For: Assisted Living and Specialty Care Facilities (Alabama)
-
Upload
sophie-young -
Category
Documents
-
view
216 -
download
0
Transcript of For: Assisted Living and Specialty Care Facilities (Alabama)
ALABAMA STATE BOARD OF HEALTHAlabama Department of Public Health
(ADPH)Tech Services and/or State Fire Marshal
“Authority Having Jurisdiction”
Assisted LivingChapter 420-5-4
Specialty CareChapter 420-5-20
Rules and Governance
NFPA 101-Life Safety Code (2000)Congregate
Chapters 18/19“Health Care Occupancies (limited care)”
GroupChapters 32/33
“Residential Board and Care Occupancies, Impractical Evacuation Capability”
Family Chapter 24
“One and Two Family Dwellings”
Rules and Governance
NFPA “Systems” Compliance :NFPA 72 (1999)
National Fire Alarm CodeNFPA 25 (1998)
Sprinkler Systems Test/InspectionWater based systems
NFPA 13 (1999)Sprinkler Systems Installation
Rules and Governance
NFPA Continued:NFPA 17/17A & 96 (1998)
Range Hood Extinguishing SystemsVentilation Control/Extinguishment
NFPA 10 (1998)Portable Fire Extinguishers
NFPA 110 (1999)Standby and E-Power Systems
Rules and Governance
RED:420-5-4.12 (3s,t)/420-5-20-.12 (3s,t)
Sprinkler System FunctionPer NFPA 25 or BY RULE
Fire Alarm System FunctionPer NFPA 72 (1999) or BY RULE
Scoring System Deficiencies
YELLOW:420-5-4-.12(3o,r,s,t) 420-5-20-.12(3o,r,s,t) Failure to provide Fire Extinguishers
Failure to Inspect/Test:ExtinguishersSprinkler SystemsAlarm Systems
Scoring System Deficiencies
YELLOW:420-5-4-.11(1a)/420-5-20-.11(1a)
Evacuation PlanWritten PlanPosted Floor PlanRevision Effectiveness Observation
Documented…..Documentation=Fire Drills
One per month/Varying times and conditions
Employee participation/System functionActual evacuation AS requiredAfter hours drills
Scoring System Deficiencies
YELLOW:420-5-4-.12(3v)/420-5-20-.12(3v)
Properly Marked Exits/Paths of Egress
Actual Exit LocationsPath to Exit Location/Path of EgressLeading to “right of way”
Illuminated (Battery or E-power)
Both bulbs burning
Scoring System Deficiencies
An emergency action plan, which details what to do when a disaster or fire occurs.
A disaster/fire prevention plan which describes what to do to prevent a fire from occurring.
Preparedness Plan-Two Essential
Components
*These two components overlap and are inseparable.
Employers are required to review the emergency action plan with each employee at the following times:
when the plan is developed.when the employee’s responsibilities
or designated actions under the plan change.
whenever the plan changes.
Emergency Prep-Fire Plan
Eight/Nine Requirements of Fire Plan:Use of alarmsAuto-transmission of alarm to fire
departmentresponse to alarms
Emergency Call to Fire Department (2003)Isolation of fireEvacuation of immediate areaEvacuation of a smoke compartment Prep for floor and building evacuationExtinguishment of fire
Fire Plan (per NFPA 101 and ADPH )
Components of Fire Watch Plan1. Notification of Tech Services2. Notification of Staff3. Fire Watch Approval4. Acceptable Plan5. Fire Watch Activity/Assignment6. Fire Watch Log
Fire Watch
Fire watch:Where a required fire alarm system or sprinkler system is out of service for more than 4 hours in a 24-hour period, the authority having jurisdiction shall be notified (Alabama Dept. of Public Health- 334-206-5890), and the building shall be evacuated or an approved fire watch shall be provided for all parts of the facility left unprotected by the shutdown until the fire alarm system has been returned to service.
Fire Watch
Fire watch:A fire watch will include a fire watch plan
approved by the local fire official indicated on a letter from that said official indicating he or she is aware of the program and has approved the facilities response plan.
A log by the individual doing the fire watch
showing that the zones or areas of the facility under the watch has been checked every 15-30 minutes will be kept on site and a copy faxed to Tech Services every 4-6 hours until the problem is corrected.
Fire Watch
Fire watch:A fire watch should involve some
special action beyond normal staffing, such as assigning an additional security guard or maintenance person to walk the areas affected.
Individuals should be specially trained in fire prevention and in occupant and fire department notification techniques, and they should understand the particular fire safety situation for public education purposes
Fire Watch
Alarm System Functions:(For the purposes of the code, a complete fire alarm system shall be used for initiation, notification, and control and shall provide the following)
(1) Initiation. The initiation function provides the input signal to the system.
(2) Notification. The notification function is the means by which the system advises that human action is required in response to a particular situation.
Alarm Systems
Alarm systems:(3) Control. The control function provides outputs to control building equipment to enhance protection of life.
The loss of any one of these functions of a fire alarm system would require the need for a fire watch if the loss as for a period of 4 hours or more in a 24 hour period.
Alarm Systems
REFERENCES:
NFPA 101 2000 Edition sec. 9.6.1.8, Fire alarm system out of service
NFPA 101 2000 sec. 9.7.6.1, Sprinkler system shutdown
Fire Watch/Alarm Systems
Fire Drill Procedures:Fire drills in health care occupancies
shall include the transmission of a fire alarm signal and simulation of emergency fire conditions.
Drills shall be conducted at least once MONTHLY (Per Rule) at varying times, days and Quarterly on each shift of Group and Congregate facilities.
Fire Drills
Fire Drill Procedures:Requires initiation of fire alarm
system unless otherwise noted Drills may be announced in advance
to residentsDrills shall involve actual evacuation
of residents to assembly areas in adjacent smoke compartments or to exterior location
Fire Drills
Procedure in case of fire:When drills are conducted between
9:00pm (2100 hours) and 6:00am (0600 hours), a coded announcement shall be permitted to be used instead of audible alarms.
EXCEPTION: Infirm or bedridden patients shall
not be required to be moved during drills to safe
areas or to the exterior of the building.
Employees of health care occupancies shall be instructed in life safety procedures and devices.
Fire Drills
No requirement for Annual 90 minute run
No requirement for weekly 30 minute run
Monthly operation for 30 minutes under load
Run cannot include cool down
Emergency PowerRef: NFPA 110 Sec. 6-4
Battery Lighting Requirements: Monthly functional test for 30 secondsBattery lighting back-up for generator
Generator:Annual 90 minute test to include
documentation of the test and level of illumination upon completion.
Emergency Lighting Ref: NFPA 110 Sec. 7.9.3
D.A.C.T. (digital alarm communicator/transmitter)Note: Secondary audible signal
requirement
Battery backup
Complete System Test EVERY month
Fire Drill vs. Alarm System Test
Alarm SystemsRef: NFPA 72
Types of Portable ExtinguishersABC
Universal TypeK
Kitchen Applications
Access to extinguishersTravel no more than 75 feet in any
directionAccess clear of ALL obstructions
Portable Fire ExtinguishersRef. NFPA 10
Types:Re-circulatingExterior vent
Inspection/Tests:Per NFPA 96 and Facility ApplicationTypically not to exceed 180 days
Cleaning:Twice per year, ORAs required per inspection documents
Kitchen Range Hood & Duct System
Ref. NFPA 96
1. Smoking prohibited in any room, ward, or compartment where flammable liquids, combustible gases or oxygen is used or stored and in any other hazardous location. All such areas shall be posted with NO SMOKING signs.2. Smoking by residents classified as not responsible is prohibited unless directly supervised.3. Ashtrays of non-combustible material and safe design shall be provided in all areas where smoking is permitted.4. A metal container/device with self-closing cover intended only for emptying ashtrays shall be readily available to all areas where smoking is permitted.
Smoking Policies & ProceduresRef. NFPA 101 19.7.4
Applicable Systems (vary per facility license)Alarm Systems
FORM 72-101 (2002 Edition)4 page handout
Sprinkler SystemsExhaust/Range HoodFire Extinguishing Equipment
VERIFY Completeness of ALL Forms (yes, no, n/a)
Contracted Tests/Inspections
Recommended References:Compressed Gas Association
(CGA)Publications for Handling, Trans-
filling, Storage, Labeling, Etc.NFPA 99 (1999) Standard For
Health Care FacilitiesStorage Requirements
Chapter 8 <3000cfChapter 4 >3000cf
Oxygen Storage/Handling
Basic Oxygen Info:Colorless, Odorless, Tasteless GasNOT Flammable….But Enriches
Atmosphere (saturates linens, clothes, etc.)
Liquid O2 release can cause frostbite and/or cryogenic burns
Contents (Liquid & Gas) under pressure
Avoid Trans-filling if Possible
Oxygen Storage/Handling
Overview of Oxygen Rules:Employees and Residents must be
properly trained on hazards and safety
Operate equipment per manufacturer and/or supplier instruction
Maintain Policy for storage and handling of Oxygen products
Posting of Non-smoking signs required (where applicable)
Oxygen Storage/Handling
Overview of Oxygen Rules :Limit repairs of equipment to
manufacturers and suppliersLimit storage quantities per “NFPA
99”Never store: Near Electrical,
Excessive Heat, Unsecured, Horizontal, Confined or Unventilated Areas
Oxygen Storage/Handling