FP-001 - planhubapp.s3-us-west-2.amazonaws.com
Transcript of FP-001 - planhubapp.s3-us-west-2.amazonaws.com
![Page 1: FP-001 - planhubapp.s3-us-west-2.amazonaws.com](https://reader030.fdocuments.us/reader030/viewer/2022013015/61d039e7b0371e37364cbdc5/html5/thumbnails/1.jpg)
PROJECT GENERAL NOTES DRAWING INDEX
SPRINKLER HEAD
FLOW SWITCH
FIRE DEPARTMENT CONNECTION
FIRE ALARM ASSEMBLY
SPRINKLER VALVE ASSEMBLY
PUMP
LEGEND
SYMBOL DESCRIPTION
ABBREVIATIONS
1. THE SPRINKLER CONTRACTOR SHALL PROVIDE COMPLETE HYDRAULIC CALCULATIONS, PIPE SIZING, PIPE MATERIAL WITH LAY-OUT DWG'S & CONSTRUCTION LAY-OUT DWG'S.
2. ALL SPRINKLER HEADS SERVING, ELECTRIC, TELEPHONE, SWITCHGEAR & ELEVATOR MACHINE ROOMS SHALL BE PROVIDED BY SHUT-OFF VALVES W/ TAMPER SWITCHES.
3. 4. THE FIRE PROTECTION SYSTEM DESIGN, INSTALLATION AND MATERIALS SHALL BE IN AS
COMPLIANCE WITH NFPA AND THE MOST RECENT STATE BUILDING CODE AND FIRE CODES, WELL AS ANY APPLICABLE STATE STATUTES.
5. SPRINKLER SYSTEM TO BE INSTALLED BY A STATE CERTIFIED FIRE PROTECTIONCONTRACTOR.6. CONTRACTOR SHALL COORDINATE WITH STRUCTURE, CEILING GRID AND ELEVATION, AND
OTHER MECHANICAL AND ELECTRICAL SERVICES BEFORE FABRICATING AND INSTALLING SPRINKLER HEADS & PIPING. MAKE OFFSETS IN PIPING AS REQUIRED PER FIELD CONDITIONS. MAINTAIN 6" CLEARANCE BETWEEN PIPING AND 1 AND 2 HOUR RATED WALLS INCLUDING CORRIDOR WALLS.
7. ALL VALVES SHALL BE BY DOMESTIC MANUFACTURER, U.L. LISTED FOR FIRE PROTECTION SERVICE AND RATED FOR 175 PSI WORKING PRESSURE. PROVIDE U.L. LISTED/ FM APPROVED TAMPER SWITCHES AT CONTROL VALVE LOCATIONS. PROVIDE U.L. LISTED/ FM APPROVED FLOW SWITCHES, WHERE SHOWN, AT CONTROL VALVE LOCATIONS.
8. SPRINKLER HEADS SHALL BE LISTED AS INDICATED IN SCHEDULE AND RATED FOR 175 PSI WORKING PRESSURE. PROVIDE HEAD GUARDS ON UPRIGHT AND PENDANT SPRINKLER HEADS LOCATED IN ELEVATOR SHAFTS, MECHANICAL SHAFTS, ELECTRICAL, TELEPHONE, MECHANICAL AND MACHINE ROOMS. CONTRACTOR SHALL PROVIDE THE OWNER WITH A COPY OF NFPA 25.
9. CONTRACTOR SHALL PROVIDE FLUSHING CONNECTIONS WHERE SHOWN ON PLANS. PROVIDE A DRAIN CONNECTION FOR ALL TRAPPED SECTION OF PIPING.
10. INSPECTORS TEST, DRAIN AND SHUT-OFF VALVES SHALL BE LOCATED AT MAXIMUM OF7'-0" AFF.11. ALL SPRINKLER HEADS SHALL BE CENTERED AND PRESENTED IN A NEAT AND BALANCED
CEILING PATTERN. FP CONTRACTOR TO COORDINATE WITH ARCHITECT AND INTERIOR DESIGNER.
12. PIPING TO BE BLACK STEEL IN AIR CONDITIONED SPACES, PIPING IN NON-AIR CONDITIONED SPACE SHALL BE BLACK STEEL SCHEDULE 40 (PAINTED) WITH AN ALTERNATE FOR GALVANIZED SCHEDULE 40. GROOVED FITTINGS ARE NOT ALLOWED WHERE PRESSURE EXCEEDS 175 PSI.
13. SPRINKLER HEADS TO BE MODEL GBR SERIES SPRINKLER WHITE PLATED SEMI RECESSED TYPE FOR SIDE WALL, AND FOR CEILING LOCATIONS, BRASS UPRIGHT FOR EXPOSED LOCATIONS, RECESSED TYPE FOR FIRST FLOOR LOBBY AREAS. TEFLON FINISHED HEADS TO BE USED IN NON-AIR CONDITIONED AREAS.
14. SPRINKLER HEADS SHOULD BE PROVIDED ON FIRE RATED WALLS WHERE THERE ARE INTERIOR ALUMINUM WINDOWS. SPRINKLER HEADS SHOULD ALSO BE PROVIDED INSIDE OF LAUNDRY CHUTES.
15. SPRINKLER SUBCONTRACTOR TO PROVIDE ALL REQUIRED STANDPIPES AND FIRE HOSE VALVES, FLOW AND TAMPER SWITCHES, PRESSURE REDUCING VALVES AT ALL FLOORS, SIAMESE CONNECTIONS, INSPECTOR TEST STATIONS, SPARE SPRINKLER HEAD CABINET. ALL NECESSARY DRAINS AND SIGNAGE.
16. FIRE PUMP AND CONTROLLER SHALL BE SIZED ACCORDING TO HYDRAULIC CALCULATIONS AND FLOW TEST. IF FIRE PUMP IS REQUIRED, FP CONTRACTOR SHALL SUBMIT FIRE PUMP SHOP DRAWINGS TO EOR FOR REVIEW. ALL ASSOCIATED ACCESSORIES INCLUDING JOCKEY PUMP AND CONTROLLER, PUMP BYPASS, AND NECESSARY VALVING SHALL MEET LOCAL CODES AND NFPA STANDARDS. PROVIDE REMOTE ANNUNCIATOR AT FIRE COMMAND ROOM AND REMOTE ALARM AT SECURITY DESK.
17. ALL EXPOSED FIRE ALARM PIECES (STROBES, SPEAKERS, PULL STATIONS) TO BE WHITE IN COLOR WHERE POSSIBLE. FP CONTRACTOR SHALL COORDINATE WITH ARCHITECT AND INTERIOR DESIGNER.
18. FIRE CONTRACTOR MUST PROVIDE LANDLORD AND TENANT WITH A COPY OF NFPA 25.
19. FP SUBCONTRACTOR SHALL CONNECT MAIN FIRE LINE TO UTILITY SOURCE AND PROVIDE CONTROL VALVE/PIV. SUCTION SIDE PIPING SHALL BE DUCTILE IRON
20. ALL FIRE SPRINKLER SHALL BE MONITORED 24 HOURS A DAY BY AN APPROVED CENTRAL STATION IN ACCORDANCE WITH NFPA 13 AND LOCAL CODES.
21. ALL NEW FIRE SPRINKLER SHALL BE HYDRO STATICALLY TESTED AT 175PSI (OR 50 PSI ABOVE SYSTEM STATIC PRESSURE, WHICHEVER GREATER) FOR NOT LESS THAN 2 HOURS.
22. SYSTEM DESIGN PLACARDS,SPARE STOCK OF SPRINKLERS, AND HEAD CABINET WILL BE SUPPLIED AT THE SPRINKLER SYSTEM RISER AS REQUIRED BY NFPA 13. THE SPARE STOCK OF SPRINKLERS SHALL NOT BE SUBJECTED TO A TEMPERATURE EXCEEDING 100 F.
23. THE STRUCTURAL ENGINEER SHALL INCLUDE THE LOAD FOR THE SPRINKLER SYSTEM AND OTHER FIRE PROTECTION COMPONENTS INTO THE DESIGN OF THE STRUCTURE. REFER TO STRUCTURAL DRAWINGS.
24. ALL FIRE PROTECTION SYSTEMS AND MATERIAL TO COMPLY WITH HYATT PLACE BRAND STANDARDS FOR FIRE PROTECTION AND LIFE SAFETY.
25. ALL MATERIALS AND EQUIPMENT SHALL BE UL LISTED FOR USE IN FIRE PROTECTION SYSTEM AND BE IN CONFORMANCE WITH LOCAL AHJ AND NFPA 13 REQUIREMENTS.
26. SEE ARCH DRAWINGS FOR EXTINGUISHER CABINET LOCATION.
27. RECESSED SPRINKLER HEADS SHALL BE USED IN ALL PUBLIC AREAS INCLUDING REST ROOMS.
28. THE FP DRAWINGS INCLUDED IN THIS DESIGN DRAWING SET ARE SPECIFICATION ONLY.
29. THE FIRE PROTECTION SYSTEM NEEDS TO BE DESIGNED BY PROFESSIONAL ENGINEERS IN THE STATE THAT THE PROJECT IS LOCATED IN.
30. THE DETAILED DRAWING ,CUT SHEETS, PUMP SPECIFICATION TO BE SEND TO BASE4 FOR REVIEW WITH SIGN AND SEAL OF A FIRE PROTECTION ENGINEER.
31. CONTRACTOR TO FOLLOW THE NFPA STANDARD FOR FIRE PROTECTION REQUIREMENTS.32. ALL HYDRAULIC CALCULATION TO BE DONE WITH REFERENCE TO CURRENT DATED FLOW TEST
REPORT.
33. CONTRACTOR SHALL ENSURE SPRINKLER SYSTEM BE ZONED AT EVERY FLOOR WITH INSPECTOR'S TEST STATION WITH SIGHT GLASS AT EVERY HORIZONTAL SPRINKLER ZONE WITH A CONTROL VALVE AND TAMPER SWITCH, WATER FLOW SWITCH, PRESSURE GAUGE, AND DRAIN AND TEST ASSEMBLY R EQUIRED BY NFPA 13
34. FIRE CONTRACTOR SHALL ENSURE TO PROVIDE CORROSION RESISTANT SPRINKLER HEADS IN POOL ROOMS, POOL EQUIPMENT ROOMS, AND POOL \STORAGE ROOMS.
35. CONTRACTOR SHALL INSTALL A REMOTE INSPECTORS TEST FOR THE WET SPRINKLER SYSTEM PER WITH NFPA 13.
36. FIRE CONTRACTOR SHALL ENSURE TO PROVIDE FIRE SPRINKLER IN LINEN CHUTE AS PER NFPA 13 , NFPA 82.
37. OWNER SHALL SUBMIT THE OWNERS INFORMATION CERTIFICATE TO CITY.
38. ALL QUALITY AND PERFORMANCE SPECIFICATIONS FOR THE FIRE PROTECTION COMPONENTS ARE PROVIDED IN THE NOTES ON THIS SHEET.
39. CONTRACTOR SUBMITTAL WHICH DEVIATE FROM THE ABOVE MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING APPROVAL AND DOCUMENTATION. CONTRACTOR TO MAKE SURE 61G32 REQUIREMENTS AS MENTIONED IN SHEET FP-001 ARE MET.
40. IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES
41. CONTRACTOR TO INSTALL SPRINKLER HEADS CENTERED AND ALIGNED IN COORDINATION WITH THE CEILING LIGHTS AND DIFFUSERS.
42. CONTRACTOR SHALL INSTALL A QUICK RESPONSE SPRINKLER HEAD FOR EARLY SUPPRESSION OF FIRE IN LIGHT HAZARD OCCUPANCY.
43. CONTRACTOR TO INSTALL SEMI RECESSED WHITE HEADS IN PUBLIC AND GUESTROOM.
44. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLAN AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH THE SECTION AND CHAPTER 33, FLORIDA STATUES. FBC 6TH ED. 2017 SECTION110.8.4.4.
FIRE PROTECTION
FIRE ALARM ASSEMBLY
FIRE DEPARTMENT CONNECTION
FIRE PROTECTION CONTRACTOR
FAA
FDC
F.P.C.
SPRINKLER VALVE ASSEMBLY
UNDERWRITERS LABORATORY INC.
SVA
U.L.
BASE4 WILL NOT BE RESPONSIBLE FOR CHANGES OF ANY KIND (CHANGE ORDERS, BACK CHARGES OR DELAY CLAIMS) FROM ANY SET PROVIDED BY BASE4 PRIOR TO THE RECEIPT OF A BUILDING PERMIT FROM THE AHJ. THIS INCLUDES BUT IS NOT LIMITED TO PROGRESS SETS, EARLY STAGE RELEASES, FRANCHISE SUBMITTALS OR BID SETS. ONLY AHJ APPROVED PERMIT SETS SHALL BE CONSIDERED ACCEPTABLE FOR CONSTRUCTION OR FINAL PRICING. BIDDING, FABRICATING OR BUILDING FROM NON PERMIT APPROVED DRAWINGS IS SOLELY AT THE CONTRACTOR'S RISK.
1. TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS,SAID DOCUMENTS SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN APPLICABLE.
a. THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER SUPPLY AS DEFINED BY SECTION 633.021(17), F.S.
BASE4 RESPONSE: SEE SITE UTILITY PLAN EXH102T.CIVIL HAS PROVIDED NEW 6' DR14 PVC MAIN FIRE SERVICE LINE.
b. APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND CONCLUSIONS. BASE4 RESPONSE: PLEASE REFER TO FP001 GENERAL NOTE #30.
c. CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR AREA. BASE4 RESPONSE: AS PER NFPA 13 THE HAZARD OCCUPANCY FOR THE BUILDING IS LIGHT AND ORDINARY HAZARD. PLEASE REFER TO SHEET FP101-106 BELOW GENERAL NOTES.
d. DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE, DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR EACH SEPARATE HAZARD OCCUPANCY. BASE4 RESPONSE: BASE4 HAS PROVIDED A WET PIPE SYSTEM FOR THIS PROJECT. MINIMUM
DENSITY AND AREA OF COVERAGE IS O.15 PER SQFT AS PER THE NFPA13 SECTION 11.2.3.1 AND SPRINKLER SPACING WOULD BE 15" SPRINKLER TO SPRINKLER SPACING AS PER NFPA 13 SECTION 8.6.2.2.1.
e. CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY DEMANDING DESIGN AREA. BASE4 RESPONSE: THE FIRE MAIN LINE IS 6" AND MAIN WATER SUPPLY LINE IS OF CIRCULATING TYPE.
f. WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION, STATIC GAUGE PRESSURE AT NO FLOW RATE WITH RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF SERVICE. BASE4 RESPONSE: A FIRE FLOW TEST WAS CONDUCTED ON 2019.01/18 at 08.3 1AM BY TWD AS PER THE FLOW TEST CONDUCTED THE FLOW RATE AT THE HYDRANT IS 1187GPM WITH RESIDUAL PRESSURE OF 60PSI AND STATIC PRESSURE OF 62PSI .OWNER TO SUPPLY COPY OF THIS TEST.
g. VALVING AND ALARM REQUIREMENTS TO MINIMIZE POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF WATER. BASE4 RESPONSE: BASE4 HAS PROVIDED VALVES AND WATER SUPPLY ENTRY DETAIL.PLEASE
REFER TO SHEET FP-001 DETAIL-3.
h. MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY WITH CONDITIONS OF THE FIRE PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE MEASURES. BASE4 RESPONSE: MICROBIAL INDUCED CORROSION IS TO BE TESTED IN THE FIRE PROTECTION PIPING GC TO TAKE NECESSARY CORRECTIVE MEASURES". BASE 4 HAS PROPOSED THE WATER SOFTENER FOR THE BUILDING. i. BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP. BASE4 RESPONSE: REFER TO SHEET FP-001DETAIL-1 FOR BFP. WE HAVE PROVIDED A NOTE ON SHEET FP-001 BELOW DETAIL-1," BACKFLOW PREVENTION AND METERING SHALL MEET LOCAL WATER PURVEYOR REQUIREMENTS INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP.
j. QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD AND INTERIOR FIRE PROTECTION COMPONENTS. BASE4 RESPONSE: BASE4 HAS ADDED NOTE "ALL QUALITY AND PERFORMANCE S PECIFICATIONS FOR THE FIRE PROTECTION COMPONENTS ARE PROVIDE IN NOTES ON THIS SHEET." PLEASE REFER TO SHEET FP-001 NOTE # 31.
k. A DETERMINATION OF WHETHER A FIRE PUMP IS REQUIRED AND IF SO, THE SPECIFIC VOLUMETRIC FLOW AND PRESSURE OF THE PUMP. BASE4 RESPONSE: AS PER THE RESIDUAL PRESSURE OF 60PSI FIRE PUMP IS REQUIRED.THE SPECIFIC VOLUMETRIC FLOW AND PRESSURE OF THE PUMP WILL PROVIDE BY THE FIRE VENDOR.
l. A VERIFICATION OF WHETHER A FIREWATER STORAGE TANK IS REQUIRED ON SITE AND IF SO, A DETERMINATION OF THE SIZE AND CAPACITY REQUIRED. BASE4 RESPONSE: A FIRE WATER STORAGE TANK IS NOT REQUIRED.
m. OWNER'S CERTIFICATE. IN STORAGE OCCUPANCIES, THE OWNER'S INFORMATION CERTIFICATE IS REQUIRED FROM THE PROPERTY OWNER AS IT CLEARLY DEFINES THE STORAGE CONFIGURATION OF THE SPACE FOR THE CURRENT AND FUTURE USE OF THE PROPERTY, AS REQUIRED BY THE CODES AND STANDARDS SET FORTH IN SUBSECTION 61G15-32.002(7), F.A.C. BASE4 RESPONSE: WE HAVE PROVIDED NOTE, "OWNER SHALL SUBMIT THE OWNER'S INFORMATION CERTIFICATE TO CITY." SEE GENERAL NOTE #36 IN FP001 SHEET.
2. CONTRACTOR SUBMITTAL WHICH DEVIATE FROM THE ABOVE MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED. MATERIAL DEVIATIONS AND REQUIRE
SUPPLEMENTAL ENGINEERING APPROVAL AND DOCUMENTATION. BASE4 RESPONSE: BASE4 HAS ADDED A NOTE. PLEASE REFER TO GENERAL NOTE#36, SHEET FP-0013. IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE INFORMATION AND DIRECTION
THAN IS ESTABLISHED ABOVE, HE OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES. BASE4 RESPONSE: BASE4 HAS ADDED A NOTE ADDRESSING THIS. PLEASE REFER TO GENERAL NOTE# 37, SHEET FP-001
61G32 REQUIREMENTS
GRV'D CHECK VALVE
GRV'D BUTTERFLY VA.W/ TAMPER SWITCH
GLOBE UMC CONTROL VA. ASSEMBLY
(1) DRAIN AND TEST(2) FLOW SWITCH(3) PRESSURE GAUGE(4) SINGS ON BODY
ST
AN
DP
IPE
2' X 2" X 1 -1/4" Tee
2"
DR
AIN
4"
DR
AIN
4"
2"
1 -1/4"
TO
HA
ND
LE
A
FF
5'-0"
2-1/2" BRASS HOSE VALVE w/2'-1/2" CAP & CHAIN
MA
INT
AIN
7'-2"
CLE
AR
HE
IGH
T
TO
SYSTEM
0'-9"
SCH 7
2-9
8'-0"
FF
FLOOR
PIPE TAP FOR BALL DRIP VALVE
HORIZONTAL MOUNTED BALL DRIP VALVE
2" DRAIN PIPE TO
OUTSIDE
FIRE DEPARTMENT CONNECTION
REFER ARCHITECTURAL DRAWINGS FOR EXTERIOR WALL TYPE
WALL PLATE (TYPICAL)
EXISTING GRADE18
" T
O 4
8"
BULK FEED MAIN TOSPRINKLER SYSTEMSIZED BY HYDRAULICCALCULATIONS
SPARE SPRINKLER HEADCABINET MTD. ON WALL.
BACKFLOW PREVENTION DEVICEASSEMBLY W/TAMPER SWITCHES ON SHUT-OFF VALVES.
CONCRETE THRUSTBLOCK (TYP.)
BRIDLE ROD (TYP.)
FINISHED FLOOR (REF.)
FIRE LINE SUPPLY.SEE SITE UTILITY FOR CONTINUATION
TO ON-SITE POSTTYPE F.D. SIAMESE CONN. SEE SITE UTILITY PLANS FOR CONTINUATION
2" MAIN DRAIN
F.D. SIAMESECONNECTION-VERIFYLOCATION WITH CIVIL
CHECK VALVEWITH BALL DRIP
RETARD CHAMBERWITH FLOW SWITCH
WATER MOTOR GONG
A/S
F
F
ALARM CHECK VALVEASSEMBLY w/TRIM
2" SCH. 40 STEEL PIPE SUPPORT
11810 HIGH TECH AVEORLANDO, FL 32817
BASE42901 CLINT MOORE ROAD, #114BOCA RATON, FLORIDA 33496888.901.8008 www.base-4.com
AA26003324CA 29917
PREMIER RESORTS & MANAGEMENT, INC.(PRM HOTEL GROUP)
730 S. ATLANTIC AVE. SUITE 102ORMOND BEACH, FLORIDA, 32176
386.677.8882
Owner:
Seal:
RICARDO J. MUNIZ-GUILLET, AIA2030 HABERSHAM TRACE,
CUMMING, GA 30041
DRAWINGS NO.
SHEET NAME
PROJECT NO.
CHECKED BY
DRAWN BY
CURRENT ISSUE
CURRENT ISSUE DATE
PROTOTYPE VERSION: VOLUME 1.0 ISSUE 1.1RELEASE DATE: MAY 06, 2019
MEP ENGINEERGARRY VERMAAS PhD, PE
2183 S BERRYS CHAPEL ROADFRANKLIN, TN 37069
FP-001
B4-171-1901
GWV
MWI
2021.06.03
GENERAL NOTES,LEGEND &
ABBREVIATIONS
100% OWNER REVIEW
SHEETNUMBER
SHEET NAMECURRENT
ISSUE DATECURRENT ISSUE
DESCRIPTIONFP-001 GENERAL NOTES, LEGEND & ABBREVIATIONS 2021.06.03 100% OWNER REVIEW
FP-101 1ST FLOOR FIRE SPECIFICATION PLAN 2021.06.03 100% OWNER REVIEW
FP-102 2ND FLOOR FIRE SPECIFICATION PLAN 2021.06.03 100% OWNER REVIEW
FP-103 3RD FLOOR FIRE SPECIFICATION PLAN 2021.06.03 100% OWNER REVIEW
FP-104 4TH FLOOR FIRE SPECIFICATION PLAN 2021.06.03 100% OWNER REVIEW
FP-105 5TH FLOOR FIRE SPECIFICATION PLAN 2021.06.03 100% OWNER REVIEW
FP-106 6TH FLOOR FIRE SPECIFICATION PLAN 2021.06.03 100% OWNER REVIEW
NTSFP-001
3 TYPICAL ZONE CONTROL ASSEMBLY
NTSFP-001
1 FIRE DEPARTMENT CONNECTION DETAIL
NTSFP-001
2 AUTOMATIC SPRINKLER SYSTEM RISER DETAIL
ISSUENO.
DELTA ISSUE DATE DESCRIPTION
1 FP0 2021.06.03 100% OWNER REVIEW
![Page 2: FP-001 - planhubapp.s3-us-west-2.amazonaws.com](https://reader030.fdocuments.us/reader030/viewer/2022013015/61d039e7b0371e37364cbdc5/html5/thumbnails/2.jpg)
2" INSPECTOR'S TEST DRAIN RELEASE ABOVE GRADE
1
4'' STAND PIPE UP LANDING VALVE
BUTTERFLY VALVE
FLOW DETECTOR SWITCH
PRESSURE GUAGE
TEST AND VALVE ASSEMBLY
PIPE TO THE SPRINKLER
4" SPRINKLER PIPE IN CEILING
TO FIRE DEPARTMENT CONNECTION. (VERIFY LOCATION AT SITE. SEE CIVIL PLAN FOR CONTINUATION)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
A
B
C
D
E
F
G
H
J
K
6" FIRE LINE CONNECT FROM THE MAIN .(VERIFY LOCATION AT SITE. SEE CIVIL PLAN FOR CONTINUATION)
SPRINKLER VALVE ASSEMBLY
PIPE UP
ELEV.2
150
ELEV.1
151
VESTIBULE
130
COMPUTER
169
WORKROOM
171
SALES
170
MEETINGROOM
168
BREAKOUT
167
MEETINGROOM
166
MEETINGROOM
165
MEETINGROOM
STORAGE
164
STAIR #1
180
ELECTRICAL
163
MECHANICAL
162
JANITOR'SCLOSET
161
MAINTENANCE
160
POOLEQUIPMENT
159
TOILET
158
EMPLOYEEBREAKROOM
157
LINENSTORAGE
155
LINENCHUTE
156
UNISEX
152
CORRIDOR
151DRYERS
154
LAUNDRY
153
STORAGE
144
DISHWASHING
145
FOODPREP
143
MEN'S
146
WOMEN'S
147
DRINKINGFOUNTAIN
148
CORRIDOR
100.2
GUESTKITCHEN
142
GUESTDINING
141
STAIR #2
181
CHECK-IN
136
LOUNGE 2
135
HOST/BAR/CAFE
133
GRAB-N-GO
132
LOUNGE 1
134
BUSINESSCENTER
139
GMOFFICE
137
LUGGAGE
138
VESTIBULE
150
ELEV.LOBBY
149
CORRIDOR
100.1
LOBBY
131
OUTDOORPOOL
172
OUTDOORPATIO
140
OUTDOORPATIO
328
4" SPRINKLER PIPE IN CEILING 4" SPRINKLER PIPE IN CEILING
4'' STAND PIPE UP
LANDING VALVEATS
CLOSET
163.1
2
31
GENERAL NOTES
1. COMBUSTIBLE CONCEALED SPACES SHALL REQUIRE SPRINKLER HEADS FOR FIRE PROTECTION.
2. PORTE-COCHERE PROJECTION SHALL BE PROTECTED WITH FIRE SPRINKLER HEADS IF IT IS NOT CONSTRUCTED WITH MATERIALS THAT ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, OR FIRE RETARDANT–TREATED WOOD”.
3. SPRINKLERS SHALL NOT BE REQUIRED IN BATHROOMS THAT ARE LOCATED WITHIN DWELLING UNITS, THAT DO NOT EXCEED 55 FT2 (5.1 M2) IN AREA, AND THAT HAVE WALLS AND CEILINGS OF NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE MATERIALS WITH A 15-MINUTE THERMAL BARRIER RATING, INCLUDING THE WALLS AND CEILINGSBEHIND ANY SHOWER ENCLOSURE OR TUB.
4. FIRE VENDOR TO PROVIDE A FIRE SPRINKLER DRAWING SUBMITTALS TO FIRE DEPARTMENT FOR APPROVAL BEFORE PRIOR TO ANY WORK ON THE FIRE SPRINKLER SYSTEM BEGINNING.
5. FIRE CONTRACTOR TO PROVIDE A FLOW BELL ON THE EXTERIOR NEAREST TO A RISER.
6. FIRE SUB CONTRACTOR SHALL ENSURE THAT THE MAIN FIRE LINE COMING TO MECHANICAL ROOM/PUMP ROOM MUST BE BURIED NOT LESS THAN 1 FT (0.3 M) BELOW THE FROST LINE OR FROM THE BOTTOM OF FOOTING
7. THE REQUIREMENT OF FIRE PUMP SHALL BE DETERMINED ONCE THE FLOW TEST REPORT IS RECEIVED, OWNER TO PROVIDE THE FLOW TEST REPORT FOR CALCULATION OF FIRE PUMP TO BASE-4.
11810 HIGH TECH AVEORLANDO, FL 32817
BASE42901 CLINT MOORE ROAD, #114BOCA RATON, FLORIDA 33496888.901.8008 www.base-4.com
AA26003324CA 29917
PREMIER RESORTS & MANAGEMENT, INC.(PRM HOTEL GROUP)
730 S. ATLANTIC AVE. SUITE 102ORMOND BEACH, FLORIDA, 32176
386.677.8882
Owner:
Seal:
RICARDO J. MUNIZ-GUILLET, AIA2030 HABERSHAM TRACE,
CUMMING, GA 30041
DRAWINGS NO.
SHEET NAME
PROJECT NO.
CHECKED BY
DRAWN BY
CURRENT ISSUE
CURRENT ISSUE DATE
PROTOTYPE VERSION: VOLUME 1.0 ISSUE 1.1RELEASE DATE: MAY 06, 2019
MEP ENGINEERGARRY VERMAAS PhD, PE
2183 S BERRYS CHAPEL ROADFRANKLIN, TN 37069
FP-101
B4-171-1901
GWV
MWI
2021.06.03
1ST FLOOR FIRESPECIFICATION
PLAN
100% OWNER REVIEWFP-101 1/8" = 1'-0"
1 1ST FLOOR FIRE SPECIFICATION PLAN
FIRE FLOW AND PUMP DATAWATER FLOW TEST DATADATE OF TEST:
TEST LOCATION:
AVAILABLE FLOW IN GPM:
RESIDUAL PRESSURE:
STATIC PRESSURE:
2020.06.11
BUILDING INFORMATION
TYPE OF BUILDING OCCUPANCY:
HEIGHT OF BUILDING:
TOTAL BUILDING AREA:
FIRE PUMP IS NOT REQUIRED.
ORLANDO, FL
1099.19
76
84
R-1
68'-0"
81,254 SF
ISSUENO.
DELTA ISSUE DATE DESCRIPTION
1 FP0 2021.06.03 100% OWNER REVIEW
FIRE PROTECTION KEYNOTES# TEXT1 PROVIDE ORDINARY HAZARD GROUP 1 OCCUPANCY COVERAGE WITH DENSITY OF 0.15 GPM PER SQ.FT. FOR 1500
SQ.FT. HYDRAULICALLY MOST REMOTE AREA. MECHANICAL ROOM, ELECTRICAL ROOM, KITCHEN, STOREGE ROOMSARE UNDER ORDINARY HAZARD CLASSIFICATION. PROVIDE LIGHT HAZARD OCCUPANCY COVERAGE WITH DENSITYOF 0.10 GPM PER SQ.FT. FOR 1500 SQ.FT. HYDRAULICALLY MOST REMOTE AREA. ALL GUEST ROOMS, COORRIDORS,MEETING ROOMS & PUBLIC TOILET ROOMS ARE UNDER LIGHT HAZAR CLASSIFICATION.
2 FIRE DEPARTMENT TO PROVIDE 750 GMP TO THE FDC AND ENSURE 100 PSI AT THE MOST REMOTE HOSECONNECTION OF MANUAL STANDPIPE SYSTEM.
3 THE FIRE VENDOR/GC TO OBTAIN A LETTER FROM THE FIRE DEPARTMENT THAT A PUMPER TRUCK IS AVAILABLE TOSUPPLEMENT THE PRESSURE OF 100PSI AT THE TOP OF THE MANUAL STANDPIPE AS PER NFPA 14 SECTION 7.7.4. IFA PUMPER TRUCK IS NOT AVAILABLE OR MANUAL STANDPIPE SYSTEM IS NOT ALLOWED BY THE CITY, FIRE PUMPSHALL BE SIZED TO MAINTAIN 100 PSI PRESSURE AND SHALL BE COORDINATED WITH THE EOR PRIOR TOINSTALLATION.
![Page 3: FP-001 - planhubapp.s3-us-west-2.amazonaws.com](https://reader030.fdocuments.us/reader030/viewer/2022013015/61d039e7b0371e37364cbdc5/html5/thumbnails/3.jpg)
1
1
FIRE SPRINKLER MAIN TO 2ND FLOOR SPRINKLERS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
A
B
C
D
E
F
G
H
J
K
KINGSTANDARD
(KA)
222
KINGSTANDARD
(KA)
223
KINGCONNECTOR
(KB)
224
QUEEN/QUEENCONNECTOR(QB)
225
QUEEN/QUEENSTANDARD(QA)
226
QUEEN/QUEENSTANDARD(QA)
227
QUEEN/QUEENSTANDARD(QA)
203
KINGSTANDARD
(KA)
204
KINGSTANDARD
(KA)
205
KINGSTANDARD
(KA)
206
KINGSTANDARD
(KA)
207
KING ONEBEDROOMACC.(KE)
R.I.S
208
QUEEN/QUEENCONNECTOR(QB)
209
KINGSTANDARD
(KA)
210
KINGSTANDARD
(KA)
211
KINGSTANDARD
(KA)
212
KINGSTANDARD
(KA)
213
KINGSTANDARD
(KA)
214
KINGSTANDARD
(KA)
215
KINGSTANDARD
(KA)
216
KINGSTANDARD
(KA)
217
QUEEN/QUEENSTANDARD(QA)
218
QUEEN/QUEENSTANDARD(QA)
219
QUEEN/QUEENCONNECTOR(QB)
220
QUEEN/QUEENACC.(QC)
R.I.S
221
STAIR#2
281
STORAGE
231
ELEC/PBX
232
TOILET
236
HOUSEKEEPING
233
ELEVATORLOBBY
230
CORRIDOR
200
STORAGE
234
STAIR#1
280
ELEV.2
150
ELEV.1
151
FITNESS
235
4'' STAND PIPE UP LANDING VALVE
BUTTERFLY VALVE
FLOW DETECTOR SWITCH
PRESSURE GUAGE
TEST AND VALVE ASSEMBLY
FIRE SPRINKLER MAIN TO 2ND FLOOR SPRINKLERS
4'' STAND PIPE UP
LANDING VALVE
11810 HIGH TECH AVEORLANDO, FL 32817
BASE42901 CLINT MOORE ROAD, #114BOCA RATON, FLORIDA 33496888.901.8008 www.base-4.com
AA26003324CA 29917
PREMIER RESORTS & MANAGEMENT, INC.(PRM HOTEL GROUP)
730 S. ATLANTIC AVE. SUITE 102ORMOND BEACH, FLORIDA, 32176
386.677.8882
Owner:
Seal:
RICARDO J. MUNIZ-GUILLET, AIA2030 HABERSHAM TRACE,
CUMMING, GA 30041
DRAWINGS NO.
SHEET NAME
PROJECT NO.
CHECKED BY
DRAWN BY
CURRENT ISSUE
CURRENT ISSUE DATE
PROTOTYPE VERSION: VOLUME 1.0 ISSUE 1.1RELEASE DATE: MAY 06, 2019
MEP ENGINEERGARRY VERMAAS PhD, PE
2183 S BERRYS CHAPEL ROADFRANKLIN, TN 37069
FP-102
B4-171-1901
GWV
MWI
2021.06.03
2ND FLOOR FIRESPECIFICATION
PLAN
100% OWNER REVIEW
FP-102 1/8" = 1'-0"
1 2ND FLOOR FIRE SPECIFICATION PLAN
FIRE PROTECTION KEYNOTE# TEXT
1
PROVIDE ORDINARY HAZARD GROUP 1 OCCUPANCY COVERAGE WITH DENSITY OF 0.15 GPM PERSQ.FT. FOR 1500 SQ.FT. HYDRAULICALLY MOST REMOTE AREA. MECHANICAL ROOM, ELECTRICALROOM, KITCHEN, STOREGE ROOMS ARE UNDER ORDINARY HAZARD CLASSIFICATION. PROVIDELIGHT HAZARD OCCUPANCY COVERAGE WITH DENSITY OF 0.10 GPM PER SQ.FT. FOR 1500 SQ.FT.HYDRAULICALLY MOST REMOTE AREA. ALL GUEST ROOMS, COORRIDORS, MEETING ROOMS &PUBLIC TOILET ROOMS ARE UNDER LIGHT HAZAR CLASSIFICATION.
ISSUENO.
DELTA ISSUE DATE DESCRIPTION
1 FP0 2021.06.03 100% OWNER REVIEW
![Page 4: FP-001 - planhubapp.s3-us-west-2.amazonaws.com](https://reader030.fdocuments.us/reader030/viewer/2022013015/61d039e7b0371e37364cbdc5/html5/thumbnails/4.jpg)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
A
B
C
D
E
F
G
H
J
K
KINGSTANDARD
(KA)
322
KINGSTANDARD
(KA)
323
KINGCONNECTOR
(KB)
324
QUEEN/QUEENCONNECTOR(QB)
325
QUEEN/QUEENSTANDARD(QA)
326
QUEEN/QUEENSTANDARD(QA)
327
QUEEN/QUEENSTANDARD(QA)
303
KINGSTANDARD
(KA)
304
KINGSTANDARD
(KA)
305
KINGSTANDARD
(KA)
306
KINGSTANDARD
(KA)
307
KING ONEBEDROOM(KD)
308
QUEEN/QUEENCONNECTOR(QB)
309
KINGSTANDARD
(KA)
310
KINGSTANDARD
(KA)
311
KINGSTANDARD
(KA)
312
KINGSTANDARD
(KA)
313
KINGSTANDARD
(KA)
314
KINGSTANDARD
(KA)
315
KINGSTANDARD
(KA)
316
KINGSTANDARD
(KA)
317
QUEEN/QUEENSTANDARD(QA)
318
QUEEN/QUEENSTANDARD(QA)
319
QUEEN/QUEENCONNECTOR(QB)
320
KINGACC.(KC)
321
QUEEN/QUEENSTANDARD(QA)
302
QUEEN/QUEENSTANDARD(QA)
301
ELEV.2
150
ELEV.1
151
STAIR#2
381
STORAGE
334
ICE
331
ELEC/PBX
332
ELEVATORLOBBY
330
HOUSEKEEPING
333
CORRIDOR
300
STAIR#1
380
1
1
FIRE SPRINKLER MAIN TO 3RD FLOOR SPRINKLERS
4'' STAND PIPE UP LANDING VALVE
BUTTERFLY VALVE
FLOW DETECTOR SWITCH
PRESSURE GUAGE
TEST AND VALVE ASSEMBLY
FIRE SPRINKLER MAIN TO 3RD FLOOR SPRINKLERS
4'' STAND PIPE UP
LANDING VALVE
11810 HIGH TECH AVEORLANDO, FL 32817
BASE42901 CLINT MOORE ROAD, #114BOCA RATON, FLORIDA 33496888.901.8008 www.base-4.com
AA26003324CA 29917
PREMIER RESORTS & MANAGEMENT, INC.(PRM HOTEL GROUP)
730 S. ATLANTIC AVE. SUITE 102ORMOND BEACH, FLORIDA, 32176
386.677.8882
Owner:
Seal:
RICARDO J. MUNIZ-GUILLET, AIA2030 HABERSHAM TRACE,
CUMMING, GA 30041
DRAWINGS NO.
SHEET NAME
PROJECT NO.
CHECKED BY
DRAWN BY
CURRENT ISSUE
CURRENT ISSUE DATE
PROTOTYPE VERSION: VOLUME 1.0 ISSUE 1.1RELEASE DATE: MAY 06, 2019
MEP ENGINEERGARRY VERMAAS PhD, PE
2183 S BERRYS CHAPEL ROADFRANKLIN, TN 37069
FP-103
B4-171-1901
GWV
MWI
2021.06.03
3RD FLOOR FIRESPECIFICATION
PLAN
100% OWNER REVIEW
FP-103 1/8" = 1'-0"
1 3RD FLOOR FIRE SPECIFICATION PLAN
FIRE PROTECTION KEYNOTE# TEXT
1
PROVIDE ORDINARY HAZARD GROUP 1 OCCUPANCY COVERAGE WITH DENSITY OF 0.15 GPM PERSQ.FT. FOR 1500 SQ.FT. HYDRAULICALLY MOST REMOTE AREA. MECHANICAL ROOM, ELECTRICALROOM, KITCHEN, STOREGE ROOMS ARE UNDER ORDINARY HAZARD CLASSIFICATION. PROVIDELIGHT HAZARD OCCUPANCY COVERAGE WITH DENSITY OF 0.10 GPM PER SQ.FT. FOR 1500 SQ.FT.HYDRAULICALLY MOST REMOTE AREA. ALL GUEST ROOMS, COORRIDORS, MEETING ROOMS &PUBLIC TOILET ROOMS ARE UNDER LIGHT HAZAR CLASSIFICATION.
ISSUENO.
DELTA ISSUE DATE DESCRIPTION
1 FP0 2021.06.03 100% OWNER REVIEW
![Page 5: FP-001 - planhubapp.s3-us-west-2.amazonaws.com](https://reader030.fdocuments.us/reader030/viewer/2022013015/61d039e7b0371e37364cbdc5/html5/thumbnails/5.jpg)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
A
B
C
D
E
F
G
H
J
K
1
1
KINGSTANDARD
(KA)
422
KINGSTANDARD
(KA)
423
KINGCONNECTOR
(KB)
424
QUEEN/QUEENCONNECTOR(QB)
425
QUEEN/QUEENSTANDARD(QA)
426
QUEEN/QUEENSTANDARD(QA)
427
QUEEN/QUEENSTANDARD(QA)
403
KINGSTANDARD
(KA)
404
KINGSTANDARD
(KA)
405
KINGSTANDARD
(KA)
406
KINGSTANDARD
(KA)
407
KING ONEBEDROOMACC.(KE)
408
QUEEN/QUEENCONNECTOR(QB)
409
KINGSTANDARD
(KA)
410
KINGSTANDARD
(KA)
411
KINGSTANDARD
(KA)
412
KINGSTANDARD
(KA)
413
KINGSTANDARD
(KA)
414
KINGSTANDARD
(KA)
415
KINGSTANDARD
(KA)
416
KINGSTANDARD
(KA)
417
QUEEN/QUEENSTANDARD(QA)
418
QUEEN/QUEENSTANDARD(QA)
419
QUEEN/QUEENCONNECTOR(QB)
420
QUEEN/QUEENACC.(QC)
421
QUEEN/QUEENSTANDARD(QA)
402
QUEEN/QUEENSTANDARD(QA)
401
ELEV.2
150
ELEV.1
151
STAIR#2
481
STORAGE
434
STORAGE
431
ELEC/PBX
432
ELEVATORLOBBY
430
HOUSEKEEPING
433
CORRIDOR
400
STAIR#1
480
FIRE SPRINKLER MAIN TO 4TH FLOOR SPRINKLERS
4'' STAND PIPE UP LANDING VALVE
BUTTERFLY VALVE
FLOW DETECTOR SWITCH
PRESSURE GUAGE
TEST AND VALVE ASSEMBLY
FIRE SPRINKLER MAIN TO 4TH FLOOR SPRINKLERS
4'' STAND PIPE UP
LANDING VALVE
11810 HIGH TECH AVEORLANDO, FL 32817
BASE42901 CLINT MOORE ROAD, #114BOCA RATON, FLORIDA 33496888.901.8008 www.base-4.com
AA26003324CA 29917
PREMIER RESORTS & MANAGEMENT, INC.(PRM HOTEL GROUP)
730 S. ATLANTIC AVE. SUITE 102ORMOND BEACH, FLORIDA, 32176
386.677.8882
Owner:
Seal:
RICARDO J. MUNIZ-GUILLET, AIA2030 HABERSHAM TRACE,
CUMMING, GA 30041
DRAWINGS NO.
SHEET NAME
PROJECT NO.
CHECKED BY
DRAWN BY
CURRENT ISSUE
CURRENT ISSUE DATE
PROTOTYPE VERSION: VOLUME 1.0 ISSUE 1.1RELEASE DATE: MAY 06, 2019
MEP ENGINEERGARRY VERMAAS PhD, PE
2183 S BERRYS CHAPEL ROADFRANKLIN, TN 37069
FP-104
B4-171-1901
GWV
MWI
2021.06.03
4TH FLOOR FIRESPECIFICATION
PLAN
100% OWNER REVIEW
FP-104 1/8" = 1'-0"
1 4TH FLOOR FIRE SPECIFICATION PLAN
FIRE PROTECTION KEYNOTE# TEXT
1
PROVIDE ORDINARY HAZARD GROUP 1 OCCUPANCY COVERAGE WITH DENSITY OF 0.15 GPM PERSQ.FT. FOR 1500 SQ.FT. HYDRAULICALLY MOST REMOTE AREA. MECHANICAL ROOM, ELECTRICALROOM, KITCHEN, STOREGE ROOMS ARE UNDER ORDINARY HAZARD CLASSIFICATION. PROVIDELIGHT HAZARD OCCUPANCY COVERAGE WITH DENSITY OF 0.10 GPM PER SQ.FT. FOR 1500 SQ.FT.HYDRAULICALLY MOST REMOTE AREA. ALL GUEST ROOMS, COORRIDORS, MEETING ROOMS &PUBLIC TOILET ROOMS ARE UNDER LIGHT HAZAR CLASSIFICATION.
ISSUENO.
DELTA ISSUE DATE DESCRIPTION
1 FP0 2021.06.03 100% OWNER REVIEW
![Page 6: FP-001 - planhubapp.s3-us-west-2.amazonaws.com](https://reader030.fdocuments.us/reader030/viewer/2022013015/61d039e7b0371e37364cbdc5/html5/thumbnails/6.jpg)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
A
B
C
D
E
F
G
H
J
K
1
1
KINGSTANDARD
(KA)
522
KINGSTANDARD
(KA)
523
KINGCONNECTOR
(KB)
524
QUEEN/QUEENCONNECTOR(QB)
525
QUEEN/QUEENSTANDARD(QA)
526
QUEEN/QUEENSTANDARD(QA)
527
QUEEN/QUEENSTANDARD(QA)
503
KINGSTANDARD
(KA)
504
KINGSTANDARD
(KA)
505
KINGSTANDARD
(KA)
506
KINGSTANDARD
(KA)
507
KING ONEBEDROOM(KD)
508
QUEEN/QUEENCONNECTOR(QB)
509
KINGSTANDARD
(KA)
510
KINGSTANDARD
(KA)
511
KINGSTANDARD
(KA)
512
KINGSTANDARD
(KA)
513
KINGSTANDARD
(KA)
514
KINGSTANDARD
(KA)
515
KINGSTANDARD
(KA)
516
KINGSTANDARD
(KA)
517
QUEEN/QUEENSTANDARD(QA)
518
QUEEN/QUEENSTANDARD(QA)
519
QUEEN/QUEENCONNECTOR(QB)
520
KINGACC.(KC)
521
QUEEN/QUEENSTANDARD(QA)
502
QUEEN/QUEENSTANDARD(QA)
501
ELEV.2
150
ELEV.1
151
STAIR#2
581
STORAGE
534
ICE
531
ELEC/PBX
532
ELEVATORLOBBY
530
HOUSEKEEPING
533
CORRIDOR
500
STAIR#1
580
FIRE SPRINKLER MAIN TO 5TH FLOOR SPRINKLERS
4'' STAND PIPE UP LANDING VALVE
BUTTERFLY VALVE
FLOW DETECTOR SWITCH
PRESSURE GUAGE
TEST AND VALVE ASSEMBLY
FIRE SPRINKLER MAIN TO 5TH FLOOR SPRINKLERS
4'' STAND PIPE UP
LANDING VALVE
11810 HIGH TECH AVEORLANDO, FL 32817
BASE42901 CLINT MOORE ROAD, #114BOCA RATON, FLORIDA 33496888.901.8008 www.base-4.com
AA26003324CA 29917
PREMIER RESORTS & MANAGEMENT, INC.(PRM HOTEL GROUP)
730 S. ATLANTIC AVE. SUITE 102ORMOND BEACH, FLORIDA, 32176
386.677.8882
Owner:
Seal:
RICARDO J. MUNIZ-GUILLET, AIA2030 HABERSHAM TRACE,
CUMMING, GA 30041
DRAWINGS NO.
SHEET NAME
PROJECT NO.
CHECKED BY
DRAWN BY
CURRENT ISSUE
CURRENT ISSUE DATE
PROTOTYPE VERSION: VOLUME 1.0 ISSUE 1.1RELEASE DATE: MAY 06, 2019
MEP ENGINEERGARRY VERMAAS PhD, PE
2183 S BERRYS CHAPEL ROADFRANKLIN, TN 37069
FP-105
B4-171-1901
GWV
MWI
2021.06.03
5TH FLOOR FIRESPECIFICATION
PLAN
100% OWNER REVIEW
FP-105 1/8" = 1'-0"
1 5TH FLOOR FIRE SPECIFICATION PLAN
FIRE PROTECTION KEYNOTE# TEXT
1
PROVIDE ORDINARY HAZARD GROUP 1 OCCUPANCY COVERAGE WITH DENSITY OF 0.15 GPM PERSQ.FT. FOR 1500 SQ.FT. HYDRAULICALLY MOST REMOTE AREA. MECHANICAL ROOM, ELECTRICALROOM, KITCHEN, STOREGE ROOMS ARE UNDER ORDINARY HAZARD CLASSIFICATION. PROVIDELIGHT HAZARD OCCUPANCY COVERAGE WITH DENSITY OF 0.10 GPM PER SQ.FT. FOR 1500 SQ.FT.HYDRAULICALLY MOST REMOTE AREA. ALL GUEST ROOMS, COORRIDORS, MEETING ROOMS &PUBLIC TOILET ROOMS ARE UNDER LIGHT HAZAR CLASSIFICATION.
ISSUENO.
DELTA ISSUE DATE DESCRIPTION
1 FP0 2021.06.03 100% OWNER REVIEW
![Page 7: FP-001 - planhubapp.s3-us-west-2.amazonaws.com](https://reader030.fdocuments.us/reader030/viewer/2022013015/61d039e7b0371e37364cbdc5/html5/thumbnails/7.jpg)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
A
B
C
D
E
F
G
H
J
K
1
1
KINGSTANDARD
(KA)
622
KINGSTANDARD
(KA)
623
KINGCONNECTOR
(KB)
624
QUEEN/QUEENCONNECTOR(QB)
625
QUEEN/QUEENSTANDARD(QA)
626
QUEEN/QUEENSTANDARD(QA)
627
QUEEN/QUEENSTANDARD(QA)
603
KINGSTANDARD
(KA)
604
KINGSTANDARD
(KA)
605
KINGSTANDARD
(KA)
606
KINGSTANDARD
(KA)
607
KING ONEBEDROOM(KD)
608
QUEEN/QUEENCONNECTOR(QB)
609
KINGSTANDARD
(KA)
610
KINGSTANDARD
(KA)
611
KINGSTANDARD
(KA)
612
KINGSTANDARD
(KA)
613
KINGSTANDARD
(KA)
614
KINGSTANDARD
(KA)
615
KINGSTANDARD
(KA)
616
KINGSTANDARD
(KA)
617
QUEEN/QUEENSTANDARD(QA)
618
QUEEN/QUEENSTANDARD(QA)
619
QUEEN/QUEENCONNECTOR(QB)
620
QUEEN/QUEENACC.(QC)
621
QUEEN/QUEENSTANDARD(QA)
602
QUEEN/QUEENSTANDARD(QA)
601
ELEV.2
150
ELEV.1
151
STAIR#2
681
STORAGE
634
GUESTLAUNDRY
631
ELEC/PBX
632
ELEVATORLOBBY
630
HOUSEKEEPING
633
CORRIDOR
600
STAIR#1
680
FIRE SPRINKLER MAIN TO 6TH FLOOR SPRINKLERS
4'' STAND PIPE UP LANDING VALVE
BUTTERFLY VALVE
FLOW DETECTOR SWITCH
PRESSURE GUAGE
TEST AND VALVE ASSEMBLY
FIRE SPRINKLER MAIN TO 6TH FLOOR SPRINKLERS
4'' STAND PIPE UP
LANDING VALVE
11810 HIGH TECH AVEORLANDO, FL 32817
BASE42901 CLINT MOORE ROAD, #114BOCA RATON, FLORIDA 33496888.901.8008 www.base-4.com
AA26003324CA 29917
PREMIER RESORTS & MANAGEMENT, INC.(PRM HOTEL GROUP)
730 S. ATLANTIC AVE. SUITE 102ORMOND BEACH, FLORIDA, 32176
386.677.8882
Owner:
Seal:
RICARDO J. MUNIZ-GUILLET, AIA2030 HABERSHAM TRACE,
CUMMING, GA 30041
DRAWINGS NO.
SHEET NAME
PROJECT NO.
CHECKED BY
DRAWN BY
CURRENT ISSUE
CURRENT ISSUE DATE
PROTOTYPE VERSION: VOLUME 1.0 ISSUE 1.1RELEASE DATE: MAY 06, 2019
MEP ENGINEERGARRY VERMAAS PhD, PE
2183 S BERRYS CHAPEL ROADFRANKLIN, TN 37069
FP-106
B4-171-1901
GWV
MWI
2021.06.03
6TH FLOOR FIRESPECIFICATION
PLAN
100% OWNER REVIEW
FP-106 1/8" = 1'-0"
1 6TH FLOOR FIRE SPECIFICATION PLAN
FIRE PROTECTION KEYNOTE# TEXT
1
PROVIDE ORDINARY HAZARD GROUP 1 OCCUPANCY COVERAGE WITH DENSITY OF 0.15 GPM PERSQ.FT. FOR 1500 SQ.FT. HYDRAULICALLY MOST REMOTE AREA. MECHANICAL ROOM, ELECTRICALROOM, KITCHEN, STOREGE ROOMS ARE UNDER ORDINARY HAZARD CLASSIFICATION. PROVIDELIGHT HAZARD OCCUPANCY COVERAGE WITH DENSITY OF 0.10 GPM PER SQ.FT. FOR 1500 SQ.FT.HYDRAULICALLY MOST REMOTE AREA. ALL GUEST ROOMS, COORRIDORS, MEETING ROOMS &PUBLIC TOILET ROOMS ARE UNDER LIGHT HAZAR CLASSIFICATION.
ISSUENO.
DELTA ISSUE DATE DESCRIPTION
1 FP0 2021.06.03 100% OWNER REVIEW