MXL MANUAL.pdf

download MXL MANUAL.pdf

of 52

Transcript of MXL MANUAL.pdf

  • US Coast Guard ApprovedCertificate No. (Cert No:161.002/22/7)

    Marine Fire DetectionSystem Manual

    MXL Control Panel

    Reference

    ULI File No. S522

    P/N 315-092382-6

    Fire Safety8 Fernwood RoadFlorham Park, NJ 07932

    Siemens Building Technologies, Inc.Phone (973) 593-2600Fax (973) 593-6612www.sbt.siemens.com/fis

  • iTable Of Contents

    I DESCRIPTION OF THE MXL MARINE CONTROL PANEL ................................................1

    Introduction .....................................................................................................................1

    Equipment Location ........................................................................................................2

    Software ...........................................................................................................................2

    Minimum MXL Control Panel Configuration .................................................................2

    Components of the Basic System ................................................................................. 5

    MMB-2 Main Board .......................................................................................................5

    MPS-6 Power Supply ....................................................................................................6

    MPS-12 Power Supply ..................................................................................................6

    MKB-1 Keyboard/Annunciator Panel .............................................................................6

    TSP-40 Logging Printer ................................................................................................. 7

    TSW-2 Tamper Switch ...................................................................................................7

    BP-61 Batteries ............................................................................................................. 7

    BTX Batteries ................................................................................................................7

    Optional Modules ............................................................................................................ 8

    MOM-4 Card Cage ........................................................................................................8

    MOM-2 Card Cage ........................................................................................................8

    CSM-4 Signal Module ...................................................................................................9

    CRM-4 Relay Module ....................................................................................................9

    CZM-4 Conventional Zone Module ...............................................................................9

    ALD-2I Analog Loop Driver ............................................................................................9

    PSR-1 Remote Power Supply .....................................................................................10

    NET-4 Communication Interface .................................................................................10

    NET-7 Communication Interface ................................................................................. 11

    MOI-7 Voice and Annunciator Driver ........................................................................... 11

    MOD-16 Output Driver................................................................................................. 11

    MID-16 Input Driver ..................................................................................................... 11

    PIM-1 Peripheral Interface Module ..............................................................................12

    CZM-1B6 Remote Conventional Zone Module............................................................12

    LIM-1 Loop Isolator Module .........................................................................................12

    Intelligent/Analog Devices ............................................................................................ 13

    FP-11 Intelligent/Analog Photoelectric Detector ..........................................................13

    FPT-11 Intelligent Thermal Detector ............................................................................13

    ILP-1 Intelligent/Analog Photoelectric Detector ...........................................................13

    ILPT-1 Intelligent/Analog Photoelectric Detector with Heat Sensor ............................13

    ILI-1 Intelligent/Analog Ionization Detector ..................................................................13

    ILI-1H Intelligent/Analog Ionization High Altitude Detector ..........................................13

    ILI-1A Intelligent/Analog Ionization High Air-Velocity Detector ....................................13

    ILI-1A Intelligent/Analog Ionization High Air-Velocity, High Velocity Detector ..............13

    ILI-1AH Intelligent/Analog Ionization High Air Velocity, High Altitude Detector ............14

    ILI-1B Intelligent/Analog Ionization Air-Duct Detector .................................................14

    ILI-1BH Intelligent/Analog Ionization Air-Duct High Altitude Detector ..........................14

    MSI-10B/20B Intelligent Manual Station ......................................................................14

    MSI-B6F Intelligent Manual Station .............................................................................14

    TRI-B6M Intelligent Interface Module ..........................................................................14

  • ii

    Conventional Devices ................................................................................................... 14

    DI-3 Ionization Detector ...............................................................................................14

    DI-3H Ionization High Altitude Detector .......................................................................14

    DI-A3 Ionization High Air-Velocity Detector .................................................................14

    DI-A3H Ionization High Air-Velocity, High Altitude Detector.........................................15

    DI-B3 Ionization Air Duct Detector ...............................................................................15

    DI-B3H Ionization Air Duct High Altitude Detector .......................................................15

    DT-11 Thermal Detector ..............................................................................................15

    DT-C Series .................................................................................................................15

    DT-135/200 WP ...........................................................................................................15

    DT-140/190 EP ............................................................................................................15

    PE-11 Photoelectric Detector ......................................................................................15

    PE-11T Photoelectric Detector with Heat Sensor ........................................................15

    DB-SEAL and DB-11 SEAL .........................................................................................16

    II POWER REQUIREMENTS ................................................................................................. 17

    Power Transfer Relay ......................................................................................................18

    III AUDIBLE ALARMS ............................................................................................................ 19

    Alarm Locations and Requirements ................................................................................19

    IV INITIATING DEVICESMANUAL ...................................................................................... 20

    V REMOTE ANNUNCIATION................................................................................................. 20

    Remote Annunciators ......................................................................................................20

    VI DETECTOR APPLICATION AND SPACING ...................................................................... 21

    1. Smoke Detectors .........................................................................................................21

    2. Thermal Detectors .......................................................................................................21

    3. Planning A Fire Detection System ...............................................................................22

    4. Detector Installation .....................................................................................................25

    VII ENCLOSURES ...................................................................................................................26

    1. Shock Mounting for Enclosures ...................................................................................26

    2. Installation ...................................................................................................................26

    VIII WIRING SPECIFICATIONS ................................................................................................ 32

    1. ALD Loop Configuration Guide ....................................................................................32

    2. Wiring Specification for MXL .......................................................................................34

    US COAST GUARD APPROVED EQUIPMENT LIST .......................................................... 37-44

    COAST GUARD TYPICAL MXL CONNECTION DIAGRAM ................................................. 45-47

  • 1INTRODUCTION

    This manual contains information regarding

    MXL equipment and detectors that are US

    Coast Guard approved. The use of any other

    equipment in systems required by US Coast

    Guard regulations, but not US Coast Guard

    approved, should only be considered when

    absolutely necessary. Special US Coast

    Guard one-time approval would be required.

    NOTE: When designing Fire Control

    Systems for various types of vessels, the

    designer should be aware of the required

    vessel type, domestic and SOLAS regula-

    tions applicable for that vessel.

    The MXL Control Panel from Siemens

    Building Technologies, Inc. is an advanced

    fire protection and alarm control panel that

    provides superior fire protection and multi-

    plexed alarm reporting. Its use of unique

    multi-processor network design along with

    its ability to utilize both analog and conven-

    tional detection devices, make it the out-

    standing control unit in the life safety field.

    Regardless of the size or complexity of the

    life safety and security system require-

    ments, the MXL system can be used for the

    smallest to the largest applications.

    The MXL is ideally suited for Marine, institu-

    tional and industrial fire and security appli-

    cations.

    The MXL Control Panel can process logical

    decisions based on the status of initiating

    devices. The system will also respond to

    specified sequences of output circuit operation.

    The MXL Control Panel is capable of read-

    ing and displaying the sensitivity of remote

    intelligent/analog ionization and photoelecric

    detection devices at the control panel.

    The system complies with the requirements

    of NFPA 72 and NFPA13. It is Underwriters

    Laboratory 864 and 1076 security listed.

    The basic MXL Control Panel can monitor

    up to 2 analog loops, each containing up to

    60 intelligent devices. Through the addition

    of a MOM-4 card cage, the System can be

    expanded to as many as 6 analog loops.

    (With the addition of PSR-1 power supplies,

    the System can be expanded to as many as

    34 analog loops.)

    The MXL Control Panel can control a wide

    variety of System outputs, such as conven-

    tional Form C relay contacts, solid state

    outputs, supervised outputs to control alarm

    notification appliances, municipal tie out-

    puts, and leased line outputs.

    The MXL Control Panel can process logical

    decisions based on the status of initiating

    devices. The System can respond with

    customer-specified sequences of output

    circuit operation.

    The System continuously checks all soft-

    ware and hardware for proper operation. It

    continuously checks all System memory

    components, control panel electronic hard-

    ware, and the System program. A hardwire

    watchdog circuit is provided to ensure that

    System programs are functioning properly. If

    I. Description of the MXL

    Marine Control Panel

  • 2a problem develops with the program or

    processor, the watchdog circuit places the

    System into a trouble condition and resets it.

    To ensure reliable operation, the MXL

    System is composed of independent mod-

    ules, each with its own microprocessor. If

    the main panels central processing unit

    stops, these modules, operating in degrade,

    still annunciate any alarm or trouble through

    common lines called Any Alarm and Any

    Trouble. All of the modules communicate

    with the MXL Panel through a serial com-

    munications system.

    All modules are continuously supervised for

    their presence and for proper operation.

    Problems are shown on the display to aid in

    servicing and troubleshooting.

    The MXL System is designed so that fire

    alarm operation has first priority over all

    other modes of operation. If the System

    loses battery and commercial power, it

    automatically goes through an initialization

    routine when power is returned.

    EQUIPMENT LOCATION

    MXL System equipment shall not be installed

    in locations that require an exceptional

    degree of protection such as those that are

    exposed to weather, seas, splashing,

    pressure-directed liquids or similar moisture

    conditions. These locations include:

    1. On deck

    2. A machinery space

    3. A cargo space

    4. A location within a galley or pantry area,

    laundry or water closet which contains a

    shower or bath; and

    5. Other spaces with similar environmental

    conditions.

    SOFTWARE

    The MXL software was written in a high

    level language for ease of maintenance.

    The software incorporates a multitasking

    operating system that allows the micropro-

    cessor to handle many tasks almost simulta-

    neously. This enables the MXL System to

    handle communications to all initiating and

    output option boards and to the annunciator.

    This also enables the MXL System to check

    that everything is running.

    When the MXL Control Panel receives

    power, the System runs a start-up proce-

    dure that sets up all initial conditions. The

    System then starts the operating system

    and the initialization routines for all of the

    tasks, most of which concern handling

    System modules. When the display task is

    finished initializing, it displays the default

    time and date at powerup. Initialization of

    other modules may take several seconds,

    but this takes place in the background and

    so does not affect System operation.

    The MXL System polls all network addresses

    to see that all specified modules are present

    and that there are no unspecified modules.

    Any modules or devices that do not agree with

    the programmed data are reported as

    troubles on the annunciator.

    MINIMUM MXL CONTROL PANEL

    CONFIGURATION TO MEET NFPA 72,

    UL 1076 AND NFPA 13

    Table 1 presents the minimum MXL System

    configuration necessary to meet NFPA 72,

    UL 1076 and NFPA 13 requirements.

    Description of the MXL Control Panel

  • 31ELBAT31APFNDNA6701LU,27APFNTEEMOTNOITARUGIFNOCLXMMUMINIM

    ytitnauQmuminiMAPFN

    eludoM noitpircseD 27LU6701 b 31

    2-BMM a tinUniaMLXM 1 1 16-SPM ylppuSrewoP 1 1 121-SPM ylppuSrewoP 1 1 1

    1-BKM lenaProtaicnunnA/draobyeK 1 1 104-PST retnirPgniggoL X 1 X4-MOM egaCdraCeludoMlanoitpO X 1c X4-MSC eludoMlangiS * X 1d

    4-MZC eludoMenoZlanoitnevnoC ** X **I2-DLA revirDpooLgolanA ** *** **

    6B1-MZC eludoMenoZlanoitnevnoCetomeR ** X **--- seirettaB f 1e 1e 1e

    2-WST hctiwSrepmaT X 1c X1-RSP ylppuSrewoPetomeR X Xg X

    deriuqerton=X

    * For NFPA 72 Remote Station applications, one CSM-4 circuit must be configured

    for alarm transmission. In addition, depending on the local authority having

    jurisdiction, additional circuits may be required for Supervisory or Trouble

    transmission. For NFPA 72 Auxiliary applications, one CSM-4 is required. For

    other NFPA 72 applications, the CSM-4 is optional.

    ** Any one of these modules is sufficient as an initiating device.

    *** Only TRI-B6 / TRI-S, TRI-B6R / TRI-R, and TRI-B6D / TRI-D can be used as

    security initiating devices.

    NOTES:

    a. The MMB-2 must be programmed by the CSG-Mfor all System configurations. (See CSG-MProgramming Manual, P/N 315-090381).

    b. Refer to System wiring Diagram in this manual.

    c. UL 1076 requires a Model TSW-2 tamper switchand a TSP-40 printer.

    d. Refer to the CSM-4 installation instructions (P/N315-090854) for programming.

    e. The batteries available are BP-61, BTX-1 andBTX-2. The BP-61 is a module consisting of two12V, 15 AH batteries. The BTX-1 batteries are apair of 12V, 31 AH batteries. The BTX-2 are apair of 12V, 55 AH batteries. Actual battery sizedepends on System Configuration.

    f. See Appendix C in the MXL Manual, P/N 315-092036 for Battery Calculations.

    g. The PSR-1 is not listed for security.

    Description of the MXL Control Panel

  • 4Description of the MXL Control Panel

    TB4

    TB5TB

    3TB

    1TB

    2

    P1

    P2P3

    SILENCE

    ALT2

    1ALT

    RESET

    ACKSEC

    ACKTRBL

    ACKSUPV

    SILAUD

    ACKALARM

    HOLDNEXTDISPLAY

    DISABLESYSTEMPARTIAL

    POWER

    SECURITY

    TROUBLE

    SUPERVISORY

    AUDIBLE

    ALARM

    ALT 2ALT 1FUNCTIONFUNCTIONFUNCTION

    F4

    F3

    F2

    F1

    FEEDFORM

    HELP

    PRINT

    CLEARENTER0

    9

    65

    87

    4

    321

    SIEMENS BUILDING TECHNOLOGIESMXL

    MPS-6OR

    MPS-12

    MOM-4(Optional #1)

    MMB-2(Main Board)

    MKB-1

    BATTERIES

    MOM-4(Optional #2)

    MOM-4(Optional #3)

    Figure 1

    The Basic MXL Control Panel

  • 5Description of the MXL Control Panel

    COMPONENTS OF THE BASIC

    SYSTEM

    The basic MXL Control Panel consists of the

    following components:

    MMB-2 Main Board

    MPS-6 or MPS-12 Power Supply

    MKB-1 Keyboard/Annunciator

    TSP-40 Logging Printer (NFPA 72

    Proprietary and UL 1076 configurations)

    MME-3-CG Enclosure

    TSW-2 Tamper Switch (UL 1076 configu-

    ration only)

    BP-61, BTX-1 or BTX-2 Batteries

    MMB-2 Main Board

    The MMB-2 Main Board contains:

    16-bit central processing unit (CPU)

    System read-only memories (EPROMs)

    System random-access memory (RAM)

    FLASH memory for the CSG-M

    Watchdog circuitry

    Network interface circuitry

    Battery charger

    24V regulator

    AC transfer relay

    Class A CZM-1 power

    24 VDC unregulated supply

    Two analog loops (initiating/control)

    Two notification appliance circuits (au-

    dible/visual circuits)

    Three dry-contact relays

    Figure 2

    MMB-2 Main Board

    CB1NAC1

    P14P1F2 BATTERY

    20A

    P2BATTERY

    MPS-6 MPS-12

    F3 CZM-1 POWER

    2 AMP

    CB2NAC2

    10

    11

    12

    CZM-1POWER1

    P8

    TB3

    P3POWER TO MOM-42 AMP MAX.

    3

    4

    4

    1

    2LOOP 2

    NAC 2

    NAC 1

    6

    6

    7

    7

    8

    8

    9

    9

    1

    1

    2

    2

    3

    3

    4

    4

    5

    5

    TO ANN-1P13

    P16

    (MXL Rev. 9and higher)

    GND FAULTDISCONNECT

    (MXL Rev. 8and lower)

    TB2

    LOOP 11

    2

    3

    5

    1

    2

    3

    412A TO MOM-4

    DO NOT USE

    MNETSPV

    TRBL

    TAMPERSWITCH

    P7

    11

    IC204

    IC110

    IC111

    IC203

    IC112

    IC113

    64K

    32K

    IC114

    IC115

    TB1

    PROGRAMMER

    P5

    S7S4

    P15

    OFF ONP17

    1P10

    D2300CP PRINTER

    1P4

    MOM-41

    P61 1 1 1 1 1

    1EXPANSION

    ALR

    F1MPS-68 AMP

    F4MOM-415 AMP

    MMB-2

  • 6Description of the MXL Control Panel

    Figure 4

    MKB-1 Keyboard/Annunciator

    TO P8 OF MMB-2

    MPS-6 Power Supply

    The MPS-6 is a supervised power supply

    that converts 120 VAC, 60 Hz to unregu-

    lated 24 VDC at 6A.

    MPS-12 Power Supply

    The MPS-12 is a high current power supply

    that provides the MXL System with primary

    24 VDC power. It is rated at 12 amps and is

    unfiltered and unregulated. The MPS-12

    supplies the MMB-2 or PSR-1 and its

    expansion modules with the power required

    for normal operation. The module incorpo-

    rated a 5 amp resettable circuit breaker on

    the primary input, a 15 amp fuse on the 24V

    output, and a built-in AC line filter for surge

    and noise suppression. The MPS-12

    mounts in the MXL enclosure backbox.

    MKB-1 Keyboard/Annunciator Panel

    The MKB-1 Keyboard/Annunciator Panel is

    the annunciator and manual control panel

    for the MXL. It includes the 2-line, 80-

    character alphanumeric display that annun-

    ciates alarms, supervisories, troubles,

    security conditions, and maintenance

    information. The Control Panel also contains

    the following indicators:

    Alarm

    Power

    Supervisory

    Trouble

    Security

    Audibles Silenced

    Partial System Disabled

    A keypad provides the following keys:

    ACKnowledge keys

    AUD SIL (Audible Silence)

    RESET

    NEXT Display

    Figure 3

    MPS-6 and MPS-12 Power Supply

  • 7Description of the MXL Control Panel

    Figure 6

    TSW-2 Tamper Switch

    Figure 5

    TSP-40 Logging Printer

    Figure 7

    BP-61 and BTX Batteries

    HOLD Display

    Numeric keys

    Cursor control keys for data entry and

    menu operation

    PRINT, HELP, and CLEAR keys

    User-configurable function keys

    TSP-40 Logging Printer

    The TSP-40 Logging Printer is installed in the

    MXL backbox and provides a paper record of

    the activity of the System.

    TSW-2 Tamper Switch

    The TSW-2 Tamper Switch (Figure 6) below

    is a 3-position switch that monitors the open-

    ing of the MXL enclosure and reports a

    security condition. Closing the door automati-

    cally returns the switch to its normal operating

    position. The switch can be pulled out to

    indicate a closed position for maintenance

    purposes.

    BP-61 Batteries

    The BP-61 is a module consisting of two 12V,

    15 AH batteries. The BP-61 is recommended

    for the NFPA 72 Local and 72 Proprietary and

    the UL 1076 Systems. Actual battery size

    depends on System configuration. See

    Appendix C- Battery Calculations in the

    MXL Manual, P/N 315-092036.

    BTX Batteries

    The BTX-1 batteries are a pair of 12V, 31 AH

    batteries. The BTX-2 batteries are a pair of

    12V, 55 AH batteries. Actual battery size

    depends on System configuration. See Ap-

    pendix C - Battery Calculations in the MXL

    Manual, P/N 315-092036.

  • 8Description of the MXL Control Panel

    OPTIONAL MODULES

    The following modules are available as

    options to the MXL Control Panel:

    MOM-4 Card Cage

    MOM-2 Card Cage

    CSM-4 Signal Module

    CRM-4 Relay Module

    CZM-4 Conventional Zone Module

    ALD-2I Analog Loop Driver

    PSR-1 Remote Power Supply

    NET-4/-7 Communication Interface

    MOI-7 Voice and Annunciator Driver

    MOD-16 Output Driver

    MID-16 Input Driver

    PIM-1 Peripheral Interface Module

    CZM-1B6 Conventional Zone Module

    LIM-1 Loop Isolator Module

    MOM-4 Card Cage

    The MOM-4 Card Cage (Figure 8) below

    contains four slots for optional module cards;

    it can handle four half-width cards or two full-

    width cards. The MOM-4 provides two power

    connector receptacles and two data connec-

    tor receptacles. A 24 VDC cable that pro-

    vides the main power used by the optional

    modules and an 8-wire ribbon cable for

    connection of 5 VDC and data are provided

    with the MOM-4 installation kit.

    A System can include as many as three

    MOM-4s in the backbox. If you install three

    MOM-4s in a backbox, you cannot install a

    TSP-40 printer in that backbox.

    MOM-2 Card Cage

    The MOM-2 Card Cage contains two slots for

    optional module cards; it can handle two half-

    width cards or one full-width card. The MOM-2

    provides two power connector receptacles

    and two data connector receptacles. A 24

    VDC cable that provides the main power used

    by the optional modules and an 8-wire ribbon

    cable for connection of 5 VDC and data are

    provided with the MOM-2 installation kit.

    Figure 8

    MOM-4 Card Cage

    Figure 9

    MOM-2 Card Cage

  • 9Description of the MXL Control Panel

    Figure 10

    CSM-4 Signal Module Card

    Figure 11

    CRM-4 Relay Module Card

    CSM-4 Signal Module

    The CSM-4 Signal module (Figure 10) controls

    two supervised notification appliance circuits.

    Each circuit is capable of either Style Z (Class

    A) or Style Y (Class B) operation. Each circuit

    can be individually configured for notification

    appliances, municipal tie or leased line.

    CRM-4 Relay Module

    The CRM-4 Relay module (Figure11) is an

    output control module that contains four relay

    outputs. Form C contacts are rated at

    2A, 30 VDC/120 VAC resistive.

    CZM-4 Conventional Zone Module

    The CZM-4 Conventional Zone module

    provides four initiating device circuits capable

    of Style D (Class A) or Style B (Class B)

    operation. Each zone supports up to thirty

    two-wire detectors or an unlimited number of

    shorting devices. Each zone has its own

    address. You can use the CSG-M to write a

    custom message for each zone (See the

    CSG-M Programming Manual, P/N 315-

    090381).

    ALD-2I Analog Loop Driver

    The ALD-2I Analog Loop Driver provides two

    signaling line circuits capable of Style 6

    (Class A) or Style 4 (Class B) operation for

    monitoring analog devices. Each loop is

    capable of monitoring up to 60 analog de-

    vices. Each device has its own address. You

    can use the CSG-M to write a custom mes-

    sage for each device (See the CSG-M Pro-

    gramming Manual, P/N 315-090381).

    Figure 12

    CZM-4 Conventional Zone Module Card

    Figure 13

    ALD-2I Analog Loop Driver

  • 10

    Figure 14

    PSR-1 Remote Power Supply

    Figure 15

    NET-4 Board

    Description of the MXL Control Panel

    PSR-1 Remote Power Supply

    The PSR-1 module is a microprocessor

    controlled remote power supply and battery

    charger. This module allows the basic MXL

    System to expand to more than 2000 points.

    It operates with an MPS-6 or an MPS-12 to

    provide 6 or 12 amps of power for various

    MXL modules.

    The PSR-1 module:

    1. Acts as an interface between remote

    option modules and the MXL when used

    with a NET-4 or NET-7 plug-in

    communication module.

    2. Can be used to power an MOI/MOD

    annunciator driver set.

    3. Can be used as an auxiliary power supply

    in a stand-alone mode without an MXL.

    There are nine status indicators on the PSR-1

    (Refer to Figure 14). There are also two

    relays used for common alarm and common

    trouble or, if programmed, for local alarm and

    local trouble.

    NET-4 Communication Interface

    The NET-4 provides the communication

    interface between remote PSR-1 panels and

    the main MXL. Each NET-4 connected

    represents one network drop on the MXL

    System. You can have up to 32 network

    drops, including the MMB-2.

    The NET-4 installs into the PSR-1 module

    which provides all necessary power to the

    NET-4. There are no configuration switches or

    jumpers on the NET-4. (See Figure 15.)

  • 11

    NET-7 Communication Interface

    The NET-7 module provides a Style 7

    communication interface between the main

    MXL and multiple remote panels in an MXL

    System. Each NET-7, except the NET-7

    connected to the MMB, electrically isolates

    the pairs from the local power supply and

    isolates ground faults to a single remote

    panel. The MMB provides ground fault

    detection for the two pairs.

    Each NET-7 connected represents one

    network drop on the MXL System. There

    can be a maximum of 32 drops including the

    MMB. The NET-7 has a network address

    which must be set on the module and

    installed into the CSG-M network map.

    The NET-7 offers advanced performance

    over the NET-4. NET-7s and NET-4s

    cannot be combined in the same system.

    MOI-7 Voice and Annunciator Driver

    The MOI-7 is an MXL network module that

    connects to a graphic annunciator using

    MOD-16s and MID-16s. The MOI-7 can be

    connected to either Style 4 or Style 7 wiring.

    MOD-16 Output Driver

    The MOD-16 Output Driver module is a

    graphic annunciator driver controlled by the

    MOI-7 module. Up to eight MOD-16s can be

    used with an MOI-7. Each MOD-16 can

    activate up to 16 outputs for a total of 128

    outputs.

    MID-16 Input Driver

    The MID-16 Input Driver provides 16 gen-

    eral purpose inputs for user-defined opera-

    tions for the MXL. The MID-16 is controlled

    by the MOI-7 module. Up to eight MID-16s

    can be used with an MOI-7. The function of

    each individual input is defined by the usage

    assigned to it in the CSG-M.

    Figure 16

    NET-7 Board

    Figure 17

    MOI-7 Voice and Annunciator Driver

    Figure 18

    MOD-16 Output Driver

    Description of the MXL Control Panel

    Figure 19

    MID-16 Input Driver

  • 12

    PIM-1 Peripheral Interface Module

    The PIM-1 module is an interface for an

    MXL System to remote peripheral devices

    such as printers, VDTs and CRTs. It con-

    nects an RS-232C device or CRT to an MXL

    System without the peripheral device's

    protective ground causing a ground fault.

    The interface operates at up to 9600 baud

    without losing any characters.

    CZM-1B6 Remote Conventional Zone

    Module

    The CZM-1B6 is an MXL intelligent device

    that connects a single zone of conventional

    devices to an analog loop. The CZM-1B6 can

    power up to 15 compatible two-wire, ioniza-

    tion or photoelectric smoke detectors. It can

    also monitor an unlimited number of shorting

    devices such as waterflow switches, thermal

    detectors, manual stations, etc.

    Each CZM-1B6 can be assigned a

    32-character custom alphanumeric message.

    It also includes an alarm indicator LED

    which is visible through the cover plate.

    The CZM-1B6 supports Style D (Class A)

    and Style B (Class B) wiring. The module

    uses one address on the analog circuit.

    LIM-1 Loop Isolator Module

    The LIM-1 Loop Isolator Module isolates

    short circuits on MXL analog loops. By

    placing devices between LIM-1s during

    installation, a short in the wiring within that

    group is disconnected from the rest of the

    loop. The remainder of the devices continue

    to operate. The LIM-1 operates in both Style

    6 (Class A) and Style 4 (Class B) circuits.

    Figure 20

    PIM-1 Peripheral Interface Module

    Description of the MXL Control Panel

    Figure 21

    CZM-1B6 Conventional Zone Module

  • 13

    INTELLIGENT/ANALOG DEVICES

    The intelligent/analog devices described

    below are available for use with the MXL

    Control Panel (ALD-2I or MMB-2).

    The UL identifiers for compatibility are the

    same as the model names specified below.

    FP-11 Intelligent/Analog

    Photoelectric Detector

    The FP-11 is an intelligent/analog photoelec-

    tric detector that can be used as an area or

    duct detector [FP-11(d)]. It uses either a

    DB-11 low profile mounting base or DB-3S

    mounting base with the DB-ADPT adapter, a

    DB-X11RS mounting base with relay or

    DB-X3RS mounting base with relay with the

    DB-ADPT adapter, an ADBI-60 audible base

    with the DB-ADPT adapter, or an AD-11P or

    AD-11XPR air duct housing.

    FPT-11 Intelligent Thermal Detector

    The FPT-11 is an intelligent/analog rate-

    compensated/fixed-temperature type thermal

    and photoelectric detector. It can only be used

    as an area detector. It uses either a DB-11

    low profile mounting base or DB-3S mounting

    base with the DB-ADPT adapter, a DB-X11RS

    mounting base with relay or DB-X3RS mount-

    ing base with relay with the DB-ADPT

    adapter, or an ADBI-60 audible base with the

    DB-ADPT adapter.

    ILP-1 Intelligent/Analog

    Photoelectric Detector

    The ILP-1 is an intelligent/analog photoelec-

    tric detector that can be used as an area or

    duct detector [ILP-1(d)]. It uses either a

    DB-3S low profile mounting base, a

    DB-X3RS mounting base with relay, an

    AD-3ILP or AD-3XRILP duct housing, or an

    ADBI-60 audible base.

    ILPT-1 Intelligent/Analog

    Photoelectric Detector with Heat

    Sensor

    The ILPT-1 is an intelligent/analog rate-

    compensated/fixed-temperature type thermal

    and photoelectric detector. It can only be

    used as an area detector. It uses either a

    DB-3S low profile mounting base, a DB-X3RS

    mounting base with relay, or an ADBI-60

    audible base.

    ILI-1 Intelligent/Analog lonization

    Detector

    The ILI-1 is an intelligent/analog ionization

    detector for use in open areas at altitudes of

    0 to 4000 feet. It uses either a DB-3S low

    profile mounting base, a DB-X3RS mounting

    base with relay, or an ADBI-60 audible base.

    ILI-1H Intelligent/Analog lonization

    High Altitude Detector

    The ILI-1H is an intelligent/analog ionization

    detector for use in open areas at altitudes of

    3000 to 8000 feet. It uses either a DB-3S

    low profile mounting base, a DB-X3RS

    mounting base with relay, or an ADBI-60

    audible base.

    ILI-1A Intelligent/Analog lonization

    High Air-Velocity Detector

    The ILI-1A is an intelligent/analog ionization

    high air-velocity detector for use in open

    areas, computer facilities, and air ducts at

    altitudes of 0 to 4000 feet, with air velocities

    of 0 to 1200 feet per minute. It uses either a

    DB-3S low profile mounting base, a DB-X3RS

    mounting base with relay, or an ADBI-60

    audible base.

    Description of the MXL Control Panel

  • 14

    ILI-1AH Intelligent/Analog lonization

    High Air-Velocity, High Altitude Detector

    The ILI-1AH is an intelligent/analog ionization

    high air-velocity, high altitude detector for

    use in open areas, computer facilities, and

    air ducts at altitudes of 3000 to 8000 feet,

    with air velocities of 0 to 1200 feet per

    minute. It uses either a DB-3S low profile

    mounting base, a DB-X3RS mounting base

    with relay, or an ADBI-60 audible base.

    ILI-1B Intelligent/Analog lonization

    Air-Duct Detector

    The ILI-1B is an intelligent/analog ionization

    detector for use in air duct applications at

    altitudes of 0 to 4000 feet, with air velocities

    of 500 to 4000 feet per minute. It uses either

    the AD-3I housing or the AD-3XRI housing.

    ILI-1BH Intelligent/Analog lonization

    Air-Duct High Altitude Detector

    The ILI-1BH is an intelligent/analog ioniza-

    tion detector for use in air duct applications

    at altitudes of 3000 to 8000 feet, with air

    velocities of 500-4000 feet per minute. It

    uses either the AD-3I or AD-3XRI housing.

    MSI-10B/20B Intelligent Manual Station

    The MSI-10B/20B is an intelligent manual

    station designed to interface with an analog

    loop. The MSI-10B/20B can be flush

    mounted or surface mounted using the

    SB-5R mounting box.

    MSI-B6F Intelligent Manual Station

    The MSI-B6F is an intelligent manual station

    designed to interface with an analog loop.

    The MSI-B6F is a single-action station;

    when used with the MS-FD adapter, the

    MSI-B6F is a double-action station. The

    MSI-B6F can be flush mounted or surface

    mounted using the MS-FB backbox.

    Description of the MXL Control Panel

    TRI-B6M Intelligent Interface Module

    The TRI-B6M addressable inferface module

    interfaces direct shorting contact devices

    with the analog loops. The TRI-B6M can

    monitor a normally open or closed dry

    contact and it can report the status of the

    contact.

    TRI-S, TRI-R, and TRI-D Intelligent

    Interface Modules

    The TRI-S/R/D series modules are intelli-

    gent interface modules that interface direct

    shorting contact devices with the analog

    loops. The TRI-S is a single-input module

    with an independently controllable Form C

    relay; the TRI-D is a dual-input module.

    CONVENTIONAL DEVICES

    The conventional devices described below are

    available for use with the MXL Control Panel.

    The UL identifiers for compatibility are the

    same as the model numbers specified below.

    DI-3 Ionization Detector

    The DI-3 is an ionization detector for use in

    open areas at altitudes of 0 to 4000 feet. It uses

    the DB-3S low profile surface mounting base.

    DI-3H Ionization High Altitude Detector

    The DI-3H is an ionization detector for use

    in open areas at altitudes of 3000 to 8000

    feet. It uses the DB-3S low profile surface

    mounting base.

    DI-A3 Ionization High Air-Velocity

    Detector

    The DI-A3 is an ionization high air velocity

    detector for use in open areas, computer

    facilities, and air ducts at altitudes of 0 to

    4000 feet, with air velocities of 0 to 1200

    feet per minute. It uses the DB-3S low

    profile surface mounting base.

  • 15

    DI-A3H Ionization High Air-Velocity,

    High Altitude Detector

    The DI-A3H is an ionization high air velocity,

    high altitude detector for use in air ducts only

    at altitudes of 3000 to 8000 feet, with air

    velocities of 0 to 1200 feet per minute. It uses

    the DB-3S low profile surface mounting base.

    DI-B3 Ionization Air Duct Detector

    The DI-B3 is an ionization detector for use

    only in air ducts at altitudes of 0 to 4000

    feet, with air velocities of 500 to 4000 feet

    per minute. It must be used with a Series 3

    air duct housing (AD-3I or AD-3RI).

    DI-B3H Ionization Air Duct High

    Altitude Detector

    The DI-B3H is an ionization detector for use

    only in air ducts at altitudes of 3000 to 8000

    feet, with air velocities of 500 to 4000 feet

    per minute. It must be used with a Series 3

    air duct housing (AD-3I or AD-3RI).

    DT-11 Thermal Detector

    The DT-11 is a thermal detector for use in

    open areas. It uses the DB-11 low profile

    surface mounting base or the DB-3S base

    with the DB-ADPT adapter.

    DT-C Series

    The DT-135CS and DT-200CS thermal

    detectors are the rate compensated type

    available in 135OF and 200OF settings. The

    DT-135CL and the DT-200CL are identical

    to CS versions, except that they have an

    internal alarm indicating lamp. There is a

    practical limit only to the number per zone.

    DT-135/200 WP

    This weatherproof thermal detector has a

    rate compensated principal available in

    either a 135OF or 200OF setting. The detec-

    tor is epoxy coated and mounts to a weath-

    erproof box for approved use in wet or

    unsheltered locations.

    DT-140/190 EP

    This explosionproof thermal detector has a

    rate compensated principal available in either

    a 140OF or 190OF setting. It should be used

    in hazardous areas requiring explosionproof

    devices. The detector mounts to an approved

    explosionproof junction box.

    PE-11 Photoelectric Detector

    The PE-11 is a photoelectric detector that

    responds to a wide range of both flaming

    and smoldering fire conditions. It uses the

    DB-11 low profile surface mounting base,

    the DB-3S base with the DB-ADPT adapter,

    or the AD-11P/PR air duct housing.

    PE-11T Photoelectric Detector with

    Heat Sensor

    The PE-11T is a photoelectric detector with

    heat sensor that responds to a wide range

    of both flaming and smoldering fire condi-

    tions. It uses the DB-11 low profile surface

    mounting base or the DB-3S base with the

    DB-ADPT adapter.

    Description of the MXL Control Panel

  • 16

    Figure 22

    Installing the DB-Seal

    Description of the MXL Control Panel

    INSTALLING the DB-SEAL for DB-3S

    BASE (See Figure 22)

    All wiring must comply with national and

    local codes.

    1. Install and wire the DB-3S base by

    following the DB-3S Installation

    Instructions (P/N 315-083225). Make sure

    that all wires are dressed flush to the

    bottom of the base.

    2. Position the tabs on the seal over the slots

    in the inner rim of the base and press the

    seal in place.

    3. Check that the four openings for the

    spring contacts clear the springs and the

    plastic terminal supports.

    4. With the seal in place, install the detector.

    5. Follow the checkout procedure in the

    detector installation instructions.

    INSTALLING the DB-11 SEAL for DB-11

    BASE (See Figure 23)

    All wiring must comply with national and

    local codes.

    1. Install and wire the DB-11 base by

    following the DB-11 Installation

    Instructions (P/N 315-094193). Make sure

    that all wires are dressed flush to the

    bottom of the base.

    2. Place the base seal (1/4" white foam)

    firmly into the bottom of the base. Do not

    cover the contact springs (See Figure 23.)

    3. Rotate the detector counterclockwise

    while pressing on it until the detector

    drops into the base.

    4. Rotate the detector clockwise until it stops

    and locks in place.

    Figure 23

    Installing the DB-11 Seal

    Refer to the MXL Operation, Installation, and Maintenance Manual, P/N 315-092036, for

    solutions to design questions regarding specific MXL fire alarm control functions and modules.

    Use DB-SEAL with all DB-3S/X3RS bases and DB-11 SEAL for DB-11

    bases. Install as shown below.

    Use the DB-Seal with a DB-3S base or the DB-11 Seal with a DB-11 base to prevent moisture

    from condensing and collecting on the rear of the detector used. This moisture can occur when

    units experience different temperatures or humidity conditions.

  • 17

    It is a US Coast Guard requirement that the

    fire detection system have two sources of

    power. Most large ships have both main

    generators and emergency generators;

    therefore, they can satisfy this requirement

    by arranging to have power supplied to the

    fire detection system by both the main and

    emergency generators.

    In cases where there are no emergency

    generators, battery backup power to the

    system is required. Revised US Coast

    Guard regulations have reduced the

    required battery operation time to 36 hours

    for passenger ships and 18 hours for all

    II. Power Requirements

    other types of vessels. In cases where it is a

    desired option to furnish the fire detection

    system with standby battery power, even

    when there are main and emergency

    generators supplying the system, there is

    no specific battery operation time period,

    although it would be recommended to be a

    minimum of 18 hours.

    When the smoke detection system is

    furnished with battery backup power, it is

    necessary to calculate the system power

    requirement to determine the battery am-

    pere-hour capacity necessary.

    NOTE: An approved Power Transfer Relay must be used for the automatic transfer from

    main power to secondary power when the main power source has 15% to 20%

    potential variation. The transfer to secondary power creates a visual and audible

    trouble signal on the MXL Control Panel. The Model PTR-1 Power Transfer Relay

    from Siemens Building Technologies, Inc. was designed for this purpose.

    Refer to the MXL Operation, Installation, and Maintenance Manual, P/N 315-092036, for

    solutions to design questions regarding specific MXL fire alarm control functions and modules.

  • 18

    Figure 25

    PTR-1 Cover (Drip-Proof)

    Figure 26

    PTR-1 Enclosure (Mounting)

    +_

    MPS-6120 VAC, 5A

    TRI-S

    TERMINALSTRIP

    3.6K, 1/4W, 5%TO ANALOG LOOP

    SUPV SWITCH

    NEUTRAL

    NEUTRAL

    PROGRAM AS TROUBLECAUSING N.C.

    POWER TRANSFER RELAYMODEL PTR-1

    MAIN POWER IN120 VAC, 5A

    AUXILIARYPOWER IN

    120 VAC, 5A

    VOLTAGE SENSITIVE POWER TRANSFERRELAY ADJUSTED TO DROP OUT AT 97V +/- 3vPULL IN AT 106V +/- 6V

    NOTE:

    Figure 24

    PTR-1 Connections

    POWER TRANSFER RELAY

    The PTR-1 is an automatic power transfer relay that transfers power from the main generators,

    at a 15% to 20% potential reduction, to the backup generators. This automatic transfer creates

    an audible and visual system trouble signal. The PTR-1 is in its own enclosure. (See Figure 24-

    26 for PTR-1 Connections, Cover and Enclosure.)

    Power Requirements

    Refer to the MXL Operation, Installation, and Maintenance Manual, P/N 315-092036, for

    solutions to design questions regarding specific MXL fire alarm control functions and modules.

  • 19

    III. Audible Alarms

    ALARM LOCATIONS AND REQUIREMENTS

    Ten inch bells are required to sound in the following locations when any alarm initiating device is

    actuated.

    1. Alarm bell must always sound on the bridge regardless of which zone is in alarm.

    2. Alarm bells must sound in the engine room, machinery spaces, and the control room when

    the alarm is initiated in any of these spaces. In case the control room might be unattended

    at the time of alarm, bells must also be installed in the passageways and lounge areas of

    the licensed engineers quarters.

    3. If an alarm is not acknowledged (silenced or reset) at the control panel within 2 minutes, the

    control panel must automatically cause the General Alarm to sound.

    NOTE: If it should be necessary to supplement the 10 inch bell audible output in high

    noise background areas with horns, sirens, strobes, flashing or rotating lights,

    the wiring to such supplementary alarm devices does not have to be supervised.

    However, audible alarms other than bells must always be accompanied by lights

    or strobes.

    Refer to the MXL Operation, Installation, and Maintenance Manual, P/N 315-092036, for

    solutions to design questions regarding specific MXL fire alarm control functions and modules.

  • 20

    V. Remote Annunciation

    REMOTE ANNUNCIATORS

    When the main control panel is located on the navigating bridge, remote annunciation is not

    required by the US Coast Guard. However when the main control panel is located in a fire

    control station which is not a constantly attended space, a supervised complete system status

    annunciator is required.

    IV. Initiating DevicesManual

    Intelligent/Analog Manual Station MSI-10B/20B

    Conventional Manual Station MS-51/501

    Reference US Coast Guard Approved Equipment List

    Manual stations are recommended for use with automatic fire detectors. If a fire is observed

    before automatic detector response, the manual activation of the station results in the same

    system response as automatic detection. Manual stations should be installed throughout the

    accommodation spaces, the service spaces, and the control stations.

    NOTE: One manual station should be located at each exit. The stations should be readily

    accessible in the corridors of each deck so that no part of the corridor is more

    than 60 feet (20 meters) from another manual station.

    Refer to the MXL Operation, Installation, and Maintenance Manual, P/N 315-092036, for

    solutions to design questions regarding specific MXL fire alarm control functions and modules.

  • 21

    VI. Detector Application and Spacing

    2. THERMAL DETECTORS

    2.1 Description and Function

    All thermal detectors respond only to exces-

    sive heat, which is assumed to be gener-

    ated from a flaming fire. The detectors are

    designed with different operating principles

    as described below.

    2.1.1 Fixed Temperature

    The air temperature has to exceed the set

    ratings of the devices in order to activate it.

    The settings are 135 F, 190 F and higher

    (on special order).

    2.1.2 Rate Compensated

    This type of thermal detector is similar to

    the fixed temperature detector in operation,

    but is compensated to eliminate the expected

    thermal lag and, therefore, responds faster.

    2.2 Spacing

    Maximum approved spacing of thermal

    detectors is as follows:

    Maximum

    Area Protected Distance from

    Type (Square Feet) Sidewalls (Feet)

    Fixed Temperature (DT-11) 625 (25 X 25) 12.5

    Fixed and

    Rate of Rise 2500 (50 X 50) 25

    DT-135 CS, CL, and WP

    Rate Compensated 2500 (50 X 50) 25

    DT-200 CS, CL and WP

    Rate Compensated 2500 (50 X 50) 25

    1. SMOKE DETECTORS

    1.1 Description and Function

    Smoke detector is the generic name given

    to either ionization type or photoelectric type

    detectors. The ionization type responds to

    both visible and invisible products of com-

    bustion, while the photoelectric type depends

    on sensing visible smoke.

    1.2 SpacingFor average areas with smooth ceilings and

    normal air movement, the maximum recom-

    mended spacing is 900 square feet or no

    more than 30 feet between centers and 15

    feet from a sidewall. In areas with higher air

    movement, the detector spacing should be

    reduced accordingly.

    1.3 Application Limitations

    1.3.1 On ceiling heights below 8 feet, the

    possibility of unintentional alarms from

    tobacco smoke does exist, especially in

    areas where people might congregate. It is

    recommended that smoke detectors in such

    areas have their zones wired through alarm

    confirmation module.

    1.3.2 Smoke detectors should not be used

    in areas where they could be subjected to

    steam or moisture condensation such as in

    galleys, laundries, etc. Thermal detectors

    should be used in such areas.

  • 22

    3. PLANNING A FIRE DETECTION

    SYSTEM

    When planning a fire detection system,

    make a choice of detector based on the

    kinds of fires expected. The type and

    quantity of fuel, possible ignition sources,

    ranges of ambient conditions, and the value

    of the property to be protected should all be

    considered.

    In general, heat detectors have the lowest

    cost and false alarm rate, but are the slow-

    est to respond. Since the heat generated by

    small fires tends to dissipate fairly rapidly,

    heat detectors are best used to protect

    confined spaces, or directly over hazards

    where flaming fires can be expected. They

    are usually installed on a grid pattern at

    their recommended spacing distances or at

    reduced spacing for faster response. The

    operating temperature of a heat detector

    should be at least 25 F above the maxi-

    mum expected ambient temperature in the

    area protected.

    Detector Application and Spacing

    Smoke detectors cost more than heat

    detectors, but respond faster to fires. They

    are better suited to protect large open

    spaces than heat detectors because smoke

    does not dissipate as rapidly as heat does

    in the same size space. Smoke detectors

    are either installed according to prevailing

    air current conditions or on a grid layout.

    Photoelectric smoke detectors are best

    used in places where wire insulation or

    other smoldering fires may be expected.

    Ionization smoke detectors are useful where

    fire would be expected to develop into a

    small flaming condition soon after pyrolysis.

    NFPA Standard 72 Chapter 5 has more

    specific information on the installation of the

    various types of detectors.

  • 23

    3.1 Detector Application

    In view of the problems that can be expected with the misapplication and location of detection

    devices aboard ship, the guidelines below should be followed when designing systems.

    These tables list situations where the use of smoke detectors, ionization and photoelectric

    should be avoided.

    Moisture

    Salt water spray Heat treating

    Corrosive atmospheres Dust or lint

    Water spray Sawing, drilling and grinding

    Live steam Pneumatic transport

    Steam tables Slop sinks

    Showers Humid outside air

    Humidifiers Excessive tobacco smoke

    Combustion Products And Fumes

    Cooking equipment Engine exhaust

    Ovens Gasoline forklift trucks

    Dryers Diesel trucks and locomotives

    Exhaust hoods Engines not vented to the outside

    Metal cutting Welding and brazing

    Machining Heating element, abnormal

    Paint spray Dust accumulation

    Curing Improper exhaust systems

    Chemical fumes Incomplete combustion

    Cleaning fluids

    3.1 MXL Intelligent/Analog Detectors

    Photoelectric/Ionization and MXL Conventional Photoelectric/Ionization Detectors shall

    not be installed in cargo holds and RO/RO spaces.

    NOTE: Conventional weatherproof thermal detectors DT-135WP/DT-200WP must be used

    in cargo holds and RO/RO spaces.

    Detector Application and Spacing

  • 24

    Areas to be Protected

    ACCOMMODATION SPACES (ION,

    PHOTO)

    Halls, dining rooms, lounges, and other

    areas of this type with permanent walls,

    corridors, sanitation facilities, cabins,

    offices, infirmaries, and leisure rooms not

    containing cooking appliances.

    SERVICE AREAS (ION, PHOTO, TEMP)

    Service cabinets, radio rooms,

    strong rooms, stores, workshops other

    than machinery spaces, and similar

    areas, including shafts going to them,

    as well as life-vest storage areas.

    SPECIAL AREAS (ION, PHOTO, TEMP)

    Closed areas for transport of special

    materials.

    SAFETY STATIONS (ION, PHOTO,

    TEMP)

    Areas housing the radio equipment,

    major navigation equipment, standby

    generator and central installations.

    MACHINERY SPACES (ION, PHOTO,

    TEMP)

    Areas housing the propulsion unit,

    boilers, liquid-fuel handling units,

    stabilization equipment, ventilation and

    air conditioning equipment, and similar

    areas, including the shafts running to

    them.

    Monitoring Machinery Spaces

    Because of the irregular shape of most

    machinery spaces and the strong air

    currents present, the number and type

    of detectors used cannot be based on

    the area protected, as is in the common

    practice on land-based installations and

    ship accommodation spaces. The best

    design approach is to pick out all poten-

    tial fire outbreak areas and place a fire

    detector above each of them at deck

    level. Areas of potential fire risk include

    the following:

    Auxiliary boiler front

    Main boiler front

    Fuel oil pressure pumps

    Auxiliary generator sets

    Main diesel engine fuel oil pumps

    and injectors

    Fuel oil purifiers

    Lubricating oil purifiers

    Fuel oil transfer pumps

    Workshops

    Electrical switchboards

    Storerooms

    Locate additional detectors with fairly

    wide spacing to give general cover to

    areas not containing special risk.

    Detector Application and Spacing

  • 25

    Detector Application and Spacing

    4. DETECTOR INSTALLATION

    After the most suitable detector for the job is

    selected, the location of the detector within

    the space to be protected should be consid-

    ered.

    Spot type detectors are usually located on

    the ceiling or side wall with the edge of the

    detector located no closer than 4 inches

    from the wall or ceiling. When heat detec-

    tors are installed at their listed spacing,

    detection times are approximately equiva-

    lent to the operating time of standard 165F

    link-and-lever sprinklers. If faster response

    is desired, reduce detector spacing. Also,

    where ceiling heights exceed 16 feet, or

    where ceiling construction is not smooth,

    reduce spacings accordingly. Specific

    information on the treatment of joisted,

    beamed, and sloped ceilings can be found

    in Chapter 5 of NFPA (2002 Edition).

    When installing any type of heat detector,

    consideration should be given to sources of

    heat within the protected space which might

    cause false alarms. For example, locate heat

    detectors away from unit heaters and ovens

    where surges of hot air might be expected.

    The installation of smoke detectors is more

    critical than for heat detectors because

    smoke transport is strongly influenced by

    the convective air flow patterns within the

    protected area. For this reason, smoke

    detectors are not assigned a listed spacing

    by the testing laboratories other than a

    maximum area coverage of 900 square feet

    per detector. Although a grid pattern can be

    used as a starting point, care must be taken

    to appropriately locate the heating supply

    registers and return air registers. Smoke

    detectors should be located away from

    turbulence caused by hot air outlets. The

    location of the smoke detectors should favor

    return air because the return air draws

    smoke toward the detector and because air

    velocity at the return tends to be lower.

    Smoke stratification also should be consid-

    ered when smoke detectors are installed.

    Smoke may stratify below a ceiling due to

    temperature gradients or air flow along the

    ceiling. When stratification is a possibility,

    smoke detectors can be installed with

    alternate detectors at different levels.

    The installation of ionization type detectors

    is similar to that of smoke detectors since

    fire gases tend to flow with smoke and are

    similarly affected by convected flows within

    the protected space. They also must be

    located away from sources of oxidizable

    gases or vapors; for example, away from

    substances like aerosol sprays or hydrocar-

    bon solvents, as these substances could

    cause false alarms.

    Refer to the MXL Operation, Installation, and Maintenance Manual, P/N 315-092036, for

    solutions to design questions regarding specific MXL fire alarm control functions and modules.

  • 26

    VII. Enclosures

    1. SHOCK MOUNTING FOR

    ENCLOSURES

    All MME-3-CG enclosures are shipped with

    shock mounting already in place.

    A US Coast Guard approval nameplate

    must be affixed to the door of the enclosure.

    2. INSTALLATION

    2.1 Model MME-3-CG

    (Refer to Figure 28, page 28)

    The Enclosure Kit Model MME-3-CG for

    use in Coast Guard installations is

    shipped as a complete package. To

    mount the enclosure, consider the

    following:

    Mounting height for visual and

    manual access to the keyboard/

    annunciator

    Weight and size of enclosure

    Local mounting codes

    To install the MME-3-CG:

    1. Hold the empty enclosure against the wall

    at a height that provides easy access.

    2. Mark drill points on the wall in the center of

    the two keyhole slots (marked "A" in Figure

    28) on the upper rails that are attached to

    the enclosure.

    3. Drill the two holes. Screw in the top bolts

    (user supplied), leaving a small gap

    between the wall and each top bolt.

    4. Mount the enclosure/rail assembly on

    the two bolts.

    5. Mark drill points on the wall for the

    remaining six holes in the rails. Drill the

    holes.

    6. Install bolts in the remaining two holes in

    the top rails and four holes in the bottom

    rails. Tighten all bolts securely.

    7. To install the BP-61 battery set in the

    enclosure, first remove the battery

    bracket from the bottom left hand corner

    of the enclosure by removing the 4 nuts

    and washers. Place them to one side.

    Install the battery. Replace the battery

    bracket and secure it in place with the 4

    nuts and washers. (Refer to Figure 27.)

    NOTE: Flexible conduit or cable with

    a maximum diameter of 3/4 inch and

    a minimum length of 18 inches from a

    rigid connection should be used to

    house external wiring.

    MPS-6OR

    MPS-12BATTERIES

    Figure 27

    MME-3-CG Battery Bracket Installation for BP-61 Battery Set

  • 27

    Enclosures

    40-5/8

    0.31 16-29/322-1/2

    A A

    Figure 28

    Mounting Diagram for MME-3-CG Enclosure

  • 28

    Enclosures

    2.2 WIRING

    In compliance with UL-864 all power limited

    fire protective signaling conductors must be

    separated a minimum of 1/4 inch from all of the

    following items located within a control panel:

    electric light

    power

    Class 1 or non-power limited fire

    protective signaling conductors

    When installing power limited field wiring,

    the installer must comply with NEC article

    760-54, which states:

    The fire alarm power-limited circuits are installed

    using Types FPL, FPLR, FPLP or permitted

    substitute cable, provided these power-limited

    cable conductors extending beyond the jacket

    are separated by a minimum of 0.25 in. (6.35

    mm) or by a nonconductive sleeve or nonconduc-

    tive barrier from all other conductors.

    To meet the above requirements, the following

    guidelines must be observed when installing

    modules and wiring to this control panel.

    WIRING ENTERING MAIN ENCLOSURE

    Non-Power Limited Wiring

    Wiring to the following MXL module termina-

    tions is considered non-power limited and

    must enter the enclosure through the knock-

    outs designated as non-power limited (Refer

    to Figures 29 and 30). Wiring between the

    knockouts and the module termination must

    be in the shortest route and must not over-

    lap any other wiring.

    2ELBAT

    eludoM noitanimreT

    *4-MRC

    4-MSC

    6-SPM

    21-SPM

    4-MOM

    4-MOM

    3,2,1

    3,2,1

    * CRM-4/CSM-4 modules must be installed inthe extreme left MOM module position. Install

    the first CRM in position A, the second in

    position B, etc., as shown in Figure 29.

    When the CSM-4 is used as Municipal Tie or

    Releasing Service.

    WIRING IN MAIN ENCLOSURE

    Non-Power Limited Wiring

    The following wiring is considered non-

    power limited:

    from the MPS-6 or MPS-12

    from the batteries to the MMB

    from the MMB (P3) to the MOM-4 (P5)

    When the TSP-40 optional printer is used,

    the printer cable to the MOM-4 (P8) is

    considered to be non-power limited. Route

    the cable as shown in Figure 30.

    WIRING ENTERING MAIN ENCLOSURE

    Power Limited Wiring

    Wiring to the following MXL module termina-

    tions is considered power limited and must

    enter the enclosure through the knockouts

    designated as power limited (Refer to

    Figures 29 and 30). When installing mod-

    ules in a MOM-2 or MOM-4, care must be

    taken to determine whether the wiring

    entering the enclosure is power limited or

    non-power limited. Wiring between the

    knockouts specified and the module termi-

    nation must be in the shortest route and

    must not overlap any other wiring.

    3ELBAT

    eludoM noitanimreT

    2-DLA

    I2-DLA

    *4-MSC

    4-MZC

    BMM

    W1-MIN

    1-PER

    4-MOM

    4-MOM

    4-MOM

    4-MOM

    )4-1(1BT

    )4-1(2BT

    )4-1(3BT

    )9-1(4BT

    4-MOM

    4-MOM

    * When the CSM-4 is used as Notification

    Application Circuit or Leased Line.

    Listed Class 2 or Power Limited Source.

  • 29

    POWER LIMITED

    NON-POWERLIMITED

    NON-POWERLIMITED

    NON-POWERLIMITED

    NON-POWERLIMITED

    MMB

    P5P5P5 P8P8P8

    A

    B D F H MK

    C G LIE

    MPS-6OR

    MPS-12

    TB1

    TB2

    TB3

    P3P2

    TB5

    TB4

    MOM-4

    or

    MOM-2

    MOM-4

    or

    MOM-2

    MOM-4

    or

    MOM-2

    + +_ _

    POWER LIMITED

    POWER LIMITED

    POWER LIMITED

    Figure 29

    MXL Wiring When No TSP-40 Is Used

    Enclosures

  • 30

    POWER LIMITED

    NON-POWERLIMITED

    NON-POWERLIMITED

    MPS-6OR

    MPS-12

    OPTIONALTSP-40

    POWER LIMITED

    MMB

    TB1

    MOM-4

    or

    MOM-2

    TB2

    TB3

    TB4

    P8P5

    MOM-4

    or

    MOM-2

    P8

    P5

    19

    TB5

    POWER LIMITED

    NON-POWERLIMITED

    + +_ _

    NON-POWERLIMITED

    Figure 30

    MXL Wiring When TSP-40 Is Used

    Enclosures

  • 31

    Enclosures

    Figure 31

    Installing Compression Raintight Fitting

    MME-3-CGEnclosure

    Compression RaintightFitting (user supplied)

    Approved 3/4 MaxFlexible Metallic/Nonmetallic Conduit OrCable (user supplied)

    Figure 32

    Installing Ferrites to Prevent Conducted Noise on AC Lines

    Cable Preparation:1. Strip the AC cable jacket approximately 30 inches.2. Allow approximately 3 inches before winding each

    individual wire (hot, neutral or ground)through one of the 3 ferrites supplied with theMME-3-CG.

    3. Cut the excess wire to 2.0 inches as shown, thenwire to the appropriate terminal of the MPS powersupply.

    4. Repeat steps 2 and 3 for the other 2 wires.

    4 times

    2.0"

    3.0" AC CABLE

    Ferrites suppliedwith MME-3-CG

    INSTALL WIRING

    Remove all system power before installa-

    tion, first battery and then AC. (To power

    up, connect the AC first and then the battery.)

    1. Wire in accordance with local codes and

    NEC 760.

    2. Determine the location of knockouts in the

    sides of the backbox where field wiring is

    required.

    a. Drill a hole of appropriate size at each

    knockout location.

    b. Install a compression raintight fitting

    (user supplied) at each knockout

    location. Refer to Figure 31.

    3. Pull all field wiring into the backbox. Do

    not dress the wiring until the location of all

    the equipment is known.

    4. Install the wiring from the external AC power

    source to the approximate location of the

    power supply (MPS-6 or MPS-12). Add one

    ferrite each to the hot, neutral and ground

    wires as shown in Figure 32. Add ferrites

    per Figure 32 for each MPS-6 or MPS-12 in

    the system.

  • 32

    VIII. Wiring Specifications

    ALD-2I LOOP CONFIGURATION GUIDE

    The ALD-2I loading graph on page 33 plots the ALD-2I Loop output current verses the total line

    resistance. The results are used to determine the maximum line resistance, which can be

    tolerated in conjunction with the number and types of devices connected to the loop. The current

    for each device is listed on the graph. Note: This is device inrush current and must be used for

    this calculation.

    1. Add the individual currents for each device that is to be connected to the loop.

    2. Locate the total ALD-2I current on the Y-axis and draw a horizontal line until it intersects

    the curve.

    3. At the point of intersection draw a vertical line down until it intersects with the X-axis. It is at

    this point that the graph will yield the total amount of line resistance that can be tolerated by

    the loop.

    The ALD-2I loading graph is to used to maximize the number of devices that can be installed on

    the ALD-2I loop of an MXL system.

    The vertical axis of the graph is milliamperes of current and the horizontal axis is ohms. When

    you know either the total device current on an ALD-2I loop or the total resistance (both wires) of

    that loop, the graph can be used to determine the other variable.

    EXAMPLE #1: The total line resistance of a loop is sixty (60) ohms. By using the graph you

    will find that the total allowable device current is seventy-six (76) milliamperes.

    EXAMPLE #2: The total device current on a loop is going to be eighty (80) milliamperes. By

    using the graph you find that the maximum allowable loop resistance is fifty-

    five (55) ohms.

  • 33

    AL

    D-2

    I

    Ou

    tpu

    t

    Cu

    rren

    t

    (mA

    )

    0

    Dash

    ed

    Lin

    e:

    AL

    D-2

    I H

    ard

    ware

    90

    100

    10

    20

    30

    40

    1.0

    mA

    1.4

    mA

    0.5

    mA

    AL

    D-2

    I L

    oa

    din

    g G

    rap

    hC

    urr

    ent

    Model

    CZM

    Seri

    es

    4.0

    mA

    IL S

    eri

    es

    TR

    I-B

    6 S

    eri

    es

    To

    tal A

    LD

    -2I L

    ine R

    esis

    tan

    ce (

    oh

    ms)

    4.0

    mA

    50

    60

    70

    80

    LIM

    -1

    ICP

    /VC

    P S

    eri

    es

    0.7

    5 m

    A

    1.6

    mA

    10

    20

    30

    40

    50

    60

    70

    TR

    I-S

    /R/D

    80

    90

    100

    0.5

    mA

    0.5

    mA

    TR

    I-60 S

    eri

    es

    120

    130

    140

    1.4

    mA

    1.8

    mA

    2.3

    mA

    TR

    I-60D

    110

    TR

    I-B

    6D

    FP

    Seri

    es

    ID S

    eri

    es

    MS

    I-B

    6 S

    eri

    es

    Wiring Specifications

  • 34

    WIRING SPECIFICATION FOR MXL

    1. ALL WIRING MUST COMPLY WITH

    LOCAL AND NATIONAL CODES.

    2. Intermixing of field wiring cable types is

    allowed.

    3. Radiated and Conducted Emissions

    Protection

    A. For each circuit type described in

    sections 4-8, add one clamp-on ferrite

    having sufficient diameter to the cable

    between the module and the knockout.

    See Table 4.

    4ELBAT

    etirreFnO-pmalC

    rerutcafunaM

    edisnI

    retemaiD

    drawetS

    2A0-4340A82N/P

    "012.0

    )mm53.5(

    drawetS

    2A0-2950A82N/P

    "981.0

    )mm08.4(

    drawetS

    2A0-3950A82N/P

    "662.0

    )mm57.6(

    yeK-igiDmorfdesahcrupebyaM

    NM,sllaFreviRfeihT,noitaroproC

    9354-443)008(enohP,10765

    B. For each circuit type described in

    sections 4-8, add one clamp-on ferrite

    having sufficient diameter to the entire

    bundle of cables outside the enclosure

    approximately 12 inches from the

    enclosure. See Table 5.

    5ELBAT

    etirreFnO-pmalC

    rerutcafunaM

    edisnI

    retemaiD

    scinortcelEhtruW

    3517247N/P

    "123.0

    )mm51.8(

    scinortcelEhtruW

    1517247N/P

    "306.0

    )mm51(

    scinortcelEhtruW

    4517247N/P

    "246.0

    )mm3.61(

    scinortcelEhtruW

    5517247N/P

    "80.1

    )mm5.72(

    nehcuteMmorfdesahcrupebyaM

    ,33770JN,ledmloH,.cnI,sroticapaC

    4103-244)008(enohP

    C. For each power supply (MPS-6 or MPS-12)

    add one ferrite each to the hot, neutral

    and ground wires as shown in Figure 32,

    page 31. Three ferrites are supplied with

    the MME-3-CG enclosure.

    4. For all Signaling Line Circuits (ALD-2I Loops)

    A. All SLC circuits are rated Power Limited

    and should be wired in accordance with

    applicable codes.

    B. The minimum wire size permitted is 18

    AWG, maximum 14 AWG.

    C. Multiple SLC circuits within the same

    cable or metal raceway do not have to

    be individually shielded.

    D. The maximum line resistance:

    Style 4 (Class B) circuit (all wires) is 100

    ohms.

    Style 6 (Class A) circuit, allowable

    resistance is 100 ohms, 25 ohms per

    line.

    Refer to the ALD-2I Loop Configuration

    Guide on page 32.

    E. The maximum allowable line

    capacitance for SLC circuits is:

    0.4 UF Line to Line

    0.8 UF Line to Ground

    5. Non-addressable Initiating Device Circuits

    (i.e., CZM-4, CZM-1, TRI Modules):

    A. All Siemens Fire Safety initiating circuits

    are rated Power Limited and should be

    wired in accordance with applicable

    codes.

    B. The minimum wire size permitted is 18

    AWG, maximum 14 AWG.

    C. The maximum allowable line resistance

    per module is as follows:

    1. Model CZM-4:

    Style B (Class B) - 70 ohms

    maximum (both wires). If a Relay

    Base is utilized, 40 ohms maximum.

    Style D (Class A) - 70 ohms

    maximum, 17.5 ohms per line. If a

    Relay Base is utilized, 40 ohms

    maximum, 10 ohms per line.

    Wiring Specifications

  • 35

    Wiring Specifications

    2. Model CZM-1 (No detector

    accessories allowed):

    Style B (Class B) - 35 ohms

    maximum (both wires).

    Style D (Class A) - 35 ohms

    maximum, 8.7 ohms per line.

    CZM-1 power wiring allowable.

    Style B (Class B) both wires,

    maximum resistance is 4 ohms.

    Style D (Class A) maximum

    resistance is 1 ohm per wire.

    3. Model TRI-Series* - minimum size

    wire for supervised switch is 18

    AWG, shielded, maximum line length

    200 feet (TRI to switch).

    Maximum Capacitance 0.04 UF Line

    to Line.

    Maximum Capacitance 0.08 UF Line

    to Ground.

    * Reference US Coast Guard Approved

    Equipment List.

    D. Parallel wiring (T-tapping) is not allowed

    on any of the above.

    6. MXL (MNET) Local Network Circuits (i.e.,

    MXL to MXLR):

    A. Minimum wire size permitted is 18 AWG,

    maximum is 14 AWG.

    B. The maximum allowable:

    Line resistance is 80 ohms (both wires)

    Line capacitance is 0.33 UF Line to Line

    and 0.66 UF Line to Ground for

    each network pair.

    C. Parallel wiring (T-tapping) is not allowable

    unless an REP-1 is utilized. Each REP-1

    provides two Style 4 Circuits providing an

    additional 80 ohms line resistance.

    D. 120 ohm, 1/4 watt resistors must be

    placed at each end of the network circuit

    (MNET).

    E. All MXL (MNET) local network wiring is

    rated Power Limited and should be wired

    in accordance with applicable codes.

    F. The MXL (MNET) local network utilizes a

    modified RS-485 (CSMA/CD). It is not

    presently compatible with modem

    transmission.

    7. MXL (XNET) Global Network Circuits (i.e.,

    MXL to MXL):

    A. Minimum wire size is 18 AWG,

    maximum is 14 AWG.

    B. The maximum allowable:

    Line resistance is 80 ohms (both wires).

    Line capacitance is 0.33 UF Line to Line, 0.66

    UF Line to Ground for each network pair.

    These parameters also apply to the

    Foreign System Interface module

    (RS-485).

    C. Parallel Wiring (T-tapping) is not

    allowable unless a REP-1 is utilized.

    D. 120 ohm, 1/4 watt resistors must be placed

    at each end of the XNET network pair.

    E. All MXL (XNET) network wiring is rated

    Power Limited and should be wired in

    accordance with applicable codes.

    F. Multiple MXL (XNET) network utilizes a

    modified RS-485 (CSMA/CD). The

    XNET can be configured with the

    NIM-1W/1M modules to allow FSK data

    transmission over properly configured

    PBX or POTs lines.

    8. Notification Appliance Circuits: (NAC)

    A. All NAC circuits must use a minimum of

    14 AWG wire.

    B. Line resistance (all wires) is 3 ohms.

    Line capacitance is 0.05 UF Line to Line

    and 0.1 UF Line to Ground.

    C. These circuits and their associated

    wiring are rated Power Limited and

    should be wired in accordance with

    applicable codes.

    D. Parallel wiring (T-tapping) is not allowed

    on any NAC circuit.

    E. When programmed for leased line

    circuits, the external wiring resistance to

    the monitoring location must be between

    2K and 5K ohms. This line must be a

    dedicated pair for fire alarm use only.

  • 36

    Wiring Specifications

    F. When programmed for municipal tie

    circuits, the external wiring resistance to

    the municipal box shall not exceed 22.5

    ohms (both wires).

    G. When programmed for releasing service

    use, the maximum line resistance is 3

    ohms (both wires).

    NOTES:

    1. When shielded cable is utilized, the wiring

    shields should only be connected at the

    point of origin, as specified.

    2. Underground wiring is permissible if all

    National and Local Code Requirements are met.

    3. All underground wiring should be shielded

    and use UL Listed / Approved (for fire

    protection) Transient Protection Devices.

    Metal raceway is recommended for

    maximum reliability and dependability.

    4. Overhead exterior wiring is not permitted.

    5. Twisted pair wires standard twist is 6 turns

    per foot.

    6. For wire resistance information, refer to the

    latest edition of the National Electric Code,

    NFPA 70, or contact the manufacturer of the

    wire in question.

  • 37

    US Coast Guard ApprovedEquipment List (Cert No:161.002/22/7)

    1. MXL Control Panel/Enclosures

    2. MXL System Modules

    3. MXL Accessories

    4. MXL Intelligent Initiating

    Devices/Bases

    5. MXL Notification Appliances/Devices

    6. MXL Conventional Initiating

    Devices/Bases

    7. Previously Listed Equipment

    MXLMarine Fire Detection System

    Fire Safety8 Fernwood RoadFlorham Park, NJ 07932

    Siemens Building Technologies, Inc.Phone (973) 593-2600Fax (973) 593-6612www.sbt.siemens.com/fis

    P/N MXL-M-03Rev-3-2/05Pages 37 - 44

  • 38

    1. MXL Control Panel/EnclosuresModel No. Part No. Description Catalog No.

    MME-3-CG 500-649569 MXL USCG Apprvd. Complete Enclosure ---

    BB-55 500-693298 MXL 55 Amp Hour Battery Box ---

    RCC-1 500-692533 Remote Control/Annunciator (MKB) 5039

    Model No. Part No. Description Catalog No.

    MMB-2 500-894049 MXL Main Board 5000

    SMB-2 500-895955 MXL-IQ Main Board 5054

    MPS-6 500-490357 MXL 6 Amp. Power Supply 5000

    MPS-12 500-492209 MXL 12 Amp. Power Supply 5000

    MPS-12/220 500-492572 MXL 12 Amp. 220 VAC Power Supply ---

    MPS-12/240 500-492573 MXL 12 Amp. 240 VAC Power Supply ---

    PSR-1 500-891182 Remote Power Supply/Controller 5010

    (Requires MPS-6 Or MPS-12)

    ALD-2I 500-891618 Analog Loop Drive (2 Circuits) 5005

    CRM-4 500-890401 Relay Module (4 Relays) 5002

    CSM-4 500-890402 Controllable Signal Module 5001

    CZM-4 500-890488 Convention Zone Mod (4 Zones) 5003

    LIM-1 500-892361 Short Circuit Line Isolator 5040

    MID-16 500-891747 Input Driver Mod. (16 Inputs) 5017

    MKB-1 500-890378 Display/Annunciator with USCG MMB-2 ---

    MOD-16 500-890828 Output Driver Mod. (16 Outputs) 5008

    MOI-7 500-892800 Network I/O Interface Style 4 or 7 5047

    MOM-2 500-892766 Expansion Cardcage (2 Slots) 5043

    MOM-4 500-890269 Expansion Cardcage (4 Slots) 5004

    NET-4 500-891181 Style 4 Communication Module 5012

    NET-7 500-091914 Style 7 Communication Module 5034

    NIM-1W 500-699103 Global (X-NET) MXL Network Interface 5072

    PIM-1 500-691324 Peripheral Interface Modules 5015

    PS-5A 500-492369 Auxiliary 5V Power Supply Module ---

    PS-5N7 500-892728 Local Network Interface Style 4/7 5046

    PTR-1 500-186248 Power Transfer Relay ---

    RCC-1 500-692533 Remote Control/Annunciator (MKB) 5039

    REP-1 500-892954 RS-485 Network Repeater 5051

    TSP-40 500-890775 Thermal Strip Printer, (Internal) 5007

    2. MXL System Modules

    --- : Catalog Sheet is not available. However, an instruction sheet is provided with the shipped equipment.

  • 39

    Model No. Part No. Description Catalog No.

    AD-11P 500-095656 Air Duct Housing (For Series 11) 6178

    AD-11PR 500-095657 Air Duct Housing with Relay (For Series 11) 6178

    AD-11XPR 500-096062 Air Duct Housing with Relay (For Series 11) 6178

    AD-3I 500-086495 Air Duct Housing, Ion 6124

    AD-3ILP 500-093268 Air Duct Photo Detector ---

    AD-3XRI 500-086499 Duct Housing with Relay for X&I Ion 6124

    AD-3XRILP 500-093269 Air Duct Photo Detector ---

    ADBI-60 500-090930 Audible Base (For X or I Series) 6163

    ADBX-11 500-096181 Audible Base (For Series 11) ---

    CZM-1B6 500-895352 Conventional Zone Module 5066

    DB-11 500-094151 Detector Mounting Base for Series 11 6173

    DB-3S 595-381804 Universal Base ---

    DB-ADPT 500-094187 Detector Base Adapter ---

    DB-X11RS 500-096125 Relay Base (For Series 11) ---

    DB-X3RS 500-083248 Relay Base (For X or I Series) ---

    EAD-3 500-686214 Weatherproof Air Duct Enclosure ---

    FP-11 500-095112 Addressable FirePrint Fire Detector 6175

    FPT-11 500-095918 Addressable Thermal Detector 6176

    ILI-1 500-092725 Intelligent Ion Detector 6165

    ILI-1A 500-093023 Intelligent Ion, High Air Velocity 6165

    ILI-1AH 500-093031 Intelligent Ion, High Air Velocity High Altitude 6165

    ILI-1B 500-093026 Intelligent Ion, Air Duct 6165

    ILI-1BH 500-093033 Intelligent Ion, Air Duct High Altitude 6165

    ILI-1H 500-093029 Intelligent Ion, High Altitude 6165

    ILP-1 500-092650 Intelligent Photo Detector 6164

    ILPT-1 500-092863 Intelligent Photo with 135 Thermal 6164

    ISM-1 500-694122 Diode Barrier ---

    MSI-10B 500-893080 Intelligent Man. Station, Single Action 6183

    MSI-20B 500-893081 Intelligent Man. Station, Double Action 6183

    MSI-B6F 500-895301 Intelligent Metal Man. Station 6188

    RA-ADB 500-689948 Flush Trim Ring for Bases ---

    TRI-B6M 500-894546 Interface Module 6170

    TRI-D 500-896226 Dual Input Module 6179

    TRI-R 500-896224 Single Input with Relay 6179

    TRI-S 500-896225 Single Input Module 6179

    Intrinisically Safe Application Requires Diode Barrier, DI-3IS Smoke Detector and Contact Devices.

    3. MXL AccessoriesModel No. Part No. Description Catalog No.

    BP-61 175-387194 Battery (15 AH, 24 VDC) 3361

    BTX-1 175-083897 Battery (35 AH) 3361

    BTX-2 175-083898 Battery (55 AH) 3361

    MPX-2 500-887821 TRI/TRX Mounting Plate ---

    MXL-MPFO 500-692880 Fiber Optic Mntg plt MOM Footprnt ---

    TSP-40-PP 500-691888 TSP-40 Printer Paper 5007

    TSW-2 500-692413 Panel Tamper Switch (UL 1076) ---

    4. MXL Intelligent Initiating Devices/Bases

    --- : Catalog Sheet is not available. However, an instruction sheet is provided with the shipped equipment.

    *

    *

  • 40

    5. MXL Notification Appliances/Devices

    --- : Catalog Sheet is not available. However, an instruction sheet is provided with the shipped equipment.

    Model No. Part No. Description Catalog No.

    BT-F 500-694372 Bell 2537

    BT-SS 500-694387 Bell 2537

    DSC 500-696872 Dual Synchronization Control Module 2553

    DSC-W 500-696873 Dual Synchronization Control Module - White 2553

    FER 500-694493 F-Series Extension Ring 2511

    FERW 500-695772 F-Series Extension Ring - White 2511

    FIB 500-694496 Indoor Surface Box 2511

    FIBW 500-695775 Indoor Surface Box - White 2511

    FWB-1 500-694494 Weatherproof Back Box 2511

    FWB-1W 500-695773 Weatherproof Back Box - White 2511

    FWB-2 500-694495 Weatherproof Back Box 2511

    FWB-2W 500-695774 Weatherproof Back Box 2511

    HN-EP 500-694290 Explosion Proof Horn - "Lower Current" 2530

    HNH-EP 500-694289 Explosion Proof Horn - "Higher dB" 2530

    U-EC 500-696850 Electronic Chime 2556

    U-EC-W 500-696851 Electronic Chime - White 2556

    U-EC-C 500-696924 Electronic Chime - Ceiling 2556

    U-EC-MCS 500-699715 Wall Chime w/Adapter Strobe 2556

    U-EC-MCS-C 500-699716 Chime w/Adapter Strobe Ceiling 2556

    U-EC-MCS-W 500-699717 Wall Chime w/Adapter Strobe - White 2556

    U-HN 500-696512 Electro-Mechanical Horn - DC 2557

    U-HN-W 500-696513 Electro-Mechanical Horn - DC / White 2557

    U-HN-C 500-696935 Electro-Mechanical Horn - DC /Ceiling 2557

    U-HN-MCS 500-699724 Electro-Mechanical Horn -DC w/Adapter Strobe 2557

    U-HN-MCS-C 500-699725 Electro-Mechanical Horn -DC w/Adapter Strobe-Ceiling 2557

    U-HN-MCS-W 500-699726 Electro-Mechanical Horn -DC w/Adapter Strobe-White 2557

    U-HN-S110-1 500-696692 Electro-Mech. Horn - DC w/110CD Strobe 2557

    U-HN-S110-1-W 500-696693 Electro-Mech. Horn - DC w/110CD Strobe-White 2557

    U-HN-S110S-1 500-696694 Electro-Mech. Horn - DC w/110CD Sync. Strobe 2557

    U-HN-S110S-1-W 500-696695 Electro-Mech. Horn - DC w/110CD Sync. Strobe-White 2557

    U-HNH 500-696534 Electro-Mechanical HIDB Horn 2557

    U-HNH-W 500-696535 Electro-Mechanical HIDB Horn-White 2557

    U-HNH-C 500-696946 Electro-Mechanical HIDB Horn-Ceiling 2557

    U-HNH-MCS 500-699729 Electro-Mechanical HIDB Horn w/Adapter Strobe 2557

    U-HNH-MCS-C 500-699730 Electro-Mech. HIDB Horn w/Adapter Strobe-White 2557

    U-HNH-MCS-W 500-699731 Electro-Mech. HIDB Horn w/Adapter Strobe-Ceiling 2557

    U-HNH-S110-1 500-696714 Electro-Mech. HIDB Horn w/110CD Strobe 2557

    U-HNH-S110-1-W 500-696715 Electro-Mech. HIDB Horn w/110CD Strobe-White 2557

    U-HNH-S110S-1 500-696716 Electro-Mech. HIDB Horn w/110CD Sync. Strobe 2557

    U-HNH-S110S-1-W 500-696717 Electro-Mech. HIDB Horn w/110CD Sync. Strobe-White 2557

    U-MCS 500-699701 Multicandela Selectable Strobe 2550

    U-MCS-W 500-699702 Multicandela Selectable Strobe-White 2550

    U-MCS-AR 500-699746 Multicandela Selectable Strobe-Agent Release 2550

    U-MCS-WE 500-648644 Multicandela Selectable Strobe-EVAC White 2550

    U-MCS-6090V 500-699703 Multicandela Selectable Strobe-Retro Plate Mount 2550

    U-MCS-6090V-W 500-699704 Multicandela Selectable Strobe-Retro Plate Mount-White 2550

    U-MH 500-696558 Steady Tone Mini-Horn 2552

    U-MH-W 500-696559 Steady