Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA...

62
Standards Certification Education & Training Publishing Conferences & Exhibits Foundation Fieldbus - Working Today, Preparing for tomorrow Ian Verhappen Director, Industrial Networks MTL Instrument Group

Transcript of Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA...

Page 1: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

Standards

Certification

Education & Training

Publishing

Conferences & Exhibits

Foundation Fieldbus -Working Today, Preparing for tomorrow

Ian VerhappenDirector, Industrial Networks

MTL Instrument Group

Page 2: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Today’s Agenda

• Fieldbus Global Projects– Global Projects– Middle East

• Fieldbus Solutions Today– EDDL– H1 and HSE

• Digital Control System Trends– EDDL Improvements– Fieldbus Safety– HSE

Page 3: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

Standards

Certification

Education & Training

Publishing

Conferences & Exhibits

Fieldbus Implementation

Page 4: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

255 unique and 378 total devices registered

Distribution of Device Types

11

45

69

36

81

2

31

51

33

19

HSE LDFlowPressureTemperatureValveControllerOtherAnalyticalLevelPS

Page 5: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Markets Served

600,000 devices

9000 Systems

Fieldbus Today

Page 6: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Market Distribution

Global Global LA

12%

NA43%AP

13%

MEA7%

EUR25%

Other8%

Mining and Metals

3%Education3%

Pulp and Paper

4%

Food & Beverage

9%

Pharm- aceutical

9%

Power13%

Oil & Gas29%

Chemical22%

Industry Industry

Page 7: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Installed Devices

2001 2002 2003 2004 2005 2006

Middle East

Global0

50000

100000

150000

200000

250000

Fiel

dbus

Dev

ices

Page 8: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

Standards

Certification

Education & Training

Publishing

Conferences & Exhibits

Today’s Fieldbus Solutions

Page 9: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

FOUNDATION™ Fieldbus H1

4-20mA

P.S.

fieldbus

P.S.

– Fieldbus devices are connected in parallel on the bus, which carries digital data from/to all the devices on the bus.

– Fieldbus devices provide information to all other devices on the network.

Page 10: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Commercial, Off The Shelf

(COTS) Ethernet Equipment

New Protocol Specifications

for HSE

System Architecture AddendumSystem Management AddendumNetwork Management Addendum Data Link Addendum - BridgingEthernet PresenceField Device Access AgentRedundancy

New Function BlockSpecifications for HSE

Flexible Function Block (MIO)Flexible Function Block (61131 )FFB Application GuideMulti - Variable Optimization

11 New FF Specifications

STANDARDETHERNET

“STACK”

FUNCTION BLOCKS

HSEAPPLICATION

PROTOCOL

Ethernet Physical Layer

High Speed Ethernet

Page 11: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

FIELDBUS H1 FIELDBUS H1

DEVICES ON DIFFERENT NETWORKS

Linking Device

FF Bridges Between FF Networks

Page 12: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Live VideoDisplay

PresentationFiber

YokogawaField Eye

Filter Deck in Plant DCSEmerson

PlantHSE

HSE Linking DevicesSmar, Softing

Blowback and Dump Process – Filter BInvensys, P+F, Westlock, Yamatake, Yokogawa

PlantH1

ConfigurationSmar, Softing

Ethernet SwitchesHirschmann

Ethernet Switches

Turck, Hirschmann

ControlHouse

HSE FFBSmar, Softing

OPC ServersSmar, Softing

H1

HSE

Fiber

Live Plant Demo Integrated ArchitecturePresentation Room

Page 13: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Smar FFB Junction Box

Westlock Positioners Driving 8’ Butterfly Valves

NitrogenPressureInvensys

∆Pressureacross Filters

Yamatake

NitrogenTemperatureYokogawa

H1

H1 H1

Live Demo – Modified LogicFilter B Sequence Logic Runs in HSE FFBs

Filter A Filter B Filter C

Emerson DeltaV

Filter A Filter B Filter C

Run in DeltaV

Del

taV

Com

man

ds

Smar

FFB

to ru

n

Smar FFB operates 5 valves and

then passes control to the Softing FFB

Softing FFB operates 5 valves and then

passes control back to DeltaV

Run in DeltaVRun in HSE FFBs

Softing FFB

HSE HSE

HSE

1

2

3

4

1

2

3

4

Permissives

Page 14: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

HSE Not The End of H1

• H1 used for field instruments• HSE used at the host-level• H1 and HSE complement each other

H1H1 HSEHSESpeed 31.25 kbit/s 10 Mbit/s or 100 Mbit/sDistance (per segment) 1,900 m (1.2 miles) 100 m (300 ft)Two-wire Yes NoMultidrop Yes No (UTP)Bus-power Yes NoIntrinsically safe Yes NoRedundancy No YesDeterministic Yes Yes (with switches)

Page 15: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Operations & MaintenanceC

ash

Flow

Higher sustained production with minimize costs

Faster time-toprofit

Safer operation

Fewer unscheduled outages

Shorter scheduled outage

Longer duration to scheduled outage

Page 16: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Expanded System View

FCS: Expanded view. Field devices are part of the system.

DCS: Limited system view. Does not include diagnostics and other information from field devices.

15.3 mA

TAG = LIC-012VALUE = 70.34UNITS = m3

STATUS = GOODALARM = Y/N

Page 17: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Increased Information

• Information is available for decision making• Conventional analog system

– 4 - 20 mA has very limited information content (PV only)

• Fieldbus system– instrument identification, location– status of PV– ambient conditions– diagnostics– configuration– instrument characteristics– calibration information: date, method, location, etc.

Page 18: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Flow

9%Level

8%

Pressure

11%

Temperature15%

Valve

20%

Others

37%

Flow 1128Level 931Pressure 1379Temp. 1859Valves 2404Others 4566

Typical Refinery Instruments Distribution

Page 19: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

CPU - 2%

Sensors - 48%

I/O - 15%

Actuators - 30%

Wiring - 5%

Areas of failures

Page 20: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Device Maintenance Effort

Routine Check, 35%

No Problem, 28%

ReRanging, 20%

Zero Drift, 6%

Process Interface, 6%

Failure, 4%

63% of time is spent investigating “problems” that do not exist. Fieldbus will tell you this so it will no longer be necessary to check these reports.

Page 21: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Asset Management Drivers

• Maintenance Cost Reduction Drives End Users

• 40% of Mfg. Cost is Maintenance• 50% of Maintenance Is Corrective

– 10 times More Costly Than Preventative Maintenance

• Preventative Maintenance is Done 25% of Time– 5 Times More costly Than Predictive

Maintenance• 60% of Preventative Maintenance is

Unnecessary0

5

10

15

20

25

30

35

40

45

50

Correct Prevent Predict

From ARC Independent Research

Page 22: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Maintenance Savings

• Estimated 10- 20% saving in maintenance– Assignment of maintenance tasks to operators / right people to

do the task– Better field diagnostics– Better preventative maintenance data– Less false alarms– Faster troubleshooting

Page 23: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Operations & Maintenance

• Operational efficiency improved by up to 2%• Predictive maintenance

– schedule maintenance based on device diagnostics– increase plant availability

Page 24: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Mean

Standard Deviation: σ

3σ 3σ2σ 2σ1σ 1σ

68%

95%

>99%

Characterizing Change

Page 25: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Control Limit

Manual

Digital

Digital

Analogue

Analogue

Pneumatic

Pneumatic

Manual

Impact of Tighter Loop Control

Page 26: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Maintenance

• Expandability and long term maintainability– sensors are field-upgradeable– open, interoperable technology

– buy spares from third parties to keep price down– buy spares from those who stock, i.e. user need not keep stock– “best of its kind” device may be used independent of manufacturer

Page 27: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Instrument Management Software (including fieldbus diagnostics)

power supply system

Hand-heldDiagnostic Module

Host control system

Controller I/O

Periodic diagnostic monitoring

Fieldbus

wiring components

Page 28: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Commissioning procedure

• Connect fieldbus tester at each field device and at rack room– record readings in each location

• Upload readings to PC

Page 29: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Instrument Management Software (including fieldbus diagnostics)Host control system

Controller I/O

On-line diagnostic monitoring

F800 Series fieldbus power supply system

H1 Fieldbus

Field junction boxSegment 1 of 8

Basic failure alarms

F809F on-line Diagnostic Monitor

Page 30: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

MTL F809F on-line monitoring

• Continuously monitors segment parameters

• Monitors 8 fieldbus segments• Reports parameters over

FOUNDATION fieldbusTM H1– Module is a Fieldbus device

• Diagnostic software– Integrated in Asset Manager

system instrument management software

Page 31: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

MTL F809F on-line monitoring

• Open solution– FOUNDATION fieldbusTM H1 device

easily integrates with Honeywell Experian PKS system

– Full device description support• Future proof architecture

– Fieldbus DTM support planned – Enhanced eDDL support planned

• Minimises total cost of ownership by integrating into fieldbus H1 system– No additional hardware costs– No additional costs in installing,

commissioning and maintenance of separate network

– Instrumentation team use same software for physical layer and fieldbus device diagnostics

Page 32: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

MTL F809F prototype results

Discrete input block

Resource block

segment transducer blocksF809FS device

Page 33: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

Standards

Certification

Education & Training

Publishing

Conferences & Exhibits

Fieldbus’ Future

Page 34: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

EDDL Cooperation Team

Page 35: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Phase 1 EnhancementsGraphing – Use EDDL for graphical display of static Y-t and XY dataCharting – Use EDDL for graphical display of real-time data from deviceEnhanced User Interface – Use EDDL to describe screen layoutEnhanced Data Storage- Use EDD to securely store data on the host

Phase 1 Specification in IEC 61804-3 Edition 1 CDVPhase 1 Approved Change Requests in IEC 61804-3 Edition 1 CDVPhase 1 Interoperability Guideline is IEC 61804-4 Edition 1 DTR

Charts Images

Enhanced User Interface

Graphs

Enhanced Data Storage

Maintain Enhancements in IEC Format

Page 36: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Visualization Extensions for Sensor/Actuator Configuration, Motor Control, Radar Level Configuration, Valve Signatures and Other Complex Configuration and Diagnostic Applications

Parameter organizationWindows, dialogs, group boxesIntegration of images Support for charts and graphsMultiple plotsInteractive zoomingDirect editing of graphsEmphasis, key points, notes

DD Cooperation Project

Page 37: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

DD Cooperation Project

Extensions for Improved Control of Data Storage on the Host System by the Field Device for Complex Valve Diagnostics, Sensor Drift, Sensor/Actuator Diagnostics and Archived Valve Signatures Applications

Independent of host operating systemIndependent of host file system

Page 38: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

DD Cooperation Project

Enhanced User Interface Example

Parameter Organization

Group BoxesDialogs

Window

Page 39: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Radar Gauge Example

Configuration of thresholds and false echo areas

GRAPH

WAVEFORM(Data from Device)

AXIS

MENUS & METHODS(Enhanced UI)

Radar GaugeThresholdCalibration

DD Cooperation Project

ARRAY(s)(Device Data)

FILE/LIST(Persistent

Data)

Echo Curve

Filter

DD Cooperation Project

Page 40: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Blue line is a reference retrievedvia FILE and ARRAY

Valve Step Response Diagnostics

Travel (From device)

Setpoint (Stored)

Valve Step Example

ARRAY(s)(Device Data)

MENUS & METHODS(Enhanced UI)

FILE(Persistent Data)

Real-time Step Response of a valve.

CHART

SOURCEs(Stored Data andData from Device) AXIS

DD Cooperation Project

Page 41: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Blue line is a reference retrievedvia FILE and ARRAY

Valve Signature

Open Stroke

Close Stroke

Valve Signature Example

Valve Signature (Hysteresis) as a measure of the air pressure to stroke the valve open and close

GRAPH

WAVEFORM(Data from Device)

ARRAY(s)(Device Data)

AXIS

MENUS & METHODS(Enhanced UI)

FILE/LIST(Persistent Data)

DD Cooperation Project

Page 42: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Blue line is a reference retrievedvia FILE and ARRAYBest Fit

Valve Signature

Best Fit Example

GRAPH

WAVEFORM(Data from Device)

ARRAY(s)(Device Data)

AXIS

MENUS & METHODS(Enhanced GUI)

FILE(Persistent Data)

“Best Fit” line can be drawn using new features in DD Methods.

DD Cooperation Project

Page 43: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Motor Control Example

Image

Display motor starts, operating hours, number of overload trips, etc.

MOTORSYMMETRY

MOTOR PARAMETERS

DD Cooperation Project

Page 44: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

OPC UA Server (UA = Unified Architecture)

EDDEDD

SimpleDevice

Client-Specific Features

OPC UA Client

Complex Device

EDD...

..

....

..

....

..

....

..

.

...

EDD

• Simple and complex device integration requires only EDDs• Advanced requirements utilize OPC UA client applications driven by

OPC UA server resident EDDs for online and offline data access

EDDL Phase 2 – Scaleable Device Integration

Page 45: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

Standards

Certification

Education & Training

Publishing

Conferences & Exhibits

Fieldbus Safety

Page 46: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Phase 2 Application Architecture

Client Applications

HSE OPC UAServer(s)

HSE Field Device

Web Services

OPC UAClient(s)

Configuration/Maintenance

Plant/Enterprise

e.g. MRP,ERP,Optimization

Trend/Historian.Asset Management

HSE Linking Device

L

H1 FFB

Blue line is a reference retrievedvia FILE and ARRAY

EDDL Cooperation Project

Blue line is a reference retrievedvia FILE and ARRAY

EDDL Cooperation Project

Blue line is a reference retrievedvia FILE and ARRAY

EDDL Cooperation Project

OperatorHMI

HSE Remote I/O

FFB

Enhanced ProceduralSupport for Complex Devices

H1 Remote I/O

FFBH1

HSE

HSE

HSE +

OPC UA

HSE

OPC UA

EDD

Off-Line Configuration+

Page 47: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Design toIEC 61508

Black Channel

New SIS Function Blocks

&Function Block

Diagnostics

Design toIEC 61508

Fieldbus Safety

FF-SIS Communication

Diagnostics

Page 48: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

SIS_DI

SIS_AVTR

SIS_DO

Write Lock (WL)

S

SIS_WL

SIS_AI

SIS_RB

SIS_WL

SIS_AI

SIS_RB

SIS_WL

SIS_AI

SIS_RB

SIS_WL

SIS_RB

Example SIS Application Analog 2 out of 3 Voter

Page 49: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

Standards

Certification

Education & Training

Publishing

Conferences & Exhibits

New Fieldbus Initiatives

Page 50: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Fieldbus Wireless

• Communications of Diagnostic Data for Maintenance– Integrate with Asset Management solutions– Accessible by Technicians in the field

• Build on work of HART Wireless and ISA-100 Committees

Page 51: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

HSE Remote I/O

• Requirements for High Speed Ethernet Remote I/O (HSE-RIO) – discrete I/O – gateways to other lower level networks

– HART– Profibus– Modbus– AS-I– DeviceNet, etc.

• Preliminary Schedule– Started January 2007– Completion Q4 2008

Page 52: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

Standards

Certification

Education & Training

Publishing

Conferences & Exhibits

Foundation FieldbusToday’s Solution

The platform for Tomorrow

®

FOUNDATION

www.mtl-inst.com

Page 53: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

QuestionsIan VerhappenDirector Industrial NetworksPhone: 877 334-3579E-Mail: [email protected]

Page 54: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

ReplaceOperations & MaintenanceEngineering, Construction,& Commissioning/Start-up

Economic Life CycleC

ash

Flow

Analogfieldbus

Time

Page 55: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Fieldbus Project Costs

• Estimated Project Savings– Materials/Field Devices: Increased by 25%– Installation Labor: Reduced by 50% – Commissioning: Reduced by 75%– Engineering: Reduced by 50%

• Overall Capital Savings of 25 – 30%– However savings will only be realized if the project is planned

as a fieldbus project.

Page 56: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Fieldbus as a Cable Multiplier

Three existing4-20 mA Pairs

J-Box

TT

Fieldbus devices

Three existingpairs, one usedfor fieldbus

J-Box

Page 57: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Termination count

FT-100

+-

FCV-100

+-

TT-100

+-

Field

PT-101

+-

123456789101112

Junction Box

123456789101112

Marsh Cab.

1

2

3

4

+-+-+-+-

+-+-+-+-

I.S.Barrier

8

24 20 5

16 4

8 2

15

+-+-+-+-+-+-

I/OAssembly

Conventional analog termination

Fieldbus termination (also includedin conventional termination count)Marshalling done in Junction Box with

Fieldbus so Marsh Cab is optional

Totals: 75 Analog34 Fieldbus

Page 58: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Multivariable Measurements

Conventional:• 1 measurement / device• Penetration / signal

Fieldbus:• Multiple measurement / device

Conventional:• 1 measurement

Fieldbus:• Multiple measurements

• Pressure• Temperature• Mass Flow• Volumetric Flow

Page 59: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

Reduced Space Requirements

• Wiring & Rack• Cable cost• Junction box• Cable Conduit• Processing

of cable• Marshalling• Barrier

ConventionalSystem

Fieldbus System

Cabinet Cable

Case of 350 I/O points

Courtesy of Emerson Process Managment

Page 60: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

I/O Reduction

Courtesy of Shell Deer Park

Courtesy of Shell Deer Park

Courtesy of Shell Deer Park Courtesy of Shell Deer Park

Courtesy of Cargill

Courtesy of Cargill

Page 61: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

• Commissioning Costs Without fieldbus:

Project Cost Benefits

• Individually ring out wiring• Attach device• Verify communications• Verify link to control strategy

2 hours / device for 2 technicians

Page 62: Foundation Fieldbus - Working Today, Preparing for tomorrow · FOUNDATION™ Fieldbus H1 4-20mA P.S. fieldbus P.S. – Fieldbus devices are connected in parallel on the bus, which

#

• Commissioning Costs With fieldbus:

Project Cost Benefits

25 minutes / device for 1 technician

• Check segment wiring• Attach device• Drag-and-drop commissioning