Product Features
• Highenergyefficiency
• Instantaneoushotwateravailability
• Electronictemperaturecontrol
• Optimisedheatingtemperaturecontrolasstandard
• Standbymodetemperaturecontrol
• Lowreturntemperaturesbacktothenetwork
Heat Interface Units
• Lowcarbonheatnetworks–Compatiblewithrenewableenergysources
• Weathercompensationoptionavailable
• Includeslowenergypump
• Suitableforradiatorsorunderfloorheatingsystems
• Requiresminimalmaintenancereducingrunningcosts
Mib
ec D
esig
n G
uide
Tel: +44 (0)1948 661639 Web: www.mibec.co.uk2
Heat Interface Units
Advantages for Designers, Developers and Architects
• IndividualgassupplytoeachpropertyisnotrequiredwhenusingHIUs
• Nofluesarerequiredtoevacuateexhaustcombustion,savingcosts
• Storagecylinderarenotrequired,reducingcostsandincreasingavailablespace
• Meetslowemissionandefficiencytargets
Advantages for Installers
• Easytoinstall,addonlyaprogrammableroomthermostattocompletethesystem
• Compactandlightweight
• Minimalinstallationrequirementsforpipework
• Simplemaintenanceandeasyaccesstoallcomponentsinsidethebox
Communal Heat NetworksAcentralboilerhouseorrenewablesourcewillgenerateheatwhichisdistributedthroughanetworkofpipetoeachseparatepropertyinthebuilding.EachhomeorapartmenthasitsownHeatInterfaceUnit(HIU)installed,whichusesheatdistributedfromthecentralnetworktoprovideheatingandhotwaterforuseinthehome,replacingtherequirementforindividualboilersineachproperty.
Advantages for Landlords
• Reducedserviceandmaintenancecostscomparedtoindividualboilers
• Meteredenergyusageforfairertenantbilling
• Practicalforcombiningwithlowercostrenewabletechnologiesforthecentralheatsource
• Noindividualfluestomaintainforhealthandsafetylaws
Advantages for the Homeowner or Tenant
• Sharedmaintenancecostsacrossthepropertiesonthenetwork
• Noboilerworries
• Efficientlycontrolledheatingandhotwatersupply
• Accuratebillingforonlytheactualenergyused
• Awarenessofenergyconsumptionpromotesenergysavinginthehome
3
Mib
ec D
esig
n G
uide
Tel: +44 (0)1948 661639 Web: www.mibec.co.uk
Heat Interface Units
The Hiper HIU Features
PID Control Unit(Proportional-Integral-Derivative)maintainstheefficiencyoftheHIU.Providestabletemperaturesundervaryingloadconditions.Uniquealgorithmsconstantlyrecalculatetheamountandthespeedofmodulationrequiredformaximumefficiency.
Pressure Independent ControlIntegralPICvalvewithelectricactuatorgivingproportionalmodulatingcontrolasinstructedbythePIDController,100%authority,(regardlessofpressurefluctuationsinthedistrictheatingsupply).UnlikemanyotherHIU,furthercontrolvalves(forexampleDifferentialPressureControlValves)arenotrequired.
Anti-Scale ControlIntheDomesticHotWater(DHW)PlateHeatExchanger(PHE)-theflowisalwaysdivertedawayfromtheDHWPHEintotheHTGPHEreducingthescaleformationpotential.
Automatic Fault DiagnosticsThecontrolunitcanidentifyfaultstocomponentswithintheHIUandissuesanidentifyingfaultcodeonthedisplay.Oncethefaultorerrorhasbeenrectifiedthecontrolunitwillautomaticallyresetandresumenormaloperation.
Heating Flow Automatic LimitationDecreasingthepossibilityofstarvingtheDomesticHeating(DH)circuitwhenextremedemandsaremadeontheentirenetwork.Forexampleincoldweatherwhenalargeheatingdemandismadeonthenetworkthecontrolunitdoesnotallow100%openingonstartupandpreventsthe‘overdemand’causingdisruptions.
Instant Hot Water ResponseInstantwaterresponseisguaranteedbykeepingheat(suppliedbythedistrictsupply)closeathandtotheHIUatalltimes.Atregularintervals(factorysetto20minutes),thecontrolleropens(factorysetto2min)thePICvalvetodeliveralowflowofabout100l/hr,thenclosesthevalveagain.ThisrepeatswhenevertheHIUisonstandbywhenthereisnodemand.
Optimised Heating ControlThereturntemperaturesareautomaticallymonitoredandcontrolled.ThecontrolleroftheHIUusesthisinformationtomaintaintheoptimumflowtempera-tureandkeeptheDISTRICTreturntemperatureaslowaspossible.ThiscanbeseenonthedisplayscreenasAUTOandisthefactorysetting.
DHWS PriorityDomesticHotWaterSupply(DHWS)isthepriorityoperationoftheHIU.AflowswitchdetectsthedemandattheHIU(ifinheatingmode)andswitchestoDHWproduction.Eveniftheheatingsystemisinfaultmode,theHIUwillstillproduceDHWS.
High DHW temperature safetyIfforwhateverreasonun-managedhotwateratextremetemperatureweretopassthroughthePlateHeatExchanger(PHE),thereisathermostaticlimitingvalveontheDHWexit.Thisislockedandfactorysetto60C.Beingnon-electricalthisstillmaintainsthesafetyfeatureevenwhenelectricsupplytotheHIUiscut.
Proven reliable componentsLowenergyErp(EnergyRelatedProducts)compliantpump.UniqueinletBlockwithByPass,testpoints,metersensorportandauniquelydesignstrainerwithincreasedsurfaceareaforlongeroperationwithoutblockingorreducedperformanceoverastandardpatternYStrainer.
Low & High Pressure protection for the HIULowpressureswitchwillstopthecirculatingpumpshouldthesecondarysystemdropbelow0.7Bar.TheHIUisfittedwithaSafetyReliefvalvesetat3barforhighpressureprotection.
Underfloor HeatingTheunitisfullycompatiblewithlowtemperaturesystemssuchasthoseinUFH.Theinstallersimplysetstherequiredvaluefortemperatureoninstallation.Fulldetailsareavailableintheinstallationmanual.
InsulationTheHIUpanelsareallfullyinsulatedincludingthebackplatetopreventoverheatingofthesurroundingarea.
Prepayment BillingCanbeaccommodatedwithanaccessorykittoshutdowntheunitwhenthetenantisnolongerincredit.
SecurityThemetalcasingcanbeclosedtopreventunauthorisedtamperingwithoptionalfixingboltsavailableonrequest.
HIU Hibernation modePressthestartbuttonandholdfor3secondsandtheHIUwillshut-down.ThePICVvalvewillshut,andheating,hotwaterandstandbyfunctionswillbedisabled.Pressthestartbuttontoresumenormaloperation.Thisisafunctionforwhentheapartmentisunoccupiedorforthetenantduringholidayperiods.
Mib
ec D
esig
n G
uide
Tel: +44 (0)1948 661639 Web: www.mibec.co.uk4
Heat Interface Units
The Hiper HIU Features
Proven PerformanceTheHIPERHIUhasbeenindependentlytestedandprovedconformstotheBritishStandardBSEN132-01-‘Gasfireddomesticappliancesproducinghotwater–Appliancesnotexceeding70kWheatinputand300ltwaterstoragecapacity–Part1,assessmentofperformanceofhotwaterdeliveries’.
TheHIUwastested,awarded2Stars,andmeasuredondeliveryofDHWat55C,withaDHflowtempof70C.Furtherdetailsandcopytestreportavailabletoallqualifiedenquiries.
Product OverviewTheHiperHIUiscompactandrequiresverylittlespaceinthepropertyandiseasytoinstall.Thedesignmeetsallvaryingdemandsofthehome.
InmanyrespectsaHIUislikeacombiboiler,providingcentralheatingandinstantaneoushotwater,butwithoutcombustionorneedingaflue.
Special Features
•Highenergyefficiency
•Instantaneoushotwateravailability
•Electronictemperaturecontrol
•Optimisedheatingtemperaturecontrolasstandard
•Standbymodetemperaturecontrol
•Lowreturntemperaturesbacktothenetwork
•Lowcarbonheatnetworks–Compatiblewithrenewableenergysources
•Weathercompensationoptionavailable
HiperXi45INDIRECTHIU45DHW/10HTG
PartCode:HIPER4510
HiperXi60INDIRECTHIU60DHW/10HTG
PartCode:HIPER6010
HiperXi60LINDIRECTHIU60DHW/15HTG
PartCode:HIPER6015
HiperXi70INDIRECTHIU70DHW/15HTG
PartCode:HIPER7015
Product Range
5
Mib
ec D
esig
n G
uide
Tel: +44 (0)1948 661639 Web: www.mibec.co.uk
Heat Interface Units
The Hiper HIU Dimensions
heat interface units Dimensions
Mib
ec D
esig
n G
uide
Tel: +44 (0)1948 661639 Web: www.mibec.co.uk6
Heat Interface Units
The Hiper HIU Internal Schematic
heat interface units internal schematic.
1 Electronic PID Controller
2. Room Thermostat (not supplied)
3. Isolation valves (Secondary side)
3A Isolation valves (District side)
4. PICV (Pressure Independent Control valve)
4A PICV Actuator with step motor
5 Circulating Pump for the central heating
6 3 port Diverting Valve
7 DHW Plate Heat Exchanger
8 DHW temperature sensor
9 Flow switch
10 Central Heating Flow temperature sensor
11 Central Heating Return temperature sensor
12 Central Heating Plate Heat Exchanger
13 Pressure Switch
14 Safety Valve
15 Filling Loop Connection
16 Pressure Gauge
1
District (Primary) FLOW
DHW Supply
3
3
Cold water mains
Central Heating
3
13
4
4A
3A
3A
District (Primary) RETURN
2
3
5
6
7
8
9
10
11 12
14
15
16
SV Discharge Pipe
Central Heating RETURN
Central Heating FLOW
1 ElectronicPIDController
2 RoomThermostat(notsupplied)
3 Isolationvalves(Secondaryside)
3A Isolationvalves(Districtside)
4 PICV(PressureIndependentControlvalve)
4A PICVActuatorwithstepmotor
5 CirculatingPumpforthecentralheating
6 3portDivertingValve
7 DHWPlateHeatExchanger
8 DHWtemperaturesensor
9 Flowswitch
10 CentralHeatingFlowtemperaturesensor
11 CentralHeatingReturntemperaturesensor
12 CentralHeatingPlateHeatExchanger
13 PressureSwitch
14 SafetyValve
15 FillingLoopConnection
16 PressureGauge
7
Mib
ec D
esig
n G
uide
Tel: +44 (0)1948 661639 Web: www.mibec.co.uk
Heat Interface Units
The Hiper HIU Product Details
Proportional ControlAproportionalcontrolsystemisnotsimplyturningtheCHandDHWSonandoff,itfeedsinthesupplyfromtheDistrictsideinproportiontothedemand.Thisgivesstablehotwatersupplytemperatures,evenatverylowdemands.
Theheatingissimilarlycontrolledformaximumefficiency,astheroomwarmsupthecontrollerstartstolowertheamountofheatbeingallowedintothePHEsupplyingthecentralheatingalwaysmaintainingminimumenergyusage.
TemperatureandflowsensorsintheunitsendconstantinformationbacktothePID(Proportional-Integral-Derivative)controlunitwhichinturnsignalsthePICVtomodulateasrequiredtomeetthedemandandmaintaintemperaturestability.
Design and ConstructionTheunitisdesignedfortheplateheatexchangerstobeatthefronttoalloweasyaccess.Thesearemountedontopurposemadebrassblockswhichcontaintheintegralwaterwaysandcomponentconnectionpoints.Inter-connectingpipeworkiskepttoaminimum.
A
B
C
A-BrassManifoldBlocksB-DivertingValveC-PICVwithElectronicModulatingActuator
Description - Hiper Indirect HIU
• FittedwithtwoPlateHeatExchangers(PHE)oneforheating(CH)andoneforhotwater(DHWS)
• Theelectronicsprovide‘PROPORTIONAL’reactivecontroltodemand.PIDelectroniccontroller
• IntegralPICV(PressureIndependentControlValve).OnePICVreplacesthreeseparatevalvesthatwouldotherwiseberequiredtomaintainthemaximumlevelofsystemcontrolsotheHIUcanoperateeffectively
• Maximumefficiencywithlowestreturntemperaturesbackintothenetworkreducingrunningcosts
• Safetywithhightemperaturelimitsenforcedevenwithoutanelectricitysupplyon
• Systemscanbedesignedwithlittlerequirementforexpensivecommissioning
• Simpletomaintain,theplateheatexchangerscanbeaccessedandremovedinjustminutes
• PlateHeatExchangersaccessfromthefront• Insulatedwithatamperproofsteelcasing• HighqualityWilolowenergypump,fixedor
variablespeed• Automaticairventand3drainpoints• 3barsafetyreliefvalveonthesecondaryheating
side• Largesurfaceareastrainermeshforextended
maintenanceschedules• Sealedsystemheating• Thermostatichightemperatureprotection.• Flatfaceunion,3/4”connections
Mib
ec D
esig
n G
uide
Tel: +44 (0)1948 661639 Web: www.mibec.co.uk8
Heat Interface Units
The Hiper HIU Components
heat interface units
1
3
4
5
6
7
8 9 10
11
12
13
14
15
16 2
components
1 District connection block inc. strainer
2 Electronic PID Controller
3. PICV (behind the controller)
4 Central Heating Plate Heat Exchanger
5 DHW Plate Heat Exchanger
6 Automatic Air vent
7 Circulating Pump for the central heating
8 Safety Valve
9 Pressure gauge
10 Flow switch
11 Filling Loop connection
12 Thermostatic High Temp. Limit Valve
13 Expansion Vessel
14 Diverting valve
15 Spacer for installation of Heat meter
16 Bypass valve
1 Districtconnectionblockinc.strainer
2 ElectronicPIDController
3 PICV(behindthecontroller)
4 CentralHeatingPlateHeatExchanger
5 DHWPlateHeatExchanger
6 AutomaticAirvent
7 CirculatingPumpforthecentralheating
8 SafetyValve
9 Pressuregauge
10 Flowswitch
11 FillingLoopconnection
12 ThermostaticHighTemp.LimitValve
13 ExpansionVessel
14 Divertingvalve
15 SpacerforinstallationofHeatmeter
16 Bypassvalve
9
Mib
ec D
esig
n G
uide
Tel: +44 (0)1948 661639 Web: www.mibec.co.uk
Heat Interface Units
The Hiper HIU Operation
1 2 3
Switch on the Power SupplyWhenpowered-upforthefirsttime,thecontrollerwillgothroughadiagnosticscheckoftheHIU.Thismaylastafewsecondsandthedisplayshowsa‘timedout’rotatingsymbol(seeabove).Ifaproblemisdetectedthecontrollerwilldisplayan‘ERROR’symbol.(seeinstalleroruserguideforfulldetails
HIU is now on stand-byHavingcompleteditschecks,thecontrollerisnowreadytobeused.Untilademandiscreateditwillremaininstandbymode.
Turn on a hot water tapThehotwatertemperatureisfactorysetto55oC(theindustryrecommendedtemperature).OncetheHIUcontrollersenseswaterflowitwillcommencetheproductionofhotwaterimmediately,andstabiliseatthesettemperature.
Turn the tap off(nodemandforhotwater)
Thescreenwillshowthe‘standby’symbol(seeabove).
Room thermostat(callsforheating………..)
TheHIUnowoperatesinheatingmode,andthedisplayshowsthesetflowtemperature.Anydemandforhotwaterwilltakepriority.
1 2 3
Factory Settings•DHWSat55oC•CentralHeatingat60oC
Mib
ec D
esig
n G
uide
Tel: +44 (0)1948 661639 Web: www.mibec.co.uk10
Heat Interface Units
The Hiper HIU Technical Specification for Hiper Xi45 and Xi60
Technical Parameters Xi45 Xi60
PRIMARY(heatsupplyfromcommunalheatsource)MAXIMUMTEMPERATURE 16bar 16Bar
PRIMARY(heatsupplyfromcommunalheatsource)MAXIMUMpressuredifferential 90oC 90oC
SECONDARY(centralheatingcircuitintheflat,apartmentorhouse)MAXIMUMPRESSURE 4bar 4bar
SECONDARY(centralheatingcircuitintheflat,apartmentorhouse)MAXIMUMTEMPERATURE 3bar 3bar
SECONDARY(centralheatingcircuitintheflat,apartmentorhouse)TEMPERATUREADJUSTMENT 85oC 85oC
SECONDARY(centralheatingcircuitintheflat,apartmentorhouse)HEATINGOUTPUT 20oCto85oC 20oCto85oC
DOMESTICHOTWATER(includingcoldwatersupplymain)MAXIMUMPRESSURE 10Kw 10Kw
DOMESTICHOTWATER 60oC 60oC
MAXIMUMTEMPERATURELIMITEDbyTMVDOMESTICHOTWATER 30oCto65oC 30oCto65oC
TEMPERATUREADJUSTMENT 45kW 60kW
11
Mib
ec D
esig
n G
uide
Tel: +44 (0)1948 661639 Web: www.mibec.co.uk
Heat Interface Units
The Hiper HIU Specification Planning List
Domestic Hot water specification Required Value submitted by the System Design House Actual confirmed
DHWLOAD(Kw)
DHWtemperaturerequirements
DHWflowraterequirements
Central Heating Specification Required Value submitted by the System Design House Actual confirmed
HeatingLOAD(Kw)
Heatingflowdesigntemperature
Primary (District) specification Required Value submitted by the System Design House
PRIMARY(District)Flowtempera-ture
PRIMARY(District)Returntemper-ature
PressureDropacrossthePrimaryFlowandreturn
Cold water Required Value submitted by the System Design House
ColdWater(inlet)designtempera-ture
ColdWater(inlet)designpressure
Additional Specification Required Value submitted by the System Design House
Pleaseforwarddetailsonthesystemwithyourenquiry(pleasevisitwww.mibec.co.uktocontactusorcallon1948661639.
Pleasecompletethetableasbelow,andwithanyadditionalinformationthatisrelevanttotheproject.Wecanneverhavetoomuch!
Mibec LimitedParkViewBusinessCentre
CombermereWhitchurchShropshire
UnitedKingdomSY134AL
Tel:+44(0)1948661639Fax:+44(0)1948871794
Web:www.mibec.co.uk