Harmonic Analysis Report & Recommendation - JL · PDF fileM/S JL Seagull power products...
Transcript of Harmonic Analysis Report & Recommendation - JL · PDF fileM/S JL Seagull power products...
JL SEAGULL POWER PRODUCTS,
#5, P.R. Complex,
New No.38 (Old No.22)
Thambiah Road Extension,
West Mambalam,
Chennai – 600 033
Off: +91 44 2484 9797
Prepared By,
GNANASOUNDAR M
JL SEAGULL Power Products
Harmonic Analysis Report & Recommendation
Customer:
Approved By,
S. Panneer Selvam, M.E., M.S., (Mgmt.,)
Proprietor
JL SEAGULL Power Products
Email: [email protected], [email protected]
Mobile: +91 98412 97730
Table of Content
Objective of this study:
S. No. Description Page
1) Objective of this study 3
2) TNEB notification details
3
3) CEA Standard - Voltage and Current Harmonics 3
4) Instrument Detail 3
5) IEEE 519 4
6) Harmonic Analysis Report
7) Recommendation and Load & Harmonic details and 5
8) Sematic Diagram
7
9) 500 KVA Transformer LT Side 8-17
10) Appendix 18-19
M/S JL Seagull power products (Distributor for Schaffner Harmonic Filter) studied in Customer name
to assess the Harmonic level on 500KVA transformer LT side. Objective of this study is to assess the
Harmonics level whether the same is within the level prescribed by the notification from TNEB.
TNEB NOTIFICATION DETAILS:
1) Determination of Tariff for Generation and Distribution; Order No. 1 of 2012 dated 30-03-
2012 (Effectivefrom01-04-2012)
2) Ministry of Power (Central Electricity Authority) Notification No: 12/X/STD (CONN)/GM/CEA
(21-Feb-07)
As per the above notification, Harmonics shall be within the limits given below:
CEA Standard –Voltage and Current Harmonics
(1) The total harmonic distortion for voltage at the connection point shall not exceed 5% with no
individual harmonic higher than3%.
(2) The total harmonic distortion for current drawn from the transmission system at the
Connection point shall not exceed 8%.
As specified in the Supply Code, when the consumer fails to provide adequate harmonic suppression
equipment to avoid dumping of harmonics beyond the limits as specified by CEA regulations in to
Licensee’s distribution system, they are liable to pay compensation at 15% of the respective tariff.
As and when the consumer brings down the harmonics within the limit, compensation charges shall
be withdrawn.
Instrument Used:
FLUKE 435 –II Power quality Analyzer –Accuracy Class –A meeting
International Standard –IEC 61000-4-30 / EN50160 and TNEB requirement
IEEE 519:
Harmonic Recommendation
Solution& Recommendation:
S. No. Location Active
Harmonic
Filter (AHF)
Size
Arrangement of filter Part No. Capacitors
1) LT side
Transformer 500KVA
1x60A 1 No of 60 A
FN3430-60-400-4 APFC should be Detuned
Harmonic Analysis Report:
Load and Harmonics Details: (with APFC)
S.
No.
Measured
Location Reference
Load
Current
(A)
(RMS)
Fundamental
Current (A)
THDi
(%)
THDv
(%)
Active
Power
Total
(KW)
Apparent
Power
Total
(KVA)
Reactive
Power
Total
(KVAR)
Power
Factor
Total
Harmonic
Compensat
ion Current
(A)
Harmonic
Compensat
ion Current
(A) with
20%
Cushion
1)
500 KVA
Transformer
LT Side
@ Maximum
RMS
Current(A)
634.8 633.8 7.44 1.7 363.95 405 180.4 0.98 47.2 56.64
@ Maximum
THDi% 295.4 293 18.29 1.9 215.3 220.05 31.7 0.98 53.6 64.32
@ Maximum
Harmonic
Compensation
Current (A)
373.8 373 17.02 2.05 252.05 256.3 52.45 0.98 63.48 76.16
Load and Harmonics Details: (Without APFC)
S.
No.
Measured
Location Reference
Load
Current
(A)
(RMS)
Fundamental
Current (A)
THDi
(%)
THDv
(%)
Active
Power
Total
(KW)
Apparent
Power
Total
(KVA)
Reactive
Power
Total
(KVAR)
Power
Factor
Total
Harmonic
Compensat
ion Current
(A)
Harmonic
Compensat
ion Current
(A) with
20%
Cushion
1)
500 KVA
Transformer
LT Side
@ Maximum
RMS
Current(A)
610.2 610.6 5.54 1.67 372.1 399.8 151.15 0.93 33.8 40.56
@ Maximum
THDi% 511.3 512 10.17 1.62 317.05 346.05 160.4 0.92 52.1 62.52
@ Maximum
Harmonic
Compensation
Current (A)
536 534.6 10.07 1.6 317.05 346.05 160.4 0.92 53.8 64.56
Customer Name
Date:
06.08.14
Measured Location 500 KVA Transformer LT side.
Measured Date & Duration 06th
August’14 to 07th
August’14 (Duration 24hrs)
Supply Voltage 433V
Load Current Rms Max. (Measured) 634.8A
Load
Used
1.Extruder Lamination Machine:
Rated Load: 79HP (58.9KW)
(Including: 45HP-DC Drive)
2.Adhesive Lamination Machine:
Rated Load: 25.5HP (19.02KW)
(Including: 17.5HP-AC Servo Drive)
3.Hot Melt Machine:
Rated Load: 18.5HP ( 13.8KW )
(Including: 17.5HP-AC Servo Drive)
4.Double & Shaft Slitting Machine:
Rated Load: 32.2HP (24.24KW)
(Including: 27.5HP-DC Drive + 2HP AC Servo Drive)
5. Single Shaft Slitting machine:
Rated Load: 14.5HP (10.81KW)
(Including: 12.5HP-DC Drive)
6. Titan Slitting machine:
Rated Load: 17HP (12.68KW)
(Including: 15HP-AC Servo Drive)
7.Thermia Boiler Unit:
Rated Load: 27HP (20.14 KW)
8.Blow Film Extruder Machine:
Rated Load: 130HP (96.94KW)
(Including: 66HP-DC Drive)
9.Romatic Printing Machine:
Rated Load: 91HP (67.86KW)
(Including: 54HP-AC Servo Drive)
10.Solventless Lamination machine:
Rated Load: 8HP (5.7KW)
(Including: 4HP-AC Servo Drive)
11.Chilling Plant Load:
Rated Load: 27HP (20.14KW)
12.Oil Printing Machine:
Rated Load: 79HP (58.9KW)
(Including: 45HP-DC Drive)
13.Lighting Load:
Rated Load: 15KW
Capacitor
Bank
details
APFC- Automatic power factor control 250KVAR ( at MV panel)
Detuning choke Detuning choke Not available
Observation: (Refer the charts) Reference at maximum Compensation Current:
Measured at 500KVA Transformer LT side
Maximum Compensation Current Required for filter sizing Ref.fig.40 : 63.48A
RMS Current Ref.fig.37 : 373.8A
Fundamental Current : 373A
THDi (Total Current Harmonic Distortion) Ref. fig.39 : 17.02%
THDv (Total Voltage Harmonic Distortion) Ref. fig.41 : 2.05%
It is clear from the graph (Ref. fig.39 ) THDi exceeds the permissible limit of IEEE
519&CEA/TNEB norms
Conclusion:
The Harmonics present in the system exceeds the permissible limits of IEEE 519 &CEA/TNEB*
norm.
Harmonic filter should be installed at LT side to reduce the Harmonic
*Permissible limits for the Harmonic: THDi-8% & THDv-5%
Logger Data & Trend:
Individual Harmonics Reference at Max. THDi%:
295.8 293
18.29
6.91 14.74
2.18 1.89 5.26 0.23 0.37 0.19 0.17 0.23 0.13 0.120
50
100
150
200
250
300
350
22:35:02
Current L3 Max Current Fundamental L3 Max THD A L3 Max Amps Harmonics3 L3 Max Amps Harmonics5 L3 Max
Amps Harmonics7 L3 Max Amps Harmonics9 L3 Max Amps Harmonics11 L3 Max Amps Harmonics13 L3 Max Amps Harmonics15 L3 Max
Amps Harmonics17 L3 Max Amps Harmonics19 L3 Max Amps Harmonics21 L3 Max Amps Harmonics23 L3 Max Amps Harmonics25 L3 Max
Load Current (RMS) (A) fig.01:
0
100
200
300
400
500
600
700
11:0
6:32
11:3
0:32
11:5
4:32
12:1
8:32
12:4
2:32
13:0
6:32
13:3
0:32
13:5
4:32
14:1
8:32
14:4
2:32
15:0
6:32
15:3
0:32
15:5
4:32
16:1
8:32
16:4
2:32
17:0
6:32
17:3
0:32
17:5
4:32
18:1
8:32
18:4
2:32
19:0
6:32
19:3
0:32
19:5
4:32
20:1
8:32
20:4
2:32
21:0
6:32
21:3
0:32
21:5
4:32
22:1
8:32
22:4
2:32
23:0
6:32
23:3
0:32
23:5
4:32
0:18
:32
0:42
:32
1:06
:32
1:30
:32
1:54
:32
2:18
:32
2:42
:32
3:06
:32
3:30
:32
3:54
:32
4:18
:32
4:42
:32
5:06
:32
5:30
:32
5:54
:32
6:18
:32
6:42
:32
7:06
:32
7:30
:32
7:54
:32
8:18
:32
8:42
:32
9:06
:32
9:30
:32
9:53
:32
10:1
7:32
10:4
0:32
11:0
4:32
11:2
8:32
Current L1 Max Current L2 Max Current L3 Max
APFC OFF From : 10:47:02 to 10:59:02
Power Cut From: 9:44:10 to 10.32:07
Fundamental Current fig.02
THDi % (Total Current Harmonics Distortion), fig.03:
Compensation Current (A) -for Filter Sizing, fig.04:
0
200
400
600
800
11:0
6:32
11:3
1:02
11:5
5:32
12:2
0:02
12:4
4:32
13:0
9:02
13:3
3:32
13:5
8:02
14:2
2:32
14:4
7:02
15:1
1:32
15:3
6:02
16:0
0:32
16:2
5:02
16:4
9:32
17:1
4:02
17:3
8:32
18:0
3:02
18:2
7:32
18:5
2:02
19:1
6:32
19:4
1:02
20:0
5:32
20:3
0:02
20:5
4:32
21:1
9:02
21:4
3:32
22:0
8:02
22:3
2:32
22:5
7:02
23:2
1:32
23:4
6:02
0:10
:32
0:35
:02
0:59
:32
1:24
:02
1:48
:32
2:13
:02
2:37
:32
3:02
:02
3:26
:32
3:51
:02
4:15
:32
4:40
:02
5:04
:32
5:29
:02
5:53
:32
6:18
:02
6:42
:32
7:07
:02
7:31
:32
7:56
:02
8:20
:32
8:45
:02
9:09
:32
9:34
:02
9:57
:32
10:2
2:02
10:4
5:32
11:1
0:02
Current Fundamental L1 Max Current Fundamental L2 Max Current Fundamental L3 Max
05
101520
11:0
6:32
11:3
0:32
11:5
4:32
12:1
8:32
12:4
2:32
13:0
6:32
13:3
0:32
13:5
4:32
14:1
8:32
14:4
2:32
15:0
6:32
15:3
0:32
15:5
4:32
16:1
8:32
16:4
2:32
17:0
6:32
17:3
0:32
17:5
4:32
18:1
8:32
18:4
2:32
19:0
6:32
19:3
0:32
19:5
4:32
20:1
8:32
20:4
2:32
21:0
6:32
21:3
0:32
21:5
4:32
22:1
8:32
22:4
2:32
23:0
6:32
23:3
0:32
23:5
4:32
0:18
:32
0:42
:32
1:06
:32
1:30
:32
1:54
:32
2:18
:32
2:42
:32
3:06
:32
3:30
:32
3:54
:32
4:18
:32
4:42
:32
5:06
:32
5:30
:32
5:54
:32
6:18
:32
6:42
:32
7:06
:32
7:30
:32
7:54
:32
8:18
:32
8:42
:32
9:06
:32
9:30
:32
9:53
:32
10:1
7:32
10:4
0:32
11:0
4:32
11:2
8:32
TNEB/CEA Limit THD A L1 Max THD A L2 Max THD A L3 Max
0.0
20.0
40.0
60.0
80.0
11:0
6:32
11:3
1:02
11:5
5:32
12:2
0:02
12:4
4:32
13:0
9:02
13:3
3:32
13:5
8:02
14:2
2:32
14:4
7:02
15:1
1:32
15:3
6:02
16:0
0:32
16:2
5:02
16:4
9:32
17:1
4:02
17:3
8:32
18:0
3:02
18:2
7:32
18:5
2:02
19:1
6:32
19:4
1:02
20:0
5:32
20:3
0:02
20:5
4:32
21:1
9:02
21:4
3:32
22:0
8:02
22:3
2:32
22:5
7:02
23:2
1:32
23:4
6:02
0:10
:32
0:35
:02
0:59
:32
1:24
:02
1:48
:32
2:13
:02
2:37
:32
3:02
:02
3:26
:32
3:51
:02
4:15
:32
4:40
:02
5:04
:32
5:29
:02
5:53
:32
6:18
:02
6:42
:32
7:07
:02
7:31
:32
7:56
:02
8:20
:32
8:45
:02
9:09
:32
9:34
:02
9:57
:32
10:2
2:02
10:4
5:32
11:1
0:02
Comp Current L1 Comp Current L2 Comp Current L3
Ref.Fig.01
Reference point at
maximum Compensation
Current
Ref.fig.01
Ref.fig.01
THDv % (Total Voltage Harmonics Distortion), fig.05:
Power Factor Total Max fig.06:
0
1
2
3
4
5
6
11:0
6:32
11:3
0:02
11:5
3:32
12:1
7:02
12:4
0:32
13:0
4:02
13:2
7:32
13:5
1:02
14:1
4:32
14:3
8:02
15:0
1:32
15:2
5:02
15:4
8:32
16:1
2:02
16:3
5:32
16:5
9:02
17:2
2:32
17:4
6:02
18:0
9:32
18:3
3:02
18:5
6:32
19:2
0:02
19:4
3:32
20:0
7:02
20:3
0:32
20:5
4:02
21:1
7:32
21:4
1:02
22:0
4:32
22:2
8:02
22:5
1:32
23:1
5:02
23:3
8:32
0:0
2:0
20
:25
:32
0:4
9:0
21
:12
:32
1:3
6:0
21
:59
:32
2:2
3:0
22
:46
:32
3:1
0:0
23
:33
:32
3:5
7:0
24
:20
:32
4:4
4:0
25
:07
:32
5:3
1:0
25
:54
:32
6:1
8:0
26
:41
:32
7:0
5:0
27
:28
:32
7:5
2:0
28
:15
:32
8:3
9:0
29
:02
:32
9:2
6:0
29
:48
:32
10:1
2:02
10:3
4:32
10:5
8:02
11:2
1:32
TNEB/CEA Limit THD V L1N Max THD V L2N Max THD V L3N Max
0
0.2
0.4
0.6
0.8
1
1.2
11:0
6:32
11:3
0:32
11:5
4:32
12:1
8:32
12:4
2:32
13:0
6:32
13:3
0:32
13:5
4:32
14:1
8:32
14:4
2:32
15:0
6:32
15:3
0:32
15:5
4:32
16:1
8:32
16:4
2:32
17:0
6:32
17:3
0:32
17:5
4:32
18:1
8:32
18:4
2:32
19:0
6:32
19:3
0:32
19:5
4:32
20:1
8:32
20:4
2:32
21:0
6:32
21:3
0:32
21:5
4:32
22:1
8:32
22:4
2:32
23:0
6:32
23:3
0:32
23:5
4:32
0:18
:32
0:42
:32
1:06
:32
1:30
:32
1:54
:32
2:18
:32
2:42
:32
3:06
:32
3:30
:32
3:54
:32
4:18
:32
4:42
:32
5:06
:32
5:30
:32
5:54
:32
6:18
:32
6:42
:32
7:06
:32
7:30
:32
7:54
:32
8:18
:32
8:42
:32
9:06
:32
9:30
:32
9:53
:32
10:1
7:32
10:4
0:32
11:0
4:32
11:2
8:32
Power Factor Total Max
Ref.fig.01
Ref.fig.01
Active Power Total Max, fig.07:
Apparent Power Total Max, fig.08:
0
50000
100000
150000
200000
250000
300000
350000
400000
11:0
6:32
11:3
0:32
11:5
4:32
12:1
8:32
12:4
2:32
13:0
6:32
13:3
0:32
13:5
4:32
14:1
8:32
14:4
2:32
15:0
6:32
15:3
0:32
15:5
4:32
16:1
8:32
16:4
2:32
17:0
6:32
17:3
0:32
17:5
4:32
18:1
8:32
18:4
2:32
19:0
6:32
19:3
0:32
19:5
4:32
20:1
8:32
20:4
2:32
21:0
6:32
21:3
0:32
21:5
4:32
22:1
8:32
22:4
2:32
23:0
6:32
23:3
0:32
23:5
4:32
0:18
:32
0:42
:32
1:06
:32
1:30
:32
1:54
:32
2:18
:32
2:42
:32
3:06
:32
3:30
:32
3:54
:32
4:18
:32
4:42
:32
5:06
:32
5:30
:32
5:54
:32
6:18
:32
6:42
:32
7:06
:32
7:30
:32
7:54
:32
8:18
:32
8:42
:32
9:06
:32
9:30
:32
9:53
:32
10:1
7:32
10:4
0:32
11:0
4:32
11:2
8:32
Active Power Total Max
0
50000
100000
150000
200000
250000
300000
350000
400000
450000
11:0
6:32
11:3
0:32
11:5
4:32
12:1
8:32
12:4
2:32
13:0
6:32
13:3
0:32
13:5
4:32
14:1
8:32
14:4
2:32
15:0
6:32
15:3
0:32
15:5
4:32
16:1
8:32
16:4
2:32
17:0
6:32
17:3
0:32
17:5
4:32
18:1
8:32
18:4
2:32
19:0
6:32
19:3
0:32
19:5
4:32
20:1
8:32
20:4
2:32
21:0
6:32
21:3
0:32
21:5
4:32
22:1
8:32
22:4
2:32
23:0
6:32
23:3
0:32
23:5
4:32
0:18
:32
0:42
:32
1:06
:32
1:30
:32
1:54
:32
2:18
:32
2:42
:32
3:06
:32
3:30
:32
3:54
:32
4:18
:32
4:42
:32
5:06
:32
5:30
:32
5:54
:32
6:18
:32
6:42
:32
7:06
:32
7:30
:32
7:54
:32
8:18
:32
8:42
:32
9:06
:32
9:30
:32
9:53
:32
10:1
7:32
10:4
0:32
11:0
4:32
11:2
8:32
Apparent Power Total Max
Ref.fig.01
Ref.fig.01
Reactive Power Total Max, fig.09:
Line to Neutral Voltage, fig.10:
0
20000
40000
60000
80000
100000
120000
140000
160000
180000
200000
11
:06
:32
11
:30
:32
11
:54
:32
12
:18
:32
12
:42
:32
13
:06
:32
13
:30
:32
13
:54
:32
14
:18
:32
14
:42
:32
15
:06
:32
15
:30
:32
15
:54
:32
16
:18
:32
16
:42
:32
17
:06
:32
17
:30
:32
17
:54
:32
18
:18
:32
18
:42
:32
19
:06
:32
19
:30
:32
19
:54
:32
20
:18
:32
20
:42
:32
21
:06
:32
21
:30
:32
21
:54
:32
22
:18
:32
22
:42
:32
23
:06
:32
23
:30
:32
23
:54
:32
0:18
:32
0:42
:32
1:06
:32
1:30
:32
1:54
:32
2:18
:32
2:42
:32
3:06
:32
3:30
:32
3:54
:32
4:18
:32
4:42
:32
5:06
:32
5:30
:32
5:54
:32
6:18
:32
6:42
:32
7:06
:32
7:30
:32
7:54
:32
8:18
:32
8:42
:32
9:06
:32
9:30
:32
9:53
:32
10
:17
:32
10
:40
:32
11
:04
:32
11
:28
:32
Reactive Power Total Max
Ref.fig.01
205
210
215
220
225
230
235
240
245
250
255
11:0
6:3
211
:30:
02
11:5
3:3
212
:17:
02
12:4
0:3
213
:04:
02
13:2
7:3
213
:51:
02
14:1
4:3
214
:38:
02
15:0
1:3
215
:25:
02
15:4
8:3
216
:12:
02
16:3
5:3
216
:59:
02
17:2
2:3
217
:46:
02
18:0
9:3
218
:33:
02
18:5
6:3
219
:20:
02
19:4
3:3
220
:07:
0220
:30:
32
20:5
4:0
221
:17:
32
21:4
1:0
222
:04:
32
22:2
8:02
22:5
1:3
223
:15:
02
23:3
8:3
20
:02
:02
0:2
5:3
20
:49
:02
1:1
2:3
21
:36
:02
1:5
9:3
22
:23
:02
2:4
6:3
23
:10
:02
3:3
3:3
23
:57
:02
4:2
0:3
24
:44
:02
5:0
7:3
25
:31
:02
5:5
4:3
26
:18
:02
6:4
1:3
27
:05
:02
7:2
8:3
27
:52
:02
8:1
5:3
28
:39
:02
9:0
2:3
29
:26
:02
9:4
8:3
210
:12:
02
10:3
4:3
210
:58:
02
11:2
1:3
2
Vrms ph-n L1N Max Vrms ph-n L2N Max Vrms ph-n L3N Max
Ref.fig.01
Line to Line Voltage, fig.11:
360
370
380
390
400
410
420
430
440
11:0
6:32
11:3
0:02
11:5
3:32
12:1
7:02
12:4
0:32
13:0
4:02
13:2
7:32
13:5
1:02
14:1
4:32
14:3
8:02
15:0
1:32
15:2
5:02
15:4
8:32
16:1
2:02
16:3
5:32
16:5
9:02
17:2
2:32
17:4
6:02
18:0
9:32
18:3
3:02
18:5
6:32
19:2
0:02
19:4
3:32
20:0
7:02
20:3
0:32
20:5
4:02
21:1
7:32
21:4
1:02
22:0
4:32
22:2
8:02
22:5
1:32
23:1
5:02
23:3
8:32
0:02
:02
0:25
:32
0:49
:02
1:12
:32
1:36
:02
1:59
:32
2:23
:02
2:46
:32
3:10
:02
3:33
:32
3:57
:02
4:20
:32
4:44
:02
5:07
:32
5:31
:02
5:54
:32
6:18
:02
6:41
:32
7:05
:02
7:28
:32
7:52
:02
8:15
:32
8:39
:02
9:02
:32
9:26
:02
9:48
:32
10:1
2:02
10:3
4:32
10:5
8:02
11:2
1:32
Vrms ph-ph L12 Max Vrms ph-ph L23 Max Vrms ph-ph L31 Max
Ref.fig.01