I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

download I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

of 68

Transcript of I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    1/68

    E96-443-

    Rail Mounted Termination AssemblAnalog Inpu

    (NRAI0

    Bailey®®

    Instructio

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    2/68

    I-E96-443-1D

    Preface

     This manual describes analog input rail mounted terminationassemblies. A termination assembly is the transition betweeninput/output plant instrumentation wiring or cabling and theINFI 90 OPEN® distributed control system.

     The name Termination Assembly or TA has been assigned todifferentiate the in-line, rail mounted characteristics of thistype of field termination from the Termination Unit or TU andthe Termination Module or TM.

    ® INFI 90 OPEN is a registered trademark of Elsag Bailey Process Automation.

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    3/68

      I-E96-443-1D

     ® 

    List of Effective Pages

     

     Total number of pages in this instruction is 59, consisting of the following:

    Page No. Ch an ge Dat e

    Preface OriginalList of Effective Pages Original

    iii through vii Original1-1 through 1-9 Original2-1 through 2-9 Original3-1 through 3-7 Original4-1 through 4-2 Original5-1 through 5-4 Original

    6-1 through 6-1 Original7-1 through 7-2 Original8-1 through 8-2 Original

     A-1 through A-7 OriginalB-1 through B-4 OriginalC-1 through C-2 OriginalD-1 through D-1 Original

    Index-1 through Index-2 Original

     When an update is received, insert the latest changed pages and dispose of the super-seded pages.

    NOTE: On an update page, the changed text or table is indicated by a vertical bar in the outer mar-

    gin of the page adjacent to the changed area. A changed figure is indicated by a vertical bar in theouter margin next to the figure caption. The date the update was prepared will appear beside the

    page number.

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    4/68

    Table of Contents

    Page

    I-E96-443-1D ii

    SECTION 1 - INTRODUCTION....................................................................................................1-1

    OVERVIEW ..................................................................................................................1-1()ASI02.........................................................................................................................1-1IMFBS01 ...............................................................................................................1-2

    IMASI03.................................................................................................................1-2INTENDED USER.........................................................................................................1-2EQUIPMENT DESCRIPTION .........................................................................................1-2

    FEATURES...................................................................................................................1-3INSTRUCTION CONTENT / HOW TO USE ....................................................................1-3EQUIPMENT APPLICATION ..........................................................................................1-3GLOSSARY OF TERMS AND ABBREVIATIONS .............................................................1-4REFERENCE DOCUMENTS..........................................................................................1-5ELSAG BAILEY CANADA REFERENCE DOCUMENTS...................................................1-6NOMENCLATURE ........................................................................................................1-7

    SPECIFICATIONS.........................................................................................................1-7

    SECTION 2 - DESCRIPTION AND OPERATION........................................................................2-1INTRODUCTION...........................................................................................................2-1FUNCTIONAL OPERATION ...........................................................................................2-1DIP SWITCH FUNCTIONALITY......................................................................................2-3DIP SWITCH SETTINGS ...............................................................................................2-4PHYSICAL OPERATION ................................................................................................2-5

    SECTION 3 - INSTALLATION....................................................................................................3-1INTRODUCTION...........................................................................................................3-1SPECIAL HANDLING ....................................................................................................3-1UNPACKING AND INSPECTION....................................................................................3-1LOCATION CONSIDERATIONS .....................................................................................3-1

    SAFETY CONSIDERATIONS .........................................................................................3-1SETUP AND PHYSICAL INSTALLATION ........................................................................3-2

     Typical Elsag Bailey Termination Cabinet Arrangement..........................................3-2Explanation ...........................................................................................................3-2

    CUSTOM OR SPECIAL .................................................................................................3-4 WIRING CONNECTIONS AND CABLING .......................................................................3-4OTHER EQUIPMENT INTERFACE ................................................................................3-7

    PRE-OPERATING ADJUSTMENTS................................................................................3-7

    SECTION 4 - CALIBRATION.......................................................................................................4-1INITIAL CALIBRATION..................................................................................................4-1CHECKOUT .................................................................................................................4-2

    IN-SERVICE CALIBRATION..........................................................................................4-2

    SECTION 5 - TROUBLESHOOTING...........................................................................................5-1INTRODUCTION...........................................................................................................5-1ERROR MESSAGES AND CORRECTIVE ACTION..........................................................5-1PROBLEM DETERMINATION AND VERIFICATION PROCEDURES................................5-1

     TROUBLESHOOTING GUIDE .......................................................................................5-1

    SECTION 6 - MAINTENANCE........................................................................................... .........6-1INTRODUCTION...........................................................................................................6-1MAINTENANCE SCHEDULE.........................................................................................6-1

    http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    5/68

    iv I-E96-443-1D

    Table of Contents (continued)

    Page 

     ® 

    SECTION 6 - MAINTENANCE (continued) 

    PREVENTATIVE MAINTENANCE PROCEDURES .......................................................... 6-1CORRECTIVE MAINTENANCE PROCEDURES.............................................................. 6-1

    SECTION 7 - REPAIR/REPLACEMENT PROCEDURES ...........................................................7-1INTRODUCTION .......................................................................................................... 7-1PROCEDURES............................................................................................................. 7-1

    SECTION 8 - SUPPORT SERVICES..........................................................................................8-1INTRODUCTION .......................................................................................................... 8-1INSTRUCTION SUBSCRIPTION.................................................................................... 8-1REPLACEMENT PARTS................................................................................................ 8-1

    APPENDIX A - APPLICATION EXAMPLES ..............................................................................A-1()ASI02, IMFBS01 AND IMASI03 .................................................................................. A-1

     Two Wire 4-20 mA with System Common Reference............................................... A-1Four Wire 4-20 mA with System Common Reference.............................................. A-1Four Wire 4-20 mA No System Common Reference ................................................ A-2Single Ended Voltage with System Common Reference........................................... A-2Differential Voltage with No System Common Reference.........................................A-3

    ()ASI02 AND AMFBS01 ONLY.......................................................................................A-3 Two Wire 4-20 mA Isolated.................................................................................... A-3Four Wire 4-20 mA Isolated................................................................................... A-4

    Differential Voltage (or mV) Isolated....................................................................... A-4 Thermocouple Isolated........................................................................................... A-5

    RTD Isolated.......................................................................................................... A-5Special or Custom Signal.......................................................................................A-6

    IMFBS01 ONLY............................................................................................................ A-6IMFBS01 Smart Transmitter.................................................................................. A-6

    IMASI03 ONLY.............................................................................................................A-7IMASI03 Thermocouple ......................................................................................... A-7IMASI03 RTD ........................................................................................................ A-7

    APPENDIX B - NRAI0_ PART DRAWING ................................................................................. B-1NRAI0_ PART DRAWING ..............................................................................................B-1

    APPENDIX C - SPECIFICATION SHEETS................................................................................C-1SPECIFICATION SHEETS ............................................................................................C-1

    APPENDIX D - CONDITIONER AND ISOLATOR PART DRAWING ........................................ D-1CONDITIONER AND ISOLATOR PART DRAWING .........................................................D-1

    http://06sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://07sectxx.pdf/http://07sectxx.pdf/http://07sectxx.pdf/http://08sectxx.pdf/http://08sectxx.pdf/http://08sectxx.pdf/http://08sectxx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://bappendx.pdf/http://bappendx.pdf/http://cappendx.pdf/http://cappendx.pdf/http://dappendx.pdf/http://dappendx.pdf/http://06sectxx.pdf/http://dappendx.pdf/http://dappendx.pdf/http://cappendx.pdf/http://cappendx.pdf/http://bappendx.pdf/http://bappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://08sectxx.pdf/http://08sectxx.pdf/http://08sectxx.pdf/http://08sectxx.pdf/http://07sectxx.pdf/http://07sectxx.pdf/http://07sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    6/68

    List of Figures

    No. Title Page

    I-E96-443-1D v

    1-1. Nomenclature ........................................................................................................1-7

    2-1. Printed Circuit Board Layout .................................................................................2-22-2. Typical Circuit Schematic ......................................................................................2-3

    2-3. DIP Switch Codes...................................................................................................2-42-4. Printed Circuit Board Switch Legend......................................................................2-52-5. NRAI01 to () ASI02 or IMFBS01..............................................................................2-5

    2-6. NRAI0_ to IMASI03 ................................................................................................2-73-1. Standard Equipment Location Numbering System .................................................3-23-2. Cabinet Interior, Front View with Side Walls Folded Out.........................................3-33-3. Cabinet Cross Section, Hardware and Zone Identification.......................................3-43-4. System Side Wiring Connections and Board Power Distribution .............................3-53-5. NRAI0_ and NRAO01 with NRCS01’s......................................................................3-64-1. Conditioner and Isolator, Calibration Potentiometer Locations (Top View)...............4-1

    4-2. Conditioner & Isolator Pin Location and Identification (Bottom View)......................4-15-1. Troubleshooting Guide...........................................................................................5-2

    5-2. Troubleshooting Guide (continued) ........................................................................5-35-3. Troubleshooting Guide (continued) ........................................................................5-47-1. Mounting Foot Release...........................................................................................7-2

     A-1. Two Wire 4-20 mA with System Common Reference .............................................. A-1 A-2. Four Wire 4-20 mA with System Common Reference ............................................. A-1 A-3. Four Wire 4-20 mA No System Common Reference................................................ A-2

     A-4. Single Ended Voltage with System Common Reference .......................................... A-2 A-5. Differential Voltage with No System Common Reference ........................................ A-3 A-6. Two Wire 4-20 mA Isolated.................................................................................... A-3 A-7. Four Wire 4-20 mA Isolated .................................................................................. A-4 A-8. Differential Voltage (or mV) Isolated....................................................................... A-4 A-9. Thermocouple Isolated.......................................................................................... A-5 A-10. RTD Isolated......................................................................................................... A-5

     A-11. Special or Custom Signal ...................................................................................... A-6

     A-12. IMFBS01 Smart Transmitter................................................................................. A-6 A-13. IMASI03 Thermocouple......................................................................................... A-7 A-14. IMASI03 RTD........................................................................................................ A-7B-1. NRAI01 Analog Input Manufacturing Drawing, Sheet 1 of 4................................... B-1

    B-2. NRAI01 Analog Input Schematic Diagram, Sheet 2 of 4 ......................................... B-2B-3. NRAI01 Analog Input Part List, Sheet 3 of 4 .......................................................... B-3B-4. Analog Input Termination Assembly Connection Details, Sheet 4 of 4 ................... B-4C-1. Input Assignment and Configuration Data Sheet for NRAI0 (Front)........................ C-1C-2. Input Assignment and Configuration Data Sheet for NRAI0 (Back) ........................ C-2D-1. Analog Device ....................................................................................................... D-1

    http://01sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://07sectxx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://bappendx.pdf/http://bappendx.pdf/http://bappendx.pdf/http://bappendx.pdf/http://cappendx.pdf/http://cappendx.pdf/http://dappendx.pdf/http://dappendx.pdf/http://cappendx.pdf/http://cappendx.pdf/http://bappendx.pdf/http://bappendx.pdf/http://bappendx.pdf/http://bappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://07sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://01sectxx.pdf/

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    7/68

    vi I-E96-443-1D

    No. Title Page  

    List of Tables

     ® 

    1-1. Glossary of Terms and Abbreviations..................................................................... 1-4

    1-2. Reference Documents ............................................................................................ 1-51-3. Elsag Bailey Canada Reference Documents............................................................ 1-61-4. General Specifications ........................................................................................... 1-7

    1-5. Mechanical and Input Specifications...................................................................... 1-81-6. Connection, Configuration, Power Requirement and Option Data........................... 1-9

    2-1. NRAI0_, Cable & () ASI02/IMFBS01 Pin-out and Conductor Use Chart ..................2-62-2. NRAI0_, Cable & IMASI03 Pin-out and Conductor Use Chart ................................. 2-84-1. Conditioner and Isolator Calibration Procedure......................................................4-2

    7-1. Termination Assembly Replacement ...................................................................... 7-18-1. Spare Parts List..................................................................................................... 8-2

    http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://04sectxx.pdf/http://07sectxx.pdf/http://08sectxx.pdf/http://08sectxx.pdf/http://07sectxx.pdf/http://04sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    8/68

    I-E96-443-1D vi

    Safety Summary

     GENERALWARNINGS

    Units marked with EN-BC-606 must have alignment keys (AMP P/N

    58327-1 Inter-Contact Plug) installed between contacts 15(S) and16(T) of the pre-terminated cable.

    Improperly set DIP switches may result in equipment damage.Please read the instructions carefully before making connections or

    applying power.

    When voltage inputs are routed to the ()ASI02 or IMFBS01 slavemodules, the high impedance input will retain the signal in the event

    of an open circuit. Bleeding resistors must be installed if timely badquality alarming is desired.

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    9/68

     ® 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    10/68

    OVERVIEW

    I-E96-443-1D 1 - 1

    SECTION 1 - INTRODUCTION

    OVERVIEW 

     This instruction is divided into 4 major sections, coveringoperation, installation, calibration. and troubleshooting of the

     Analog Input Termination Assembly (NRAI0_). Each topic within these sections is divided into sub-sections with infor-mation specific to a particular application.

     The analog input termination assembly is available in severa variations. The symbol _ (underscore) is used when referring toa feature that is common to all variations. When it is necessaryto refer to a particular model, a specific number is used. Referto NOMENCLATURE  in this section for more information.

     The NRAI0_ can be used with any of the ()ASI02, IMFBS01 orIMASI03 slave modules. The available capabilities and alterna-tives vary depending on which slave module is being used

     The ASI02 slave is available in Network 90 and INFI 90 OPENform factors. They are functionally identical so far as the ter-mination assembly is concerned and are grouped by the () pre-fix.

     A complete listing of product instructions for associated slaveand master modules is in REFERENCE DOCUMENTS .

     The NRAO01 Analog Output Termination Assembly is comple-mentary to the NRAI0_. Refer to the documents listed in

    ELSAG BAI LEY CANADA REFERENCE DOCUMENTS  for com-plete information.

    ()ASI02 

     The ()ASI02 has 15 input channels to digitize voltage signalsfor use within the INFI 90 OPEN system. The NRAI0_ providesa corresponding 15 channels of field terminations. Each chan-nel of the NRAI0_ has socket pins for optional signal condition-ers and isolators.

     When a channel of the NRAI0_ is being used in the straight

    through mode (no isolator or conditioner), passive signal prep-aration for the analog input slave is performed. DIP switchesare used to select the signal preparation.

     A broad range of conditioners and isolators are available forinstalled use in one or more channels in place of the jumper

     boards supplied as standard. All conditioners and isolatorshave a common DIP switch setting. Refer to Figure 2-4  andFigures  A-6, A-7, A-8, A-9, and A-10.

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    11/68

    INTRODUCTION

    INTENDED USER

    1 - 2 I-E96-443-1D

     ® 

    IMFBS01

     The IMFBS01 slave has the functionality of the ()ASI02 slave, but includes Elsag Bailey field bus (smart transmitter) sup-port.

     When the smart transmitters are used in the analogpoint-to-point mode there is no functional change versus the()ASI02.

    NOTE: Signal isolators do not pass the field bus FSK protocol and

    therefore should not be installed when Elsag Bailey field bus com-

    munication is required. Refer to Figure A-12.

    IMASI03 

     The IMASI03 enhanced slave module has 16 isolated inputs,each individually able to digitize a broad range of signal types.

     The use of the optional isolators is not generally required.

     The NRAI0_ performs passive signal conditioning for theenhanced analog input slave module. DIP switches are used toselect the required conditions. Low level, thermocouple andRTD inputs are routed straight through to the slave. Refer toFigures A-13 and A-14.

     The NRAI02 includes cold junction compensation and must beused when thermocouple inputs to the IMASI03 are required.

    INTENDED USER 

     This manual is intended for use by:

    • Prospective customers to answer their questions about thehardware design flexibility of the INFI 90 OPEN analoginputs.

    • Instrument engineers or technicians for installation, optionand programming details.

    • Maintenance personnel for ongoing use of the assemblies.

    EQUIPMENT DESCRIPTION 

     The NRAI0_ consists of screw clamp terminations for 16 input channels, mounted onto a printed circuit board and installedin an extruded plastic channel, 109 mm (4 1/2 inches) wideand 610 mm (24 inches) long. The channel has mounting feet that can attach to standard DIN rails (U or C).

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    12/68

    INTRODUCTION

    FEATURES

    I-E96-443-1D 1 - 3

    FEATURES 

     The NRAI0_ features:

    • In-line, cage clamp terminal blocks for all wiring connec-tions.

    • DIP switch programming.

    • Full power distribution with current limiting or fusing when necessary.

    • Socket pins for optional signal conditioners and isolators.

    • Connection to slave modules via pre-terminated cables.

    Ribbon cable headers provide for connection to the NRCS01 which supports connection to NDCS03, NDIS02 or IISAC01

    control stations and indicators. Refer to Figure 3-5, NRAI0_and NRAO01 with NRCS01's.

    INSTRUCTION CONTENT / HOW TO USE 

     This manual has been arranged, indexed, and cross referencedto provide easy movement between related topics.

    Most users will only need to refer to Section 2 - DESCRIPTIONAND OPERAT ION  for the functional operation and use of theNRAI0_.

    Control system design engineers should review Section 3 -

    INSTALLATION  before the detailed hardware design stage of aproject.

    Personnel responsible for system maintenance and repairshould read and understand Section 5 - TROUBLESHOOTINGand Section 6 - MAINTENANCE   when mis-operation is sus-pected. Section 7 - REPAIR/REPLACEMENT PROCEDURESand Section 8 - SUPPORT SERVICES   should be referred toprior to replacing and returning any failed units.

    Other than setting the DIP switches, the base NRAI0_ requiresno calibration unless the optional signal conditioners and iso-lators are installed. Refer to Section 4 - CALIBRATION .

    EQUIPMENT APPLICATION 

     The NRAI0_ is intended to be used in systems:

    • Using the digital termination assemblies,

    • Requiring terminal block (screw clamp) connectiontechnology,

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    13/68

    INTRODUCTION

    GLOSSARY OF TERMS AND ABBREVIATIONS

    1 - 4 I-E96-443-1D

     ® 

    • Requiring signal isolation,

    • Having small numbers of signal ranges not supported by the ()ASI02, or 

    • Needing NDCS03/IISAC01 support with ASI/ASO slave

    modules,

     The NRAI01 is supported by the ()ASI02, IMFBS01 or IMASI03slave modules. The NRAI02, with cold junction compensation,is used if direct thermocouple inputs to the IMASI03 aredesired.

    System cable part number L700741-1-(length) is required for 

    the ()ASI02 or IMFBS01 slave modules.

    System cable part number L700743-1-(length) is required for the IMASI03 slave module.

    GLOSSARY OF TERMS AND ABBREVIATIONS 

    Table 1-1. Glossary of Terms and Abbreviat ions 

    Term Definition

    () (empty parenthesis) Used when statements are applicable to all variations of the unit.

     _ (underscore) Used when a character may vary but there are differences between variations

    that must be considered.

    - (dash) Space holder, character not relevant to this instruction.

    Cold Junction

    Compensation

    The measurement of the temperature and subsequent elimination of the millivolt

    signals created between thermocouple wires and the terminal blocks they areconnected to.

    Control Station Panel mounted array providing operator access to a software based manual/ 

    automatic transfer station. Includes: process variable, set point and control out-

    put indication, mode switching between manual/automatic/ratio or cascade and

    bypass (backup) for the control output from the slave module.

    DIP Dual Inline Pin arrangement.

    DIP Switch Printed circuit board mounted miniature switch for the selection of specific func-

    tionality.

    DIN Deutsche Industrie Normen, German industrial standards and accepted global

    standard.

    Expander Bus Parallel communication bus between the Elsag Bailey master and I/O slave mod-

    ules.

    Field Bus A digital serial communication system connecting one or more smart transmitters

    to the distributed control system.

    Four Wire A transmitting device having two conductors dedicated to the measured signal

    while receiving its power via two other conductors.

    Isolator A device providing electrical isolation between its input, output and ground.

    Jumper Board A printed circuit board having the single function of making a direct electrical con-

    nection between two or more contacts.

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    14/68

    INTRODUCTION

    REFERENCE DOCUMENTS

    I-E96-443-1D 1 - 5

    REFERENCE DOCUMENTS 

    Mounting Rail A formed metal strip having standardized dimensions (DIN) that allow the mount-

    ing of a wide variety of devices from various manufacturers.

    Point-To-Point Wiring The process of manually connecting two or more electrical contact points with

    single conductor wires.

    Pre-Terminated Cable A multi conductor cable having pre-installed connectors, usually at both ends,

    permitting efficient connection of large numbers of electrical signals in a reduced

    time.

    RTD Resistance Temperature Detector; a temperature sensitive resistor.

    Screw Clamp Type of terminal requiring no ring or spade lug, providing high locking force and

    excellent vibration resistance without damaging the conductor.

    Signal Conditioner Electronic module that converts one signal range or type to another signal range

    or type.

    Slave Module A self contained module that accepts and responds to all instructions received

    from a master module via the expander bus.

    Socket Pin A spring-loaded socket that mounts directly into a printed circuit board to allow

    easy removal and replacement of the installed device.

    Straight Through Mode No signal conditioning or isolation being performed.

    Terminal Block The mouldings and associated metal parts that form an insulated assembly for

    the termination and/or continuation of electrical wiring.

    Termination Assembly Field wire terminating devices featuring in-line terminal blocks and rail mounting.

    Termination Module A cage mounted printed circuit board providing high density field wire termina-

    tions.

    Termination Unit A surface mounted printed circuit board providing field wiring terminations using

    screw terminals.

    Thermistor Like the RTD, a temperature sensitive resistor. Composed of sintered semicon-

    ductor material which is best described as sensitive.

    Two Wire A system in which the power to a transmitting device and the signal from thatsame device are carried by the same pair of wires.

    Table 1-1. Glossary of Terms and Abbreviat ions (continued) 

    Term Definition

    Tab le 1-2. Reference Documents 

    Document

    NumberDocument

    I-E93-902-1 Digital Control Station (NDCS03).

    I-E93-906-7 Multi-Function Controller (NMFC03).I-E93-906-12 Multi-Function Controller (NMFC04).

    I-E93-906-13 Multi-Function Controller (NMFC05).

    I-E93-912-10 Analog Slave Input Module (NASI02).

    I-E96-116 Digital Indicating Station (NDIS02).

    I-E96-117 Analog Control Station (IISAC01).

    I-E96-200 Function Code Application Manual.

    I-E96-201 Multi-Function Processor (IMMFP01).

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    15/68

    INTRODUCTION

    ELSAG BAILEY CANADA REFERENCE DOCUMENTS

    1 - 6 I-E96-443-1D

     ® 

    ELSAG BAILEY CANADA REFERENCE DOCUMENTS 

    I-E96-202 Multi-Function Processor (IMMFP02).

    I-E96-203 Multi-Function Processor (IMMFP03).

    I-E96-211 Multi-Function Controller (IMMFC03).

    I-E96-212 Multi-Function Controller (IMMFC04).

    I-E96-213 Function Controller (IMMFC05).

    I-E96-301 Analog Slave Input Module (IMASI03).

    I-E96-302 Field Bus Slave Module (IMFBS01).

    I-E96-304 Analog Slave Input Module (IMASI02).

    I-E96-500 Site Planning, Preparation and Equipment Installation.

    Tab le 1-2. Reference Documen ts (continued) 

    Document

    NumberDocument

    Table 1-3. Elsag Bai ley Cana da Reference Docum ents 

    Document

    NumberDocument

    I-E97-443-3 Digital Input Termination Assembly (NRDI0_).

    I-E97-443-4 Digital Output Termination Assembly (NRDO01).

    I-E97-443-5 Relay Output Termination Assembly (NRDO02).

    I-E97-443-2 Analog Output Termination Assembly (NRAO01).

    HARDWARE/COMMUNICATIONS CHECKOUT

    DOCUMENT.

    DL700783_,SHTS 1-4

    Analog Input Termination Assembly Part Drawing.

    DL700837 Conditioner and Isolator Part Drawing.

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    16/68

    INTRODUCTION

    NOMENCLATURE

    I-E96-443-1D 1 - 7

    NOMENCLATURE 

    SPECIFICATIONS 

    Figure 1-1. Nomenclature 

    Table 1-4. General Specif ications 

    Nomenclature

    (Part No.) (Model)

    NRAI0_ 

    (L700783-_) (990598)

    Name Analog Input Termination Assembly.

    Environmental

    Operating Temperature

    Relative Humidity

    0°C to 70°C

    (32 deg. F to 158°F)

    5% - 90% up to 55°C (131°F) (non-condensing).

    5% - 40% up to 70°C (158°F) (non-condensing).

    Elsag Bailey equipment should be operated and stored in a non-corrosive

    environment.

    Cooling Requirements No cooling is necessary when enclosed in cabinets and operated within the

    stated environmental limits.

    Certification All assemblies are CSA certified as process control equipment (C22.2 No.142)

    for use in ordinary (non-hazardous) locations.

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    17/68

     S P E  C I  F I   C A T I   ON  S 

    1 -8 

    I  -E 9 6 -4 4 3 -1 D 

    Table 1-5. Mechanical and Input Specif ications 

    Nomenclature

    (Part No.)

    (Model)

    Name

    Dimensions

    mm (inches)  Mounting

    Slave

    Connecti-

    vity

    Cable

    Type

    Cable

    Key

    Slot

    Loc’n

    I/O

    Quan

    -tity

    Input

    Specifications 

    Length Width Height Height

    on Rail

    Input Slave Option

    condit

    mount

    NRAI01

    (L700783-1)

    (990598)

    Analog Input

    Termination

    Assembly

    610

    (24)109

    (4.29)

    74.6

    (2.95)

    82.6

    (3.26)

    DIN U

    (35 mm)

    or DIN C

    (32 mm)

    Rail

    NASI02

    IMASI02

    IMFBS01

    L700741-

    (Length)

    Round

    Cable

    15/16

    or S/T

    15 Refer to Product 

    Specification or

    Instruction 

    I-E93-912-10 (NASI02) 

    I-E96-302 (IMFBS02) 

    I-E96-304 (IMASI02) 

    Refer

    COND

    TOR P

    consu

    Engin

    inform

    Gener

    240 V

    protec

    transf

    Worst

    IEEE

    to +85

    Potted

    enviro*

    IMASI03

    L700743-

    (Length)

    Round

    Cable

    16 Refer toProduct 

    Specification or

    Instruction 

    I-E96-301

    (IMASI03) 

    Them

    be use

    more

    condit

    be red

    **NRAI02

    (L700783-2)

    (N/A) Analog

    Input

    Termination

    Assembly With

    Themistors

    **

    IMASI03

    **

    L700743-

    (Length)

    Round

    Cable

    ***16 ***

    Refer to Product 

    Specification or

    Instruction 

    I-E96-301

    (IMASI03) 

    ***

    Most c

    would

    isolate

    Custo

    could

    first 15

    * No cold junction compensation for thermocouple conversion by the IMASI03.

    ** Can be used with NASI02, IMSI02 and IMFBS01 if desired, L700741-1 cable must be used.*** 15 inputs and same specifications as with NRAI01 when used with NASI02, IMSI02 or IMFBS01 slave modules.

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    18/68

     S P E  C I  F I   C A T I   ON  S 

    I  -E 9 6 -4 4 3 -1 D 

    1 -9 

    Table 1-6. Connection, Configurat ion, Pow er Requirement an d Option Data 

    Nomenclature

    (Part No.)

    (Model)

    Name

    Wire Size

    (Qty./Size)

    Connections

    Number of Blocks per

    Electrical Point

    Switch Settings +24 Vdc Current Requirements

    Field Power Shield S1 to S16

    System versus

    Field Powered

    S17 to S32 ***

    Signal

    Preparation

    Total

    Assembly

    S1 to S16 Conditioners

    and Isolator=C1 =C2

    NRAI0_ 

    (700783-_)

    (990598)

    Analog Input

    Termination

    Assembly

    #14-#22

    AWG

    (1 / #14)

    (2 / #16)

    (3 / #18)

    (5 / #20)

    (7 / #22)

    2

    (+’ve)

    2

    (-’ve)

    1

    (C

    compen-

    sation)

    1(SH

    shield)

    4

    (+24 V)

    4

    (COM)

    3 One single

    pole double

    throw switch

    per input

    selects two

    wire signal

    versus 24 Vdc

    system power

    to the

    + terminal:

    C1 = two wiresignal

    C2 = 24 Vdc to

    + terminal

    Two single

    pole double

    throw

    switches per

    input.

    Pole 1 selects

    current to

    voltage (250

    ohm resistor)

    conversion:

    1C1 =resistor in.

    Pole 2 selects

    system

    common

    reference:

    2C1 = floating

    input,

    2C2 = system

    common

    reference

    used.

    Minimum

    4mA

    Typical

    300 mA

    Maximum

    900 mA

    0 MA

    (field

    powered)

    Typical

    15 mA**

    Maximum

    24 mA**

    Typical

    40mA**

    Maximum

    60 mA**

    (4-20 mA

    2 wire only)

    * When conditioners and isolators are used, set S1 to S16 = C1, S17 to S32 = 1C1, 2C2.** The values shown are for a single input channel. All 15 or 16 channels must be summed to arrive at the total power requirements.*** The function of S32 pole 1 is reversed on REV.A boards only.

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    19/68

     ® 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    20/68

    INTRODUCTION

    I-E96-443-1D 2 - 1

    SECTION 2 - DESCRIPTION AND OPERATION

    INTRODUCTION 

     This section provides sufficient information to allow users tounderstand the use of the assembly, document instrumenta-tion wiring connections, determine and document DIP switchconfigurations, and perform basic problem solving.

     There is a considerable variety of hardware combinations pos-sible. Detailed descriptions and diagrams are used to illustrateas many combinations as possible.

    FUNCTIONAL OPERATION 

     The NRAI0_ consists of a circuit repeated 16 times. The first 15

    circuits have socket pins for the optional isolators and condi-tioners. Removable jumper boards, P/N WTL 990756, are pro-

     vided with the base unit. Optional jumper boards, P/N WTL990757, are available to provide input protection againstsurges as defined by IEEE C37.90a - 1974 Surge WithstandCapability (SWC) Tests. The sixteenth circuit, which is onlyused with the IMASI03 slave module, has no socket pins.

    Refer to Figures 2-5, 2-6 and 3-5 for cable connection details.

    Refer to Figure 3-4 for power, common, and shield drain con-nection details.

    24 Vdc power is distributed along two paths. The presence opower on each path is indicated by an LED being on g r een On the first path DS1 indicates that power is available for two

     wire devices, the power leaving the termination assembly beingcurrent limited to about 170 mA per channel by 150 Ω resis-tors. The second power path is routed through fuse F1 tosocket pin 3 of the 15 conditioner and isolator mounting posi-tions, with DS2 indicating the fuse status.

     The total power requirements are determined by summingindividual power requirements for each input channel per

     Table 1-6.

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    21/68

    DESCRIPTION AND OPERATION

    FUNCTIONAL OPERATION

    2 - 2 I-E96-443-1D

     ® 

    FIELD SIDE SYSTEM SIDE

    REFER TO SECTION 3 - INSTALLATION 

    CIRCUIT NO. 1 -

    TERMINAL BLOCKS FOR

    dc COMMON - REFER TO FIGURE 3-4.

    CIRCUIT NO. 2 +TERMINAL BLOCKS FOR

    24 Vdc POWER.

    CIRCUIT NO. 3REFER TO FIGURE 3-4.

    CIRCUIT NO. 4P3 RIBBON CABLE

    CIRCUIT NO. 5REFER TO FIGURE 3-5.

    CIRCUIT NO. 6

    CIRCUIT NO. 7 P4RIBBON CABLE

    REFER TO FIGURE 3-5.

    CIRCUIT NO. 8

    USER’S

    INSTRUMENTATION

    WIRING ON THIS SIDE

    SEE DETAILS IN

    FIGURE 2-2 AND

    APPENDIX A - APPLICA- 

    TION EXAMPLES 

    LOCATION

    LABELS AND

    BRIEF

    INSTRUCTIONS

    P1

    CARD EDGE CONNECTION FOR

    PRE-TERMINATED CABLE TO SLAVE

    MODULE REFER TO FIGURES 2-5

    AND 2-6.

    CIRCUIT NO. 9 SH TERMINAL BLOCKS FOR

    SHIELD DRAIN.

    CIRCUIT NO. 10

    CIRCUIT NO. 11 P5 RIBBON CABLE - REFER TO FIGURE 3-5.

    CIRCUIT NO. 12

    CIRCUIT NO. 13

    P6 RIBBON CABLE - REFER TO FIGURE 3-5.

    CIRCUIT NO. 14

    CIRCUIT NO. 15

    CIRCUIT NO. 16

    Figure 2-1. Printed Circuit Board Lay out 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    22/68

    DESCRIPTION AND OPERATION

    DIP SWITCH FUNCTIONALITY

    I-E96-443-1D 2 - 3

    NOTES:

    1. The NN refers to circuit numbers 1 to 16.

    2. The dual +'ve and -'ve terminals are supplied to allow indepen-

    dent marshalling. Refer to Figures A-1 through A-14 for examples.

    3. The C terminal becomes the third or compensating lead of an

    RTD or thermocouple cold junction compensation.

    4. The SH terminal is for cable shields.

    5. The terminal is used with the optional surge withstand

     jumper board.

    DIP SWITCH FUNCTIONALITY 

    S1 C1 sets the input for 4-wire transmitter operation and S1C2 is for 2-wire transmitter operation.

    S17 1C1 allows voltage inputs. S17 1C2 connects a precisionresistor for conversion from 4 to 20 mA dc to 1 to 5 Vdc. S17

    2C1 is for differential inputs. S17 2C2 provides a system com-mon reference.

     When voltage inputs are routed to the ()ASI02 OR IMFBS01slave modules, consideration of the effect of an open circuit isnecessary. The high impedance of the input circuit will holdthe residual voltage indefinitely and the fault monitoringinherent in the system will not be triggered.

    Figure 2-2. Typical Circui t Schema tic 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    23/68

    DESCRIPTION AND OPERATION

    DIP SWITCH SETTINGS

    2 - 4 I-E96-443-1D

     ® 

    If the voltage input has an elevated zero, such as a 1-5 Vdc sig-nal, a bleeding resistor installed between the extra +ve and -veterminals will drain the voltage to 0 Vdc and a Bad Quality alarm will be triggered. A 4.7 MΩ, 1/4 W  resistor is recom-mended for this application. Refer to Figures  A-4 and A-5.

    If the voltage input has 0 Vdc as a valid part of its signal rangeor if it is desirable to f a i l h i g h  , special consideration isrequired. Please consult your Elsag Bailey system engineer, or refer to Section 8 - SUPPORT SERVICES .

     The IMASI03 slave and the optional signal isolators have built-in open circuit detection so no special consideration isrequired for them.

    If conditioners and isolators are used, the switch settings must  be set for 4-wire, voltage, and system common reference (S1C1, S17 1C1 and S17 2C2).

    DIP SWITCH SETTINGS 

    Figure 2-3. DIP Sw itch Codes 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    24/68

    DESCRIPTION AND OPERATION

    PHYSICAL OPERATION

    I-E96-443-1D 2 - 5

     The settings are summarized on the P.C. board artwork asfollows:

    Examples of all commonly used settings are shown in Figure A-1 to Figure A-14.

    PHYSICAL OPERATION 

     The analog input termination assembly can be connected to a variety of slaves and other hardware options. The following fig-ures detail connection to the slave modules. Refer to OTHEREQUIPMENT INTERFACE   in Section 3  and Figure  3-5  for

    additional information concerning connection to other devicessuch as the NRCS01 for NDCS03 and IISAC01 support.

    Figure 2-4. Printed Circuit Board Sw itch Legend 

    Figure 2-5. NRAI01 to () ASI02 or IMFBS01 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    25/68

    DESCRIPTION AND OPERATION

    PHYSICAL OPERATION

    2 - 6 I-E96-443-1D

     ® 

    NOTES:

    1. Traces A to S on the slave, or even numbers on the NRAI, are

    on the component side.

    2. Traces 1 to 15 on the slave, or odd numbers on the NRAI are on

    the solder side.

    NOTES: The following traces on the NRAI01 Termination Assembly

    are not used when the ()ASI02 or IMFBS01 slave modules are

    employed:

    1. 1 and 2 are the thermistors for cold junction compensation.

    2. 5, 6, 11, 12, 17, 18, 23, 24, 29, 30, 35, 36, 41, 42 and 47 are the

    compensation conductors for RTD and TC inputs.

    3. 48, 49 and 50 are for analog input channel 16.

    Table 2-1. NRAI0_, Cable & () ASI02/ IMFBS01 Pin-out and

    Condu ctor Use Cha rt 

    Slave

    Signal

    Slave

    Trace

    NRAI01

    Trace

    NRAI01

    Signal

    AI-1-

    AI-2-

    AI-3-

    AI-4-

    AI-5-

    AI-6-

    AI-7-

    AI-8-

    AI-9-

    AI-10-

    AI-11-

    AI-12-

    AI-13-

    AI-14-AI-15-

    AI-1+

    AI-2+

    AI-3+

    AI-4+

    AI-5+

    AI-6+

    AI-7+

    AI-8+

    AI-9+

    AI-10+

    AI-11+

    AI-12+

    AI-13+AI-14+

    AI-15+

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    1415

    A

    B

    C

    D

    E

    F

    H

    J

    K

    L

    M

    N

    PR

    S

    4

    7

    10

    13

    16

    19

    22

    25

    28

    31

    34

    37

    40

    4347

    3

    8

    9

    14

    15

    20

    21

    26

    27

    32

    33

    38

    3944

    45

    AI-1-

    AI-2-

    AI-3-

    AI-4-

    AI-5-

    AI-6-

    AI-7-

    AI-8-

    AI-9-

    AI-10-

    AI-11-

    AI-12-

    AI-13-

    AI-14-AI-15-

    AI-1+

    AI-2+

    AI-3+

    AI-4+

    AI-5+

    AI-6+

    AI-7+

    AI-8+

    AI-9+

    AI-10+

    AI-11+

    AI-12+

    AI-13+AI-14+

    AI-15+

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    26/68

    DESCRIPTION AND OPERATION

    PHYSICAL OPERATION

    I-E96-443-1D 2 - 7

     The NRAI02 must be used if thermocouple inputs to theIMASI03 are desired.

     

    Figure 2-6. NRAI0_ to IMASI03 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    27/68

    DESCRIPTION AND OPERATION

    PHYSICAL OPERATION

    2 - 8 I-E96-443-1D

     ® 

     

    Table 2-2. NRAI0_, Cable & IMASI03 Pin-out and

    Condu ctor Use Char t 

    IMASI03

    Signal

    IMASI03

    Trace

    NRAI02

    Trace

    NRAI02

    Signal

    RTD -

    AI 1 +

    AI 1 COM

    AI 2 -

    AI 3 +

    AI 3 COM

    AI 4 -

    AI 5 +

    AI 5 COM

    AI 6 -

    AI 7 +

    AI 7 COM

    AI 8 -

    AI 9 +AI 9 COM

    AI 10 -

    AI 11 +

    AI 11 COM

    AI 12 -

    AI 13 +

    AI 13 COM

    AI 14 -

    AI 15 +

    AI 15 COM

    AI 16 -

    RTD +

    AI 1 -

    AI 2 COMAI 2 +

    AI 3 -

    AI 4 COM

    AI 4 +

    AI 5 -

    AI 6 COM

    AI 6 +

    AI 7 -

    AI 8 COM

    AI 8 +

    AI 9 -

    AI 10 COM

    AI 10 +

    AI 11 -AI 12 COM

    AI 12 +

    AI 13 -

    AI 14 COM

    AI 14 +

    AI 15 -

    AI 16 COM

    AI 16 +

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    1415

    16

    17

    18

    19

    20

    21

    22

    23

    24

    25

    26

    27

    2829

    30

    31

    32

    33

    34

    35

    36

    37

    38

    39

    40

    41

    4243

    44

    45

    46

    47

    48

    49

    50

    1

    3

    5

    7

    9

    11

    13

    15

    17

    19

    21

    23

    25

    2729

    31

    33

    35

    37

    39

    41

    43

    45

    47

    49

    2

    4

    68

    10

    12

    14

    16

    18

    20

    22

    24

    26

    28

    30

    32

    3436

    38

    40

    42

    44

    46

    48

    50

    RTD -

    AI 1 +

    AI 1 COM

    AI 2 -

    AI 3 +

    AI 3 COM

    AI 4 -

    AI 5 +

    AI 5 COM

    AI 6 -

    AI 7 +

    AI 7 COM

    AI 8 -

    AI 9 +AI 9 COM

    AI 10 -

    AI 11 +

    AI 11 COM

    AI 12 -

    AI 13 +

    AI 13 COM

    AI 14 -

    AI 15 +

    AI 15 COM

    AI 16 -

    RTD +

    AI 1 -

    AI 2 COMAI 2 +

    AI 3 -

    AI 4 COM

    AI 4 +

    AI 5 -

    AI 6 COM

    AI 6 +

    AI 7 -

    AI 8 COM

    AI 8 +

    AI 9 -

    AI 10 COM

    AI 10 +

    AI 11 -AI 12 COM

    AI 12 +

    AI 13 -

    AI 14 COM

    AI 14 +

    AI 15 -

    AI 16 COM

    AI 16 +

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    28/68

    DESCRIPTION AND OPERATION

    PHYSICAL OPERATION

    I-E96-443-1D 2 - 9

    NOTES:

    1. On the IMASI03, traces 1 to 25 are on the component side.

    2. Traces 26 to 50 are on the solder side.

    3. On the NRAI0_, odd numbered traces are on the component

    side.

    4. Even numbered traces are on the solder side.

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    29/68

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    30/68

    INTRODUCTION

    I-E96-443-1D 3 - 1

    SECTION 3 - INSTALLATION

    INTRODUCTION 

     This section explains the standard Elsag Bailey installationpractices as well as providing the basic information for thoseinstallations where special mounting is required.

    SPECIAL HANDLING 

    Preassembled termination cabinets should be handled in

    accordance with the instructions found in the S i t e Pl a n n i n gPr e p a r a t i o n a n d E qu i pm en t I n s t a l l a t i o n I n s t r u c t i o n  .

    Loose termination assemblies are shipped in foam paddedcardboard cartons. No special handling is required.

    UNPACKING AND INSPECTION 

     The termination assemblies should be inspected for damageand/or broken components. Although the assemblies are indi-

     vidually packaged in foam padded boxes, some bending ofcomponents may occur during shipment. Most of these typesof problems can be corrected by the user. Physical breakageshould be reported to the shipping company.

     The Elsag Bailey part drawing is listed in ELSAG BAIL EY CANADA REFERENCE DOCUMENTS   in Section 1, and should be

    obtained if detailed inspection of components is necessary.

    LOCATION CONSIDERATIONS 

     As with all electrical connections, the termination assembliesshould be mounted in environments that are relatively freefrom conductive dusts and corrosive gases. Refer to I SA Env ir o nme n t a l S t a n d a r d S 7 1 .0 4 -1 9 8 5  . The severity level should

     be no worse than a good G2.

     The assemblies have no exposed hazardous conductors and nospecial enclosures are needed.

    SAFETY CONSIDERATIONS 

    No special safety considerations are necessary.

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    31/68

    INSTALLATION

    SETUP AND PHYSICAL INSTALLATION

    3 - 2 I-E96-443-1D

     ® 

    SETUP AND PHYSICAL INSTALLATION 

    Typical Elsag Bailey Termination Cabinet Arrangement 

     The termination assemblies are oriented vertically on the DIN

    mounting rails. The assemblies are inverted when field wiringis to be on the right hand side.

     The vertical orientation allows field instrumentation wire or cable entering via the top or bottom of a cabinet, to be directly routed to the appropriate terminal block.

     The most accessible areas, at the front of each side, and at thecentre of the facing surface, are available for field I/O wiring.Fifteen cm (six inches) of support space is available next to thedoor on each side. If desired, plastic wire trays can be installed

     with five cm (two inches) allowed between the plastic tray andthe field terminals for wire tag visibility.

     The standard Elsag Bailey cabinet has 10 divisions from top to bottom called rows and 4 location designations A to D, startingat the front left, called zones. Zones C and D are eliminated

     when front access (wall mounting) cabinet options are used.Refer to Figure 3-2. Cabinet Interior and Figure 3-3. Cabinet Cross Section, for a diagrammatic representation.

     The vertically oriented rail mounting system, combined withthe variable lengths of the assemblies, has led to a modifica-tion of the standard equipment location numbering system.Positions are used rather than rows and each zone has beensubdivided into (for example) A and A1. An example of the

    complete location numbering system is below.

    Explanation 

     

    Figure 3-1. Stand ard Equipment Location Numbering Sys tem 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    32/68

    INSTALLATION

    SETUP AND PHYSICAL INSTALLATION

    I-E96-443-1D 3 - 3

    Figure 3-2. Cabin et Interior, Front View w ith Side Walls Folded Out 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    33/68

    INSTALLATION

    CUSTOM OR SPECIAL

    3 - 4 I-E96-443-1D

     ® 

    CUSTOM OR SPECIAL

     The assemblies can be mounted on rails in almost any enclo-sure and orientation. When sufficient mounting width is avail-able, horizontal orientation may be used.

    Figure  3-2  is an approximate scale representation of a stan-dard Elsag Bailey cabinet showing relative sizes of assembliesand the position numbering that would be used. Zone A shows3 type NRAI0_ input assemblies, zone B1 shows 3 typeNRAO01 output assemblies.

    WIRING CONNECTIONS AND CABLING 

    Each terminal block is clearly marked with black lettering on a  white clip-on tag. Several connections have compound termi-nal blocks connected by printed circuit board traces. Thesecompound blocks allow the jumping of wires while maintain-

    Figure 3-3. Cabinet Cross Section, Hard w are and Zone Identi f ication 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    34/68

    INSTALLATION

    WIRING CONNECTIONS AND CABLING

    I-E96-443-1D 3 - 5

    ing a single wire in any one clamp. All terminal block functionsare uniquely marked. The cage clamp technology provides afast and secure means of wiring connection such that crimpedlugs or ferrules are not necessary.

    In addition to the pre-terminated cable to the slave, three wir-

    ing connections are required on the system side of the termi-nation assembly. When the optional jumper boards, P/N WTL990757 are used, a fourth connection is required.

     A nominal +24 Vdc and dc common signal zero reference arerequired. Refer to Table 1-6. Connection, Configuration, PowerRequirements and Option Data for voltage tolerance, currentrequirements and necessary dc common grounding character-istics.

    Figure 3-4. System Side Wiring Connections and B oard Pow er Distr ibu tion 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    35/68

    INSTALLATION

    WIRING CONNECTIONS AND CABLING

    3 - 6 I-E96-443-1D

     ® 

    Field instrument cable shielding is drained by connecting thesystem side SH terminals to an appropriate ground with suffi-ciently low impedance to drain the EMF noise expected fromthe plant environment.

     The fourth connection is between the terminal and chassis

    ground to provide a low impedance path to ground for theunwanted incoming surges induced onto the input signal con-ductors.

     

    Figure 3-5. NRAI0_ an d NRAO01 w ith NRCS01’s 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    36/68

    INSTALLATION

    OTHER EQUIPMENT INTERFACE

    I-E96-443-1D 3 - 7

    OTHER EQUIPMENT INTERFACE 

     The supplied jumper boards can be replaced with either theoptional conditioners and isolators or custom designed daugh-ter boards allowing considerable interface flexibility. Refer toFigure A-11.

     The NRAI0_ can be interfaced to NDCS03, IISAC01 andNDIS0_ via the NRCS01 Termination Assembly. Refer to Figure3-5. When the IMASI03 is employed, keep in mind that theNDCS03 and IISAC01 can only accommodate 1-5 volt signalsfor direct bar graph display in the bypass mode.

    PRE-OPERATING ADJUSTMENTS 

    Every used input should be reviewed and DIP switches setand/or conditioners or isolators installed as required.

     The converters and isolators are pre-calibrated by the manu-facturer. However, for maximum accuracy, the calibrationshould be checked as outlined in Section 4  during initiainstallation and periodically as outlined in Section 6.

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    37/68

     ® 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    38/68

    INITIAL CALIBRATION

    I-E96-443-1D 4 - 1

    SECTION 4 - CALIBRATION

    INITIAL CALIBRATION 

     The base NRAI0_ Termination Assembly requires no calibra-tion. Proper setting of the DIP switches and proper configura-tion of the associated slave and processor modules isnecessary.

     The optional conditioners and isolators are calibrated by themanufacturer.

    Should the calibration of the conditioners drift with time, theycan be adjusted using the potentiometers located beneath thetop label.

    It is recommended that a bench or test set up be used whendoing the re-calibration of the conditioners and isolators.

    Peel back the top label, and refer to Figure 4-1.

    Figure 4-1. Condit ioner and Isolator,

    Cal ibra tion Potentiometer Locations (Top View ) 

    Figure 4-2. Condit ioner & Is olator Pin Location and Identi f ication (Bottom View ) 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    39/68

    CALIBRATION

    CHECKOUT

    4 - 2 I-E96-443-1D

     ® 

    CHECKOUT 

     All termination assemblies are factory checked for short cir-cuits, open circuits, and functional components (DIP switches,etc.).

     Termination assemblies installed in cabinet assemblies or racks by Elsag Bailey are 100% checked in conjunction withtheir respective slave modules. Refer to the Hardware/Com-munications Checkout Document listed in ELSAG BAILEY CANADA REFERENCE DOCUMENT S  in Section 1.

    IN-SERVICE CALIBRATION 

    In-service calibration is not recommended.

    Table 4-1. Condit ioner and Isolator Cal ibration Procedu re 

    1 Determine the desired input type and span and obtain test equipment able to sim-

    ulate 0 and 100% input.

    1.1 Ensure that the model being used is appropriate for the desired input span.

    2 Connect power supply, signal source and voltmeter as outlined in Figure 4-2.

    3 Set the signal source at zero (0%) input; adjust the zero potentiometer until 1 volt(or 0 volts, depending on output range) is seen at the output.

    4 Set the signal source to full scale (100%) input; adjust the span potentiometer until

    5 volts (or 10 volts, depending on output range) is seen at the output.

    5 Repeat steps 3 and 4 as required.

    6 Set the signal source to 3 volts; check that the output is 12 mA (or 3 volts depend-

    ing on output range). The isolator should be replaced if half scale accuracy is not

    acceptable.

    7 The conditioner or isolator is now ready for installation on to the termination

    assembly.

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    40/68

    INTRODUCTION

    I-E96-443-1D 5 - 1

    SECTION 5 - TROUBLESHOOTING

    INTRODUCTION 

     As an essentially passive device, it is unlikely that the termina-tion assembly will be the source of an equipment failure. Verifythat the procedures outlined in Section 6  have been per-formed.

     Any personnel performing troubleshooting should be familiar with both the hardware and software aspects of the systemand related field devices.

    ERROR MESSAGES AND CORRECTIVE ACTION 

    Error messages pertaining to system inputs and outputs are

    reported within the status bytes and error codes of the appli-cable controller or processor module. Refer to the REFERENCE DOCUMENT S  in Section 1 of this manual to determinethe appropriate controller or processor module instruction

     book.

     When operator interface stations are provided, the I90 Statusdisplays, which translate the module status bytes into textmessages, allow operators or maintenance personnel to iden-tify specific point malfunctions.

    PROBLEM DETERMINATION AND VERIFICATION PROCEDURES 

    In an industrial setting there may be a variety of causes forequipment malfunction. The age of a device, the quality of theenvironment (including extreme heat, temperature swingscorrosive gases, and conductive dusts) and of course, humanerror and accidents.

     As previously mentioned, the Elsag Bailey system can assist inthe location of a problem at a particular slave or input. Keep inmind that the termination assembly is the division betweenfield equipment and the DCS software (configuration), so bothmust be considered when pinpointing a problem.

    TROUBLESHOOTING GUIDE 

     The following guide is intended to assist in troubleshooting bydetailing the areas within the Elsag Bailey system that should

     be considered.

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    41/68

    TROUBLESHOOTING

    TROUBLESHOOTING GUIDE

    5 - 2 I-E96-443-1D

      F  i g u r e

      5 -  1 . 

      T r o u

      b  l e s

      h o o

      t  i n g

      G u

      i  d e

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    42/68

    TROUBLESHOOTING

    TROUBLESHOOTING GUIDE

    I-E96-443-1D 5 - 3

      F  i g u r e

      5 -  2 . 

      T r o u

      b  l e s

      h o o

      t  i n g

      G u

      i  d e

      ( c o n

      t  i n u

     e  d  )

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    43/68

    TROUBLESHOOTING

    TROUBLESHOOTING GUIDE

    5 - 4 I-E96-443-1D

      F  i g u r e

      5 -  3 . 

      T r o u

      b  l e s

      h o o

      t  i n g

      G u

      i  d e

      ( c o n

      t  i n u e

      d  )

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    44/68

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    45/68

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    46/68

    INTRODUCTION

    I-E96-443-1D 7 - 1

    SECTION 7 - REPAIR/REPLACEMENT PROCEDURES

    INTRODUCTION 

     The base termination assembly has no active components andhas been carefully designed to tolerate as many field wiringinconsistencies as possible. Without the optional conditionersand isolators, incorrect field wiring or DIP switch settings canresult in damage to a connected slave module.

    Inadvertent connection of a supply voltage greater than 48 Vdc will result in the destruction of one or both power supply sta-tus LED's DS1 and DS2. Damage to isolators and conditionersmay also occur if the incorrect voltage remains connected foran extended period.

     The optional conditioners and isolators provide protection tothe input of up to 240 Vac for limited time durations. Refer tothe Isolator Procedures in Section 4 - CALIBRATION .

    PROCEDURES 

    Refer to Section 5 - TROUBLESHOOTING   before replacingShould replacement of the assembly be necessary, the mostimportant connections to check are the +24 and COM. Theseconnections are often in a daisy chain arrangement and dis-connecting them could result in the loss of power to otherfunctioning termination assemblies.

     The daisy chaining done by Elsag Bailey is normally in a loopso that no power loss will occur if only a single terminationassembly is removed. Refer to the p ow er w i r i n g d r a w i n g ssupplied with your system to verify the wiring scheme used.

     To replace the termination assembly, follow Table 7-1.

    Table 7-1. Termin ation Assemb ly Replacement 

    1. Obtain a suitable replacement termination assembly.

    1.1 Ensure the availability of an appropriate replacement fuse.

    2. Remove any cables connected to P1, P3, P4, P5 and P6.

    3. Tag and disconnect all connections to the field side of the termination assembly.

    4. Disconnect and insulate the +24, COM and SH (shield) wiring.

    5. Remove the termination assembly using a medium flat blade screwdriver at

    each of the four mounting feet. Refer to Figure 7-1. Mounting Foot Release.

    6. Set all DIP switches on the replacement assembly to match the removed unit.

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    47/68

    REPAIR/REPLACEMENT PROCEDURES

    PROCEDURES

    7 - 2 I-E96-443-1D

     ® 

    .

    6.1 Move any optional conditioners and isolators to the replacement assem-

    bly, ensuring any thermocouple converters have a cold junction compen-

    sating thermistor mounted between the extra +’ve and C terminals.

    6.2 Install F1 if required.

    7. Install the replacement assembly by ensuring that each of the four feet engageon the system side, then pivot the field side in until all feet have latched into

    place.

    8. Reconnect the system side +24, COM and SH wiring.

    9. Reconnect all field side wiring.

    10. Reconnect all system side cabling.

    11. Verify proper operation of inputs. Refer to Figure 5-1. Troubleshooting Guide.

    Figure 7-1. Mountin g Foot Release 

    Table 7-1. Termina tion Assemb ly Replacement (continued) 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    48/68

    INTRODUCTION

    I-E96-443-1D 8 - 1

    SECTION 8 - SUPPORT SERVICES

    INTRODUCTION 

    Elsag Bailey is ready to help in the use, application and repairof its products. Contact your nearest sales office to makerequests for sales, applications, installation, repair, overhauland maintenance contract services.

    If it necessary to return an Elsag Bailey product for repair(warranty or chargeable) please contact the Return MaterialsDepartment for a reference number. Obtaining and using thisreference number on shipping documentation and correspon-dence will allow us to provide the fastest possible service.

    INSTRUCTION SUBSCRIPTION 

    Elsag Bailey offers the service of supplying Registered Cata-logue And Product Instruction Set manuals to Elsag Baileycustomers. This set of manuals incorporates all of the litera-ture relating to all Elsag Bailey products and systems equip-ment.

     These registered manuals are serialized and automaticallyupdated with new literature every three months. Elsag Baileycontrols will track the set(s) of manuals and supply detailedinstructions for the insertion of new or replacement materials

     with each submission of updates.

    Complete form LEC 1500-1190 and forward to the InstructionBook Department to order a new set of registered manuals. Arenewal notice will be sent to registered manual holders for theupdate services prior to the expiry date.

    REPLACEMENT PARTS 

    Most parts used on the termination assemblies are widelyavailable through industrial electronic component suppliersRefer to the parts list included in the part drawing set under

     Appendix B - NRAI0_ PART DRAWING .

     When making repairs at your facility, replacement parts can be ordered from an Elsag Bailey office. Provide this informa-tion:

    1. The nomenclature and complete part number of the prod-uct requiring parts.

    2. Part description, part number, and quantity.

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    49/68

    SUPPORT SERVICES

    REPLACEMENT PARTS

    8 - 2 I-E96-443-1D

     ® 

    3. Elsag Bailey instruction manual number, page number,and reference figure that identifies the part.

     When ordering standard parts from an Elsag Bailey office, usepart numbers and descriptions from Table 8-1.

    Table 8-1. Spare Parts List 

    Description ComponentPart Number

    Elsag Bailey Alternate

    Fuse, 3.0 Amp F1 L700723-13000 GMA-3A

    Jumper Board X1 to X15 L700837-B00000 WTL990599/63

    Cond./Isol. X1 to X15 L700837-______ 7B (Various)

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    50/68

    ()ASI02, IMFBS01 AND IMASI03

    I-E96-443-1D A - 1

    APPENDIX A - APPLICATION EXAMPLES

    ()ASI02, IMFBS01 AND IMASI03 

    Two Wire 4-20 mA with System Common Reference 

     Two wire transmitter, 24 Vdc system powered:

    S1 TO S16 = C2S7 TO S32 = 1C2, 2C2

    Four Wire 4-20 mA with System Common Reference 

    Four wire isolated by 120 Vac:

    S1 TO S16 = C1S17 TO S32 = 1C2, 2C2

    Figure A-1. Tw o Wire 4-20 mA w ith System Common Reference 

    Figure A-2. Four Wire 4-20 mA w ith System Common Reference 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    51/68

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    52/68

    APPLICATION EXAMPLES

    ()ASI02 AND AMFBS01 ONLY

    I-E96-443-1D A - 3

    Differential Voltage with No System Common Reference 

    Differential voltage input:

    S1 TO S16 = C1S17 TO S32 = 1C1, 2C1

    ()ASI02 AND AMFBS01 ONLY 

    Two Wire 4-20 mA Isolated 

     Two wire transmitter, 24 Vdc system powered with optiona

    isolator:

    S1 TO S16 = C1S17 TO S32 = 1C1, 2C2

    Figure A-5. Differential Voltage w ith No Sys tem Common Reference 

    Figure A-6. Tw o Wire 4-20 mA Isolated 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    53/68

    APPLICATION EXAMPLES

    ()ASI02 AND AMFBS01 ONLY

    A - 4 I-E96-443-1D

     ® 

    Four Wire 4-20 mA Isolated 

    Four wire transmitter, usually separately powered by 120 Vac, with optional isolator:

    S1 TO S16 = C1S17 TO S32 = 1C1, 2C2

    Differential Voltage (or mV) Isolated 

    Differential voltage (or mV) input with signal conditioner:

    S1 TO S16 = C1S17 TO S32 = 1C1, 2C2

    Figure A-7. Four Wire 4-20 mA Isolated 

    Figur e A-8. Differen tia l Voltage (or mV) Isolat ed 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    54/68

    APPLICATION EXAMPLES

    ()ASI02 AND AMFBS01 ONLY

    I-E96-443-1D A - 5

    Thermocouple Isolated 

     Thermocouple input with conditioner option and cold junctioncompensating thermistor:

    S1 TO S16 = C1S17 TO S32 = 1C1, 2C2

    RTD Isolated 

    RTD input with conditioner option:

    S1 TO S16 = C1S17 TO S32 = 1C1, 2C2

    Figure A-9. Thermocouple Isolated 

    Figure A-10. RTD Isolated 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    55/68

    APPLICATION EXAMPLES

    IMFBS01 ONLY

    A - 6 I-E96-443-1D

     ® 

    Special or Custom Signal 

    Special signal types can be conditioned using custom designeddaughter boards in place of the supplied jumper boards. Con-sult head office concerning feasibility and price.

    IMFBS01 ONLY 

    IMFBS01 Smart Transmitter 

    Point to point smart (Elsag Bailey) transmitter:

    S1 TO S16 = C2S17 TO S32 = 1C2, 2C2

    Figure A-11. Special or Custom Signal 

    Figure A-12. IMFBS01 Smar t Transmi t ter 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    56/68

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    57/68

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    58/68

    NRAI0_ PART DRAWING

    I-E96-443-1D B - 1

    APPENDIX B - NRAI0_ PART DRAWING

    NRAI0_ PART DRAWING 

    Figure B-1. NRAI01 Ana log Input Manu factur ing Draw ing, Sheet 1 of 4 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    59/68

    NRAI0_ PART DRAWING

    NRAI0_ PART DRAWING

    B - 2 I-E96-443-1D

     ® 

    Figure B-2. NRAI01 Ana log Inpu t Schema tic Diagram , Sheet 2 of 4 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    60/68

    NRAI0_ PART DRAWING

    NRAI0_ PART DRAWING

    I-E96-443-1D B - 3

    Figure B-3. NRAI01 Ana log Inpu t Part List, Sheet 3 of 4 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    61/68

    NRAI0_ PART DRAWING

    NRAI0_ PART DRAWING

    B - 4 I-E96-443-1D

     ® 

    Figure B-4. Ana log Inpu t Term inat ion Assembly Connection Detai ls, Sheet 4 of 4 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    62/68

    SPECIFICATION SHEETS

    I-E96-443-1D C - 1

    APPENDIX C - SPECIFICATION SHEETS

    SPECIFICATION SHEETS 

    Figure C-1. Inpu t Assignment a nd Configura tion Data Sheet for NRAI0 (Front) 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    63/68

    SPECIFICATION SHEETS

    SPECIFICATION SHEETS

    C - 2 I-E96-443-1D

     ® 

    Figure C-2. Input Ass ignment an d Configurat ion Data Sheet for NRAI0 (Ba ck) 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    64/68

    CONDITIONER AND ISOLATOR PART DRAWING

    I-E96-443-1D D - 1

    APPENDIX D - CONDITIONER AND ISOLATOR PART DRAWING

    CONDITIONER AND ISOLATOR PART DRAWING 

    Figure D-1. Ana log Device 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    65/68

     ® 

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    66/68

    I-E96-443-1D Index - 1

    Index

    Symbols- .................................................................................. 1-4

    () ................................................................................. 1-4

     _ ................................................................................. 1-4

    ()ASI02

    Slave Module........................................................ 1-1

    Straight Through Mode ......................................... 1-1

    A

    Analog Input Termination Assembly........................... 1-1

    Physical Operation................................................ 2-5

    Application Examples .................................................A-1

    ()ASI02.......................................................... A-1, A-3

    ()ASI02, IMFBS01, And IMASI03 .........................A-1AMFBS01 .............................................................A-3

    IMASI03........................................................ A-1, A-7

    IMFBS01....................................................... A-1, A-6

    C

    Cabling ....................................................................... 3-4

    Calibration .................................................................. 4-1

    Conditioner and Isolator........................................ 4-2

    Initial Calibration ................................................... 4-1

    In-Service.............................................................. 4-2

    Checkout .................................................................... 4-2

    Elsag Bailey Canada Reference Documents........ 4-2

    Conditioner and Isolator Calibration Procedure.......... 4-2Conditioner and Isolator Part Drawing........................D-1

    Corrective Maintenance ............................................. 6-1

    D

    Description and Operation.......................................... 2-1

    DIP Switch.................................................................. 2-3

    Settings................................................................. 2-4

    DIP Switch Functionality............................................. 2-3

    E

    Elsag Bailey Canada Reference Documents ............. 1-6

    Equipment Application................................................ 1-3Equipment Description ............................................... 1-2

    Equipment Malfunction............................................... 5-1

    Error Message

    Error Codes .......................................................... 5-1

    Error Messages

    Reference Documents .......................................... 5-1

    Status Bytes.......................................................... 5-1

    Error Messages and Corrective Action....................... 5-1

    FFunctional Operation...................................................2-1

    G

    Glossary of Terms.......................................................1-4

    I

    IMASI03 Slave Module ...............................................1-2

    IMFBS01

    Elsag Bailey Field Bus ..........................................1-2

    Smart Transmitter .................................................1-2

    IMFBS01 Slave Module ..............................................1-2

    In-Service Calibration..................................................4-2Installation

    Handling ................................................................3-1

    Introduction ...........................................................3-1

    Location Considerations........................................3-1

    Safety Considerations...........................................3-1

    Setup And Physical Installation.............................3-2

    Termination Cabinet Handling...............................3-1

    Unpacking and Inspection.....................................3-1

    Intended User .............................................................1-2

    Introduction .................................................................2-1

    M

    Maintenance ...............................................................6-1Maintenance Schedule..........................................6-1

    Preventative Maintenance.....................................6-1

    Manual Instructions.....................................................1-3

    N

    NRAI0 .........................................................................1-3

    Equipment Application ..........................................1-3

    Features ................................................................1-3

    Functional Operation.............................................2-1

    NRAI0_ Part Drawing................................................. B-1

    O

    Other Equipment Interface..........................................3-7

    Overview .....................................................................1-1

    Analog Input Termination Assembly .....................1-1

    P

    Physical Operation......................................................2-5

    Pre-Operating Adjustments.........................................3-7

    http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://02sectxx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://03sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://dappendx.pdf/http://06sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://02sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://04sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://01sectxx.pdf/http://02sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://02sectxx.pdf/http://bappendx.pdf/http://03sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://02sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://02sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://03sectxx.pdf/http://bappendx.pdf/http://02sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://06sectxx.pdf/http://02sectxx.pdf/http://01sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://03sectxx.pdf/http://04sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://02sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://05sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://02sectxx.pdf/http://06sectxx.pdf/http://dappendx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://04sectxx.pdf/http://03sectxx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://aappendx.pdf/http://02sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/http://01sectxx.pdf/

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    67/68

  • 8/15/2019 I-E96-443-1 NRAI0_ Rail Mounted Termination Assembly Analog Input

    68/68

    For the latest information on ABB and Year 2000 Product Compatibility 

    Visit us on the World Wide Web at http://www.abb.com 

    Our worldwide staff of professionals is ready to meet your needs for process automation.

    For the location nearest you, please contact the appropriate regional office.