PROJECT GENERAL NOTES DRAWING INDEX SPRINKLER HEAD FLOW SWITCH FIRE DEPARTMENT CONNECTION FIRE ALARM ASSEMBLY SPRINKLER VALVE ASSEMBLY PUMP LEGEND SYMBOL DESCRIPTION ABBREVIATIONS 1. THE SPRINKLER CONTRACTOR SHALL PROVIDE COMPLETE HYDRAULIC CALCULATIONS, PIPE SIZING, PIPE MATERIAL WITH LAY-OUT DWG'S & CONSTRUCTION LAY-OUT DWG'S. 2. ALL SPRINKLER HEADS SERVING, ELECTRIC, TELEPHONE, SWITCHGEAR & ELEVATOR MACHINE ROOMS SHALL BE PROVIDED BY SHUT-OFF VALVES W/ TAMPER SWITCHES. 3. 4. THE FIRE PROTECTION SYSTEM DESIGN, INSTALLATION AND MATERIALS SHALL BE IN AS COMPLIANCE WITH NFPA AND THE MOST RECENT STATE BUILDING CODE AND FIRE CODES, WELL AS ANY APPLICABLE STATE STATUTES. 5. SPRINKLER SYSTEM TO BE INSTALLED BY A STATE CERTIFIED FIRE PROTECTIONCONTRACTOR. 6. CONTRACTOR SHALL COORDINATE WITH STRUCTURE, CEILING GRID AND ELEVATION, AND OTHER MECHANICAL AND ELECTRICAL SERVICES BEFORE FABRICATING AND INSTALLING SPRINKLER HEADS & PIPING. MAKE OFFSETS IN PIPING AS REQUIRED PER FIELD CONDITIONS. MAINTAIN 6" CLEARANCE BETWEEN PIPING AND 1 AND 2 HOUR RATED WALLS INCLUDING CORRIDOR WALLS. 7. ALL VALVES SHALL BE BY DOMESTIC MANUFACTURER, U.L. LISTED FOR FIRE PROTECTION SERVICE AND RATED FOR 175 PSI WORKING PRESSURE. PROVIDE U.L. LISTED/ FM APPROVED TAMPER SWITCHES AT CONTROL VALVE LOCATIONS. PROVIDE U.L. LISTED/ FM APPROVED FLOW SWITCHES, WHERE SHOWN, AT CONTROL VALVE LOCATIONS. 8. SPRINKLER HEADS SHALL BE LISTED AS INDICATED IN SCHEDULE AND RATED FOR 175 PSI WORKING PRESSURE. PROVIDE HEAD GUARDS ON UPRIGHT AND PENDANT SPRINKLER HEADS LOCATED IN ELEVATOR SHAFTS, MECHANICAL SHAFTS, ELECTRICAL, TELEPHONE, MECHANICAL AND MACHINE ROOMS. CONTRACTOR SHALL PROVIDE THE OWNER WITH A COPY OF NFPA 25. 9. CONTRACTOR SHALL PROVIDE FLUSHING CONNECTIONS WHERE SHOWN ON PLANS. PROVIDE A DRAIN CONNECTION FOR ALL TRAPPED SECTION OF PIPING. 10. INSPECTORS TEST, DRAIN AND SHUT-OFF VALVES SHALL BE LOCATED AT MAXIMUM OF7'-0" AFF. 11. ALL SPRINKLER HEADS SHALL BE CENTERED AND PRESENTED IN A NEAT AND BALANCED CEILING PATTERN. FP CONTRACTOR TO COORDINATE WITH ARCHITECT AND INTERIOR DESIGNER. 12. PIPING TO BE BLACK STEEL IN AIR CONDITIONED SPACES, PIPING IN NON-AIR CONDITIONED SPACE SHALL BE BLACK STEEL SCHEDULE 40 (PAINTED) WITH AN ALTERNATE FOR GALVANIZED SCHEDULE 40. GROOVED FITTINGS ARE NOT ALLOWED WHERE PRESSURE EXCEEDS 175 PSI. 13. SPRINKLER HEADS TO BE MODEL GBR SERIES SPRINKLER WHITE PLATED SEMI RECESSED TYPE FOR SIDE WALL, AND FOR CEILING LOCATIONS, BRASS UPRIGHT FOR EXPOSED LOCATIONS, RECESSED TYPE FOR FIRST FLOOR LOBBY AREAS. TEFLON FINISHED HEADS TO BE USED IN NON-AIR CONDITIONED AREAS. 14. SPRINKLER HEADS SHOULD BE PROVIDED ON FIRE RATED WALLS WHERE THERE ARE INTERIOR ALUMINUM WINDOWS. SPRINKLER HEADS SHOULD ALSO BE PROVIDED INSIDE OF LAUNDRY CHUTES. 15. SPRINKLER SUBCONTRACTOR TO PROVIDE ALL REQUIRED STANDPIPES AND FIRE HOSE VALVES, FLOW AND TAMPER SWITCHES, PRESSURE REDUCING VALVES AT ALL FLOORS, SIAMESE CONNECTIONS, INSPECTOR TEST STATIONS, SPARE SPRINKLER HEAD CABINET. ALL NECESSARY DRAINS AND SIGNAGE. 16. FIRE PUMP AND CONTROLLER SHALL BE SIZED ACCORDING TO HYDRAULIC CALCULATIONS AND FLOW TEST. IF FIRE PUMP IS REQUIRED, FP CONTRACTOR SHALL SUBMIT FIRE PUMP SHOP DRAWINGS TO EOR FOR REVIEW. ALL ASSOCIATED ACCESSORIES INCLUDING JOCKEY PUMP AND CONTROLLER, PUMP BYPASS, AND NECESSARY VALVING SHALL MEET LOCAL CODES AND NFPA STANDARDS. PROVIDE REMOTE ANNUNCIATOR AT FIRE COMMAND ROOM AND REMOTE ALARM AT SECURITY DESK. 17. ALL EXPOSED FIRE ALARM PIECES (STROBES, SPEAKERS, PULL STATIONS) TO BE WHITE IN COLOR WHERE POSSIBLE. FP CONTRACTOR SHALL COORDINATE WITH ARCHITECT AND INTERIOR DESIGNER. 18. FIRE CONTRACTOR MUST PROVIDE LANDLORD AND TENANT WITH A COPY OF NFPA 25. 19. FP SUBCONTRACTOR SHALL CONNECT MAIN FIRE LINE TO UTILITY SOURCE AND PROVIDE CONTROL VALVE/PIV. SUCTION SIDE PIPING SHALL BE DUCTILE IRON 20. ALL FIRE SPRINKLER SHALL BE MONITORED 24 HOURS A DAY BY AN APPROVED CENTRAL STATION IN ACCORDANCE WITH NFPA 13 AND LOCAL CODES. 21. ALL NEW FIRE SPRINKLER SHALL BE HYDRO STATICALLY TESTED AT 175PSI (OR 50 PSI ABOVE SYSTEM STATIC PRESSURE, WHICHEVER GREATER) FOR NOT LESS THAN 2 HOURS. 22. SYSTEM DESIGN PLACARDS,SPARE STOCK OF SPRINKLERS, AND HEAD CABINET WILL BE SUPPLIED AT THE SPRINKLER SYSTEM RISER AS REQUIRED BY NFPA 13. THE SPARE STOCK OF SPRINKLERS SHALL NOT BE SUBJECTED TO A TEMPERATURE EXCEEDING 100 F. 23. THE STRUCTURAL ENGINEER SHALL INCLUDE THE LOAD FOR THE SPRINKLER SYSTEM AND OTHER FIRE PROTECTION COMPONENTS INTO THE DESIGN OF THE STRUCTURE. REFER TO STRUCTURAL DRAWINGS. 24. ALL FIRE PROTECTION SYSTEMS AND MATERIAL TO COMPLY WITH HYATT PLACE BRAND STANDARDS FOR FIRE PROTECTION AND LIFE SAFETY. 25. ALL MATERIALS AND EQUIPMENT SHALL BE UL LISTED FOR USE IN FIRE PROTECTION SYSTEM AND BE IN CONFORMANCE WITH LOCAL AHJ AND NFPA 13 REQUIREMENTS. 26. SEE ARCH DRAWINGS FOR EXTINGUISHER CABINET LOCATION. 27. RECESSED SPRINKLER HEADS SHALL BE USED IN ALL PUBLIC AREAS INCLUDING REST ROOMS. 28. THE FP DRAWINGS INCLUDED IN THIS DESIGN DRAWING SET ARE SPECIFICATION ONLY. 29. THE FIRE PROTECTION SYSTEM NEEDS TO BE DESIGNED BY PROFESSIONAL ENGINEERS IN THE STATE THAT THE PROJECT IS LOCATED IN. 30. THE DETAILED DRAWING ,CUT SHEETS, PUMP SPECIFICATION TO BE SEND TO BASE4 FOR REVIEW WITH SIGN AND SEAL OF A FIRE PROTECTION ENGINEER. 31. CONTRACTOR TO FOLLOW THE NFPA STANDARD FOR FIRE PROTECTION REQUIREMENTS. 32. ALL HYDRAULIC CALCULATION TO BE DONE WITH REFERENCE TO CURRENT DATED FLOW TEST REPORT. 33. CONTRACTOR SHALL ENSURE SPRINKLER SYSTEM BE ZONED AT EVERY FLOOR WITH INSPECTOR'S TEST STATION WITH SIGHT GLASS AT EVERY HORIZONTAL SPRINKLER ZONE WITH A CONTROL VALVE AND TAMPER SWITCH, WATER FLOW SWITCH, PRESSURE GAUGE, AND DRAIN AND TEST ASSEMBLY R EQUIRED BY NFPA 13 34. FIRE CONTRACTOR SHALL ENSURE TO PROVIDE CORROSION RESISTANT SPRINKLER HEADS IN POOL ROOMS, POOL EQUIPMENT ROOMS, AND POOL \STORAGE ROOMS. 35. CONTRACTOR SHALL INSTALL A REMOTE INSPECTORS TEST FOR THE WET SPRINKLER SYSTEM PER WITH NFPA 13. 36. FIRE CONTRACTOR SHALL ENSURE TO PROVIDE FIRE SPRINKLER IN LINEN CHUTE AS PER NFPA 13 , NFPA 82. 37. OWNER SHALL SUBMIT THE OWNERS INFORMATION CERTIFICATE TO CITY. 38. ALL QUALITY AND PERFORMANCE SPECIFICATIONS FOR THE FIRE PROTECTION COMPONENTS ARE PROVIDED IN THE NOTES ON THIS SHEET. 39. CONTRACTOR SUBMITTAL WHICH DEVIATE FROM THE ABOVE MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING APPROVAL AND DOCUMENTATION. CONTRACTOR TO MAKE SURE 61G32 REQUIREMENTS AS MENTIONED IN SHEET FP-001 ARE MET. 40. IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES 41. CONTRACTOR TO INSTALL SPRINKLER HEADS CENTERED AND ALIGNED IN COORDINATION WITH THE CEILING LIGHTS AND DIFFUSERS. 42. CONTRACTOR SHALL INSTALL A QUICK RESPONSE SPRINKLER HEAD FOR EARLY SUPPRESSION OF FIRE IN LIGHT HAZARD OCCUPANCY. 43. CONTRACTOR TO INSTALL SEMI RECESSED WHITE HEADS IN PUBLIC AND GUESTROOM. 44. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLAN AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH THE SECTION AND CHAPTER 33, FLORIDA STATUES. FBC 6TH ED. 2017 SECTION110.8.4.4. FIRE PROTECTION FIRE ALARM ASSEMBLY FIRE DEPARTMENT CONNECTION FIRE PROTECTION CONTRACTOR FAA FDC F.P.C. SPRINKLER VALVE ASSEMBLY UNDERWRITERS LABORATORY INC. SVA U.L. BASE4 WILL NOT BE RESPONSIBLE FOR CHANGES OF ANY KIND (CHANGE ORDERS, BACK CHARGES OR DELAY CLAIMS) FROM ANY SET PROVIDED BY BASE4 PRIOR TO THE RECEIPT OF A BUILDING PERMIT FROM THE AHJ. THIS INCLUDES BUT IS NOT LIMITED TO PROGRESS SETS, EARLY STAGE RELEASES, FRANCHISE SUBMITTALS OR BID SETS. ONLY AHJ APPROVED PERMIT SETS SHALL BE CONSIDERED ACCEPTABLE FOR CONSTRUCTION OR FINAL PRICING. BIDDING, FABRICATING OR BUILDING FROM NON PERMIT APPROVED DRAWINGS IS SOLELY AT THE CONTRACTOR'S RISK. 1. TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS,SAID DOCUMENTS SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN APPLICABLE. a. THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER SUPPLY AS DEFINED BY SECTION 633.021(17), F.S. BASE4 RESPONSE: SEE SITE UTILITY PLAN EXH102T.CIVIL HAS PROVIDED NEW 6' DR14 PVC MAIN FIRE SERVICE LINE. b. APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND CONCLUSIONS. BASE4 RESPONSE: PLEASE REFER TO FP001 GENERAL NOTE #30. c. CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR AREA. BASE4 RESPONSE: AS PER NFPA 13 THE HAZARD OCCUPANCY FOR THE BUILDING IS LIGHT AND ORDINARY HAZARD. PLEASE REFER TO SHEET FP101-106 BELOW GENERAL NOTES. d. DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE, DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR EACH SEPARATE HAZARD OCCUPANCY. BASE4 RESPONSE: BASE4 HAS PROVIDED A WET PIPE SYSTEM FOR THIS PROJECT. MINIMUM DENSITY AND AREA OF COVERAGE IS O.15 PER SQFT AS PER THE NFPA13 SECTION 11.2.3.1 AND SPRINKLER SPACING WOULD BE 15" SPRINKLER TO SPRINKLER SPACING AS PER NFPA 13 SECTION 8.6.2.2.1. e. CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY DEMANDING DESIGN AREA. BASE4 RESPONSE: THE FIRE MAIN LINE IS 6" AND MAIN WATER SUPPLY LINE IS OF CIRCULATING TYPE. f. WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION, STATIC GAUGE PRESSURE AT NO FLOW RATE WITH RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF SERVICE. BASE4 RESPONSE: A FIRE FLOW TEST WAS CONDUCTED ON 2019.01/18 at 08.3 1AM BY TWD AS PER THE FLOW TEST CONDUCTED THE FLOW RATE AT THE HYDRANT IS 1187GPM WITH RESIDUAL PRESSURE OF 60PSI AND STATIC PRESSURE OF 62PSI .OWNER TO SUPPLY COPY OF THIS TEST. g. VALVING AND ALARM REQUIREMENTS TO MINIMIZE POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF WATER. BASE4 RESPONSE: BASE4 HAS PROVIDED VALVES AND WATER SUPPLY ENTRY DETAIL.PLEASE REFER TO SHEET FP-001 DETAIL-3. h. MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY WITH CONDITIONS OF THE FIRE PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE MEASURES. BASE4 RESPONSE: MICROBIAL INDUCED CORROSION IS TO BE TESTED IN THE FIRE PROTECTION PIPING GC TO TAKE NECESSARY CORRECTIVE MEASURES". BASE 4 HAS PROPOSED THE WATER SOFTENER FOR THE BUILDING. i. BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP. BASE4 RESPONSE: REFER TO SHEET FP-001DETAIL-1 FOR BFP. WE HAVE PROVIDED A NOTE ON SHEET FP-001 BELOW DETAIL-1," BACKFLOW PREVENTION AND METERING SHALL MEET LOCAL WATER PURVEYOR REQUIREMENTS INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP. j. QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD AND INTERIOR FIRE PROTECTION COMPONENTS. BASE4 RESPONSE: BASE4 HAS ADDED NOTE "ALL QUALITY AND PERFORMANCE S PECIFICATIONS FOR THE FIRE PROTECTION COMPONENTS ARE PROVIDE IN NOTES ON THIS SHEET." PLEASE REFER TO SHEET FP-001 NOTE # 31. k. A DETERMINATION OF WHETHER A FIRE PUMP IS REQUIRED AND IF SO, THE SPECIFIC VOLUMETRIC FLOW AND PRESSURE OF THE PUMP. BASE4 RESPONSE: AS PER THE RESIDUAL PRESSURE OF 60PSI FIRE PUMP IS REQUIRED.THE SPECIFIC VOLUMETRIC FLOW AND PRESSURE OF THE PUMP WILL PROVIDE BY THE FIRE VENDOR. l. A VERIFICATION OF WHETHER A FIREWATER STORAGE TANK IS REQUIRED ON SITE AND IF SO, A DETERMINATION OF THE SIZE AND CAPACITY REQUIRED. BASE4 RESPONSE: A FIRE WATER STORAGE TANK IS NOT REQUIRED. m. OWNER'S CERTIFICATE. IN STORAGE OCCUPANCIES, THE OWNER'S INFORMATION CERTIFICATE IS REQUIRED FROM THE PROPERTY OWNER AS IT CLEARLY DEFINES THE STORAGE CONFIGURATION OF THE SPACE FOR THE CURRENT AND FUTURE USE OF THE PROPERTY, AS REQUIRED BY THE CODES AND STANDARDS SET FORTH IN SUBSECTION 61G15-32.002(7), F.A.C. BASE4 RESPONSE: WE HAVE PROVIDED NOTE, "OWNER SHALL SUBMIT THE OWNER'S INFORMATION CERTIFICATE TO CITY." SEE GENERAL NOTE #36 IN FP001 SHEET. 2. CONTRACTOR SUBMITTAL WHICH DEVIATE FROM THE ABOVE MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED. MATERIAL DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING APPROVAL AND DOCUMENTATION. BASE4 RESPONSE: BASE4 HAS ADDED A NOTE. PLEASE REFER TO GENERAL NOTE#36, SHEET FP-001 3. IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES. BASE4 RESPONSE: BASE4 HAS ADDED A NOTE ADDRESSING THIS. PLEASE REFER TO GENERAL NOTE# 37, SHEET FP-001 61G32 REQUIREMENTS GRV'D CHECK VALVE GRV'D BUTTERFLY VA. W/ TAMPER SWITCH GLOBE UMC CONTROL VA. ASSEMBLY (1) DRAIN AND TEST (2) FLOW SWITCH (3) PRESSURE GAUGE (4) SINGS ON BODY STANDPIPE 2' X 2" X 1 - 1/4" Tee 2" DRAIN 4" DRAIN 4" 2" 1 - 1/4" TO HANDLE AFF 5'-0" 2 - 1/2" BRASS HOSE VALVE w/ 2' - 1/2" CAP & CHAIN MAINTAIN 7'-2" CLEAR HEIGHT TO SYSTEM 0'-9" SCH 7 2-9 8'-0" FF FLOOR PIPE TAP FOR BALL DRIP VALVE HORIZONTAL MOUNTED BALL DRIP VALVE 2" DRAIN PIPE TO OUTSIDE FIRE DEPARTMENT CONNECTION REFER ARCHITECTURAL DRAWINGS FOR EXTERIOR WALL TYPE WALL PLATE (TYPICAL) EXISTING GRADE 18" TO 48" BULK FEED MAIN TO SPRINKLER SYSTEM SIZED BY HYDRAULIC CALCULATIONS SPARE SPRINKLER HEAD CABINET MTD. ON WALL. BACKFLOW PREVENTION DEVICE ASSEMBLY W/TAMPER SWITCHES ON SHUT-OFF VALVES. CONCRETE THRUST BLOCK (TYP.) BRIDLE ROD (TYP.) FINISHED FLOOR (REF.) FIRE LINE SUPPLY. SEE SITE UTILITY FOR CONTINUATION TO ON-SITE POST TYPE F.D. SIAMESE CONN. SEE SITE UTILITY PLANS FOR CONTINUATION 2" MAIN DRAIN F.D. SIAMESE CONNECTION-VERIFY LOCATION WITH CIVIL CHECK VALVE WITH BALL DRIP RETARD CHAMBER WITH FLOW SWITCH WATER MOTOR GONG A/S F F ALARM CHECK VALVE ASSEMBLY w/TRIM 2" SCH. 40 STEEL PIPE SUPPORT 11810 HIGH TECH AVE ORLANDO, FL 32817 BASE4 2901 CLINT MOORE ROAD , #114 BOCA RATON, FLORIDA 33496 888.901.8008 www.base - 4.com AA26003324 CA 29917 PREMIER RESORTS & MANAGEMENT, INC. (PRM HOTEL GROUP ) 730 S. ATLANTIC AVE. SUITE 102 ORMOND BEACH, FLORIDA, 32176 386.677.8882 Owner: Seal: RICARDO J. MUNIZ - GUILLET, AIA 2030 HABERSHAM TRACE, CUMMING, GA 30041 DRAWINGS NO. SHEET NAME PROJECT NO. CHECKED BY DRAWN BY CURRENT ISSUE CURRENT ISSUE DATE PROTOTYPE VERSION: VOLUME 1.0 ISSUE 1.1 RELEASE DATE: MAY 06, 2019 MEP ENGINEER GARRY VERMAAS PhD, PE 2183 S BERRYS CHAPEL ROAD FRANKLIN, TN 37069 FP - 001 B4 - 171 - 1901 GWV MWI 2021.06.03 GENERAL NOTES, LEGEND & ABBREVIATIONS 100% OWNER REVIEW SHEET NUMBER SHEET NAME CURRENT ISSUE DATE CURRENT ISSUE DESCRIPTION FP-001 GENERAL NOTES, LEGEND & ABBREVIATIONS 2021.06.03 100% OWNER REVIEW FP-101 1ST FLOOR FIRE SPECIFICATION PLAN 2021.06.03 100% OWNER REVIEW FP-102 2ND FLOOR FIRE SPECIFICATION PLAN 2021.06.03 100% OWNER REVIEW FP-103 3RD FLOOR FIRE SPECIFICATION PLAN 2021.06.03 100% OWNER REVIEW FP-104 4TH FLOOR FIRE SPECIFICATION PLAN 2021.06.03 100% OWNER REVIEW FP-105 5TH FLOOR FIRE SPECIFICATION PLAN 2021.06.03 100% OWNER REVIEW FP-106 6TH FLOOR FIRE SPECIFICATION PLAN 2021.06.03 100% OWNER REVIEW NTS FP-001 3 TYPICAL ZONE CONTROL ASSEMBLY NTS FP-001 1 FIRE DEPARTMENT CONNECTION DETAIL NTS FP-001 2 AUTOMATIC SPRINKLER SYSTEM RISER DETAIL ISSUE NO. DELTA ISSUE DATE DESCRIPTION 1 FP0 2021.06.03 100% OWNER REVIEW

Transcript of FP-001 - planhubapp.s3-us-west-2.amazonaws.com

Page 1: FP-001 - planhubapp.s3-us-west-2.amazonaws.com

PROJECT GENERAL NOTES DRAWING INDEX

SPRINKLER HEAD

FLOW SWITCH

FIRE DEPARTMENT CONNECTION

FIRE ALARM ASSEMBLY

SPRINKLER VALVE ASSEMBLY

PUMP

LEGEND

SYMBOL DESCRIPTION

ABBREVIATIONS

1. THE SPRINKLER CONTRACTOR SHALL PROVIDE COMPLETE HYDRAULIC CALCULATIONS, PIPE SIZING, PIPE MATERIAL WITH LAY-OUT DWG'S & CONSTRUCTION LAY-OUT DWG'S.

2. ALL SPRINKLER HEADS SERVING, ELECTRIC, TELEPHONE, SWITCHGEAR & ELEVATOR MACHINE ROOMS SHALL BE PROVIDED BY SHUT-OFF VALVES W/ TAMPER SWITCHES.

3. 4. THE FIRE PROTECTION SYSTEM DESIGN, INSTALLATION AND MATERIALS SHALL BE IN AS

COMPLIANCE WITH NFPA AND THE MOST RECENT STATE BUILDING CODE AND FIRE CODES, WELL AS ANY APPLICABLE STATE STATUTES.

5. SPRINKLER SYSTEM TO BE INSTALLED BY A STATE CERTIFIED FIRE PROTECTIONCONTRACTOR.6. CONTRACTOR SHALL COORDINATE WITH STRUCTURE, CEILING GRID AND ELEVATION, AND

OTHER MECHANICAL AND ELECTRICAL SERVICES BEFORE FABRICATING AND INSTALLING SPRINKLER HEADS & PIPING. MAKE OFFSETS IN PIPING AS REQUIRED PER FIELD CONDITIONS. MAINTAIN 6" CLEARANCE BETWEEN PIPING AND 1 AND 2 HOUR RATED WALLS INCLUDING CORRIDOR WALLS.

7. ALL VALVES SHALL BE BY DOMESTIC MANUFACTURER, U.L. LISTED FOR FIRE PROTECTION SERVICE AND RATED FOR 175 PSI WORKING PRESSURE. PROVIDE U.L. LISTED/ FM APPROVED TAMPER SWITCHES AT CONTROL VALVE LOCATIONS. PROVIDE U.L. LISTED/ FM APPROVED FLOW SWITCHES, WHERE SHOWN, AT CONTROL VALVE LOCATIONS.

8. SPRINKLER HEADS SHALL BE LISTED AS INDICATED IN SCHEDULE AND RATED FOR 175 PSI WORKING PRESSURE. PROVIDE HEAD GUARDS ON UPRIGHT AND PENDANT SPRINKLER HEADS LOCATED IN ELEVATOR SHAFTS, MECHANICAL SHAFTS, ELECTRICAL, TELEPHONE, MECHANICAL AND MACHINE ROOMS. CONTRACTOR SHALL PROVIDE THE OWNER WITH A COPY OF NFPA 25.

9. CONTRACTOR SHALL PROVIDE FLUSHING CONNECTIONS WHERE SHOWN ON PLANS. PROVIDE A DRAIN CONNECTION FOR ALL TRAPPED SECTION OF PIPING.

10. INSPECTORS TEST, DRAIN AND SHUT-OFF VALVES SHALL BE LOCATED AT MAXIMUM OF7'-0" AFF.11. ALL SPRINKLER HEADS SHALL BE CENTERED AND PRESENTED IN A NEAT AND BALANCED

CEILING PATTERN. FP CONTRACTOR TO COORDINATE WITH ARCHITECT AND INTERIOR DESIGNER.

12. PIPING TO BE BLACK STEEL IN AIR CONDITIONED SPACES, PIPING IN NON-AIR CONDITIONED SPACE SHALL BE BLACK STEEL SCHEDULE 40 (PAINTED) WITH AN ALTERNATE FOR GALVANIZED SCHEDULE 40. GROOVED FITTINGS ARE NOT ALLOWED WHERE PRESSURE EXCEEDS 175 PSI.

13. SPRINKLER HEADS TO BE MODEL GBR SERIES SPRINKLER WHITE PLATED SEMI RECESSED TYPE FOR SIDE WALL, AND FOR CEILING LOCATIONS, BRASS UPRIGHT FOR EXPOSED LOCATIONS, RECESSED TYPE FOR FIRST FLOOR LOBBY AREAS. TEFLON FINISHED HEADS TO BE USED IN NON-AIR CONDITIONED AREAS.

14. SPRINKLER HEADS SHOULD BE PROVIDED ON FIRE RATED WALLS WHERE THERE ARE INTERIOR ALUMINUM WINDOWS. SPRINKLER HEADS SHOULD ALSO BE PROVIDED INSIDE OF LAUNDRY CHUTES.

15. SPRINKLER SUBCONTRACTOR TO PROVIDE ALL REQUIRED STANDPIPES AND FIRE HOSE VALVES, FLOW AND TAMPER SWITCHES, PRESSURE REDUCING VALVES AT ALL FLOORS, SIAMESE CONNECTIONS, INSPECTOR TEST STATIONS, SPARE SPRINKLER HEAD CABINET. ALL NECESSARY DRAINS AND SIGNAGE.

16. FIRE PUMP AND CONTROLLER SHALL BE SIZED ACCORDING TO HYDRAULIC CALCULATIONS AND FLOW TEST. IF FIRE PUMP IS REQUIRED, FP CONTRACTOR SHALL SUBMIT FIRE PUMP SHOP DRAWINGS TO EOR FOR REVIEW. ALL ASSOCIATED ACCESSORIES INCLUDING JOCKEY PUMP AND CONTROLLER, PUMP BYPASS, AND NECESSARY VALVING SHALL MEET LOCAL CODES AND NFPA STANDARDS. PROVIDE REMOTE ANNUNCIATOR AT FIRE COMMAND ROOM AND REMOTE ALARM AT SECURITY DESK.

17. ALL EXPOSED FIRE ALARM PIECES (STROBES, SPEAKERS, PULL STATIONS) TO BE WHITE IN COLOR WHERE POSSIBLE. FP CONTRACTOR SHALL COORDINATE WITH ARCHITECT AND INTERIOR DESIGNER.

18. FIRE CONTRACTOR MUST PROVIDE LANDLORD AND TENANT WITH A COPY OF NFPA 25.

19. FP SUBCONTRACTOR SHALL CONNECT MAIN FIRE LINE TO UTILITY SOURCE AND PROVIDE CONTROL VALVE/PIV. SUCTION SIDE PIPING SHALL BE DUCTILE IRON

20. ALL FIRE SPRINKLER SHALL BE MONITORED 24 HOURS A DAY BY AN APPROVED CENTRAL STATION IN ACCORDANCE WITH NFPA 13 AND LOCAL CODES.

21. ALL NEW FIRE SPRINKLER SHALL BE HYDRO STATICALLY TESTED AT 175PSI (OR 50 PSI ABOVE SYSTEM STATIC PRESSURE, WHICHEVER GREATER) FOR NOT LESS THAN 2 HOURS.

22. SYSTEM DESIGN PLACARDS,SPARE STOCK OF SPRINKLERS, AND HEAD CABINET WILL BE SUPPLIED AT THE SPRINKLER SYSTEM RISER AS REQUIRED BY NFPA 13. THE SPARE STOCK OF SPRINKLERS SHALL NOT BE SUBJECTED TO A TEMPERATURE EXCEEDING 100 F.

23. THE STRUCTURAL ENGINEER SHALL INCLUDE THE LOAD FOR THE SPRINKLER SYSTEM AND OTHER FIRE PROTECTION COMPONENTS INTO THE DESIGN OF THE STRUCTURE. REFER TO STRUCTURAL DRAWINGS.

24. ALL FIRE PROTECTION SYSTEMS AND MATERIAL TO COMPLY WITH HYATT PLACE BRAND STANDARDS FOR FIRE PROTECTION AND LIFE SAFETY.

25. ALL MATERIALS AND EQUIPMENT SHALL BE UL LISTED FOR USE IN FIRE PROTECTION SYSTEM AND BE IN CONFORMANCE WITH LOCAL AHJ AND NFPA 13 REQUIREMENTS.

26. SEE ARCH DRAWINGS FOR EXTINGUISHER CABINET LOCATION.

27. RECESSED SPRINKLER HEADS SHALL BE USED IN ALL PUBLIC AREAS INCLUDING REST ROOMS.

28. THE FP DRAWINGS INCLUDED IN THIS DESIGN DRAWING SET ARE SPECIFICATION ONLY.

29. THE FIRE PROTECTION SYSTEM NEEDS TO BE DESIGNED BY PROFESSIONAL ENGINEERS IN THE STATE THAT THE PROJECT IS LOCATED IN.

30. THE DETAILED DRAWING ,CUT SHEETS, PUMP SPECIFICATION TO BE SEND TO BASE4 FOR REVIEW WITH SIGN AND SEAL OF A FIRE PROTECTION ENGINEER.

31. CONTRACTOR TO FOLLOW THE NFPA STANDARD FOR FIRE PROTECTION REQUIREMENTS.32. ALL HYDRAULIC CALCULATION TO BE DONE WITH REFERENCE TO CURRENT DATED FLOW TEST

REPORT.

33. CONTRACTOR SHALL ENSURE SPRINKLER SYSTEM BE ZONED AT EVERY FLOOR WITH INSPECTOR'S TEST STATION WITH SIGHT GLASS AT EVERY HORIZONTAL SPRINKLER ZONE WITH A CONTROL VALVE AND TAMPER SWITCH, WATER FLOW SWITCH, PRESSURE GAUGE, AND DRAIN AND TEST ASSEMBLY R EQUIRED BY NFPA 13

34. FIRE CONTRACTOR SHALL ENSURE TO PROVIDE CORROSION RESISTANT SPRINKLER HEADS IN POOL ROOMS, POOL EQUIPMENT ROOMS, AND POOL \STORAGE ROOMS.

35. CONTRACTOR SHALL INSTALL A REMOTE INSPECTORS TEST FOR THE WET SPRINKLER SYSTEM PER WITH NFPA 13.

36. FIRE CONTRACTOR SHALL ENSURE TO PROVIDE FIRE SPRINKLER IN LINEN CHUTE AS PER NFPA 13 , NFPA 82.

37. OWNER SHALL SUBMIT THE OWNERS INFORMATION CERTIFICATE TO CITY.

38. ALL QUALITY AND PERFORMANCE SPECIFICATIONS FOR THE FIRE PROTECTION COMPONENTS ARE PROVIDED IN THE NOTES ON THIS SHEET.

39. CONTRACTOR SUBMITTAL WHICH DEVIATE FROM THE ABOVE MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING APPROVAL AND DOCUMENTATION. CONTRACTOR TO MAKE SURE 61G32 REQUIREMENTS AS MENTIONED IN SHEET FP-001 ARE MET.

40. IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES

41. CONTRACTOR TO INSTALL SPRINKLER HEADS CENTERED AND ALIGNED IN COORDINATION WITH THE CEILING LIGHTS AND DIFFUSERS.

42. CONTRACTOR SHALL INSTALL A QUICK RESPONSE SPRINKLER HEAD FOR EARLY SUPPRESSION OF FIRE IN LIGHT HAZARD OCCUPANCY.

43. CONTRACTOR TO INSTALL SEMI RECESSED WHITE HEADS IN PUBLIC AND GUESTROOM.

44. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLAN AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH THE SECTION AND CHAPTER 33, FLORIDA STATUES. FBC 6TH ED. 2017 SECTION110.8.4.4.

FIRE PROTECTION

FIRE ALARM ASSEMBLY

FIRE DEPARTMENT CONNECTION

FIRE PROTECTION CONTRACTOR

FAA

FDC

F.P.C.

SPRINKLER VALVE ASSEMBLY

UNDERWRITERS LABORATORY INC.

SVA

U.L.

BASE4 WILL NOT BE RESPONSIBLE FOR CHANGES OF ANY KIND (CHANGE ORDERS, BACK CHARGES OR DELAY CLAIMS) FROM ANY SET PROVIDED BY BASE4 PRIOR TO THE RECEIPT OF A BUILDING PERMIT FROM THE AHJ. THIS INCLUDES BUT IS NOT LIMITED TO PROGRESS SETS, EARLY STAGE RELEASES, FRANCHISE SUBMITTALS OR BID SETS. ONLY AHJ APPROVED PERMIT SETS SHALL BE CONSIDERED ACCEPTABLE FOR CONSTRUCTION OR FINAL PRICING. BIDDING, FABRICATING OR BUILDING FROM NON PERMIT APPROVED DRAWINGS IS SOLELY AT THE CONTRACTOR'S RISK.

1. TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS,SAID DOCUMENTS SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN APPLICABLE.

a. THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER SUPPLY AS DEFINED BY SECTION 633.021(17), F.S.

BASE4 RESPONSE: SEE SITE UTILITY PLAN EXH102T.CIVIL HAS PROVIDED NEW 6' DR14 PVC MAIN FIRE SERVICE LINE.

b. APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND CONCLUSIONS. BASE4 RESPONSE: PLEASE REFER TO FP001 GENERAL NOTE #30.

c. CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR AREA. BASE4 RESPONSE: AS PER NFPA 13 THE HAZARD OCCUPANCY FOR THE BUILDING IS LIGHT AND ORDINARY HAZARD. PLEASE REFER TO SHEET FP101-106 BELOW GENERAL NOTES.

d. DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE, DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR EACH SEPARATE HAZARD OCCUPANCY. BASE4 RESPONSE: BASE4 HAS PROVIDED A WET PIPE SYSTEM FOR THIS PROJECT. MINIMUM

DENSITY AND AREA OF COVERAGE IS O.15 PER SQFT AS PER THE NFPA13 SECTION 11.2.3.1 AND SPRINKLER SPACING WOULD BE 15" SPRINKLER TO SPRINKLER SPACING AS PER NFPA 13 SECTION 8.6.2.2.1.

e. CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY DEMANDING DESIGN AREA. BASE4 RESPONSE: THE FIRE MAIN LINE IS 6" AND MAIN WATER SUPPLY LINE IS OF CIRCULATING TYPE.

f. WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION, STATIC GAUGE PRESSURE AT NO FLOW RATE WITH RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF SERVICE. BASE4 RESPONSE: A FIRE FLOW TEST WAS CONDUCTED ON 2019.01/18 at 08.3 1AM BY TWD AS PER THE FLOW TEST CONDUCTED THE FLOW RATE AT THE HYDRANT IS 1187GPM WITH RESIDUAL PRESSURE OF 60PSI AND STATIC PRESSURE OF 62PSI .OWNER TO SUPPLY COPY OF THIS TEST.

g. VALVING AND ALARM REQUIREMENTS TO MINIMIZE POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF WATER. BASE4 RESPONSE: BASE4 HAS PROVIDED VALVES AND WATER SUPPLY ENTRY DETAIL.PLEASE

REFER TO SHEET FP-001 DETAIL-3.

h. MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY WITH CONDITIONS OF THE FIRE PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE MEASURES. BASE4 RESPONSE: MICROBIAL INDUCED CORROSION IS TO BE TESTED IN THE FIRE PROTECTION PIPING GC TO TAKE NECESSARY CORRECTIVE MEASURES". BASE 4 HAS PROPOSED THE WATER SOFTENER FOR THE BUILDING. i. BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP. BASE4 RESPONSE: REFER TO SHEET FP-001DETAIL-1 FOR BFP. WE HAVE PROVIDED A NOTE ON SHEET FP-001 BELOW DETAIL-1," BACKFLOW PREVENTION AND METERING SHALL MEET LOCAL WATER PURVEYOR REQUIREMENTS INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP.

j. QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD AND INTERIOR FIRE PROTECTION COMPONENTS. BASE4 RESPONSE: BASE4 HAS ADDED NOTE "ALL QUALITY AND PERFORMANCE S PECIFICATIONS FOR THE FIRE PROTECTION COMPONENTS ARE PROVIDE IN NOTES ON THIS SHEET." PLEASE REFER TO SHEET FP-001 NOTE # 31.

k. A DETERMINATION OF WHETHER A FIRE PUMP IS REQUIRED AND IF SO, THE SPECIFIC VOLUMETRIC FLOW AND PRESSURE OF THE PUMP. BASE4 RESPONSE: AS PER THE RESIDUAL PRESSURE OF 60PSI FIRE PUMP IS REQUIRED.THE SPECIFIC VOLUMETRIC FLOW AND PRESSURE OF THE PUMP WILL PROVIDE BY THE FIRE VENDOR.

l. A VERIFICATION OF WHETHER A FIREWATER STORAGE TANK IS REQUIRED ON SITE AND IF SO, A DETERMINATION OF THE SIZE AND CAPACITY REQUIRED. BASE4 RESPONSE: A FIRE WATER STORAGE TANK IS NOT REQUIRED.

m. OWNER'S CERTIFICATE. IN STORAGE OCCUPANCIES, THE OWNER'S INFORMATION CERTIFICATE IS REQUIRED FROM THE PROPERTY OWNER AS IT CLEARLY DEFINES THE STORAGE CONFIGURATION OF THE SPACE FOR THE CURRENT AND FUTURE USE OF THE PROPERTY, AS REQUIRED BY THE CODES AND STANDARDS SET FORTH IN SUBSECTION 61G15-32.002(7), F.A.C. BASE4 RESPONSE: WE HAVE PROVIDED NOTE, "OWNER SHALL SUBMIT THE OWNER'S INFORMATION CERTIFICATE TO CITY." SEE GENERAL NOTE #36 IN FP001 SHEET.

2. CONTRACTOR SUBMITTAL WHICH DEVIATE FROM THE ABOVE MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED. MATERIAL DEVIATIONS AND REQUIRE

SUPPLEMENTAL ENGINEERING APPROVAL AND DOCUMENTATION. BASE4 RESPONSE: BASE4 HAS ADDED A NOTE. PLEASE REFER TO GENERAL NOTE#36, SHEET FP-0013. IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE INFORMATION AND DIRECTION

THAN IS ESTABLISHED ABOVE, HE OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES. BASE4 RESPONSE: BASE4 HAS ADDED A NOTE ADDRESSING THIS. PLEASE REFER TO GENERAL NOTE# 37, SHEET FP-001

61G32 REQUIREMENTS

GRV'D CHECK VALVE

GRV'D BUTTERFLY VA.W/ TAMPER SWITCH

GLOBE UMC CONTROL VA. ASSEMBLY

(1) DRAIN AND TEST(2) FLOW SWITCH(3) PRESSURE GAUGE(4) SINGS ON BODY

ST

AN

DP

IPE

2' X 2" X 1 -1/4" Tee

2"

DR

AIN

4"

DR

AIN

4"

2"

1 -1/4"

TO

HA

ND

LE

A

FF

5'-0"

2-1/2" BRASS HOSE VALVE w/2'-1/2" CAP & CHAIN

MA

INT

AIN

7'-2"

CLE

AR

HE

IGH

T

TO

SYSTEM

0'-9"

SCH 7

2-9

8'-0"

FF

FLOOR

PIPE TAP FOR BALL DRIP VALVE

HORIZONTAL MOUNTED BALL DRIP VALVE

2" DRAIN PIPE TO

OUTSIDE

FIRE DEPARTMENT CONNECTION

REFER ARCHITECTURAL DRAWINGS FOR EXTERIOR WALL TYPE

WALL PLATE (TYPICAL)

EXISTING GRADE18

" T

O 4

8"

BULK FEED MAIN TOSPRINKLER SYSTEMSIZED BY HYDRAULICCALCULATIONS

SPARE SPRINKLER HEADCABINET MTD. ON WALL.

BACKFLOW PREVENTION DEVICEASSEMBLY W/TAMPER SWITCHES ON SHUT-OFF VALVES.

CONCRETE THRUSTBLOCK (TYP.)

BRIDLE ROD (TYP.)

FINISHED FLOOR (REF.)

FIRE LINE SUPPLY.SEE SITE UTILITY FOR CONTINUATION

TO ON-SITE POSTTYPE F.D. SIAMESE CONN. SEE SITE UTILITY PLANS FOR CONTINUATION

2" MAIN DRAIN

F.D. SIAMESECONNECTION-VERIFYLOCATION WITH CIVIL

CHECK VALVEWITH BALL DRIP

RETARD CHAMBERWITH FLOW SWITCH

WATER MOTOR GONG

A/S

F

F

ALARM CHECK VALVEASSEMBLY w/TRIM

2" SCH. 40 STEEL PIPE SUPPORT

11810 HIGH TECH AVEORLANDO, FL 32817

BASE42901 CLINT MOORE ROAD, #114BOCA RATON, FLORIDA 33496888.901.8008 www.base-4.com

AA26003324CA 29917

PREMIER RESORTS & MANAGEMENT, INC.(PRM HOTEL GROUP)

730 S. ATLANTIC AVE. SUITE 102ORMOND BEACH, FLORIDA, 32176

386.677.8882

Owner:

Seal:

RICARDO J. MUNIZ-GUILLET, AIA2030 HABERSHAM TRACE,

CUMMING, GA 30041

DRAWINGS NO.

SHEET NAME

PROJECT NO.

CHECKED BY

DRAWN BY

CURRENT ISSUE

CURRENT ISSUE DATE

PROTOTYPE VERSION: VOLUME 1.0 ISSUE 1.1RELEASE DATE: MAY 06, 2019

MEP ENGINEERGARRY VERMAAS PhD, PE

2183 S BERRYS CHAPEL ROADFRANKLIN, TN 37069

FP-001

B4-171-1901

GWV

MWI

2021.06.03

GENERAL NOTES,LEGEND &

ABBREVIATIONS

100% OWNER REVIEW

SHEETNUMBER

SHEET NAMECURRENT

ISSUE DATECURRENT ISSUE

DESCRIPTIONFP-001 GENERAL NOTES, LEGEND & ABBREVIATIONS 2021.06.03 100% OWNER REVIEW

FP-101 1ST FLOOR FIRE SPECIFICATION PLAN 2021.06.03 100% OWNER REVIEW

FP-102 2ND FLOOR FIRE SPECIFICATION PLAN 2021.06.03 100% OWNER REVIEW

FP-103 3RD FLOOR FIRE SPECIFICATION PLAN 2021.06.03 100% OWNER REVIEW

FP-104 4TH FLOOR FIRE SPECIFICATION PLAN 2021.06.03 100% OWNER REVIEW

FP-105 5TH FLOOR FIRE SPECIFICATION PLAN 2021.06.03 100% OWNER REVIEW

FP-106 6TH FLOOR FIRE SPECIFICATION PLAN 2021.06.03 100% OWNER REVIEW

NTSFP-001

3 TYPICAL ZONE CONTROL ASSEMBLY

NTSFP-001

1 FIRE DEPARTMENT CONNECTION DETAIL

NTSFP-001

2 AUTOMATIC SPRINKLER SYSTEM RISER DETAIL

ISSUENO.

DELTA ISSUE DATE DESCRIPTION

1 FP0 2021.06.03 100% OWNER REVIEW

Page 2: FP-001 - planhubapp.s3-us-west-2.amazonaws.com

2" INSPECTOR'S TEST DRAIN RELEASE ABOVE GRADE

1

4'' STAND PIPE UP LANDING VALVE

BUTTERFLY VALVE

FLOW DETECTOR SWITCH

PRESSURE GUAGE

TEST AND VALVE ASSEMBLY

PIPE TO THE SPRINKLER

4" SPRINKLER PIPE IN CEILING

TO FIRE DEPARTMENT CONNECTION. (VERIFY LOCATION AT SITE. SEE CIVIL PLAN FOR CONTINUATION)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22

A

B

C

D

E

F

G

H

J

K

6" FIRE LINE CONNECT FROM THE MAIN .(VERIFY LOCATION AT SITE. SEE CIVIL PLAN FOR CONTINUATION)

SPRINKLER VALVE ASSEMBLY

PIPE UP

ELEV.2

150

ELEV.1

151

VESTIBULE

130

COMPUTER

169

WORKROOM

171

SALES

170

MEETINGROOM

168

BREAKOUT

167

MEETINGROOM

166

MEETINGROOM

165

MEETINGROOM

STORAGE

164

STAIR #1

180

ELECTRICAL

163

MECHANICAL

162

JANITOR'SCLOSET

161

MAINTENANCE

160

POOLEQUIPMENT

159

TOILET

158

EMPLOYEEBREAKROOM

157

LINENSTORAGE

155

LINENCHUTE

156

UNISEX

152

CORRIDOR

151DRYERS

154

LAUNDRY

153

STORAGE

144

DISHWASHING

145

FOODPREP

143

MEN'S

146

WOMEN'S

147

DRINKINGFOUNTAIN

148

CORRIDOR

100.2

GUESTKITCHEN

142

GUESTDINING

141

STAIR #2

181

CHECK-IN

136

LOUNGE 2

135

HOST/BAR/CAFE

133

GRAB-N-GO

132

LOUNGE 1

134

BUSINESSCENTER

139

GMOFFICE

137

LUGGAGE

138

VESTIBULE

150

ELEV.LOBBY

149

CORRIDOR

100.1

LOBBY

131

OUTDOORPOOL

172

OUTDOORPATIO

140

OUTDOORPATIO

328

4" SPRINKLER PIPE IN CEILING 4" SPRINKLER PIPE IN CEILING

4'' STAND PIPE UP

LANDING VALVEATS

CLOSET

163.1

2

31

GENERAL NOTES

1. COMBUSTIBLE CONCEALED SPACES SHALL REQUIRE SPRINKLER HEADS FOR FIRE PROTECTION.

2. PORTE-COCHERE PROJECTION SHALL BE PROTECTED WITH FIRE SPRINKLER HEADS IF IT IS NOT CONSTRUCTED WITH MATERIALS THAT ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, OR FIRE RETARDANT–TREATED WOOD”.

3. SPRINKLERS SHALL NOT BE REQUIRED IN BATHROOMS THAT ARE LOCATED WITHIN DWELLING UNITS, THAT DO NOT EXCEED 55 FT2 (5.1 M2) IN AREA, AND THAT HAVE WALLS AND CEILINGS OF NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE MATERIALS WITH A 15-MINUTE THERMAL BARRIER RATING, INCLUDING THE WALLS AND CEILINGSBEHIND ANY SHOWER ENCLOSURE OR TUB.

4. FIRE VENDOR TO PROVIDE A FIRE SPRINKLER DRAWING SUBMITTALS TO FIRE DEPARTMENT FOR APPROVAL BEFORE PRIOR TO ANY WORK ON THE FIRE SPRINKLER SYSTEM BEGINNING.

5. FIRE CONTRACTOR TO PROVIDE A FLOW BELL ON THE EXTERIOR NEAREST TO A RISER.

6. FIRE SUB CONTRACTOR SHALL ENSURE THAT THE MAIN FIRE LINE COMING TO MECHANICAL ROOM/PUMP ROOM MUST BE BURIED NOT LESS THAN 1 FT (0.3 M) BELOW THE FROST LINE OR FROM THE BOTTOM OF FOOTING

7. THE REQUIREMENT OF FIRE PUMP SHALL BE DETERMINED ONCE THE FLOW TEST REPORT IS RECEIVED, OWNER TO PROVIDE THE FLOW TEST REPORT FOR CALCULATION OF FIRE PUMP TO BASE-4.

11810 HIGH TECH AVEORLANDO, FL 32817

BASE42901 CLINT MOORE ROAD, #114BOCA RATON, FLORIDA 33496888.901.8008 www.base-4.com

AA26003324CA 29917

PREMIER RESORTS & MANAGEMENT, INC.(PRM HOTEL GROUP)

730 S. ATLANTIC AVE. SUITE 102ORMOND BEACH, FLORIDA, 32176

386.677.8882

Owner:

Seal:

RICARDO J. MUNIZ-GUILLET, AIA2030 HABERSHAM TRACE,

CUMMING, GA 30041

DRAWINGS NO.

SHEET NAME

PROJECT NO.

CHECKED BY

DRAWN BY

CURRENT ISSUE

CURRENT ISSUE DATE

PROTOTYPE VERSION: VOLUME 1.0 ISSUE 1.1RELEASE DATE: MAY 06, 2019

MEP ENGINEERGARRY VERMAAS PhD, PE

2183 S BERRYS CHAPEL ROADFRANKLIN, TN 37069

FP-101

B4-171-1901

GWV

MWI

2021.06.03

1ST FLOOR FIRESPECIFICATION

PLAN

100% OWNER REVIEWFP-101 1/8" = 1'-0"

1 1ST FLOOR FIRE SPECIFICATION PLAN

FIRE FLOW AND PUMP DATAWATER FLOW TEST DATADATE OF TEST:

TEST LOCATION:

AVAILABLE FLOW IN GPM:

RESIDUAL PRESSURE:

STATIC PRESSURE:

2020.06.11

BUILDING INFORMATION

TYPE OF BUILDING OCCUPANCY:

HEIGHT OF BUILDING:

TOTAL BUILDING AREA:

FIRE PUMP IS NOT REQUIRED.

ORLANDO, FL

1099.19

76

84

R-1

68'-0"

81,254 SF

ISSUENO.

DELTA ISSUE DATE DESCRIPTION

1 FP0 2021.06.03 100% OWNER REVIEW

FIRE PROTECTION KEYNOTES# TEXT1 PROVIDE ORDINARY HAZARD GROUP 1 OCCUPANCY COVERAGE WITH DENSITY OF 0.15 GPM PER SQ.FT. FOR 1500

SQ.FT. HYDRAULICALLY MOST REMOTE AREA. MECHANICAL ROOM, ELECTRICAL ROOM, KITCHEN, STOREGE ROOMSARE UNDER ORDINARY HAZARD CLASSIFICATION. PROVIDE LIGHT HAZARD OCCUPANCY COVERAGE WITH DENSITYOF 0.10 GPM PER SQ.FT. FOR 1500 SQ.FT. HYDRAULICALLY MOST REMOTE AREA. ALL GUEST ROOMS, COORRIDORS,MEETING ROOMS & PUBLIC TOILET ROOMS ARE UNDER LIGHT HAZAR CLASSIFICATION.

2 FIRE DEPARTMENT TO PROVIDE 750 GMP TO THE FDC AND ENSURE 100 PSI AT THE MOST REMOTE HOSECONNECTION OF MANUAL STANDPIPE SYSTEM.

3 THE FIRE VENDOR/GC TO OBTAIN A LETTER FROM THE FIRE DEPARTMENT THAT A PUMPER TRUCK IS AVAILABLE TOSUPPLEMENT THE PRESSURE OF 100PSI AT THE TOP OF THE MANUAL STANDPIPE AS PER NFPA 14 SECTION 7.7.4. IFA PUMPER TRUCK IS NOT AVAILABLE OR MANUAL STANDPIPE SYSTEM IS NOT ALLOWED BY THE CITY, FIRE PUMPSHALL BE SIZED TO MAINTAIN 100 PSI PRESSURE AND SHALL BE COORDINATED WITH THE EOR PRIOR TOINSTALLATION.

Page 3: FP-001 - planhubapp.s3-us-west-2.amazonaws.com

1

1

FIRE SPRINKLER MAIN TO 2ND FLOOR SPRINKLERS

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22

A

B

C

D

E

F

G

H

J

K

KINGSTANDARD

(KA)

222

KINGSTANDARD

(KA)

223

KINGCONNECTOR

(KB)

224

QUEEN/QUEENCONNECTOR(QB)

225

QUEEN/QUEENSTANDARD(QA)

226

QUEEN/QUEENSTANDARD(QA)

227

QUEEN/QUEENSTANDARD(QA)

203

KINGSTANDARD

(KA)

204

KINGSTANDARD

(KA)

205

KINGSTANDARD

(KA)

206

KINGSTANDARD

(KA)

207

KING ONEBEDROOMACC.(KE)

R.I.S

208

QUEEN/QUEENCONNECTOR(QB)

209

KINGSTANDARD

(KA)

210

KINGSTANDARD

(KA)

211

KINGSTANDARD

(KA)

212

KINGSTANDARD

(KA)

213

KINGSTANDARD

(KA)

214

KINGSTANDARD

(KA)

215

KINGSTANDARD

(KA)

216

KINGSTANDARD

(KA)

217

QUEEN/QUEENSTANDARD(QA)

218

QUEEN/QUEENSTANDARD(QA)

219

QUEEN/QUEENCONNECTOR(QB)

220

QUEEN/QUEENACC.(QC)

R.I.S

221

STAIR#2

281

STORAGE

231

ELEC/PBX

232

TOILET

236

HOUSEKEEPING

233

ELEVATORLOBBY

230

CORRIDOR

200

STORAGE

234

STAIR#1

280

ELEV.2

150

ELEV.1

151

FITNESS

235

4'' STAND PIPE UP LANDING VALVE

BUTTERFLY VALVE

FLOW DETECTOR SWITCH

PRESSURE GUAGE

TEST AND VALVE ASSEMBLY

FIRE SPRINKLER MAIN TO 2ND FLOOR SPRINKLERS

4'' STAND PIPE UP

LANDING VALVE

11810 HIGH TECH AVEORLANDO, FL 32817

BASE42901 CLINT MOORE ROAD, #114BOCA RATON, FLORIDA 33496888.901.8008 www.base-4.com

AA26003324CA 29917

PREMIER RESORTS & MANAGEMENT, INC.(PRM HOTEL GROUP)

730 S. ATLANTIC AVE. SUITE 102ORMOND BEACH, FLORIDA, 32176

386.677.8882

Owner:

Seal:

RICARDO J. MUNIZ-GUILLET, AIA2030 HABERSHAM TRACE,

CUMMING, GA 30041

DRAWINGS NO.

SHEET NAME

PROJECT NO.

CHECKED BY

DRAWN BY

CURRENT ISSUE

CURRENT ISSUE DATE

PROTOTYPE VERSION: VOLUME 1.0 ISSUE 1.1RELEASE DATE: MAY 06, 2019

MEP ENGINEERGARRY VERMAAS PhD, PE

2183 S BERRYS CHAPEL ROADFRANKLIN, TN 37069

FP-102

B4-171-1901

GWV

MWI

2021.06.03

2ND FLOOR FIRESPECIFICATION

PLAN

100% OWNER REVIEW

FP-102 1/8" = 1'-0"

1 2ND FLOOR FIRE SPECIFICATION PLAN

FIRE PROTECTION KEYNOTE# TEXT

1

PROVIDE ORDINARY HAZARD GROUP 1 OCCUPANCY COVERAGE WITH DENSITY OF 0.15 GPM PERSQ.FT. FOR 1500 SQ.FT. HYDRAULICALLY MOST REMOTE AREA. MECHANICAL ROOM, ELECTRICALROOM, KITCHEN, STOREGE ROOMS ARE UNDER ORDINARY HAZARD CLASSIFICATION. PROVIDELIGHT HAZARD OCCUPANCY COVERAGE WITH DENSITY OF 0.10 GPM PER SQ.FT. FOR 1500 SQ.FT.HYDRAULICALLY MOST REMOTE AREA. ALL GUEST ROOMS, COORRIDORS, MEETING ROOMS &PUBLIC TOILET ROOMS ARE UNDER LIGHT HAZAR CLASSIFICATION.

ISSUENO.

DELTA ISSUE DATE DESCRIPTION

1 FP0 2021.06.03 100% OWNER REVIEW

Page 4: FP-001 - planhubapp.s3-us-west-2.amazonaws.com

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22

A

B

C

D

E

F

G

H

J

K

KINGSTANDARD

(KA)

322

KINGSTANDARD

(KA)

323

KINGCONNECTOR

(KB)

324

QUEEN/QUEENCONNECTOR(QB)

325

QUEEN/QUEENSTANDARD(QA)

326

QUEEN/QUEENSTANDARD(QA)

327

QUEEN/QUEENSTANDARD(QA)

303

KINGSTANDARD

(KA)

304

KINGSTANDARD

(KA)

305

KINGSTANDARD

(KA)

306

KINGSTANDARD

(KA)

307

KING ONEBEDROOM(KD)

308

QUEEN/QUEENCONNECTOR(QB)

309

KINGSTANDARD

(KA)

310

KINGSTANDARD

(KA)

311

KINGSTANDARD

(KA)

312

KINGSTANDARD

(KA)

313

KINGSTANDARD

(KA)

314

KINGSTANDARD

(KA)

315

KINGSTANDARD

(KA)

316

KINGSTANDARD

(KA)

317

QUEEN/QUEENSTANDARD(QA)

318

QUEEN/QUEENSTANDARD(QA)

319

QUEEN/QUEENCONNECTOR(QB)

320

KINGACC.(KC)

321

QUEEN/QUEENSTANDARD(QA)

302

QUEEN/QUEENSTANDARD(QA)

301

ELEV.2

150

ELEV.1

151

STAIR#2

381

STORAGE

334

ICE

331

ELEC/PBX

332

ELEVATORLOBBY

330

HOUSEKEEPING

333

CORRIDOR

300

STAIR#1

380

1

1

FIRE SPRINKLER MAIN TO 3RD FLOOR SPRINKLERS

4'' STAND PIPE UP LANDING VALVE

BUTTERFLY VALVE

FLOW DETECTOR SWITCH

PRESSURE GUAGE

TEST AND VALVE ASSEMBLY

FIRE SPRINKLER MAIN TO 3RD FLOOR SPRINKLERS

4'' STAND PIPE UP

LANDING VALVE

11810 HIGH TECH AVEORLANDO, FL 32817

BASE42901 CLINT MOORE ROAD, #114BOCA RATON, FLORIDA 33496888.901.8008 www.base-4.com

AA26003324CA 29917

PREMIER RESORTS & MANAGEMENT, INC.(PRM HOTEL GROUP)

730 S. ATLANTIC AVE. SUITE 102ORMOND BEACH, FLORIDA, 32176

386.677.8882

Owner:

Seal:

RICARDO J. MUNIZ-GUILLET, AIA2030 HABERSHAM TRACE,

CUMMING, GA 30041

DRAWINGS NO.

SHEET NAME

PROJECT NO.

CHECKED BY

DRAWN BY

CURRENT ISSUE

CURRENT ISSUE DATE

PROTOTYPE VERSION: VOLUME 1.0 ISSUE 1.1RELEASE DATE: MAY 06, 2019

MEP ENGINEERGARRY VERMAAS PhD, PE

2183 S BERRYS CHAPEL ROADFRANKLIN, TN 37069

FP-103

B4-171-1901

GWV

MWI

2021.06.03

3RD FLOOR FIRESPECIFICATION

PLAN

100% OWNER REVIEW

FP-103 1/8" = 1'-0"

1 3RD FLOOR FIRE SPECIFICATION PLAN

FIRE PROTECTION KEYNOTE# TEXT

1

PROVIDE ORDINARY HAZARD GROUP 1 OCCUPANCY COVERAGE WITH DENSITY OF 0.15 GPM PERSQ.FT. FOR 1500 SQ.FT. HYDRAULICALLY MOST REMOTE AREA. MECHANICAL ROOM, ELECTRICALROOM, KITCHEN, STOREGE ROOMS ARE UNDER ORDINARY HAZARD CLASSIFICATION. PROVIDELIGHT HAZARD OCCUPANCY COVERAGE WITH DENSITY OF 0.10 GPM PER SQ.FT. FOR 1500 SQ.FT.HYDRAULICALLY MOST REMOTE AREA. ALL GUEST ROOMS, COORRIDORS, MEETING ROOMS &PUBLIC TOILET ROOMS ARE UNDER LIGHT HAZAR CLASSIFICATION.

ISSUENO.

DELTA ISSUE DATE DESCRIPTION

1 FP0 2021.06.03 100% OWNER REVIEW

Page 5: FP-001 - planhubapp.s3-us-west-2.amazonaws.com

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22

A

B

C

D

E

F

G

H

J

K

1

1

KINGSTANDARD

(KA)

422

KINGSTANDARD

(KA)

423

KINGCONNECTOR

(KB)

424

QUEEN/QUEENCONNECTOR(QB)

425

QUEEN/QUEENSTANDARD(QA)

426

QUEEN/QUEENSTANDARD(QA)

427

QUEEN/QUEENSTANDARD(QA)

403

KINGSTANDARD

(KA)

404

KINGSTANDARD

(KA)

405

KINGSTANDARD

(KA)

406

KINGSTANDARD

(KA)

407

KING ONEBEDROOMACC.(KE)

408

QUEEN/QUEENCONNECTOR(QB)

409

KINGSTANDARD

(KA)

410

KINGSTANDARD

(KA)

411

KINGSTANDARD

(KA)

412

KINGSTANDARD

(KA)

413

KINGSTANDARD

(KA)

414

KINGSTANDARD

(KA)

415

KINGSTANDARD

(KA)

416

KINGSTANDARD

(KA)

417

QUEEN/QUEENSTANDARD(QA)

418

QUEEN/QUEENSTANDARD(QA)

419

QUEEN/QUEENCONNECTOR(QB)

420

QUEEN/QUEENACC.(QC)

421

QUEEN/QUEENSTANDARD(QA)

402

QUEEN/QUEENSTANDARD(QA)

401

ELEV.2

150

ELEV.1

151

STAIR#2

481

STORAGE

434

STORAGE

431

ELEC/PBX

432

ELEVATORLOBBY

430

HOUSEKEEPING

433

CORRIDOR

400

STAIR#1

480

FIRE SPRINKLER MAIN TO 4TH FLOOR SPRINKLERS

4'' STAND PIPE UP LANDING VALVE

BUTTERFLY VALVE

FLOW DETECTOR SWITCH

PRESSURE GUAGE

TEST AND VALVE ASSEMBLY

FIRE SPRINKLER MAIN TO 4TH FLOOR SPRINKLERS

4'' STAND PIPE UP

LANDING VALVE

11810 HIGH TECH AVEORLANDO, FL 32817

BASE42901 CLINT MOORE ROAD, #114BOCA RATON, FLORIDA 33496888.901.8008 www.base-4.com

AA26003324CA 29917

PREMIER RESORTS & MANAGEMENT, INC.(PRM HOTEL GROUP)

730 S. ATLANTIC AVE. SUITE 102ORMOND BEACH, FLORIDA, 32176

386.677.8882

Owner:

Seal:

RICARDO J. MUNIZ-GUILLET, AIA2030 HABERSHAM TRACE,

CUMMING, GA 30041

DRAWINGS NO.

SHEET NAME

PROJECT NO.

CHECKED BY

DRAWN BY

CURRENT ISSUE

CURRENT ISSUE DATE

PROTOTYPE VERSION: VOLUME 1.0 ISSUE 1.1RELEASE DATE: MAY 06, 2019

MEP ENGINEERGARRY VERMAAS PhD, PE

2183 S BERRYS CHAPEL ROADFRANKLIN, TN 37069

FP-104

B4-171-1901

GWV

MWI

2021.06.03

4TH FLOOR FIRESPECIFICATION

PLAN

100% OWNER REVIEW

FP-104 1/8" = 1'-0"

1 4TH FLOOR FIRE SPECIFICATION PLAN

FIRE PROTECTION KEYNOTE# TEXT

1

PROVIDE ORDINARY HAZARD GROUP 1 OCCUPANCY COVERAGE WITH DENSITY OF 0.15 GPM PERSQ.FT. FOR 1500 SQ.FT. HYDRAULICALLY MOST REMOTE AREA. MECHANICAL ROOM, ELECTRICALROOM, KITCHEN, STOREGE ROOMS ARE UNDER ORDINARY HAZARD CLASSIFICATION. PROVIDELIGHT HAZARD OCCUPANCY COVERAGE WITH DENSITY OF 0.10 GPM PER SQ.FT. FOR 1500 SQ.FT.HYDRAULICALLY MOST REMOTE AREA. ALL GUEST ROOMS, COORRIDORS, MEETING ROOMS &PUBLIC TOILET ROOMS ARE UNDER LIGHT HAZAR CLASSIFICATION.

ISSUENO.

DELTA ISSUE DATE DESCRIPTION

1 FP0 2021.06.03 100% OWNER REVIEW

Page 6: FP-001 - planhubapp.s3-us-west-2.amazonaws.com

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22

A

B

C

D

E

F

G

H

J

K

1

1

KINGSTANDARD

(KA)

522

KINGSTANDARD

(KA)

523

KINGCONNECTOR

(KB)

524

QUEEN/QUEENCONNECTOR(QB)

525

QUEEN/QUEENSTANDARD(QA)

526

QUEEN/QUEENSTANDARD(QA)

527

QUEEN/QUEENSTANDARD(QA)

503

KINGSTANDARD

(KA)

504

KINGSTANDARD

(KA)

505

KINGSTANDARD

(KA)

506

KINGSTANDARD

(KA)

507

KING ONEBEDROOM(KD)

508

QUEEN/QUEENCONNECTOR(QB)

509

KINGSTANDARD

(KA)

510

KINGSTANDARD

(KA)

511

KINGSTANDARD

(KA)

512

KINGSTANDARD

(KA)

513

KINGSTANDARD

(KA)

514

KINGSTANDARD

(KA)

515

KINGSTANDARD

(KA)

516

KINGSTANDARD

(KA)

517

QUEEN/QUEENSTANDARD(QA)

518

QUEEN/QUEENSTANDARD(QA)

519

QUEEN/QUEENCONNECTOR(QB)

520

KINGACC.(KC)

521

QUEEN/QUEENSTANDARD(QA)

502

QUEEN/QUEENSTANDARD(QA)

501

ELEV.2

150

ELEV.1

151

STAIR#2

581

STORAGE

534

ICE

531

ELEC/PBX

532

ELEVATORLOBBY

530

HOUSEKEEPING

533

CORRIDOR

500

STAIR#1

580

FIRE SPRINKLER MAIN TO 5TH FLOOR SPRINKLERS

4'' STAND PIPE UP LANDING VALVE

BUTTERFLY VALVE

FLOW DETECTOR SWITCH

PRESSURE GUAGE

TEST AND VALVE ASSEMBLY

FIRE SPRINKLER MAIN TO 5TH FLOOR SPRINKLERS

4'' STAND PIPE UP

LANDING VALVE

11810 HIGH TECH AVEORLANDO, FL 32817

BASE42901 CLINT MOORE ROAD, #114BOCA RATON, FLORIDA 33496888.901.8008 www.base-4.com

AA26003324CA 29917

PREMIER RESORTS & MANAGEMENT, INC.(PRM HOTEL GROUP)

730 S. ATLANTIC AVE. SUITE 102ORMOND BEACH, FLORIDA, 32176

386.677.8882

Owner:

Seal:

RICARDO J. MUNIZ-GUILLET, AIA2030 HABERSHAM TRACE,

CUMMING, GA 30041

DRAWINGS NO.

SHEET NAME

PROJECT NO.

CHECKED BY

DRAWN BY

CURRENT ISSUE

CURRENT ISSUE DATE

PROTOTYPE VERSION: VOLUME 1.0 ISSUE 1.1RELEASE DATE: MAY 06, 2019

MEP ENGINEERGARRY VERMAAS PhD, PE

2183 S BERRYS CHAPEL ROADFRANKLIN, TN 37069

FP-105

B4-171-1901

GWV

MWI

2021.06.03

5TH FLOOR FIRESPECIFICATION

PLAN

100% OWNER REVIEW

FP-105 1/8" = 1'-0"

1 5TH FLOOR FIRE SPECIFICATION PLAN

FIRE PROTECTION KEYNOTE# TEXT

1

PROVIDE ORDINARY HAZARD GROUP 1 OCCUPANCY COVERAGE WITH DENSITY OF 0.15 GPM PERSQ.FT. FOR 1500 SQ.FT. HYDRAULICALLY MOST REMOTE AREA. MECHANICAL ROOM, ELECTRICALROOM, KITCHEN, STOREGE ROOMS ARE UNDER ORDINARY HAZARD CLASSIFICATION. PROVIDELIGHT HAZARD OCCUPANCY COVERAGE WITH DENSITY OF 0.10 GPM PER SQ.FT. FOR 1500 SQ.FT.HYDRAULICALLY MOST REMOTE AREA. ALL GUEST ROOMS, COORRIDORS, MEETING ROOMS &PUBLIC TOILET ROOMS ARE UNDER LIGHT HAZAR CLASSIFICATION.

ISSUENO.

DELTA ISSUE DATE DESCRIPTION

1 FP0 2021.06.03 100% OWNER REVIEW

Page 7: FP-001 - planhubapp.s3-us-west-2.amazonaws.com

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22

A

B

C

D

E

F

G

H

J

K

1

1

KINGSTANDARD

(KA)

622

KINGSTANDARD

(KA)

623

KINGCONNECTOR

(KB)

624

QUEEN/QUEENCONNECTOR(QB)

625

QUEEN/QUEENSTANDARD(QA)

626

QUEEN/QUEENSTANDARD(QA)

627

QUEEN/QUEENSTANDARD(QA)

603

KINGSTANDARD

(KA)

604

KINGSTANDARD

(KA)

605

KINGSTANDARD

(KA)

606

KINGSTANDARD

(KA)

607

KING ONEBEDROOM(KD)

608

QUEEN/QUEENCONNECTOR(QB)

609

KINGSTANDARD

(KA)

610

KINGSTANDARD

(KA)

611

KINGSTANDARD

(KA)

612

KINGSTANDARD

(KA)

613

KINGSTANDARD

(KA)

614

KINGSTANDARD

(KA)

615

KINGSTANDARD

(KA)

616

KINGSTANDARD

(KA)

617

QUEEN/QUEENSTANDARD(QA)

618

QUEEN/QUEENSTANDARD(QA)

619

QUEEN/QUEENCONNECTOR(QB)

620

QUEEN/QUEENACC.(QC)

621

QUEEN/QUEENSTANDARD(QA)

602

QUEEN/QUEENSTANDARD(QA)

601

ELEV.2

150

ELEV.1

151

STAIR#2

681

STORAGE

634

GUESTLAUNDRY

631

ELEC/PBX

632

ELEVATORLOBBY

630

HOUSEKEEPING

633

CORRIDOR

600

STAIR#1

680

FIRE SPRINKLER MAIN TO 6TH FLOOR SPRINKLERS

4'' STAND PIPE UP LANDING VALVE

BUTTERFLY VALVE

FLOW DETECTOR SWITCH

PRESSURE GUAGE

TEST AND VALVE ASSEMBLY

FIRE SPRINKLER MAIN TO 6TH FLOOR SPRINKLERS

4'' STAND PIPE UP

LANDING VALVE

11810 HIGH TECH AVEORLANDO, FL 32817

BASE42901 CLINT MOORE ROAD, #114BOCA RATON, FLORIDA 33496888.901.8008 www.base-4.com

AA26003324CA 29917

PREMIER RESORTS & MANAGEMENT, INC.(PRM HOTEL GROUP)

730 S. ATLANTIC AVE. SUITE 102ORMOND BEACH, FLORIDA, 32176

386.677.8882

Owner:

Seal:

RICARDO J. MUNIZ-GUILLET, AIA2030 HABERSHAM TRACE,

CUMMING, GA 30041

DRAWINGS NO.

SHEET NAME

PROJECT NO.

CHECKED BY

DRAWN BY

CURRENT ISSUE

CURRENT ISSUE DATE

PROTOTYPE VERSION: VOLUME 1.0 ISSUE 1.1RELEASE DATE: MAY 06, 2019

MEP ENGINEERGARRY VERMAAS PhD, PE

2183 S BERRYS CHAPEL ROADFRANKLIN, TN 37069

FP-106

B4-171-1901

GWV

MWI

2021.06.03

6TH FLOOR FIRESPECIFICATION

PLAN

100% OWNER REVIEW

FP-106 1/8" = 1'-0"

1 6TH FLOOR FIRE SPECIFICATION PLAN

FIRE PROTECTION KEYNOTE# TEXT

1

PROVIDE ORDINARY HAZARD GROUP 1 OCCUPANCY COVERAGE WITH DENSITY OF 0.15 GPM PERSQ.FT. FOR 1500 SQ.FT. HYDRAULICALLY MOST REMOTE AREA. MECHANICAL ROOM, ELECTRICALROOM, KITCHEN, STOREGE ROOMS ARE UNDER ORDINARY HAZARD CLASSIFICATION. PROVIDELIGHT HAZARD OCCUPANCY COVERAGE WITH DENSITY OF 0.10 GPM PER SQ.FT. FOR 1500 SQ.FT.HYDRAULICALLY MOST REMOTE AREA. ALL GUEST ROOMS, COORRIDORS, MEETING ROOMS &PUBLIC TOILET ROOMS ARE UNDER LIGHT HAZAR CLASSIFICATION.

ISSUENO.

DELTA ISSUE DATE DESCRIPTION

1 FP0 2021.06.03 100% OWNER REVIEW