TS-TC- 06G (X4) HITACHI SPLIT-SYSTEM AIR CONDITIONERS Nominal Capacity Range Technical Catalog (50 Hz) 9,500 kcal/h to 52,200 kcal/h Design Information 11,100 W to 60,800 W Models: 37,700 Btu/h to 207,100 Btu/h Cooling Units Condensing Units RAS-4U2S + RAS-4CT2S RAS-5U2S + RAS-5CT2S RAS-6U2S + RAS-6CT2S RAS-8U2S + RAS-8CT2S RAS-9U2S + RAS-9CT2S RAS-10U2S + RAS-10CT2S RAS-13U2S + RAS-13CT2S RAS-15U2S + RAS-15CT2S RAS-20U2S + RAS-20CT2S HITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and medium outdoor temperatures and comply with almost any types of installation requirements. These split-system air conditioners are composed of condensing units and cooling units. The condensing units are composed of compressors, air-cooled condensers, condenser fans, auxiliary and control equipments compactly packed in a weather-proof cabinet. The cooling units are direct expansion fan coil units for indoor installations, and are designed for duct air distribution systems in domestic and commercial applications. These units are composed of evaporator, expansion valve(s) or capillary tubes (for RAS-4U2S through RAS -10U2S only), an evaporator fan, a fan motor and auxiliary equipments in a cabinet.

Transcript of HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of...

Page 1: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

TS-TCⅠ- 06G (X4)

HITACHI SPLIT-SYSTEM AIR CONDITIONERS

Nominal Capacity Range Technical Catalog Ⅰ (50 Hz) 9,500 kcal/h to 52,200 kcal/h ─ Design Information ─ 11,100 W to 60,800 W Models: 37,700 Btu/h to 207,100 Btu/h Cooling Units Condensing Units RAS-4U2S + RAS-4CT2S RAS-5U2S + RAS-5CT2S RAS-6U2S + RAS-6CT2S RAS-8U2S + RAS-8CT2S

RAS-9U2S + RAS-9CT2S RAS-10U2S + RAS-10CT2S RAS-13U2S + RAS-13CT2S RAS-15U2S + RAS-15CT2S RAS-20U2S + RAS-20CT2S

HITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and medium outdoor temperatures and comply with almost any types of installation requirements. These split-system air conditioners are composed of condensing units and cooling units. The condensing units are composed of compressors, air-cooled condensers, condenser fans, auxiliary and control equipments compactly packed in a

weather-proof cabinet. The cooling units are direct expansion fan coil units for indoor installations, and are designed for duct air distribution systems in domestic and commercial applications. These units are composed of evaporator, expansion valve(s) or capillary tubes (for RAS-4U2S through RAS -10U2S only), an evaporator fan, a fan motor and auxiliary equipments in a cabinet.

Page 2: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

2

FEATURES Optimum Designs for Individual Requirements

Cooling Units

High Performance Evaporator Fan The powerful and efficient multi-blade centrifugal fan creates high static pressure with minimum power consumption and smooth air flow. Evaporator fan bearings can be replaced without removing fans. An adjustable motor pulley is mounted in RAS-6U2S through RAS-20U2S, in order to cover wider ranges of fan speed.

Well-Designed Evaporator Highly-Efficient cross fin coils have been applied to provide a larger cooling capacity with low air speed on the coil.

Condensing Units

Energy-Saving Design Highly-Efficient Scroll Compressors - Low power input is achieved by specially designed compressors and heat exchangers and their combinations.

Optional Accessories Filter Box and Filter - A high performance air filter and a filter box are provided for the return air connection of all models.

Optional Accessory Attachment

RAS-4U2S through RAS-15U2S

RAS-20U2S

Air Inlet

Air Filter

Cooling

Filter Box

Unit

(Standard Type)

(Optional Type)

Page 3: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

3

GENERAL DATA Unit General Data

Cooling Capacity According to Unit Combination Model

Cooling Unit RAS-4U2S RAS-5U2S RAS-6U2S RAS-8U2S RAS-9U2S RAS-10U2S RAS-13U2S RAS-15U2S RAS-20U2S

Condensing Unit RAS-4CT2S RAS-5CT2S RAS-6CT2S RAS-8CT2S RAS-9CT2S RAS-10CT2S RAS-13CT2S RAS-15CT2S RAS-20CT2S

kcal/h 9,500 12,000 15,000 18,100 22,400 25,300 30,100 37,600 52,200 W 11,100 14,000 17,500 21,100 26,000 29,400 35,000 43,700 60,800

Nominal Cooling Capacity at 35℃ outdoor temperature *1 Btu/h 37,700 47,600 59,500 71,800 88,900 100,400 119,500 149,200 207,100

kcal/h 8,500 10,800 13,400 16,300 20,000 22,500 26,900 33,600 46,600 W 9,900 12,600 15,500 19,000 23,300 26,200 31,300 39,100 54,200

Nominal Cooling Capacity at 46℃ outdoor temperature **1 Btu/h 33,700 42,900 53,200 64,700 79,500 89,300 106,700 133,300 184,900

Condensing Unit Model RAS-4CT2S RAS-5CT2S RAS-6CT2S RAS-8CT2S RAS-9CT2S RAS-10CT2S RAS-13CT2S RAS-15CT2S RAS-20CT2S

Capacity Control % 100,0 100,0 100,0 100,0 100,0 100,0 100,60,0 100,60,0 100,50,0 Cabinet Synthetic Resin Painted on Galvanized Steel Plates

Color Beige (MUNSELL Code) (2.5Y 8/2)

Height mm 880 880 880 910 1,000 1,000 790 790 1,012

(in.) (34-5/8) (34-5/8) (34-5/8) (35-13/16) (39-3/8) (39-3/8) (31-1/16) (31-1/16) (39-27/32)

Width mm 782 782 782 782 985 985 1,806 1,806 1,986

(in.) (30-13/16) (30-13/16) (30-13/16) (30-13/16) (38-3/4) (38-3/4) (71) (71) (78-3/16)

Depth mm 862 862 862 862 1,020 1,020 966 966 1,000

Outer

Dimensions

(in.) (33-15/16) (33-15/16) (33-15/16) (33-15/16) (40-3/16) (40-3/16) (38-1/32) (38-1/32) (39-3/8)

kg 130 130 133 185 220 220 330 400 425 Net Weight

(lbs.) (287) (287) (293) (408) (485) (485) (727) (881) (936) Refrigerant R-22

Number of Circuits 1 1 1 1 1 1 2 2 2

Compressor Hermetic Hermetic Hermetic Hermetic Hermetic Hermetic Hermetic Hermetic HermeticType Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Model 400DH 500DH 600DH 750EL 900EL 1000EL 750EL/500DH 1000EL/600DH 1000EL

Quantity 1 1 1 1 1 1 1/1 1/1 2 Condenser Multi-Pass Cross-Finned Tube Condenser Fan Direct Driven Propeller Fan

Motor kW 0.15 0.3 0.25 0.25 0.4 0.4 0.4/0.3 0.3 0.3 (hp) (1/5) (2/5) (1/3) (1/3) (1/2) (1/2) (1/2)/(2/5) (2/5) (2/5)

Quantity 1 1 1 1 1 1 2 2 2

Piping Connections With Flare Nut or Companion Flange for Field Piping Gas Line

Size (O.D) mm Ø19.05 Ø19.05 Ø19.05 Ø22.2 Ø28.57 Ø28.57 Ø25.4/Ø19.05 Ø25.4/Ø19.05 Ø25.4 (in.) (3/4) (3/4) (3/4) (7/8) (1-1/8) (1-1/8) (1)/(3/4) (1)/(3/4) (1) Type Flare Flare Flare Flange Flange Flange Flange/Flare Flange/Flare Flange

Quantity 1 1 1 1 1 1 1/1 1/1 2

Liquid Line Size (O.D) mm Ø12.7 Ø12.7 Ø12.7 Ø12.7 Ø15.88 Ø15.88 Ø12.7 Ø15.88/Ø12.7 Ø15.88

(in.) (1/2) (1/2) (1/2) (1/2) (5/8) (5/8) (1/2) (5/8)/(1/2) (5/8) Type Flare Flare Flare Flare Flare Flare Flare Flare Flare Quantity 1 1 1 1 1 1 2 1/1 2

Wiring Hole Main Power mm Ø52* Ø52* Ø52* Ø52* Ø52* Ø52* Ø52* Ø52* Ø52*

(in.) (2-1/16) (2-1/16) (2-1/16) (2-1/16) (2-1/16) (2-1/16) (2-1/16) (2-1/16) (2-1/16) Control mm Ø26.1* Ø26.1* Ø26.1* Ø26.1* Ø26.1* Ø26.1* Ø26.1* Ø26.1* Ø26.1*

(in.) (1-1/32) (1-1/32) (1-1/32) (1-1/32) (1-1/32) (1-1/32) (1-1/32) (1-1/32) (1-1/32)

kg 150 150 153 205 245 245 365 435 460 Shipping Weight

(lbs.) (330) (330) (337) (452) (540) (540) (803) (957) (1,012) Approximate Packing List

Height mm 1,010 1,010 1,010 1,040 1,130 1,130 945 945 1,168 (in.) (39-3/4) (39-3/4) (39-3/4) (40-15/16) (44-1/2) (44-1/2) (37-3/16) (37-3/16) (45-15/16)

Width mm 842 842 842 842 1,065 1,065 1,885 1,885 2,045 (in.) (33-5/32) (33-5/32) (33-5/32) (33-5/32) (41-15/16) (41-15/16) (74-1/4) (74-1/4) (80-1/2)

Depth mm 950 950 950 950 1,080 1,080 1,025 1,025 1,060 (in.) (37-3/8) (37-3/8) (37-3/8) (37-3/8) (42-1/2) (42-1/2) (40-11/32) (40-11/32) (41-23/32)

Measurements m3 0 . 8 1 0 . 8 1 0 . 8 1 0 . 8 3 1 .3 0 1 . 3 0 1 . 8 3 1 . 8 3 2 . 5 3 * : Knockout Hole

Page 4: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

4

GENERAL DATA

Unit General Data (Continued) Cooling Unit Model RAS-4U2S RAS-5U2S RAS-6U2S RAS-8U2S RAS-9U2S RAS-10U2S RAS-13U2S RAS-15U2S RAS-20U2S

Cabinet Galvanized Steel Plate

Color ─ (MUNSELL Code) ─

Height mm 500 500 500 500 550 550 600 600 1,055

(in.) (19-11/16) (19-11/16) (19-11/16) (19-11/16) (21-5/8) (21-5/8) (23-5/8) (23-5/8) (41-17/32)

Width mm 750 750 750 750 1,400 1,400 1,400 1,400 1,600 (in.) (29-1/2) (29-1/2) (29-1/2) (29-1/2) (55-1/8) (55-1/8) (55-3/16) (55-3/16) (63) Depth mm 890 890 1,080 1,280 1,100 1,100 1,015 1,015 860

Outer Dimensions

(in.) (35) (35) (42-1/2) (50-3/8) (43-5/16) (43-5/16) (39-15/16) (39-15/16) (33-27/32) kg 70 70 75 75 135 135 170 180 235

Net Weight (lbs.) (154) (154) (165) (165) (297) (297) (374) (396) (518)

Refrigerant R-22

Flow Control Device Capillary Tube Thermal Expansion Valve (One for Each Circuit)

Number of Circuits 1 1 1 1 1 1 2 2 2 Evaporator Fan Multi-Blade Centrifugal Fan(Double Suction)

Nominal Air Flow m3/min 37 50 65 69 82 90 110 130 180 m3/s 0.62 0.83 1.08 1.15 1.37 1.5 1.83 2.17 3.0 L/s 620 830 1080 1150 1370 1500 1830 2170 3000 (cfm) (1,310) (1,770) (2,300) (2,440) (2,920) (3,180) (3,880) (4,590) (6,360)

Motor kW 0.35 0.55 0.75 0.75 1.5 1.5 2.2 2.2 3.7 (hp) (1/2) (3/4) (1) (1) (2) (2) (3) (3) (5)

Quantity 1 1 1 1 1 1 1 1 1 Evaporator Multi-Pass Cross-Finned Tube Piping Connections Brazing Connection

Liquid Line

Size (O.D) mm Ø12.7 Ø12.7 Ø12.7 Ø12.7 Ø15.88 Ø15.88 Ø12.7 Ø15.88/Ø12.7 Ø15.88 (in.) (1/2) (1/2) (1/2) (1/2) (5/8) (5/8) (1/2) (5/8)/(1/2) (5/8)

Quantity 1 1 1 1 1 1 2 1/1 2

Gas Line

Size (O.D) mm Ø19.05 Ø19.05 Ø19.05 Ø22.2 Ø28.57 Ø28.57 Ø25.4/Ø19.05 Ø25.4/Ø19.05 Ø25.4

(in.) (3/4) (3/4) (3/4) (7/8) (1-1/8) (1-1/8) (1)/(3/4) (1)/(3/4) (1)

Quantity 1 1 1 1 1 1 1/1 1/1 2

Condensate Drain Female Piping Thread Screw Size FPT 3/4 3/4 3/4 3/4 1 1 3/4 3/4 3/4 Quantity 1 1 1 1 1 1 1 1 1

Wiring Hole Main mm Ø30 Ø30 Ø30 Ø30 Ø30 Ø30 Ø26 Ø26 Ø28

(in.) (1-3/16) (1-3/16) (1-3/16) (1-3/16) (1-3/16) (1-3/16) (1) (1) (1-3/32)

kg 90 90 100 100 160 160 190 200 255 Shipping Weight

(lbs.) (198) (198) (220) (220) (352) (352) (418) (440) (562)

Approximate Packing List Height mm 615 615 615 615 1,305 1,305 1,055 1,055 1,175

(in.) (24-7/32) (24-7/32) (24-7/32) (24-7/32) (51-3/8) (51-3/8) (41-1/2) (41-1/2) (46-1/4)

Width mm 810 810 810 810 1,590 1,590 1,450 1,450 1,720 (in.) (31-7/8) (31-7/8) (31-7/8) (31-7/8) (62-19/32) (62-19/32) (57-1/16) (57-1/16) (67-23/32)

Depth mm 1,010 1,010 1,200 1,400 615 615 740 740 910 (in.) (39-3/4) (39-3/4) (47-1/4) (55-1/8) (24-7/32) (24-7/32) (29-1/8) (29-1/8) (35-13/16)

Measurements m3 0.50 0.50 0.60 0.70 1.28 1.28 1.13 1.13 1.84

NOTES: 1.The capacities are gross capacities, which include the effect of

evaporator fan motor heat. 2.The nominal cooling capacity is based on the combined capacity of

the HITACHI standard split system, and is based on JIS standard B8616-1999 Temperature Conditions:

Evaporator Air Inlet Temperature: 27°C DB (80°F DB) 19°C WB (66°F WB) Condenser Air Inlet Temperature: *1) 35°C DB (95°F DB) **1) 46°C DB (115°F DB)

3.The standard combination of the HITACHI split-system air conditioners

is as follows:

Cooling Unit Condensing Unit Standard Power Supply RAS-4U2S + RAS-4CT2S Main (AC 3Ø ) Control (AC 1Ø ) RAS-5U2S + RAS-5CT2S 380V 50Hz 220V 50Hz RAS-6U2S + RAS-6CT2S 415V 50Hz 240V 50Hz RAS-8U2S + RAS-8CT2S RAS-9U2S + RAS-9CT2S RAS-10U2S + RAS-10CT2S RAS-13U2S + RAS-13CT2S RAS-15U2S + RAS-15CT2S RAS-20U2S + RAS-20CT2S

Page 5: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

5

WORKING RANGE

Working Range

Power Supply

The applicable voltage range for each unit is given in the Electrical Data. The working voltage among the three phases must be balanced within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the rated voltage.

Condenser Air Inlet Temperature and Evaporator Air Inlet Temperature

Condenser Air Inlet Temperature -Dry Bulb-

Evaporator Air Inlet Temperature -Dry/Wet Bulb- Model

Maximum Minimum Maximum Minimum

All Models 52°C 125°F

20°C 68°F

35°C / 21.5°C 95°F / 70.7°F

20°C / 14°C 68°F / 57.2°F

NOTES:

1. When the unit is operating at a condenser air inlet temperature of 52°C DB (125°F DB), the maximum evaporator air inlet temperature shall be 18°C WB (64.4°F WB).

2. All models: 80% to 120% of Nominal Air Flow.

Page 6: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

6

o

o 12.7 Brazing

20o

19.05 Brazingo

30

Summary

FPT 3/43

5

76 Both Sides

8 Air IntakeAir Discharge9

Duct ConnectionDuct Connection

Hole for Power Supply WiringCondensate Drain Connection

Magnetic Switch Box

1Mark Name

2

Service Panel

4

Gas Refrigerant Piping ConnectionLiquid Refrigerant Piping Connection

Hole for Operation Circuit Wiring

Hole for Power Supply WiringCondensate Drain Connection

Magnetic Switch Box

1Mark Name

2

Service Panel

4

Gas Refrigerant Piping ConnectionLiquid Refrigerant Piping Connection

Hole for Operation Circuit Wiringo

o 12.7 Brazing

20o 30

Summary

FPT 3/43

5

76 Both Sides

22.2 Brazingo

Duct ConnectionDuct Connection

Air DischargeAir Intake

98

Hole for Power Supply WiringCondensate Drain Connection

Magnetic Switch Box

1Mark Name

2

Service Panel

4

Gas Refrigerant Piping ConnectionLiquid Refrigerant Piping Connection

Hole for Operation Circuit Wiringo

o 12.7 Brazing

20o

19.05 Brazingo

30

Summary

FPT 3/43

5

76 Both Sides

Duct ConnectionDuct Connection

Air DischargeAir Intake

98

DIMENSIONAL DATA

Cooling Units RAS-4U2S and RAS-5U2S

RAS-6U2S

RAS-8U2S

Page 7: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

7

3 Refrigerant Gas Outlet for NO.1 Cycle 25.4 Brazing o

Condensate Drain Connection

1

Mark Name

2

Refrigerant Liquid Inlet for NO.1 Cycle

Summary

56

Refrigerant Liquid Inlet for NO.2 Cycle

Refrigerant Gas Outlet for NO.2 Cycle4

12.7 Brazingo

19.05 Brazing

Service Panel for Expansion Valve7Hole for Power Supply Wiring

o

12.7 Brazing for RAS-13U2So 15.88 Brazing for RAS-15U2So

FPT 3/4 26o

Screw Holes for Suspension Bolt8 4-M16

11

1312

4

NameMark

23

1Summary

Liquid Refrigerant Piping ConnectionGas Refrigerant Piping Connection

O 15.88 BrazingO 28.57 Brazing

Condensate Drain Piping Connection FPT 1Hole for Power Supply Wiring

56

Hole for Operation Circuit WiringO 30O 20

78

Service PanelService Panel

Service PanelRear Side OnlyBoth Sides

Front Side Only

910

Magenetic Switch BoxFresh Air Intake Duct ConnectionSuspension Bracket

Air DischargeAir Intake Duct Connection

Duct Connection

*2. Movable 50mm Right and Lefts Side.

*1. Movable 50mm Right and Lefts Side.Notes:

DIMENSIONAL DATA

Cooling Units RAS-9U2S and RAS-10U2S

RAS-13U2S and RAS-15U2S

Page 8: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

8

Hole for Power Supply Wiring 26-Both Sideso

Screw Holes for Suspension Bolt8 4-M16

Condensate Drain Connection

Service Panel for Expansion Valve

1Mark Name

2Refrigerant Gas Outlet for NO.1 Cycle

Refrigerant Liquid Inlet for NO.1 Cycle o 15.88 Brazing

25.4 Brazingo

Summary

FPT 1

3

5

76

Refrigerant Liquid Inlet for NO.2 Cycle o

25.4 BrazingoRefrigerant Gas Outlet for NO.2 Cycle4

15.88 Brazing

DIMENSIONAL DATA

Cooling Units RAS-20U2S

Page 9: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

9

26.1 (Knockout Hole)

12.7 Flare Connection19.05 Flare Connection

Summary

52 (Knockout Hole)

Magnetic Switch Box

Name

Connecting Hole for Refrigerant Liquid Line

Connecting Hole for

Power Supply Wiring

Operation Circuit Wiring

Refrigerant Gas Line

Mounting Hole

Service Panel

765

4

3

2

Mark1

4- 12.5

26.1(Knockout Hole)

12.7 Flare Connection25.4 Flare Connection

Summary

52(Knockout Hole)

Magnetic Switch Box

Name

Connecting Hole for Refrigerant Liquid Line

Connecting Hole for

Power Supply Wiring

Operation Circuit Wiring

Refrigerant Gas Line

Mounting Hole

Service Panel

765

4

3

2

Mark1

4- 12.5

26.1 (Knockout Hole)

15.88 Flare Connection 25.4 Flare Connection

Summary

52 (Knockout Hole)

Magnetic Switch Box

Name

Connecting Hole for Refrigerant Liquid Line

Connecting Hole for

Power Supply Wiring

Operation Circuit Wiring

Refrigerant Gas Line

Mounting Hole

Service Panel

765

4

3

2

Mark1

4- 12.5

DIMENSIONAL DATA

Condensing Units RAS-4CT2S through RAS-6CT2S

RAS-8CT2S

RAS-9CT2S and RAS-10CT2S

Page 10: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

10

Knockout Hole for Power Supply Wiring

1Mark Name

2Refrigerant Gas Outlet for NO.1 Cycle

Refrigerant Liquid Inlet for NO.1 Cycle

Knockout Hole for Operation Circuit Wiringo

o 15.88 Flare for Connection

26o

25.4 Flange Connectiono

52

Summary

3

5

8

6

Refrigerant Liquid Inlet for NO.2 Cycle

Refrigerant Gas Outlet for NO.2 Cycle4 o

15.88 Flare for Connectiono

25.4 Flange Connection

Magnetic Switch Box7 Service Panel

o

Knockout Hole for Power Supply Wiring

1

Mark Name

2Refrigerant Gas Outlet for NO.1 Cycle

Refrigerant Liquid Inlet for NO.1 Cycle

Knockout Hole for Operation Circuit Wiringo

26o

25.4 Flange Connection

52

Summary

3

5

8

6

Refrigerant Liquid Inlet for NO.2 Cycle

Refrigerant Gas Outlet for NO.2 Cycle4

12.7 Flare Connectiono

19.05 Flare Connection

Magnetic Switch Box7 Service Panel

o

12.7 Flare for RAS-13CT2So 15.88 Flare for RAS-15CT2So

DIMENSIONAL DATA

Condensing Units RAS-13CT2S and RAS-15CT2S

RAS-20CT2S

Page 11: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

11

Refrigerant Piping Connection Side

Refrigerant Piping Connection Side

SELECTION DATA

Operation Space

Cooling Units

RAS-4U2S through RAS-8U2S

RAS-9U2S and RAS-10U2S

RAS-13U2S and RAS-15U2S

RAS-20U2S

Condensing Units

Dimensions(mm)Model a b RAS-4CT2S 400 700 RAS-5CT2S 400 700 RAS-6CT2S 400 700 RAS-8CT2S 400 700 RAS-9CT2S 500 900 RAS-10CT2S 500 900

RAS-13CT2S and RAS-15CT2S

RAS-20CT2S

Page 12: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

12

805

Fan Motor

410

A

Evaporator

1400

Center of Gravity

A

Evaporator

CB

GravityCenter of

Fan Motor

950

D

Evaporator

A1600

460

GravityCenter of Fan Motor

SELECTION DATA

Weight Balance

Cooling Units

Dimensions(mm) Model A B C D

ApproximateOperating

Weight (kg) RAS-4U2S 522 380 890 700 70 RAS-5U2S 522 380 890 700 70 RAS-6U2S 650 380 1,080 700 75 RAS-8U2S 750 380 1,280 700 75 RAS-9U2S 820 520 1,400 1,100 135 RAS-10U2S 820 520 1,400 1,100 135

Dimensions(mm) Model A

Approximate OperatingWeight (kg)

RAS-13U2S 740 170 RAS-15U2S 730 180

Dimensions(mm) Model A

Approximate OperatingWeight (kg)

RAS-20U2S 720 235

Page 13: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

13

SELECTION DATA Weight Balance (Continued)

Condensing Units

Dimensions(mm) Model

A B C D

ApproximateOperating Weight (kg)

RAS-4CT2S 350 350 782 862 130

RAS-5CT2S 320 330 782 862 130

RAS-6CT2S 300 325 782 862 133

RAS-8CT2S 370 435 782 862 185

RAS-9CT2S 420 480 985 1,020 220

RAS-10CT2S 420 480 985 1,020 220

Dimensions(mm) Model

A B

Approximate Operating Weight (kg)

RAS-13CT2S 810 400 330 RAS-15CT2S 810 400 400 RAS-20CT2S 870 400 425

RAS-4CT2S, RAS-5CT2S, and RAS-6CT2S

RAS-8CT2S, RAS-9CT2S, and RAS-10CT2S RAS-13CT2S and RAS-15CT2S

RAS-20CT2S

Page 14: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

14

SELECTION DATA

Selection GuideSelection Example:

1. Determine the System Requirements

Calculate the total cooling capacity, sensible heat capacity, evaporator air flow and required external static pressure according to the design conditions. Clarify the power source frequency and the climatic conditions.

Given Conditions: Total Cooling Capacity 27,500 kcal/h Sensible Heat Capacity 21,000 kcal/h Condenser Air Inlet Temperature 40°C Evaporator Air Inlet Dry Bulb 29°C Evaporator Air Inlet Wet Bulb 20°C Evaporator Air Flow 115 m3/min External Static Pressure 16 mmAq Power Source 415V / 50 Hz Climatic Conditions High / Medium

2. Select a Matching Model Select model RAS-13U2S+RAS-13CT2S, by entering 40°C condenser air inlet temperature and 20 °C evaporator air inlet wet bulb (WB) at 110 m3/min. Evaporator air flow (QA) in the Cooling Capacity Table.(RAS-13U2S+RAS-13CT2S unit will provide cooling capacity of 29,200 kcal/h and a sensible heat capacity of 21,700 kcal/h)

3. Read Performance of the Model

The total cooling capacity (TC), sensible heat capacity (SHC*) at the dry bulb given in the table, compressor power input (IPT), and sensible heat correction factor (CR) can be determined by interpolation (or some can be read directly from the table when the conditions coincide with the tabulated figures).

At 20℃ WB

TC SHC* IPT CR (x1,000 (x1,000 kcal/h) kcal/h) (kW)

At 121 m3/min QA 30.2 22.8 11.0 1.82

At 110 m3/min QA 29.2 21.7 10.9 1.69

At 115 m3/min QA 29.7 22.2 11.0 1.75

(By Interpolation)

4. Correct the Sensible Heat Capacity (If Required)

Correct the sensible heat capacity for the given 29°C evaporator air inlet dry bulb from the tabulated 27°C (DB*) according to the following formula.

SHC =SHC*+CR×(DB-DB*), where,

SHC : corrected sensible heat capacity (×1,000kcal/h),

SHC* : sensible heat capacity from in the table (×1,000kcal/h),

DB : given evaporator air inlet dry bulb (°C) and

DB*: evaporator air inlet dry bulb (°C) given for each WB in the table.

For this example,

SHC =22.2+1.75x(29-27)=25.7(x1,000kca/h) 5. Determine the Readjusting Requirements for

Evaporator Fan From the Fan Performance Table (Page 19), the required fan speeds and motor brake power are determined to be 1,045 rpm and 1.10kW, respectively. (Evaporator fan motor input is 1.19kW as seen on Page 23, Electrical Data-Cooling Unit-IPT column for evaporator fan motor at 415V). In this case, the factory-mounted standard fan motor (2.2kW) possesses sufficient capacity. However, the regulation space of the adjustable motor pulley should be readjusted to 2.2mm (see “Fan Speed Adjustment” on Page 21).

6. Determine the Net Capacity

The capacities are gross capacities, which include the effect of evaporator fan motor heat. To determine net capacity as follows: Net capacity =gross capacity – MIF heat

=gross capacity (kcal/h) – MIF input (kW) x 860 (kcal/kW.h)

=30,100 kcal/h – 1.19 kW x 860 kcal/kW.h =30,100 kcal/h – 1,023 kcal/h =29,077 kcal/h

Net sensible capacity =25,700 kcal/h – 1,023 kcal/h =24,677 kcal/h

NOTE: 1.Direct interpolation is permissible. Do not extrapolate.

Page 15: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

15

SELECTION DATA Cooling Capacities

Conversion Multiplier:1 kcal/h=1.163W =3.968Btu/h

Evaporator Inlet Air Condenser Air Inlet Temperature ( oC ) Model QA WB DB* 20 25 30 35 40 46 52

-CR- oC TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT 16 23 8.9 7.2 2.7 8.6 7.1 2.9 8.2 6.9 3.1 7.9 6.8 3.3 7.5 6.6 3.4 6.9 6.4 3.7 6.4 6.1 3.9 33.3 18 25 9.7 7.3 2.8 9.3 7.1 3.0 8.9 7.0 3.2 8.5 6.8 3.3 8.1 6.6 3.5 7.6 6.4 3.8 6.9 6.1 4.0 20 27 10.3 7.2 2.9 10.0 7.1 3.1 9.6 6.9 3.3 9.1 6.8 3.4 8.7 6.6 3.6 8.1 6.4 3.9 7.4 6.1 4.1

-0.522- 22 30 10.8 7.6 2.9 10.4 7.4 3.1 10.0 7.3 3.3 9.5 7.1 3.5 9.1 7.0 3.7 8.4 6.7 4.0 7.8 6.5 4.3 RAS- 14 20 8.3 7.0 2.6 8.1 6.8 2.8 7.7 6.7 3.0 7.4 6.5 3.2 7.0 6.4 3.4 6.5 6.2 3.6 6.0 5.9 3.8 4U2S 37.0 16 23 9.2 7.6 2.7 8.9 7.5 2.9 8.5 7.3 3.1 8.1 7.2 3.3 7.7 7.0 3.5 7.2 6.8 3.7 6.6 6.5 4.0

+ 18 25 10.0 7.7 2.8 9.6 7.5 3.0 9.2 7.4 3.2 8.8 7.2 3.4 8.4 7.0 3.6 7.8 6.8 3.9 7.1 6.5 4.1 RAS- -0.567- 20 27 10.7 7.6 2.9 10.3 7.5 3.1 9.9 7.3 3.3 9.5 7.2 3.5 9.0 7.0 3.7 8.3 6.8 3.9 7.7 6.5 4.2

4CT2S 22 30 11.1 8.0 3.0 10.7 7.9 3.2 10.3 7.7 3.4 9.8 7.6 3.6 9.4 7.4 3.8 8.7 7.2 4.1 8.0 6.9 4.3 14 20 8.6 7.3 2.7 8.3 7.2 2.9 8.0 7.1 3.0 7.6 6.9 3.2 7.2 6.7 3.4 6.7 6.5 3.7 6.2 6.2 3.9 40.7 16 23 9.5 8.0 2.8 9.1 7.9 3.0 8.8 7.7 3.1 8.4 7.6 3.3 8.0 7.4 3.5 7.4 7.2 3.8 6.8 6.8 4.0 18 25 10.3 8.1 2.8 9.9 7.9 3.0 9.5 7.8 3.2 9.1 7.6 3.4 8.7 7.4 3.6 8.1 7.2 3.9 7.3 6.9 4.1 -0.610- 20 27 11.0 8.0 2.9 10.6 7.9 3.1 10.2 7.7 3.3 9.8 7.5 3.5 9.3 7.4 3.7 8.6 7.1 4.0 7.9 6.9 4.2 22 30 11.5 8.5 3.0 11.1 8.3 3.2 10.6 8.1 3.4 10.2 8.0 3.6 9.7 7.8 3.8 9.0 7.6 4.1 8.3 7.3 4.3

16 23 11.1 9.3 3.3 10.7 9.2 3.6 10.3 9.0 3.8 9.8 8.8 4.0 9.3 8.6 4.2 8.7 8.3 4.5 7.9 7.9 4.8 45.0 18 25 12.1 9.4 3.4 11.6 9.2 3.7 11.2 9.0 3.9 10.7 8.8 4.1 10.1 8.6 4.4 9.4 8.3 4.7 8.6 8.0 5.0

20 27 12.9 9.3 3.5 12.5 9.2 3.8 12.0 9.0 4.0 11.4 8.8 4.2 10.8 8.6 4.5 10.1 8.3 4.8 9.3 8.0 5.1

-0.705- 22 30 13.5 9.8 3.6 13.0 9.7 3.9 12.5 9.5 4.1 11.9 9.3 4.3 11.3 9.1 4.6 10.5 8.8 4.9 9.7 8.5 5.2

RAS- 14 20 10.4 9.0 3.2 10.1 8.9 3.5 9.7 8.7 3.7 9.2 8.5 3.9 8.8 8.3 4.1 8.2 8.0 4.4 7.5 7.5 4.7 5U2S 50.0 16 23 11.5 9.9 3.4 11.1 9.7 3.6 10.6 9.5 3.8 10.2 9.3 4.0 9.6 9.1 4.3 9.0 8.8 4.6 8.2 8.2 4.9

+ 18 25 12.5 9.9 3.5 12.0 9.8 3.7 11.5 9.6 3.9 11.0 9.4 4.2 10.5 9.1 4.4 9.7 8.9 4.7 8.9 8.5 5.0 RAS- -0.766- 20 27 13.3 9.9 3.5 12.9 9.7 3.8 12.4 9.5 4.0 11.8 9.3 4.3 11.2 9.1 4.5 10.4 8.8 4.9 9.6 8.5 5.1

5CT2S 22 30 13.9 10.4 3.6 13.4 10.2 3.9 12.9 10.1 4.1 12.3 9.9 4.4 11.7 9.6 4.6 10.9 9.4 5.0 10.0 9.1 5.3 14 20 10.7 9.5 3.3 10.4 9.3 3.5 10.0 9.1 3.7 9.5 8.9 3.9 9.0 8.7 4.2 8.4 8.4 4.5 7.7 7.7 4.8

55.0 16 23 11.8 10.4 3.4 11.4 10.2 3.6 11.0 10.1 3.9 10.5 9.9 4.1 10.0 9.6 4.3 9.3 9.3 4.6 8.5 8.5 4.9 18 25 12.9 10.5 3.5 12.4 10.3 3.7 11.9 10.1 4.0 11.4 9.9 4.2 10.8 9.7 4.5 10.1 9.4 4.8 9.2 9.0 5.1

-0.824- 20 27 13.8 10.4 3.6 13.3 10.2 3.8 12.8 10.0 4.1 12.2 9.8 4.3 11.6 9.6 4.6 10.8 9.3 4.9 9.9 9.0 5.2

22 30 14.4 11.0 3.7 13.8 10.8 3.9 13.3 10.6 4.2 12.7 10.4 4.4 12.1 10.2 4.7 11.2 9.9 5.0 10.4 9.6 5.3 52.0 18 25 15.2 11.5 4.2 14.6 11.2 4.5 14.1 11.0 4.8 13.4 10.7 5.0 12.8 10.5 5.3 11.9 10.1 5.7 10.8 9.7 6.1 20 27 16.2 11.4 4.3 15.7 11.2 4.6 15.1 10.9 4.9 14.4 10.7 5.2 13.7 10.4 5.5 12.7 10.1 5.9 11.7 9.7 6.2 -0.832- 22 30 16.9 12.0 4.4 16.3 11.8 4.7 15.7 11.5 5.0 15.0 11.3 5.3 14.2 11.0 5.6 13.3 10.7 6.0 12.2 10.3 6.4 16 23 14.5 12.2 4.1 14.0 11.9 4.4 13.4 11.7 4.7 12.8 11.4 4.9 12.2 11.2 5.2 11.3 10.8 5.6 10.4 10.4 6.0 58.5 18 25 15.7 12.2 4.2 15.2 12.0 4.5 14.6 11.7 4.8 13.9 11.5 5.1 13.2 11.2 5.4 12.3 10.8 5.8 11.2 10.4 6.2 20 27 16.8 12.1 4.3 16.2 11.9 4.7 15.6 11.7 4.9 14.9 11.4 5.2 14.1 11.1 5.5 13.1 10.8 5.9 12.1 10.4 6.3 -0.916- 22 30 17.5 12.8 4.5 16.9 12.6 4.8 16.2 12.3 5.1 15.5 12.1 5.4 14.7 11.8 5.7 13.7 11.4 6.1 12.7 11.1 6.5 14 20 13.5 11.7 4.0 13.1 11.5 4.3 12.6 11.3 4.6 12.0 11.0 4.8 11.4 10.8 5.1 10.6 10.4 5.5 9.7 9.7 5.8

RAS- 65.0 16 23 14.9 12.9 4.2 14.4 12.6 4.5 13.8 12.4 4.7 13.2 12.1 5.0 12.6 11.9 5.3 11.7 11.5 5.7 10.7 10.7 6.0 6U2S 18 25 16.2 12.9 4.3 15.7 12.7 4.6 15.0 12.4 4.9 14.4 12.2 5.2 13.7 11.9 5.5 12.7 11.5 5.9 11.6 11.1 6.2

+ -0.996- 20 27 17.4 12.9 4.4 16.8 12.6 4.7 16.1 12.4 5.0 15.4 12.1 5.3 14.6 11.8 5.6 13.6 11.4 6.0 12.5 11.0 6.4 RAS- 22 30 18.1 13.5 4.5 17.5 13.3 4.8 16.8 13.1 5.1 16.0 12.8 5.4 15.2 12.5 5.7 14.2 12.2 6.2 13.1 11.8 6.5

6CT2S 14 20 14.0 12.3 4.1 13.5 12.1 4.4 13.0 11.9 4.6 12.4 11.6 4.9 11.8 11.4 5.2 11.0 11.0 5.6 10.0 10.0 5.9 71.5 16 23 15.4 13.6 4.2 14.9 13.3 4.5 14.3 13.1 4.8 13.7 12.8 5.1 13.0 12.5 5.4 12.1 12.1 5.8 11.0 11.0 6.1 18 25 16.8 13.6 4.3 16.2 13.4 4.6 15.5 13.1 4.9 14.8 12.8 5.2 14.1 12.6 5.5 13.1 12.2 5.9 11.9 11.7 6.3 -1.08- 20 27 17.9 13.5 4.4 17.3 13.3 4.8 16.6 13.0 5.1 15.9 12.8 5.3 15.1 12.5 5.7 14.0 12.1 6.1 12.9 11.7 6.4 22 30 18.7 14.3 4.6 18.0 14.1 4.9 17.3 13.8 5.2 16.5 13.5 5.5 15.7 13.3 5.8 14.7 12.9 6.2 13.5 12.5 6.6 14 20 14.4 12.9 4.1 13.9 12.7 4.4 13.4 12.5 4.7 12.8 12.2 4.9 12.1 11.9 5.2 11.3 11.3 5.6 10.4 10.4 6.0 78.0 16 23 15.9 14.2 4.2 15.4 14.0 4.5 14.7 13.7 4.8 14.1 13.5 5.1 13.4 13.2 5.4 12.4 12.4 5.8 11.4 11.4 6.2 18 25 17.3 14.3 4.4 16.7 14.0 4.7 16.0 13.8 5.0 15.3 13.5 5.3 14.5 13.2 5.6 13.5 12.8 6.0 12.3 12.3 6.3 -1.15- 20 27 18.5 14.2 4.5 17.9 14.0 4.8 17.1 13.7 5.1 16.4 13.4 5.4 15.5 13.1 5.7 14.5 12.7 6.1 13.3 12.3 6.5 22 30 19.3 15.0 4.6 18.6 14.8 4.9 17.9 14.5 5.2 17.1 14.2 5.5 16.2 14.0 5.9 15.1 13.6 6.3 13.9 13.2 6.7

QA : Evaporator Air Flow (m3/min) TC : Total Cooling Capacity (x 1000kcal/h) CR : Sensible Heat Correction Factor SHC* : Sensible Heat Capacity (x 1000kcal/h) Given for Each WB and DB* WB : Evaporator Air Inlet Wet Bulb (°C) IPT : Compressor Input Power (kW) DB* : Evaporator Air Inlet Dry Bulb (°C) Given for Each WB NOTE: The data is based on the following conditions. Refrigerant Piping Length in One Direction: 5 Meters Horizontal.

Page 16: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

16

SELECTION DATA Cooling Capacities

Conversion Multiplier:1 kcal/h=1.163W =3.968Btu/h

Evaporator Inlet Air Condenser Air Inlet Temperature ( oC ) Model QA WB DB* 20 25 30 35 40 46 52

-CR- oC TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT 55.2 18 25 18.3 13.1 5.6 17.7 12.8 6.0 17.0 12.5 6.4 16.2 12.2 6.8 15.4 11.9 7.2 14.3 11.4 7.7 13.0 10.9 8.2 20 27 19.6 13.1 5.8 18.9 12.8 6.2 18.2 12.5 6.6 17.3 12.2 6.9 16.5 11.8 7.3 15.3 11.4 7.9 14.1 10.9 8.4 -0.883- 22 30 20.4 13.6 5.9 19.7 13.3 6.3 18.9 13.1 6.7 18.1 12.7 7.1 17.2 12.4 7.5 16.0 12.0 8.1 14.8 11.6 8.6 16 23 17.4 13.8 5.5 16.8 13.6 5.9 16.2 13.3 6.3 15.4 12.9 6.6 14.7 12.6 7.0 13.6 12.1 7.6 12.5 11.7 8.0 62.1 18 25 19.0 13.9 5.7 18.3 13.6 6.1 17.6 13.3 6.5 16.8 13.0 6.8 15.9 12.6 7.2 14.8 12.2 7.8 13.5 11.7 8.3 20 27 20.3 13.8 5.8 19.6 13.6 6.2 18.8 13.3 6.6 17.9 12.9 7.0 17.0 12.6 7.4 15.8 12.1 8.0 14.5 11.6 8.5 -0.972- 22 30 21.1 14.5 6.0 20.4 14.2 6.4 19.6 13.9 6.8 18.7 13.6 7.2 17.8 13.3 7.6 16.6 12.8 8.2 15.3 12.4 8.7 14 20 16.3 13.4 5.4 15.8 13.1 5.8 15.2 12.8 6.1 14.5 12.5 6.5 13.8 12.2 6.9 12.8 11.7 7.4 11.7 11.3 7.8

RAS- 69.0 16 23 18.0 14.6 5.6 17.4 14.3 6.0 16.7 14.0 6.4 16.0 13.7 6.7 15.1 13.3 7.1 14.1 12.9 7.6 12.9 12.4 8.1 8U2S 18 25 19.6 14.7 5.7 18.9 14.4 6.2 18.1 14.1 6.6 17.3 13.8 6.9 16.5 13.4 7.3 15.3 12.9 7.9 13.9 12.4 8.4

+ -1.06- 20 27 21.0 14.6 5.9 20.2 14.3 6.3 19.4 14.0 6.7 18.5 13.7 7.1 17.6 13.3 7.5 16.4 12.9 8.1 15.0 12.4 8.6 RAS- 22 30 21.9 15.3 6.1 21.1 15.0 6.5 20.2 14.7 6.9 19.3 14.4 7.3 18.4 14.1 7.7 17.1 13.6 8.3 15.8 13.2 8.8

8CT2S 14 20 16.9 14.0 5.4 16.3 13.8 5.8 15.7 13.5 6.2 15.0 13.2 6.6 14.2 12.8 6.9 13.2 12.4 7.5 12.1 11.9 7.9 75.9 16 23 18.6 15.4 5.6 18.0 15.1 6.0 17.2 14.8 6.4 16.5 14.4 6.8 15.6 14.1 7.2 14.5 13.6 7.7 13.3 13.1 8.2 18 25 20.2 15.5 5.8 19.5 15.1 6.2 18.7 14.8 6.6 17.9 14.5 7.0 17.0 14.1 7.4 15.8 13.7 8.0 14.4 13.1 8.4 -1.14- 20 27 21.6 15.4 6.0 20.9 15.1 6.4 20.0 14.8 6.8 19.1 14.4 7.2 18.2 14.0 7.6 16.9 13.6 8.2 15.5 13.1 8.7 22 30 22.6 16.1 6.1 21.8 15.8 6.6 20.9 15.5 7.0 20.0 15.2 7.4 19.0 14.9 7.8 17.7 14.4 8.4 16.3 13.9 8.9 14 20 17.4 14.7 5.5 16.8 14.4 5.9 16.1 14.1 6.3 15.4 13.8 6.6 14.6 13.4 7.0 13.6 13.0 7.5 12.5 12.5 8.0 82.8 16 23 19.2 16.1 5.7 18.5 15.8 6.1 17.8 15.5 6.5 17.0 15.1 6.8 16.1 14.8 7.3 15.0 14.3 7.8 13.7 13.7 8.3 18 25 20.9 16.2 5.9 20.1 15.9 6.3 19.3 15.5 6.7 18.5 15.2 7.1 17.5 14.8 7.5 16.3 14.3 8.0 14.9 13.8 8.5 -1.22- 20 27 22.3 16.1 6.0 21.5 15.8 6.4 20.7 15.5 6.9 19.8 15.1 7.2 18.7 14.7 7.7 17.4 14.3 8.2 16.0 13.7 8.7 22 30 23.3 16.9 6.2 22.4 16.6 6.6 21.5 16.3 7.0 20.6 16.0 7.4 19.6 15.6 7.9 18.2 15.2 8.5 16.8 14.7 9.0 65.6 18 25 22.7 16.0 5.6 21.8 15.6 6.1 21.0 15.2 6.7 20.0 14.8 7.2 19.0 14.4 7.9 17.7 13.9 8.6 16.1 13.2 9.3 20 27 24.2 15.9 5.8 23.4 15.6 6.3 22.5 15.2 6.8 21.4 14.8 7.4 20.4 14.3 8.1 18.9 13.8 8.9 17.4 13.2 9.6 -1.05- 22 30 25.3 16.6 5.9 24.4 16.2 6.5 23.4 15.8 7.0 22.3 15.5 7.6 21.2 15.0 8.3 19.8 14.5 9.1 18.2 14.0 9.8 16 23 21.6 16.8 5.5 20.8 16.5 6.0 20.0 16.1 6.5 19.1 15.7 7.1 18.1 15.3 7.7 16.8 14.7 8.5 15.4 14.1 9.2 73.8 18 25 23.5 16.9 5.7 22.6 16.6 6.2 21.7 16.2 6.7 20.7 15.8 7.3 19.7 15.3 8.0 18.3 14.8 8.7 16.7 14.1 9.5 20 27 25.1 16.8 5.8 24.2 16.5 6.4 23.2 16.1 6.9 22.2 15.7 7.5 21.1 15.3 8.2 19.6 14.7 9.0 18.0 14.1 9.7 -1.16- 22 30 26.2 17.6 6.0 25.2 17.2 6.6 24.2 16.9 7.1 23.1 16.5 7.7 22.0 16.1 8.4 20.5 15.5 9.2 18.9 15.0 9.9 14 20 20.2 16.3 5.4 19.5 15.9 5.9 18.8 15.6 6.5 17.9 15.2 6.9 17.0 14.8 7.6 15.8 14.2 8.3 14.5 13.6 9.0

RAS- 82.0 16 23 22.3 17.8 5.6 21.5 17.4 6.1 20.7 17.0 6.6 19.7 16.6 7.2 18.7 16.2 7.8 17.4 15.6 8.6 16.0 15.0 9.39U2S 18 25 24.2 17.9 5.8 23.4 17.5 6.3 22.4 17.1 6.8 21.4 16.7 7.4 20.4 16.2 8.0 18.9 15.7 8.8 17.3 15.0 9.6

+ -1.26- 20 27 25.9 17.8 5.9 25.0 17.4 6.5 24.0 17.0 7.0 22.9 16.6 7.6 21.8 16.2 8.2 20.3 15.6 9.1 18.6 15.0 9.8RAS- 22 30 27.0 18.6 6.1 26.1 18.2 6.6 25.0 17.9 7.2 23.9 17.5 7.8 22.7 17.0 8.5 21.2 16.5 9.3 19.5 15.9 10.0

9CT2S 14 20 20.9 17.1 5.4 20.2 16.7 6.0 19.4 16.4 6.5 18.5 16.0 7.0 17.6 15.5 7.6 16.4 15.0 8.4 15.0 14.4 9.1 90.2 16 23 23.0 18.7 5.6 22.2 18.3 6.2 21.3 17.9 6.7 20.4 17.5 7.3 19.3 17.0 7.9 18.0 16.5 8.7 16.5 15.8 9.4 18 25 25.0 18.8 5.8 24.1 18.4 6.4 23.2 18.0 6.9 22.1 17.6 7.5 21.0 17.1 8.1 19.5 16.5 8.9 17.8 15.8 9.6 -1.36- 20 27 26.8 18.7 6.0 25.8 18.3 6.5 24.8 17.9 7.1 23.7 17.5 7.7 22.5 17.0 8.3 20.9 16.4 9.1 19.2 15.8 9.9 22 30 27.9 19.6 6.1 26.9 19.2 6.7 25.8 18.8 7.3 24.7 18.4 7.9 23.5 18.0 8.5 21.9 17.4 9.4 20.1 16.8 10.1 14 20 21.5 17.9 5.5 20.8 17.5 6.0 20.0 17.1 6.5 19.1 16.7 7.1 18.1 16.3 7.7 16.9 15.7 8.5 15.4 15.1 9.2 98.4 16 23 23.7 19.5 5.7 22.9 19.2 6.2 22.0 18.8 6.7 21.0 18.3 7.3 19.9 17.9 8.0 18.5 17.3 8.8 17.0 16.6 9.5 18 25 25.8 19.6 5.9 24.9 19.3 6.4 23.9 18.9 7.0 22.8 18.4 7.6 21.7 18.0 8.2 20.2 17.3 9.0 18.4 16.6 9.7 -1.45- 20 27 27.6 19.5 6.0 26.6 19.2 6.6 25.6 18.8 7.1 24.4 18.3 7.7 23.2 17.8 8.4 21.6 17.2 9.2 19.8 16.6 10.0 22 30 28.8 20.5 6.2 27.8 20.1 6.8 26.6 19.7 7.3 25.5 19.3 8.0 24.2 18.9 8.6 22.5 18.3 9.5 20.8 17.7 10.2 72.0 18 25 25.6 17.9 6.9 24.7 17.4 7.3 23.7 17.0 7.8 22.6 16.6 8.2 21.5 16.1 8.7 20.0 15.4 9.4 18.2 14.7 10.0 20 27 27.4 17.8 7.0 26.4 17.4 7.5 25.4 16.9 8.0 24.2 16.5 8.5 23.0 16.0 9.0 21.4 15.4 9.6 19.6 14.7 10.2 -1.16- 22 30 28.5 18.5 7.2 27.5 18.1 7.7 26.4 17.7 8.2 25.2 17.2 8.7 24.0 16.8 9.2 22.4 16.2 9.9 20.6 15.5 10.5 16 23 24.4 18.8 6.7 23.5 18.4 7.2 22.6 18.0 7.7 21.6 17.5 8.1 20.5 17.0 8.6 19.0 16.4 9.2 17.4 15.7 9.8 81.0 18 25 26.5 18.9 6.9 25.5 18.5 7.4 24.5 18.1 7.9 23.4 17.6 8.3 22.2 17.1 8.8 20.7 16.5 9.5 18.8 15.7 10.1 20 27 28.3 18.8 7.1 27.3 18.4 7.6 26.2 18.0 8.1 25.1 17.5 8.6 23.8 17.0 9.1 22.1 16.4 9.7 20.3 15.7 10.3 -1.27- 22 30 29.5 19.6 7.3 28.5 19.2 7.8 27.3 18.8 8.3 26.1 18.3 8.8 24.8 17.9 9.3 23.1 17.3 10.0 21.3 16.6 10.6 14 20 22.8 18.2 6.6 22.1 17.8 7.0 21.2 17.4 7.5 20.2 16.9 7.9 19.2 16.4 8.4 17.9 15.8 9.0 16.4 15.1 9.6

RAS- 90.0 16 23 25.2 19.8 6.8 24.3 19.4 7.3 23.3 19.0 7.8 22.3 18.5 8.2 21.1 18.0 8.7 19.7 17.4 9.3 18.0 16.7 9.9 10U2S 18 25 27.4 19.9 7.0 26.4 19.5 7.5 25.3 19.1 8.0 24.2 18.6 8.4 23.0 18.1 8.9 21.4 17.4 9.6 19.5 16.7 10.2

+ -1.38- 20 27 29.3 19.8 7.2 28.3 19.4 7.7 27.1 19.0 8.2 25.9 18.5 8.7 24.6 18.0 9.2 22.9 17.3 9.9 21.0 16.6 10.5 RAS- 22 30 30.5 20.7 7.4 29.4 20.3 7.9 28.3 19.9 8.4 27.0 19.4 8.9 25.7 18.9 9.4 23.9 18.3 10.1 22.0 17.7 10.7

10CT2S 14 20 23.6 19.1 6.6 22.8 18.7 7.1 21.9 18.2 7.6 20.9 17.8 8.0 19.8 17.3 8.5 18.5 16.7 9.1 16.9 16.0 9.7 99.0 16 23 26.0 20.8 6.9 25.1 20.4 7.4 24.1 20.0 7.8 23.0 19.5 8.3 21.8 19.0 8.8 20.3 18.3 9.4 18.6 17.6 10.0 18 25 28.3 20.9 7.1 27.2 20.5 7.6 26.2 20.1 8.1 25.0 19.6 8.5 23.7 19.1 9.0 22.1 18.4 9.7 20.1 17.6 10.3 -1.49- 20 27 30.2 20.8 7.3 29.2 20.4 7.8 28.0 20.0 8.3 26.7 19.5 8.7 25.4 18.9 9.3 23.6 18.3 10.0 21.7 17.6 10.6 22 30 31.5 21.8 7.5 30.4 21.4 8.0 29.2 20.9 8.5 27.9 20.5 9.0 26.5 20.0 9.5 24.7 19.4 10.2 22.7 18.7 10.8 14 20 24.3 19.9 6.7 23.5 19.5 7.2 22.5 19.1 7.6 21.6 18.6 8.1 20.4 18.1 8.6 19.0 17.5 9.2 17.4 16.8 9.8 108.0 16 23 26.8 21.8 6.9 25.9 21.4 7.4 24.8 20.9 7.9 23.7 20.4 8.4 22.5 19.9 8.8 20.9 19.2 9.5 19.2 18.5 10.1 18 25 29.2 21.9 7.2 28.1 21.5 7.7 27.0 21.0 8.2 25.8 20.5 8.6 24.5 20.0 9.1 22.8 19.3 9.8 20.7 18.5 10.4 -1.59- 20 27 31.2 21.8 7.3 30.1 21.4 7.9 28.9 20.9 8.4 27.6 20.4 8.8 26.2 19.9 9.3 24.4 19.2 10.1 22.4 18.4 10.7 22 30 32.5 22.8 7.5 31.4 22.4 8.1 30.1 22.0 8.6 28.7 21.5 9.1 27.3 21.0 9.6 25.5 20.3 10.3 23.5 19.6 10.9

QA : Evaporator Air Flow (m3/min) TC : Total Cooling Capacity (x 1000kcal/h) CR : Sensible Heat Correction Factor SHC* : Sensible Heat Capacity (x 1000kcal/h) Given for Each WB and DB* WB : Evaporator Air Inlet Wet Bulb (°C) IPT : Compressor Input Power (kW) DB* : Evaporator Air Inlet Dry Bulb (°C) Given for Each WB NOTE: The data is based on the following conditions. Refrigerant Piping Length in One Direction: 5 Meters Horizontal.

Page 17: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

17

SELECTION DATA Cooling Capacities

Conversion Multiplier:1 kcal/h=1.163W =3.968Btu/h

Evaporator Inlet Air Condenser Air Inlet Temperature ( oC )

Model QA WB DB* 20 25 30 35 40 46 52

-CR- oC TC SHC* IPT TC SHC

* IPT TC SHC*

IPT TC SHC*

IPT TC SHC*

IPT TC SHC* IPT TC SHC

*IPT

88.0 18 25 30.4 21.4 8.2 29.3 21.0 8.8 28.2 20.5 9.3 26.9 19.9 9.8 25.6 19.3 10.4 23.8 18.6 11.2 21.7 17.7 11.9 20 27 32.5 21.3 8.4 31.4 20.9 9.0 30.2 20.4 9.5 28.8 19.8 10.1 27.3 19.2 10.7 25.4 18.5 11.5 23.3 17.7 12.2 -1.41- 22 30 34.0 22.2 8.6 32.7 21.8 9.2 31.4 21.3 9.8 30.0 20.7 10.3 28.5 20.2 11.0 26.6 19.5 11.8 24.5 18.7 12.5 16 23 29.0 22.6 8.0 27.9 22.1 8.6 26.8 21.6 9.1 25.6 21.1 9.7 24.3 20.5 10.2 22.6 19.7 11.0 20.7 18.9 11.7 99.0 18 25 31.5 22.7 8.3 30.4 22.2 8.9 29.2 21.7 9.4 27.9 21.2 9.9 26.5 20.6 10.5 24.6 19.8 11.3 22.4 18.9 12.0 20 27 33.7 22.6 8.5 32.5 22.1 9.1 31.2 21.6 9.7 29.8 21.1 10.2 28.3 20.5 10.8 26.3 19.7 11.6 24.2 18.9 12.3 -1.55- 22 30 35.1 23.6 8.7 33.9 23.1 9.3 32.5 22.6 9.9 31.1 22.1 10.5 29.5 21.5 11.1 27.5 20.8 11.9 25.4 20.1 12.7 14 20 27.1 21.8 7.8 26.2 21.4 8.4 25.2 20.9 8.9 24.1 20.4 9.4 22.8 19.8 10.0 21.3 19.1 10.7 19.5 18.3 11.4

RAS- 110.0 16 23 29.9 23.8 8.1 28.9 23.4 8.7 27.7 22.8 9.2 26.5 22.3 9.8 25.2 21.7 10.3 23.4 20.9 11.1 21.4 20.1 11.8 13U2S 18 25 32.6 24.0 8.4 31.4 23.5 9.0 30.1 23.0 9.5 28.8 22.4 10.1 27.3 21.8 10.7 25.4 21.0 11.5 23.2 20.1 12.2

+ -1.69- 20 27 34.8 23.8 8.6 33.6 23.4 9.2 32.3 22.8 9.8 30.8 22.3 10.3 29.2 21.7 10.9 27.2 20.9 11.7 25.0 20.1 12.5 RAS- 22 30 36.3 25.0 8.8 35.0 24.5 9.4 33.6 24.0 10.0 32.1 23.4 10.6 30.5 22.8 11.2 28.4 22.1 12.1 26.2 21.3 12.8

13CT2S 14 20 28.0 22.9 7.9 27.1 22.5 8.5 26.0 22.0 9.0 24.8 21.4 9.5 23.6 20.8 10.1 22.0 20.1 10.9 20.1 19.3 11.5 121.0 16 23 30.9 25.0 8.2 29.8 24.6 8.8 28.6 24.0 9.3 27.4 23.5 9.9 26.0 22.9 10.4 24.1 22.1 11.2 22.1 21.2 11.9 18 25 33.6 25.2 8.4 32.4 24.7 9.0 31.1 24.1 9.6 29.7 23.6 10.2 28.2 23.0 10.8 26.2 22.2 11.6 23.9 21.2 12.3 -1.82- 20 27 35.9 25.1 8.7 34.7 24.6 9.3 33.3 24.0 9.9 31.8 23.4 10.4 30.2 22.8 11.0 28.1 22.0 11.9 25.8 21.2 12.6 22 30 37.5 26.3 8.9 36.2 25.8 9.5 34.7 25.3 10.1 33.1 24.7 10.7 31.5 24.1 11.3 29.4 23.4 12.2 27.1 22.6 12.9 14 20 28.9 24.0 8.0 27.9 23.5 8.6 26.8 23.0 9.1 25.6 22.4 9.6 24.3 21.8 10.2 22.6 21.1 11.0 20.7 20.2 11.6 132.0 16 23 31.9 26.2 8.3 30.8 25.7 8.9 29.5 25.2 9.4 28.2 24.6 10.0 26.8 24.0 10.5 24.9 23.2 11.3 22.8 22.3 12.0 18 25 34.7 26.4 8.5 33.4 25.8 9.1 32.1 25.3 9.7 30.7 24.7 10.3 29.1 24.1 10.9 27.1 23.3 11.7 24.7 22.3 12.4 -1.94- 20 27 37.1 26.2 8.7 35.8 25.7 9.4 34.4 25.2 10.0 32.8 24.6 10.5 31.1 23.9 11.1 29.0 23.1 12.0 26.6 22.3 12.7 22 30 38.7 27.5 9.0 37.3 27.0 9.6 35.8 26.5 10.2 34.2 25.9 10.8 32.5 25.3 11.4 30.3 24.6 12.3 27.9 23.7 13.1

104.0 18 25 38.0 26.2 8.1 36.6 25.6 9.3 35.2 25.0 10.6 33.6 24.3 11.9 31.9 23.6 13.5 29.7 22.6 15.2 27.0 21.5 17.0 20 27 40.6 26.1 8.4 39.2 25.5 9.6 37.7 24.9 10.9 36.0 24.2 12.2 34.1 23.5 13.8 31.8 22.5 15.6 29.2 21.5 17.5

-1.67- 22 30 42.4 27.1 8.5 40.9 26.6 9.9 39.2 25.9 11.2 37.5 25.3 12.6 35.6 24.6 14.1 33.2 23.7 16.0 30.6 22.7 17.9 16 23 36.2 27.6 8.0 34.9 27.0 9.2 33.5 26.3 10.4 32.0 25.7 11.7 30.4 24.9 13.1 28.2 24.0 15.0 25.9 23.0 16.8

117.0 18 25 39.3 27.8 8.2 37.9 27.1 9.5 36.4 26.5 10.7 34.8 25.8 12.1 33.0 25.1 13.6 30.7 24.1 15.5 28.0 23.0 17.2 20 27 42.1 27.6 8.4 40.6 27.0 9.7 39.0 26.4 11.0 37.2 25.7 12.4 35.3 24.9 13.9 32.9 24.0 15.8 30.2 22.9 17.7

-1.84- 22 30 43.9 28.8 8.7 42.3 28.2 9.9 40.6 27.6 11.3 38.8 26.9 12.7 36.9 26.2 14.3 34.3 25.3 16.2 31.7 24.3 18.2 14 20 33.9 26.7 7.8 32.8 26.1 9.0 31.4 25.5 10.2 30.1 24.8 11.5 28.5 24.1 12.8 26.6 23.2 14.7 24.3 22.2 16.4

130.0 16 23 37.4 29.1 8.0 36.1 28.5 9.3 34.6 27.8 10.5 33.1 27.1 11.9 31.4 26.4 13.4 29.2 25.4 15.1 26.7 24.4 16.9 18 25 40.7 29.3 8.3 39.2 28.6 9.6 37.6 28.0 10.9 36.0 27.3 12.2 34.1 26.5 13.7 31.7 25.5 15.6 28.9 24.4 17.5

-2.00- 20 27 43.5 29.1 8.5 42.0 28.5 9.9 40.3 27.8 11.2 38.5 27.1 12.5 36.5 26.4 14.1 34.0 25.4 16.0 31.2 24.3 17.8 22 30 45.4 30.4 8.8 43.7 29.8 10.0 42.0 29.1 11.5 40.1 28.5 12.9 38.1 27.7 14.4 35.5 26.8 16.5 32.7 25.8 18.3 14 20 35.0 28.0 7.9 33.8 27.4 9.1 32.5 26.8 10.3 31.0 26.1 11.6 29.4 25.3 13.0 27.4 24.4 14.8 25.1 23.4 16.5

143.0 16 23 38.6 30.5 8.1 37.2 29.9 9.4 35.8 29.3 10.6 34.2 28.5 12.0 32.4 27.8 13.5 30.1 26.8 15.2 27.6 25.7 17.1 18 25 42.0 30.7 8.4 40.5 30.1 9.7 38.9 29.4 11.0 37.1 28.7 12.3 35.3 27.9 13.9 32.8 26.9 15.8 29.9 25.7 17.6

-2.15- 20 27 44.9 30.6 8.6 43.3 29.9 9.9 41.6 29.3 11.3 39.7 28.5 12.7 37.7 27.7 14.2 35.1 26.7 16.1 32.2 25.7 18.1 22 30 46.8 32.0 8.9 45.2 31.3 10.2 43.3 30.7 11.6 41.4 30.0 13.0 39.3 29.2 14.6 36.7 28.3 16.6 33.8 27.3 18.5 14 20 36.1 29.2 8.0 34.9 28.7 9.2 33.5 28.0 10.4 32.0 27.3 11.7 30.4 26.5 13.1 28.3 25.6 14.9 25.9 24.5 16.6

156.0 16 23 39.8 31.9 8.2 38.4 31.3 9.5 36.9 30.6 10.8 35.2 29.9 12.1 33.4 29.1 13.6 31.1 28.1 15.5 28.5 27.0 17.2 18 25 43.3 32.1 8.4 41.7 31.5 9.8 40.1 30.8 11.1 38.3 30.0 12.5 36.4 29.2 14.0 33.8 28.2 15.9 30.8 27.0 17.8

-2.29- 20 27 46.3 32.0 8.7 44.7 31.3 10.0 42.9 30.6 11.4 41.0 29.9 12.8 38.9 29.1 14.3 36.2 28.1 16.4 33.2 27.0 18.2

RAS- 15U2S

+ RAS-

15CT2S

22 30 48.3 33.5 8.9 46.6 32.8 10.3 44.7 32.2 11.7 42.7 31.4 13.1 40.6 30.7 14.7 37.8 29.7 16.7 34.8 28.7 18.8 126.0 18 25 50.9 34.2 11.2 49.1 33.4 12.5 47.1 32.5 14.0 45.0 31.6 15.4 42.8 30.6 17.0 39.7 29.3 19.0 36.2 27.8 20.9 20 27 54.4 34.1 11.5 52.6 33.3 12.8 50.4 32.4 14.3 48.2 31.4 15.8 45.7 30.4 17.4 42.5 29.1 19.5 39.0 27.7 21.5 -2.06- 22 30 56.8 35.3 11.8 54.8 34.5 13.2 52.6 33.6 14.6 50.2 32.7 16.2 47.7 31.7 17.9 44.5 30.5 20.1 41.0 29.2 22.1 144.0 18 25 52.7 36.4 11.3 50.8 35.5 12.7 48.8 34.6 14.2 46.6 33.7 15.6 44.3 32.7 17.2 41.2 31.4 19.3 37.5 29.8 21.2 20 27 56.4 36.2 11.6 54.5 35.4 13.0 52.3 34.5 14.5 49.9 33.5 16.0 47.4 32.5 17.6 44.1 31.2 19.7 40.4 29.8 21.7 -2.31- 22 30 58.8 37.6 11.9 56.7 36.8 13.4 54.5 35.9 14.8 52.0 35.0 16.4 49.4 34.0 18.1 46.1 32.8 20.3 42.5 31.5 22.3 16 23 50.2 38.2 11.1 48.4 37.4 12.4 46.5 36.5 13.9 44.4 35.6 15.3 42.2 34.5 16.9 39.2 33.2 18.9 35.9 31.8 20.8 162.0 18 25 54.6 38.5 11.5 52.6 37.6 12.8 50.5 36.7 14.3 48.3 35.8 15.8 45.8 34.7 17.4 42.6 33.4 19.5 38.8 31.8 21.5 20 27 58.4 38.3 11.7 56.4 37.5 13.2 54.1 36.6 14.6 51.7 35.6 16.2 49.0 34.5 17.8 45.6 33.2 20.0 41.9 31.8 21.9

RAS- -2.54- 22 30 60.9 39.9 12.1 58.7 39.1 13.5 56.4 38.2 15.0 53.8 37.2 16.6 51.1 36.3 18.3 47.7 35.0 20.5 43.9 33.7 22.6 20U2S 14 20 47.0 37.0 10.9 45.5 36.2 12.2 43.6 35.3 13.6 41.7 34.4 15.0 39.6 33.4 16.5 36.8 32.1 18.4 33.7 30.7 20.4

+ 180.0 16 23 51.9 40.3 11.2 50.1 39.5 12.6 48.1 38.6 14.1 45.9 37.6 15.5 43.6 36.6 17.1 40.5 35.2 19.1 37.1 33.8 21.0 RAS- 18 25 56.4 40.6 11.6 54.4 39.7 13.0 52.2 38.8 14.5 49.9 37.8 15.9 47.4 36.7 17.6 44.0 35.4 19.7 40.1 33.8 21.7

20CT2S -2.76- 20 27 60.3 40.4 11.9 58.2 39.5 13.4 55.9 38.6 14.8 53.4 37.6 16.3 50.7 36.5 18.0 47.1 35.2 20.2 43.3 33.7 22.3 22 30 62.9 42.1 12.2 60.7 41.3 13.6 58.2 40.4 15.2 55.6 39.4 16.8 52.9 38.4 18.6 49.3 37.1 20.7 45.4 35.8 22.8

14 20 48.6 38.8 10.9 46.9 38.0 12.4 45.1 37.1 13.7 43.1 36.2 15.1 40.8 35.1 16.7 38.0 33.8 18.7 34.8 32.4 20.6 198.0 16 23 53.6 42.3 11.4 51.7 41.5 12.7 49.6 40.5 14.2 47.4 39.6 15.6 45.0 38.5 17.3 41.8 37.1 19.3 38.3 35.6 21.3 18 25 58.3 42.6 11.7 56.2 41.7 13.1 53.9 40.7 14.6 51.5 39.7 16.1 48.9 38.7 17.8 45.5 37.3 20.0 41.4 35.6 21.9 -2.97- 20 27 62.3 42.4 12.0 60.1 41.5 13.5 57.7 40.5 14.9 55.1 39.5 16.5 52.3 38.4 18.2 48.7 37.1 20.4 44.7 35.6 22.5 22 30 65.0 44.3 12.3 62.7 43.4 13.8 60.1 42.5 15.4 57.4 41.5 17.0 54.6 40.5 18.8 50.9 39.2 20.9 46.9 37.8 23.1 14 20 50.1 40.5 11.1 48.4 39.7 12.4 46.5 38.8 13.8 44.4 37.8 15.3 42.1 36.8 16.9 39.2 35.5 18.9 35.9 34.0 20.7 216.0 16 23 55.3 44.3 11.5 53.3 43.4 12.8 51.2 42.5 14.3 48.9 41.5 15.8 46.4 40.4 17.4 43.1 39.0 19.5 39.5 37.4 21.5 18 25 60.1 44.5 11.8 57.9 43.6 13.3 55.6 42.7 14.7 53.1 41.6 16.3 50.5 40.5 17.9 46.9 39.1 20.1 42.7 37.4 22.2 -3.17- 20 27 64.3 44.3 12.1 62.0 43.4 13.5 59.5 42.4 15.1 56.9 41.4 16.7 54.0 40.3 18.5 50.2 38.9 20.6 46.1 37.3 22.7 22 30 67.0 46.4 12.4 64.6 45.5 13.9 62.0 44.6 15.5 59.3 43.6 17.1 56.3 42.5 18.9 52.5 41.2 21.2 48.4 39.8 23.3

QA : Evaporator Air Flow (m3/min) SHC* : Sensible Heat Capacity (x 1000kcal/h) Given for Each WB and DB* CR : Sensible Heat Correction Factor IPT : Compressor Input Power (kW) WB : Evaporator Air Inlet Wet Bulb (°C) DB* : Evaporator Air Inlet Dry Bulb (°C) Given for Each WB NOTE: TC : Total Cooling Capacity (x 1000kcal/h) The data is based on the following conditions: Refrigerant Piping Length in One Direction: 5 Meters Horizontal.

Page 18: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

18

SELECTION DATA Fan Performance Table

Conversion Multiplier: 1 mmAq = 9.81 Pa Air Flow External Static Pressure (mmAq)

Model (m3/min.) 3 5 7.5

RAS-4U2S 37.0 RPM 670 740 830

RAS-5U2S 50.0 RPM 830 900 960

Conversion Multiplier: 1 mmAq = 9.81 Pa

External Static Pressure (mmAq) Model Air Flow (m3/min.) 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30

590 630 710 760 800 860 910 970 1000 1030 1060 1090 1120 1140 1160 118052.0 RPM BKW 0.21 0.24 0.28 0.32 0.36 0.38 0.42 0.46 0.50 0.54 0.57 0.61 0.64 0.68 0.72 0.78

670 710 770 810 880 910 960 1010 1030 1060 1090 1110 1140 1170 1190 122058.5 RPM BKW 0.25 0.29 0.34 0.37 0.41 0.46 0.50 0.53 0.58 0.62 0.65 0.70 0.74 0.78 0.82 0.86

740 790 840 900 940 980 1010 1030 1080 1110 1140 1170 1190 1210 1240 127065.0 RPM BKW 0.35 0.39 0.44 0.49 0.53 0.57 0.62 0.66 0.71 0.74 0.79 0.83 0.89 0.93 0.98 1.02

820 860 910 960 1000 1020 1050 1090 1120 1150 1180 1200 1220 1240 126071.5 RPM BKW 0.48 0.53 0.58 0.63 0.68 0.73 0.78 0.83 0.88 0.93 0.98 1.03 1.07 1.12 1.17

930 970 1000 1030 1060 1090 1110 1140 1170 1200 1220 1250 1280

RAS-6U2S

78.0 RPM BKW 0.66 0.71 0.77 0.82 0.88 0.93 0.99 1.04 1.09 1.15 1.20 1.26 1.31

— — —

55.2 RPM BKW

590 0.21

6500.25

710 0.28

760 0.32

8000.36

8400.39

9200.43

9700.46

10000.50

10300.54

10600.57

1090 0.61

1120 0.64

11400.68

11600.72

11800.78

62.1 RPM BKW

670 0.25

7200.30

770 0.34

800 0.38

8600.42

9100.46

9600.50

10000.54

10300.58

10600.62

10800.66

1110 0.70

1140 0.74

11700.78

11900.82

12200.86

69.0 RPM BKW

740 0.35

7900.39

840 0.44

880 0.48

9200.53

9800.57

10100.62

10300.66

10800.71

11000.75

11300.80

1160 0.84

1190 0.89

12100.93

12400.98

12701.02

75.9 RPM BKW

820 0.48

8600.53

910 0.58

960 0.63

10000.68

10200.73

10500.78

10900.83

11200.88

11500.93

11800.98

1200 1.03

1240 1.08

12601.13

12901.18

RAS-8U2S

82.8 RPM BKW

940 0.67

9800.72

1010 0.78

1040 0.83

10700.89

11000.94

11201.00

11501.05

11801.10

12101.16

12301.21

1260 1.27

1290 1.32

— — —

65.6 RPM BKW

540 0.08

6100.11

680 0.15

740 0.25

8000.33

8400.40

8700.57

9100.63

9400.69

9800.75

10200.81

1060 0.86

1100 0.92

11500.98

12001.04

12801.10

73.8 RPM BKW

600 0.10

6700.13

740 0.20

800 0.28

8500.36

8800.43

9200.58

9500.64

9700.70

10000.76

10600.82

1110 0.89

1160 0.97

12001.05

12601.12

13201.20

82.0 RPM BKW

720 0.12

7500.19

780 0.27

820 0.34

8600.42

9000.50

9300.59

9700.65

10000.72

10400.80

10900.89

1130 0.98

1170 1.08

12101.17

12701.26

13301.35

90.2 RPM BKW

740 0.26

7700.34

800 0.42

840 0.49

8800.57

9200.65

9600.72

10000.80

10800.98

11101.09

11401.24

1170 1.27

1200 1.31

12301.38

13301.50

RAS-9U2S

98.4 RPM BKW

790 0.39

8100.50

850 0.64

900 0.78

9400.87

9700.95

10001.03

10501.11

11001.20

11501.28

12001.37

1280 1.49

1320 1.61

13701.70

— —

72.0 RPM BKW

540 0.02

6100.04

680 0.11

740 0.18

8000.24

8600.31

9100.38

9700.45

10100.52

10500.58

10900.65

1130 0.72

1170 0.79

12100.86

12400.92

12800.90

81.0 RPM BKW

600 0.05

6700.13

740 0.20

790 0.28

8500.36

9000.43

9600.51

10000.59

10600.66

10800.74

11000.82

1180 0.89

1210 0.97

12401.05

12701.12

13101.20

90.0 RPM BKW

670 0.15

7300.23

790 0.32

840 0.40

9000.49

9500.57

10000.66

10400.74

10800.83

11200.91

11701.00

1200 1.08

1240 1.17

12701.25

13101.34

13401.42

99.0 RPM BKW

740 0.26

8000.35

850 0.45

900 0.54

9500.64

10000.73

10400.82

10800.92

11201.01

11701.10

12001.20

1240 1.29

1270 1.38

13101.48

13401.57

RAS-10U2S

108.0 RPM BKW

810 0.39

8600.50

910 0.60

960 0.70

10000.80

10500.90

10901.01

11301.11

11701.21

12001.31

12401.41

1280 1.51

1310 1.62

13501.72

— —

RPM: Fan Speed (rpm) BKW: Brake Power (kW) NOTE: When the external static pressure exceeds the shaded area an oversized fan motor or a fan pulley are required.

Page 19: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

19

SELECTION DATA Fan Performance Table (Continued)

Conversion Multiplier: 1 mmAq = 9.81 Pa External Static Pressure (mmAq) Model Air Flow

(m3/min.) 0 4 8 12 16 20 24 28 32 36 40

88.0 RPM BKW

650 0.27

730 0.39

790 0.51

8800.64

9800.76

10800.88

11001.00

11701.13

12301.25

1270 1.37

1310 1.50

99.0 RPM BKW

700 0.31

790 0.43

860 0.58

9200.70

10100.86

10901.00

11401.13

11901.27

12401.43

1290 1.58

1320 1.69

110.0 RPM BKW

740 0.39

810 0.54

890 0.70

9600.85

10301.00

11001.16

11501.31

12201.46

12701.62

1310 1.77

1350 1.92

121.0 RPM BKW

770 0.69

840 0.84

910 0.98

9901.13

10901.27

11501.42

12201.60

12801.74

13101.88

1340 2.01

1370 2.15

RAS-13U2S

132.0 RPM BKW

810 0.85

870 1.01

980 1.18

10901.35

11701.52

1220 1.69

12801.86

13202.03

13702.20

1410 2.37

104.0 RPM BKW

630 0.43

730 0.55

850 0.66

930 0.78

10000.89

10501.01

11101.12

11701.24

12201.35

1270 1.49

1320 1.58

117.0 RPM BKW

710 0.52

800 0.65

880 0.78

950 0.91

10201.03

10801.16

11401.29

11801.42

12601.55

1310 1.68

1360 1.81

130.0 RPM BKW

790 0.66

890 0.81

940 0.95

1000 1.09

11001.24

11401.38

11901.52

12501.67

1290 1.81

1350 1.95

1380 2.10

143.0 RPM BKW

880 0.90

970 1.04

1040 1.28

11001.41

11601.50

12201.66

12801.82

13201.97

13702.13

1400 2.99

RAS-15U2S

156.0 RPM BKW

980 1.20

1060 1.36

1120 1.50

12001.65

12501.79

12901.94

13202.08

13502.34

14002.51

— —

External Static Pressure (mmAq) Model

Air Flow (m3/min.) 0 6 12 18 24 30 36 42 48 54 60

RPM 620 670 720 760 790 830 890 930 990 1040 1080 144.0

BKW 0.24 0.56 0.88 1.21 1.53 1.85 2.17 2.49 2.82 3.14 3.46

RPM 630 680 740 780 820 860 920 970 1020 1060 1100 162.0

BKW 0.29 0.64 0.99 1.34 1.69 2.04 2.39 2.74 3.09 3.44 3.79

RPM 650 690 750 820 870 920 950 1010 1050 1100 1140 180.0

BKW 0.39 0.78 1.17 1.56 1.95 2.34 2.73 3.12 3.51 3.89 4.28

RPM 670 760 830 870 920 970 1020 1060 1100 1160 1190 198.0

BKW 0.58 1.02 1.45 1.89 2.32 2.76 3.19 3.63 4.06 4.50 4.93

RPM 820 860 910 950 1000 1030 1070 1120 1170 1220 1250

RAS-20U2S

216.0 BKW 0.82 1.32 1.81 2.30 2.80 3.29 3.78 4.28 4.77 5.26 5.76

RPM: Fan Speed (rpm) BKW: Brake Power (kW) NOTE: When the external static pressure exceeds the shaded area an oversized fan motor or a fan pulley are required.

Page 20: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

20

60

170160150100 110 1301200 140

Air Flow (m /min )3

1400 rpm

1.5kW

Internal Static Pressure

Sta

tic P

ress

ure

(mm

Aq)

109

2019

30

40

50

1200 rpm

1100 rpm

1000 rpm

900 rpm

1300 rpm

2.2kW

(MAX)

Internal Static Pressure7

: Factory Set Point(980rpm)Standard Motor Output : 2.2kW

Air Flow (m /min )

RAS-15U2S

70

80

550 69 7060 803

90

0.75kW

Sta

tic P

ress

ure

(mm

Aq)

1012

20

30

1100 rpm

1000 rpm

800 rpm900 rpm

1300 rpm

1200 rpm

(MAX)

0 70

7.610

Sta

tic P

ress

ure

(mm

Aq)

17.620

40

30

60

50

70

900 rpm800 rpm

140

Air Flow (m /min )

Internal Static Pressure

1101009080 120 1303

150

1000 rpm

1100 rpm

1200 rpm

1300 rpm1.5kW

(MAX)1400 rpm

2.2kW

Standard Motor Output : 0.75kW: Factory Set Point(885rpm)RAS-8U2S

40

RAS-6U2S

Internal Static Pressure

RAS-13U2S

Sta

tic P

ress

ure

(mm

Aq)

0 52

80

7

1012

30

20

40

: Factory Set Point(920rpm)Standard Motor Output : 2.2kW

70 80786055 65

Air Flow (m /min )3

900 rpm800 rpm

1000 rpm

90

Standard Motor Output : 0.75kW: Factory Set Point(865rpm)

0.75kW

1100 rpm

1200 rpm

(MAX)1300 rpm

1350 rpm

30

7

10

20

14.5Sta

tic P

ress

ure

(mm

Aq)

Internal Static Pressure

100

Air Flow (m /min )

800 70 903

110

1.5kW

1300 rpm

900 rpm

800 rpm

1200 rpm

1100 rpm

1000 rpm

0.75kW

(MAX)

40

RAS-10U2SStandard Motor Output : 1.5kW

: Factory Set Point(890rpm)

1350 rpm

30

7

10

20

14.5Sta

tic P

ress

ure

(mm

Aq)

Internal Static Pressure

100

Air Flow (m /min )

800 65 903

1.5kW

1300 rpm

900 rpm

800 rpm

1100 rpm

1000 rpm

(MAX)

40

RAS-9U2SStandard Motor Output : 1.5kW

: Factory Set Point(850rpm)

70

1200 rpm

Internal Static Pressure

Sta

tic P

ress

ure

(mm

Aq)

26

10

0

20

30

50

40

Air Flow (m /min)

140 1803

60

70

80

90

100

3.7kW

900 rpm

800 rpm 1000 rpm

1100 rpm

220

:Factory Set (830rpm)Stantard Motor Output: 3.7kW

1200 rpm

6

150 160 170 190 200 210

5.5kW

1300 rpm(MAX)

RAS-20U2S

0.75kW

82

RAS-5U2S

Sta

tic P

ress

ure

(mm

Aq)

Air Flow (m /min )

Internal Static Pressure

34320 30

910

4238 4440363

: Factory Set Point(740rpm)Standard Motor Output : 0.27kW

30

20

RAS-4U2S40

: Factory Set Point(900rpm)Standard Motor Output : 0.43kW

1415

25

35

37

Hi

Me

Lo

Sta

tic P

ress

ure

(mm

Aq)

Air Flow (m /min )

Internal Static Pressure

47440 41

910

5953 6256503

30

20

40

1415

25

35

Hi

Me

Lo

SELECTION DATA

Fan Performance Curve

NOTE: External static pressure are available by the following equation (External Static Pressure)= (Static Pressure) - (Internal Static Pressure)

Page 21: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

21

SELECTION DATA Fan Speed Adjustment

For Models RAS-4U2S and RAS-5U2S

Fan Speed Adjustment

For Models RAS-6U2S through RAS-15U2S

Motor Pulley Adjustment Regulation Space X of Motor Pulley (mm) Factory Set Point Model 0 1 2 3 4 5 6 7 X RPM PD* rpm/turn**

RPM 940 915 890 865 835 810 785 760 RAS-6U2S PD* 112 109 106 103 99 96 93 90

3 865 103 45

RPM 1100 1070 1040 1010 975 950 915 885 RAS-8U2S PD* 112 109 106 103 99 96 93 90

7 885 90 47

RPM 1040 1010 980 950 920 880 850 820RAS-9U2S PD* 105 102 99 96 93 89 86 83

6 850 86 47

RPM 1110 1080 1050 1020 980 950 920 890RAS-10U2S PD* 112 109 106 103 99 96 93 90

7 890 90 47

RPM 1110 1080 1050 1020 980 950 920 890RAS-13U2S PD* 112 109 106 103 99 96 93 90

6 920 93 45

RPM 1185 1155 1125 1085 1055 1025 980 965RAS-15U2S PD* 120 117 114 110 107 104 100 98

6 980 100 45

Motor Pulley Dimensions Motor Pulley Dimensions (mm) Model b c d e f g

RAS-6U2S 121.5 55 M48 19 6 21.5RAS-8U2S 121.5 55 M48 19 6 21.5RAS-9U2S 137 62.6 M48 24 8 27 RAS-10U2S 121.5 55 M48 24 8 27 RAS-13U2S 121.5 55 M48 24 8 27 RAS-15U2S 129 65 M48 24 8 27

Fan Pulley Dimensions Fan Pulley Dimensions (mm)Model

a b PD* RAS-6U2S 179 20 170 RAS-8U2S 153 20 144 RAS-9U2S 164 25 155 RAS-10U2S 153 25 144 RAS-13U2S 153 25 144 RAS-15U2S 153 25 144

PRM : Fan Speed (rpm) * : Pitch Diameter of Pulley (mm) ** : Fan Speed Change per One Turn of Movable Pulley (rpm/turn)

Fan Speed (rpm) Factory Set PointModels Hi Me Lo rpm RAS-4U2S 830 740 670 740 RAS-5U2S 960 900 830 900

Page 22: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

22

SELECTION DATA Fan Speed Adjustment (Continued)

V-Belt Model Form Length (mm) Number of

V-Belt RAS-6U2S A 787 1 RAS-8U2S A 737 1 RAS-9U2S A 711 1 RAS-10U2S A 711 1 RAS-13U2S A 737 1 RAS-15U2S A 737 1

For Model RAS-20U2S

Motor Pulley Adjustment Regulation Space X of Motor Pulley (mm) Factory Set Point

Model 0 1 2 3 4 5 6 7 8 X RPM PD* rpm/turn**

RPM 1000 980 960 935 910 890 870 850 830RAS-20U2S

PD* 150 147 144 140.5 137 134 131 128 1258 830 125 32

Motor Pulley Dimensions

Pulley Dimensions (mm) Model a b c RAS-20U2S 31 28 8

Fan Pulley Dimensions Pulley Dimensions (mm) Model

a b c d PD* RAS-20U2S 226 196 35 38.5 215

RPM : Fan Speed (rpm) * : Pitch Diameter of Pulley (mm) ** : Fan Speed Change per One Turn of Movable Pulley (rpm/turn) V-Belt

Model Form Length (mm) Number of V-Belt

RAS-20U2S B 1118 2

Page 23: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

23

ELECTRICAL DATA

Electrical Data Cooling Unit

Unit Main Power Applicable Voltage Evaporator Fan Motor Model VOL Hz Maximum Minimum RNC IPT

RAS-4U2S 380/415 50 456 342 0.8/0.8 0.37 RAS-5U2S 380/415 50 456 342 1.1/1.1 0.61 RAS-6U2S 380/415 50 456 342 1.2/1.2 0.66 RAS-8U2S 380/415 50 456 342 1.2/1.2 0.66 RAS-9U2S 380/415 50 456 342 1.3/1.3 0.68 RAS-10U2S 380/415 50 456 342 1.3/1.3 0.68 RAS-13U2S 380/415 50 456 342 2.2/2.2 1.19 RAS-15U2S 380/415 50 456 342 3.1/3.2 1.6 RAS-20U2S 380/415 50 456 342 6.2/6.3 3.4/3.6

VOL : Unit Power Supply Rated (Plated) Voltage (V) Hz : Frequency (Hz) RNC : Running Current (A) IPT : Input (kW) NOTES: 1.These data are based on the factory set fan speeds with the factory-supplied fan motor at the nominal airflow. 2.These data are based on the standard conditions. 3.Only RAS-4U2S and RAS-5U2S equipped with single-phase evaporator fan motor, others are equipped with three-phase

evaporator fan motor.

Condensing Unit Unit Main Power Applicable Voltage Compressor Motor

(Three-Phase) Condenser Fan Motor

(Three-Phase) Condensing Unit (Cooling Unit) VOL Hz Maximum Minimum STC RNC IPT RNC IPT RAS-4CT2S (RAS-4U2S)

380/415 50 456 342 58 6.1/5.8 3.6 0.7/0.7 0.23

RAS-5CT2S (RAS-5U2S)

380/415 50 456 342 67 7.8/7.7 4.5 0.85/0.85 0.45

RAS-6CT2S (RAS-6U2S)

380/415 50 456 342 60 8.7/8.4 5.2 0.51/0.48 0.28

RAS-8CT2S (RAS-8U2S)

380/415 50 456 342 100/108 12.2/12.3 7.0 0.51/0.48 0.28

RAS-9CT2S (RAS-9U2S)

380/415 50 456 342 109/118 12.5/12.8 7.5 0.95/0.92 0.48

RAS-10CT2S (RAS-10U2S)

380/415 50 456 342 123/134 15.0/15.4 8.55 0.95/0.92 0.4

10.9/11.7 6.1 1.47/1.55 0.78/0.84 RAS-13CT2S (RAS-13U2S)

380/415 50 456 342 100/1087.2/7.4 4.1 0.95/0.99 0.42/0.44

13.5/13.8 7.9 1.3/1.3 0.7/0.7 RAS-15CT2S (RAS-15U2S)

380/415 50 456 342 123/1347.5/7.6 4.5 0.9/1.0 0.53/0.53

RAS-20CT2S (RAS-20U2S)

380/415 50 456 342 123/134 14.1x2/14.2x2 8.1x2 1.3x2 0.7x2

VOL : Unit Power Supply Rated (Plated) Voltage (V) Hz : Frequency (Hz) STC: Starting Current (A) RNC: Running Current (A) IPT : Input (kW)

NOTES: 1.These data are based on the following conditions.

Evaporator Air Inlet Temperature 27°C DB, 19°C WB. Condenser Air Inlet Temperature 35°C DB

2.The maximum current of the compressors can be estimated as follows. Maximum Running Current: RNC x Max. IPT */IPT Max. IPT*: Compressor Power Input from the Performance Table at the Expected Maximum Condition IPT, RNC : Compressor data from the above table

3.The data in the compressor motor column shall indicate the respective values of the refrigeration cycles.

Page 24: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

24

SOUND DATA Sound Data

Cooling Unit

Frequency Band (Hz)

Model Sound Level 45 ∫ 90

90 ∫

180

180 ∫

355

355 ∫

710

710 ∫

1,400

1,400∫

2,800

2,800 ∫

5,600

5,600 ∫

11,200 Over-all

RAS-4U2S SPL-A SPL-C PWL

34.7 61.3 69.0

37.7 53.3 61.0

43.7 53.1 61.0

44.7 48.1 56.0

44.7 44.9 53.0

42.7 41.1 49.0

37.7 36.1 44.0

29.7 27.8 36.0

51 63 71

RAS-5U2S SPL-A SPL-C PWL

37.0 61.6 71.0

40.0 53.6 63.0

49.0 56.4 65.0

50.0 51.4 60.0

51.0 49.2 58.0

46.0 42.4 51.0

44.0 40.4 49.0

38.0 34.1 43.0

56 64 73

RAS-6U2S SPL-A SPL-C PWL

37.3 63.9 72.0

48.8 64.4 72.0

49.8 59.2 67.0

54.8 58.2 66.0

57.3 57.5 66.0

53.3 51.7 60.0

46.3 44.7 53.0

37.3 35.4 43.0

61.1 68.8 77.0

RAS-8U2S SPL-A SPL-C PWL

42.4 67.7 75.7

46.4 62.3 70.3

51.4 60.0 68.0

53.1 56.3 64.3

56.4 56.4 64.4

54.4 53.0 61.0

52.4 50.6 58.6

43.9 42.0 50.0

61.2 69.9 77.9

RAS-9U2S SPL-A SPL-C PWL

40.9 66.2 74.2

50.9 66.8 74.8

52.4 61.0 69.0

53.9 57.1 65.1

55.4 55.4 63.4

53.4 52.0 60.0

50.9 49.1 57.1

42.9 41.0 49.0

61.1 70.5 78.5

RAS-10U2S SPL-A SPL-C PWL

40.9 66.2 74.2

50.9 66.8 74.8

52.4 61.0 69.0

53.9 57.1 65.1

55.4 55.4 63.4

53.4 52.0 60.0

50.9 49.1 57.1

42.9 41.0 49.0

61.1 70.5 78.5

RAS-13U2S SPL-A SPL-C PWL

42.9 68.4 76.4

49.9 65.8 73.8

52.4 61.0 69.0

53.4 56.6 64.6

55.9 55.9 63.9

53.4 52.0 60.0

51.4 49.6 57.6

43.1 41.2 49.2

61.0 71.2 79.2

RAS-15U2S SPL-A SPL-C PWL

48.9 74.2 82.2

55.4 71.3 79.3

53.9 62.5 70.5

54.4 57.6 65.6

57.4 57.4 65.4

55.9 54.5 62.5

55.9 54.1 62.1

47.4 45.5 53.5

63.7 76.4 84.4

RAS-20U2S SPL-A SPL-C PWL

53.0 78.3 86.3

58.0 73.9 81.9

61.0 69.6 77.6

68.7 71.9 79.9

69.5 69.5 77.5

67.5 66.1 74.1

66.5 64.7 72.7

54.5 52.6 60.6

74.7 81.2 89.2

SPL-A: A Scale Sound Pressure Level (dB) SPL-C: C Scale Sound Pressure Level (dB) PWL : Sound Power Level (dB) NOTES: 1.The measuring point is 1.0 meter from the side panel of the machine surface and 1.0 meter from the floor level. 2.The units are operating under the standard working conditions. 3.The above data was measured in an anechoic chamber so that reflection sound should be taken into consideration.

Page 25: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

25

SOUND DATA

Sound Data (Continued) Condensing Unit

Frequency Band (Hz)

Model Sound Level 45 ∫ 90

90 ∫

180

180 ∫

355

355 ∫

710

710 ∫

1,400

1,400∫

2,800

2,800 ∫

5,600

5,600 ∫

11,200 Over-all

RAS-4CT2S SPL-A SPL-C PWL

40.5 67.1 75.1

47.6 63.5 71.7

50.7 59.3 67.5

56.8 60.0 68.2

54.8 54.8 63.0

50.5 49.1 57.3

45.4 43.6 51.8

40.3 38.4 46.6

60.5 69.8 77.9

RAS-5CT2S SPL-A SPL-C PWL

41.4 65.1 72.8

53.5 66.5 74.2

47.6 53.3 61.0

59.7 60.0 67.7

61.7 58.8 66.5

53.4 49.1 56.8

51.3 46.6 54.3

47.2 42.4 50.1

64.9 69.9 77.6

RAS-6CT2S SPL-A SPL-C PWL

39.4 66.0 74.0

49.5 65.4 73.4

51.6 60.2 68.2

56.2 59.4 67.4

59.2 59.2 67.2

54.9 53.5 61.5

46.8 45.0 53.0

38.7 36.8 44.8

62.7 70.2 78.2

RAS-8CT2S SPL-A SPL-C PWL

39.2 65.8 74.3

50.8 66.7 75.2

51.9 60.5 69.0

57.0 60.2 68.7

59.5 59.5 68.0

55.2 53.8 62.3

48.1 46.3 54.8

39.0 37.1 45.6

63.2 70.7 79.2

RAS-9CT2S SPL-A SPL-C PWL

40.6 67.2 75.2

50.7 66.6 74.6

52.8 61.4 69.4

57.4 60.6 68.6

60.4 60.4 68.4

56.1 54.7 62.7

48.0 46.2 54.2

39.9 38.0 46.0

63.9 71.4 79.4

RAS-10CT2S SPL-A SPL-C PWL

40.6 67.2 75.2

50.7 66.6 74.6

52.8 61.4 69.4

57.4 60.6 68.6

60.4 60.4 68.4

56.1 54.7 62.7

48.0 46.2 54.2

39.9 38.0 46.0

63.9 71.4 79.4

RAS-13CT2S SPL-A SPL-C PWL

45.0 71.6 80.0

53.3 68.9 77.0

56.4 65.8 74.0

58.6 62.0 70.0

60.8 61.0 69.0

52.9 51.3 59.0

45.5 43.9 52.0

39.6 37.7 46.0

64.5 74.6 83.0

RAS-15CT2S SPL-A SPL-C PWL

45.5 72.1 80.0

53.5 69.1 77.0

56.8 66.2 74.0

58.4 61.8 70.0

61.5 61.7 70.0

52.9 51.3 59.0

46.1 44.5 53.0

39.4 37.5 46.0

64.9 75.0 83.0

RAS-20CT2S SPL-A SPL-C PWL

46.0 72.6 81.0

54.0 69.6 78.0

57.3 66.7 75.0

58.9 62.3 70.0

62.0 62.2 70.0

53.4 51.8 60.0

46.6 45.0 53.0

39.9 38.0 46.0

65.4 75.5 84.0

SPL-A: A Scale Sound Pressure Level (dB) SPL-C: C Scale Sound Pressure Level (dB) PWL : Sound Power Level (dB) NOTES: 1.Measuring Point 1.0 Meter from the Center of the Machine Surface 1.5 Meter from the Floor Level 2.The units are operating under the standard working conditions. 3.The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration.

Page 26: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

26

ACCESSORY and COMPONENT DATA

Accessory Availability

Optional Accessories Unit Cooling Unit Condensing Unit

Standard (Factory-Supplied) Accessory

Liquid Line Filter-Dryer

Yes (RAS-13U2S~RAS-20U2S)

Optional Accessory Filter Filter Box Sight Glass Solenoid Valve

Yes Yes ─ ─

─ ─

Yes Yes

Component Detailed Data Compressor

Compressor Model 400DH 500DH 600DH 750EL 900EL 1000EL

Compressor Type Herm. Scroll Herm. Scroll Herm. Scroll Herm. Scroll Herm. Scroll Herm. Scroll

Revolution rpm 2,880 2,880 2,880 2,880 2,880 2,880

Displacement m3/h 11.09 13.82 15.55 22.12 24.88 27.65

Air-Tight Pressure

Discharge

kg/cm2 G kPa

30

2,940

30

2,940

30

2,940

30

2,940

30

2,940

30

2,940

Suction kg/cm2 G

kPa 15

1,470 15

1,470 15

1,470 15

1,470 15

1,470 15

1,470

Motor Type Special Squirrel-Cage, Three-Phase Motor

Starting Method Direct-On-Line Starting

Poles 2 2 2 2 2 2

Insulation Class E E E E E E

Oil Type SUNISO 4GDI-HT

Charge Liters 1.5 1.5 1.5 2.5 2.5 2.5

Page 27: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

27

COMPONENT DATA

Component Detailed Data (Continued)

Evaporator and Evaporator Fan Model RAS-4U2S RAS-5U2S RAS-6U2S RAS-8U2S RAS-9U2S RAS-10U2S RAS-13U2S RAS-15U2S RAS-20U2S

Evaporator Multi-Pass Cross-Finned Tube Tube Material Copper

Outer Diameter Thickness Rows Number of Tubes/Evaporator

mm mm

9.53 0.34

3 48

9.53 0.34

3 48

9.53 0.34

3 44

9.53 0.34

3 42

9.53 0.34

3 72

9.53 0.34

3 72

9.53 0.34

3 74

9.53 0.34

3 74

9.53 0.34

3 114

Fin Material Aluminum Thickness Pitch

mm mm

0.11 2.0

0.11 2.0

0.11 2.0

0.11 2.0

0.11 2.0

0.11 2.0

0.11 2.0

0.11 2.0

0.11 2.0

Number of Evaporators/Unit Total Face Area

m2

1 0.29

1 0.29

1 0.37

1 0.45

1 0.75

1 0.75

1 0.73

1 0.81

1 1.25

Maximum Applicable Pressure kg/cm2 G

kPa 13

1,270 13

1,270 13

1,27013

1,270 13

1,27013

1,270 13

1,270 13

1,270 13

1,270Evaporator Fan Multi-Blade Centrifugal Fan (Double Suction)

Number/Unit Outer Diameter Total Nominal Air Flow

mm m3/min

m3/s L/s

1 264 37

0.62 620

1 264 50

0.83 830

1 264 65

1.08 1,080

1 264 69

1.15 1,150

2 264 82

1.37 1,370

2 264 90

1.50 1,500

2 264 110 1.83

1,830

2 264 130 2.17

2,170

1 385 180 3.00

3,000Evaporator Fan Motor

Starting Method

Drip-Proof Type Enclosure Direct-On-Line Starting

Nominal Output kW 0.35 0.55 0.75 0.75 1.5 1.5 2.2 2.2 3.7 Poles Number/Unit Insulation Class

4 1 B

4 1 B

4 1 B

4 1 B

4 1 B

4 1 B

4 1 B

4 1 B

4 1 B

Condenser and Condenser Fan

Model RAS-4CT2S RAS-5CT2S RAS-6CT2S RAS-8CT2S RAS-9CT2S RAS-10CT2S RAS-13CT2S RAS-15CT2S RAS-20CT2S

Condenser Coil Multi-Pass Cross-Finned Tube Tube Material Copper

Outer Diameter Thickness Rows Number of Tubes/Cond.

mm mm

9.53 0.34

2 58

9.53 0.34

2 58

9.53 0.34

2 56

9.53 0.34

2 62

9.53 0.34

3 98

9.53 0.34

3 98

9.53 0.34 3/2

78/52

9.53 0.34 3/3

78/78

9.53 0.34 3/3

108/108Fin Material Aluminum

Thickness Pitch

mm mm

0.11 2.0

0.11 2.0

0.11 2.0

0.11 2.0

0.11 2.0

0.11 2.0

0.11 2.0

0.11 2.0

0.11 2.0

Maximum Operating Pressure kg/cm2G

kPa 30

2,940 30

2,940 30

2,94030

2,940 30

2,94030

2,940 30

2,940 30

2,940 30

2,940Number of Condensers/Unit Total Face Area

m2

1 1.05

1 1.16

1 1.24

1 1.42

1 1.70

1 1.70

2 2.24

2 2.24

2 2.37

Condenser Fan Direct driven Propeller Fan Number/Unit Outer Diameter

mm

1 610

1 610

1 610

1 610

1 710

1 710

2 710/610

2 710/610

2 710

Revolution rpm 870 870 870 870 870 770 810 810 810 Nominal Air Flow m3/min.

m3/s L/s

120 2.0

2,000

120 2.0

2,000

135 2.25

2,250

135 2.25

2,250

160 2.67

2,670

160 2.67

2,670

315 5.25

5,250

330 5.5

5,500

320 5.33

5,330Condenser Fan Motor

Starting Method

Drip-Proof Type Enclosure Direct-On-Line Starting

Nominal Output kW 0.15 0.3 0.25 0.25 0.4 0.4 0.3 0.3 0.3 Poles Number/Unit Insulation Class

6 1 H

6 1 H

6 1 H

6 1 H

6 1 H

6 1 H

6 2 H

6 2 H

6 2 H

Page 28: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

28

CONTROL SYSTEM Refrigerant Control

Refrigeration Cycle

Condensing Unit Models RAS-13CT2S through RAS-20CT2S are composed of two refrigeration cycles. In addition to the basic condensing unit components (compressor and air-cooled condenser), the following components are equipped in each circuit.

Stop Valves for Gas Line and Liquid Line – These stop valves are equipped at the unit piping connections, and enhance the evacuation and charging functions.

Cooling Unit Refrigerant Flow Control – Thermal expansion valves are equipped for models RAS-13U2S, RAS-15U2S and RAS-20U2S.

Dryer – A filter-dryer is shipped for installation at the site. (for models RAS-13U2S, RAS-15U2S and RAS-20U2S)

Electrical Operation Control

A field-supplied main power switch supplies to the unit. When the room thermostat is set at “FAN ON” position, the indoor fan is started. When the room thermostat is set at “FAN AUTO” and “COOL ON” position, all electrical and protective devices are satisfied, the thermostat in the room thermostat controls the compressor operation (refer to “Operational Sequence Chart”).

Capacity Control – The field supplied Room Thermostat for the dual-circuited models starts and stops compressor operation in each circuit, responding to the room temperature with the room thermostat elements. This system enables full load, 60% or 50% load and no load (ceasing both compressor) operations. Function of Safety Devices Automatic Restarting System (Standard Sequence) – The timer relay for compressor connected in the compressor control circuit delays the compressor restarting period for approximately three (3) minutes after the thermostat calls for the cooling operation or automatic resetting of the protection devices, thereby preventing a harmful compressor cycling operation.

For Models: RAS-4U2S+RAS-4CT2S through RAS-10U2S+RAS-10CT2S

Operational Sequence Chart : ON : OFF

*Main Power Switch OFF ON

FAN AUTO ON AUTO

COOL OFF ON Operation Equipments *Room Thermostat

TH ─ ─ ─

Indoor Fan Motor MIF

Outdoor Fan Motor MOF

Compressor MC Electric Components

Safety Devices Close Close Close Close Close Close Open

NOTES: 1. * :Field Supplied.

After 3 min.

Page 29: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

29

CONTROL SYSTEM

For Models: RAS-13U2S+RAS-13CT2S through RAS-20U2S+RAS-20CT2S

Operational Sequence Chart : ON : OFF

*Main Power Switch OFF ON

FAN AUTO ON AUTO

COOL OFF ON

(Stage) COOLING CALL

─ 1st … ON ON ON ON OFF ON

Operation Equipment *Room Thermostat

TH

2nd … ON ON ON OFF OFF ON

Indoor Fan Motor MIF

Outdoor Fan Motor 1 MOF1

Outdoor Fan Motor 2 MOF2

Compressor 1 MC1

Compressor 2 MC2

**Crankcase Heater CH **Crankcase Heater CH

Electric Components

Safety Devices Close Close Close Close Close Close Close Close Open NOTES: 1. * :Field Supplied.

2. ** :Crankcase Heater are provided for model RAS-13CT2S No.2 cycle, RAS-15CT2S No.1 cycle and RAS-20CT2S.

After 3 min.

After 3.5 min.

Page 30: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

30

CONTROL SYSTEM

For M

odel

s R

AS

-4U

2S+R

AS-4

CT2

S a

nd R

AS

-5U

2S+R

AS

-5C

T2S

Page 31: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

31

CONTROL SYSTEM

For M

odel

s R

AS

-6U

2S+R

AS-6

CT2

S th

roug

h R

AS-

10U

2S+R

AS

-10C

T2S

Page 32: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

32

CONTROL SYSTEM

For M

odel

RA

S-1

3U2S

+RA

S-1

3CT2

S

Page 33: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

33

CONTROL SYSTEM

For M

odel

RA

S-1

5U2S

+RA

S-1

5CT2

S

Page 34: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

34

CONTROL SYSTEM

For M

odel

RA

S-2

0U2S

+RA

S-2

0CT2

S

Page 35: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

35

CONTROL SYSTEM

Protection and Safety ControlCompressor Protection All units are equipped with the following compressor protection system, in order to provide a perfect guarding function for the compressor.

High Pressure Switches – Leading the pressures from the compressor discharge lines, this switch cut out the compressor operation when the discharge pressure exceeds the setting pressure.

Overcurrent Transformer – This sensor stop the compressor operation when the current exceeds the setting.

Internal Thermostat for compressor – Embedded in the compressor motor winding, this thermostat cuts out the compressor operation when the compressor winding temperature exceeds the setting.

Reverse Phase Protection – The reverse phase protection which is a built-in function of PCB will make the compressor not start when the power source is incorrectly connected.

Compressor Cycling Protection Timer – This timer which is a built-in function of PCB provides the above combination with the most effective functions by delaying the compressor restarting period (refer to “Operational Sequence Chart”)

Other Protection

The fan motor is protected by the following device:

Overcurrent Relay for Evaporator Fan Motor – This manual reset type thermal overcurrent relay for the evaporator fan motor interlocks system operation.

Internal Thermostat for Condenser Fan Motor – Embedded in the fan motor winding, this internal thermostat cuts out the operation of the fan motor when winding temperature exceeds the setting.

Internal Thermostat for Evaporator Fan Motor – Embedded in the fan motor winding, this internal thermostat cuts out the operation of the fan motor when winding temperature exceeds the setting. (RAS-4U2S and RAS-5U2S only)

Page 36: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

36

CONTROL SYSTEM

Safety and Control Device Settings Cooling Unit

Model RAS-4U2S RAS-5U2S RAS-6U2S RAS-8U2S RAS-9U2S RAS-10U2S Manual Reset, Adjustable For Evaporator Fan Motor

Overcurrent Relay A 3.3 4.4 2.1 2.1 4.0 4.0

Condensing Unit

Model RAS-4CT2S RAS-5CT2S RAS-6CT2S RAS-8CT2S RAS-9CT2S RAS-10CT2S RAS-13CT2S RAS-15CT2S RAS-20CT2S

For Compressor

400DH 500DH 600DH 750EL 900EL 1000EL 750EL/

500DH

1000EL/

600DH

1000EL/

1000EL

Automatic Reset, Non-Adjustable

kg/cm2G 30 30 30 30 30 30 30 30 30

kPa 2,940 2,940 2,940 2,940 2,940 2,940 2,940 2,940 2,940

kg/cm2G 24 24 24 24 24 24 24 24 24

High Pressure Switch

Cut-Out

Cut-In

kPa 2,350 2,350 2,350 2,350 2,350 2,350 2,350 2,350 2,350

Automatic Reset, Non-Adjustable

Overcurrent Transformer

Cut-Out A 13.2 16.8 19.8 24.2 28.5 31.5 24.2/16.8 31.5/19.8 31.5/31.5

Automatic Reset, Non-Adjustable

°C 135 135 135 135 135 135 135 135 135

Internal Thermostat

Cut-Out

Cut-In °C 113 113 113 113 113 113 113 113 113

Non-Adjustable Timer

min 3 3 3 3 3 3 3/3.5 3/3.5 3/3.5

Crankcase Heater W ─ ─ ─ ─ ─ ─ ─/40 60/─ 60/60

Manual Reset, Adjustable For Evaporator Fan Motor

Overcurrent Relay A ─ ─ ─ ─ ─ ─ 5.1 5.1 8.0

Automatic Reset, Non-Adjustable

Internal Thermostat

Cut-Out

Cut-In

°C

°C

130

100

130

100

Automatic Reset, Non-Adjustable

°C 160 160 160 160 160 160 160 160 160

For Condenser Fan Motor

Internal Thermostat

Cut-Out

Cut-In °C 130 130 130 130 130 130 130 130 130

For Control Circuit Fuse

Capacity

A

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

Automatic Reset, Non-Adjustable

kg/cm2G

kPa

24

2,350

24

2,350

24

2,350

For Condensing

Pressure Control Valve

Open Starting Pressure

Full Open Pressure

kg/cm2G

kPa

27

2,650

27

2,650

27

2,650

Page 37: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

37

INSTALLATION DATA Maximum Foundation Gradient Foundation Provisions Cooling Units

Dimensions A B Model

deg. mm deg. mmRAS-4U2S 0.6 7 0.6 9 RAS-5U2S 0.6 7 0.6 9 RAS-6U2S 0.6 7 0.6 11 RAS-8U2S 0.6 7 0.6 13 RAS-9U2S 0.6 11 0.6 15 RAS-10U2S 0.6 11 0.6 15

Dimensions A B Model

deg. mm deg. mmRAS-13U2S 0.7 12 0.6 15 RAS-15U2S 0.7 12 0.6 15 RAS-20U2S 0.7 10 0.6 16

Condensing Units

Dimensions A B Model

deg. mm deg. mmRAS-4CT2S 1.0 14 1.0 15 RAS-5CT2S 1.0 14 1.0 15 RAS-6CT2S 1.0 14 1.0 15 RAS-8CT2S 1.0 14 1.0 15 RAS-9CT2S 1.0 17 1.0 18 RAS-10CT2S 1.0 17 1.0 18

Dimensions A B Model

deg. mm deg. mmRAS-13CT2S 1.0 32 1.0 17 RAS-15CT2S 1.0 32 1.0 17 RAS-20CT2S 1.0 35 1.0 17

Page 38: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

38

INSTALLATION DATA Installation Dimensions Foundation Provisions Cooling Units

Dimensions (mm) Model

A RAS-4U2S 940 RAS-5U2S 940 RAS-6U2S 1,130 RAS-8U2S 1,330

RAS-4U2S through RAS-8U2S

RAS-9U2S and RAS-10U2S RAS-13U2S and RAS-15U2S

RAS-20U2S

Page 39: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

39

INSTALLATION DATA

Foundation Provisions (Continued) Condensing Units

Dimensions (mm) Model

A B RAS-4CT2S 660 895 RAS-5CT2S 660 895 RAS-6CT2S 660 895 RAS-8CT2S 660 895 RAS-9CT2S 863 1,053 RAS-10CT2S 863 1,053

RAS-4CT2S through RAS-10CT2S

Dimensions (mm) Model

A B RAS-13CT2S 440 1,825 RAS-15CT2S 440 1,825 RAS-20CT2S 457 2,005

RAS-13CT2S through RAS-20CT2S

Page 40: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

40

Longer than "L"

Longer than "1/2L"Downward Pitch

Horizontal or Pitched Down

Water Seal Trap

Condensate Drain ConnectionCooling Unit

Auxiliary Drain Pan(Field-Supplied)

Cooling Unit

To the Atmosphere

INSTALLATION DATA Ducting Provisions

Connections Pre-drilled duct flanges for return and supply air ducting are equipped at the factory for these units.

Duct Arrangement Model RAS-20U2S is composed of a fan compartment and a coil compartment. The factory standard horizontal flow air can be changed as explained in the figure on page 2. .

Field Piping Provisions for Condensate Drain

A female piping thread screw connection is provided. Dimension “L” in the figure should be sufficiently longer than the negative fan pressure at the drain connection

(50 mm to 100mm depending on the return air duct design).

Condensate Drain Connection NOTE: When the relative humidity of inlet air or ambient air exceeds 80%, apply an (field-supplied) auxiliary drain pan beneath the cooling unit shown in the figure.

Field Piping Provisions for Refrigerant Piping Piping Arrangement These units are pre-piped at the factory: the required field piping is connection piping between the cooling unit and the condensing unit. To ensure satisfactory operation, the following piping arrangements must be provided.

Loops and Traps – Liquid loops or oil traps must be provided according to the mutual locations of the condensing unit and the cooling unit.

Filter-Dryer – A factory-supplied filter-dryer should be provided as shown in the figure for each refrigeration cycle.(RAS-13U2S, RAS-15U2S and RAS-20U2S only)

Sight Glass – A field-supplied liquid line sight glass must be assembled and mounted in the field, as shown in the figure for each refrigeration cycle.

Solenoid Valve – A field-supplied solenoid valve for each cycle must be equipped immediately up-stream of the expansion valve of the cooling unit, when the connection piping length exceeds the following limits. Refer to the typical wiring diagram for the solenoid valve control wiring.

Page 41: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

41

Cooling Unit

Filter-Dryer

*Sight Glass U-Trap

Liquid Loop

*Solenoid Valve

Oil Trap

Filter-Dryer*Solenoid Valve

*Sight Glass

Cooling Unit

(At Each 10 Meters)Oil Trap

Liquid Loop

Condensing Unit

INSTALLATION DATA Field Piping Provisions for Refrigerant Piping (Continued)

* :Field-Supplied :Liquid Refrigerant Pipe :Gas Refrigerant Pipe

A: Condensing Unit Below B: Condensing Unit Above

NOTES: 1.These piping arrangements should be performed for the both refrigeration cycles of the dual-circuited models. 2.Do not connect the dual circuited models with a single-circuited cooling unit.

Field Piping

Refrigerant Piping Limitation Maximum Lift (m)

Model Refrigerant

Cycle (Compressor Model) A B

Maximum Equivalent Piping Length - One Way - (m)

RAS-4U2S + RAS-4CT2S 400DH 15 25 *5/**30 RAS-5U2S + RAS-5CT2S 500DH 15 25 *5/**30 RAS-6U2S + RAS-6CT2S 600DH 15 25 *5/**30 RAS-8U2S + RAS-8CT2S 750 EL 15 25 *5/**30 RAS-9U2S + RAS-9CT2S 900 EL 15 25 *5/**30 RAS-10U2S + RAS-10CT2S 1000 EL 15 25 *5/**30

No. 1: 750EL 15 25 *6/**30 RAS-13U2S + RAS-13CT2S

No. 2: 500DH 15 25 *6/**30 No. 1: 1000EL 15 25 *6/**30

RAS-15U2S + RAS-15CT2S No. 2: 600DH 15 25 *6/**30 No. 1: 1000EL 15 25 *6/**30/***60

RAS-20U2S + RAS-20CT2S No. 2: 1000EL 15 25 *6/**30/***60

A: The condensing unit is installed below the cooling unit. B: The condensing unit is installed above the cooling unit. * : Maximum Length without Solenoid Valve Control. ** : Maximum Length with Solenoid Valve Shut-Off Control. *** : Maximum Length with Pump-Down Control.

Refrigerant Piping Size and Refrigerant Charging Data Charge correct quantity of refrigerant in accordance with these two following tables “Refrigerant of Holding Charge” and “Pipe size and Charging Data”. The condensing units are factory-charged with a correct quantity of the factory testing. The tolerance of the charging quantity should be within 0.1kg.

Refrigerant of Holding Charge Cooling Unit Condensing Unit

Model Charge (kg) Model Charge (kg) RAS-4U2S 0 RAS-4CT2S 2.0 RAS-5U2S 0 RAS-5CT2S 2.0 RAS-6U2S 0 RAS-6CT2S 2.0 RAS-8U2S 0 RAS-8CT2S 2.0 RAS-9U2S 0 RAS-9CT2S 3.0 RAS-10U2S 0 RAS-10CT2S 3.0 RAS-13U2S 0 RAS-13CT2S 1.0X2 RAS-15U2S 0 RAS-15CT2S 1.0X2 RAS-20U2S 0 RAS-20CT2S 3.0X2

Page 42: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

42

INSTALLATION DATA Piping Size and Charging Data

Equivalent Piping Length (One Way for Each Cycle) -(m)- Model Refrigerant Cycle (Compressor Model) 5 10 15 20 25 30 40 50 60

L ODxT PD

12.7×0.9 0.08(7.8)

12.7×0.90.15(14.7)

12.7×0.90.22(21.6)

15.88×1.10.09(8.8)

15.88×1.10.12(11.8)

15.88×1.10.14(13.7)

─ ─

─ ─

─ ─

G ODxT PD

19.05×1.1 0.13(12.7)

19.05×1.10.26(25.5)

22.2×1.20.18(17.7)

22.2×1.20.24(23.5)

28.57×1.30.08(7.8)

28.57×1.30.09(8.8)

─ ─

─ ─

─ ─

*Refrigerant Charge (kg) 3.2 3.5 3.8 4.0 4.3 4.6 ─ ─ ─

RAS-4U2S +

RAS-4CT2S 400DH

**Additional Oil Charge(l) ─ ─ ─ ─ 0.03 0.07 ─ ─ ─

L ODxT PD

12.7×0.9 0.08(7.8)

12.7×0.90.15(14.7)

12.7×0.90.22(21.6)

15.88×1.10.09(8.8)

15.88×1.10.12(11.8)

15.88×1.10.14(13.7)

─ ─

─ ─

─ ─

G ODxT PD

19.05×1.1 0.13(12.7)

19.05×1.10.26(25.5)

22.2×1.20.18(17.7)

22.2×1.20.24(23.5)

28.57×1.30.08(7.8)

28.57×1.30.09(8.8)

─ ─

─ ─

─ ─

*Refrigerant Charge (kg) 4.2 4.9 5.6 6.2 6.9 7.6 ─ ─ ─

RAS-5U2S +

RAS-5CT2S 500DH

**Additional Oil Charge(l) ─ ─ ─ ─ 0.08 0.15 ─ ─ ─

L ODxT PD

12.7×0.9 0.08(7.8)

12.7×0.90.15(14.7)

12.7×0.90.22(21.6)

15.88×1.10.09(8.8)

15.88×1.10.12(11.8)

15.88×1.10.14(13.7)

─ ─

─ ─

─ ─

G ODxT PD

19.05×1.1 0.13(12.7)

19.05×1.10.26(25.5)

22.2×1.20.18(17.7)

22.2×1.20.24(23.5)

28.57×1.30.08(7.8)

28.57×1.30.09(8.8)

─ ─

─ ─

─ ─

*Refrigerant Charge (kg) 4.0 4.9 5.9 6.8 7.7 8.5 ─ ─ ─

RAS-6U2S +

RAS-6CT2S 600DH

**Additional Oil Charge(l) ─ ─ ─ ─ 0.10 0.19 ─ ─ ─

L ODxT PD

12.7×0.9 0.08(7.8)

12.7×0.90.15(14.7)

12.7×0.90.22(21.6)

15.88×1.10.09(8.8)

15.88×1.10.12(11.8)

15.88×1.10.14(13.7)

─ ─

─ ─

─ ─

G ODxT PD

22.2×1.2 0.12(11.8)

28.57×1.30.07(6.9)

28.57×1.30.10(9.8)

28.57×1.30.13(12.7)

28.57×1.30.16(15.7)

28.57×1.30.19(18.6)

─ ─

─ ─

─ ─

*Refrigerant Charge (kg) 4.8 5.5 6.2 6.8 7.5 8.2 ─ ─ ─

RAS-8U2S +

RAS-8CT2S 750EL

**Additional Oil Charge(l) ─ ─ ─ ─ 0.08 0.15 ─ ─ ─

L ODxT PD

15.88×1.1 0.06(6.0)

15.88×1.10.12(11.8)

15.88×1.10.18(18.0)

15.88×1.10.24(24.0)

19.05×1.10.14(13.8)

19.05×1.10.17(16.7)

─ ─

─ ─

─ ─

G ODxT PD

28.57×1.3 0.08(8.0)

28.57×1.30.15(14.7)

28.57×1.30.23(22.5)

28.57×1.30.3(29.4)

34.9×1.40.13(12.9)

34.9×1.40.15(14.7)

─ ─

─ ─

─ ─

*Refrigerant Charge (kg) 6.6 7.7 8.8 9.8 10.9 12.0 ─ ─ ─

RAS-9U2S +

RAS-9CT2S 900EL

**Additional Oil Charge(l) ─ ─ ─ ─ 0.12 0.24 ─ ─ ─

L ODxT PD

15.88×1.1 0.06(6.0)

15.88×1.10.12(11.8)

15.88×1.10.18(18.0)

15.88×1.10.24(24.0)

19.05×1.10.14(13.8)

19.05×1.10.17(16.7)

─ ─

─ ─

─ ─

G ODxT PD

28.57×1.3 0.08(8.0)

28.57×1.30.15(14.7)

28.57×1.30.23(22.5)

28.57×1.30.3(29.4)

34.9×1.40.13(12.9)

34.9×1.40.15(14.7)

─ ─

─ ─

─ ─

*Refrigerant Charge (kg) 7.0 8.2 9.4 10.6 11.8 13.0 ─ ─ ─

RAS-10U2S +

RAS-10CT2S 1000EL

**Additional Oil Charge(l) ─ ─ ─ ─ 0.13 0.26 ─ ─ ─

L ODxT PD

12.7×0.9 0.02(2.0)

12.7×0.90.05(4.9)

12.7×0.90.07(6.9)

15.88×1.10.09(8.8)

15.88×1.10.12(11.8)

15.88×1.10.14(13.7)

─ ─

─ ─

─ ─

G ODxT PD

22.2×1.2 0.12(11.8)

28.57×1.30.07(6.9)

28.57×1.30.10(9.8)

28.57×1.30.13(12.7)

28.57×1.30.16(15.7)

28.57×1.30.19(18.6)

─ ─

─ ─

─ ─

*Refrigerant Charge (kg) 4.9 5.6 6.2 6.9 7.5 8.2 ─ ─ ─

No. 1: 750EL

**Additional Oil Charge(l) ─ ─ ─ ─ 0.07 0.14 ─ ─ ─

L ODxT PD

12.7×0.9 0.01(1.0)

12.7×0.90.02(2.0)

12.7×0.90.03(2.9)

15.88×1.10.05(4.9)

15.88×1.10.06(5.9)

15.88×1.10.07(6.9)

─ ─

─ ─

─ ─

G ODxT PD

19.05×1.1 0.13(12.7)

19.05×1.10.26(25.5)

22.2×1.20.18(17.7)

22.2×1.20.24(23.5)

28.57×1.30.08(7.8)

28.57x1.30.09(8.8)

─ ─

─ ─

─ ─

*Refrigerant Charge (kg) 3.0 3.7 4.4 5.0 5.7 6.4 ─ ─ ─

RAS-13U2S +

RAS-13CT2S

No. 2: 500DH

**Additional Oil Charge(l) ─ ─ ─ ─ 0.08 0.15 ─ ─ ─

L ODxT PD

15.88×1.1 0.02(2.0)

15.88×1.10.05(4.9)

15.88×1.10.07(6.9)

15.88×1.10.09(8.8)

19.05X1.10.12(11.8)

19.05X1.10.14(13.7)

─ ─

─ ─

─ ─

G ODxT PD

28.57×1.3 0.12(11.8)

28.57×1.30.07(6.9)

28.57×1.30.10(9.8)

28.57×1.30.13(12.7)

34.9×1.40.16(15.7)

34.9×1.40.19(18.6)

─ ─

─ ─

─ ─

*Refrigerant Charge (kg) 5.8 6.6 7.5 8.3 9.2 10 ─ ─ ─

No. 1: 1000EL

**Additional Oil Charge(l) ─ ─ ─ ─ 0.10 0.19 ─ ─ ─

L ODxT PD

12.7×0.9 0.02(2.0)

12.7×0.90.05(4.9)

12.7×0.90.07(6.9)

15.88×1.10.09(8.8)

15.88×1.10.12(11.8)

15.88×1.10.14(13.7)

─ ─

─ ─

─ ─

G ODxT PD

19.05×1.1 0.12(11.8)

19.05×1.10.07(6.9)

22.2×1.20.10(9.8)

22.2×1.20.13(12.7)

28.57×1.30.16(15.7)

28.57×1.30.19(18.6)

─ ─

─ ─

─ ─

*Refrigerant Charge (kg) 3.1 3.6 4.0 4.5 4.9 5.4 ─ ─ ─

RAS-15U2S +

RAS-15CT2S

No. 2: 600DH

**Additional Oil Charge(l) ─ ─ ─ ─ 0.04 0.10 ─ ─ ─

L ODxT PD

15.88X1.1 0.06(5.0)

15.88X1.10.12(11.8)

15.88X1.10.18(17.7)

15.88X1.10.24(23.5)

19.05X1.10.14(13.7)

19.05X1.10.17(16.7)

19.05X1.1 0.23(22.6)

19.05X1.10.28(27.4)

19.05X1.1 0.34(33.3)

G ODxT PD

28.57X1.3 0.08(7.8)

28.57X1.30.15(14.7)

28.57X1.30.23(22.6)

28.57X1.30.30(29.4)

34.9X1.40.13(12.7)

34.9X1.40.15(14.7)

34.9X1.4 0.20(19.6)

34.9X1.40.25(24.5)

34.9X1.4 0.30(29.4)

*Refrigerant Charge (kg) 6.8 8.0 9.3 10.5 11.8 13.0 15.3 17.7 20.0

No. 1: 1000EL

**Additional Oil Charge(l) ─ ─ ─ ─ 0.14 0.28 0.53 0.79 1.05

L ODxT PD

15.88X1.1 0.06(5.9)

15.88X1.10.12(11.8)

15.88X1.10.24(23.5)

15.88X1.10.14(13.7)

19.05X1.10.14(13.7)

19.05X1.10.17(16.7)

19.05X1.1 0.23(22.6)

19.05X1.10.28(27.4)

19.05X1.1 0.34(33.3)

G ODxT PD

28.57X1.3 0.08(7.8)

28.57X1.30.15(14.7)

28.57X1.30.23(22.6)

28.57X1.30.30(29.4)

34.9X1.40.13(12.7)

34.9X1.40.15(14.7)

34.9X1.4 0.20(19.6)

34.9X1.40.25(24.5)

34.9X1.4 0.30(29.4)

*Refrigerant Charge (kg) 6.8 8.0 9.3 10.5 11.8 13.0 15.3 17.7 20.0

RAS-20U2S +

RAS-20CT2S

No. 2 1000EL

**Additional Oil Charge(l) ─ ─ ─ ─ 0.14 0.28 0.53 0.79 1.05 G : Gas Piping PD : Pressure Drop for Equivalent Piping Length[kg/cm2 (kPa)] L : Liquid Piping * : Total Refrigerant Charge for One Cycle for Actual Piping Length (kg)

OD×T : Outer Diameter and Thickness of pipe (mm) ** : Additional charge is required for one cycle

Page 43: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

43

18 19

Electrical Box

B DA E F

INSTALLATION DATA

Field Wiring Provisions Field wiring The units are internally wired at the factory according to generally accepted electrical technology. Required field wiring to conform to the HITACHI Standard Wiring and required components are as follows.

Required Field Wiring – Main power wiring to the unit, Earth Wiring, Thermostat Control Wiring and Solenoid Valve Control Wiring (When the unit is to be operated under the conditions specified in the Field Piping Provisions)

Required Components – Main Power Switch, Main Power Fuses, Conduit Coupling, Solenoid Valve (When the unit is to be operated under the conditions specified in the Field Piping Provisions) and Room Thermostat.

NOTE: When installing the solenoid valve, connect the wiring of the solenoid valve to the terminals for control, in order that the solenoid valve will be opened when the compressor is operating and will be closed when the compressor is stopped.

Wire and Fuse Size Selection Wire and fuse sizes should be selected in accordance with national and local codes, taking the designed maximum ambient temperature into account. The system maximum current will be the sum of the compressor maximum current, condenser fan motor current and evaporator fan motor maximum current (refer to the Electrical Data).

Page 44: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

44

through RAS-10U2S

18 19

1 2 3 4 5 6

L3TS

L2L1R

Control CircuitTerminal

PCBTerminal

1B DA E F

Control Circuit

Switch(Field-Supplied)

Main Power

(Cooling Unit)

(Field-Supplied)Thermostat

Room ※

RAS-6U2S

Electrical Box

RAS-6CT2S through RAS-10CT2S

Main Power Terminal

L2 L3L1R TS

N 2Mp

(Condensing Unit)

3 4 5 6

Motor Terminal

20211819

RAS-13CT2S through RAS-20CT2S

RAS-13U2S through RAS-20U2S

(Field Supplied)

Main PowerSwitch

Motor Terminal

(Cooling Unit)(Field-Supplied)Thermostat

Room ※

(Condensing Unit)

Electrical Box

Electrical Box

FS T

U V W

NMp

L3T

L2S

L1R

Main Power Terminal

(Field-Supplied)

ValveNo.1

Solenoid

(Field-Supplied)

ValveNo.2

Solenoid

D EAR

PCB

B

INSTALLATION DATA NOTE: The control circuit is wired for the 240V control circuit (unit power source 415V)at the factory, therefore for the 220V control circuit, change the wiring at the terminal base in the electrical box, according to the “Typical Wiring”.

Page 45: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

45

SPECIFICATIONS

Standard Specifications Unit – The air conditioner shall be a split-system air conditioner for application with R-22 refrigerant, and shall be composed of a cooling unit and a condensing unit(s) with one or two refrigeration cycles, electrical components and enclosing cabinets. Optional accessories shall also be provided upon customer request. The condensing unit shall be completely weatherproof for outdoor installation, and the cooling unit shall be designed for indoor installation. The condensing unit and the cooling unit shall be properly assembled, internally piped and wired, and thoroughly tested and holding charged with R-22 refrigerant at the factory. Capacity – The total cooling capacity of the unit shall be kcal/h or greater, and the sensible heat capacity shall be kcal/h or greater with °C evaporator air inlet dry bulb, °C evaporator air inlet wet bulb, °C condenser air inlet temperature and m3/min. evaporator air flow. The total compressor power input shall not exceed kW. CONDENSING UNIT

Cabinet – The cabinet shall be constructed of galvanized steel baked with synthetic resin paint. The service panels shall be easily removable for service access to electrical components, compressors, condensers and condenser fans. Refrigeration Cycle – The refrigeration cycle shall be equipped with a hermetic compressor, an air-cooled condenser coil, an evaporator coil, check joints for high pressure line and low pressure line. Compressor – The compressor shall be a hermetic compressor. The starting method shall be the direct-on-line type. The hermetic compressor shall be a welded shell type, and spring-suspended internally. The compressor shall be mounted on vibration-proof rubber bushings. Condenser Fan and Condenser Fan Motor – The condenser fan shall be the aluminum propeller type, dynamically and statically balanced, and the condenser fan shall be directly driven by a kW motor for up-flow air discharge. The motor shall be permanently lubricated, and protected from water invasion.

Condenser – The air-cooled coil shall be the multi-pass, cross-finned tube type, equipped with highly-efficient aluminum fins, mechanically bonded to oxygen-free copper tubes. The coil shall be cleaned, dehydrated and tested for leakage at the factory. Compressor Protection – The compressor shall be protected against breakdown by a quick response overcurrent relay, a high pressure switch, a cycling protection circuit and a discharge gas thermostat. COOLING UNIT

Evaporator - The evaporator shall be the multi-pass cross-finned tube type, equipped with highly-efficient aluminum fins, mechanically bonded to seamless, oxygen-free copper tubes. The fins shall be spaced at more than 12 fins per 25.4 mm. The face area of the evaporator shall not be less than m2. The coil shall be cleaned, dehydrated and tested for leakage at the factory. Evaporator Fan and Evaporator Fan Motor – The evaporator fan shall be the forward-curved, multi-blade centrifugal type, statically and dynamically balanced, and V-belt driven by a kW motor. The evaporator fan motor shall be permanently lubricated. The fan shall deliver air flow m3/min. at mmAq external static pressure at rpm. OTHER ITEMS

Control – All electrical control devices, except for the field-supplied room thermostat assembly, shall be enclosed in a weatherproof location of a unit. In addition to the compressor protection devices, the unit shall be provided with fuses for the control circuit, and auxiliary relays.

Page 46: HITACHI SPLIT-SYSTEM AIR CONDITIONERSHITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and

Specifications in this catalog are subject to change without notice, in order that HITACHI may bring the latest innovations to our customers.