device, the quality of theenvironment (including extreme heat, temperature swingscorrosive gases, and conductive dusts) and of course, humanerror and accidents.
As previously mentioned, the Elsag Bailey system can assist inthe location of a problem at a particular slave or input. Keep inmind that the termination assembly is the division betweenfield equipment and the DCS software (configuration), so bothmust be considered when pinpointing a problem.
TROUBLESHOOTING GUIDE
The following guide is intended to assist in troubleshooting bydetailing the areas within the Elsag Bailey system that should
be considered.
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
41/68
TROUBLESHOOTING
TROUBLESHOOTING GUIDE
5 - 2 I-E96-443-1D
F i g u r e
5 - 1 .
T r o u
b l e s
h o o
t i n g
G u
i d e
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
42/68
TROUBLESHOOTING
TROUBLESHOOTING GUIDE
I-E96-443-1D 5 - 3
F i g u r e
5 - 2 .
T r o u
b l e s
h o o
t i n g
G u
i d e
( c o n
t i n u
e d )
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
43/68
TROUBLESHOOTING
TROUBLESHOOTING GUIDE
5 - 4 I-E96-443-1D
F i g u r e
5 - 3 .
T r o u
b l e s
h o o
t i n g
G u
i d e
( c o n
t i n u e
d )
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
44/68
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
45/68
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
46/68
INTRODUCTION
I-E96-443-1D 7 - 1
SECTION 7 - REPAIR/REPLACEMENT PROCEDURES
INTRODUCTION
The base termination assembly has no active components andhas been carefully designed to tolerate as many field wiringinconsistencies as possible. Without the optional conditionersand isolators, incorrect field wiring or DIP switch settings canresult in damage to a connected slave module.
Inadvertent connection of a supply voltage greater than 48 Vdc will result in the destruction of one or both power supply sta-tus LED's DS1 and DS2. Damage to isolators and conditionersmay also occur if the incorrect voltage remains connected foran extended period.
The optional conditioners and isolators provide protection tothe input of up to 240 Vac for limited time durations. Refer tothe Isolator Procedures in Section 4 - CALIBRATION .
PROCEDURES
Refer to Section 5 - TROUBLESHOOTING before replacingShould replacement of the assembly be necessary, the mostimportant connections to check are the +24 and COM. Theseconnections are often in a daisy chain arrangement and dis-connecting them could result in the loss of power to otherfunctioning termination assemblies.
The daisy chaining done by Elsag Bailey is normally in a loopso that no power loss will occur if only a single terminationassembly is removed. Refer to the p ow er w i r i n g d r a w i n g ssupplied with your system to verify the wiring scheme used.
To replace the termination assembly, follow Table 7-1.
Table 7-1. Termin ation Assemb ly Replacement
1. Obtain a suitable replacement termination assembly.
1.1 Ensure the availability of an appropriate replacement fuse.
2. Remove any cables connected to P1, P3, P4, P5 and P6.
3. Tag and disconnect all connections to the field side of the termination assembly.
4. Disconnect and insulate the +24, COM and SH (shield) wiring.
5. Remove the termination assembly using a medium flat blade screwdriver at
each of the four mounting feet. Refer to Figure 7-1. Mounting Foot Release.
6. Set all DIP switches on the replacement assembly to match the removed unit.
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
47/68
REPAIR/REPLACEMENT PROCEDURES
PROCEDURES
7 - 2 I-E96-443-1D
®
.
6.1 Move any optional conditioners and isolators to the replacement assem-
bly, ensuring any thermocouple converters have a cold junction compen-
sating thermistor mounted between the extra +’ve and C terminals.
6.2 Install F1 if required.
7. Install the replacement assembly by ensuring that each of the four feet engageon the system side, then pivot the field side in until all feet have latched into
place.
8. Reconnect the system side +24, COM and SH wiring.
9. Reconnect all field side wiring.
10. Reconnect all system side cabling.
11. Verify proper operation of inputs. Refer to Figure 5-1. Troubleshooting Guide.
Figure 7-1. Mountin g Foot Release
Table 7-1. Termina tion Assemb ly Replacement (continued)
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
48/68
INTRODUCTION
I-E96-443-1D 8 - 1
SECTION 8 - SUPPORT SERVICES
INTRODUCTION
Elsag Bailey is ready to help in the use, application and repairof its products. Contact your nearest sales office to makerequests for sales, applications, installation, repair, overhauland maintenance contract services.
If it necessary to return an Elsag Bailey product for repair(warranty or chargeable) please contact the Return MaterialsDepartment for a reference number. Obtaining and using thisreference number on shipping documentation and correspon-dence will allow us to provide the fastest possible service.
INSTRUCTION SUBSCRIPTION
Elsag Bailey offers the service of supplying Registered Cata-logue And Product Instruction Set manuals to Elsag Baileycustomers. This set of manuals incorporates all of the litera-ture relating to all Elsag Bailey products and systems equip-ment.
These registered manuals are serialized and automaticallyupdated with new literature every three months. Elsag Baileycontrols will track the set(s) of manuals and supply detailedinstructions for the insertion of new or replacement materials
with each submission of updates.
Complete form LEC 1500-1190 and forward to the InstructionBook Department to order a new set of registered manuals. Arenewal notice will be sent to registered manual holders for theupdate services prior to the expiry date.
REPLACEMENT PARTS
Most parts used on the termination assemblies are widelyavailable through industrial electronic component suppliersRefer to the parts list included in the part drawing set under
Appendix B - NRAI0_ PART DRAWING .
When making repairs at your facility, replacement parts can be ordered from an Elsag Bailey office. Provide this informa-tion:
1. The nomenclature and complete part number of the prod-uct requiring parts.
2. Part description, part number, and quantity.
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
49/68
SUPPORT SERVICES
REPLACEMENT PARTS
8 - 2 I-E96-443-1D
®
3. Elsag Bailey instruction manual number, page number,and reference figure that identifies the part.
When ordering standard parts from an Elsag Bailey office, usepart numbers and descriptions from Table 8-1.
Table 8-1. Spare Parts List
Description ComponentPart Number
Elsag Bailey Alternate
Fuse, 3.0 Amp F1 L700723-13000 GMA-3A
Jumper Board X1 to X15 L700837-B00000 WTL990599/63
Cond./Isol. X1 to X15 L700837-______ 7B (Various)
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
50/68
()ASI02, IMFBS01 AND IMASI03
I-E96-443-1D A - 1
APPENDIX A - APPLICATION EXAMPLES
()ASI02, IMFBS01 AND IMASI03
Two Wire 4-20 mA with System Common Reference
Two wire transmitter, 24 Vdc system powered:
S1 TO S16 = C2S7 TO S32 = 1C2, 2C2
Four Wire 4-20 mA with System Common Reference
Four wire isolated by 120 Vac:
S1 TO S16 = C1S17 TO S32 = 1C2, 2C2
Figure A-1. Tw o Wire 4-20 mA w ith System Common Reference
Figure A-2. Four Wire 4-20 mA w ith System Common Reference
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
51/68
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
52/68
APPLICATION EXAMPLES
()ASI02 AND AMFBS01 ONLY
I-E96-443-1D A - 3
Differential Voltage with No System Common Reference
Differential voltage input:
S1 TO S16 = C1S17 TO S32 = 1C1, 2C1
()ASI02 AND AMFBS01 ONLY
Two Wire 4-20 mA Isolated
Two wire transmitter, 24 Vdc system powered with optiona
isolator:
S1 TO S16 = C1S17 TO S32 = 1C1, 2C2
Figure A-5. Differential Voltage w ith No Sys tem Common Reference
Figure A-6. Tw o Wire 4-20 mA Isolated
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
53/68
APPLICATION EXAMPLES
()ASI02 AND AMFBS01 ONLY
A - 4 I-E96-443-1D
®
Four Wire 4-20 mA Isolated
Four wire transmitter, usually separately powered by 120 Vac, with optional isolator:
S1 TO S16 = C1S17 TO S32 = 1C1, 2C2
Differential Voltage (or mV) Isolated
Differential voltage (or mV) input with signal conditioner:
S1 TO S16 = C1S17 TO S32 = 1C1, 2C2
Figure A-7. Four Wire 4-20 mA Isolated
Figur e A-8. Differen tia l Voltage (or mV) Isolat ed
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
54/68
APPLICATION EXAMPLES
()ASI02 AND AMFBS01 ONLY
I-E96-443-1D A - 5
Thermocouple Isolated
Thermocouple input with conditioner option and cold junctioncompensating thermistor:
S1 TO S16 = C1S17 TO S32 = 1C1, 2C2
RTD Isolated
RTD input with conditioner option:
S1 TO S16 = C1S17 TO S32 = 1C1, 2C2
Figure A-9. Thermocouple Isolated
Figure A-10. RTD Isolated
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
55/68
APPLICATION EXAMPLES
IMFBS01 ONLY
A - 6 I-E96-443-1D
®
Special or Custom Signal
Special signal types can be conditioned using custom designeddaughter boards in place of the supplied jumper boards. Con-sult head office concerning feasibility and price.
IMFBS01 ONLY
IMFBS01 Smart Transmitter
Point to point smart (Elsag Bailey) transmitter:
S1 TO S16 = C2S17 TO S32 = 1C2, 2C2
Figure A-11. Special or Custom Signal
Figure A-12. IMFBS01 Smar t Transmi t ter
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
56/68
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
57/68
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
58/68
NRAI0_ PART DRAWING
I-E96-443-1D B - 1
APPENDIX B - NRAI0_ PART DRAWING
NRAI0_ PART DRAWING
Figure B-1. NRAI01 Ana log Input Manu factur ing Draw ing, Sheet 1 of 4
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
59/68
NRAI0_ PART DRAWING
NRAI0_ PART DRAWING
B - 2 I-E96-443-1D
®
Figure B-2. NRAI01 Ana log Inpu t Schema tic Diagram , Sheet 2 of 4
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
60/68
NRAI0_ PART DRAWING
NRAI0_ PART DRAWING
I-E96-443-1D B - 3
Figure B-3. NRAI01 Ana log Inpu t Part List, Sheet 3 of 4
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
61/68
NRAI0_ PART DRAWING
NRAI0_ PART DRAWING
B - 4 I-E96-443-1D
®
Figure B-4. Ana log Inpu t Term inat ion Assembly Connection Detai ls, Sheet 4 of 4
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
62/68
SPECIFICATION SHEETS
I-E96-443-1D C - 1
APPENDIX C - SPECIFICATION SHEETS
SPECIFICATION SHEETS
Figure C-1. Inpu t Assignment a nd Configura tion Data Sheet for NRAI0 (Front)
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
63/68
SPECIFICATION SHEETS
SPECIFICATION SHEETS
C - 2 I-E96-443-1D
®
Figure C-2. Input Ass ignment an d Configurat ion Data Sheet for NRAI0 (Ba ck)
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
64/68
CONDITIONER AND ISOLATOR PART DRAWING
I-E96-443-1D D - 1
APPENDIX D - CONDITIONER AND ISOLATOR PART DRAWING
CONDITIONER AND ISOLATOR PART DRAWING
Figure D-1. Ana log Device
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
65/68
®
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
66/68
I-E96-443-1D Index - 1
Index
Symbols- .................................................................................. 1-4
() ................................................................................. 1-4
_ ................................................................................. 1-4
()ASI02
Slave Module........................................................ 1-1
Straight Through Mode ......................................... 1-1
A
Analog Input Termination Assembly........................... 1-1
Physical Operation................................................ 2-5
Application Examples .................................................A-1
()ASI02.......................................................... A-1, A-3
()ASI02, IMFBS01, And IMASI03 .........................A-1AMFBS01 .............................................................A-3
IMASI03........................................................ A-1, A-7
IMFBS01....................................................... A-1, A-6
C
Cabling ....................................................................... 3-4
Calibration .................................................................. 4-1
Conditioner and Isolator........................................ 4-2
Initial Calibration ................................................... 4-1
In-Service.............................................................. 4-2
Checkout .................................................................... 4-2
Elsag Bailey Canada Reference Documents........ 4-2
Conditioner and Isolator Calibration Procedure.......... 4-2Conditioner and Isolator Part Drawing........................D-1
Corrective Maintenance ............................................. 6-1
D
Description and Operation.......................................... 2-1
DIP Switch.................................................................. 2-3
Settings................................................................. 2-4
DIP Switch Functionality............................................. 2-3
E
Elsag Bailey Canada Reference Documents ............. 1-6
Equipment Application................................................ 1-3Equipment Description ............................................... 1-2
Equipment Malfunction............................................... 5-1
Error Message
Error Codes .......................................................... 5-1
Error Messages
Reference Documents .......................................... 5-1
Status Bytes.......................................................... 5-1
Error Messages and Corrective Action....................... 5-1
FFunctional Operation...................................................2-1
G
Glossary of Terms.......................................................1-4
I
IMASI03 Slave Module ...............................................1-2
IMFBS01
Elsag Bailey Field Bus ..........................................1-2
Smart Transmitter .................................................1-2
IMFBS01 Slave Module ..............................................1-2
In-Service Calibration..................................................4-2Installation
Handling ................................................................3-1
Introduction ...........................................................3-1
Location Considerations........................................3-1
Safety Considerations...........................................3-1
Setup And Physical Installation.............................3-2
Termination Cabinet Handling...............................3-1
Unpacking and Inspection.....................................3-1
Intended User .............................................................1-2
Introduction .................................................................2-1
M
Maintenance ...............................................................6-1Maintenance Schedule..........................................6-1
Preventative Maintenance.....................................6-1
Manual Instructions.....................................................1-3
N
NRAI0 .........................................................................1-3
Equipment Application ..........................................1-3
Features ................................................................1-3
Functional Operation.............................................2-1
NRAI0_ Part Drawing................................................. B-1
O
Other Equipment Interface..........................................3-7
Overview .....................................................................1-1
Analog Input Termination Assembly .....................1-1
P
Physical Operation......................................................2-5
Pre-Operating Adjustments.........................................3-7
http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://02sectxx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://03sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://dappendx.pdf/http://06sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://02sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://04sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://01sectxx.pdf/http://02sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://02sectxx.pdf/http://bappendx.pdf/http://03sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://02sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://02sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://03sectxx.pdf/http://bappendx.pdf/http://02sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://02sectxx.pdf/http://01sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://04sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://02sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://06sectxx.pdf/http://dappendx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://03sectxx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://02sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
67/68
-
8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input
68/68
For the latest information on ABB and Year 2000 Product Compatibility
Visit us on the World Wide Web at http://www.abb.com
Our worldwide staff of professionals is ready to meet your needs for process automation.
For the location nearest you, please contact the appropriate regional office.