Fire Safety Security Products MXL / MXLV ASC-1 from Siemens Industry ... EL-410D amplifier output....

2
Amplifier Supervisory Cards 5020 s Industry, Inc. Building Technologies Division s Data Sheet Fire Safety & Security Products MXL / MXLV Amplifier Supervisory Cards Models ASC-1 and ASC-2 ARCHITECT AND ENGINEER SPECIFICATIONS Product Overview Product Overview Model ASC-1: Model ASC-2: Model ASC-1 from Siemens Industry Fire Safety is a MXLV card that plugs into one (1) slot of the Model OMM- 1 or Model OMM-2 card cage. Model ASC-1 supervises the output of up to three (3) primary amplifiers, as well as to one (1) optional backup amplifier. The amplifiers may be on same or different audio channels. One (1) Model ASC-1 is required for each three (3) primary amplifiers even if no backup amplifiers are being used. Model ASC-1 monitors and compares the channel-riser output on Model OMM-1 and Model OMM-2 to the Model EL-410D amplifier output. If Model ASC-1 determines the output of any primary amplifier is incorrect, it will automatically transfer operation to the backup amplifier. The backup amplifier may be shared by multiple Model ASC-1 cards, providing the ability to determine the primary-to-backup ratio. If preferred, backup amplification can be provided on a one-for-one basis, using one (1) Model ASC-1 for each primary / backup amplifier set. Each Model ASC-1 occupies one (1) Model OCC-1 sub- address. The address is set using an on-board DIP switch. A second DIP switch is provided for configuration of Model ASC-1. Connections between the amplifiers, audio-riser busses and to Model ASC-1 are made through the appropriate Models OMM-1 and OMM-2 screw terminals. Model ASC-2 from Siemens Industry Fire Safety is a MXLV card that plugs into one (1) slot of the Model OMM- 1 or Model OMM-2 card cage, supervising the output of one (1) primary amplifier, as well as one (1) optional backup amplifier. One (1) Model ASC-2 is required for each primary amplifier, whenever a high-power audio riser is to be connected to Model ICP Control modules, or to Model ZC Zone cards in remote enclosures, even if no backup amplifiers are being used. Model ASC-2 monitors and compares the channel-riser output on Models OMM-1 and Model OMM-2 to the Model EL-410D amplifier output. If Model ASC-2 determines the output of any primary amplifier is incorrect, Model ASC-2 will automatically transfer operation to the backup amplifier. The backup amplifier may be shared by multiple Model ASC-2 cards, providing the ability to determine the primary-to-backup ratio. If desired, backup amplification can be provided on a one-for-one basis, using one (1) Model ASC-2 for each primary / backup amplifier set. Each Model ASC-2 occupies one (1) Model OCC-1 sub- address. The address is set using an on-board DIP switch. A second DIP switch is provided for audio configuration of Model ASC-2. Connections between the amplifiers, audio-riser busses and Model ASC-2 are made through the appropriate Model OMM-1 and Model OMM-2 screw terminals. Plugs into Models OMM-1 and OMM-2 card cage Amplifier input / output supervision Variable backup-amplifier ratio Automatic transfer-to-backup amplifier UL 864 9th Edition Listed, ULC Listed; CSFM, NYMEA and City of Chicago Approved (713)-395-1508 Fax: (713) 893-6924 [email protected] www.industrialzone.com IndustrialZone P.O. Box 667306 Houston, Texas 77266 United States

Transcript of Fire Safety Security Products MXL / MXLV ASC-1 from Siemens Industry ... EL-410D amplifier output....

Amplifier Supervisory Cards 5020 s Industry, Inc. Building Technologies Division

s Data Sheet 

Fire Safety & Security Products 

MXL / MXLV Amplifier Supervisory Cards Models ASC-1 and ASC-2

ARCHITECT AND ENGINEER SPECIFICATIONS

Product Overview Product Overview Model ASC-1: Model ASC-2:Model ASC-1 from Siemens Industry – Fire Safety is a MXLV card that plugs into one (1) slot of the Model OMM-1 or Model OMM-2 card cage. Model ASC-1 supervises the output of up to three (3) primary amplifiers, as well as to one (1) optional backup amplifier. The amplifiers may be on same or different audio channels.

One (1) Model ASC-1 is required for each three (3) primary amplifiers − even if no backup amplifiers are being used.

Model ASC-1 monitors and compares the channel-riser output on Model OMM-1 and Model OMM-2 to the Model EL-410D amplifier output. If Model ASC-1 determines the output of any primary amplifier is incorrect, it will automatically transfer operation to the backup amplifier. The backup amplifier may be shared by multiple Model ASC-1 cards, providing the ability to determine the primary-to-backup ratio. If preferred, backup amplification can be provided on a one-for-one basis, using one (1) Model ASC-1 for each primary / backup amplifier set.

Each Model ASC-1 occupies one (1) Model OCC-1 sub-address. The address is set using an on-board DIP switch. A second DIP switch is provided for configuration of Model ASC-1.

Connections between the amplifiers, audio-riser busses and to Model ASC-1 are made through the appropriate Models OMM-1 and OMM-2 screw terminals. Model ASC-2 from Siemens Industry – Fire Safety is a

MXLV card that plugs into one (1) slot of the Model OMM-1 or Model OMM-2 card cage, supervising the output of one (1) primary amplifier, as well as one (1) optional backup amplifier.

One (1) Model ASC-2 is required for each primary amplifier, whenever a high-power audio riser is to be connected to Model ICP Control modules, or to Model ZC Zone cards in remote enclosures, even if no backup amplifiers are being used.

Model ASC-2 monitors and compares the channel-riser output on Models OMM-1 and Model OMM-2 to the Model EL-410D amplifier output. If Model ASC-2 determines the output of any primary amplifier is incorrect, Model ASC-2 will automatically transfer operation to the backup amplifier.

The backup amplifier may be shared by multiple Model ASC-2 cards, providing the ability to determine the primary-to-backup ratio. If desired, backup amplification can be provided on a one-for-one basis, using one (1) Model ASC-2 for each primary / backup amplifier set.

Each Model ASC-2 occupies one (1) Model OCC-1 sub-address. The address is set using an on-board DIP switch. A second DIP switch is provided for audio configuration of Model ASC-2.

Connections between the amplifiers, audio-riser busses and Model ASC-2 are made through the appropriate Model OMM-1 and Model OMM-2 screw terminals.

• Plugs into Models OMM-1 and OMM-2 card cage

• Amplifier input / output supervision

• Variable backup-amplifier ratio

• Automatic transfer-to-backup amplifier

• UL 864 9th Edition Listed, ULC Listed; CSFM, NYMEA and City of Chicago Approved

(713)-395-1508Fax: (713) [email protected]

IndustrialZoneP.O. Box 667306Houston, Texas 77266United States

s Industry, Inc. Building Technologies Division

Fire Safety 8 Fernwood Road Florham Park, NJ 07932 Tel: (973) 593-2600 FAX: (908) 547-6877 URL: www.SBT.Siemens.com/FIS

(SII‐FS) Printed in U.S.A.

 

Fire Safety 2 Kenview Boulevard Brampton, Ontario L6T 5E4 / Canada Tel: (905) 799-9937 FAX: (905) 799-9858

March 2011 Supersedes sheet dated 6/03

(Rev.1)

Electrical Ratings Models ASC-1 / ASC-2:

25VRMS, 100 Watts High-Level Outputs:

70.7VRMS, 100 Watts

Backup-Amp. Input: 1VRMS

Installation and Operation Manual [IOM]

Model Number

Part Number

Description

ASC-1 315-091263 Amplifier Supervisory Card

ASC-2 315-092085 Amplifier Supervisory Card

Note: For further details, refer to MXLV IOM manual: 315-092036.

Related Documentation Product Data Sheet Number

MXLV 5035

EL-410 3393

 

Temperature and Humidity Range Products are UL 864 9th Edition Listed for indoor dry locations within a temperature range of 120+/-3°F (49+/-2°C) to 32+/-3°F (0+/-2°C) and a relative humidity of 93+/-2% at a temperature of 90+/-3°F (32+/-2°C).

Details for Ordering Model

Number Part

Number Description

ASC-1 500-891187 Amplifier Supervisory Card

ASC-2 500-892084 Amplifier Supervisory Card

Speaker-Zone Decibel Losses

Gauge @ 25VRMS [Loss, in decibels]

Length [in ft.]

14 AWG 16 AWG 18 AWG

200 0.2 0.3 0.6

400 0.5 0.7 1.1

600 0.7 1.1 1.6

800 0.9 1.5 2.2

1000 1.2 1.8 2.7

Notice: This marketing data sheet is not intended to be used for system design or installation purposes. For the most up-to-date information, refer to each product’s installation instructions.

Gauge @ 70VRMS [Loss, in decibels]

Length [in ft.]

16 AWG 18 AWG

200 0.04 0.06

400 0.07 0.11

600 0.11 0.17

800 0.14 0.22

(713)-395-1508Fax: (713) [email protected]