Nominal Capacity Range Technical Catalog Ⅰ (50 Hz) 9,500 kcal/h to 52,200 kcal/h ─ Design Information ─ 11,100 W to 60,800 W Models: 37,700 Btu/h to 207,100 Btu/h Cooling Units Condensing Units RAS-4U2S + RAS-4CT2S RAS-5U2S + RAS-5CT2S RAS-6U2S + RAS-6CT2S RAS-8U2S + RAS-8CT2S
RAS-9U2S + RAS-9CT2S RAS-10U2S + RAS-10CT2S RAS-13U2S + RAS-13CT2S RAS-15U2S + RAS-15CT2S RAS-20U2S + RAS-20CT2S
HITACHI proudly presents to our customers this wide range of split-system air conditioners, from 4 HP to 20 HP, which is designed for high and medium outdoor temperatures and comply with almost any types of installation requirements. These split-system air conditioners are composed of condensing units and cooling units. The condensing units are composed of compressors, air-cooled condensers, condenser fans, auxiliary and control equipments compactly packed in a
weather-proof cabinet. The cooling units are direct expansion fan coil units for indoor installations, and are designed for duct air distribution systems in domestic and commercial applications. These units are composed of evaporator, expansion valve(s) or capillary tubes (for RAS-4U2S through RAS -10U2S only), an evaporator fan, a fan motor and auxiliary equipments in a cabinet.
2
FEATURES Optimum Designs for Individual Requirements
Cooling Units
High Performance Evaporator Fan The powerful and efficient multi-blade centrifugal fan creates high static pressure with minimum power consumption and smooth air flow. Evaporator fan bearings can be replaced without removing fans. An adjustable motor pulley is mounted in RAS-6U2S through RAS-20U2S, in order to cover wider ranges of fan speed.
Well-Designed Evaporator Highly-Efficient cross fin coils have been applied to provide a larger cooling capacity with low air speed on the coil.
Condensing Units
Energy-Saving Design Highly-Efficient Scroll Compressors - Low power input is achieved by specially designed compressors and heat exchangers and their combinations.
Optional Accessories Filter Box and Filter - A high performance air filter and a filter box are provided for the return air connection of all models.
Optional Accessory Attachment
RAS-4U2S through RAS-15U2S
RAS-20U2S
Air Inlet
Air Filter
Cooling
Filter Box
Unit
(Standard Type)
(Optional Type)
3
GENERAL DATA Unit General Data
Cooling Capacity According to Unit Combination Model
Cooling Unit RAS-4U2S RAS-5U2S RAS-6U2S RAS-8U2S RAS-9U2S RAS-10U2S RAS-13U2S RAS-15U2S RAS-20U2S
Condensing Unit RAS-4CT2S RAS-5CT2S RAS-6CT2S RAS-8CT2S RAS-9CT2S RAS-10CT2S RAS-13CT2S RAS-15CT2S RAS-20CT2S
kcal/h 9,500 12,000 15,000 18,100 22,400 25,300 30,100 37,600 52,200 W 11,100 14,000 17,500 21,100 26,000 29,400 35,000 43,700 60,800
Nominal Cooling Capacity at 35℃ outdoor temperature *1 Btu/h 37,700 47,600 59,500 71,800 88,900 100,400 119,500 149,200 207,100
kcal/h 8,500 10,800 13,400 16,300 20,000 22,500 26,900 33,600 46,600 W 9,900 12,600 15,500 19,000 23,300 26,200 31,300 39,100 54,200
Nominal Cooling Capacity at 46℃ outdoor temperature **1 Btu/h 33,700 42,900 53,200 64,700 79,500 89,300 106,700 133,300 184,900
Condensing Unit Model RAS-4CT2S RAS-5CT2S RAS-6CT2S RAS-8CT2S RAS-9CT2S RAS-10CT2S RAS-13CT2S RAS-15CT2S RAS-20CT2S
Capacity Control % 100,0 100,0 100,0 100,0 100,0 100,0 100,60,0 100,60,0 100,50,0 Cabinet Synthetic Resin Painted on Galvanized Steel Plates
Color Beige (MUNSELL Code) (2.5Y 8/2)
Height mm 880 880 880 910 1,000 1,000 790 790 1,012
(in.) (34-5/8) (34-5/8) (34-5/8) (35-13/16) (39-3/8) (39-3/8) (31-1/16) (31-1/16) (39-27/32)
Width mm 782 782 782 782 985 985 1,806 1,806 1,986
(in.) (30-13/16) (30-13/16) (30-13/16) (30-13/16) (38-3/4) (38-3/4) (71) (71) (78-3/16)
Depth mm 862 862 862 862 1,020 1,020 966 966 1,000
Outer
Dimensions
(in.) (33-15/16) (33-15/16) (33-15/16) (33-15/16) (40-3/16) (40-3/16) (38-1/32) (38-1/32) (39-3/8)
kg 130 130 133 185 220 220 330 400 425 Net Weight
(lbs.) (287) (287) (293) (408) (485) (485) (727) (881) (936) Refrigerant R-22
Number of Circuits 1 1 1 1 1 1 2 2 2
Compressor Hermetic Hermetic Hermetic Hermetic Hermetic Hermetic Hermetic Hermetic HermeticType Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Model 400DH 500DH 600DH 750EL 900EL 1000EL 750EL/500DH 1000EL/600DH 1000EL
Quantity 1 1 1 1 1 1 1/1 1/1 2 Condenser Multi-Pass Cross-Finned Tube Condenser Fan Direct Driven Propeller Fan
Motor kW 0.15 0.3 0.25 0.25 0.4 0.4 0.4/0.3 0.3 0.3 (hp) (1/5) (2/5) (1/3) (1/3) (1/2) (1/2) (1/2)/(2/5) (2/5) (2/5)
Quantity 1 1 1 1 1 1 2 2 2
Piping Connections With Flare Nut or Companion Flange for Field Piping Gas Line
Size (O.D) mm Ø19.05 Ø19.05 Ø19.05 Ø22.2 Ø28.57 Ø28.57 Ø25.4/Ø19.05 Ø25.4/Ø19.05 Ø25.4 (in.) (3/4) (3/4) (3/4) (7/8) (1-1/8) (1-1/8) (1)/(3/4) (1)/(3/4) (1) Type Flare Flare Flare Flange Flange Flange Flange/Flare Flange/Flare Flange
Quantity 1 1 1 1 1 1 1/1 1/1 2
Liquid Line Size (O.D) mm Ø12.7 Ø12.7 Ø12.7 Ø12.7 Ø15.88 Ø15.88 Ø12.7 Ø15.88/Ø12.7 Ø15.88
(in.) (1/2) (1/2) (1/2) (1/2) (5/8) (5/8) (1/2) (5/8)/(1/2) (5/8) Type Flare Flare Flare Flare Flare Flare Flare Flare Flare Quantity 1 1 1 1 1 1 2 1/1 2
Wiring Hole Main Power mm Ø52* Ø52* Ø52* Ø52* Ø52* Ø52* Ø52* Ø52* Ø52*
(in.) (2-1/16) (2-1/16) (2-1/16) (2-1/16) (2-1/16) (2-1/16) (2-1/16) (2-1/16) (2-1/16) Control mm Ø26.1* Ø26.1* Ø26.1* Ø26.1* Ø26.1* Ø26.1* Ø26.1* Ø26.1* Ø26.1*
(in.) (1-1/32) (1-1/32) (1-1/32) (1-1/32) (1-1/32) (1-1/32) (1-1/32) (1-1/32) (1-1/32)
kg 150 150 153 205 245 245 365 435 460 Shipping Weight
(lbs.) (330) (330) (337) (452) (540) (540) (803) (957) (1,012) Approximate Packing List
Height mm 1,010 1,010 1,010 1,040 1,130 1,130 945 945 1,168 (in.) (39-3/4) (39-3/4) (39-3/4) (40-15/16) (44-1/2) (44-1/2) (37-3/16) (37-3/16) (45-15/16)
Width mm 842 842 842 842 1,065 1,065 1,885 1,885 2,045 (in.) (33-5/32) (33-5/32) (33-5/32) (33-5/32) (41-15/16) (41-15/16) (74-1/4) (74-1/4) (80-1/2)
Depth mm 950 950 950 950 1,080 1,080 1,025 1,025 1,060 (in.) (37-3/8) (37-3/8) (37-3/8) (37-3/8) (42-1/2) (42-1/2) (40-11/32) (40-11/32) (41-23/32)
Measurements m3 0 . 8 1 0 . 8 1 0 . 8 1 0 . 8 3 1 .3 0 1 . 3 0 1 . 8 3 1 . 8 3 2 . 5 3 * : Knockout Hole
4
GENERAL DATA
Unit General Data (Continued) Cooling Unit Model RAS-4U2S RAS-5U2S RAS-6U2S RAS-8U2S RAS-9U2S RAS-10U2S RAS-13U2S RAS-15U2S RAS-20U2S
Cabinet Galvanized Steel Plate
Color ─ (MUNSELL Code) ─
Height mm 500 500 500 500 550 550 600 600 1,055
(in.) (19-11/16) (19-11/16) (19-11/16) (19-11/16) (21-5/8) (21-5/8) (23-5/8) (23-5/8) (41-17/32)
Width mm 750 750 750 750 1,400 1,400 1,400 1,400 1,600 (in.) (29-1/2) (29-1/2) (29-1/2) (29-1/2) (55-1/8) (55-1/8) (55-3/16) (55-3/16) (63) Depth mm 890 890 1,080 1,280 1,100 1,100 1,015 1,015 860
Outer Dimensions
(in.) (35) (35) (42-1/2) (50-3/8) (43-5/16) (43-5/16) (39-15/16) (39-15/16) (33-27/32) kg 70 70 75 75 135 135 170 180 235
Net Weight (lbs.) (154) (154) (165) (165) (297) (297) (374) (396) (518)
Refrigerant R-22
Flow Control Device Capillary Tube Thermal Expansion Valve (One for Each Circuit)
Number of Circuits 1 1 1 1 1 1 2 2 2 Evaporator Fan Multi-Blade Centrifugal Fan(Double Suction)
Nominal Air Flow m3/min 37 50 65 69 82 90 110 130 180 m3/s 0.62 0.83 1.08 1.15 1.37 1.5 1.83 2.17 3.0 L/s 620 830 1080 1150 1370 1500 1830 2170 3000 (cfm) (1,310) (1,770) (2,300) (2,440) (2,920) (3,180) (3,880) (4,590) (6,360)
Motor kW 0.35 0.55 0.75 0.75 1.5 1.5 2.2 2.2 3.7 (hp) (1/2) (3/4) (1) (1) (2) (2) (3) (3) (5)
Quantity 1 1 1 1 1 1 1 1 1 Evaporator Multi-Pass Cross-Finned Tube Piping Connections Brazing Connection
Liquid Line
Size (O.D) mm Ø12.7 Ø12.7 Ø12.7 Ø12.7 Ø15.88 Ø15.88 Ø12.7 Ø15.88/Ø12.7 Ø15.88 (in.) (1/2) (1/2) (1/2) (1/2) (5/8) (5/8) (1/2) (5/8)/(1/2) (5/8)
Quantity 1 1 1 1 1 1 2 1/1 2
Gas Line
Size (O.D) mm Ø19.05 Ø19.05 Ø19.05 Ø22.2 Ø28.57 Ø28.57 Ø25.4/Ø19.05 Ø25.4/Ø19.05 Ø25.4
(in.) (3/4) (3/4) (3/4) (7/8) (1-1/8) (1-1/8) (1)/(3/4) (1)/(3/4) (1)
Quantity 1 1 1 1 1 1 1/1 1/1 2
Condensate Drain Female Piping Thread Screw Size FPT 3/4 3/4 3/4 3/4 1 1 3/4 3/4 3/4 Quantity 1 1 1 1 1 1 1 1 1
Wiring Hole Main mm Ø30 Ø30 Ø30 Ø30 Ø30 Ø30 Ø26 Ø26 Ø28
(in.) (1-3/16) (1-3/16) (1-3/16) (1-3/16) (1-3/16) (1-3/16) (1) (1) (1-3/32)
kg 90 90 100 100 160 160 190 200 255 Shipping Weight
(lbs.) (198) (198) (220) (220) (352) (352) (418) (440) (562)
Approximate Packing List Height mm 615 615 615 615 1,305 1,305 1,055 1,055 1,175
(in.) (24-7/32) (24-7/32) (24-7/32) (24-7/32) (51-3/8) (51-3/8) (41-1/2) (41-1/2) (46-1/4)
Width mm 810 810 810 810 1,590 1,590 1,450 1,450 1,720 (in.) (31-7/8) (31-7/8) (31-7/8) (31-7/8) (62-19/32) (62-19/32) (57-1/16) (57-1/16) (67-23/32)
Depth mm 1,010 1,010 1,200 1,400 615 615 740 740 910 (in.) (39-3/4) (39-3/4) (47-1/4) (55-1/8) (24-7/32) (24-7/32) (29-1/8) (29-1/8) (35-13/16)
Measurements m3 0.50 0.50 0.60 0.70 1.28 1.28 1.13 1.13 1.84
NOTES: 1.The capacities are gross capacities, which include the effect of
evaporator fan motor heat. 2.The nominal cooling capacity is based on the combined capacity of
the HITACHI standard split system, and is based on JIS standard B8616-1999 Temperature Conditions:
Evaporator Air Inlet Temperature: 27°C DB (80°F DB) 19°C WB (66°F WB) Condenser Air Inlet Temperature: *1) 35°C DB (95°F DB) **1) 46°C DB (115°F DB)
3.The standard combination of the HITACHI split-system air conditioners
is as follows:
Cooling Unit Condensing Unit Standard Power Supply RAS-4U2S + RAS-4CT2S Main (AC 3Ø ) Control (AC 1Ø ) RAS-5U2S + RAS-5CT2S 380V 50Hz 220V 50Hz RAS-6U2S + RAS-6CT2S 415V 50Hz 240V 50Hz RAS-8U2S + RAS-8CT2S RAS-9U2S + RAS-9CT2S RAS-10U2S + RAS-10CT2S RAS-13U2S + RAS-13CT2S RAS-15U2S + RAS-15CT2S RAS-20U2S + RAS-20CT2S
5
WORKING RANGE
Working Range
Power Supply
The applicable voltage range for each unit is given in the Electrical Data. The working voltage among the three phases must be balanced within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the rated voltage.
Condenser Air Inlet Temperature and Evaporator Air Inlet Temperature
Condenser Air Inlet Temperature -Dry Bulb-
Evaporator Air Inlet Temperature -Dry/Wet Bulb- Model
Maximum Minimum Maximum Minimum
All Models 52°C 125°F
20°C 68°F
35°C / 21.5°C 95°F / 70.7°F
20°C / 14°C 68°F / 57.2°F
NOTES:
1. When the unit is operating at a condenser air inlet temperature of 52°C DB (125°F DB), the maximum evaporator air inlet temperature shall be 18°C WB (64.4°F WB).
2. All models: 80% to 120% of Nominal Air Flow.
6
o
o 12.7 Brazing
20o
19.05 Brazingo
30
Summary
FPT 3/43
5
76 Both Sides
8 Air IntakeAir Discharge9
Duct ConnectionDuct Connection
Hole for Power Supply WiringCondensate Drain Connection
Magnetic Switch Box
1Mark Name
2
Service Panel
4
Gas Refrigerant Piping ConnectionLiquid Refrigerant Piping Connection
Hole for Operation Circuit Wiring
Hole for Power Supply WiringCondensate Drain Connection
Magnetic Switch Box
1Mark Name
2
Service Panel
4
Gas Refrigerant Piping ConnectionLiquid Refrigerant Piping Connection
Hole for Operation Circuit Wiringo
o 12.7 Brazing
20o 30
Summary
FPT 3/43
5
76 Both Sides
22.2 Brazingo
Duct ConnectionDuct Connection
Air DischargeAir Intake
98
Hole for Power Supply WiringCondensate Drain Connection
Magnetic Switch Box
1Mark Name
2
Service Panel
4
Gas Refrigerant Piping ConnectionLiquid Refrigerant Piping Connection
Hole for Operation Circuit Wiringo
o 12.7 Brazing
20o
19.05 Brazingo
30
Summary
FPT 3/43
5
76 Both Sides
Duct ConnectionDuct Connection
Air DischargeAir Intake
98
DIMENSIONAL DATA
Cooling Units RAS-4U2S and RAS-5U2S
RAS-6U2S
RAS-8U2S
7
3 Refrigerant Gas Outlet for NO.1 Cycle 25.4 Brazing o
Condensate Drain Connection
1
Mark Name
2
Refrigerant Liquid Inlet for NO.1 Cycle
Summary
56
Refrigerant Liquid Inlet for NO.2 Cycle
Refrigerant Gas Outlet for NO.2 Cycle4
12.7 Brazingo
19.05 Brazing
Service Panel for Expansion Valve7Hole for Power Supply Wiring
o
12.7 Brazing for RAS-13U2So 15.88 Brazing for RAS-15U2So
FPT 3/4 26o
Screw Holes for Suspension Bolt8 4-M16
11
1312
4
NameMark
23
1Summary
Liquid Refrigerant Piping ConnectionGas Refrigerant Piping Connection
O 15.88 BrazingO 28.57 Brazing
Condensate Drain Piping Connection FPT 1Hole for Power Supply Wiring
56
Hole for Operation Circuit WiringO 30O 20
78
Service PanelService Panel
Service PanelRear Side OnlyBoth Sides
Front Side Only
910
Magenetic Switch BoxFresh Air Intake Duct ConnectionSuspension Bracket
Air DischargeAir Intake Duct Connection
Duct Connection
*2. Movable 50mm Right and Lefts Side.
*1. Movable 50mm Right and Lefts Side.Notes:
DIMENSIONAL DATA
Cooling Units RAS-9U2S and RAS-10U2S
RAS-13U2S and RAS-15U2S
8
Hole for Power Supply Wiring 26-Both Sideso
Screw Holes for Suspension Bolt8 4-M16
Condensate Drain Connection
Service Panel for Expansion Valve
1Mark Name
2Refrigerant Gas Outlet for NO.1 Cycle
Refrigerant Liquid Inlet for NO.1 Cycle o 15.88 Brazing
25.4 Brazingo
Summary
FPT 1
3
5
76
Refrigerant Liquid Inlet for NO.2 Cycle o
25.4 BrazingoRefrigerant Gas Outlet for NO.2 Cycle4
15.88 Brazing
DIMENSIONAL DATA
Cooling Units RAS-20U2S
9
26.1 (Knockout Hole)
12.7 Flare Connection19.05 Flare Connection
Summary
52 (Knockout Hole)
Magnetic Switch Box
Name
Connecting Hole for Refrigerant Liquid Line
Connecting Hole for
Power Supply Wiring
Operation Circuit Wiring
Refrigerant Gas Line
Mounting Hole
Service Panel
765
4
3
2
Mark1
4- 12.5
26.1(Knockout Hole)
12.7 Flare Connection25.4 Flare Connection
Summary
52(Knockout Hole)
Magnetic Switch Box
Name
Connecting Hole for Refrigerant Liquid Line
Connecting Hole for
Power Supply Wiring
Operation Circuit Wiring
Refrigerant Gas Line
Mounting Hole
Service Panel
765
4
3
2
Mark1
4- 12.5
26.1 (Knockout Hole)
15.88 Flare Connection 25.4 Flare Connection
Summary
52 (Knockout Hole)
Magnetic Switch Box
Name
Connecting Hole for Refrigerant Liquid Line
Connecting Hole for
Power Supply Wiring
Operation Circuit Wiring
Refrigerant Gas Line
Mounting Hole
Service Panel
765
4
3
2
Mark1
4- 12.5
DIMENSIONAL DATA
Condensing Units RAS-4CT2S through RAS-6CT2S
RAS-8CT2S
RAS-9CT2S and RAS-10CT2S
10
Knockout Hole for Power Supply Wiring
1Mark Name
2Refrigerant Gas Outlet for NO.1 Cycle
Refrigerant Liquid Inlet for NO.1 Cycle
Knockout Hole for Operation Circuit Wiringo
o 15.88 Flare for Connection
26o
25.4 Flange Connectiono
52
Summary
3
5
8
6
Refrigerant Liquid Inlet for NO.2 Cycle
Refrigerant Gas Outlet for NO.2 Cycle4 o
15.88 Flare for Connectiono
25.4 Flange Connection
Magnetic Switch Box7 Service Panel
o
Knockout Hole for Power Supply Wiring
1
Mark Name
2Refrigerant Gas Outlet for NO.1 Cycle
Refrigerant Liquid Inlet for NO.1 Cycle
Knockout Hole for Operation Circuit Wiringo
26o
25.4 Flange Connection
52
Summary
3
5
8
6
Refrigerant Liquid Inlet for NO.2 Cycle
Refrigerant Gas Outlet for NO.2 Cycle4
12.7 Flare Connectiono
19.05 Flare Connection
Magnetic Switch Box7 Service Panel
o
12.7 Flare for RAS-13CT2So 15.88 Flare for RAS-15CT2So
DIMENSIONAL DATA
Condensing Units RAS-13CT2S and RAS-15CT2S
RAS-20CT2S
11
Refrigerant Piping Connection Side
Refrigerant Piping Connection Side
SELECTION DATA
Operation Space
Cooling Units
RAS-4U2S through RAS-8U2S
RAS-9U2S and RAS-10U2S
RAS-13U2S and RAS-15U2S
RAS-20U2S
Condensing Units
Dimensions(mm)Model a b RAS-4CT2S 400 700 RAS-5CT2S 400 700 RAS-6CT2S 400 700 RAS-8CT2S 400 700 RAS-9CT2S 500 900 RAS-10CT2S 500 900
RAS-13CT2S and RAS-15CT2S
RAS-20CT2S
12
805
Fan Motor
410
A
Evaporator
1400
Center of Gravity
A
Evaporator
CB
GravityCenter of
Fan Motor
950
D
Evaporator
A1600
460
GravityCenter of Fan Motor
SELECTION DATA
Weight Balance
Cooling Units
Dimensions(mm) Model A B C D
ApproximateOperating
Weight (kg) RAS-4U2S 522 380 890 700 70 RAS-5U2S 522 380 890 700 70 RAS-6U2S 650 380 1,080 700 75 RAS-8U2S 750 380 1,280 700 75 RAS-9U2S 820 520 1,400 1,100 135 RAS-10U2S 820 520 1,400 1,100 135
Dimensions(mm) Model A
Approximate OperatingWeight (kg)
RAS-13U2S 740 170 RAS-15U2S 730 180
Dimensions(mm) Model A
Approximate OperatingWeight (kg)
RAS-20U2S 720 235
13
SELECTION DATA Weight Balance (Continued)
Condensing Units
Dimensions(mm) Model
A B C D
ApproximateOperating Weight (kg)
RAS-4CT2S 350 350 782 862 130
RAS-5CT2S 320 330 782 862 130
RAS-6CT2S 300 325 782 862 133
RAS-8CT2S 370 435 782 862 185
RAS-9CT2S 420 480 985 1,020 220
RAS-10CT2S 420 480 985 1,020 220
Dimensions(mm) Model
A B
Approximate Operating Weight (kg)
RAS-13CT2S 810 400 330 RAS-15CT2S 810 400 400 RAS-20CT2S 870 400 425
RAS-4CT2S, RAS-5CT2S, and RAS-6CT2S
RAS-8CT2S, RAS-9CT2S, and RAS-10CT2S RAS-13CT2S and RAS-15CT2S
RAS-20CT2S
14
SELECTION DATA
Selection GuideSelection Example:
1. Determine the System Requirements
Calculate the total cooling capacity, sensible heat capacity, evaporator air flow and required external static pressure according to the design conditions. Clarify the power source frequency and the climatic conditions.
Given Conditions: Total Cooling Capacity 27,500 kcal/h Sensible Heat Capacity 21,000 kcal/h Condenser Air Inlet Temperature 40°C Evaporator Air Inlet Dry Bulb 29°C Evaporator Air Inlet Wet Bulb 20°C Evaporator Air Flow 115 m3/min External Static Pressure 16 mmAq Power Source 415V / 50 Hz Climatic Conditions High / Medium
2. Select a Matching Model Select model RAS-13U2S+RAS-13CT2S, by entering 40°C condenser air inlet temperature and 20 °C evaporator air inlet wet bulb (WB) at 110 m3/min. Evaporator air flow (QA) in the Cooling Capacity Table.(RAS-13U2S+RAS-13CT2S unit will provide cooling capacity of 29,200 kcal/h and a sensible heat capacity of 21,700 kcal/h)
3. Read Performance of the Model
The total cooling capacity (TC), sensible heat capacity (SHC*) at the dry bulb given in the table, compressor power input (IPT), and sensible heat correction factor (CR) can be determined by interpolation (or some can be read directly from the table when the conditions coincide with the tabulated figures).
At 20℃ WB
TC SHC* IPT CR (x1,000 (x1,000 kcal/h) kcal/h) (kW)
At 121 m3/min QA 30.2 22.8 11.0 1.82
At 110 m3/min QA 29.2 21.7 10.9 1.69
At 115 m3/min QA 29.7 22.2 11.0 1.75
(By Interpolation)
4. Correct the Sensible Heat Capacity (If Required)
Correct the sensible heat capacity for the given 29°C evaporator air inlet dry bulb from the tabulated 27°C (DB*) according to the following formula.
SHC =SHC*+CR×(DB-DB*), where,
SHC : corrected sensible heat capacity (×1,000kcal/h),
SHC* : sensible heat capacity from in the table (×1,000kcal/h),
DB : given evaporator air inlet dry bulb (°C) and
DB*: evaporator air inlet dry bulb (°C) given for each WB in the table.
For this example,
SHC =22.2+1.75x(29-27)=25.7(x1,000kca/h) 5. Determine the Readjusting Requirements for
Evaporator Fan From the Fan Performance Table (Page 19), the required fan speeds and motor brake power are determined to be 1,045 rpm and 1.10kW, respectively. (Evaporator fan motor input is 1.19kW as seen on Page 23, Electrical Data-Cooling Unit-IPT column for evaporator fan motor at 415V). In this case, the factory-mounted standard fan motor (2.2kW) possesses sufficient capacity. However, the regulation space of the adjustable motor pulley should be readjusted to 2.2mm (see “Fan Speed Adjustment” on Page 21).
6. Determine the Net Capacity
The capacities are gross capacities, which include the effect of evaporator fan motor heat. To determine net capacity as follows: Net capacity =gross capacity – MIF heat
=gross capacity (kcal/h) – MIF input (kW) x 860 (kcal/kW.h)
=30,100 kcal/h – 1.19 kW x 860 kcal/kW.h =30,100 kcal/h – 1,023 kcal/h =29,077 kcal/h
Net sensible capacity =25,700 kcal/h – 1,023 kcal/h =24,677 kcal/h
NOTE: 1.Direct interpolation is permissible. Do not extrapolate.
15
SELECTION DATA Cooling Capacities
Conversion Multiplier:1 kcal/h=1.163W =3.968Btu/h
Evaporator Inlet Air Condenser Air Inlet Temperature ( oC ) Model QA WB DB* 20 25 30 35 40 46 52
-CR- oC TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT 16 23 8.9 7.2 2.7 8.6 7.1 2.9 8.2 6.9 3.1 7.9 6.8 3.3 7.5 6.6 3.4 6.9 6.4 3.7 6.4 6.1 3.9 33.3 18 25 9.7 7.3 2.8 9.3 7.1 3.0 8.9 7.0 3.2 8.5 6.8 3.3 8.1 6.6 3.5 7.6 6.4 3.8 6.9 6.1 4.0 20 27 10.3 7.2 2.9 10.0 7.1 3.1 9.6 6.9 3.3 9.1 6.8 3.4 8.7 6.6 3.6 8.1 6.4 3.9 7.4 6.1 4.1
-0.522- 22 30 10.8 7.6 2.9 10.4 7.4 3.1 10.0 7.3 3.3 9.5 7.1 3.5 9.1 7.0 3.7 8.4 6.7 4.0 7.8 6.5 4.3 RAS- 14 20 8.3 7.0 2.6 8.1 6.8 2.8 7.7 6.7 3.0 7.4 6.5 3.2 7.0 6.4 3.4 6.5 6.2 3.6 6.0 5.9 3.8 4U2S 37.0 16 23 9.2 7.6 2.7 8.9 7.5 2.9 8.5 7.3 3.1 8.1 7.2 3.3 7.7 7.0 3.5 7.2 6.8 3.7 6.6 6.5 4.0
+ 18 25 10.0 7.7 2.8 9.6 7.5 3.0 9.2 7.4 3.2 8.8 7.2 3.4 8.4 7.0 3.6 7.8 6.8 3.9 7.1 6.5 4.1 RAS- -0.567- 20 27 10.7 7.6 2.9 10.3 7.5 3.1 9.9 7.3 3.3 9.5 7.2 3.5 9.0 7.0 3.7 8.3 6.8 3.9 7.7 6.5 4.2
4CT2S 22 30 11.1 8.0 3.0 10.7 7.9 3.2 10.3 7.7 3.4 9.8 7.6 3.6 9.4 7.4 3.8 8.7 7.2 4.1 8.0 6.9 4.3 14 20 8.6 7.3 2.7 8.3 7.2 2.9 8.0 7.1 3.0 7.6 6.9 3.2 7.2 6.7 3.4 6.7 6.5 3.7 6.2 6.2 3.9 40.7 16 23 9.5 8.0 2.8 9.1 7.9 3.0 8.8 7.7 3.1 8.4 7.6 3.3 8.0 7.4 3.5 7.4 7.2 3.8 6.8 6.8 4.0 18 25 10.3 8.1 2.8 9.9 7.9 3.0 9.5 7.8 3.2 9.1 7.6 3.4 8.7 7.4 3.6 8.1 7.2 3.9 7.3 6.9 4.1 -0.610- 20 27 11.0 8.0 2.9 10.6 7.9 3.1 10.2 7.7 3.3 9.8 7.5 3.5 9.3 7.4 3.7 8.6 7.1 4.0 7.9 6.9 4.2 22 30 11.5 8.5 3.0 11.1 8.3 3.2 10.6 8.1 3.4 10.2 8.0 3.6 9.7 7.8 3.8 9.0 7.6 4.1 8.3 7.3 4.3
16 23 11.1 9.3 3.3 10.7 9.2 3.6 10.3 9.0 3.8 9.8 8.8 4.0 9.3 8.6 4.2 8.7 8.3 4.5 7.9 7.9 4.8 45.0 18 25 12.1 9.4 3.4 11.6 9.2 3.7 11.2 9.0 3.9 10.7 8.8 4.1 10.1 8.6 4.4 9.4 8.3 4.7 8.6 8.0 5.0
20 27 12.9 9.3 3.5 12.5 9.2 3.8 12.0 9.0 4.0 11.4 8.8 4.2 10.8 8.6 4.5 10.1 8.3 4.8 9.3 8.0 5.1
-0.705- 22 30 13.5 9.8 3.6 13.0 9.7 3.9 12.5 9.5 4.1 11.9 9.3 4.3 11.3 9.1 4.6 10.5 8.8 4.9 9.7 8.5 5.2
RAS- 14 20 10.4 9.0 3.2 10.1 8.9 3.5 9.7 8.7 3.7 9.2 8.5 3.9 8.8 8.3 4.1 8.2 8.0 4.4 7.5 7.5 4.7 5U2S 50.0 16 23 11.5 9.9 3.4 11.1 9.7 3.6 10.6 9.5 3.8 10.2 9.3 4.0 9.6 9.1 4.3 9.0 8.8 4.6 8.2 8.2 4.9
+ 18 25 12.5 9.9 3.5 12.0 9.8 3.7 11.5 9.6 3.9 11.0 9.4 4.2 10.5 9.1 4.4 9.7 8.9 4.7 8.9 8.5 5.0 RAS- -0.766- 20 27 13.3 9.9 3.5 12.9 9.7 3.8 12.4 9.5 4.0 11.8 9.3 4.3 11.2 9.1 4.5 10.4 8.8 4.9 9.6 8.5 5.1
5CT2S 22 30 13.9 10.4 3.6 13.4 10.2 3.9 12.9 10.1 4.1 12.3 9.9 4.4 11.7 9.6 4.6 10.9 9.4 5.0 10.0 9.1 5.3 14 20 10.7 9.5 3.3 10.4 9.3 3.5 10.0 9.1 3.7 9.5 8.9 3.9 9.0 8.7 4.2 8.4 8.4 4.5 7.7 7.7 4.8
55.0 16 23 11.8 10.4 3.4 11.4 10.2 3.6 11.0 10.1 3.9 10.5 9.9 4.1 10.0 9.6 4.3 9.3 9.3 4.6 8.5 8.5 4.9 18 25 12.9 10.5 3.5 12.4 10.3 3.7 11.9 10.1 4.0 11.4 9.9 4.2 10.8 9.7 4.5 10.1 9.4 4.8 9.2 9.0 5.1
-0.824- 20 27 13.8 10.4 3.6 13.3 10.2 3.8 12.8 10.0 4.1 12.2 9.8 4.3 11.6 9.6 4.6 10.8 9.3 4.9 9.9 9.0 5.2
22 30 14.4 11.0 3.7 13.8 10.8 3.9 13.3 10.6 4.2 12.7 10.4 4.4 12.1 10.2 4.7 11.2 9.9 5.0 10.4 9.6 5.3 52.0 18 25 15.2 11.5 4.2 14.6 11.2 4.5 14.1 11.0 4.8 13.4 10.7 5.0 12.8 10.5 5.3 11.9 10.1 5.7 10.8 9.7 6.1 20 27 16.2 11.4 4.3 15.7 11.2 4.6 15.1 10.9 4.9 14.4 10.7 5.2 13.7 10.4 5.5 12.7 10.1 5.9 11.7 9.7 6.2 -0.832- 22 30 16.9 12.0 4.4 16.3 11.8 4.7 15.7 11.5 5.0 15.0 11.3 5.3 14.2 11.0 5.6 13.3 10.7 6.0 12.2 10.3 6.4 16 23 14.5 12.2 4.1 14.0 11.9 4.4 13.4 11.7 4.7 12.8 11.4 4.9 12.2 11.2 5.2 11.3 10.8 5.6 10.4 10.4 6.0 58.5 18 25 15.7 12.2 4.2 15.2 12.0 4.5 14.6 11.7 4.8 13.9 11.5 5.1 13.2 11.2 5.4 12.3 10.8 5.8 11.2 10.4 6.2 20 27 16.8 12.1 4.3 16.2 11.9 4.7 15.6 11.7 4.9 14.9 11.4 5.2 14.1 11.1 5.5 13.1 10.8 5.9 12.1 10.4 6.3 -0.916- 22 30 17.5 12.8 4.5 16.9 12.6 4.8 16.2 12.3 5.1 15.5 12.1 5.4 14.7 11.8 5.7 13.7 11.4 6.1 12.7 11.1 6.5 14 20 13.5 11.7 4.0 13.1 11.5 4.3 12.6 11.3 4.6 12.0 11.0 4.8 11.4 10.8 5.1 10.6 10.4 5.5 9.7 9.7 5.8
RAS- 65.0 16 23 14.9 12.9 4.2 14.4 12.6 4.5 13.8 12.4 4.7 13.2 12.1 5.0 12.6 11.9 5.3 11.7 11.5 5.7 10.7 10.7 6.0 6U2S 18 25 16.2 12.9 4.3 15.7 12.7 4.6 15.0 12.4 4.9 14.4 12.2 5.2 13.7 11.9 5.5 12.7 11.5 5.9 11.6 11.1 6.2
+ -0.996- 20 27 17.4 12.9 4.4 16.8 12.6 4.7 16.1 12.4 5.0 15.4 12.1 5.3 14.6 11.8 5.6 13.6 11.4 6.0 12.5 11.0 6.4 RAS- 22 30 18.1 13.5 4.5 17.5 13.3 4.8 16.8 13.1 5.1 16.0 12.8 5.4 15.2 12.5 5.7 14.2 12.2 6.2 13.1 11.8 6.5
6CT2S 14 20 14.0 12.3 4.1 13.5 12.1 4.4 13.0 11.9 4.6 12.4 11.6 4.9 11.8 11.4 5.2 11.0 11.0 5.6 10.0 10.0 5.9 71.5 16 23 15.4 13.6 4.2 14.9 13.3 4.5 14.3 13.1 4.8 13.7 12.8 5.1 13.0 12.5 5.4 12.1 12.1 5.8 11.0 11.0 6.1 18 25 16.8 13.6 4.3 16.2 13.4 4.6 15.5 13.1 4.9 14.8 12.8 5.2 14.1 12.6 5.5 13.1 12.2 5.9 11.9 11.7 6.3 -1.08- 20 27 17.9 13.5 4.4 17.3 13.3 4.8 16.6 13.0 5.1 15.9 12.8 5.3 15.1 12.5 5.7 14.0 12.1 6.1 12.9 11.7 6.4 22 30 18.7 14.3 4.6 18.0 14.1 4.9 17.3 13.8 5.2 16.5 13.5 5.5 15.7 13.3 5.8 14.7 12.9 6.2 13.5 12.5 6.6 14 20 14.4 12.9 4.1 13.9 12.7 4.4 13.4 12.5 4.7 12.8 12.2 4.9 12.1 11.9 5.2 11.3 11.3 5.6 10.4 10.4 6.0 78.0 16 23 15.9 14.2 4.2 15.4 14.0 4.5 14.7 13.7 4.8 14.1 13.5 5.1 13.4 13.2 5.4 12.4 12.4 5.8 11.4 11.4 6.2 18 25 17.3 14.3 4.4 16.7 14.0 4.7 16.0 13.8 5.0 15.3 13.5 5.3 14.5 13.2 5.6 13.5 12.8 6.0 12.3 12.3 6.3 -1.15- 20 27 18.5 14.2 4.5 17.9 14.0 4.8 17.1 13.7 5.1 16.4 13.4 5.4 15.5 13.1 5.7 14.5 12.7 6.1 13.3 12.3 6.5 22 30 19.3 15.0 4.6 18.6 14.8 4.9 17.9 14.5 5.2 17.1 14.2 5.5 16.2 14.0 5.9 15.1 13.6 6.3 13.9 13.2 6.7
QA : Evaporator Air Flow (m3/min) TC : Total Cooling Capacity (x 1000kcal/h) CR : Sensible Heat Correction Factor SHC* : Sensible Heat Capacity (x 1000kcal/h) Given for Each WB and DB* WB : Evaporator Air Inlet Wet Bulb (°C) IPT : Compressor Input Power (kW) DB* : Evaporator Air Inlet Dry Bulb (°C) Given for Each WB NOTE: The data is based on the following conditions. Refrigerant Piping Length in One Direction: 5 Meters Horizontal.
16
SELECTION DATA Cooling Capacities
Conversion Multiplier:1 kcal/h=1.163W =3.968Btu/h
Evaporator Inlet Air Condenser Air Inlet Temperature ( oC ) Model QA WB DB* 20 25 30 35 40 46 52
-CR- oC TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT TC SHC* IPT 55.2 18 25 18.3 13.1 5.6 17.7 12.8 6.0 17.0 12.5 6.4 16.2 12.2 6.8 15.4 11.9 7.2 14.3 11.4 7.7 13.0 10.9 8.2 20 27 19.6 13.1 5.8 18.9 12.8 6.2 18.2 12.5 6.6 17.3 12.2 6.9 16.5 11.8 7.3 15.3 11.4 7.9 14.1 10.9 8.4 -0.883- 22 30 20.4 13.6 5.9 19.7 13.3 6.3 18.9 13.1 6.7 18.1 12.7 7.1 17.2 12.4 7.5 16.0 12.0 8.1 14.8 11.6 8.6 16 23 17.4 13.8 5.5 16.8 13.6 5.9 16.2 13.3 6.3 15.4 12.9 6.6 14.7 12.6 7.0 13.6 12.1 7.6 12.5 11.7 8.0 62.1 18 25 19.0 13.9 5.7 18.3 13.6 6.1 17.6 13.3 6.5 16.8 13.0 6.8 15.9 12.6 7.2 14.8 12.2 7.8 13.5 11.7 8.3 20 27 20.3 13.8 5.8 19.6 13.6 6.2 18.8 13.3 6.6 17.9 12.9 7.0 17.0 12.6 7.4 15.8 12.1 8.0 14.5 11.6 8.5 -0.972- 22 30 21.1 14.5 6.0 20.4 14.2 6.4 19.6 13.9 6.8 18.7 13.6 7.2 17.8 13.3 7.6 16.6 12.8 8.2 15.3 12.4 8.7 14 20 16.3 13.4 5.4 15.8 13.1 5.8 15.2 12.8 6.1 14.5 12.5 6.5 13.8 12.2 6.9 12.8 11.7 7.4 11.7 11.3 7.8
RAS- 69.0 16 23 18.0 14.6 5.6 17.4 14.3 6.0 16.7 14.0 6.4 16.0 13.7 6.7 15.1 13.3 7.1 14.1 12.9 7.6 12.9 12.4 8.1 8U2S 18 25 19.6 14.7 5.7 18.9 14.4 6.2 18.1 14.1 6.6 17.3 13.8 6.9 16.5 13.4 7.3 15.3 12.9 7.9 13.9 12.4 8.4
+ -1.06- 20 27 21.0 14.6 5.9 20.2 14.3 6.3 19.4 14.0 6.7 18.5 13.7 7.1 17.6 13.3 7.5 16.4 12.9 8.1 15.0 12.4 8.6 RAS- 22 30 21.9 15.3 6.1 21.1 15.0 6.5 20.2 14.7 6.9 19.3 14.4 7.3 18.4 14.1 7.7 17.1 13.6 8.3 15.8 13.2 8.8
8CT2S 14 20 16.9 14.0 5.4 16.3 13.8 5.8 15.7 13.5 6.2 15.0 13.2 6.6 14.2 12.8 6.9 13.2 12.4 7.5 12.1 11.9 7.9 75.9 16 23 18.6 15.4 5.6 18.0 15.1 6.0 17.2 14.8 6.4 16.5 14.4 6.8 15.6 14.1 7.2 14.5 13.6 7.7 13.3 13.1 8.2 18 25 20.2 15.5 5.8 19.5 15.1 6.2 18.7 14.8 6.6 17.9 14.5 7.0 17.0 14.1 7.4 15.8 13.7 8.0 14.4 13.1 8.4 -1.14- 20 27 21.6 15.4 6.0 20.9 15.1 6.4 20.0 14.8 6.8 19.1 14.4 7.2 18.2 14.0 7.6 16.9 13.6 8.2 15.5 13.1 8.7 22 30 22.6 16.1 6.1 21.8 15.8 6.6 20.9 15.5 7.0 20.0 15.2 7.4 19.0 14.9 7.8 17.7 14.4 8.4 16.3 13.9 8.9 14 20 17.4 14.7 5.5 16.8 14.4 5.9 16.1 14.1 6.3 15.4 13.8 6.6 14.6 13.4 7.0 13.6 13.0 7.5 12.5 12.5 8.0 82.8 16 23 19.2 16.1 5.7 18.5 15.8 6.1 17.8 15.5 6.5 17.0 15.1 6.8 16.1 14.8 7.3 15.0 14.3 7.8 13.7 13.7 8.3 18 25 20.9 16.2 5.9 20.1 15.9 6.3 19.3 15.5 6.7 18.5 15.2 7.1 17.5 14.8 7.5 16.3 14.3 8.0 14.9 13.8 8.5 -1.22- 20 27 22.3 16.1 6.0 21.5 15.8 6.4 20.7 15.5 6.9 19.8 15.1 7.2 18.7 14.7 7.7 17.4 14.3 8.2 16.0 13.7 8.7 22 30 23.3 16.9 6.2 22.4 16.6 6.6 21.5 16.3 7.0 20.6 16.0 7.4 19.6 15.6 7.9 18.2 15.2 8.5 16.8 14.7 9.0 65.6 18 25 22.7 16.0 5.6 21.8 15.6 6.1 21.0 15.2 6.7 20.0 14.8 7.2 19.0 14.4 7.9 17.7 13.9 8.6 16.1 13.2 9.3 20 27 24.2 15.9 5.8 23.4 15.6 6.3 22.5 15.2 6.8 21.4 14.8 7.4 20.4 14.3 8.1 18.9 13.8 8.9 17.4 13.2 9.6 -1.05- 22 30 25.3 16.6 5.9 24.4 16.2 6.5 23.4 15.8 7.0 22.3 15.5 7.6 21.2 15.0 8.3 19.8 14.5 9.1 18.2 14.0 9.8 16 23 21.6 16.8 5.5 20.8 16.5 6.0 20.0 16.1 6.5 19.1 15.7 7.1 18.1 15.3 7.7 16.8 14.7 8.5 15.4 14.1 9.2 73.8 18 25 23.5 16.9 5.7 22.6 16.6 6.2 21.7 16.2 6.7 20.7 15.8 7.3 19.7 15.3 8.0 18.3 14.8 8.7 16.7 14.1 9.5 20 27 25.1 16.8 5.8 24.2 16.5 6.4 23.2 16.1 6.9 22.2 15.7 7.5 21.1 15.3 8.2 19.6 14.7 9.0 18.0 14.1 9.7 -1.16- 22 30 26.2 17.6 6.0 25.2 17.2 6.6 24.2 16.9 7.1 23.1 16.5 7.7 22.0 16.1 8.4 20.5 15.5 9.2 18.9 15.0 9.9 14 20 20.2 16.3 5.4 19.5 15.9 5.9 18.8 15.6 6.5 17.9 15.2 6.9 17.0 14.8 7.6 15.8 14.2 8.3 14.5 13.6 9.0
RAS- 82.0 16 23 22.3 17.8 5.6 21.5 17.4 6.1 20.7 17.0 6.6 19.7 16.6 7.2 18.7 16.2 7.8 17.4 15.6 8.6 16.0 15.0 9.39U2S 18 25 24.2 17.9 5.8 23.4 17.5 6.3 22.4 17.1 6.8 21.4 16.7 7.4 20.4 16.2 8.0 18.9 15.7 8.8 17.3 15.0 9.6
+ -1.26- 20 27 25.9 17.8 5.9 25.0 17.4 6.5 24.0 17.0 7.0 22.9 16.6 7.6 21.8 16.2 8.2 20.3 15.6 9.1 18.6 15.0 9.8RAS- 22 30 27.0 18.6 6.1 26.1 18.2 6.6 25.0 17.9 7.2 23.9 17.5 7.8 22.7 17.0 8.5 21.2 16.5 9.3 19.5 15.9 10.0
9CT2S 14 20 20.9 17.1 5.4 20.2 16.7 6.0 19.4 16.4 6.5 18.5 16.0 7.0 17.6 15.5 7.6 16.4 15.0 8.4 15.0 14.4 9.1 90.2 16 23 23.0 18.7 5.6 22.2 18.3 6.2 21.3 17.9 6.7 20.4 17.5 7.3 19.3 17.0 7.9 18.0 16.5 8.7 16.5 15.8 9.4 18 25 25.0 18.8 5.8 24.1 18.4 6.4 23.2 18.0 6.9 22.1 17.6 7.5 21.0 17.1 8.1 19.5 16.5 8.9 17.8 15.8 9.6 -1.36- 20 27 26.8 18.7 6.0 25.8 18.3 6.5 24.8 17.9 7.1 23.7 17.5 7.7 22.5 17.0 8.3 20.9 16.4 9.1 19.2 15.8 9.9 22 30 27.9 19.6 6.1 26.9 19.2 6.7 25.8 18.8 7.3 24.7 18.4 7.9 23.5 18.0 8.5 21.9 17.4 9.4 20.1 16.8 10.1 14 20 21.5 17.9 5.5 20.8 17.5 6.0 20.0 17.1 6.5 19.1 16.7 7.1 18.1 16.3 7.7 16.9 15.7 8.5 15.4 15.1 9.2 98.4 16 23 23.7 19.5 5.7 22.9 19.2 6.2 22.0 18.8 6.7 21.0 18.3 7.3 19.9 17.9 8.0 18.5 17.3 8.8 17.0 16.6 9.5 18 25 25.8 19.6 5.9 24.9 19.3 6.4 23.9 18.9 7.0 22.8 18.4 7.6 21.7 18.0 8.2 20.2 17.3 9.0 18.4 16.6 9.7 -1.45- 20 27 27.6 19.5 6.0 26.6 19.2 6.6 25.6 18.8 7.1 24.4 18.3 7.7 23.2 17.8 8.4 21.6 17.2 9.2 19.8 16.6 10.0 22 30 28.8 20.5 6.2 27.8 20.1 6.8 26.6 19.7 7.3 25.5 19.3 8.0 24.2 18.9 8.6 22.5 18.3 9.5 20.8 17.7 10.2 72.0 18 25 25.6 17.9 6.9 24.7 17.4 7.3 23.7 17.0 7.8 22.6 16.6 8.2 21.5 16.1 8.7 20.0 15.4 9.4 18.2 14.7 10.0 20 27 27.4 17.8 7.0 26.4 17.4 7.5 25.4 16.9 8.0 24.2 16.5 8.5 23.0 16.0 9.0 21.4 15.4 9.6 19.6 14.7 10.2 -1.16- 22 30 28.5 18.5 7.2 27.5 18.1 7.7 26.4 17.7 8.2 25.2 17.2 8.7 24.0 16.8 9.2 22.4 16.2 9.9 20.6 15.5 10.5 16 23 24.4 18.8 6.7 23.5 18.4 7.2 22.6 18.0 7.7 21.6 17.5 8.1 20.5 17.0 8.6 19.0 16.4 9.2 17.4 15.7 9.8 81.0 18 25 26.5 18.9 6.9 25.5 18.5 7.4 24.5 18.1 7.9 23.4 17.6 8.3 22.2 17.1 8.8 20.7 16.5 9.5 18.8 15.7 10.1 20 27 28.3 18.8 7.1 27.3 18.4 7.6 26.2 18.0 8.1 25.1 17.5 8.6 23.8 17.0 9.1 22.1 16.4 9.7 20.3 15.7 10.3 -1.27- 22 30 29.5 19.6 7.3 28.5 19.2 7.8 27.3 18.8 8.3 26.1 18.3 8.8 24.8 17.9 9.3 23.1 17.3 10.0 21.3 16.6 10.6 14 20 22.8 18.2 6.6 22.1 17.8 7.0 21.2 17.4 7.5 20.2 16.9 7.9 19.2 16.4 8.4 17.9 15.8 9.0 16.4 15.1 9.6
RAS- 90.0 16 23 25.2 19.8 6.8 24.3 19.4 7.3 23.3 19.0 7.8 22.3 18.5 8.2 21.1 18.0 8.7 19.7 17.4 9.3 18.0 16.7 9.9 10U2S 18 25 27.4 19.9 7.0 26.4 19.5 7.5 25.3 19.1 8.0 24.2 18.6 8.4 23.0 18.1 8.9 21.4 17.4 9.6 19.5 16.7 10.2
+ -1.38- 20 27 29.3 19.8 7.2 28.3 19.4 7.7 27.1 19.0 8.2 25.9 18.5 8.7 24.6 18.0 9.2 22.9 17.3 9.9 21.0 16.6 10.5 RAS- 22 30 30.5 20.7 7.4 29.4 20.3 7.9 28.3 19.9 8.4 27.0 19.4 8.9 25.7 18.9 9.4 23.9 18.3 10.1 22.0 17.7 10.7
10CT2S 14 20 23.6 19.1 6.6 22.8 18.7 7.1 21.9 18.2 7.6 20.9 17.8 8.0 19.8 17.3 8.5 18.5 16.7 9.1 16.9 16.0 9.7 99.0 16 23 26.0 20.8 6.9 25.1 20.4 7.4 24.1 20.0 7.8 23.0 19.5 8.3 21.8 19.0 8.8 20.3 18.3 9.4 18.6 17.6 10.0 18 25 28.3 20.9 7.1 27.2 20.5 7.6 26.2 20.1 8.1 25.0 19.6 8.5 23.7 19.1 9.0 22.1 18.4 9.7 20.1 17.6 10.3 -1.49- 20 27 30.2 20.8 7.3 29.2 20.4 7.8 28.0 20.0 8.3 26.7 19.5 8.7 25.4 18.9 9.3 23.6 18.3 10.0 21.7 17.6 10.6 22 30 31.5 21.8 7.5 30.4 21.4 8.0 29.2 20.9 8.5 27.9 20.5 9.0 26.5 20.0 9.5 24.7 19.4 10.2 22.7 18.7 10.8 14 20 24.3 19.9 6.7 23.5 19.5 7.2 22.5 19.1 7.6 21.6 18.6 8.1 20.4 18.1 8.6 19.0 17.5 9.2 17.4 16.8 9.8 108.0 16 23 26.8 21.8 6.9 25.9 21.4 7.4 24.8 20.9 7.9 23.7 20.4 8.4 22.5 19.9 8.8 20.9 19.2 9.5 19.2 18.5 10.1 18 25 29.2 21.9 7.2 28.1 21.5 7.7 27.0 21.0 8.2 25.8 20.5 8.6 24.5 20.0 9.1 22.8 19.3 9.8 20.7 18.5 10.4 -1.59- 20 27 31.2 21.8 7.3 30.1 21.4 7.9 28.9 20.9 8.4 27.6 20.4 8.8 26.2 19.9 9.3 24.4 19.2 10.1 22.4 18.4 10.7 22 30 32.5 22.8 7.5 31.4 22.4 8.1 30.1 22.0 8.6 28.7 21.5 9.1 27.3 21.0 9.6 25.5 20.3 10.3 23.5 19.6 10.9
QA : Evaporator Air Flow (m3/min) TC : Total Cooling Capacity (x 1000kcal/h) CR : Sensible Heat Correction Factor SHC* : Sensible Heat Capacity (x 1000kcal/h) Given for Each WB and DB* WB : Evaporator Air Inlet Wet Bulb (°C) IPT : Compressor Input Power (kW) DB* : Evaporator Air Inlet Dry Bulb (°C) Given for Each WB NOTE: The data is based on the following conditions. Refrigerant Piping Length in One Direction: 5 Meters Horizontal.
17
SELECTION DATA Cooling Capacities
Conversion Multiplier:1 kcal/h=1.163W =3.968Btu/h
Evaporator Inlet Air Condenser Air Inlet Temperature ( oC )
Model QA WB DB* 20 25 30 35 40 46 52
-CR- oC TC SHC* IPT TC SHC
* IPT TC SHC*
IPT TC SHC*
IPT TC SHC*
IPT TC SHC* IPT TC SHC
*IPT
88.0 18 25 30.4 21.4 8.2 29.3 21.0 8.8 28.2 20.5 9.3 26.9 19.9 9.8 25.6 19.3 10.4 23.8 18.6 11.2 21.7 17.7 11.9 20 27 32.5 21.3 8.4 31.4 20.9 9.0 30.2 20.4 9.5 28.8 19.8 10.1 27.3 19.2 10.7 25.4 18.5 11.5 23.3 17.7 12.2 -1.41- 22 30 34.0 22.2 8.6 32.7 21.8 9.2 31.4 21.3 9.8 30.0 20.7 10.3 28.5 20.2 11.0 26.6 19.5 11.8 24.5 18.7 12.5 16 23 29.0 22.6 8.0 27.9 22.1 8.6 26.8 21.6 9.1 25.6 21.1 9.7 24.3 20.5 10.2 22.6 19.7 11.0 20.7 18.9 11.7 99.0 18 25 31.5 22.7 8.3 30.4 22.2 8.9 29.2 21.7 9.4 27.9 21.2 9.9 26.5 20.6 10.5 24.6 19.8 11.3 22.4 18.9 12.0 20 27 33.7 22.6 8.5 32.5 22.1 9.1 31.2 21.6 9.7 29.8 21.1 10.2 28.3 20.5 10.8 26.3 19.7 11.6 24.2 18.9 12.3 -1.55- 22 30 35.1 23.6 8.7 33.9 23.1 9.3 32.5 22.6 9.9 31.1 22.1 10.5 29.5 21.5 11.1 27.5 20.8 11.9 25.4 20.1 12.7 14 20 27.1 21.8 7.8 26.2 21.4 8.4 25.2 20.9 8.9 24.1 20.4 9.4 22.8 19.8 10.0 21.3 19.1 10.7 19.5 18.3 11.4
RAS- 110.0 16 23 29.9 23.8 8.1 28.9 23.4 8.7 27.7 22.8 9.2 26.5 22.3 9.8 25.2 21.7 10.3 23.4 20.9 11.1 21.4 20.1 11.8 13U2S 18 25 32.6 24.0 8.4 31.4 23.5 9.0 30.1 23.0 9.5 28.8 22.4 10.1 27.3 21.8 10.7 25.4 21.0 11.5 23.2 20.1 12.2
+ -1.69- 20 27 34.8 23.8 8.6 33.6 23.4 9.2 32.3 22.8 9.8 30.8 22.3 10.3 29.2 21.7 10.9 27.2 20.9 11.7 25.0 20.1 12.5 RAS- 22 30 36.3 25.0 8.8 35.0 24.5 9.4 33.6 24.0 10.0 32.1 23.4 10.6 30.5 22.8 11.2 28.4 22.1 12.1 26.2 21.3 12.8
13CT2S 14 20 28.0 22.9 7.9 27.1 22.5 8.5 26.0 22.0 9.0 24.8 21.4 9.5 23.6 20.8 10.1 22.0 20.1 10.9 20.1 19.3 11.5 121.0 16 23 30.9 25.0 8.2 29.8 24.6 8.8 28.6 24.0 9.3 27.4 23.5 9.9 26.0 22.9 10.4 24.1 22.1 11.2 22.1 21.2 11.9 18 25 33.6 25.2 8.4 32.4 24.7 9.0 31.1 24.1 9.6 29.7 23.6 10.2 28.2 23.0 10.8 26.2 22.2 11.6 23.9 21.2 12.3 -1.82- 20 27 35.9 25.1 8.7 34.7 24.6 9.3 33.3 24.0 9.9 31.8 23.4 10.4 30.2 22.8 11.0 28.1 22.0 11.9 25.8 21.2 12.6 22 30 37.5 26.3 8.9 36.2 25.8 9.5 34.7 25.3 10.1 33.1 24.7 10.7 31.5 24.1 11.3 29.4 23.4 12.2 27.1 22.6 12.9 14 20 28.9 24.0 8.0 27.9 23.5 8.6 26.8 23.0 9.1 25.6 22.4 9.6 24.3 21.8 10.2 22.6 21.1 11.0 20.7 20.2 11.6 132.0 16 23 31.9 26.2 8.3 30.8 25.7 8.9 29.5 25.2 9.4 28.2 24.6 10.0 26.8 24.0 10.5 24.9 23.2 11.3 22.8 22.3 12.0 18 25 34.7 26.4 8.5 33.4 25.8 9.1 32.1 25.3 9.7 30.7 24.7 10.3 29.1 24.1 10.9 27.1 23.3 11.7 24.7 22.3 12.4 -1.94- 20 27 37.1 26.2 8.7 35.8 25.7 9.4 34.4 25.2 10.0 32.8 24.6 10.5 31.1 23.9 11.1 29.0 23.1 12.0 26.6 22.3 12.7 22 30 38.7 27.5 9.0 37.3 27.0 9.6 35.8 26.5 10.2 34.2 25.9 10.8 32.5 25.3 11.4 30.3 24.6 12.3 27.9 23.7 13.1
104.0 18 25 38.0 26.2 8.1 36.6 25.6 9.3 35.2 25.0 10.6 33.6 24.3 11.9 31.9 23.6 13.5 29.7 22.6 15.2 27.0 21.5 17.0 20 27 40.6 26.1 8.4 39.2 25.5 9.6 37.7 24.9 10.9 36.0 24.2 12.2 34.1 23.5 13.8 31.8 22.5 15.6 29.2 21.5 17.5
-1.67- 22 30 42.4 27.1 8.5 40.9 26.6 9.9 39.2 25.9 11.2 37.5 25.3 12.6 35.6 24.6 14.1 33.2 23.7 16.0 30.6 22.7 17.9 16 23 36.2 27.6 8.0 34.9 27.0 9.2 33.5 26.3 10.4 32.0 25.7 11.7 30.4 24.9 13.1 28.2 24.0 15.0 25.9 23.0 16.8
117.0 18 25 39.3 27.8 8.2 37.9 27.1 9.5 36.4 26.5 10.7 34.8 25.8 12.1 33.0 25.1 13.6 30.7 24.1 15.5 28.0 23.0 17.2 20 27 42.1 27.6 8.4 40.6 27.0 9.7 39.0 26.4 11.0 37.2 25.7 12.4 35.3 24.9 13.9 32.9 24.0 15.8 30.2 22.9 17.7
-1.84- 22 30 43.9 28.8 8.7 42.3 28.2 9.9 40.6 27.6 11.3 38.8 26.9 12.7 36.9 26.2 14.3 34.3 25.3 16.2 31.7 24.3 18.2 14 20 33.9 26.7 7.8 32.8 26.1 9.0 31.4 25.5 10.2 30.1 24.8 11.5 28.5 24.1 12.8 26.6 23.2 14.7 24.3 22.2 16.4
130.0 16 23 37.4 29.1 8.0 36.1 28.5 9.3 34.6 27.8 10.5 33.1 27.1 11.9 31.4 26.4 13.4 29.2 25.4 15.1 26.7 24.4 16.9 18 25 40.7 29.3 8.3 39.2 28.6 9.6 37.6 28.0 10.9 36.0 27.3 12.2 34.1 26.5 13.7 31.7 25.5 15.6 28.9 24.4 17.5
-2.00- 20 27 43.5 29.1 8.5 42.0 28.5 9.9 40.3 27.8 11.2 38.5 27.1 12.5 36.5 26.4 14.1 34.0 25.4 16.0 31.2 24.3 17.8 22 30 45.4 30.4 8.8 43.7 29.8 10.0 42.0 29.1 11.5 40.1 28.5 12.9 38.1 27.7 14.4 35.5 26.8 16.5 32.7 25.8 18.3 14 20 35.0 28.0 7.9 33.8 27.4 9.1 32.5 26.8 10.3 31.0 26.1 11.6 29.4 25.3 13.0 27.4 24.4 14.8 25.1 23.4 16.5
143.0 16 23 38.6 30.5 8.1 37.2 29.9 9.4 35.8 29.3 10.6 34.2 28.5 12.0 32.4 27.8 13.5 30.1 26.8 15.2 27.6 25.7 17.1 18 25 42.0 30.7 8.4 40.5 30.1 9.7 38.9 29.4 11.0 37.1 28.7 12.3 35.3 27.9 13.9 32.8 26.9 15.8 29.9 25.7 17.6
-2.15- 20 27 44.9 30.6 8.6 43.3 29.9 9.9 41.6 29.3 11.3 39.7 28.5 12.7 37.7 27.7 14.2 35.1 26.7 16.1 32.2 25.7 18.1 22 30 46.8 32.0 8.9 45.2 31.3 10.2 43.3 30.7 11.6 41.4 30.0 13.0 39.3 29.2 14.6 36.7 28.3 16.6 33.8 27.3 18.5 14 20 36.1 29.2 8.0 34.9 28.7 9.2 33.5 28.0 10.4 32.0 27.3 11.7 30.4 26.5 13.1 28.3 25.6 14.9 25.9 24.5 16.6
156.0 16 23 39.8 31.9 8.2 38.4 31.3 9.5 36.9 30.6 10.8 35.2 29.9 12.1 33.4 29.1 13.6 31.1 28.1 15.5 28.5 27.0 17.2 18 25 43.3 32.1 8.4 41.7 31.5 9.8 40.1 30.8 11.1 38.3 30.0 12.5 36.4 29.2 14.0 33.8 28.2 15.9 30.8 27.0 17.8
-2.29- 20 27 46.3 32.0 8.7 44.7 31.3 10.0 42.9 30.6 11.4 41.0 29.9 12.8 38.9 29.1 14.3 36.2 28.1 16.4 33.2 27.0 18.2
RAS- 15U2S
+ RAS-
15CT2S
22 30 48.3 33.5 8.9 46.6 32.8 10.3 44.7 32.2 11.7 42.7 31.4 13.1 40.6 30.7 14.7 37.8 29.7 16.7 34.8 28.7 18.8 126.0 18 25 50.9 34.2 11.2 49.1 33.4 12.5 47.1 32.5 14.0 45.0 31.6 15.4 42.8 30.6 17.0 39.7 29.3 19.0 36.2 27.8 20.9 20 27 54.4 34.1 11.5 52.6 33.3 12.8 50.4 32.4 14.3 48.2 31.4 15.8 45.7 30.4 17.4 42.5 29.1 19.5 39.0 27.7 21.5 -2.06- 22 30 56.8 35.3 11.8 54.8 34.5 13.2 52.6 33.6 14.6 50.2 32.7 16.2 47.7 31.7 17.9 44.5 30.5 20.1 41.0 29.2 22.1 144.0 18 25 52.7 36.4 11.3 50.8 35.5 12.7 48.8 34.6 14.2 46.6 33.7 15.6 44.3 32.7 17.2 41.2 31.4 19.3 37.5 29.8 21.2 20 27 56.4 36.2 11.6 54.5 35.4 13.0 52.3 34.5 14.5 49.9 33.5 16.0 47.4 32.5 17.6 44.1 31.2 19.7 40.4 29.8 21.7 -2.31- 22 30 58.8 37.6 11.9 56.7 36.8 13.4 54.5 35.9 14.8 52.0 35.0 16.4 49.4 34.0 18.1 46.1 32.8 20.3 42.5 31.5 22.3 16 23 50.2 38.2 11.1 48.4 37.4 12.4 46.5 36.5 13.9 44.4 35.6 15.3 42.2 34.5 16.9 39.2 33.2 18.9 35.9 31.8 20.8 162.0 18 25 54.6 38.5 11.5 52.6 37.6 12.8 50.5 36.7 14.3 48.3 35.8 15.8 45.8 34.7 17.4 42.6 33.4 19.5 38.8 31.8 21.5 20 27 58.4 38.3 11.7 56.4 37.5 13.2 54.1 36.6 14.6 51.7 35.6 16.2 49.0 34.5 17.8 45.6 33.2 20.0 41.9 31.8 21.9
RAS- -2.54- 22 30 60.9 39.9 12.1 58.7 39.1 13.5 56.4 38.2 15.0 53.8 37.2 16.6 51.1 36.3 18.3 47.7 35.0 20.5 43.9 33.7 22.6 20U2S 14 20 47.0 37.0 10.9 45.5 36.2 12.2 43.6 35.3 13.6 41.7 34.4 15.0 39.6 33.4 16.5 36.8 32.1 18.4 33.7 30.7 20.4
+ 180.0 16 23 51.9 40.3 11.2 50.1 39.5 12.6 48.1 38.6 14.1 45.9 37.6 15.5 43.6 36.6 17.1 40.5 35.2 19.1 37.1 33.8 21.0 RAS- 18 25 56.4 40.6 11.6 54.4 39.7 13.0 52.2 38.8 14.5 49.9 37.8 15.9 47.4 36.7 17.6 44.0 35.4 19.7 40.1 33.8 21.7
20CT2S -2.76- 20 27 60.3 40.4 11.9 58.2 39.5 13.4 55.9 38.6 14.8 53.4 37.6 16.3 50.7 36.5 18.0 47.1 35.2 20.2 43.3 33.7 22.3 22 30 62.9 42.1 12.2 60.7 41.3 13.6 58.2 40.4 15.2 55.6 39.4 16.8 52.9 38.4 18.6 49.3 37.1 20.7 45.4 35.8 22.8
14 20 48.6 38.8 10.9 46.9 38.0 12.4 45.1 37.1 13.7 43.1 36.2 15.1 40.8 35.1 16.7 38.0 33.8 18.7 34.8 32.4 20.6 198.0 16 23 53.6 42.3 11.4 51.7 41.5 12.7 49.6 40.5 14.2 47.4 39.6 15.6 45.0 38.5 17.3 41.8 37.1 19.3 38.3 35.6 21.3 18 25 58.3 42.6 11.7 56.2 41.7 13.1 53.9 40.7 14.6 51.5 39.7 16.1 48.9 38.7 17.8 45.5 37.3 20.0 41.4 35.6 21.9 -2.97- 20 27 62.3 42.4 12.0 60.1 41.5 13.5 57.7 40.5 14.9 55.1 39.5 16.5 52.3 38.4 18.2 48.7 37.1 20.4 44.7 35.6 22.5 22 30 65.0 44.3 12.3 62.7 43.4 13.8 60.1 42.5 15.4 57.4 41.5 17.0 54.6 40.5 18.8 50.9 39.2 20.9 46.9 37.8 23.1 14 20 50.1 40.5 11.1 48.4 39.7 12.4 46.5 38.8 13.8 44.4 37.8 15.3 42.1 36.8 16.9 39.2 35.5 18.9 35.9 34.0 20.7 216.0 16 23 55.3 44.3 11.5 53.3 43.4 12.8 51.2 42.5 14.3 48.9 41.5 15.8 46.4 40.4 17.4 43.1 39.0 19.5 39.5 37.4 21.5 18 25 60.1 44.5 11.8 57.9 43.6 13.3 55.6 42.7 14.7 53.1 41.6 16.3 50.5 40.5 17.9 46.9 39.1 20.1 42.7 37.4 22.2 -3.17- 20 27 64.3 44.3 12.1 62.0 43.4 13.5 59.5 42.4 15.1 56.9 41.4 16.7 54.0 40.3 18.5 50.2 38.9 20.6 46.1 37.3 22.7 22 30 67.0 46.4 12.4 64.6 45.5 13.9 62.0 44.6 15.5 59.3 43.6 17.1 56.3 42.5 18.9 52.5 41.2 21.2 48.4 39.8 23.3
QA : Evaporator Air Flow (m3/min) SHC* : Sensible Heat Capacity (x 1000kcal/h) Given for Each WB and DB* CR : Sensible Heat Correction Factor IPT : Compressor Input Power (kW) WB : Evaporator Air Inlet Wet Bulb (°C) DB* : Evaporator Air Inlet Dry Bulb (°C) Given for Each WB NOTE: TC : Total Cooling Capacity (x 1000kcal/h) The data is based on the following conditions: Refrigerant Piping Length in One Direction: 5 Meters Horizontal.
18
SELECTION DATA Fan Performance Table
Conversion Multiplier: 1 mmAq = 9.81 Pa Air Flow External Static Pressure (mmAq)
Model (m3/min.) 3 5 7.5
RAS-4U2S 37.0 RPM 670 740 830
RAS-5U2S 50.0 RPM 830 900 960
Conversion Multiplier: 1 mmAq = 9.81 Pa
External Static Pressure (mmAq) Model Air Flow (m3/min.) 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
590 630 710 760 800 860 910 970 1000 1030 1060 1090 1120 1140 1160 118052.0 RPM BKW 0.21 0.24 0.28 0.32 0.36 0.38 0.42 0.46 0.50 0.54 0.57 0.61 0.64 0.68 0.72 0.78
670 710 770 810 880 910 960 1010 1030 1060 1090 1110 1140 1170 1190 122058.5 RPM BKW 0.25 0.29 0.34 0.37 0.41 0.46 0.50 0.53 0.58 0.62 0.65 0.70 0.74 0.78 0.82 0.86
740 790 840 900 940 980 1010 1030 1080 1110 1140 1170 1190 1210 1240 127065.0 RPM BKW 0.35 0.39 0.44 0.49 0.53 0.57 0.62 0.66 0.71 0.74 0.79 0.83 0.89 0.93 0.98 1.02
820 860 910 960 1000 1020 1050 1090 1120 1150 1180 1200 1220 1240 126071.5 RPM BKW 0.48 0.53 0.58 0.63 0.68 0.73 0.78 0.83 0.88 0.93 0.98 1.03 1.07 1.12 1.17
—
930 970 1000 1030 1060 1090 1110 1140 1170 1200 1220 1250 1280
RAS-6U2S
78.0 RPM BKW 0.66 0.71 0.77 0.82 0.88 0.93 0.99 1.04 1.09 1.15 1.20 1.26 1.31
— — —
55.2 RPM BKW
590 0.21
6500.25
710 0.28
760 0.32
8000.36
8400.39
9200.43
9700.46
10000.50
10300.54
10600.57
1090 0.61
1120 0.64
11400.68
11600.72
11800.78
62.1 RPM BKW
670 0.25
7200.30
770 0.34
800 0.38
8600.42
9100.46
9600.50
10000.54
10300.58
10600.62
10800.66
1110 0.70
1140 0.74
11700.78
11900.82
12200.86
69.0 RPM BKW
740 0.35
7900.39
840 0.44
880 0.48
9200.53
9800.57
10100.62
10300.66
10800.71
11000.75
11300.80
1160 0.84
1190 0.89
12100.93
12400.98
12701.02
75.9 RPM BKW
820 0.48
8600.53
910 0.58
960 0.63
10000.68
10200.73
10500.78
10900.83
11200.88
11500.93
11800.98
1200 1.03
1240 1.08
12601.13
12901.18
—
RAS-8U2S
82.8 RPM BKW
940 0.67
9800.72
1010 0.78
1040 0.83
10700.89
11000.94
11201.00
11501.05
11801.10
12101.16
12301.21
1260 1.27
1290 1.32
— — —
65.6 RPM BKW
540 0.08
6100.11
680 0.15
740 0.25
8000.33
8400.40
8700.57
9100.63
9400.69
9800.75
10200.81
1060 0.86
1100 0.92
11500.98
12001.04
12801.10
73.8 RPM BKW
600 0.10
6700.13
740 0.20
800 0.28
8500.36
8800.43
9200.58
9500.64
9700.70
10000.76
10600.82
1110 0.89
1160 0.97
12001.05
12601.12
13201.20
82.0 RPM BKW
720 0.12
7500.19
780 0.27
820 0.34
8600.42
9000.50
9300.59
9700.65
10000.72
10400.80
10900.89
1130 0.98
1170 1.08
12101.17
12701.26
13301.35
90.2 RPM BKW
740 0.26
7700.34
800 0.42
840 0.49
8800.57
9200.65
9600.72
10000.80
10800.98
11101.09
11401.24
1170 1.27
1200 1.31
12301.38
13301.50
—
RAS-9U2S
98.4 RPM BKW
790 0.39
8100.50
850 0.64
900 0.78
9400.87
9700.95
10001.03
10501.11
11001.20
11501.28
12001.37
1280 1.49
1320 1.61
13701.70
— —
72.0 RPM BKW
540 0.02
6100.04
680 0.11
740 0.18
8000.24
8600.31
9100.38
9700.45
10100.52
10500.58
10900.65
1130 0.72
1170 0.79
12100.86
12400.92
12800.90
81.0 RPM BKW
600 0.05
6700.13
740 0.20
790 0.28
8500.36
9000.43
9600.51
10000.59
10600.66
10800.74
11000.82
1180 0.89
1210 0.97
12401.05
12701.12
13101.20
90.0 RPM BKW
670 0.15
7300.23
790 0.32
840 0.40
9000.49
9500.57
10000.66
10400.74
10800.83
11200.91
11701.00
1200 1.08
1240 1.17
12701.25
13101.34
13401.42
99.0 RPM BKW
740 0.26
8000.35
850 0.45
900 0.54
9500.64
10000.73
10400.82
10800.92
11201.01
11701.10
12001.20
1240 1.29
1270 1.38
13101.48
13401.57
—
RAS-10U2S
108.0 RPM BKW
810 0.39
8600.50
910 0.60
960 0.70
10000.80
10500.90
10901.01
11301.11
11701.21
12001.31
12401.41
1280 1.51
1310 1.62
13501.72
— —
RPM: Fan Speed (rpm) BKW: Brake Power (kW) NOTE: When the external static pressure exceeds the shaded area an oversized fan motor or a fan pulley are required.
19
SELECTION DATA Fan Performance Table (Continued)
Conversion Multiplier: 1 mmAq = 9.81 Pa External Static Pressure (mmAq) Model Air Flow
(m3/min.) 0 4 8 12 16 20 24 28 32 36 40
88.0 RPM BKW
650 0.27
730 0.39
790 0.51
8800.64
9800.76
10800.88
11001.00
11701.13
12301.25
1270 1.37
1310 1.50
99.0 RPM BKW
700 0.31
790 0.43
860 0.58
9200.70
10100.86
10901.00
11401.13
11901.27
12401.43
1290 1.58
1320 1.69
110.0 RPM BKW
740 0.39
810 0.54
890 0.70
9600.85
10301.00
11001.16
11501.31
12201.46
12701.62
1310 1.77
1350 1.92
121.0 RPM BKW
770 0.69
840 0.84
910 0.98
9901.13
10901.27
11501.42
12201.60
12801.74
13101.88
1340 2.01
1370 2.15
RAS-13U2S
132.0 RPM BKW
810 0.85
870 1.01
980 1.18
10901.35
11701.52
1220 1.69
12801.86
13202.03
13702.20
1410 2.37
—
104.0 RPM BKW
630 0.43
730 0.55
850 0.66
930 0.78
10000.89
10501.01
11101.12
11701.24
12201.35
1270 1.49
1320 1.58
117.0 RPM BKW
710 0.52
800 0.65
880 0.78
950 0.91
10201.03
10801.16
11401.29
11801.42
12601.55
1310 1.68
1360 1.81
130.0 RPM BKW
790 0.66
890 0.81
940 0.95
1000 1.09
11001.24
11401.38
11901.52
12501.67
1290 1.81
1350 1.95
1380 2.10
143.0 RPM BKW
880 0.90
970 1.04
1040 1.28
11001.41
11601.50
12201.66
12801.82
13201.97
13702.13
1400 2.99
—
RAS-15U2S
156.0 RPM BKW
980 1.20
1060 1.36
1120 1.50
12001.65
12501.79
12901.94
13202.08
13502.34
14002.51
— —
External Static Pressure (mmAq) Model
Air Flow (m3/min.) 0 6 12 18 24 30 36 42 48 54 60
RPM 620 670 720 760 790 830 890 930 990 1040 1080 144.0
BKW 0.24 0.56 0.88 1.21 1.53 1.85 2.17 2.49 2.82 3.14 3.46
RPM 630 680 740 780 820 860 920 970 1020 1060 1100 162.0
BKW 0.29 0.64 0.99 1.34 1.69 2.04 2.39 2.74 3.09 3.44 3.79
RPM 650 690 750 820 870 920 950 1010 1050 1100 1140 180.0
BKW 0.39 0.78 1.17 1.56 1.95 2.34 2.73 3.12 3.51 3.89 4.28
RPM 670 760 830 870 920 970 1020 1060 1100 1160 1190 198.0
BKW 0.58 1.02 1.45 1.89 2.32 2.76 3.19 3.63 4.06 4.50 4.93
RPM 820 860 910 950 1000 1030 1070 1120 1170 1220 1250
RAS-20U2S
216.0 BKW 0.82 1.32 1.81 2.30 2.80 3.29 3.78 4.28 4.77 5.26 5.76
RPM: Fan Speed (rpm) BKW: Brake Power (kW) NOTE: When the external static pressure exceeds the shaded area an oversized fan motor or a fan pulley are required.
20
60
170160150100 110 1301200 140
Air Flow (m /min )3
1400 rpm
1.5kW
Internal Static Pressure
Sta
tic P
ress
ure
(mm
Aq)
109
2019
30
40
50
1200 rpm
1100 rpm
1000 rpm
900 rpm
1300 rpm
2.2kW
(MAX)
Internal Static Pressure7
: Factory Set Point(980rpm)Standard Motor Output : 2.2kW
Air Flow (m /min )
RAS-15U2S
70
80
550 69 7060 803
90
0.75kW
Sta
tic P
ress
ure
(mm
Aq)
1012
20
30
1100 rpm
1000 rpm
800 rpm900 rpm
1300 rpm
1200 rpm
(MAX)
0 70
7.610
Sta
tic P
ress
ure
(mm
Aq)
17.620
40
30
60
50
70
900 rpm800 rpm
140
Air Flow (m /min )
Internal Static Pressure
1101009080 120 1303
150
1000 rpm
1100 rpm
1200 rpm
1300 rpm1.5kW
(MAX)1400 rpm
2.2kW
Standard Motor Output : 0.75kW: Factory Set Point(885rpm)RAS-8U2S
40
RAS-6U2S
Internal Static Pressure
RAS-13U2S
Sta
tic P
ress
ure
(mm
Aq)
0 52
80
7
1012
30
20
40
: Factory Set Point(920rpm)Standard Motor Output : 2.2kW
70 80786055 65
Air Flow (m /min )3
900 rpm800 rpm
1000 rpm
90
Standard Motor Output : 0.75kW: Factory Set Point(865rpm)
0.75kW
1100 rpm
1200 rpm
(MAX)1300 rpm
1350 rpm
30
7
10
20
14.5Sta
tic P
ress
ure
(mm
Aq)
Internal Static Pressure
100
Air Flow (m /min )
800 70 903
110
1.5kW
1300 rpm
900 rpm
800 rpm
1200 rpm
1100 rpm
1000 rpm
0.75kW
(MAX)
40
RAS-10U2SStandard Motor Output : 1.5kW
: Factory Set Point(890rpm)
1350 rpm
30
7
10
20
14.5Sta
tic P
ress
ure
(mm
Aq)
Internal Static Pressure
100
Air Flow (m /min )
800 65 903
1.5kW
1300 rpm
900 rpm
800 rpm
1100 rpm
1000 rpm
(MAX)
40
RAS-9U2SStandard Motor Output : 1.5kW
: Factory Set Point(850rpm)
70
1200 rpm
Internal Static Pressure
Sta
tic P
ress
ure
(mm
Aq)
26
10
0
20
30
50
40
Air Flow (m /min)
140 1803
60
70
80
90
100
3.7kW
900 rpm
800 rpm 1000 rpm
1100 rpm
220
:Factory Set (830rpm)Stantard Motor Output: 3.7kW
1200 rpm
6
150 160 170 190 200 210
5.5kW
1300 rpm(MAX)
RAS-20U2S
0.75kW
82
RAS-5U2S
Sta
tic P
ress
ure
(mm
Aq)
Air Flow (m /min )
Internal Static Pressure
34320 30
910
4238 4440363
: Factory Set Point(740rpm)Standard Motor Output : 0.27kW
30
20
RAS-4U2S40
: Factory Set Point(900rpm)Standard Motor Output : 0.43kW
1415
25
35
37
Hi
Me
Lo
Sta
tic P
ress
ure
(mm
Aq)
Air Flow (m /min )
Internal Static Pressure
47440 41
910
5953 6256503
30
20
40
1415
25
35
Hi
Me
Lo
SELECTION DATA
Fan Performance Curve
NOTE: External static pressure are available by the following equation (External Static Pressure)= (Static Pressure) - (Internal Static Pressure)
21
SELECTION DATA Fan Speed Adjustment
For Models RAS-4U2S and RAS-5U2S
Fan Speed Adjustment
For Models RAS-6U2S through RAS-15U2S
Motor Pulley Adjustment Regulation Space X of Motor Pulley (mm) Factory Set Point Model 0 1 2 3 4 5 6 7 X RPM PD* rpm/turn**
RPM 940 915 890 865 835 810 785 760 RAS-6U2S PD* 112 109 106 103 99 96 93 90
3 865 103 45
RPM 1100 1070 1040 1010 975 950 915 885 RAS-8U2S PD* 112 109 106 103 99 96 93 90
7 885 90 47
RPM 1040 1010 980 950 920 880 850 820RAS-9U2S PD* 105 102 99 96 93 89 86 83
6 850 86 47
RPM 1110 1080 1050 1020 980 950 920 890RAS-10U2S PD* 112 109 106 103 99 96 93 90
7 890 90 47
RPM 1110 1080 1050 1020 980 950 920 890RAS-13U2S PD* 112 109 106 103 99 96 93 90
6 920 93 45
RPM 1185 1155 1125 1085 1055 1025 980 965RAS-15U2S PD* 120 117 114 110 107 104 100 98
6 980 100 45
Motor Pulley Dimensions Motor Pulley Dimensions (mm) Model b c d e f g
RAS-6U2S 121.5 55 M48 19 6 21.5RAS-8U2S 121.5 55 M48 19 6 21.5RAS-9U2S 137 62.6 M48 24 8 27 RAS-10U2S 121.5 55 M48 24 8 27 RAS-13U2S 121.5 55 M48 24 8 27 RAS-15U2S 129 65 M48 24 8 27
Fan Pulley Dimensions Fan Pulley Dimensions (mm)Model
a b PD* RAS-6U2S 179 20 170 RAS-8U2S 153 20 144 RAS-9U2S 164 25 155 RAS-10U2S 153 25 144 RAS-13U2S 153 25 144 RAS-15U2S 153 25 144
PRM : Fan Speed (rpm) * : Pitch Diameter of Pulley (mm) ** : Fan Speed Change per One Turn of Movable Pulley (rpm/turn)
Fan Speed (rpm) Factory Set PointModels Hi Me Lo rpm RAS-4U2S 830 740 670 740 RAS-5U2S 960 900 830 900
22
SELECTION DATA Fan Speed Adjustment (Continued)
V-Belt Model Form Length (mm) Number of
V-Belt RAS-6U2S A 787 1 RAS-8U2S A 737 1 RAS-9U2S A 711 1 RAS-10U2S A 711 1 RAS-13U2S A 737 1 RAS-15U2S A 737 1
For Model RAS-20U2S
Motor Pulley Adjustment Regulation Space X of Motor Pulley (mm) Factory Set Point
Model 0 1 2 3 4 5 6 7 8 X RPM PD* rpm/turn**
RPM 1000 980 960 935 910 890 870 850 830RAS-20U2S
PD* 150 147 144 140.5 137 134 131 128 1258 830 125 32
Motor Pulley Dimensions
Pulley Dimensions (mm) Model a b c RAS-20U2S 31 28 8
Fan Pulley Dimensions Pulley Dimensions (mm) Model
a b c d PD* RAS-20U2S 226 196 35 38.5 215
RPM : Fan Speed (rpm) * : Pitch Diameter of Pulley (mm) ** : Fan Speed Change per One Turn of Movable Pulley (rpm/turn) V-Belt
Model Form Length (mm) Number of V-Belt
RAS-20U2S B 1118 2
23
ELECTRICAL DATA
Electrical Data Cooling Unit
Unit Main Power Applicable Voltage Evaporator Fan Motor Model VOL Hz Maximum Minimum RNC IPT
RAS-4U2S 380/415 50 456 342 0.8/0.8 0.37 RAS-5U2S 380/415 50 456 342 1.1/1.1 0.61 RAS-6U2S 380/415 50 456 342 1.2/1.2 0.66 RAS-8U2S 380/415 50 456 342 1.2/1.2 0.66 RAS-9U2S 380/415 50 456 342 1.3/1.3 0.68 RAS-10U2S 380/415 50 456 342 1.3/1.3 0.68 RAS-13U2S 380/415 50 456 342 2.2/2.2 1.19 RAS-15U2S 380/415 50 456 342 3.1/3.2 1.6 RAS-20U2S 380/415 50 456 342 6.2/6.3 3.4/3.6
VOL : Unit Power Supply Rated (Plated) Voltage (V) Hz : Frequency (Hz) RNC : Running Current (A) IPT : Input (kW) NOTES: 1.These data are based on the factory set fan speeds with the factory-supplied fan motor at the nominal airflow. 2.These data are based on the standard conditions. 3.Only RAS-4U2S and RAS-5U2S equipped with single-phase evaporator fan motor, others are equipped with three-phase
evaporator fan motor.
Condensing Unit Unit Main Power Applicable Voltage Compressor Motor
(Three-Phase) Condenser Fan Motor
(Three-Phase) Condensing Unit (Cooling Unit) VOL Hz Maximum Minimum STC RNC IPT RNC IPT RAS-4CT2S (RAS-4U2S)
380/415 50 456 342 58 6.1/5.8 3.6 0.7/0.7 0.23
RAS-5CT2S (RAS-5U2S)
380/415 50 456 342 67 7.8/7.7 4.5 0.85/0.85 0.45
RAS-6CT2S (RAS-6U2S)
380/415 50 456 342 60 8.7/8.4 5.2 0.51/0.48 0.28
RAS-8CT2S (RAS-8U2S)
380/415 50 456 342 100/108 12.2/12.3 7.0 0.51/0.48 0.28
RAS-9CT2S (RAS-9U2S)
380/415 50 456 342 109/118 12.5/12.8 7.5 0.95/0.92 0.48
RAS-10CT2S (RAS-10U2S)
380/415 50 456 342 123/134 15.0/15.4 8.55 0.95/0.92 0.4
10.9/11.7 6.1 1.47/1.55 0.78/0.84 RAS-13CT2S (RAS-13U2S)
380/415 50 456 342 100/1087.2/7.4 4.1 0.95/0.99 0.42/0.44
13.5/13.8 7.9 1.3/1.3 0.7/0.7 RAS-15CT2S (RAS-15U2S)
380/415 50 456 342 123/1347.5/7.6 4.5 0.9/1.0 0.53/0.53
RAS-20CT2S (RAS-20U2S)
380/415 50 456 342 123/134 14.1x2/14.2x2 8.1x2 1.3x2 0.7x2
VOL : Unit Power Supply Rated (Plated) Voltage (V) Hz : Frequency (Hz) STC: Starting Current (A) RNC: Running Current (A) IPT : Input (kW)
NOTES: 1.These data are based on the following conditions.
Evaporator Air Inlet Temperature 27°C DB, 19°C WB. Condenser Air Inlet Temperature 35°C DB
2.The maximum current of the compressors can be estimated as follows. Maximum Running Current: RNC x Max. IPT */IPT Max. IPT*: Compressor Power Input from the Performance Table at the Expected Maximum Condition IPT, RNC : Compressor data from the above table
3.The data in the compressor motor column shall indicate the respective values of the refrigeration cycles.
24
SOUND DATA Sound Data
Cooling Unit
Frequency Band (Hz)
Model Sound Level 45 ∫ 90
90 ∫
180
180 ∫
355
355 ∫
710
710 ∫
1,400
1,400∫
2,800
2,800 ∫
5,600
5,600 ∫
11,200 Over-all
RAS-4U2S SPL-A SPL-C PWL
34.7 61.3 69.0
37.7 53.3 61.0
43.7 53.1 61.0
44.7 48.1 56.0
44.7 44.9 53.0
42.7 41.1 49.0
37.7 36.1 44.0
29.7 27.8 36.0
51 63 71
RAS-5U2S SPL-A SPL-C PWL
37.0 61.6 71.0
40.0 53.6 63.0
49.0 56.4 65.0
50.0 51.4 60.0
51.0 49.2 58.0
46.0 42.4 51.0
44.0 40.4 49.0
38.0 34.1 43.0
56 64 73
RAS-6U2S SPL-A SPL-C PWL
37.3 63.9 72.0
48.8 64.4 72.0
49.8 59.2 67.0
54.8 58.2 66.0
57.3 57.5 66.0
53.3 51.7 60.0
46.3 44.7 53.0
37.3 35.4 43.0
61.1 68.8 77.0
RAS-8U2S SPL-A SPL-C PWL
42.4 67.7 75.7
46.4 62.3 70.3
51.4 60.0 68.0
53.1 56.3 64.3
56.4 56.4 64.4
54.4 53.0 61.0
52.4 50.6 58.6
43.9 42.0 50.0
61.2 69.9 77.9
RAS-9U2S SPL-A SPL-C PWL
40.9 66.2 74.2
50.9 66.8 74.8
52.4 61.0 69.0
53.9 57.1 65.1
55.4 55.4 63.4
53.4 52.0 60.0
50.9 49.1 57.1
42.9 41.0 49.0
61.1 70.5 78.5
RAS-10U2S SPL-A SPL-C PWL
40.9 66.2 74.2
50.9 66.8 74.8
52.4 61.0 69.0
53.9 57.1 65.1
55.4 55.4 63.4
53.4 52.0 60.0
50.9 49.1 57.1
42.9 41.0 49.0
61.1 70.5 78.5
RAS-13U2S SPL-A SPL-C PWL
42.9 68.4 76.4
49.9 65.8 73.8
52.4 61.0 69.0
53.4 56.6 64.6
55.9 55.9 63.9
53.4 52.0 60.0
51.4 49.6 57.6
43.1 41.2 49.2
61.0 71.2 79.2
RAS-15U2S SPL-A SPL-C PWL
48.9 74.2 82.2
55.4 71.3 79.3
53.9 62.5 70.5
54.4 57.6 65.6
57.4 57.4 65.4
55.9 54.5 62.5
55.9 54.1 62.1
47.4 45.5 53.5
63.7 76.4 84.4
RAS-20U2S SPL-A SPL-C PWL
53.0 78.3 86.3
58.0 73.9 81.9
61.0 69.6 77.6
68.7 71.9 79.9
69.5 69.5 77.5
67.5 66.1 74.1
66.5 64.7 72.7
54.5 52.6 60.6
74.7 81.2 89.2
SPL-A: A Scale Sound Pressure Level (dB) SPL-C: C Scale Sound Pressure Level (dB) PWL : Sound Power Level (dB) NOTES: 1.The measuring point is 1.0 meter from the side panel of the machine surface and 1.0 meter from the floor level. 2.The units are operating under the standard working conditions. 3.The above data was measured in an anechoic chamber so that reflection sound should be taken into consideration.
25
SOUND DATA
Sound Data (Continued) Condensing Unit
Frequency Band (Hz)
Model Sound Level 45 ∫ 90
90 ∫
180
180 ∫
355
355 ∫
710
710 ∫
1,400
1,400∫
2,800
2,800 ∫
5,600
5,600 ∫
11,200 Over-all
RAS-4CT2S SPL-A SPL-C PWL
40.5 67.1 75.1
47.6 63.5 71.7
50.7 59.3 67.5
56.8 60.0 68.2
54.8 54.8 63.0
50.5 49.1 57.3
45.4 43.6 51.8
40.3 38.4 46.6
60.5 69.8 77.9
RAS-5CT2S SPL-A SPL-C PWL
41.4 65.1 72.8
53.5 66.5 74.2
47.6 53.3 61.0
59.7 60.0 67.7
61.7 58.8 66.5
53.4 49.1 56.8
51.3 46.6 54.3
47.2 42.4 50.1
64.9 69.9 77.6
RAS-6CT2S SPL-A SPL-C PWL
39.4 66.0 74.0
49.5 65.4 73.4
51.6 60.2 68.2
56.2 59.4 67.4
59.2 59.2 67.2
54.9 53.5 61.5
46.8 45.0 53.0
38.7 36.8 44.8
62.7 70.2 78.2
RAS-8CT2S SPL-A SPL-C PWL
39.2 65.8 74.3
50.8 66.7 75.2
51.9 60.5 69.0
57.0 60.2 68.7
59.5 59.5 68.0
55.2 53.8 62.3
48.1 46.3 54.8
39.0 37.1 45.6
63.2 70.7 79.2
RAS-9CT2S SPL-A SPL-C PWL
40.6 67.2 75.2
50.7 66.6 74.6
52.8 61.4 69.4
57.4 60.6 68.6
60.4 60.4 68.4
56.1 54.7 62.7
48.0 46.2 54.2
39.9 38.0 46.0
63.9 71.4 79.4
RAS-10CT2S SPL-A SPL-C PWL
40.6 67.2 75.2
50.7 66.6 74.6
52.8 61.4 69.4
57.4 60.6 68.6
60.4 60.4 68.4
56.1 54.7 62.7
48.0 46.2 54.2
39.9 38.0 46.0
63.9 71.4 79.4
RAS-13CT2S SPL-A SPL-C PWL
45.0 71.6 80.0
53.3 68.9 77.0
56.4 65.8 74.0
58.6 62.0 70.0
60.8 61.0 69.0
52.9 51.3 59.0
45.5 43.9 52.0
39.6 37.7 46.0
64.5 74.6 83.0
RAS-15CT2S SPL-A SPL-C PWL
45.5 72.1 80.0
53.5 69.1 77.0
56.8 66.2 74.0
58.4 61.8 70.0
61.5 61.7 70.0
52.9 51.3 59.0
46.1 44.5 53.0
39.4 37.5 46.0
64.9 75.0 83.0
RAS-20CT2S SPL-A SPL-C PWL
46.0 72.6 81.0
54.0 69.6 78.0
57.3 66.7 75.0
58.9 62.3 70.0
62.0 62.2 70.0
53.4 51.8 60.0
46.6 45.0 53.0
39.9 38.0 46.0
65.4 75.5 84.0
SPL-A: A Scale Sound Pressure Level (dB) SPL-C: C Scale Sound Pressure Level (dB) PWL : Sound Power Level (dB) NOTES: 1.Measuring Point 1.0 Meter from the Center of the Machine Surface 1.5 Meter from the Floor Level 2.The units are operating under the standard working conditions. 3.The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration.
26
ACCESSORY and COMPONENT DATA
Accessory Availability
Optional Accessories Unit Cooling Unit Condensing Unit
Standard (Factory-Supplied) Accessory
Liquid Line Filter-Dryer
Yes (RAS-13U2S~RAS-20U2S)
─
Optional Accessory Filter Filter Box Sight Glass Solenoid Valve
Yes Yes ─ ─
─ ─
Yes Yes
Component Detailed Data Compressor
Compressor Model 400DH 500DH 600DH 750EL 900EL 1000EL
Compressor Type Herm. Scroll Herm. Scroll Herm. Scroll Herm. Scroll Herm. Scroll Herm. Scroll
Revolution rpm 2,880 2,880 2,880 2,880 2,880 2,880
Displacement m3/h 11.09 13.82 15.55 22.12 24.88 27.65
Air-Tight Pressure
Discharge
kg/cm2 G kPa
30
2,940
30
2,940
30
2,940
30
2,940
30
2,940
30
2,940
Suction kg/cm2 G
kPa 15
1,470 15
1,470 15
1,470 15
1,470 15
1,470 15
1,470
Motor Type Special Squirrel-Cage, Three-Phase Motor
Starting Method Direct-On-Line Starting
Poles 2 2 2 2 2 2
Insulation Class E E E E E E
Oil Type SUNISO 4GDI-HT
Charge Liters 1.5 1.5 1.5 2.5 2.5 2.5
27
COMPONENT DATA
Component Detailed Data (Continued)
Evaporator and Evaporator Fan Model RAS-4U2S RAS-5U2S RAS-6U2S RAS-8U2S RAS-9U2S RAS-10U2S RAS-13U2S RAS-15U2S RAS-20U2S
Evaporator Multi-Pass Cross-Finned Tube Tube Material Copper
Outer Diameter Thickness Rows Number of Tubes/Evaporator
mm mm
9.53 0.34
3 48
9.53 0.34
3 48
9.53 0.34
3 44
9.53 0.34
3 42
9.53 0.34
3 72
9.53 0.34
3 72
9.53 0.34
3 74
9.53 0.34
3 74
9.53 0.34
3 114
Fin Material Aluminum Thickness Pitch
mm mm
0.11 2.0
0.11 2.0
0.11 2.0
0.11 2.0
0.11 2.0
0.11 2.0
0.11 2.0
0.11 2.0
0.11 2.0
Number of Evaporators/Unit Total Face Area
m2
1 0.29
1 0.29
1 0.37
1 0.45
1 0.75
1 0.75
1 0.73
1 0.81
1 1.25
Maximum Applicable Pressure kg/cm2 G
kPa 13
1,270 13
1,270 13
1,27013
1,270 13
1,27013
1,270 13
1,270 13
1,270 13
1,270Evaporator Fan Multi-Blade Centrifugal Fan (Double Suction)
Number/Unit Outer Diameter Total Nominal Air Flow
mm m3/min
m3/s L/s
1 264 37
0.62 620
1 264 50
0.83 830
1 264 65
1.08 1,080
1 264 69
1.15 1,150
2 264 82
1.37 1,370
2 264 90
1.50 1,500
2 264 110 1.83
1,830
2 264 130 2.17
2,170
1 385 180 3.00
3,000Evaporator Fan Motor
Starting Method
Drip-Proof Type Enclosure Direct-On-Line Starting
Nominal Output kW 0.35 0.55 0.75 0.75 1.5 1.5 2.2 2.2 3.7 Poles Number/Unit Insulation Class
4 1 B
4 1 B
4 1 B
4 1 B
4 1 B
4 1 B
4 1 B
4 1 B
4 1 B
Condenser and Condenser Fan
Model RAS-4CT2S RAS-5CT2S RAS-6CT2S RAS-8CT2S RAS-9CT2S RAS-10CT2S RAS-13CT2S RAS-15CT2S RAS-20CT2S
Condenser Coil Multi-Pass Cross-Finned Tube Tube Material Copper
Outer Diameter Thickness Rows Number of Tubes/Cond.
mm mm
9.53 0.34
2 58
9.53 0.34
2 58
9.53 0.34
2 56
9.53 0.34
2 62
9.53 0.34
3 98
9.53 0.34
3 98
9.53 0.34 3/2
78/52
9.53 0.34 3/3
78/78
9.53 0.34 3/3
108/108Fin Material Aluminum
Thickness Pitch
mm mm
0.11 2.0
0.11 2.0
0.11 2.0
0.11 2.0
0.11 2.0
0.11 2.0
0.11 2.0
0.11 2.0
0.11 2.0
Maximum Operating Pressure kg/cm2G
kPa 30
2,940 30
2,940 30
2,94030
2,940 30
2,94030
2,940 30
2,940 30
2,940 30
2,940Number of Condensers/Unit Total Face Area
m2
1 1.05
1 1.16
1 1.24
1 1.42
1 1.70
1 1.70
2 2.24
2 2.24
2 2.37
Condenser Fan Direct driven Propeller Fan Number/Unit Outer Diameter
mm
1 610
1 610
1 610
1 610
1 710
1 710
2 710/610
2 710/610
2 710
Revolution rpm 870 870 870 870 870 770 810 810 810 Nominal Air Flow m3/min.
m3/s L/s
120 2.0
2,000
120 2.0
2,000
135 2.25
2,250
135 2.25
2,250
160 2.67
2,670
160 2.67
2,670
315 5.25
5,250
330 5.5
5,500
320 5.33
5,330Condenser Fan Motor
Starting Method
Drip-Proof Type Enclosure Direct-On-Line Starting
Nominal Output kW 0.15 0.3 0.25 0.25 0.4 0.4 0.3 0.3 0.3 Poles Number/Unit Insulation Class
6 1 H
6 1 H
6 1 H
6 1 H
6 1 H
6 1 H
6 2 H
6 2 H
6 2 H
28
CONTROL SYSTEM Refrigerant Control
Refrigeration Cycle
Condensing Unit Models RAS-13CT2S through RAS-20CT2S are composed of two refrigeration cycles. In addition to the basic condensing unit components (compressor and air-cooled condenser), the following components are equipped in each circuit.
Stop Valves for Gas Line and Liquid Line – These stop valves are equipped at the unit piping connections, and enhance the evacuation and charging functions.
Cooling Unit Refrigerant Flow Control – Thermal expansion valves are equipped for models RAS-13U2S, RAS-15U2S and RAS-20U2S.
Dryer – A filter-dryer is shipped for installation at the site. (for models RAS-13U2S, RAS-15U2S and RAS-20U2S)
Electrical Operation Control
A field-supplied main power switch supplies to the unit. When the room thermostat is set at “FAN ON” position, the indoor fan is started. When the room thermostat is set at “FAN AUTO” and “COOL ON” position, all electrical and protective devices are satisfied, the thermostat in the room thermostat controls the compressor operation (refer to “Operational Sequence Chart”).
Capacity Control – The field supplied Room Thermostat for the dual-circuited models starts and stops compressor operation in each circuit, responding to the room temperature with the room thermostat elements. This system enables full load, 60% or 50% load and no load (ceasing both compressor) operations. Function of Safety Devices Automatic Restarting System (Standard Sequence) – The timer relay for compressor connected in the compressor control circuit delays the compressor restarting period for approximately three (3) minutes after the thermostat calls for the cooling operation or automatic resetting of the protection devices, thereby preventing a harmful compressor cycling operation.
For Models: RAS-4U2S+RAS-4CT2S through RAS-10U2S+RAS-10CT2S
Operational Sequence Chart : ON : OFF
*Main Power Switch OFF ON
FAN AUTO ON AUTO
COOL OFF ON Operation Equipments *Room Thermostat
TH ─ ─ ─
Indoor Fan Motor MIF
Outdoor Fan Motor MOF
Compressor MC Electric Components
Safety Devices Close Close Close Close Close Close Open
NOTES: 1. * :Field Supplied.
After 3 min.
29
CONTROL SYSTEM
For Models: RAS-13U2S+RAS-13CT2S through RAS-20U2S+RAS-20CT2S
Operational Sequence Chart : ON : OFF
*Main Power Switch OFF ON
FAN AUTO ON AUTO
COOL OFF ON
(Stage) COOLING CALL
─ 1st … ON ON ON ON OFF ON
Operation Equipment *Room Thermostat
TH
2nd … ON ON ON OFF OFF ON
Indoor Fan Motor MIF
Outdoor Fan Motor 1 MOF1
Outdoor Fan Motor 2 MOF2
Compressor 1 MC1
Compressor 2 MC2
**Crankcase Heater CH **Crankcase Heater CH
Electric Components
Safety Devices Close Close Close Close Close Close Close Close Open NOTES: 1. * :Field Supplied.
2. ** :Crankcase Heater are provided for model RAS-13CT2S No.2 cycle, RAS-15CT2S No.1 cycle and RAS-20CT2S.
After 3 min.
After 3.5 min.
30
CONTROL SYSTEM
For M
odel
s R
AS
-4U
2S+R
AS-4
CT2
S a
nd R
AS
-5U
2S+R
AS
-5C
T2S
31
CONTROL SYSTEM
For M
odel
s R
AS
-6U
2S+R
AS-6
CT2
S th
roug
h R
AS-
10U
2S+R
AS
-10C
T2S
32
CONTROL SYSTEM
For M
odel
RA
S-1
3U2S
+RA
S-1
3CT2
S
33
CONTROL SYSTEM
For M
odel
RA
S-1
5U2S
+RA
S-1
5CT2
S
34
CONTROL SYSTEM
For M
odel
RA
S-2
0U2S
+RA
S-2
0CT2
S
35
CONTROL SYSTEM
Protection and Safety ControlCompressor Protection All units are equipped with the following compressor protection system, in order to provide a perfect guarding function for the compressor.
High Pressure Switches – Leading the pressures from the compressor discharge lines, this switch cut out the compressor operation when the discharge pressure exceeds the setting pressure.
Overcurrent Transformer – This sensor stop the compressor operation when the current exceeds the setting.
Internal Thermostat for compressor – Embedded in the compressor motor winding, this thermostat cuts out the compressor operation when the compressor winding temperature exceeds the setting.
Reverse Phase Protection – The reverse phase protection which is a built-in function of PCB will make the compressor not start when the power source is incorrectly connected.
Compressor Cycling Protection Timer – This timer which is a built-in function of PCB provides the above combination with the most effective functions by delaying the compressor restarting period (refer to “Operational Sequence Chart”)
Other Protection
The fan motor is protected by the following device:
Overcurrent Relay for Evaporator Fan Motor – This manual reset type thermal overcurrent relay for the evaporator fan motor interlocks system operation.
Internal Thermostat for Condenser Fan Motor – Embedded in the fan motor winding, this internal thermostat cuts out the operation of the fan motor when winding temperature exceeds the setting.
Internal Thermostat for Evaporator Fan Motor – Embedded in the fan motor winding, this internal thermostat cuts out the operation of the fan motor when winding temperature exceeds the setting. (RAS-4U2S and RAS-5U2S only)
36
CONTROL SYSTEM
Safety and Control Device Settings Cooling Unit
Model RAS-4U2S RAS-5U2S RAS-6U2S RAS-8U2S RAS-9U2S RAS-10U2S Manual Reset, Adjustable For Evaporator Fan Motor
Overcurrent Relay A 3.3 4.4 2.1 2.1 4.0 4.0
Condensing Unit
Model RAS-4CT2S RAS-5CT2S RAS-6CT2S RAS-8CT2S RAS-9CT2S RAS-10CT2S RAS-13CT2S RAS-15CT2S RAS-20CT2S
For Compressor
400DH 500DH 600DH 750EL 900EL 1000EL 750EL/
500DH
1000EL/
600DH
1000EL/
1000EL
Automatic Reset, Non-Adjustable
kg/cm2G 30 30 30 30 30 30 30 30 30
kPa 2,940 2,940 2,940 2,940 2,940 2,940 2,940 2,940 2,940
kg/cm2G 24 24 24 24 24 24 24 24 24
High Pressure Switch
Cut-Out
Cut-In
kPa 2,350 2,350 2,350 2,350 2,350 2,350 2,350 2,350 2,350
Automatic Reset, Non-Adjustable
Overcurrent Transformer
Cut-Out A 13.2 16.8 19.8 24.2 28.5 31.5 24.2/16.8 31.5/19.8 31.5/31.5
Automatic Reset, Non-Adjustable
°C 135 135 135 135 135 135 135 135 135
Internal Thermostat
Cut-Out
Cut-In °C 113 113 113 113 113 113 113 113 113
Non-Adjustable Timer
min 3 3 3 3 3 3 3/3.5 3/3.5 3/3.5
Crankcase Heater W ─ ─ ─ ─ ─ ─ ─/40 60/─ 60/60
Manual Reset, Adjustable For Evaporator Fan Motor
Overcurrent Relay A ─ ─ ─ ─ ─ ─ 5.1 5.1 8.0
Automatic Reset, Non-Adjustable
Internal Thermostat
Cut-Out
Cut-In
°C
°C
130
100
130
100
─
─
─
─
─
─
─
─
─
─
─
─
─
─
Automatic Reset, Non-Adjustable
°C 160 160 160 160 160 160 160 160 160
For Condenser Fan Motor
Internal Thermostat
Cut-Out
Cut-In °C 130 130 130 130 130 130 130 130 130
For Control Circuit Fuse
Capacity
A
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
Automatic Reset, Non-Adjustable
kg/cm2G
kPa
─
─
─
─
─
─
─
─
─
─
─
─
24
2,350
24
2,350
24
2,350
For Condensing
Pressure Control Valve
Open Starting Pressure
Full Open Pressure
kg/cm2G
kPa
─
─
─
─
─
─
─
─
─
─
─
─
27
2,650
27
2,650
27
2,650
37
INSTALLATION DATA Maximum Foundation Gradient Foundation Provisions Cooling Units
Dimensions A B Model
deg. mm deg. mmRAS-4U2S 0.6 7 0.6 9 RAS-5U2S 0.6 7 0.6 9 RAS-6U2S 0.6 7 0.6 11 RAS-8U2S 0.6 7 0.6 13 RAS-9U2S 0.6 11 0.6 15 RAS-10U2S 0.6 11 0.6 15
Dimensions A B Model
deg. mm deg. mmRAS-13U2S 0.7 12 0.6 15 RAS-15U2S 0.7 12 0.6 15 RAS-20U2S 0.7 10 0.6 16
Condensing Units
Dimensions A B Model
deg. mm deg. mmRAS-4CT2S 1.0 14 1.0 15 RAS-5CT2S 1.0 14 1.0 15 RAS-6CT2S 1.0 14 1.0 15 RAS-8CT2S 1.0 14 1.0 15 RAS-9CT2S 1.0 17 1.0 18 RAS-10CT2S 1.0 17 1.0 18
Dimensions A B Model
deg. mm deg. mmRAS-13CT2S 1.0 32 1.0 17 RAS-15CT2S 1.0 32 1.0 17 RAS-20CT2S 1.0 35 1.0 17
38
INSTALLATION DATA Installation Dimensions Foundation Provisions Cooling Units
Dimensions (mm) Model
A RAS-4U2S 940 RAS-5U2S 940 RAS-6U2S 1,130 RAS-8U2S 1,330
RAS-4U2S through RAS-8U2S
RAS-9U2S and RAS-10U2S RAS-13U2S and RAS-15U2S
RAS-20U2S
39
INSTALLATION DATA
Foundation Provisions (Continued) Condensing Units
Dimensions (mm) Model
A B RAS-4CT2S 660 895 RAS-5CT2S 660 895 RAS-6CT2S 660 895 RAS-8CT2S 660 895 RAS-9CT2S 863 1,053 RAS-10CT2S 863 1,053
RAS-4CT2S through RAS-10CT2S
Dimensions (mm) Model
A B RAS-13CT2S 440 1,825 RAS-15CT2S 440 1,825 RAS-20CT2S 457 2,005
RAS-13CT2S through RAS-20CT2S
40
Longer than "L"
Longer than "1/2L"Downward Pitch
Horizontal or Pitched Down
Water Seal Trap
Condensate Drain ConnectionCooling Unit
Auxiliary Drain Pan(Field-Supplied)
Cooling Unit
To the Atmosphere
INSTALLATION DATA Ducting Provisions
Connections Pre-drilled duct flanges for return and supply air ducting are equipped at the factory for these units.
Duct Arrangement Model RAS-20U2S is composed of a fan compartment and a coil compartment. The factory standard horizontal flow air can be changed as explained in the figure on page 2. .
Field Piping Provisions for Condensate Drain
A female piping thread screw connection is provided. Dimension “L” in the figure should be sufficiently longer than the negative fan pressure at the drain connection
(50 mm to 100mm depending on the return air duct design).
Condensate Drain Connection NOTE: When the relative humidity of inlet air or ambient air exceeds 80%, apply an (field-supplied) auxiliary drain pan beneath the cooling unit shown in the figure.
Field Piping Provisions for Refrigerant Piping Piping Arrangement These units are pre-piped at the factory: the required field piping is connection piping between the cooling unit and the condensing unit. To ensure satisfactory operation, the following piping arrangements must be provided.
Loops and Traps – Liquid loops or oil traps must be provided according to the mutual locations of the condensing unit and the cooling unit.
Filter-Dryer – A factory-supplied filter-dryer should be provided as shown in the figure for each refrigeration cycle.(RAS-13U2S, RAS-15U2S and RAS-20U2S only)
Sight Glass – A field-supplied liquid line sight glass must be assembled and mounted in the field, as shown in the figure for each refrigeration cycle.
Solenoid Valve – A field-supplied solenoid valve for each cycle must be equipped immediately up-stream of the expansion valve of the cooling unit, when the connection piping length exceeds the following limits. Refer to the typical wiring diagram for the solenoid valve control wiring.
41
Cooling Unit
Filter-Dryer
*Sight Glass U-Trap
Liquid Loop
*Solenoid Valve
Oil Trap
Filter-Dryer*Solenoid Valve
*Sight Glass
Cooling Unit
(At Each 10 Meters)Oil Trap
Liquid Loop
Condensing Unit
INSTALLATION DATA Field Piping Provisions for Refrigerant Piping (Continued)
* :Field-Supplied :Liquid Refrigerant Pipe :Gas Refrigerant Pipe
A: Condensing Unit Below B: Condensing Unit Above
NOTES: 1.These piping arrangements should be performed for the both refrigeration cycles of the dual-circuited models. 2.Do not connect the dual circuited models with a single-circuited cooling unit.
Field Piping
Refrigerant Piping Limitation Maximum Lift (m)
Model Refrigerant
Cycle (Compressor Model) A B
Maximum Equivalent Piping Length - One Way - (m)
RAS-4U2S + RAS-4CT2S 400DH 15 25 *5/**30 RAS-5U2S + RAS-5CT2S 500DH 15 25 *5/**30 RAS-6U2S + RAS-6CT2S 600DH 15 25 *5/**30 RAS-8U2S + RAS-8CT2S 750 EL 15 25 *5/**30 RAS-9U2S + RAS-9CT2S 900 EL 15 25 *5/**30 RAS-10U2S + RAS-10CT2S 1000 EL 15 25 *5/**30
No. 1: 750EL 15 25 *6/**30 RAS-13U2S + RAS-13CT2S
No. 2: 500DH 15 25 *6/**30 No. 1: 1000EL 15 25 *6/**30
RAS-15U2S + RAS-15CT2S No. 2: 600DH 15 25 *6/**30 No. 1: 1000EL 15 25 *6/**30/***60
RAS-20U2S + RAS-20CT2S No. 2: 1000EL 15 25 *6/**30/***60
A: The condensing unit is installed below the cooling unit. B: The condensing unit is installed above the cooling unit. * : Maximum Length without Solenoid Valve Control. ** : Maximum Length with Solenoid Valve Shut-Off Control. *** : Maximum Length with Pump-Down Control.
Refrigerant Piping Size and Refrigerant Charging Data Charge correct quantity of refrigerant in accordance with these two following tables “Refrigerant of Holding Charge” and “Pipe size and Charging Data”. The condensing units are factory-charged with a correct quantity of the factory testing. The tolerance of the charging quantity should be within 0.1kg.
Refrigerant of Holding Charge Cooling Unit Condensing Unit
Model Charge (kg) Model Charge (kg) RAS-4U2S 0 RAS-4CT2S 2.0 RAS-5U2S 0 RAS-5CT2S 2.0 RAS-6U2S 0 RAS-6CT2S 2.0 RAS-8U2S 0 RAS-8CT2S 2.0 RAS-9U2S 0 RAS-9CT2S 3.0 RAS-10U2S 0 RAS-10CT2S 3.0 RAS-13U2S 0 RAS-13CT2S 1.0X2 RAS-15U2S 0 RAS-15CT2S 1.0X2 RAS-20U2S 0 RAS-20CT2S 3.0X2
42
INSTALLATION DATA Piping Size and Charging Data
Equivalent Piping Length (One Way for Each Cycle) -(m)- Model Refrigerant Cycle (Compressor Model) 5 10 15 20 25 30 40 50 60
L ODxT PD
12.7×0.9 0.08(7.8)
12.7×0.90.15(14.7)
12.7×0.90.22(21.6)
15.88×1.10.09(8.8)
15.88×1.10.12(11.8)
15.88×1.10.14(13.7)
─ ─
─ ─
─ ─
G ODxT PD
19.05×1.1 0.13(12.7)
19.05×1.10.26(25.5)
22.2×1.20.18(17.7)
22.2×1.20.24(23.5)
28.57×1.30.08(7.8)
28.57×1.30.09(8.8)
─ ─
─ ─
─ ─
*Refrigerant Charge (kg) 3.2 3.5 3.8 4.0 4.3 4.6 ─ ─ ─
RAS-4U2S +
RAS-4CT2S 400DH
**Additional Oil Charge(l) ─ ─ ─ ─ 0.03 0.07 ─ ─ ─
L ODxT PD
12.7×0.9 0.08(7.8)
12.7×0.90.15(14.7)
12.7×0.90.22(21.6)
15.88×1.10.09(8.8)
15.88×1.10.12(11.8)
15.88×1.10.14(13.7)
─ ─
─ ─
─ ─
G ODxT PD
19.05×1.1 0.13(12.7)
19.05×1.10.26(25.5)
22.2×1.20.18(17.7)
22.2×1.20.24(23.5)
28.57×1.30.08(7.8)
28.57×1.30.09(8.8)
─ ─
─ ─
─ ─
*Refrigerant Charge (kg) 4.2 4.9 5.6 6.2 6.9 7.6 ─ ─ ─
RAS-5U2S +
RAS-5CT2S 500DH
**Additional Oil Charge(l) ─ ─ ─ ─ 0.08 0.15 ─ ─ ─
L ODxT PD
12.7×0.9 0.08(7.8)
12.7×0.90.15(14.7)
12.7×0.90.22(21.6)
15.88×1.10.09(8.8)
15.88×1.10.12(11.8)
15.88×1.10.14(13.7)
─ ─
─ ─
─ ─
G ODxT PD
19.05×1.1 0.13(12.7)
19.05×1.10.26(25.5)
22.2×1.20.18(17.7)
22.2×1.20.24(23.5)
28.57×1.30.08(7.8)
28.57×1.30.09(8.8)
─ ─
─ ─
─ ─
*Refrigerant Charge (kg) 4.0 4.9 5.9 6.8 7.7 8.5 ─ ─ ─
RAS-6U2S +
RAS-6CT2S 600DH
**Additional Oil Charge(l) ─ ─ ─ ─ 0.10 0.19 ─ ─ ─
L ODxT PD
12.7×0.9 0.08(7.8)
12.7×0.90.15(14.7)
12.7×0.90.22(21.6)
15.88×1.10.09(8.8)
15.88×1.10.12(11.8)
15.88×1.10.14(13.7)
─ ─
─ ─
─ ─
G ODxT PD
22.2×1.2 0.12(11.8)
28.57×1.30.07(6.9)
28.57×1.30.10(9.8)
28.57×1.30.13(12.7)
28.57×1.30.16(15.7)
28.57×1.30.19(18.6)
─ ─
─ ─
─ ─
*Refrigerant Charge (kg) 4.8 5.5 6.2 6.8 7.5 8.2 ─ ─ ─
RAS-8U2S +
RAS-8CT2S 750EL
**Additional Oil Charge(l) ─ ─ ─ ─ 0.08 0.15 ─ ─ ─
L ODxT PD
15.88×1.1 0.06(6.0)
15.88×1.10.12(11.8)
15.88×1.10.18(18.0)
15.88×1.10.24(24.0)
19.05×1.10.14(13.8)
19.05×1.10.17(16.7)
─ ─
─ ─
─ ─
G ODxT PD
28.57×1.3 0.08(8.0)
28.57×1.30.15(14.7)
28.57×1.30.23(22.5)
28.57×1.30.3(29.4)
34.9×1.40.13(12.9)
34.9×1.40.15(14.7)
─ ─
─ ─
─ ─
*Refrigerant Charge (kg) 6.6 7.7 8.8 9.8 10.9 12.0 ─ ─ ─
RAS-9U2S +
RAS-9CT2S 900EL
**Additional Oil Charge(l) ─ ─ ─ ─ 0.12 0.24 ─ ─ ─
L ODxT PD
15.88×1.1 0.06(6.0)
15.88×1.10.12(11.8)
15.88×1.10.18(18.0)
15.88×1.10.24(24.0)
19.05×1.10.14(13.8)
19.05×1.10.17(16.7)
─ ─
─ ─
─ ─
G ODxT PD
28.57×1.3 0.08(8.0)
28.57×1.30.15(14.7)
28.57×1.30.23(22.5)
28.57×1.30.3(29.4)
34.9×1.40.13(12.9)
34.9×1.40.15(14.7)
─ ─
─ ─
─ ─
*Refrigerant Charge (kg) 7.0 8.2 9.4 10.6 11.8 13.0 ─ ─ ─
RAS-10U2S +
RAS-10CT2S 1000EL
**Additional Oil Charge(l) ─ ─ ─ ─ 0.13 0.26 ─ ─ ─
L ODxT PD
12.7×0.9 0.02(2.0)
12.7×0.90.05(4.9)
12.7×0.90.07(6.9)
15.88×1.10.09(8.8)
15.88×1.10.12(11.8)
15.88×1.10.14(13.7)
─ ─
─ ─
─ ─
G ODxT PD
22.2×1.2 0.12(11.8)
28.57×1.30.07(6.9)
28.57×1.30.10(9.8)
28.57×1.30.13(12.7)
28.57×1.30.16(15.7)
28.57×1.30.19(18.6)
─ ─
─ ─
─ ─
*Refrigerant Charge (kg) 4.9 5.6 6.2 6.9 7.5 8.2 ─ ─ ─
No. 1: 750EL
**Additional Oil Charge(l) ─ ─ ─ ─ 0.07 0.14 ─ ─ ─
L ODxT PD
12.7×0.9 0.01(1.0)
12.7×0.90.02(2.0)
12.7×0.90.03(2.9)
15.88×1.10.05(4.9)
15.88×1.10.06(5.9)
15.88×1.10.07(6.9)
─ ─
─ ─
─ ─
G ODxT PD
19.05×1.1 0.13(12.7)
19.05×1.10.26(25.5)
22.2×1.20.18(17.7)
22.2×1.20.24(23.5)
28.57×1.30.08(7.8)
28.57x1.30.09(8.8)
─ ─
─ ─
─ ─
*Refrigerant Charge (kg) 3.0 3.7 4.4 5.0 5.7 6.4 ─ ─ ─
RAS-13U2S +
RAS-13CT2S
No. 2: 500DH
**Additional Oil Charge(l) ─ ─ ─ ─ 0.08 0.15 ─ ─ ─
L ODxT PD
15.88×1.1 0.02(2.0)
15.88×1.10.05(4.9)
15.88×1.10.07(6.9)
15.88×1.10.09(8.8)
19.05X1.10.12(11.8)
19.05X1.10.14(13.7)
─ ─
─ ─
─ ─
G ODxT PD
28.57×1.3 0.12(11.8)
28.57×1.30.07(6.9)
28.57×1.30.10(9.8)
28.57×1.30.13(12.7)
34.9×1.40.16(15.7)
34.9×1.40.19(18.6)
─ ─
─ ─
─ ─
*Refrigerant Charge (kg) 5.8 6.6 7.5 8.3 9.2 10 ─ ─ ─
No. 1: 1000EL
**Additional Oil Charge(l) ─ ─ ─ ─ 0.10 0.19 ─ ─ ─
L ODxT PD
12.7×0.9 0.02(2.0)
12.7×0.90.05(4.9)
12.7×0.90.07(6.9)
15.88×1.10.09(8.8)
15.88×1.10.12(11.8)
15.88×1.10.14(13.7)
─ ─
─ ─
─ ─
G ODxT PD
19.05×1.1 0.12(11.8)
19.05×1.10.07(6.9)
22.2×1.20.10(9.8)
22.2×1.20.13(12.7)
28.57×1.30.16(15.7)
28.57×1.30.19(18.6)
─ ─
─ ─
─ ─
*Refrigerant Charge (kg) 3.1 3.6 4.0 4.5 4.9 5.4 ─ ─ ─
RAS-15U2S +
RAS-15CT2S
No. 2: 600DH
**Additional Oil Charge(l) ─ ─ ─ ─ 0.04 0.10 ─ ─ ─
L ODxT PD
15.88X1.1 0.06(5.0)
15.88X1.10.12(11.8)
15.88X1.10.18(17.7)
15.88X1.10.24(23.5)
19.05X1.10.14(13.7)
19.05X1.10.17(16.7)
19.05X1.1 0.23(22.6)
19.05X1.10.28(27.4)
19.05X1.1 0.34(33.3)
G ODxT PD
28.57X1.3 0.08(7.8)
28.57X1.30.15(14.7)
28.57X1.30.23(22.6)
28.57X1.30.30(29.4)
34.9X1.40.13(12.7)
34.9X1.40.15(14.7)
34.9X1.4 0.20(19.6)
34.9X1.40.25(24.5)
34.9X1.4 0.30(29.4)
*Refrigerant Charge (kg) 6.8 8.0 9.3 10.5 11.8 13.0 15.3 17.7 20.0
No. 1: 1000EL
**Additional Oil Charge(l) ─ ─ ─ ─ 0.14 0.28 0.53 0.79 1.05
L ODxT PD
15.88X1.1 0.06(5.9)
15.88X1.10.12(11.8)
15.88X1.10.24(23.5)
15.88X1.10.14(13.7)
19.05X1.10.14(13.7)
19.05X1.10.17(16.7)
19.05X1.1 0.23(22.6)
19.05X1.10.28(27.4)
19.05X1.1 0.34(33.3)
G ODxT PD
28.57X1.3 0.08(7.8)
28.57X1.30.15(14.7)
28.57X1.30.23(22.6)
28.57X1.30.30(29.4)
34.9X1.40.13(12.7)
34.9X1.40.15(14.7)
34.9X1.4 0.20(19.6)
34.9X1.40.25(24.5)
34.9X1.4 0.30(29.4)
*Refrigerant Charge (kg) 6.8 8.0 9.3 10.5 11.8 13.0 15.3 17.7 20.0
RAS-20U2S +
RAS-20CT2S
No. 2 1000EL
**Additional Oil Charge(l) ─ ─ ─ ─ 0.14 0.28 0.53 0.79 1.05 G : Gas Piping PD : Pressure Drop for Equivalent Piping Length[kg/cm2 (kPa)] L : Liquid Piping * : Total Refrigerant Charge for One Cycle for Actual Piping Length (kg)
OD×T : Outer Diameter and Thickness of pipe (mm) ** : Additional charge is required for one cycle
43
18 19
Electrical Box
B DA E F
INSTALLATION DATA
Field Wiring Provisions Field wiring The units are internally wired at the factory according to generally accepted electrical technology. Required field wiring to conform to the HITACHI Standard Wiring and required components are as follows.
Required Field Wiring – Main power wiring to the unit, Earth Wiring, Thermostat Control Wiring and Solenoid Valve Control Wiring (When the unit is to be operated under the conditions specified in the Field Piping Provisions)
Required Components – Main Power Switch, Main Power Fuses, Conduit Coupling, Solenoid Valve (When the unit is to be operated under the conditions specified in the Field Piping Provisions) and Room Thermostat.
NOTE: When installing the solenoid valve, connect the wiring of the solenoid valve to the terminals for control, in order that the solenoid valve will be opened when the compressor is operating and will be closed when the compressor is stopped.
Wire and Fuse Size Selection Wire and fuse sizes should be selected in accordance with national and local codes, taking the designed maximum ambient temperature into account. The system maximum current will be the sum of the compressor maximum current, condenser fan motor current and evaporator fan motor maximum current (refer to the Electrical Data).
44
through RAS-10U2S
18 19
1 2 3 4 5 6
L3TS
L2L1R
Control CircuitTerminal
PCBTerminal
1B DA E F
Control Circuit
Switch(Field-Supplied)
Main Power
(Cooling Unit)
(Field-Supplied)Thermostat
Room ※
RAS-6U2S
Electrical Box
RAS-6CT2S through RAS-10CT2S
Main Power Terminal
L2 L3L1R TS
N 2Mp
(Condensing Unit)
3 4 5 6
Motor Terminal
20211819
RAS-13CT2S through RAS-20CT2S
RAS-13U2S through RAS-20U2S
(Field Supplied)
Main PowerSwitch
Motor Terminal
(Cooling Unit)(Field-Supplied)Thermostat
Room ※
(Condensing Unit)
Electrical Box
Electrical Box
FS T
U V W
NMp
L3T
L2S
L1R
Main Power Terminal
(Field-Supplied)
ValveNo.1
Solenoid
(Field-Supplied)
ValveNo.2
Solenoid
D EAR
PCB
B
INSTALLATION DATA NOTE: The control circuit is wired for the 240V control circuit (unit power source 415V)at the factory, therefore for the 220V control circuit, change the wiring at the terminal base in the electrical box, according to the “Typical Wiring”.
45
SPECIFICATIONS
Standard Specifications Unit – The air conditioner shall be a split-system air conditioner for application with R-22 refrigerant, and shall be composed of a cooling unit and a condensing unit(s) with one or two refrigeration cycles, electrical components and enclosing cabinets. Optional accessories shall also be provided upon customer request. The condensing unit shall be completely weatherproof for outdoor installation, and the cooling unit shall be designed for indoor installation. The condensing unit and the cooling unit shall be properly assembled, internally piped and wired, and thoroughly tested and holding charged with R-22 refrigerant at the factory. Capacity – The total cooling capacity of the unit shall be kcal/h or greater, and the sensible heat capacity shall be kcal/h or greater with °C evaporator air inlet dry bulb, °C evaporator air inlet wet bulb, °C condenser air inlet temperature and m3/min. evaporator air flow. The total compressor power input shall not exceed kW. CONDENSING UNIT
Cabinet – The cabinet shall be constructed of galvanized steel baked with synthetic resin paint. The service panels shall be easily removable for service access to electrical components, compressors, condensers and condenser fans. Refrigeration Cycle – The refrigeration cycle shall be equipped with a hermetic compressor, an air-cooled condenser coil, an evaporator coil, check joints for high pressure line and low pressure line. Compressor – The compressor shall be a hermetic compressor. The starting method shall be the direct-on-line type. The hermetic compressor shall be a welded shell type, and spring-suspended internally. The compressor shall be mounted on vibration-proof rubber bushings. Condenser Fan and Condenser Fan Motor – The condenser fan shall be the aluminum propeller type, dynamically and statically balanced, and the condenser fan shall be directly driven by a kW motor for up-flow air discharge. The motor shall be permanently lubricated, and protected from water invasion.
Condenser – The air-cooled coil shall be the multi-pass, cross-finned tube type, equipped with highly-efficient aluminum fins, mechanically bonded to oxygen-free copper tubes. The coil shall be cleaned, dehydrated and tested for leakage at the factory. Compressor Protection – The compressor shall be protected against breakdown by a quick response overcurrent relay, a high pressure switch, a cycling protection circuit and a discharge gas thermostat. COOLING UNIT
Evaporator - The evaporator shall be the multi-pass cross-finned tube type, equipped with highly-efficient aluminum fins, mechanically bonded to seamless, oxygen-free copper tubes. The fins shall be spaced at more than 12 fins per 25.4 mm. The face area of the evaporator shall not be less than m2. The coil shall be cleaned, dehydrated and tested for leakage at the factory. Evaporator Fan and Evaporator Fan Motor – The evaporator fan shall be the forward-curved, multi-blade centrifugal type, statically and dynamically balanced, and V-belt driven by a kW motor. The evaporator fan motor shall be permanently lubricated. The fan shall deliver air flow m3/min. at mmAq external static pressure at rpm. OTHER ITEMS
Control – All electrical control devices, except for the field-supplied room thermostat assembly, shall be enclosed in a weatherproof location of a unit. In addition to the compressor protection devices, the unit shall be provided with fuses for the control circuit, and auxiliary relays.
Specifications in this catalog are subject to change without notice, in order that HITACHI may bring the latest innovations to our customers.