Panel Box size per schedule INTERIOR Stucco wall assembly: Wall system and membrane details as specified by architect Build-up as required to clear projecting objects Safe Rail Flashing Safe bottom profile EXTERIOR 2" min. Outline of stucco beyond Outline of drywall beyond Architect approved sealant Minimum 1 1/2" penetration into wood framing recommended Flashing as specified by architect 2 6 2 2 8 8 Stainless steel or equivalent weatherproof fasteners - architect to specify Architect approved sealant 1 6 Mini Safe curtain profile GENERIC DETAILS © ROLLSHUTTER RETROFIT SYSTEM STUCCO WALL APPLICATION DISCLAIMER: DETAILS PROVIDED BY TALIUS ARE GENERAL RECOMMENDATIONS. CONSULTATION WTIH AND EXPERIENCED ARCHITECT, STRUCTURAL ENGINEER, OR CONTRACTOR IS NECESSARY FOR PROPER EXECUTION OF WEATHERPROOFING DETAILS, STRUCTURAL REQUIREMENTS AND COMPLIANCE WITH REGIONAL AND LOCAL BUILDING CODES. TALIUS PLACES SOLE RESPONSIBILITY OF THESE INSTALLATION ISSUES WITH THE ARCHITECT, STRUCTURAL ENGINEER, GENERAL CONTRACTOR AND/OR BUILDING OWNER. NOTE: IT IS THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO SUPPLY ALL REQUIRED SEALANTS, FLASHINGS, AND MOUNTING HARDWARE. RS_Stucco01

Transcript of GENERIC DETAILS STUCCO WALL APPLICATION …...Outline of stucco Outline of beyond drywall beyond...

  • Panel Box sizeper schedule

    INTERIOR

    Stucco wall assembly:Wall system and

    membrane details asspecified by architect

    Build-up as required toclear projecting objects

    Safe Rail

    Flashing

    Safe bottomprofile

    EXTERIOR2"

    min

    .

    Outline of stuccobeyond

    Outline ofdrywall beyond

    Architect approvedsealant

    Minimum 1 1/2"penetration into

    wood framingrecommended

    Flashing as specifiedby architect

    2 6

    2 2

    8 8

    Stainless steel or equivalent weatherprooffasteners - architect to specify

    Architect approvedsealant

    16

    Mini Safecurtain profile

    GENERIC DETAILS©

    ROLLSHUTTER RETROFIT SYSTEM

    STUCCO WALL APPLICATION

    DISCLAIMER: DETAILS PROVIDED BY TALIUS ARE GENERAL RECOMMENDATIONS. CONSULTATION WTIH AND EXPERIENCED ARCHITECT, STRUCTURAL ENGINEER, OR CONTRACTOR ISNECESSARY FOR PROPER EXECUTION OF WEATHERPROOFING DETAILS, STRUCTURAL REQUIREMENTS AND COMPLIANCE WITH REGIONAL AND LOCAL BUILDING CODES. TALIUS PLACES SOLERESPONSIBILITY OF THESE INSTALLATION ISSUES WITH THE ARCHITECT, STRUCTURAL ENGINEER, GENERAL CONTRACTOR AND/OR BUILDING OWNER.

    NOTE: IT IS THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO SUPPLY ALL REQUIRED SEALANTS, FLASHINGS, AND MOUNTING HARDWARE.

    RS_Stucco01

  • INTERIOR EXTERIOR

    Safe Rail

    Sill Flashing

    Safe U-Sill with 1/4"Ødrains @ 18" o.c.

    Stucco wall assembly:Wall system and

    membrane details asspecified by architect

    Outline of stuccobeyondOutline of

    drywall beyond

    Build-up as required toclear projecting objects

    Minimum 1 1/2"penetration into

    wood framingrecommended

    Architectapproved sealant

    2 6

    2 6

    Architect approvedrod & sealant

    Safe bottomprofile

    Mini Safecurtain profile

    © GENERIC DETAILS

    ROLLSHUTTER RETROFIT SYSTEM

    STUCCO WALL APPLICATION

    NOTE: IT IS THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO SUPPLY ALL REQUIRED SEALANTS, FLASHINGS, AND MOUNTING HARDWARE.

    DISCLAIMER: DETAILS PROVIDED BY TALIUS ARE GENERAL RECOMMENDATIONS. CONSULTATION WTIH AND EXPERIENCED ARCHITECT, STRUCTURAL ENGINEER, OR CONTRACTOR ISNECESSARY FOR PROPER EXECUTION OF WEATHERPROOFING DETAILS, STRUCTURAL REQUIREMENTS AND COMPLIANCE WITH REGIONAL AND LOCAL BUILDING CODES. TALIUS PLACES SOLERESPONSIBILITY OF THESE INSTALLATION ISSUES WITH THE ARCHITECT, STRUCTURAL ENGINEER, GENERAL CONTRACTOR AND/OR BUILDING OWNER. RS_Stucco02

  • Stucco wall assembly:Wall system andmembrane details asspecified by architect

    Architectapprovedsealant

    Build-up as required toclear projecting objects

    Outline of drywallbeyond

    INTERIOR

    EXTERIOR

    Safe Rail

    Safe U-Sill

    Minimum 1 1/2"penetration into

    wood framingrecommended

    curtain

    Outermost projectionof sill flashing below

    2 2

    6 6

    Architect approvedrod & sealant

    © GENERIC DETAILS

    ROLLSHUTTER RETROFIT SYSTEM

    STUCCO WALL APPLICATION

    NOTE: IT IS THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO SUPPLY ALL REQUIRED SEALANTS, FLASHINGS, AND MOUNTING HARDWARE.

    DISCLAIMER: DETAILS PROVIDED BY TALIUS ARE GENERAL RECOMMENDATIONS. CONSULTATION WTIH AND EXPERIENCED ARCHITECT, STRUCTURAL ENGINEER, OR CONTRACTOR ISNECESSARY FOR PROPER EXECUTION OF WEATHERPROOFING DETAILS, STRUCTURAL REQUIREMENTS AND COMPLIANCE WITH REGIONAL AND LOCAL BUILDING CODES. TALIUS PLACES SOLERESPONSIBILITY OF THESE INSTALLATION ISSUES WITH THE ARCHITECT, STRUCTURAL ENGINEER, GENERAL CONTRACTOR AND/OR BUILDING OWNER. RS_Stucco03

  • Stucco wall assembly:Wall system and

    membrane details asspecified by architect

    Architect approvedsealant

    Build-up asrequired to clearprojecting objects

    Outermostprojection of sill

    flashing below

    Outline of drywallbeyond

    INTERIOR

    EXTERIOR

    (2) Safe Rails

    Safe U-Sill

    Minimum 1 1/2"penetration into

    wood framingrecommended

    curtaincurtain

    Outline of drywallbeyond

    Architect approvedsealant

    Architect approvedrod & sealant

    © GENERIC DETAILS

    ROLLSHUTTER RETROFIT SYSTEM

    STUCCO WALL APPLICATION

    NOTE: IT IS THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO SUPPLY ALL REQUIRED SEALANTS, FLASHINGS, AND MOUNTING HARDWARE.

    DISCLAIMER: DETAILS PROVIDED BY TALIUS ARE GENERAL RECOMMENDATIONS. CONSULTATION WTIH AND EXPERIENCED ARCHITECT, STRUCTURAL ENGINEER, OR CONTRACTOR ISNECESSARY FOR PROPER EXECUTION OF WEATHERPROOFING DETAILS, STRUCTURAL REQUIREMENTS AND COMPLIANCE WITH REGIONAL AND LOCAL BUILDING CODES. TALIUS PLACES SOLERESPONSIBILITY OF THESE INSTALLATION ISSUES WITH THE ARCHITECT, STRUCTURAL ENGINEER, GENERAL CONTRACTOR AND/OR BUILDING OWNER. RS_Stucco04

  • Minimum 1 1/2"penetration into

    wood framingrecommended

    Outline ofdrywall beyond

    Mini SafeProfile

    Outline of stuccobeyond

    EXTERIORINTERIOR

    Stucco Wall assembly:Wall system and

    membrane details asspecified by architect

    Removable access panel under Panel Boxopening by others (matched to existing soffit)

    Soffit

    Soffit Joist

    *Do not attach removableaccess panel to Panel Box

    Roof System:Details as specified by architector structural engineer

    1" x 1" x 1/4" aluminum angle forservice panel attachment

    Ceiling Joist

    Architect approved sealant

    Flashing

    Safe Rail

    2 6

    2 6

    2

    10

    2

    10

    2

    4

    Panel Box sizeper schedule

    Wood blockingas required

    © GENERIC DETAILS STUCCO WALL APPLICATION

    PANEL BOX IN-SOFFIT SYSTEM

    NOTE: IT IS THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO SUPPLY ALL REQUIRED SEALANTS, FLASHINGS, AND MOUNTING HARDWARE.

    DISCLAIMER: DETAILS PROVIDED BY TALIUS ARE GENERAL RECOMMENDATIONS. CONSULTATION WTIH AND EXPERIENCED ARCHITECT, STRUCTURAL ENGINEER, OR CONTRACTOR ISNECESSARY FOR PROPER EXECUTION OF WEATHERPROOFING DETAILS, STRUCTURAL REQUIREMENTS AND COMPLIANCE WITH REGIONAL AND LOCAL BUILDING CODES. TALIUS PLACES SOLERESPONSIBILITY OF THESE INSTALLATION ISSUES WITH THE ARCHITECT, STRUCTURAL ENGINEER, GENERAL CONTRACTOR AND/OR BUILDING OWNER. RS_Stucco05

  • Stucco Wall assembly:Wall system and membrane

    details asspecified by architect

    Ceiling Joist

    Roof System:Details as specified by architector structural engineer

    Soffit Joist

    Architect approved sealant

    Outline of stucco beyond

    Safe bottom profile

    Flashing

    Safe RailEXTERIOR

    Soffit

    Panel Box sizeper schedule

    INTERIOR

    Outline ofdrywall beyond

    Minimum 1 1/2" penetrationinto wood framing

    recommended

    2 6

    2 6

    Wood blockingas required

    Mini Safe curtain profile

    © GENERIC DETAILS

    PANEL BOX BELOW-SOFFIT SYSTEM

    STUCCO WALL APPLICATION

    NOTE: IT IS THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO SUPPLY ALL REQUIRED SEALANTS, FLASHINGS, AND MOUNTING HARDWARE.

    DISCLAIMER: DETAILS PROVIDED BY TALIUS ARE GENERAL RECOMMENDATIONS. CONSULTATION WTIH AND EXPERIENCED ARCHITECT, STRUCTURAL ENGINEER, OR CONTRACTOR ISNECESSARY FOR PROPER EXECUTION OF WEATHERPROOFING DETAILS, STRUCTURAL REQUIREMENTS AND COMPLIANCE WITH REGIONAL AND LOCAL BUILDING CODES. TALIUS PLACES SOLERESPONSIBILITY OF THESE INSTALLATION ISSUES WITH THE ARCHITECT, STRUCTURAL ENGINEER, GENERAL CONTRACTOR AND/OR BUILDING OWNER. RS_Stucco06

  • 2"

    min

    .

    Outline ofdrywall beyond

    Minimum 1 1/2"penetration into

    wood framingrecommended

    Stucco wall assembly:Wall system and

    membrane details asspecified by architect

    Architect approvedsealant

    Outline of stuccobeyond

    EXTERIOR

    Flashing

    Safe Rail

    INTERIOR

    Panel Box sizeper schedule

    Build-up as required toclear projecting objects

    16

    Stainless steel or equivalent weatherprooffasteners - architect to specify

    Architect approvedsealant

    Flashing asspecifiedby architect

    Safe bottomprofile

    Mini Safecurtain profile

    © GENERIC DETAILS STUCCO WALL APPLICATION

    PANEL BOX BELOW-SOFFIT SYSTEM

    NOTE: IT IS THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO SUPPLY ALL REQUIRED SEALANTS, FLASHINGS, AND MOUNTING HARDWARE.

    DISCLAIMER: DETAILS PROVIDED BY TALIUS ARE GENERAL RECOMMENDATIONS. CONSULTATION WTIH AND EXPERIENCED ARCHITECT, STRUCTURAL ENGINEER, OR CONTRACTOR ISNECESSARY FOR PROPER EXECUTION OF WEATHERPROOFING DETAILS, STRUCTURAL REQUIREMENTS AND COMPLIANCE WITH REGIONAL AND LOCAL BUILDING CODES. TALIUS PLACES SOLERESPONSIBILITY OF THESE INSTALLATION ISSUES WITH THE ARCHITECT, STRUCTURAL ENGINEER, GENERAL CONTRACTOR AND/OR BUILDING OWNER. RS_Stucco07

  • INTERIOR EXTERIOR

    Safe Rail

    Sill Flashing

    Stucco wall assembly:Wall system and

    membrane details asspecified by architect

    Outline of stuccobeyondOutline of

    drywall beyond

    Build-up as required toclear projecting objects

    Minimum 1 1/2"penetration into

    wood framingrecommended

    Architectapproved sealant

    Safe U-Sill with 1/4"Ødrains @ 18" o.c.

    Safe bottomprofile

    Mini Safecurtain profile

    © GENERIC DETAILS STUCCO WALL APPLICATION

    PANEL BOX BELOW-SOFFIT SYSTEM

    NOTE: IT IS THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO SUPPLY ALL REQUIRED SEALANTS, FLASHINGS, AND MOUNTING HARDWARE.

    DISCLAIMER: DETAILS PROVIDED BY TALIUS ARE GENERAL RECOMMENDATIONS. CONSULTATION WTIH AND EXPERIENCED ARCHITECT, STRUCTURAL ENGINEER, OR CONTRACTOR ISNECESSARY FOR PROPER EXECUTION OF WEATHERPROOFING DETAILS, STRUCTURAL REQUIREMENTS AND COMPLIANCE WITH REGIONAL AND LOCAL BUILDING CODES. TALIUS PLACES SOLERESPONSIBILITY OF THESE INSTALLATION ISSUES WITH THE ARCHITECT, STRUCTURAL ENGINEER, GENERAL CONTRACTOR AND/OR BUILDING OWNER. RS_Stucco08

  • Stucco wall assembly:Wall system andmembrane details asspecified by architect

    Architectapproved sealant

    Build-up as required toclear projecting objects

    Outline of drywallbeyond

    INTERIOR

    EXTERIOR

    Safe Rail

    Safe U-Sill

    Minimum 1 1/2"penetration into

    wood framingrecommended

    curtain

    Outermost projectionof sill flashing

    © GENERIC DETAILS

    PANEL BOX BELOW-SOFFIT SYSTEM

    STUCCO WALL APPLICATION

    NOTE: IT IS THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO SUPPLY ALL REQUIRED SEALANTS, FLASHINGS, AND MOUNTING HARDWARE.

    DISCLAIMER: DETAILS PROVIDED BY TALIUS ARE GENERAL RECOMMENDATIONS. CONSULTATION WTIH AND EXPERIENCED ARCHITECT, STRUCTURAL ENGINEER, OR CONTRACTOR ISNECESSARY FOR PROPER EXECUTION OF WEATHERPROOFING DETAILS, STRUCTURAL REQUIREMENTS AND COMPLIANCE WITH REGIONAL AND LOCAL BUILDING CODES. TALIUS PLACES SOLERESPONSIBILITY OF THESE INSTALLATION ISSUES WITH THE ARCHITECT, STRUCTURAL ENGINEER, GENERAL CONTRACTOR AND/OR BUILDING OWNER. RS_Stucco09

  • Stucco wall assembly:Wall system andmembrane details asspecified by architect

    Build-up asrequired to clearprojecting objects

    Outermostprojection of sill

    flashing

    Outline of drywallbeyond

    INTERIOR

    EXTERIOR

    Safe Centre Rail

    Safe U-Sill

    Minimum 1 1/2"penetration into

    wood framingrecommended

    Outline of drywallbeyond

    Architect approvedsealant

    Architectapproved sealant

    © GENERIC DETAILS

    PANEL BOX BELOW-SOFFIT SYSTEM

    STUCCO WALL APPLICATION

    NOTE: IT IS THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO SUPPLY ALL REQUIRED SEALANTS, FLASHINGS, AND MOUNTING HARDWARE.

    DISCLAIMER: DETAILS PROVIDED BY TALIUS ARE GENERAL RECOMMENDATIONS. CONSULTATION WTIH AND EXPERIENCED ARCHITECT, STRUCTURAL ENGINEER, OR CONTRACTOR ISNECESSARY FOR PROPER EXECUTION OF WEATHERPROOFING DETAILS, STRUCTURAL REQUIREMENTS AND COMPLIANCE WITH REGIONAL AND LOCAL BUILDING CODES. TALIUS PLACES SOLERESPONSIBILITY OF THESE INSTALLATION ISSUES WITH THE ARCHITECT, STRUCTURAL ENGINEER, GENERAL CONTRACTOR AND/OR BUILDING OWNER. RS_Stucco10

  • Panel Box sizeper schedule

    INTERIOR

    Stucco wall assembly:Wall system and

    membrane details asspecified by architect

    Pro-40 Rail

    Flashing

    Safe bottomprofile

    EXTERIOR

    Outline of stuccobeyond

    1x treated shutterhousing (providesaccess for installationprior to application ofexterior finish)

    Header beam (consultarchitect or structuralengineer)

    Custom shop fabricatedremovable millwork

    panel for service access

    Removable 1" thickrigid foam insulation

    Vapour barrier adheredto studs or blocking

    Custom fabricated,watertight, continuous drip

    pan flashing

    Wall thickness will vary with rollshutter housing size.Talius housing sizes must be coordinated with actual lumber sizes toavoid conflicts - to be specified by architect or structural engineer

    Architectapproved sealant

    Do not installpanel box lid

    Mini Safecurtain profile

    © GENERIC DETAILS

    PANEL BOX IN-WALL SYSTEM

    STUCCO WALL APPLICATION

    NOTE: IT IS THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO SUPPLY ALL REQUIRED SEALANTS, FLASHINGS, AND MOUNTING HARDWARE.

    DISCLAIMER: DETAILS PROVIDED BY TALIUS ARE GENERAL RECOMMENDATIONS. CONSULTATION WTIH AND EXPERIENCED ARCHITECT, STRUCTURAL ENGINEER, OR CONTRACTOR ISNECESSARY FOR PROPER EXECUTION OF WEATHERPROOFING DETAILS, STRUCTURAL REQUIREMENTS AND COMPLIANCE WITH REGIONAL AND LOCAL BUILDING CODES. TALIUS PLACES SOLERESPONSIBILITY OF THESE INSTALLATION ISSUES WITH THE ARCHITECT, STRUCTURAL ENGINEER, GENERAL CONTRACTOR AND/OR BUILDING OWNER. RS_Stucco11

  • INTERIOR EXTERIOR

    Pro-40 Rail

    Continuous sill panflashing - as specifiedby architect

    Safe bottomprofile

    Safe U-Sill

    Stucco wall assembly:Wall system and

    membrane details asspecified by architect

    Outline of stuccobeyond

    Outline ofwindow frame

    beyond

    Architectapproved sealant

    Window set back into wallfar enough for all projecting

    trim to have clearance ofshutter slats and side rails

    Custom stone windowsill - as specified inarchitectural projectdocuments

    Outline indicatesheight of sill panflashing at jambbeyond

    Continuous sill panflashing - as specified

    by architect

    U-sill to be securedwith #8 self tapingmasonry screws@ 6" o.c.

    Mini Safe curtain profile

    © GENERIC DETAILS STUCCO WALL APPLICATION

    PANEL BOX IN-WALL SYSTEM

    NOTE: IT IS THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO SUPPLY ALL REQUIRED SEALANTS, FLASHINGS, AND MOUNTING HARDWARE.

    DISCLAIMER: DETAILS PROVIDED BY TALIUS ARE GENERAL RECOMMENDATIONS. CONSULTATION WTIH AND EXPERIENCED ARCHITECT, STRUCTURAL ENGINEER, OR CONTRACTOR ISNECESSARY FOR PROPER EXECUTION OF WEATHERPROOFING DETAILS, STRUCTURAL REQUIREMENTS AND COMPLIANCE WITH REGIONAL AND LOCAL BUILDING CODES. TALIUS PLACES SOLERESPONSIBILITY OF THESE INSTALLATION ISSUES WITH THE ARCHITECT, STRUCTURAL ENGINEER, GENERAL CONTRACTOR AND/OR BUILDING OWNER. RS_Stucco12

  • INTERIOR

    24

    curtain

    Safe U-Sill

    EXTERIOR

    Stucco wall assembly:Wall system andmembrane details asspecified by architect

    Outermost projection of customstone window sill - Sill asspecified in architecturalproject documents

    Outline of millwork serviceaccess panel above

    Outline indicatesextent of sill panflashing within wallcavity

    Treated 1x at side rail (toprovides access for installationprior to application of exteriorfinish)

    Outline indicatesextent of sill pan

    flashing withinwall cavity

    Architect approved sealant

    Pro-40 Rail

    © GENERIC DETAILS STUCCO WALL APPLICATION

    PANEL BOX IN-WALL SYSTEM

    NOTE: IT IS THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO SUPPLY ALL REQUIRED SEALANTS, FLASHINGS, AND MOUNTING HARDWARE.

    DISCLAIMER: DETAILS PROVIDED BY TALIUS ARE GENERAL RECOMMENDATIONS. CONSULTATION WTIH AND EXPERIENCED ARCHITECT, STRUCTURAL ENGINEER, OR CONTRACTOR ISNECESSARY FOR PROPER EXECUTION OF WEATHERPROOFING DETAILS, STRUCTURAL REQUIREMENTS AND COMPLIANCE WITH REGIONAL AND LOCAL BUILDING CODES. TALIUS PLACES SOLERESPONSIBILITY OF THESE INSTALLATION ISSUES WITH THE ARCHITECT, STRUCTURAL ENGINEER, GENERAL CONTRACTOR AND/OR BUILDING OWNER. RS_Stucco13

  • 2X8

    Structural header orlaminated joist(consult architect orstructural engineer)

    Panel boxopening

    Double 2 x 8 top plate

    Window opening

    2 x 8 cripples @ 16" o.c.

    Dashed line indicateswindow unit

    Double 2 x 8 sill plate

    2 x 8 trimmer

    2 x 8 king stud

    Use 2 x 4's to frame outrough opening to provide

    an attachment surface forcomponents and allows

    set-back of window2X8 trimmerripped down tosupport panelsill plate above

    Panel box sill plate (2 x 8ripped down to fit side railsand slats into outside face.)

    2 x 8 studs @ 16" o.c.

    2 x 8 cripples @ 16" o.c.

    2 x 8 sole plate

    Trimmer to support panelbox sill plate (2 x 8 ripped

    down to fit side rails andslats into outside face.)

    © GENERIC DETAILS STUCCO WALL APPLICATION

    PANEL BOX IN-WALL SYSTEM

    NOTE: IT IS THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO SUPPLY ALL REQUIRED SEALANTS, FLASHINGS, AND MOUNTING HARDWARE.

    DISCLAIMER: DETAILS PROVIDED BY TALIUS ARE GENERAL RECOMMENDATIONS. CONSULTATION WTIH AND EXPERIENCED ARCHITECT, STRUCTURAL ENGINEER, OR CONTRACTOR ISNECESSARY FOR PROPER EXECUTION OF WEATHERPROOFING DETAILS, STRUCTURAL REQUIREMENTS AND COMPLIANCE WITH REGIONAL AND LOCAL BUILDING CODES. TALIUS PLACES SOLERESPONSIBILITY OF THESE INSTALLATION ISSUES WITH THE ARCHITECT, STRUCTURAL ENGINEER, GENERAL CONTRACTOR AND/OR BUILDING OWNER. RS_Stucco14

    StuccoWall_Rollshutter_Dec14-09p.1p.2p.3p.4p.5p.6p.7p.8p.9p.10p.11p.12p.13p.14