2 Freedom to Choose. Power to Integrate.2 Freedom to Choose. Power to Integrate.
Commissioning Benefits?
Since late 1990s, major end users like Shell, BP and Petronas
are standardizing their installations on Foundation Fieldbus.
First reports in 1997 by Dow Chemical1 indicated “74% reduction
in field wiring, a 93% reduction in required control room space,
and an 80% reduction in field-device commissioning time over
previous installations done with conventional input/output”.“Startup took only 15 man-hours instead of 200”2.
Too good to be true?
Why do end users report significant reductions in time?
– Let us find out.
Sources:1 Gregory K. McMillan, Douglas M. Considine ,“Process/industrial instruments and controls handbook”, McGraw Hill, 1999 2 InTech, June 1997, “Dow claims first fieldbus installation”, International Society of Automation (ISA), 1997
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 3/43
3 Freedom to Choose. Power to Integrate.3 Freedom to Choose. Power to Integrate.
Contents
About project commissioning Comparing 4-20mA and Fieldbus infrastructure
Commissioning process
– 4-20mA
– Fieldbus
– Comparison Commissioning in practice
Conclusion
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 4/43
4 Freedom to Choose. Power to Integrate.4 Freedom to Choose. Power to Integrate.
About Project Commissioning
Project commissioning is the process of assuring that allsystems and components of a building or industrial plant
are designed, installed, tested, operated, and maintained
according to the operational requirements of the owner or
final client.
A commissioning process may be applied not only to new
projects but also to existing units and systems subject to
expansion, renovation or revamping.
Source: Wikipedia
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 5/43
5 Freedom to Choose. Power to Integrate.5 Freedom to Choose. Power to Integrate.
About Project Commissioning
Apply engineering techniques and procedures to check,inspect and test every operational component of the
project
– individual functions, such as instruments and
equipment
– complex amalgamations such as modules,subsystems and systems
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 6/43
6 Freedom to Choose. Power to Integrate.6 Freedom to Choose. Power to Integrate.
Comparing 4-20mA and Fieldbus Infrastructure
One signal per I/O point Process value is coded in
4-20mA analog signal
Only little diagnostics
(LB/SC)
6
4-20mA
I/O
fieldbus
FF H1 T FF
PS
T
Parallel connection Cable carries power and
digital data
Plenty of information
Data integrity checks
Diagrams simplified
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 7/437 Freedom to Choose. Power to Integrate.7 Freedom to Choose. Power to Integrate.
Commissioning Process 4-20mA
4-20mA
Install the cables
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 8/438 Freedom to Choose. Power to Integrate.8 Freedom to Choose. Power to Integrate.
Commissioning Process 4-20mA
4-20mA
Install the cables
Verify the cable installation
Test Report
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 9/439 Freedom to Choose. Power to Integrate.9 Freedom to Choose. Power to Integrate.
Commissioning Process 4-20mA
4-20mA
Install the cables
Verify the cable installation
Install the devices
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 10/4310 Freedom to Choose. Power to Integrate.10 Freedom to Choose. Power to Integrate.
Commissioning Process 4-20mA
4-20mA
Install the cables
Verify the cable installation
Install the devices
Verify device installation
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 11/4311 Freedom to Choose. Power to Integrate.11 Freedom to Choose. Power to Integrate.
Commissioning Process 4-20mA
4-20mA
Install the cables
Verify the cable installation
Install the devices
Verify device installation
Install the DCS
Assigning the I/O
These two steps may also happen earlier or later in the commissioning process.
The actual work on the I/O is system-dependent. The required steps would be:
• Determine which I/O point of the system is connected to which field instrument• Assign/verify the tag (typically using walkie-talkie)
• Put it into the control application
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 12/4312 Freedom to Choose. Power to Integrate.12 Freedom to Choose. Power to Integrate.
Commissioning Process 4-20mA
4-20mA
Install the cables
Verify the cable installation
Install the devices
Verify device installation
Install the DCS
Assigning the I/O Calibrate the sensor
(sensor drift)
Thermocouple → mV
RTD → Ohm
Analog measurement
can drift and must be
calibrated from time
to time
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 13/4313 Freedom to Choose. Power to Integrate.13 Freedom to Choose. Power to Integrate.
Commissioning Process 4-20mA
4-20mA
Install the cables Verify the cable installation
Install the devices
Verify device installation
Install the DCS
Assigning the I/O Calibrate the sensor
(sensor drift)
Ranging
Using HART (or sometimes DIP switches):
“4mA shall be 20 C, 20mA shall be 120 C”
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 14/4314 Freedom to Choose. Power to Integrate.14 Freedom to Choose. Power to Integrate.
Commissioning Process 4-20mA
4-20mA
Install the cables Verify the cable installation
Install the devices
Verify device installation
Install the DCS
Assigning the I/O Calibrate the sensor
(sensor drift)
Ranging
Calibrate the 4-20mA
(current drift)
Analog output can driftand must be calibrated
from time to time
Simulate a
measurement
value using
HART
Measure
the output
current with a
precision tool
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 15/4315 Freedom to Choose. Power to Integrate.15 Freedom to Choose. Power to Integrate.
Commissioning Process 4-20mA
4-20mA
Install the cables Verify the cable installation
Install the devices
Verify device installation
Install the DCS
Assigning the I/O Calibrate the sensor
(sensor drift)
Ranging
Calibrate the 4-20mA
(current drift) System ranging (DCS)
DCS must know what 4mA means
and what 20mA means.
If your instrument is set to:
“4mA shall be 20 C, 20mA shall be
120 C”, your DCS must be set to
the same range.
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 16/4316 Freedom to Choose. Power to Integrate.16 Freedom to Choose. Power to Integrate.
Positioner
Ranging, 4-20mA
Transmitter
Range
40-200 °C
System
Range
0-200 °C
12 mAProcess
120 °C
Reading
100 °C
...alarms and trips
not working
Instrument range and DCS system range must match
Transmitter
CPU
AI
A/D
D/A4-20 mA
AO
D/A
A/D4-20 mA
Range #2Range #1
CPU
CTRL
CPU
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 17/4317 Freedom to Choose. Power to Integrate.17 Freedom to Choose. Power to Integrate.
Commissioning Process 4-20mA
4-20mA
Install the cables Verify the cable installation
Install the devices
Verify device installation
Install the DCS
Assigning the I/O Calibrate the sensor
(sensor drift)
Ranging
Calibrate the 4-20mA
(current drift) System ranging (DCS)
System calibration 4-20mA
(current drift)
AI: Simulate a current
and check thereading on the DCS
AO: Set an output
value on the console
and verify the current
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 18/4318 Freedom to Choose. Power to Integrate.18 Freedom to Choose. Power to Integrate.
Commissioning Process Fieldbus
Fieldbus uses a bus structure, so a single trunk cable is run into
the field. This reduces the number of required terminations, and
hence reduces installation time and the number of potential
points of failures.
Fieldbus
Install the cables
Verify the cable installation
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 19/43
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 20/4320 Freedom to Choose. Power to Integrate.20 Freedom to Choose. Power to Integrate.
Commissioning Process Fieldbus
Fieldbus uses digital communication and requires dedicated tools to
verify proper installation. These “Multimeters for fieldbus” are
operated similar to regular multimeters, so that no disadvantage
arises out of „being digital‟ (which someone may perceive as
complex).
Fieldbus
Install the cables
Verify the cable installation
Install the devices
Verify device installation
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 21/43
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 22/43
22 Freedom to Choose. Power to Integrate.22 Freedom to Choose. Power to Integrate.
Commissioning Process Fieldbus
Fieldbus systems offer “commissioning wizards”, that enable fool-
proof and fast commissioning of FF instruments.
Fieldbus
Install the cables Verify the cable installation
Install the devices
Verify device installation
Install the DCS
Assigning the I/O
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 23/43
23 Freedom to Choose. Power to Integrate.23 Freedom to Choose. Power to Integrate.
Commissioning Process Fieldbus
Foundation Fieldbus devices are
recognized by three mechanisms:
• node address for communication
• device tag corresponding to the
project P&I diagram
• a unique identifier allowing thesystem to automatically resolve
any tag or address conflicts
Fieldbus
Install the cables Verify the cable installation
Install the devices
Verify device installation
Install the DCS
Assigning the I/O
The system automatically assigns the address to all devices, avoiding human
errors such as address duplication associated with manually managed
protocols, and saving time.Therefore technicians work based on tag and need not be concerned with
address.
Thanks to the unique identifier, multiple devices can be connected and
commissioned at the same time. It is plug-'n'-play.
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 24/43
24 Freedom to Choose. Power to Integrate.24 Freedom to Choose. Power to Integrate.
Commissioning Process Fieldbus
For instruments with analog sensors such as RTDs or
thermocouples, the measurement circuit may drift and may require
calibration. For other types like time-of-flight (e.g. radar level
sensor), they are considered “digital” and do not require calibration.
Fieldbus
Install the cables Verify the cable installation
Install the devices
Verify device installation
Install the DCS
Assigning the I/O Calibrate the sensor
(sensor drift)
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 25/43
25 Freedom to Choose. Power to Integrate.25 Freedom to Choose. Power to Integrate.
Commissioning Process Fieldbus
Transmission is digital. A conversion from one unit to another takes place inthe instrument function block:
Example: A temperature may transmit its reading in °C, °F, or Kelvin. It may
also scale a certain measurement range into a % value.
There is no conversion required by the DCS, as the readings are all
transmitted with the engineering unit included.
Fieldbus
Install the cables Verify the cable installation
Install the devices
Verify device installation
Install the DCS
Assigning the I/O Calibrate the sensor
(sensor drift)
Ranging
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 26/43
26 Freedom to Choose. Power to Integrate.26 Freedom to Choose. Power to Integrate.
Positioner
Ranging, 4-20mA
Transmitter
Range
40-200 °C
System
Range
0-200 °C
12 mAProcess
120 °C
Reading
100 °C
...alarms and trips
not working
Results:
Range mismatch
Range exceeded (more than100%, less than 0%)
Transmitter
CPU
AI
A/D
D/A4-20 mA
AO
D/A
A/D4-20 mA
Range #2Range #1
CPU
CTRL
CPU
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 27/43
27 Freedom to Choose. Power to Integrate.27 Freedom to Choose. Power to Integrate.
PositionerTransmitter
Ranging, Fieldbus
FF FF
BUS
FF
CTRL
CPU
CPU
CPUDigital
Digital
Digital
Transmitter
Range
-200 to 850 °C
System
(No range)
120 °CProcess
120 °C
Reading
120 °C
Results:
Range mismatch impossible
Making full use of physical measurement range of transmitter
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 28/43
28 Freedom to Choose. Power to Integrate.28 Freedom to Choose. Power to Integrate.
Commissioning Process Fieldbus
Digital signaling/communication is standardized and does not require any
kind of adjustment.
Fieldbus
Install the cables Verify the cable installation
Install the devices
Verify device installation
Install the DCS
Assigning the I/O Calibrate the sensor
(sensor drift)
Ranging
Calibrate the comm‟s signal?
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 29/43
29 Freedom to Choose. Power to Integrate.29 Freedom to Choose. Power to Integrate.
Commissioning Process Fieldbus
Not required and not reasonable, as the transmitter provides readings
inclusive engineering unit.
Fieldbus
Install the cables Verify the cable installation
Install the devices
Verify device installation
Install the DCS
Assigning the I/O Calibrate the sensor
(sensor drift)
Ranging
Calibrate the comm‟s signal
System ranging (DCS)
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 30/43
30 Freedom to Choose. Power to Integrate.30 Freedom to Choose. Power to Integrate.
Commissioning Process Fieldbus
Fieldbus
Install the cables Verify the cable installation
Install the devices
Verify device installation
Install the DCS
Assigning the I/O Calibrate the sensor
(sensor drift)
Ranging
Calibrate the comm‟s signal
System ranging (DCS) System calibration comm‟s
signal
Digital signaling/communication is standardized and does not require any
kind of adjustment.
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 31/43
31 Freedom to Choose. Power to Integrate.31 Freedom to Choose. Power to Integrate.
Commissioning Process Comparison
Fieldbus
Install the cables Verify the cable installation
Install the devices
Verify device installation
Install the DCS
Assigning the I/O Calibrate the sensor
(sensor drift)
Ranging
Calibrate the comm‟s signal
System ranging (DCS) System calibration comm‟s
signal
4-20mA
Install the cables Verify the cable installation
Install the devices
Verify device installation
Install the DCS
Assigning the I/O Calibrate the sensor
(sensor drift)
Ranging
Calibrate the 4-20mA
(current drift) System ranging (DCS)
System calibration 4-20mA
(current drift)
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 32/43
32 Freedom to Choose. Power to Integrate.32 Freedom to Choose. Power to Integrate.
Commissioning in Practice
80 – 95% of problems are installation related
What are these problems?
How to avoid them?
How to find them if they occur? (Troubleshooting)
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 33/43
33 Freedom to Choose. Power to Integrate.33 Freedom to Choose. Power to Integrate.33
Bad wiring technique
Welding, variable frequency drives (VFD), Motors,machinery:
Increase of HF noise
Increasing number of retransmissions
Can be a combination of both
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 34/43
34 Freedom to Choose. Power to Integrate.34 Freedom to Choose. Power to Integrate.34
Case study: faults in operationCable jacket stripped back
too far can causeinstrument malfunction:
– Water ingress
– Wires shorted to
housing
– Corrosion
– Tearing wires(increasing
resistance)
Increasing number of
retransmissions
Signal amplitude rises
Increase of FF noise Can be a combination of
above
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 35/43
35 Freedom to Choose. Power to Integrate.35 Freedom to Choose. Power to Integrate.35
Wires coming out of ferrules:
Spur:
Device drops off (may or may not return)
Increasing number of retransmissions
Trunk:
Devices drop off (may or may not return)
Signal amplitude sometimes ok,
sometimes high
Increasing number of retransmissions
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 36/43
36 Freedom to Choose. Power to Integrate.36 Freedom to Choose. Power to Integrate.36
Bend radius too tight, Upward facing gland risks water ingress
Two cables into one gland
prevents sealing of gland
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 37/43
37 Freedom to Choose. Power to Integrate.37 Freedom to Choose. Power to Integrate.37
Corroded terminals:
Increasing number of retransmissions
Increase of FF noise
Can be a combination of both
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 38/43
38 Freedom to Choose. Power to Integrate.38 Freedom to Choose. Power to Integrate.
Commissioning 4-20mA
Always on the critical path (may bring signal down)
Manual, step-by-step procedure
Labor intensive
Requires
– Screw driver
– Check sheet – Pencil
– Multimeter
– Scope
Check one device at a time
Test Report
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 39/43
39 Freedom to Choose. Power to Integrate.39 Freedom to Choose. Power to Integrate.
Portable Commissioning tools for fieldbus
Portable tools for commissioning, monitoring, and
troubleshooting. Different products on the market to suit
different needs.
Can connect to any spur or trunk
Menu guided user interface
Can store & upload data No paper needed
No manual recording
Check many devices at same time
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 40/43
40 Freedom to Choose. Power to Integrate.40 Freedom to Choose. Power to Integrate.
Instrument Management Software
(including fieldbus diagnostics)
Fieldbus power
supply system
Host control system
Controller I/O
Portable Commissioning tools
Fieldbus
wiring components
Hand-held
Diagnostic Module
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 41/43
41 Freedom to Choose. Power to Integrate.41 Freedom to Choose. Power to Integrate.
Fieldbus Diagnostic Modules
Integrated single tool for commissioning, monitoring, and
troubleshooting. Operated in the control room, usually
mounted on fieldbus power supply carrier.
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 42/43
42 Freedom to Choose. Power to Integrate.42 Freedom to Choose. Power to Integrate.
Benefits of Fieldbus in Commissioning
Faster installation and checkout due to reduced wiring
and bus structure
Faster device troubleshooting due to dedicated portable
fieldbus multimeter
Faster device commissioning due to dedicated fieldbus
diagnostic modules Avoids ranging problems
Avoids double-addressing and addressing in general
Reduces number of tools required for testing
Eliminates troublesome calibration procedures
All this and more leads to
significant faster project commissioning.
8/9/2019 FOUNDATION FIELDBUS Commissioning Benefits
http://slidepdf.com/reader/full/foundation-fieldbus-commissioning-benefits 43/43
Freedom to
Choose. Power to
Integrate.
www.fieldbus.org
www.fieldbus.org.sg