R-22 60HZ Sharjah Economic Excellence Award winner www.skmaircon.com facebook.com/skmaircon @skmaircon Range 5 TR to 25 TR ( 18 kW to 88 kW ) Split Air Conditioners ACUM-L + CADX-L Series

Transcript of Split Air Conditioners ACUM-L + CADX-L Series 60Hz.pdf · Split Air Conditioners ACUM-L + CADX-L...

R-2260HZ

Sharjah Economic Excellence Award winnerwww.skmaircon.comfacebook.com/skmaircon @skmaircon

Range 5 TR to 25 TR( 18 kW to 88 kW )

Split Air ConditionersACUM-L + CADX-L Series

SKM Split Air ConditionersACUM-L + CADX-L Series - R-22

2

IntroductionThe new series of SKM air cooled split system air conditioner has been developed to satisfy the needs in air conditioning practices, meet high quality of job requirements every time and to deliver the best in split system performance.SKM air cooled split air conditioners consist of ceiling suspended indoor air handler (CADX-L) matched with floor mounted outdoor air cooled condensing unit (ACUM-L) series.

SKM air cooled split air conditioners available in 11 variations to cover the range from 5 TR to 25 TR (18 kW to 88 kW) in 60Hz at nominal AHRI conditions. It is suitable to operate in a wide range of ambient temperatures from 50 °F (10°C) to 125°F (51.7°C).

SKM split units are internally wired and all that is required to be done on site is ducting, refrigerant piping, power wiring for CADX-L motor from ACUM-L, thermostat wiring and power supply connection which reduces installation work and consequently keeps costs to a minimum. Two independent refrigeration circuits are provided when two compressors are used.

SKM provides qualified service and stock of replacement parts in all major cities of the G.C.C. countries, Egypt, Jordan, and Pakistan. See back cover for details or call SKM.

SKM Air Conditioning LLC

You name it.....We cool it

Contents

Legend The following legends are used throughout this manual:

Nomenclature

Introduction....................................02Legend...........................................02Nomenclature.................................02Component Features...........................03Optional Features................................04Specifications.....................................06Capacity Ratings.................................08Fan Performance.................................10

Air Cooled Condensing Units

ACU M - 060 L E

Power Suppy CodeE: 460V/3Ph/60HzR: 380V/3Ph/60HzT: 220V/3Ph/60Hz

M-series

Comfort Air ConditionerPower SuppyE: 460V/3Ph/60HzR: 380V/3Ph/60HzT: 220V/3Ph/60Hz

Model Designation

Nominal Capacity (MBh)

Model Designation

CA DX - 060 L E

Nominal Capacity (MBh)

Direct Expansion Cooling Coil

cfm ......... Cubic feet per minuteHz .......... HertzkW ......... Kilowattskg ........... Kilogramlbs .......... Poundsl/s .......... Liters per secondMBh ....... BTUH x 1000Ph .......... Phase

PI ........... Power Input of CompressorTR .......... Tons of RefrigerationV ............ VoltskPa ....... KilopascalEWB...... Evaporator Wet Bulb air entering temperature.BPF....... By Pass Factor

Electrical Data .....................................11Typical Wiring Diagram .....................12Dimensional Data ...............................13Recommended Line Sizes ..................16Recommended Clearances ................17Installation and commissioning .........18Guide Specifications..........................20

SKM Split Air ConditionersACUM-L + CADX-L Series - R-22

3

Condenser Coils

Condenser coils are manufactured from cross fin Waffle Louvre and Hi-X seamless copper tubes mechanically bonded to aluminium fins to ensure optimum heat transfer. All coils are tested against leakage by air pressure 450psig (3100 kPa) under water. An integral subcooling circuit is incorporated in the lower section of the condenser to increase system capacity. The additional condenser surface provides more cooling using less energy at no additional cost.

Condenser Fans

Condenser fans are propeller type with aluminium alloy blades and are directly driven by electric motors. Motors are Totally Enclosed Air Over (TEAO), six pole or four pole with Class F insulation and minimum IP-54 protection. The TEAO and Class F insulation features ensure long life and are unique to SKM. The condenser fans are individually statically and dynamically balanced at the factory. Complete fan assembly is mounted downward on the strong and acrylic coated fan guard for the smaller units. For larger units fan, assembly is separate and provided with suitable acrylic coated fan guard.

GENERAL FEATURESSKM split system air conditioners incorporate many features and benefits in both the air handler and condensing units, which together provides a heavy duty, robust and long lasting commercial unit’s application.SKM split air conditioners combined high efficiency components to provide an extremely rugged and energy efficient split system that will provide cooling with higher efficiency for a long and extended period of time. SKM split system is ACUM-L+ CADX-L is yet another model in the top class range of SKM products which uses the following basic components:

• High efficiency totally sealed hermetic scroll compressors utilizing the most current state of the art technology and provides smooth, efficient and quiet operation.

• Totally enclosed, Class F insulated,condenser and evaporator fan motors.

• Heavy duty condenser and evaporator coils optimized and designed for a long life maintenance free operation.

• Cabinet construction specifically for gulf climate condition.

• Electronic control board for the unit operation.

• Factory matched performance and reliable output to minimize field decisions.

• Many standard features which are not included in residential domestic type split systems.

• Typically, much heavier gauge tubing and thicker fins for ruggedness and long life.

Compressor

Compressors used in the ACUM-L series condensing units are hermetically sealed, hi-efficiency, low noise, and compact scroll with the following features:

• High efficiency.• Quiet operation, low sound levels.• Better debris handling.• Self compensating of wear (“wear-in vs. wear-out”).• 70% fewer moving parts than comparably sized reciprocating

• Internal motor protection / Advanced scroll temperature

• Suction gas motor cooling.• Suction screen.

COMPONENT FEATURES

• Disc type check valve.• Centrifugal force for oil lubrication.• Brazed fittings as standard, rotalock as an option.

compressors.

protection.

ACUM-L CONDENSING UNIT

Control PanelThe ACUM-L series condensing units are provided with IP-54 control panel enclosure comprising all starting, operating and safety controls.

The following are the standard components used in all ACUM-L control panel:

• Starting contactors for compressors and motors.• Internal overload protection for compressors.• Internal OR External overload protection for the motors

(depending on the model).• Electronic control board for unit operation.• Diagnostic LEDs on the control board for easy

troubleshooting .• Compressor short cycling protection.• Control switch for unit on/off.• Control circuit breaker.• Power and control circuit terminal blocks.• High pressure protection.• Low pressure protection.• Starter (contactor & overload relay) for CADX-L

evaporator fan motor.

(Power wiring from ACUM-L control panel to CADX-L motor to be done at site by others)

SKM Split Air ConditionersACUM-L + CADX-L Series - R-22

4

All evaporator coils are made of inner grooved copper tubes mechanically bonded into cross wave aluminum fins to ensure optimum heat transfer. Coils conform to AHRI-410. All evaporator coils are tested against leakage by air pressure of 300 psig (2068 kPa) under water. Each evaporator coil is supplied with a factory sized and matched thermostatic expansion valves and 4 mounting holes for ceiling suspension.

Evaporator fans are forward curved centrifugal double inlet, double width, statically and dynamically balanced. Bearings used in the fans are self aligning and lubricated for life. Evaporator fans are belt driven and use “V” belts with an adjustable variable pitch motor pulley resulting in an accurate fan air flow adjustment.

Fans are driven by Totally Enclosed, IP55 Protected, 4 Pole Class F insulated electric motors which conform to relevant IEC standards.

CADX-L AIR HANDLING UNIT

All CADX-L units are supplied as standard with 1” (25mm) thick permanent washable expanded aluminum flat filter having average dust arrestance 54% according to ASHRAE standard 52-76.

Filter

Unit Casing The unit casing used in the ACUM-L condensing unit is made of zinc coated galvanised steel sheets conforming to JIS-G 3302 and ASTM A525 which is phosphatized and baked after an electrostatic powder coating in RAL7032 color scheme of approximately 60 microns. This finish and coating can pass a 1000 hour in 5% salt spray testing at 95°F (35°C) and 95% relative humidity as per ASTM B117.

Evaporator Fan & Drive

Evaporator Coils

Casing \ Structure (CADX-L):

OPTIONAL FEATURESAs with all SKM air conditioning units, a wide range of options are available with SKM Split Units on request.

Copper Fins (FC)

Pre Coated Aluminum Fins (FAP)

Aeris Coating for Aluminium Fins (FAA)/(FCA) /Copper Fins.

2” (50mm) Flat Filter Section (FFS) For heavy filtration need a section can be provided without or with aluminium cleanable filter (2AF). Voltage Monitoring Module (VMM)To prevent ACUM-L unit operation in the event of Phase loss Phase reversal, and Under / Over voltage on the incoming line voltage.

The unit casing for CADX-L is made of zinc coated galvanized steel sheets conforming to JIS-G3302 and ASTM A525 which is phosphatized and baked after an electrostatic powder coating in RAL7032 color scheme of approximately 60 microns. This finish and coating can pass a 1000 hour in 5% salt spray testing at 95°F (35°C) and 95% relative humidity as per ASTM B117. Panels and casing are insulated with 1” (25mm) thick fiberglass (with BGT coating) thermal and acoustic insulation having density of 2 lb/ft³. (32 kg/m³) and thermal conductivity of 0.23 BTU.in/ft²°Fh (0.033 W/m°K). Insulation meets the requirements of NFPA 90A and 90B for fire resistance.

External Overload Protection (EOP)For those electrical specification requires additional overload protection for the compressors.

Liquid Line Controls (CRSP)Refrigeration specialties comprising solenoid valve, filter drier, sight glass and shut-off valve. Factory sizing and selection ensures correctly sized and selected components to complete the field installation.

Low voltage thermostats (CHTS)Wall mounted 24 volts cooling/heating thermostats, supplied loose for field installation.

Rotalock Valves on compressors (RVC)For additional facilitation of maintenance of unit.

Circuit Breaker for compressor (CBC)For those electrical specification which requires additional short circuit and overload protection for the compressors.

SKM Split Air ConditionersACUM-L + CADX-L Series - R-22

5

060L 060L 6070L 070L 7.5090L 090L 9100L 100L105L 105L120L 120L150L 150L 15180L 180L 18215L 215L240L 240L300L 300L

112

224

ACUM CADX Heater (kW) Stages

Table 1

Electric Heating (HTR1) Pump Down Facility (PDS)The compressor will switch off each time with a Pump Down Cycle in order to prevent Liquid refrigerant migration to the compressor during off Cycle periods.With this option, each circuit will be provided with an additional discharge check valve to prevent Refrigerant Migration from High side to Low side when the compressor is off.

Condenser Coil Guard (CGP) Wire mesh guard, in painted finish, for condenser coils. Recommended on ground level installation where coil needs to be protected against vandalism

Electric heating batteries are made up of finned heating elements, constructed from high quality 80/20 nickel chrome resistance wire centred in metal tube by compressed magnesium oxide. Helical fins are tightly wound around the tubular heating element.

Heater batteries when ordered comes with CADX-L mounted control panel consisting of stage contactors, primary auto reset thermal safety cut-out, secondary manual reset thermal safety cut-out and air flow switch. Control of the heater stages will be from ACUM-L control panel through heating/cooling thermostat (either supplied by SKM or by customer).

Following are the optional kW ratings for electric heater.

SKM Split Air ConditionersACUM-L + CADX-L Series - R-22

6

Table 2

CONDENSING UNIT SPECIFICATIONS

(1) The capacity ratings are based on AHRI standard 210/240 & 340/360. Evaporator entering air conditions of 80°F/67°F (26.7°C/19.5°C) dry bulb / wet bulb and condenser entering air temperature of 95°F (35°C) dry bulb.

(2) Evaporator entering air conditions of 80°F/67°F (26.7°C/19.5°C) dry bulb / wet bulb and condenser entering air temperature of 115°F(46°C) dry bulb.

(3) Connections are based on 25 ft maximum linear distance between the outdoor & indoor unit and 66 ft maximum lift.

(4) Refrigerant operating charge is for combined condensing uint with the matching air handling unit and 25 ft (7.6m) of interconnecting refrigerant lines.

Capacity for condition (1)&(2) are gross which doesn’t include the effect of evaporator fan motor heat.

ACUML 060L 070L 090L 100L 105L 120LCADXL 060L 070L 090L 100L 105L 120L

MBh 63.6 73.3 87.4 102.4 102.5 124.6kW 18.6 21.5 25.6 30.0 30.0 36.5

MBh 59.0 68.0 80.1 94.5 94.3 115.6kW 17.3 19.9 23.5 27.7 27.6 33.9% 100-0 100-0 100-0 100-0 100-50-0 100-50-0

1 1 1 1 2 2

1 1 1 1 2 2ft 20.00 20.00 26.67 26.67 40.00 40.00m 1.86 1.86 2.48 2.48 3.72 3.72

1 1 1 1 1 2Liquid in 1/2 1/2 1/2 5/8 1/2 1/2 (x2)

Suction in 7/8 7/8 1 1/8 1 1/8 7/8 (x2) 7/8 (x2)

550 / 1 550 / 1 723 / 2 723 / 2 550 / 2 550 / 2cfm 5390 5390 8500 8410 10940 10780l/s 2544 2544 4011 3969 5163 5087

Size / Qty. kW / # 0.36 / 1 0.36 / 1 1.1 / 2 1.1 / 2 0.36 / 2 0.36 / 2lbs 11.2 11.2 9.2 15.6 13.8 22.1kg 5.1 5.1 4.2 7.1 6.3 10.0lbs 335 337 344 27 569 646kg 152 153 156 12 258 293

ACUML 150L 180L 215L 240L 300LCADXL 150L 180L 215L 240L 300L

MBh 151.8 174.3 211.5 234.5 298.6kW 44.5 51.1 62.0 68.7 87.5

MBh 140.8 159.9 194.6 217.2 274.1kW 41.3 46.9 57.0 63.7 80.3% 100-50-0 100-50-0 100-50-0 100-50-0 100-50-0

2 2 2 2 2

2 2 2 2 2ft 40.00 40.00 40.00 54.67 54.67m 3.72 3.72 3.72 5.08 5.08

2 2 2 2 2Liquid in 1/2 (x2) 1/2 (x2) 5/8 (x2) 5/8 (x2) 5/8 (x2)

Suction in 7/8 (x2) 1 1/8 (x2) 1 1/8 (x2) 1 1/8 (x2) 1 1/8 (x2)

630 / 2 630 / 2 723 / 2 729 / 2 823 / 2cfm 11600 11600 16600 18680 23940l/s 5474 5474 7834 8815 11298

Size / Qty. kW / # 0.48 / 2 0.48 / 2 1.1 / 2 1.5 / 2 1.5 / 2lbs 22.3 23.1 27.1 31.7 33.3kg 10.1 10.5 12.3 14.4 15.1lbs 662 669 824 879 891kg 300 303 374 399 404

Hermetic - Scroll

Motor Type

Refrigerant Operating Charge R-22 (4)

Operating Weight Approximate

No. Refrigerant Circuits

Connections (3)

Outdoor Fan

Type

Cooling Capacity (2)

Capacity Steps

Compressor Type

Code/Qty

Air Flow

Qty.

Outdoor Coil

Type Qty.

Type Code/Qty

Type

Condensing Unit Matched Air Handling Unit

Cooling Capacity (1)

Cooling Capacity (1)

Cooling Capacity (2)

Face Area

Capacity Steps

Compressor

Outdoor Coil

Type

Air Flow

Qty. Type Qty.

Condensing Unit Matched Air Handling Unit

Waffle louver fins and Hi-X tubes 3/8'' OD

Hermetic - Scroll

Operating Weight Approximate

Refrigerant Operating Charge R-22 (4)

Totally Enclosed Air Over, Class-F Insulation. 4 pole or 6 pole, IP54 protected

Propeller Direct Drive

Connections (3)

No. Refrigerant Circuits

Outdoor Fan

Motor

Waffle louver fins and Hi-X tubes 3/8'' OD

Propeller Direct Drive

Totally Enclosed Air Over, Class-F Insulation. 4 pole or 6 pole, IP54 protected

Face Area

Notes:

SKM Split Air ConditionersACUM-L + CADX-L Series - R-22

7

AIR HANDLING UNIT SPECIFICATIONS 060L 070L 090L 100L 105L 120L

ACUML 060L 070L 090L 100L 105L 120LMBh 63.6 73.3 87.4 102.4 102.5 124.6kW 18.6 21.5 25.6 30.0 30.0 36.5

MBh 59.0 68.0 80.1 94.5 94.3 115.6kW 17.3 19.9 23.5 27.7 27.6 33.9

ft 5.81 5.81 7.99 7.99 7.99 7.99m 0.5 0.5 0.7 0.7 0.7 0.7

in 1/2 1/2 1/2 5/8 1/2 (x2) 1/2 (x2)Suction in 7/8 7/8 1 1/8 1 1/8 7/8 (x2) 7/8 (x2)

10/10 10/10 12/12 12/12 12/12 12/12 cfm 2000 2400 3000 3400 3400 3600l/s 944 1133 1416 1605 1605 1699

Size / Qty. kW / # 0.55 / 1 0.75 / 1 1.1 / 1 1.1 / 1 1.1 / 1 1.5 / 1lbs 225 227 305 312 310 334kg 102 103 138 141 141 151

Motor Type Totally Enclosed Fan Cooled, Class-F Insulation. 4 pole, IP55 protected

Operating Weight Approximate

Indoor Fan

Type Centrifugal DIDW Belt Drive Code

Air Flow

Hi-X tubes 3/8'' OD

Thermostatic Expansion Valve(s)

Table 3

(1) The capacity ratings are based on AHRI standard 210/240 & 340/360. Evaporator entering air conditions of 80°F/67°F (26.7°C/19.5°C) dry bulb / wet bulb and condenser entering air temperature of 95°F (35°C) dry bulb.

(2) Evaporator entering air conditions of 80°F/67°F (26.7°C/19.5°C) dry bulb / wet bulb and condenser entering air temperature of 115°F(46°C) dry bulb.

(3) Connections are based on 25 ft maximum linear distance between the outdoor & indoor unit and 66 ft maximum lift.

Capacity for condition (1)&(2) are gross which doesn’t include the effect of evaporator fan motor heat.

Notes:

150L 180L 215L 240L 300LACUML 150L 180L 215L 240L 300L

MBh 151.8 174.3 211.5 234.5 298.6kW 44.5 51.1 62.0 68.7 87.5

MBh 140.8 159.9 194.6 217.2 274.1kW 41.3 46.9 57.0 63.7 80.3

ft 11.67 14.17 19.36 19.36 19.36m 1.1 1.3 1.8 1.8 1.8

in 1/2 (x2) 1/2 (x2) 5/8 (x2) 5/8 (x2) 5/8 (x2)Suction in 7/8 (x2) 1 1/8 (x2) 1 1/8 (x2) 1 1/8 (x2) 1 1/8 (x2)

15/15 12/12 R2 15/15 R2 15/15 R2 15/15 R2cfm 4800 6200 7200 8000 8000l/s 2265 2926 3398 3775 3775

Size / Qty. kW / # 1.5 / 1 2.2 / 1 2.2 / 1 2.2 / 1 3.0 / 1lbs 442 470 673 678 712kg 200 213 305 307 323

Motor Type Totally Enclosed Fan Cooled, Class-F Insulation. 4 pole, IP55 protected

Operating Weight Approximate

Thermostatic Expansion Valve(s)

Indoor Fan

Type Centrifugal DIDW Belt Drive Code

Air Flow

Hi-X tubes 3/8'' OD

Air Handling Unit CADXLMatched Condensing Unit

Cooling Capacity (1)

Cooling Capacity (2)

TypeIndoor Coil

Face Area

Refrigerant ControlLiquid

Connections (3)

Air Handling Unit C A D X L Matched Condensing Unit

Cooling Capacity (1)

Cooling Capacity (2)

TypeIndoor Coil

Face Area

Refrigerant ControlLiquid

Connections (3)

SKM Split Air ConditionersACUM-L + CADX-L Series - R-22

8

AFRcfm

*IP*IP*IP*IP*IPs/l

(BPF) °F °C MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW1597 62 16.7 56.2 16.5 48.4 14.2 4 54.1 15.9 47.5 13.9 4.5 51.5 15.1 46.4 13.6 5 50.5 14.8 46 13.5 5.2 48.8 14.3 45.2 13.3 5.6754 67 19.4 61.1 17.9 40.4 11.8 4.1 59 17.3 39.6 11.6 4.6 56.8 16.6 38.7 11.3 5.2 56 16.4 38.4 11.3 5.3 54.4 16 37.8 11.1 5.70.17 72 22.2 66.3 19.4 32.3 9.5 4.2 64 18.8 31.5 9.2 4.7 61.6 18 30.7 9 5.3 60.7 17.8 30.4 8.9 5.5 59 17.3 29.8 8.7 5.82000 62 16.7 57.9 17 54.1 15.9 4.1 55.2 16.2 53 15.5 4.5 52.6 15.4 51.9 15.2 5.1 51.7 15.1 51.6 15.1 5.2 50 14.6 50 14.6 5.6944 67 19.4 63.6 18.7 44.8 13.1 4.1 61.4 18 44 12.9 4.6 59 17.3 43.1 12.6 5.2 58.2 17.1 42.8 12.5 5.4 56.6 16.6 42.2 12.4 5.80.19 72 22.2 68.9 20.2 35.1 10.3 4.2 66.5 19.5 34.3 10.1 4.7 63.8 18.7 33.4 9.8 5.3 62.9 18.4 33.1 9.7 5.5 61.2 17.9 32.6 9.5 5.93193 62 16.7 60.3 17.7 60.3 17.7 4.1 57.8 16.9 57.8 16.9 4.6 55.2 16.2 55.2 16.2 5.1 54.4 15.9 54.4 15.9 5.3 52.7 15.4 52.7 15.4 5.71507 67 19.4 68.2 20 56.4 16.5 4.2 65.7 19.2 55.5 16.3 4.7 62.3 18.3 54.4 15.9 5.3 61.2 17.9 54 15.8 5.5 59.2 17.3 53.3 15.6 5.80.26 72 22.2 73.4 21.5 42.4 12.4 4.3 70.7 20.7 41.5 12.2 4.8 - - - - - - - - - - - - - - -1597 62 16.7 63.3 18.6 51.6 15.1 4.8 61 17.9 50.5 14.8 5.5 58.4 17.1 49.4 14.5 6.2 57.6 16.9 49 14.4 6.5 55.9 16.4 48.3 14.2 7754 67 19.4 68.2 20 43.3 12.7 4.9 65.8 19.3 42.3 12.4 5.6 63.4 18.6 41.3 12.1 6.3 62.5 18.3 41 12 6.6 60.9 17.8 40.3 11.8 70.17 72 22.2 73.8 21.6 35 10.3 5 71.3 20.9 34.1 10 5.7 68.6 20.1 33.1 9.7 6.4 67.7 19.8 32.8 9.6 6.7 65.9 19.3 32.2 9.4 7.12400 62 16.7 67.7 19.8 63 18.5 4.9 64.9 19 61.9 18.1 5.6 61.6 18 60.5 17.7 6.3 60.5 17.7 60.1 17.6 6.5 58.4 17.1 58.4 17.1 71133 67 19.4 73.3 21.5 51.8 15.2 5 70.7 20.7 50.8 14.9 5.7 68 19.9 49.8 14.6 6.4 67 19.7 49.5 14.5 6.7 65.2 19.1 48.8 14.3 7.10.22 72 22.2 79.2 23.2 40.4 11.9 5.1 76.4 22.4 39.5 11.6 5.8 73.3 21.5 38.5 11.3 6.5 72.2 21.2 38.1 11.2 6.8 70.1 20.5 37.5 11 7.23193 62 16.7 69.3 20.3 69.3 20.3 4.9 66.1 19.4 66.1 19.4 5.6 63 18.5 63 18.5 6.3 62 18.2 62 18.2 6.6 60 17.6 60 17.6 71507 67 19.4 76.4 22.4 59.3 17.4 5.1 73.6 21.6 58.3 17.1 5.7 70.6 20.7 57.3 16.8 6.5 69.6 20.4 56.9 16.7 6.7 67.7 19.8 56.2 16.5 7.10.26 72 22.2 82.4 24.1 45.2 13.2 5.2 79.2 23.2 44.2 12.9 5.9 75.8 22.2 43.1 12.6 6.6 74.6 21.9 42.7 12.5 6.8 72.3 21.2 42 12.3 7.22196 62 16.7 76.9 22.5 66.4 19.5 6.2 73.3 21.5 64.8 19 6.9 68.9 20.2 63 18.5 7.6 67.5 19.8 62.4 18.3 7.9 65 19.1 61.3 18 8.31036 67 19.4 83.1 24.4 55.2 16.2 6.4 79.6 23.3 53.9 15.8 7.1 76.1 22.3 52.5 15.4 7.7 75 22 52.1 15.3 7.9 74.5 21.8 51.9 15.2 80.17 72 22.2 89.5 26.2 43.9 12.9 6.6 85.9 25.2 42.6 12.5 7.2 82.3 24.1 41.4 12.1 7.7 81.2 23.8 41 12 7.9 80.6 23.6 40.8 11.95 7.93000 62 16.7 79.3 23.2 77.4 22.7 6.3 75.1 22 75.1 22 7 71.1 20.8 71.1 20.8 7.7 69.8 20.4 69.8 20.4 7.9 67.4 19.8 67.4 19.8 8.31416 67 19.4 87.4 25.6 63.7 18.7 6.5 83.7 24.5 62.4 18.3 7.1 80.1 23.5 61.1 17.9 7.7 78.9 23.1 60.6 17.8 7.9 78.4 22.9 60.5 17.7 80.21 72 22.2 93.6 27.4 49.1 14.4 6.7 89.9 26.3 47.9 14 7.2 86.3 25.3 46.7 13.7 7.7 85.1 24.9 46.4 13.6 7.9 84.6 24.8 46.2 13.5 7.94392 62 16.7 81.9 24 81.9 24 6.3 77.9 22.8 77.9 22.8 7 73.9 21.7 73.9 21.7 7.7 72.7 21.3 72.7 21.3 7.9 72.1 21.1 72.1 21.1 82073 67 19.4 91.6 26.8 76.8 22.5 6.6 87.2 25.6 75.3 22.1 7.2 82.7 24.2 73.8 21.6 7.7 81.3 23.8 73.3 21.5 7.9 80.7 23.6 73.1 21.4 7.90.26 72 22.2 97.6 28.6 57.2 16.8 6.7 - - - - - - - - - - - - - - - - - - - -2196 62 16.7 88 25.8 71.4 20.9 6.7 84.6 24.8 69.8 20.5 7.5 80.8 23.7 68.1 20 8.4 79.5 23.3 67.5 19.8 8.7 77 22.6 66.4 19.5 9.31036 67 19.4 94.8 27.8 59.9 17.6 6.8 91.3 26.8 58.5 17.1 7.6 87.6 25.7 57 16.7 8.5 86.3 25.3 56.5 16.6 8.8 83.8 24.6 55.5 16.3 9.40.17 72 22.2 102.6 30.1 48.5 14.2 6.9 98.9 29 47.2 13.8 7.7 94.9 27.8 45.8 13.4 8.6 93.6 27.4 45.3 13.3 8.9 91 26.7 44.4 13 9.53400 62 16.7 94.5 27.7 88.5 25.9 6.8 90.5 26.5 86.8 25.4 7.6 85.4 25 84.7 24.8 8.5 83.7 24.5 83.7 24.5 8.8 80.6 23.6 80.6 23.6 9.31605 67 19.4 102.4 30 72.6 21.3 6.9 98.6 28.9 71.2 20.9 7.7 94.5 27.7 69.7 20.4 8.6 93.1 27.3 69.2 20.3 8.9 90.4 26.5 68.2 20 9.50.22 72 22.2 110.5 32.4 56.6 16.6 7 106.4 31.2 55.3 16.2 7.9 102 29.9 53.8 15.8 8.8 100.5 29.5 53.3 15.6 9.1 97.7 28.6 52.4 15.4 9.74392 62 16.7 96.6 28.3 96.6 28.3 6.8 92 27 92 27 7.6 87.2 25.5 87.2 25.5 8.5 85.6 25.1 85.6 25.1 8.8 82.6 24.2 82.6 24.2 9.42073 67 19.4 106.1 31.1 81.9 24 6.9 102.1 29.9 80.5 23.6 7.8 97.8 28.7 79 23.2 8.7 96.4 28.2 78.5 23 9 93.6 27.4 77.5 22.7 9.60.26 72 22.2 114.3 33.5 62.4 18.3 7.1 109.9 32.2 61.1 17.9 7.9 105.3 30.9 59.6 17.5 8.9 103.8 30.4 59.1 17.3 9.2 100.9 29.6 58.2 17.1 9.82196 62 16.7 88.3 25.9 71.5 21 7.1 84.8 24.9 69.9 20.5 8 81 23.7 68.2 20 9 79.7 23.4 67.6 19.8 9.4 77.3 22.6 66.6 19.5 101036 67 19.4 95.1 27.9 60 17.6 7.2 91.4 26.8 58.5 17.2 8.2 87.6 25.7 57 16.7 9.1 86.3 25.3 56.5 16.6 9.5 83.9 24.6 55.5 16.3 10.10.17 72 22.2 102.7 30.1 48.6 14.2 7.4 98.8 29 47.2 13.8 8.3 94.8 27.8 45.7 13.4 9.3 93.4 27.4 45.2 13.3 9.6 90.8 26.6 44.3 13 10.23400 62 16.7 94.7 27.8 88.5 26 7.2 90.6 26.6 86.8 25.5 8.1 85.6 25.1 84.8 24.9 9.1 83.9 24.6 83.9 24.6 9.4 80.9 23.7 80.9 23.7 101605 67 19.4 102.5 30 72.7 21.3 7.4 98.5 28.9 71.2 20.9 8.3 94.3 27.7 69.7 20.4 9.3 92.9 27.2 69.1 20.3 9.6 90.2 26.4 68.2 20 10.20.22 72 22.2 110.5 32.4 56.6 16.6 7.6 106.2 31.1 55.2 16.2 8.5 101.6 29.8 53.7 15.7 9.5 100.1 29.3 53.2 15.6 9.8 97.1 28.5 52.3 15.3 10.44392 62 16.7 96.9 28.4 96.9 28.4 7.3 92.1 27 92.1 27 8.2 87.3 25.6 87.3 25.6 9.1 85.7 25.1 85.7 25.1 9.5 82.7 24.3 82.7 24.3 102073 67 19.4 106.2 31.1 81.9 24 7.5 102 29.9 80.5 23.6 8.4 97.6 28.6 78.9 23.1 9.4 96.1 28.2 78.4 23 9.7 93.3 27.3 77.4 22.7 10.20.26 72 22.2 114.2 33.5 62.4 18.3 7.7 109.5 32.1 60.9 17.9 8.6 104.8 30.7 59.4 17.4 9.6 103.1 30.2 58.9 17.3 9.9 100 29.3 58 17 10.52196 62 16.7 - - - - - 99.2 29.1 79.5 23.3 8.8 95.4 28 77.7 22.8 9.9 94.1 27.6 77.1 22.6 10.3 91.5 26.8 75.9 22.2 111036 67 19.4 111.7 32.7 69.1 20.3 8.1 107.4 31.5 67.3 19.7 9 103.4 30.3 65.6 19.2 10.1 102.1 29.9 65 19.1 10.5 99.4 29.1 63.9 18.7 11.20.09 72 22.2 120.7 35.4 56.6 16.6 8.2 116.7 34.2 55.1 16.2 9.2 112.5 33 53.5 15.7 10.3 111 32.5 52.9 15.5 10.7 108.1 31.7 51.9 15.2 11.43600 62 16.7 114.5 33.5 105.1 30.8 8.1 109.3 32 102.9 30.2 9 103.9 30.4 100.6 29.5 10.1 102 29.9 99.9 29.3 10.5 98.6 28.9 98.5 28.9 11.21699 67 19.4 124.6 36.5 86.9 25.5 8.3 120.3 35.3 85.3 25 9.2 115.6 33.9 83.5 24.5 10.3 114 33.4 82.9 24.3 10.7 110.9 32.5 81.8 24 11.40.13 72 22.2 135.1 39.6 68.4 20.1 8.4 130.4 38.2 66.8 19.6 9.4 125.2 36.7 65.1 19.1 10.6 123.5 36.2 64.5 18.9 11 120.1 35.2 63.4 18.6 11.74392 62 16.7 116.5 34.1 116.4 34.1 8.1 111.2 32.6 111.2 32.6 9.1 106 31.1 106 31.1 10.1 104.3 30.6 104.3 30.6 10.5 100.9 29.6 100.9 29.6 11.22073 67 19.4 129.1 37.8 95.9 28.1 8.3 124.5 36.5 94.2 27.6 9.3 119.6 35.1 92.4 27.1 10.4 117.9 34.6 91.8 26.9 10.8 114.7 33.6 90.6 26.6 11.50.14 72 22.2 139.7 40.9 74.1 21.7 8.5 134.7 39.5 72.5 21.2 9.5 129.2 37.9 70.7 20.7 10.7 127.4 37.3 70.1 20.5 11.1 123.9 36.3 69 20.2 11.8

yticapaC latoTyticapaC latoT SensibleCapacityTotal Capacity Sensible

CapacitySensibleCapacity

105L+

105L

120L+

120L

090L+

090L

100L+

100L

Total Capacity SensibleCapacity

060L+

060L

070L+

070L

Total Capacity SensibleCapacity

ACUM-L+

CADX-L

EWB

Condenser Entering Air Temperature95°F (35°C) 105°F (40.6°C) 115°F (46.1°C) 118.4°F (48°C) 125°F (51.7°C)

Table 4

CAPACITY RATINGS

SKM Split Air ConditionersACUM-L + CADX-L Series - R-22

9

CAPACITY RATINGS AFRcfm

*IP*IP*IP*IP*IPs/l

(BPF) °F °C MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW3208 62 16.7 131.5 38.6 105.6 30.9 10.1 126.7 37.1 103.4 30.3 11.4 121.5 35.6 101.1 29.6 12.9 119.7 35.1 100.3 29.4 13.4 116.3 34.1 98.7 28.9 14.41514 67 19.4 141.8 41.6 88.9 26 10.3 136.4 40 86.7 25.4 11.6 131.3 38.5 84.6 24.8 13.1 129.5 38 83.9 24.6 13.6 126.1 37 82.5 24.2 14.50.17 72 22.2 152.8 44.8 71.9 21.1 10.5 147.5 43.2 70 20.5 11.9 142.1 41.6 68.1 20 13.3 140.2 41.1 67.4 19.8 13.8 136.5 40 66.1 19.4 14.74800 62 16.7 140.5 41.2 128.3 37.6 10.2 135.2 39.6 126.1 36.9 11.6 129 37.8 123.5 36.2 13.1 126.6 37.1 122.5 35.9 13.6 122.2 35.8 120.7 35.4 14.52265 67 19.4 151.8 44.5 105.6 31 10.5 146.4 42.9 103.6 30.4 11.9 140.8 41.3 101.5 29.7 13.3 138.9 40.7 100.7 29.5 13.8 135.1 39.6 99.4 29.1 14.70.22 72 22.2 163.9 48 82.7 24.3 10.7 158 46.3 80.8 23.7 12.1 151.9 44.5 78.8 23.1 13.6 149.7 43.9 78.1 22.9 14.1 145.5 42.6 76.7 22.5 156417 62 16.7 145.1 42.5 145.1 42.5 10.3 138.4 40.6 138.4 40.6 11.7 131.6 38.6 131.6 38.6 13.1 129.4 37.9 129.4 37.9 13.6 125.1 36.7 125.1 36.7 14.53028 67 19.4 158.2 46.4 120.8 35.4 10.6 152.5 44.7 118.8 34.8 12 146.5 42.9 116.7 34.2 13.5 144.4 42.3 116 34 13.9 140.4 41.2 114.6 33.6 14.80.26 72 22.2 170.6 50 92.4 27.1 10.9 164.2 48.1 90.3 26.5 12.3 157.4 46.1 88.2 25.8 13.8 155 45.4 87.5 25.6 14.2 150.4 44.1 86 25.2 15.24604 62 16.7 153.9 45.1 134.1 39.3 11.9 147.3 43.2 131.3 38.5 13.4 139.5 40.9 128 37.5 14.9 136.6 40 126.7 37.1 15.3 131.2 38.5 124.5 36.5 16.32173 67 19.4 166.3 48.7 111.3 32.6 12.3 159.6 46.8 108.7 31.9 13.7 152.5 44.7 106 31.1 15 150.2 44 105.1 30.8 15.4 146 42.8 103.6 30.4 16.30.19 72 22.2 179.2 52.5 88.2 25.8 12.6 172.2 50.5 85.7 25.1 13.9 165 48.4 83.3 24.4 15.1 162.7 47.7 82.5 24.2 15.5 158.3 46.4 81 23.8 16.26200 62 16.7 159.9 46.9 155.7 45.6 12.1 151.5 44.4 151.5 44.4 13.5 142.9 41.9 142.9 41.9 14.9 140.2 41.1 140.2 41.1 15.4 135.2 39.6 135.2 39.6 16.32926 67 19.4 174.3 51.1 127.5 37.4 12.5 167.2 49 124.9 36.6 13.8 159.9 46.9 122.3 35.8 15.1 157.5 46.2 121.4 35.6 15.5 153.2 44.9 119.9 35.1 16.20.22 72 22.2 187.3 54.9 98.4 28.8 12.8 179.8 52.7 95.9 28.1 14 172.4 50.5 93.6 27.4 15.1 170 49.8 92.8 27.2 15.4 165.6 48.5 91.4 26.8 16.17792 62 16.7 162.3 47.6 162.3 47.6 12.1 154.2 45.2 154.2 45.2 13.5 145.9 42.8 145.9 42.8 14.9 143.2 42 143.2 42 15.4 138.4 40.6 138.4 40.6 16.33677 67 19.4 179.5 52.6 142.3 41.7 12.6 172.2 50.5 139.7 40.9 13.9 164.7 48.3 137.1 40.2 15.1 162.3 47.6 136.2 39.9 15.5 157.1 46 134.4 39.4 16.20.26 72 22.2 192.2 56.3 107.4 31.5 13 184.6 54.1 105.1 30.8 14 177.2 51.9 102.8 30.1 15.1 174.8 51.2 102 29.9 15.4 173.71 50.9 101.7 29.8 15.66292 62 16.7 189.7 55.6 174.5 51.1 13.9 180.1 52.8 170.4 50 15.6 170.3 49.9 166.4 48.8 17.4 167.2 49 165.1 48.4 18 161.3 47.3 161.3 47.3 19.12969 67 19.4 207.1 60.7 144.4 42.3 14.3 199 58.3 141.3 41.4 16 190.5 55.9 138.1 40.5 17.8 187.7 55 137.1 40.2 18.4 182.5 53.5 135.1 39.6 19.50.19 72 22.2 223.1 65.4 113 33.1 14.6 214.3 62.8 110.1 32.3 16.4 205.3 60.2 107 31.4 18.3 202.3 59.3 106.1 31.1 18.9 196.8 57.7 104.3 30.6 19.97200 62 16.7 191.6 56.2 186.5 54.7 14 182.3 53.4 182.3 53.4 15.7 172.8 50.6 172.8 50.6 17.5 169.7 49.7 169.7 49.7 18.1 164 48.1 164 48.1 19.13398 67 19.4 211.5 62 153.8 45.1 14.3 203.2 59.6 150.7 44.2 16.1 194.6 57 147.5 43.2 17.9 191.7 56.2 146.5 42.9 18.5 186.3 54.6 144.6 42.4 19.60.2 72 22.2 227.5 66.7 118.9 34.9 14.7 218.5 64 116 34 16.5 209.2 61.3 113 33.1 18.4 206.1 60.4 112 32.8 19 200.5 58.8 110.2 32.3 20.1

10649 62 16.7 198.2 58.1 198.2 58.1 14.1 189.3 55.5 189.3 55.5 15.8 180.1 52.8 180.1 52.8 17.6 177 51.9 177 51.9 18.2 171.4 50.2 171.4 50.2 19.35026 67 19.4 222.7 65.3 186.5 54.7 14.6 212.4 62.2 182.9 53.6 16.3 201.3 59 179.1 52.5 18.1 197.7 58 177.9 52.1 18.7 191.2 56 175.6 51.5 19.70.26 72 22.2 238.2 69.8 139.2 40.8 14.9 - - - - - - - - - - - - - - - - - - - -6292 62 16.7 208.8 61.2 182.6 53.5 15.3 201 58.9 179.2 52.5 17.1 192.1 56.3 175.5 51.4 19.1 188.6 55.3 174 51 19.8 182 53.4 171.2 50.2 212969 67 19.4 225.6 66.1 151.4 44.4 15.6 217.6 63.8 148.3 43.5 17.4 209.3 61.3 145.2 42.6 19.4 206.4 60.5 144.1 42.2 20.1 200.9 58.9 142 41.6 21.30.19 72 22.2 243.4 71.3 120 35.2 15.9 234.7 68.8 117 34.3 17.8 225.6 66.1 113.8 33.4 19.8 222.4 65.2 112.8 33.1 20.5 216.3 63.4 110.7 32.4 21.78000 62 16.7 215.7 63.2 206 60.4 15.4 205.7 60.3 201.9 59.2 17.2 195.7 57.3 195.7 57.3 19.2 192.3 56.4 192.3 56.4 19.8 186 54.5 186 54.5 21.13776 67 19.4 234.5 68.7 169 49.5 15.8 226.1 66.3 165.9 48.6 17.6 217.2 63.7 162.6 47.7 19.6 214.2 62.8 161.5 47.3 20.3 208.3 61.1 159.4 46.7 21.50.22 72 22.2 252.6 74 131 38.4 16.1 243.1 71.3 128 37.5 18 233.2 68.4 124.7 36.6 20 229.8 67.4 123.7 36.2 20.7 223.2 65.4 121.5 35.6 21.9

10649 62 16.7 219.7 64.4 219.7 64.4 15.5 210.2 61.6 210.2 61.6 17.3 200.6 58.8 200.6 58.8 19.3 197.4 57.8 197.4 57.8 19.9 191.3 56.1 191.3 56.1 21.15026 67 19.4 243.7 71.4 193.8 56.8 15.9 234.6 68.8 190.7 55.9 17.8 225.2 66 187.4 54.9 19.8 221.9 65 186.2 54.6 20.5 214.8 63 183.7 53.9 21.70.26 72 22.2 261.3 76.6 146.4 42.9 16.3 251.2 73.6 143.3 42 18.2 240.7 70.6 140 41 20.3 237.1 69.5 138.8 40.7 21 230 67.4 136.7 40.1 22.26292 62 16.7 264.6 77.6 216.7 63.5 20.9 253.1 74.2 211.4 62 23.5 241.2 70.7 206 60.4 26.2 237.1 69.5 204.2 59.8 27.1 229.4 67.2 200.7 58.8 28.72969 67 19.4 284.2 83.3 181.6 53.2 21.4 272.8 79.9 176.8 51.8 24 261 76.5 172 50.4 26.6 257 75.3 170.4 50 27.5 249.6 73.1 167.4 49.1 290.1 72 22.2 305.9 89.7 146.3 42.9 21.9 293.9 86.1 141.9 41.6 24.5 281.8 82.6 137.5 40.3 27.1 277.8 81.4 136.1 39.9 27.9 270.2 79.2 133.4 39.1 29.4

8000 62 16.7 277.2 81.3 245 71.8 21.2 265 77.7 239.7 70.3 23.8 250.1 73.3 233.3 68.4 26.4 245 71.8 231.2 67.8 27.3 235.5 69 227.2 66.6 28.83776 67 19.4 298.6 87.5 202.7 59.4 21.7 286.4 83.9 197.9 58 24.3 274.1 80.3 193.2 56.6 26.9 270 79.2 191.7 56.2 27.7 262.3 76.9 188.8 55.3 29.20.12 72 22.2 320.2 93.9 159.7 46.8 22.3 307.7 90.2 155.4 45.5 24.8 295.3 86.5 151.1 44.3 27.4 291.1 85.3 149.6 43.9 28.2 283 83 146.9 43.1 29.7

10649 62 16.7 286.5 84 284 83.2 21.4 271.6 79.6 271.6 79.6 23.9 256.9 75.3 256.9 75.3 26.5 252.1 73.9 252.1 73.9 27.4 243.3 71.3 243.3 71.3 28.95026 67 19.4 312.7 91.6 232.3 68.1 22.1 299.9 87.9 227.7 66.7 24.6 287.3 84.2 223 65.4 27.2 283.1 83 221.5 64.9 28 275 80.6 218.6 64.1 29.50.14 72 22.2 333.7 97.8 178.1 52.2 22.6 320.7 94 173.8 50.9 25.2 308 90.3 169.7 49.7 27.8 303.7 89 168.3 49.3 28.6 301.6 88.4 167.7 49.1 29.01

yticapaC latoTyticapaC latoT SensibleCapacityTotal Capacity Sensible

CapacitySensibleCapacity

300L+

300L

150L+

150L

180L+

180L

215L+

215L

240L+

240L

Total Capacity SensibleCapacityTotal Capacity Sensible

Capacity

ACUM-L+

CADX-L

EWB

Condenser Entering Air Temperature95°F (35°C) 105°F (40.6°C) 115°F (46.1°C) 118.4°F (48°C) 125°F (51.7°C)

Notes:1. See Page 2 for legend2. Ratings are based on 80°F (26.7°C) return air dry bulb temperature.3. Direct interpolation is permissible. Do not extrapolate.4. SKM Computer Selection Software are available for quick and accurate selections..5. Shaded area in gray are at 120°F condenser entering air temperature.* Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical data page 11 should be referred for the same.

Table 5

SKM Split Air ConditionersACUM-L + CADX-L Series - R-22

10

Fan Performance

cfm l/s in.wg Pa RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW1597 754 0.24 59.75 630 0.18 736 0.23 785 0.25 833 0.28 926 0.33 1017 0.39 1129 0.472000 944 0.36 90.18 731 0.31 821 0.37 863 0.4 905 0.43 984 0.5 1060 0.56 1153 0.653193 1507 0.96 239.18 1085 1.15 1145 1.24 1175 1.29 1204 1.34 1261 1.43 1315 1.53 1382 1.651597 754 0.24 59.75 630 0.18 736 0.23 785 0.25 833 0.28 926 0.33 1017 0.39 1129 0.472400 1133 0.53 131.35 844 0.51 922 0.58 960 0.62 996 0.66 1066 0.73 1133 0.8 1214 0.93193 1507 0.96 239.18 1085 1.15 1145 1.24 1175 1.29 1204 1.34 1261 1.43 1315 1.53 1382 1.652196 1036 0.24 59.71 - - 656 0.32 699 0.35 740 0.39 818 0.46 893 0.54 982 0.643000 1416 0.43 107.54 700 0.55 774 0.65 809 0.69 843 0.74 908 0.83 970 0.93 1045 1.054392 2073 0.96 239.14 973 1.6 1026 1.74 1052 1.8 1077 1.87 1127 2.01 1176 2.15 1234 2.322196 1036 0.24 59.71 656 0.32 699 0.35 740 0.39 818 0.46 893 0.54 982 0.643400 1604 0.56 139.76 776 0.78 843 0.88 875 0.94 906 0.99 966 1.1 1024 1.2 1092 1.334392 2073 0.96 239.14 973 1.6 1026 1.74 1052 1.8 1077 1.87 1127 2.01 1176 2.15 1234 2.322196 1036 0.24 59.71 - - 656 0.32 699 0.35 740 0.39 818 0.46 893 0.54 982 0.643400 1604 0.56 139.76 776 0.78 843 0.88 875 0.94 906 0.99 966 1.1 1024 1.2 1092 1.334392 2073 0.96 239.14 973 1.6 1026 1.74 1052 1.8 1077 1.87 1127 2.01 1176 2.15 1234 2.322196 1036 0.28 69.69 674 0.33 716 0.37 756 0.4 834 0.48 907 0.55 996 0.663600 1699 0.74 185.52 851 0.97 913 1.09 942 1.14 972 1.2 1028 1.31 1082 1.42 1148 1.564392 2073 1.13 282.67 1019 1.72 1071 1.86 1096 1.92 1121 1.99 1170 2.13 1217 2.27 1274 2.443208 1514 0.24 59.71 472 0.35 549 0.45 585 0.5 619 0.55 683 0.65 744 0.76 817 0.924800 2265 0.52 130.04 632 1 690 1.14 717 1.21 744 1.27 795 1.42 844 1.56 902 1.756417 3028 0.96 239.21 816 2.29 861 2.46 882 2.55 904 2.64 946 2.82 986 3 1034 3.244604 2173 0.29 71.1 621 0.62 714 0.78 758 0.86 799 0.93 879 1.09 955 1.26 1045 1.496200 2926 0.53 132.42 781 1.37 855 1.58 891 1.68 925 1.79 991 1.99 1054 2.2 1129 2.477792 3677 0.87 215.67 954 2.6 1015 2.86 1044 2.99 1073 3.12 1129 3.39 1183 3.65 1249 3.976292 2969 0.29 71.09 513 0.77 593 0.98 629 1.08 665 1.19 732 1.42 796 1.67 873 27200 3398 0.38 93.5 565 1.09 637 1.32 671 1.44 703 1.56 765 1.81 824 2.07 895 2.41

10649 5025 0.87 215.67 785 3.23 837 3.55 863 3.72 887 3.88 935 4.22 981 4.56 - -6292 2969 0.29 71.09 513 0.77 593 0.98 629 1.08 665 1.19 732 1.42 796 1.67 873 28000 3775 0.47 117 614 1.45 680 1.7 712 1.83 742 1.96 800 2.22 855 2.5 921 2.87

10649 5025 0.87 215.67 785 3.23 837 3.55 863 3.72 887 3.88 935 4.22 981 4.56 - -6292 2969 0.34 84.79 536 0.83 613 1.03 649 1.14 683 1.25 750 1.49 813 1.74 889 2.088000 3775 0.56 139.89 645 1.56 709 1.82 740 1.95 769 2.08 826 2.35 880 2.64 945 3.01

10649 5025 1.04 259.21 831 3.51 881 3.84 905 4.01 929 4.18 975 4.52 1021 4.87 - -300L + 300L

070L + 070L

090L + 090L

100L + 100L

105L + 105L

120L + 120L

150L + 150L

180L + 180L

215L + 215L

240L + 240L

0.5(125) 0.6(150) RPMRange

869to

1084

928to

1157

060L + 060L

ModelACUML

+CADXL

External Static Pressure - in.wg(Pa)AirFlowRate Internal Static

Pressure 0.2(50) 0.4(100) 1.25(312)0.8(200) 1.0(250)

672to

838

780to

973

782to

975

882to

1099

670to

835

785to

979

600to

748

Notes:1- Areas shaded in blue indicate factory setting of rpm.2- Areas shaded in gray indicate operating range outside the standard motor. Shift one step larger motor size in this area.3- Internal static pressure is based on pressure drops through evaporator coil, fan casing & 1” washable flate filter.4- The shown rpm range is with standard pulleys combination.

Table 6

SKM Split Air ConditionersACUM-L + CADX-L Series - R-22

11

Table 9

ELECTRICAL DATA

Table 7

Table 8

Legend

MFA Maximum Fuse Amps (for fuse/circuit breaker sizing), complies with NEC Article 440-22 & 430-52.

MCA Minimum Circuit Amps.(for wire sizing), complies with NEC article 440-33.

ICF Maximum Instantaneous Current FlowRLA Rated Load Amps. (at worst operating condition) LRA Locked Rotor AmpsFLA Full Load Amps

Note :Voltage imbalance not to exceed ± 2 % of the rated voltage

Power Supply: 380V/3Ph/60Hz

MFA MCA ICF QTY RLA LRA QTY FLA LRA FLA LRA060L 32 16 80 1 11 75 1 1.0 3.0 060L 1.5 5.8070L 32 17 75 1 11 70 1 1.0 3.0 070L 1.9 7.8090L 32 20 113 1 12 100 1 2.8 11.0 090L 2.4 10.6100L 50 26 136 1 17 123 1 2.8 11.0 100L 2.4 10.6105L 40 25 69 1 + 1 9 + 9 54 + 54 2 1.0 3.0 105L 2.4 10.6120L 50 30 93 1 + 1 11 + 11 75 + 75 2 1.0 3.0 120L 3.4 14.6150L 50 31 89 1 + 1 11 + 11 70 + 70 2 1.3 3.6 150L 3.4 14.6180L 50 34 122 1 + 1 12 + 12 100 + 100 2 1.3 3.6 180L 4.8 19.2215L 80 49 159 1 + 1 17 + 17 123 + 123 2 2.8 11.0 215L 4.8 19.2240L 80 55 183 1 + 1 19 + 19 140 + 140 2 3.5 16.0 240L 4.8 19.2300L 100 67 195 1 + 1 24 + 24 145 + 145 2 3.5 16.0 300L 6.5 27.3

Model ACUM-

Unit Characteristic Compressor Condenser Fan Motor Evaporator Fan MotorModel CADX-

Power Supply: 460V/3Ph/60Hz

MFA MCA ICF QTY RLA LRA QTY FLA LRA FLA LRA060L 25 13 65 1 8 60 1 1.0 3.0 060L 1.5 6.5070L 32 15 80 1 10 75 1 1.0 3.0 070L 1.9 9.4090L 32 20 115 1 12 100 1 2.8 13.0 090L 2.3 12.6100L 50 25 110 1 16 95 1 2.8 13.0 100L 2.3 12.6105L 32 22 64 1 + 1 8 + 8 50 + 50 2 1.0 3.0 105L 2.3 12.6120L 32 23 75 1 + 1 8 + 8 60 + 60 2 1.0 3.0 120L 3.2 18.0150L 40 28 93 1 + 1 10 + 10 75 + 75 2 1.3 3.6 150L 3.2 18.0180L 50 34 121 1 + 1 12 + 12 100 + 100 2 1.3 3.6 180L 4.4 24.7215L 63 46 131 1 + 1 16 + 16 95 + 95 2 2.8 13.0 215L 4.4 24.7240L 80 50 157 1 + 1 17 + 17 114 + 114 2 3.5 18.0 240L 4.4 24.7300L 100 59 173 1 + 1 21 + 21 125 + 125 2 3.5 18.0 300L 5.6 33.1

Power Supply: 220V/3Ph/60Hz

Model ACUM-

Unit Characteristic Compressor Condenser Fan Motor Evaporator Fan MotorModel CADX-

Power Supply: 220V/3Ph/60Hz

MFA MCA ICF QTY RLA LRA QTY FLA LRA FLA LRA060L 50 26 132 1 17 124 1 1.73 5.2 060L 2.6 9.8070L 63 31 164 1 21 156 1 1.73 5.2 070L 3.3 13.7090L 80 41 185 1 25 164 1 5.4 16.7 090L 4.2 18.5100L 100 50 216 1 32 195 1 5.4 16.7 100L 4.2 18.5105L 63 44 118 1 + 1 16 + 16 91 + 91 2 1.73 5.2 105L 4.2 18.5120L 80 48 154 1 + 1 17 + 17 124 + 124 2 1.73 5.2 120L 5.8 24.4150L 80 58 192 1 + 1 21 + 21 156 + 156 2 2.3 6.9 150L 5.8 24.4180L 100 69 206 1 + 1 25 + 25 164 + 164 2 2.3 6.9 180L 8.1 35.0215L 125 91 257 1 + 1 32 + 32 195 + 195 2 5.4 16.7 215L 8.1 35.0240L 160 97 297 1 + 1 34 + 34 225 + 225 2 6.4 23.7 240L 8.1 35.0300L 200 129 333 1 + 1 47 + 47 245 + 245 2 6.4 23.7 300L 10.7 49.0

Model ACUM-

Unit Characteristic Compressor Condenser Fan Motor Evaporator Fan MotorModel CADX-

SKM Split Air ConditionersACUM-L + CADX-L Series - R-22

12

Typical Wiring DiagramACUM- Models: 060L - 100L

ACUM- Models: 105L - 300L

24V

WHITE

RED

RED

10V

220V

TFR

BLACK

WHITE

BLACK

THERMOSTAT ( BY OTHERS )

RC YG

6AMCB

R Y B

EFM

FIELD WIRING( BY OTHERS )

CADX - L

CCH1

CFM

2

C4 C3

CFM

1

CCH2

C5

EFM

C2

CM2

C1

CM1

C1

CM1

L2L3

L1

N

C1

C2

CM2 CFM1 CFM2

C2C3 C4

RC

CS

HPS1OL

HPS2

LPS1

LPS2

RC G Y1 Y2

L1 L2L1L3

L2L3

FCS1

FCS2

PTB**

CTB

CONTROL CIRCUIT

POWER SUPPLY ( V/Ph/Hz )*

ECB

24V

WHITE

RED

RED

10V

220V

TFR

BLACK

WHITE

BLACK

(ON

/ OFF

)

ON /

OFF

(HP

2)

HP 1

(HP

1)

HP 2

(LP

2)

LP 1

(LP

1)

LP 2

6AMCB

OL

C5

FIELD WIRING & FIELD SUPPLIED DEVICES

C CONTACTOR

CM COMPRESSOR MOTOR

CFM CONDENSER FAN MOTOR

OL OVERLOAD RELAY

EFM EVAPORATOR FAN MOTOR

MCB MINIATURE CIRCUIT BREAKER

CCH CRANK CASE HEATER

CS CONTROL SWITCH

HPS HIGH PRESSURE SWITCH

LPS LOW PRESSURE SWITCH

PTB POWER TERMINAL BLOCK

TFR TRANSFORMER

CTB CONTROL TERMINAL BLOCK

ECB ELECTRONIC CONTROL BOARD

CONTROL CIRCUIT

LEGEND

R Y B

FIELD WIRING( BY OTHERS )

EFM

CADX - A

F1

L1

T5A

L250

V

P1CM

1CM

2P2

INFA

N

RLY9

RLY1

0RL

Y11

RLY8

RLY7

N1

PRI1

SEC1

1

S14

32

IDOD

THERMOSTAT ( BY OTHERS )

OUT

FAN2

RLY2

HTR2

HTR1

X1FA

N1X2

OUT

RLY4

RLY6

RLY5

RLY3

RLY1

GY1

W2

W1

Y2

P-CO

M1

CCH

C2

EFM

C1

CM+

CFM

C1

CM

L2L3

L1**

N

C1

CFM

OL

C2

L1 L2L3

PTB POWER SUPPLY ( V/Ph/Hz )*

FIELD WIRING & FIELD SUPPLIED DEVICES

C CONTACTOR

CM COMPRESSOR MOTOR

CFM CONDENSER FAN MOTOR

OL OVERLOAD RELAY

EFM EVAPORATOR FAN MOTOR

MCB MINIATURE CIRCUIT BREAKER

CCH CRANK CASE HEATER

CS CONTROL SWITCH

HPS HIGH PRESSURE SWITCH

LPS LOW PRESSURE SWITCH

PTB POWER TERMINAL BLOCK

TFR TRANSFORMER

CTB CONTROL TERMINAL BLOCK

FCS FAN CYCLING SWITCH

ECB ELECTRONIC CONTROL BOARD

LEGEND

*

ACUM Models : 060L ~ 100L

Typical Wiring Diagram

ACUM Models : 105L ~ 300L

CTB

F1

L1

T5A

L250

V

P1CM

1CM

2P2

INFA

N

RLY9

RLY1

0RL

Y11

RLY8

RLY7

N1

PRI1

SEC1

1

S14

32

IDOD

OUT

FAN2

RLY2

HTR2

HTR1

X1FA

N1X2

OUT

RLY4

RLY6

RLY5

RLY3

(ON

/ OFF

)

ON /

OFF

(HP

2)

HP 1

(HP

1)RL

Y1

GY1

W2

W1

Y2

P-CO

M1

RC

HP 2

(LP

2)

LP 1

(LP

1)

LP 2

CS

HPSOL

LPS

ECB

TYPICAL WIRING DIAGRAM SHOWN IS SUITABLE FOR 380~ 415V/3Ph/50Hz ONLY . FOR 440V/3Ph/50Hz , PLEASE CONSULT SKM.

** PROVIDE OVERCURRENT, EARTH FAULT PROTECTION, SHORT CIRCUIT AND DISCONNECT MEANS AS REQUIRED BY LOCAL & NATIONAL ELECTRIC CODE. (BY OTHERS)

24V

WHITE

RED

RED

10V

220V

TFR

BLACK

WHITE

BLACK

THERMOSTAT ( BY OTHERS )

RC YG

6AMCB

R Y B

EFM

FIELD WIRING( BY OTHERS )

CADX - L

CCH1

CFM

2

C4 C3

CFM

1

CCH2

C5

EFM

C2

CM2

C1

CM1

C1

CM1

L2L3

L1

N

C1

C2

CM2 CFM1 CFM2

C2C3 C4

RC

CS

HPS1OL

HPS2

LPS1

LPS2

RC G Y1 Y2

L1 L2L1L3

L2L3

FCS1

FCS2

PTB**

CTB

CONTROL CIRCUIT

POWER SUPPLY ( V/Ph/Hz )*

ECB

24V

WHITE

RED

RED

10V

220V

TFR

BLACK

WHITE

BLACK

(ON

/ OFF

)

ON /

OFF

(HP

2)

HP 1

(HP

1)

HP 2

(LP

2)

LP 1

(LP

1)

LP 2

6AMCB

OL

C5

FIELD WIRING & FIELD SUPPLIED DEVICES

C CONTACTOR

CM COMPRESSOR MOTOR

CFM CONDENSER FAN MOTOR

OL OVERLOAD RELAY

EFM EVAPORATOR FAN MOTOR

MCB MINIATURE CIRCUIT BREAKER

CCH CRANK CASE HEATER

CS CONTROL SWITCH

HPS HIGH PRESSURE SWITCH

LPS LOW PRESSURE SWITCH

PTB POWER TERMINAL BLOCK

TFR TRANSFORMER

CTB CONTROL TERMINAL BLOCK

ECB ELECTRONIC CONTROL BOARD

CONTROL CIRCUIT

LEGEND

R Y B

FIELD WIRING( BY OTHERS )

EFM

CADX - A

F1

L1

T5A

L250

V

P1CM

1CM

2P2

INFA

N

RLY9

RLY1

0RL

Y11

RLY8

RLY7

N1

PRI1

SEC1

1

S14

32

IDOD

THERMOSTAT ( BY OTHERS )

OUT

FAN2

RLY2

HTR2

HTR1

X1FA

N1X2

OUT

RLY4

RLY6

RLY5

RLY3

RLY1

GY1

W2

W1

Y2

P-CO

M1

CCH

C2

EFM

C1

CM+

CFM

C1

CM

L2L3

L1**

N

C1

CFM

OL

C2

L1 L2L3

PTB POWER SUPPLY ( V/Ph/Hz )*

FIELD WIRING & FIELD SUPPLIED DEVICES

C CONTACTOR

CM COMPRESSOR MOTOR

CFM CONDENSER FAN MOTOR

OL OVERLOAD RELAY

EFM EVAPORATOR FAN MOTOR

MCB MINIATURE CIRCUIT BREAKER

CCH CRANK CASE HEATER

CS CONTROL SWITCH

HPS HIGH PRESSURE SWITCH

LPS LOW PRESSURE SWITCH

PTB POWER TERMINAL BLOCK

TFR TRANSFORMER

CTB CONTROL TERMINAL BLOCK

FCS FAN CYCLING SWITCH

ECB ELECTRONIC CONTROL BOARD

LEGEND

*

ACUM Models : 060L ~ 100L

Typical Wiring Diagram

ACUM Models : 105L ~ 300L

CTB

F1

L1

T5A

L250

V

P1CM

1CM

2P2

INFA

N

RLY9

RLY1

0RL

Y11

RLY8

RLY7

N1

PRI1

SEC1

1

S14

32

IDOD

OUT

FAN2

RLY2

HTR2

HTR1

X1FA

N1X2

OUT

RLY4

RLY6

RLY5

RLY3

(ON

/ OFF

)

ON /

OFF

(HP

2)

HP 1

(HP

1)RL

Y1

GY1

W2

W1

Y2

P-CO

M1

RC

HP 2

(LP

2)

LP 1

(LP

1)

LP 2

CS

HPSOL

LPS

ECB

TYPICAL WIRING DIAGRAM SHOWN IS SUITABLE FOR 380~ 415V/3Ph/50Hz ONLY . FOR 440V/3Ph/50Hz , PLEASE CONSULT SKM.

** PROVIDE OVERCURRENT, EARTH FAULT PROTECTION, SHORT CIRCUIT AND DISCONNECT MEANS AS REQUIRED BY LOCAL & NATIONAL ELECTRIC CODE. (BY OTHERS)

SKM Split Air ConditionersACUM-L + CADX-L Series - R-22

13

Models: ACUM- 060L & 070LCondensing Unit Dimensional Data

[711]

A4

A3

216[1

52]

[50]

1.97

4

28

[102

4]40

.31

42.2

8[1

074]

6[1

52]

[711]28

A2

A1

FOR ANCHOR BOLTS4-Ø0.79 HOLES[20]

HOLE Ø1CONTROL CIRCUIT

POWER SOURCE

HOLE Ø0.75

[203][40]1.6

LIQ.Ø

[50]8 2

ACCESS FORCOMPRESSOR

SUC.Ø

3

[19]

[25]

ALL DIMENSIONS ARE IN INCHES

4- COMPRESSOR

A1-A4 ARE LOADING POINTS

[762]30

L E G E N D

3- CONTROL PANEL

2- CONDENSER FAN

1- CONDENSER COIL

[mm]

Models: ACUM- 090L & 100L

38[40] [40]

[965]

1.97

[50] 1.6 1.6

A2

[121

9]47

.99

[102

4]40

.31

[152

]6

[965]38

[152

]

A1

6

CONTROL CIRCUITLIQ.ØHOLE Ø0.75

[50][279]11 2

ACCESS FORCOMPRESSOR

[19]

A4

POWER SOURCEHOLE Ø1SUC.Ø

[965]38

[25]

2

A3

[51]

SKM Split Air ConditionersACUM-L + CADX-L Series - R-22

14

Models: ACUM-240L & 300L

Condensing Unit Dimensional DataModels: ACUM-105L, 120L, 150L, 180L & 215L

A3

[254

]10

A1[1

472]

57.9

6

[122

7] AIR IN

3.94

[100

]48

.31

[254

]10

A3

[247

]

Ø0.79 x 4Nos.[20]RIGGING HOLES [1

52]

6

9.72

HOLES Ø 1 1/2 POWER SOURCE

CONTROL CIRCUIT

LIQ.Ø #1

SUC.Ø #1

[38]

[25]HOLES Ø1

4

[1092]43

A4

3

[2032]80

LIQ.Ø #2SUC.Ø #2

2

MODELS: ACUM- 240L & 300L

[254

]10 A1

1

ACCESS

3.94

[100

]

A2

FOR ANCHOR BOLTS4-Ø0.79 HOLES[20]

[20]RIGGING HOLESØ0.79 x 4Nos. [1

52]

6

A

A2

AIR IN

40.3

1

44.2

5*

[112

4]

[102

4][2

54]

10

1

ACCESS

2

110L 215L120L 150L 180L

43

AIR OUT[1092]

16.4[416]A 16.4

[416]16.4[416]

16.4[416] [213]

8.4

FOR ANCHOR BOLTS4-Ø0.79 HOLES

A4

[20]

[mm]ALL DIMENSIONS ARE IN INCHESA1-A4 ARE LOADING POINTS

DIMENSIONMOD E L S ACUM

ADD 145mm FOR MODEL 215FOR UPWARD CONDENSER FAN

*

MODEL: ACUM- 105L, 120L, 150L, 180L & 215L

4- COMPRESSOR

2- CONDENSER FAN

3- CONTROL PANEL

1- CONDENSER COIL

L E G E N D

CONTROL CIRCUITHOLE Ø0.75

SUC. Ø#1LIQ. Ø#1

[25]HOLE Ø1

ACCESS

POWER SOURCE

SUC. Ø#2LIQ. Ø#2

74[1880]

[19]

A3

[254

]10

A1

[147

2]57

.96

[122

7] AIR IN

3.94

[100

]48

.31

[254

]10

A3

[247

]

Ø0.79 x 4Nos.[20]RIGGING HOLES [1

52]

6

9.72

HOLES Ø 1 1/2 POWER SOURCE

CONTROL CIRCUIT

LIQ.Ø #1

SUC.Ø #1

[38]

[25]HOLES Ø1

4

[1092]43

A4

3

[2032]80

LIQ.Ø #2SUC.Ø #2

2

MODELS: ACUM- 240L & 300L

[254

]10 A1

1

ACCESS

3.94

[100

]

A2

FOR ANCHOR BOLTS4-Ø0.79 HOLES[20]

[20]RIGGING HOLESØ0.79 x 4Nos. [1

52]

6

A

A2

AIR IN

40.3

1

44.2

5*

[112

4]

[102

4][2

54]

10

1

ACCESS

2

110L 215L120L 150L 180L

43

AIR OUT[1092]

16.4[416]A 16.4

[416]16.4[416]

16.4[416] [213]

8.4

FOR ANCHOR BOLTS4-Ø0.79 HOLES

A4

[20]

[mm]ALL DIMENSIONS ARE IN INCHESA1-A4 ARE LOADING POINTS

DIMENSIONMOD E L S ACUM

ADD 145mm FOR MODEL 215FOR UPWARD CONDENSER FAN

*

MODEL: ACUM- 105L, 120L, 150L, 180L & 215L

4- COMPRESSOR

2- CONDENSER FAN

3- CONTROL PANEL

1- CONDENSER COIL

L E G E N D

CONTROL CIRCUITHOLE Ø0.75

SUC. Ø#1LIQ. Ø#1

[25]HOLE Ø1

ACCESS

POWER SOURCE

SUC. Ø#2LIQ. Ø#2

74[1880]

[19]

SKM Split Air ConditionersACUM-L + CADX-L Series - R-22

15

Air Handling Unit Dimensional Data

Models: CADX-180L to 300L

1.97

[83]

[341][514] [89] [395][508][690] [660] [1168][1270] [1422]090L [514]

[514]20.2

20.2[514]

25.73[653]

[514]20.2

FORMODELS 150 to 300

[30]

A1-A4 ARE LOADING POINTS

2- EVAPORATOR FAN MOTOR

1- EVAPORATOR FAN

3- EVAPORATOR COIL

4- 1"THK. FLAT FILTER

L E G E N D

1.2

AH

MODELS WITH DOUBLE CIRCUITS.

[25]

ALL DIMESIONS ARE IN INCHES

USE DRAIN SIZE Ø1

*

*

*150L

120L

*

100L

105L [1270] [1422]

[1422]

[1778]58

[1474]

[1270]50

70

56

[1422][1270]50

50

56

56

[mm]

[1168]

[1168]

[1524]

[1168][690] [660]

[660]

[737]30.2[767]

27.2[690]

29

26

[660][690]27.2

27.2

26

26

[508]20

[508]25

[635]60

46

[508]20

2046

46

3.3

LIQ.Ø

SUC.Ø

15.55[395]

[653]

[395]

18.54[395]15.55

15.55

D

W

G

3.50[89]

[89]

[63]2.48

3.50[89]

3.50[514]20.2[514]25.73[653]

20.2[514]20.2

[341]

15.91

13.43[341]

[404]

13.43[341]13.43

E

D

17.48

17.48[444]

[444]

20.2

060L

070L

CADXMODEL

4845

[1219]

[1219]

[1143]45

50

[1143]48

56

L W

JF

DIMENSIONS

[965]

[965]

2425.2

[610]

[610]

[640]25.2

27.2

[640]24

26

H A

38 20[508]

[508]20

20

38

46

B C

15.55

13.03[331]

[331]13.03

[43]1.69

[43]1.69

3.50

17.48

17.48[444]

[444]

20.2

E F

11.38[289]

[289]11.38

13.43

J G

DRAIN Ø3/4CABLEENTRY Ø

[63]2.5

S/A

ACCESS[19]

R/A C

3

MOUNTING HOLES

A24-Ø0.5

1

L

2

[13]A4

4

[165]

6.5

REMOVALFILTER

B

[19]0.75

[38]

[50]

A1

ACCESS

1.5

3.5

[89]

A3

Models: CADX-060L to 150L

[152

]6

REMOVALFILTER

[13]MOUNTING HOLES4-Ø0.5

ACCESS

B

.7[19] [1

02]

4

[2083][1560]240L 61.4 92[2337]

35.2[895]

33.5[850]

1.8[45] [404]

15.91[504]19.8619.86

[504]82

[152]6 52.28

[1328]

[2083][45][850][895][2337]300L [1560]61.4 92 35.2 33.5 1.8

[1328][152][504] [504] [404]15.9119.8619.8682 6 52.28

E

3.3

[83]

2.5[63]

[25]

S/A

FJ

1

DRAIN Ø1Ø 1CABLE ENTRY

[25]

2 4

[635

]

[25]

25

5

[mm]

[1109]52.28[1328][504]

19.86[504]19.86

13.2[334]

D

13.2[334]

E

[152]6

[404]15.91

8.98[228]

F

13.43[341]

J

43.7

G

[50]2

1.5[38]

ACCESS

MODELS: CADX-215L to 300L

2- EVAPORATOR FAN MOTOR

ALL DIMENSIONS ARE IN INCHESA1-A4 ARE LOADING POINTS

W

H

H1

A

D G

L E G E N D1- EVAPORATOR FAN

3- EVAPORATOR COIL

4- 1"THK. FLAT FILTER

W

70

92[1778]

[2337]

MODEL

180L

215L

CADX

[1560]61.4

L

60[1524]

DIMENSIONS

[813]

[850][895]35.2 33.5[843]33.2

H

32

A

1.8[45] [2083]

82

1.2[30]

H1

60[1524]

B

1 L

SUC.Ø#1LIQ.Ø#1SUC.Ø#2LIQ.Ø#2

SKM Split Air ConditionersACUM-L + CADX-L Series - R-22

16

Recommended Suction and Liquid Line Sizes:

Weights:WEIGHTS & LOADING POINTS

lbs lbs lbs lbs lbs lbs lbs lbs lbs lbskg kg kg kg kg kg kg kg kg kg82 86 82 84 335 65 61 53 47 22537 39 37 38 152 29 28 24 21 10283 86 83 85 337 65 61 53 47 22738 39 38 39 153 30 28 24 21 10385 88 85 87 344 79 83 72 71 30538 40 38 39 156 36 37 32 32 138105 109 105 108 427 81 84 73 73 31248 50 48 49 194 37 38 33 33 141141 141 143 143 569 80 84 73 72 31064 64 65 65 258 37 38 33 33 140161 161 162 162 646 87 91 79 78 33473 73 74 74 293 39 41 36 35 152165 165 167 167 662 115 120 104 103 44275 75 76 76 300 52 54 47 47 200166 166 168 168 669 119 133 105 113 47075 75 76 76 303 54 60 48 51 213205 205 207 207 824 170 191 151 161 67393 93 94 94 374 77 87 68 73 305218 218 221 221 879 171 192 152 162 67899 99 100 100 399 78 87 69 74 308221 221 224 224 891 180 202 159 171 712100 100 102 102 404 82 92 72 77 323

180L

215L

AIR HANDLING UNIT CADX

240L

300L

060L

070L

090L

100L

105L

120L

150L

LOADING POINTSTOTAL WEIGHT

A1 A2 A3 A4

LOADING POINTSTOTAL WEIGHT

120L

150L

A1 A2 A3 A4CONDENSING UNIT ACUM

180L

215L

100L

105L

240L

300L

060L

070L

090L

lbs lbs lbs lbs lbs lbs lbs lbs lbs lbskg kg kg kg kg kg kg kg kg kg82 86 82 84 335 65 61 53 47 22537 39 37 38 152 29 28 24 21 10283 86 83 85 337 65 61 53 47 22738 39 38 39 153 30 28 24 21 10385 88 85 87 344 79 83 72 71 30538 40 38 39 156 36 37 32 32 138105 109 105 108 427 81 84 73 73 31248 50 48 49 194 37 38 33 33 141141 141 143 143 569 80 84 73 72 31064 64 65 65 258 37 38 33 33 140161 161 162 162 646 87 91 79 78 33473 73 74 74 293 39 41 36 35 152165 165 167 167 662 115 120 104 103 44275 75 76 76 300 52 54 47 47 200166 166 168 168 669 119 133 105 113 47075 75 76 76 303 54 60 48 51 213205 205 207 207 824 170 191 151 161 67393 93 94 94 374 77 87 68 73 305218 218 221 221 879 171 192 152 162 67899 99 100 100 399 78 87 69 74 308221 221 224 224 891 180 202 159 171 712100 100 102 102 404 82 92 72 77 323

180L

215L

AIR HANDLING UNIT CADX

240L

300L

060L

070L

090L

100L

105L

120L

150L

LOADING POINTSTOTAL WEIGHT

A1 A2 A3 A4

LOADING POINTSTOTAL WEIGHT

120L

150L

A1 A2 A3 A4CONDENSING UNIT ACUM

180L

215L

100L

105L

240L

300L

060L

070L

090L

Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction060L 060L 1/2 7/8 - - 1/2 1 1/8 - - 1/2 1 1/8 - - 5/8 1 1/8 - -070L 070L 1/2 7/8 - - 1/2 1 1/8 - - 5/8 1 1/8 - - 5/8 1 3/8 - -090L 090L 1/2 1 1/8 - - 5/8 1 1/8 - - 5/8 1 3/8 - - 5/8 1 3/8 - -100L 100L 5/8 1 1/8 - - 5/8 1 1/8 - - 5/8 1 3/8 - - 5/8 1 3/8 - -105L 105L 1/2 7/8 1/2 7/8 1/2 7/8 1/2 7/8 1/2 1 3/8 1/2 1 3/8 1/2 1 3/8 1/2 1 3/8120L 120L 1/2 7/8 1/2 7/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 5/8 1 1/8 5/8 1 1/8150L 150L 1/2 7/8 1/2 7/8 1/2 1 1/8 1/2 1 1/8 5/8 1 1/8 5/8 1 1/8 5/8 1 3/8 5/8 1 3/8180L 180L 1/2 1 1/8 1/2 1 1/8 5/8 1 1/8 5/8 1 1/8 5/8 1 3/8 5/8 1 3/8 5/8 1 3/8 5/8 1 3/8215L 215L 5/8 1 1/8 5/8 1 1/8 5/8 1 3/8 5/8 1 3/8 5/8 1 3/8 5/8 1 3/8 5/8 1 3/8 5/8 1 3/8240L 240L 5/8 1 1/8 5/8 1 1/8 5/8 1 3/8 5/8 1 3/8 5/8 1 3/8 5/8 1 3/8 3/4 1 3/8 3/4 1 3/8300L 300L 5/8 1 1/8 5/8 1 1/8 3/4 1 3/8 3/4 1 3/8 3/4 1 3/8 3/4 1 3/8 3/4 1 5/8 3/4 1 5/8

ACUM CADX

25 (7.6)Circuit A Circuit B

Models

Circuit A Circuit B

PIPE LENGTH - FEET (m)

Circuit A Circuit B75 (22.9)

Circuit A Circuit B50 (15.2) 100 (30.5)

Notes : 1. Pipe diameters are based on equivalent length of copper tubing sizes. 2. Pipe sizes are based on 2ºF (1.1ºC) or less temperature losses for liquid and suction line in equivalent pipe length. 3. If the condensing unit is below the evaporating unit, the maximum lift should not exceed to 66 feet. 4. Do not exceed 100 feet piping length without checking with SKM. 5. These sizes are for guidance only. For detailed proper piping, refer to recognized piping references like ASHRAE Guide and Data Book.

Table 10

Table 11

The recommended or required suction and liquid line sizes do not necessarily correspond with the refrigerant connections available on the outdoor or indoor unit. Necessary transformation may be required and it’s field performed.

SKM Split Air ConditionersACUM-L + CADX-L Series - R-22

17

Recommended Clearances

[762]30

UNIT CLEARENCE

[762]30

30

SPACING FOR AIR FLOW

ALL DIMENSIONS ARE IN INCHES[mm]

SPACING FOR SERVICE

30

[762]

30

[762]

30

[762] [762]SINGLE UNITACUM- 060L to 100L

MULTIPLE UNIT

ACUM- 060L to 100L

[762]30

[762]30

[762]

30

[1143]

45[762]

30

SINGLE UNIT

[1321]52

ACUM- 105L to 300L

UNIT CLEARENCE

[1321]52

52[132

2]

52

[762

]30

[2235]88

52

SPACING FOR SERVICE

[1321]52

SPACING FOR AIR FLOW

[762

]

[132

2]52

30

[132

2]52

30 [762

]

[132

2]

[132

2]

[762

]30

[1321]52

[132

2]52

[762

][132

2]52

30[762

]

[132

2]52

30

MULTIPLE UNIT

SKM Split Air ConditionersACUM-L + CADX-L Series - R-22

18

Installation and Commissioning• Install the unit in such a location which is flat and strong enough to support its weight.

• All field wiring must comply with applicable local and national codes.

• Service spacing should be provided as shown in the figure. If any obstacles are around the unit, distributed air is short-circuited so that the unit stops frequently and access to the unit is difficult for inspection and aftersales services.

AIR OUT

SUCTIO

N

LIQUID

POWERCIR

CUIT

CONTRO

L

CIRCUIT

No obstacle

AIR OUT 3000mm

ACUM-105L to 180L

LINE

LINE

AIR IN AIRIN

SPACING FOR SERVICE

INSTALLATION& COMMISSIONING

CONTRO

L

PANEL

AIRIN

SUCTIO

N

LINELIQU

IDLINE

AIR IN

No obstacle

3000mm

AIR OUT

AIR IN

No obstacle

PANELCON

TROL

AIRIN

LINELIQUID

LINESUC

TION

AIR IN

SPACING FOR AIRFLOW

AIR OUT

AIR OUT 3000mm

A IRIN

AIR IN

AIRIN

LINELIQUID

SUCTIO

N

LINE AIR IN

CONTRO

L

PANEL

AIR IN

3000mm

No obstacle

ACUM-060L & 070LPOW

ER

CIRCUIT

CONTRO

L

CIRCUI

TAIR

IN

AIRIN

CONTRO

L

CIRCUIT

CIRCUI

T

POWER

LIQUID

SUCTIO

N

ACUM-215L to 300L

AIR INLINE

LINE

CONTRO

L

ACUM-090L & 100LPOW

ER

CIRCUIT

CIRCUI

T

CONTRO

L

PANEL

LINESUCTIO

N

LINELIQUID

AIRIN

SKM Split Air ConditionersACUM-L + CADX-L Series - R-22

19

Typical Refrigeration Piping

Correct design and size of refrigerant piping is necessary to proper operation. The refrigerant piping generally should be designed to accomplish the following:

a) To ensure proper refrigerant feed to the evaporator.

b) To provide practical refrigerant line sizes without excessive pressure drop.

c) To maintain uniform return of lubricating oil to the compressor.

d) To prevent refrigerant from entering the compressor and causing compressor damage due to “slugging”.

INVERTED TRAP WITHOUT PUMP DOWN CONTOL.

5 6

*

43

DOTTED WITH PUMP DOWN CONTROL.*

12

INSIDE CADXEXPANSION VALVENOTE:-

R/A

EXPANSION VALVEINSIDE CADX

NOTE:-

6 SUCTION LINE5 LIQUID LINE4 SHUT OFF VALVE

L E G E N D

2 SOLENOID VALVE1 SIGHT GLASS

3 FILTER DRIER

4 SHUT OFF VALVE5 LIQUID LINE6 SUCTION LINE

1 SIGHT GLASS

3 FILTER DRIER2 SOLENOID VALVE

L E G E N D

ACUM L

R/A

6

5

ACUM L CADX L

43

21

CADX L

Refrigerant Piping:

SKM Split Air ConditionersACUM-L + CADX-L Series - R-22

20

Evaporator coil shall be constructed of inner grooved copper tubes 3/8” OD mechanically bonded to aluminum cross wave fins. Coil consists of headers of seamless copper tubing, thermostatic expansion valve(s) & multi-circuited distributor(s). These coils shall be tested against leakage by air pressure of 300 psig (2068 Kpa) under water, cleaned & dehydrated at the factory. Coil shall conform to AHRI-410.

GUIDE SPECIFICATIONS

Split air conditioner shall be composed of a ceiling suspended air handling unit & floor mounted air cooled condensing unit, rated in accordance with AHRI standards 210 / 240 and 340 / 360.Unit should be capable to operate in a wide range of ambient temperatures from 50°F (10°C) to 125°F (51.7°C) and shall be selected in accordance with project requirements and installed as per Instruction, Operation & Maintenance Manual.

Compressor shall be hermetically sealed, compact high efficiency and low noise scroll type. These compressors are refrigerant gas cooled, furnished with advanced scroll temperature protection or internal motor protection.

Condenser coils shall be air cooled with integral sub cooler, constructed of special inner grooved seamless copper tubes 3/8” OD mechanically expanded into waffle louver aluminum fins . These coils shall be tested against leakage by air pressure of 450 psig (3100 kPa) under water, cleaned & dehydrated at the factory.

The panel shall be factory wired and confirm to IP-54 requirements. Control panel shall contain compressor and motor starting contactors, electronic control board for unit operation, compressor anti-recycle time delay, control on/off switch, control circuit breaker and power & control terminal blocks. High and Low pressure switches should be provided for protection.

EVAPORATOR FAN AND MOTORFans of evaporators shall be forward curved, double inlet double width (DIDW), centrifugal type, Statically & dynamically balanced, mounted on a single heavy duty statically & shaft with permanently lubricated bearings & driven by V belt with an adjustable variable pitch motor pulley. Motor shall be Totally Enclosed Fan Cooled (TEFC), 4 poles, class-F insulated, minimum IP55 protection & wired to unit control panel.

FILTERSAir handling units shall be provided with air filter. Filter should be 1” (25mm) standard or 2” (50mm) thick optional washable aluminum media with average dust arrestance 54% based on ASHRAE standards 52.1.

CONDENSER COIL(S)

COMPRESSOR

CONDENSER FAN(S) & MOTOR(S)

CONTROL PANEL

CONDENSING UNIT

Condenser Fans shall be direct driven propeller type discharging air vertically upward, equipped with statically & dynamically balanced aluminum alloy blades, inherent corrosion resistant shaft & PVC coated steel wire fan guard. Condenser fan motor(s) shall be Totally Enclosed Air Over (TEAO), 6 poles with class-F insulation, minimum IP55 protection & wired to unit control panel.

Units casing shall be made of hot dip galvanized steel sheets (zinc coated) conforming to JIS-G3302 and ASTMA525 that shall be phosphatized and then electrostatically dry powder coated of approx 60 microns to provide an extremely tough, scratch resistance, excellent anti corrosive protection that can pass 1000 hours in 5% salt spray testing at 95°F relative humidity as per ASTM B117.

CONDENSING UNIT CASING

AIR HANDLING UNIT CASINGThe unit casing for CADX-L is made of zinc coated galvanized steel sheets conforming to JIS-G3302 and ASTM A525 which is phosphatized and baked after an electrostatic powder coat of approximately 60 microns. This finish and coating can pass a 1000 hour in 5% salt spray testing at 95°F (35°C) and 95% relative humidity as per ASTM B117. Panels and casing are insulated with 1” (25mm) thick fiberglass (with BGT coating) thermal and acoustic insulation having density of 2 lb/ft³. (32 kg/m³) and thermal conductivity of 0.23 BTU.in/ft²°Fh (0.033 W/m°K). Insulation meets the requirements of NFPA 90A and 90B for fire resistance.

The condensing unit shall be composed of compressor(s), coil(s) and condenser fan(s) and motor(s).

GENERAL

EVAPORATOR COIL

REGIONAL OFFICES

For SKM Distributors visit: www.skmaircon.com

Email: [email protected]

Spare Parts DivisionEmail: [email protected]

Service Centre

HEAD OFFICEP.O Box: 6004Sharjah, United Arab EmiratesTel: +971 6 514 3333Fax: +971 6 514 3300Email: [email protected] Email: [email protected]

KuwaitDasmanP.O Box: 1215-PC 15463Tel: +965 2 2492200Fax: +965 2 2494400Email: [email protected]

SKM Air Conditioning Factory Eastern provinceAD Dammam2nd industrial cityAbqiq main road Hail StreetTel: +966 3 8123332 / 4 / 5Fax: +966 3 8123337 / +966 3 8123092Email: [email protected]

Saudi Arabia (Production Facility)

AlgeriaAissat Idir ( EX-ENMA) CityBldg1, Flat 2, Dar El Beida AlgiersTel: +213 21 508197Fax: +213 21 508197Email: [email protected]

Abu DhabiP.O Box: 27788Tel: +971 2 6445223Fax: +971 2 6445145Email: [email protected]

United Arab EmiratesDubaiP.O Box: 98822Tel: +971 4 2940900Fax: +971 4 2940029Email: [email protected]

Al AinTel: +971 3 7619921Fax: +971 3 7619941Email: [email protected]

078/2015Supersedes # 078/2014