Fire Pumps, Controllers & Associated Electrical Distribution Aspects

120
FIRE PUMPS, CONTROLLERS & ASSOCIATED ELECTRICAL DISTRIBUTION ASPECTS IEEE - IAS/IES DINNER PRESENTATION APRIL 15, 2009 - by - James S. Nasby Columbia Engineering File: IEEE- IAS_2009_Fire_Pumps-d.ppt

description

Electric Motor Driven Fire Pump Considerations - Power Supply requirements of NFPA-20 - 2007 - NFPA-70 (NEC®) Article 695 - Changes to Articles 700 & 701 in the NEC - Selective Coordination - New §708 - Critical Operations Power Systems - Junction boxes and wiring protective systems.

Transcript of Fire Pumps, Controllers & Associated Electrical Distribution Aspects

Page 1: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

FIRE PUMPS, CONTROLLERS & ASSOCIATED ELECTRICAL DISTRIBUTION ASPECTS

IEEE - IAS/IES DINNER PRESENTATION

APRIL 15, 2009

- by -

James S. Nasby

Columbia Engineering

File: IEEE-IAS_2009_Fire_Pumps-d.ppt

Page 2: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

2

Main Topics Covered: A) Rewritten Power Supply requirements of NFPA-20 -

2007 B) Differences between new requirements and NFPA-20 -

2003 C) Define which sections of NFPA-70 (NEC®) Article 695

are "extract text" from NFPA-20. D) An overview of §695 from the 2005 & 2008 Edition of

the NEC. E) Proposed changes to §695 for the 2010 Edition of the

NEC F) Changes to Articles 700 & 701 in the NEC G) Selective Coordination H) Brief introduction to new §708 - Critical Operations

Power Systems (COPS) I) New requirements for junction boxes and wiring

protective systems. J) Summary of Power Supply Requirements

Page 3: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

3

Fire Pump Power Supplies

Page 4: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

4

NFPA 20 – Standard for the Installation of Stationary Pumps for Fire Protection

Many requirements of Article 695, including power sources, are extracted from NFPA 20

*

* Note: The NEC TCC rejected updating extract text from NFPA-20-2007. Thus the 2008 NEC retained the wording from NFPA-20-2003. An NFPA task group missed the proposal date.

Page 5: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

5

NFPA-20 2007 Chapter 9Electric Drive for Pumps 9.1 General. 9.1.1 This chapter covers the minimum

performance and testing requirements of the sources and transmission of electrical power to motors driving fire pumps.

9.1.2 This chapter also covers the minimum performance requirements of all intermediate equipment between the source(s) and the pump, including the motor(s) but excepting the electric fire pump controller, transfer switch, and accessories (see Chapter 10 Electric-Drive Controllers).

Page 6: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

6

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd

9.1.3 All electrical equipment and installation methods shall comply with NFPA 70, National Electrical Code, Article 695, and other applicable articles.

9.1.4* All power supplies shall be located and arranged to protect against damage by fire from within the premises and exposing hazards.

A.9.1.4 Where the power supply involves an on-site power production facility, the protection is required for the facility in addition to the wiring and equipment.

Page 7: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

7

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd

9.1.5 All power supplies shall have the capacity to run the fire pump on a continuous basis.

No intermittent sources or equipment, except as specifically dictated in NFPA-20 and Article 695. The fire pump may be called upon to run for hours fighting a fire.

9.1.6 All power supplies shall comply with the voltage drop requirements of Section 9.4.

Page 8: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

8

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd

9.2 Normal Power. 9.2.1 An electric motor driven fire pump

shall be provided with a normal source of power as a continually available source.

9.2.2* The normal source of power required in 9.2.1 and its routing shall be arranged in accordance with one of the following:

[Next Slide]

Page 9: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

9

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd (1) Service connection dedicated to the fire pump installation (2) On-site power production facility connection dedicated to the

fire pump installation (3) Dedicated feeder connection derived directly from the

dedicated service to the fire pump installation (4) As a feeder connection where all of the following conditions

are met:(a) The protected facility is part of a multi-building campus style

arrangement.(b) A back-up source of power is provided from a source independent of

the normal source of power.(c) It is impractical to supply the normal source of power through

arrangement 9.2.2(1), 9.2.2(2), or 9.2.2(3).(d) The arrangement is acceptable to the authority having jurisdiction.(e) The overcurrent protection device(s) in each disconnecting means

shall be selectively coordinated with any other supply side overcurrent protective device(s).

(5) Dedicated transformer connection directly from the service meeting the requirements of Article 695 of NFPA 70, National Electrical Code

Page 10: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

10

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd

A.9.2.2 Phase converters that take single phase power and convert it to three phase power for the use of fire pump motors are not recommended because of the imbalance in the voltage between the phases when there is no load on the equipment. If the power utility installs phase converters in its own power transmission lines, such phase converters are outside the scope of this standard and need to be evaluated by the authority having jurisdiction to determine the reliability of the electric supply.

Note: This prohibition becomes mandatory in the 2010 Edition.

Page 11: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

11

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd

9.2.3 For fire pump installations using the arrangement of 9.2.2(1), 9.2.2(2), 9.2.2(3), or 9.2.2(5) for the normal source of power, no more than one disconnecting means and associated overcurrent protection device shall be installed in the power supply to the fire pump controller.

9.2.3.1 Where the disconnecting means permitted by 9.2.3 is installed, the disconnecting means shall meet all of the following:

(1) They shall be identified as being suitable for use as service equipment.(2) They shall be lockable in the closed position.(3)*They shall be located remote from other building disconnecting means.(4)*They shall be located remote from other fire pump source disconnecting

means.(5) They shall be marked Fire Pump Disconnecting Means in letters that are

no less than 1 in. (25 mm) in height and that can be seen without opening enclosure doors or covers.

A.9.2.3.1(3) The disconnecting means should be located such that inadvertent simultaneous operation is not likely.

A.9.2.3.1(4) -- Ditto --

More conditions . . .

Page 12: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

12

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd

9.2.3.2 Where the disconnecting means permitted by 9.2.3 is installed, a placard shall be placed adjacent to the fire pump controller stating the location of this disconnection means and the location of any key needed to unlock the disconnect.

9.2.3.3 Where the disconnecting means permitted by 9.2.3 is installed, the disconnect shall be supervised in the closed position by one of the following methods:

(1) Central station, proprietary, or remote station signal device(2) Local signaling service that will cause the sounding of an

audible signal at a constantly attended location(3) Locking the disconnecting means in the closed position(4) Sealing of disconnecting means and approved weekly

recorded inspections where the disconnecting means are located within fenced enclosures or in buildings under the control of the owner

More conditions . . .

Page 13: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

13

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd

9.2.3.4 Where the overcurrent protection permitted by 9.2.3 is installed, the overcurrent protection device shall be selected or set to carry indefinitely the sum of the locked-rotor current of the fire pump motor(s) and the pressure maintenance pump motor(s) and the full-load current of the associated fire pump accessory equipment.

E.g.: Any OCP must be set to and carry LRA (typically 600% of FLA) of the Fire Pump, or Pumps, plus any other connected loads.

Note that the Fire Pump Controller will hold at least 300% of FLA continuously, or until the Motor, Controller, or Conductors are destroyed. Its Locked rotor tripping time set between 8 seconds and 20 seconds.

Therefore Coordination is assured if the rules are followed.

Page 14: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

14

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd 9.3 Alternate Power. 9.3.1 Except for an arrangement described in 9.3.3*, at least

one alternate source of power shall be provided when the height of the structure is beyond the pumping capacity of the fire department apparatus. * Note: "9.3.6" in the text is in error.

9.3.2* Other Sources. Except for an arrangement described in 9.3.3, at least one alternate source of power shall be provided where the normal source is not reliable. [Annex A.9.3.2 - next slide.]

9.3.3 An alternate source of power is not required where a back-up engine driven or back-up steam turbine driven fire pump is installed in accordance with this standard.

9.3.4 When provided, the alternate source of power shall be supplied from one of the following sources:

(1) A generator installed in accordance with Section 9.6(2) One of the sources identified in 9.2.2(1), 9.2.2(2), 9.2.2(3), or

9.2.2(5) when the power is provided independent of the normal source of power 9.3.5 When provided, the alternate supply shall be arranged so that the power to the fire pump is not disrupted when overhead lines are de-energized for fire department operations.

Page 15: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

15

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd

A.9.3.2 A reliable power source possesses the following characteristics: 1) The source power plant has not experienced any shutdowns of longer than 4 continuous

hours in the year prior to plan submittal. NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, begins to require special undertakings (i.e., fire watches) when a water-based fire protection system is taken out of service for longer than 4 hours. If the normal source power plant has been intentionally shut down for longer than 4 hours in the past, it is reasonable to require a back-up source of power.

2) No power outages have been experienced in the area of the protected facility caused by failures in the power grid that were not due to natural disasters or electric grid management failure. The standard does not require that the normal source of power is infallible. NFPA 20 does not intend to require a back-up source of power for every installation using an electric motor-driven fire pump. Should the normal source of power fail due to a natural disaster (hurricane) or due to a problem with electric grid management (regional blackout), the fire protection system could be supplied through the fire department connection. However, if the power grid is known to have had problems in the past (i.e., switch failures or animals shorting a substation), it is reasonable to require a back-up source of power.

3) The normal source of power is not supplied by overhead conductors outside the protected facility. Fire departments responding to an incident at the protected facility will not operate aerial apparatus near live overhead power lines, without exception. A back-up source of power is required in case this scenario occurs and the normal source of power must be shut off. Additionally, many utility providers will remove power to the protected facility by physically cutting the overhead conductors. If the normal source of power is provided by overhead conductors, which will not be identified, the utility provider could mistakenly cut the overhead conductor supplying the fire pump.

4) Only the disconnect switches and overcurrent protection devices permitted by 9.2.3 are installed in the normal source of power. Power disconnection and activated overcurrent protection should only occur in the fire pump controller. The provisions of 9.2.2 for the disconnect switch and overcurrent protection essentially require disconnection and overcurrent protection to occur in the fire pump controller. If unanticipated unanticipated disconnect switches or overcurrent protection devices are installed in the normal source of power that do not meet the requirements of 9.2.2, the normal source of power must be considered not reliable and a back-up source of power is necessary. Typical methods of routing power from the source to the motor are shown in Figure A.9.3.2. Other configurations are also acceptable. The determination of the reliability of a service is left up to the discretion of the authority having jurisdiction.

Page 16: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

16

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd

9.3.6 Junction Boxes. Where fire pump wiring to or from a fire pump controller is routed through a junction box, the following requirements shall be met:

(1) The junction box shall be securely mounted.(2)*Mounting and installing of a junction box shall not violate

the enclosure type rating of the fire pump controller(s).(3)*Mounting and installing of a junction box shall not violate

the integrity of the fire pump controller(s) and shall not affect the short circuit rating of the controller(s).

(4) As a minimum, a Type 2, dripproof enclosure (junction box) shall be used. The enclosure shall be listed to match the fire pump controller enclosure type rating.

(5) Terminals, junction blocks, and splices, when used, shall be listed.

A.9.3.6(2) See also 10.3.3. [Note: 10.3.3 is fire pump controller Enclosures.]

A.9.3.6(3) See 10.1.2.1, controller short circuit (withstand) rating.

Page 17: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

17

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd 9.3.7 Listed Electrical Circuit Protective System to

Controller Wiring. 9.3.7.1* Where single conductors (individual conductors)

are used, they shall be terminated in a separate junction box. Single conductors (individual conductors) shall not enter the fire pump enclosure separately.

A.9.3.7.1 Cutting slots or rectangular cutouts in a fire pump controller will violate the enclosure type rating and the controller’s short circuit (withstand) rating and will void the manufacturer’s warranty. See also NFPA70, National Electrical Code, Articles 300.20 and 322, for example, for further information.

9.3.7.2* Where required by the manufacturer of a listed electrical circuit protective system or by NFPA70, National Electrical Code, or by the listing, the raceway between a junction box and the fire pump controller shall be sealed at the junction box end as required and in accordance with the instructions of the manufacturer.

9.3.7.3 Standard wiring between the junction box and the controller is acceptable.

A.9.3.7.2 When so required, this seal is to prevent flammable gases from entering into the fire pump controller.

Page 18: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

18

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd

9.3.8 Raceway Terminations. 9.3.8.1 Listed conduit hubs shall be used to

terminate raceway (conduit) to the fire pump controller.

9.3.8.2 The type rating* of the conduit hub(s) shall be at least equal to that of the fire pump controller.

* - U.L. Listed Type (NEMA rating) 9.3.8.3 The installation instructions of the

manufacturer of the fire pump controller shall be followed.

9.3.8.4 Alterations to the fire pump controller, other than conduit entry as allowed by NFPA 70, National Electrical Code, shall be approved by the authority having jurisdiction.

Note: Underlines added by me for emphasis, where ever they appear.

Page 19: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

19

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd

9.4* Voltage Drop. 9.4.1 Unless the requirements of 9.4.2 are met, the

voltage at the controller line terminals shall not drop more than 15 percent below normal (controller-rated voltage) under motor starting conditions.

9.4.2 The requirements of 9.4.1 shall not apply to emergency run mechanical starting. (See 10.5.3.2.)

9.4.3 The voltage at the motor terminals shall not drop more than 5 percent below the voltage rating of the motor when the motor is operating at 115 percent of the full-load current rating of the motor.

A.9.4 Normally, conductor sizing is based on appropriate sections of NFPA70, National Electrical Code, Article 430, except larger sizes could be required to meet the requirements of NFPA 70, Section 695.7 (NFPA20, Section 9.4). Transformer sizing is to be in accordance with NFPA 70, Section 695.5(a), except larger minimum sizes could be required to meet the requirements of NFPA 70, Section 695.7 (NFPA 20, Section 9.4).

Page 20: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

20

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd 9.5 Motors. [Typically a Pump Company responsibility.] 9.5.1 General. 9.5.1.1 All motors shall comply with NEMA MG-1, Motors and

Generators, shall be marked as complying with NEMA Design B standards, and shall be specifically listed for fire pump service. (See Table 9.5.1.1.)

9.5.1.2 The requirements of 9.5.1.1 shall not apply to direct-current, high-voltage (over 600 V), large-horsepower [over 500 hp (373 kW)], single-phase, universal-type, or wound-rotor motors, which shall be permitted to be used where approved.

9.5.1.3 Motors used with variable speed controllers shall additionally meet the applicable requirements of NEMA MG-1, Motors and Generators, Part 31 and shall be marked for inverter duty.

9.5.1.4* The corresponding values of locked rotor current for motors rated at other voltages shall be determined by multiplying the values shown by the ratio of 460 V to the rated voltage in Table 9.5.1.1.

A.9.5.1.4 The locked rotor currents for 460 V motors are approximately six times the full-load current.

Page 21: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

21

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd

9.5.1.5 Code letters of motors for all other voltages shall conform with those shown for 460 V in Table 9.5.1.1*.

Table 9.5.1.1 Locked Rotor Current Motor Designation for NEMA Design B Motors

Motor Designation (Locked Rotor Indicating Code Letter) "F" to and Including:

"J" for 5 Hp, "H" for 7-1/2 & 10 Hp, and "G" for 15 Hp and up.

* Note: There is a recurring problem with motors having higher service factors. Controllers are not designed, built, approved, nor tested for higher service factors.

9.5.1.6 All motors shall be rated for continuous duty. 9.5.1.7 Electric motor-induced transients shall be

coordinated with the provisions of 10.4.3.3 to prevent nuisance tripping of motor controller protective devices.

9.5.1.8 Motors for Vertical Shaft Turbine-Type Pumps. [Pump Supplier Requirements.]

Page 22: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

22

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd 9.5.2 Current Limits. [Typically a Pump Company responsibility.] 9.5.2.1 The motor capacity in horsepower shall be such that the

maximum motor current in any phase under any condition of pump load and voltage unbalance shall not exceed the motor-rated full-load current multiplied by the service factor.

9.5.2.2 The following shall apply to the service factor: (1) The maximum service factor at which a motor shall be used is

1.15. (2) Where the motor is used with a variable speed pressure

limiting controller, the service factor shall not be used. 9.5.2.3 These service factors shall be in accordance with NEMA

MG-1, Motors and Generators. 9.5.2.4 General-purpose (open and dripproof) motors, totally

enclosed fan-cooled (TEFC) motors, and totally enclosed nonventilated (TENV) motors shall not have a service factor larger than 1.15.

9.5.2.5 Motors used at altitudes above 3300 ft (1000 m) shall be operated or derated according to NEMA MG-1, Motors and Generators, Part 14.

Note: Motors should also be derated for higher ambient temperatures and for any voltage unbalance exceeding 1% per NEMA Standard MG-1.

Page 23: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

23

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd 9.5.3 Marking. [Pump & Motor Supplier

Requirements.]

9.6 On-Site Standby Generator Systems. 9.6.1 Capacity. 9.6.1.1 Where on-site generator systems are used to

supply power to fire pump motors to meet the requirements of 9.3.2, they shall be of sufficient capacity to allow normal starting and running of the motor(s) driving the fire pump(s) while supplying all other simultaneously operated load(s) while meeting the requirements of Section 9.4.

9.6.1.2 A tap ahead of the on-site generator disconnecting means shall not be required.

Page 24: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

24

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd

9.6.2* Power Sources. 9.6.2.1 On-site standby generator systems shall comply with

Section 6.4 and shall meet the requirements of Level 1, Type 10, Class X* systems of NFPA 110, Standard for Emergency and Standby Power Systems.

*Sufficient fuel supply so generator can operate for eight hours at 100% capacity of the pump and other demands (Class “8”).

9.6.2.2 The fuel supply capacity shall be sufficient to provide 8 hours of fire pump operation at 100 percent of the rated pump capacity in addition to the supply required for other demands.

9.6.3 Sequencing. Automatic sequencing of the fire pumps shall be permitted in accordance with 10.5.2.5.

9.6.4 Transfer of Power. Transfer of power to the fire pump controller between the normal supply and one alternate supply shall take place within the pump room.

A.9.6.2 Where a generator is installed to supply power to loads in addition to one or more fire pump drivers, the fuel supply should be sized to provide adequate fuel for all connected loads for the desired duration. The connected loads can include such loads as emergency lighting, exit signage, and elevators.

Page 25: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

25

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd

9.6.5* Protective Devices. Where protective devices are installed in the on-site power source circuits at the generator, such devices shall allow instantaneous pickup* of the full pump room load.

A.9.6.5 Generator protective devices, where used, need to be sized to allow the generator to allow instantaneous pickup of the full pump room load. This includes starting any and all connected fire pumps in the across-the-line (direct on line) full voltage starting mode. This is always the case when the fire pump(s) is running by use of the emergency mechanical operator of 10.5.3.2

*Assume that any and all pumps are running with the Mechanical Manual Operator latched in. E.g.: Starting will be A-T-L and simultaneous for all fire pumps on the generator.

Page 26: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

26

NFPA-20-2003 Chapter 9Electric Drive for Pumps - Review 9.1 General. 9.1.1 (Scope) Same as or similar to 2007 text. 9.1.2 - Ditto. 9.1.3 - Ditto. 9.2 Power Source(s). 9.2.1 General. 9.2.1.1 Power shall be supplied to the electric

motor driven fire pump by a reliable source or two or more approved independent sources, all of which shall make compliance with Section 9.4 possible.

9.2.1.2 Where electric motors are used and the height of the structure is beyond the pumping capacity of the fire department apparatus, a second source in accordance with 9.2.4 shall be provided.

Page 27: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

27

NFPA-20 2003 Chapter 9Electric Drive for Pumps - cont'd

9.2.2 Service. Where power is supplied by a service, it shall be located and arranged to minimize the possibility of damage by fire from within the premises and exposing hazards.

9.2.3* On-Site Electrical Power Production Facility. Where power is supplied to the fire pump(s) solely by an on-site electrical power production facility, such facility shall be located and protected to minimize the possibility of damage by fire.

9.2.4* Other Sources. For pump(s) driven by electric motor(s) where reliable power cannot be obtained from one of the power sources of 9.2.2 or 9.2.3, one of the following arrangements shall be provided:

(1) An approved combination of two or more of the power sources in Section 9.2

(2) One of the approved power sources and an on-site standby generator (see 9.2.5.2)

(3) An approved combination of feeders constituting two or more power sources, but only as permitted in 9.2.5.3

(4) An approved combination of one or more feeders in combination with an on-site standby generator, but only as permitted in 9.2.5.3

(5) One of the approved power sources and a redundant fire pump driven by a diesel engine complying with Chapter 11

(6) One of the approved power sources and a redundant fire pump driven by a steam turbine complying with Chapter 13

Page 28: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

28

NFPA-20 2003 Chapter 9Electric Drive for Pumps - cont'd

9.2.5 Multiple Power Sources to Electric Motor Driven Fire Pumps.

9.2.5.1 Arrangement of Multiple Power Sources. Where multiple electric power sources are provided, they shall be arranged so that a fire, structural failure, or operational accident that interrupts one source will not cause an interruption of the other source.

9.2.5.2 On-Site Standby Generator. Where alternate power is supplied by an on-site generator, the generator shall be located and protected in accordance with 9.2.2 and Section 9.6.

Page 29: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

29

NFPA-20 2003 Chapter 9Electric Drive for Pumps - cont'd 9.2.5.3 Feeder Sources. 9.2.5.3.1 This requirement shall apply to

multibuilding campus-style complexes with fire pumps at one or more buildings.

9.2.5.3.2 Where sources in 9.2.2 and 9.2.3 are not practicable, with the approval of the authority having jurisdiction, two or more feeder sources shall be permitted as one power source or as more than one power source where such feeders are connected to or derived from separate utility services.

9.2.5.3.3 The connection(s), overcurrent protective device(s), and disconnecting means for such feeders shall meet the requirements of 9.3.2.2.3.

Page 30: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

30

NFPA-20 2003 Chapter 9Electric Drive for Pumps - cont'd

9.2.5.4 Supply Conductors. Supply conductors shall directly connect the power sources to either a listed combination fire pump controller and power transfer switch or to a disconnecting means and overcurrent protective device(s) meeting the requirements of 9.3.2.2.3.

9.2.5.5 Two or More Alternate Sources. Where the alternate source consists of two or more sources of power and one of the sources is a dedicated feeder derived from a utility service separate from that used by the normal source, the disconnecting means, overcurrent protective device, and conductors shall be installed in accordance with NFPA 70.

Note: OCP of the Emergency (Alternate) Power Supply need not hold LRA indefinitely. It must, however, allow ATL starting of all fire pump loads.

Page 31: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

31

NFPA-20 2003 Chapter 9Electric Drive for Pumps - cont'd

9.3* Power Supply Lines. 9.3.1* Circuit Conductors. Circuits feeding fire

pump(s) and their accessories shall be dedicated and protected to resist possible damage by fire, structural failure, or operational accident.

9.3.2* Power Supply Arrangement. 9.3.2.1 Power Supply Connection. 9.3.2.1.1 Unless the requirements of 9.3.2.1.2 are

met, the power supply to the fire pump shall not be disconnected when the plant power is disconnected.

9.3.2.1.2 The requirements of 9.3.2.1.1 shall not apply where the installation is approved in accordance with 9.2.5.3; the disconnection of plant power to the fire pumps shall be permitted under circumstances that automatically ensure the continued availability of an alternate power supply.

Page 32: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

32

NFPA-20 2003 Chapter 9Electric Drive for Pumps - cont'd

9.3.2.2 Continuity of Power. 9.3.2.2.1 General. Circuits that supply electric motor

driven fire pumps shall be arranged to prevent inadvertent disconnection, as covered in 9.3.2.2.2 or 9.3.2.2.3.

9.3.2.2.2* Direct Connection. The supply conductors shall directly connect the power source to either a listed fire pump controller or listed combination fire pump controller and power transfer switch.

9.3.2.2.3 Supervised Connection. 9.3.2.2.3.1 A single disconnecting means and associated

overcurrent protective device(s) shall be permitted to be installed between a power source remote from the pump room and one of the following:

(1) A listed fire pump controller(2) A listed fire pump transfer switch(3) A listed combination fire pump controller and power transfer

switch

Page 33: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

33

NFPA-20 2003 Chapter 9Electric Drive for Pumps - cont'd

9.3.2.2.3.2 All disconnecting means and overcurrent protective device(s) that are unique to the fire pump loads shall comply with all of the requirements in 9.3.2.2.3.2(A) through 9.3.2.2.3.2(E).

(A) Overcurrent Device Selection. The overcurrent protective device(s) shall be selected or set to carry indefinitely the sum of the locked-rotor current of the fire pump motor(s) and the pressure maintenance pump motor(s) and the full-load current of the associated fire pump accessory equipment when connected to this power supply.

(B) Disconnecting Means. The disconnecting means shall be as follows:(1) Identified as being suitable for use as service equipment(2) Lockable in the closed position(3) Located sufficiently remote from other building or other fire pump source disconnecting

means that inadvertent contemporaneous operation would be unlikely

(C) Disconnect Marking. The disconnecting means shall be marked Fire Pump Disconnecting Means. The letters shall be at least 25 mm (1 in.) in height, and they shall be visible without opening enclosure doors or covers.

(D) Controller Marking. A placard shall be placed adjacent to the fire pump controller stating the location of this disconnecting means and the location of the key (if the disconnecting means is locked).

(E) Supervision. The disconnecting means shall be supervised in the closed position by one of the following methods:

(1) Central station, proprietary, or remote station signal device(2) Local signaling service that will cause the sounding of an audible signal at a constantly

attended location

(3) Locking the disconnecting means in the closed position(4) Sealing of disconnecting means and approved weekly recorded

inspections where the disconnecting means are located within fenced enclosures or in buildings under the control of the owner

Page 34: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

34

NFPA-20 2003 Chapter 9Electric Drive for Pumps - cont'd

9.3.2.2.3.3 For systems installed under the provisions of 9.2.5.3 only, such additional disconnecting means and associated overcurrent protective device(s) shall be permitted as required to comply with the provisions of NFPA 70, National Electrical Code.

9.3.2.2.4 Short Circuit Coordination. For systems installed under the provisions of 9.2.5.3 only, and where more than one disconnecting means is supplied by a single feeder, the overcurrent protection device(s) in each disconnecting means shall be selectively coordinated with any other supply side overcurrent protective device(s).

Page 35: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

35

NFPA-20 2003 Chapter 9Electric Drive for Pumps - cont'd

9.3.2.2.5 Transformers. Where the supply voltage is different from the utilization voltage of the fire pump motor, a transformer with primary disconnecting means and overcurrent protective devices meeting the requirements of 9.3.2.2.3 and Article 695 of NFPA 70, National Electrical Code, shall be installed.

Page 36: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

36

NFPA-20 2003 Chapter 9Electric Drive for Pumps - cont'd

9.4* Voltage Drop. - Same as 2007 text.

9.5 Motors. - Same as 2007 text, except for requiring marking of variable speed motors for inverter duty.

9.5.2 Current Limits. - Same except for limiting duty cycle incursion for variable speed duty motors.

9.6 On-Site Standby Generator Systems. - Same as 2007 text except for minor re-wording of 9.6.1.1 and 9.6.5

Page 37: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

37

NFPA-20 2003 Chapter 9Electric Drive for Pumps - cont'd

Items new to 2007 edition (not in 2003):

- Junction Boxes.

- Listed Electrical Circuit Protective System to Controller Wiring.

- Raceway Terminations.

Page 38: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

38

NFPA-70 2008* (NEC) Article 695Extracted Text from NFPA-20

* Note: 2005 & 2008 Editions of §695 differ little.

695.2 Definitions. 695.3 Power Source(s) for Electric Motor-

Driven Fire Pumps. 695.4 Continuity of Power [Normal Power] 695.7 Voltage Drop. 695.9 On-Site Standby Generator

Systems. 695.10 Listed Equipment. 695.12 Equipment Location. 695.14(A thru D) Control Wiring.

Page 39: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

39

NFPA-70 2008 (NEC) Article 695Non-Extract Text

695.1 Scope. 695.5 Transformers. 695.6 Power Wiring. 695.14(E) and 695.14(F) Control Wiring

Page 40: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

40

NFPA-70 2008 (NEC) Article 695Extract Text Not Yet Added

695.10 Junction Boxes 695.11 Listed Electrical Circuit

Protective System to Controller Wiring

695.12 Raceway Terminations

Page 41: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

41

What is Covered by NEC Article 695

Electrical power sources (Extract Text) Interconnecting circuits Switching and control equipment

dedicated to fire fire pump drivers. E.g.: Service Entrance Gear.

695.1(A)695.1(A)

Power Sources Control Circuits Control Equipment

Fire Pump

Page 42: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

42

What Is Not Covered By Article 695 System Performance -- NFPA-20 E.g.

Fire Pump Controllers and Transfer Switches.

Maintenance -- NFPA-25 Acceptance testing -- NFPA-20 Routine (Periodic) Testing -- NFPA-25 Jockey pumps -- NEC Article 430 Alarm Systems -- NFPA-72

COVERED

695.1(B)695.1(B)

Page 43: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

43

Overview of Article 695 (2005 & 2008) Non-Extract Text

To be Covered Power Supply Section:

695.5 Transformers.

695.6 Power Wiring.

695.14(E) & (F) Control Wiring

Page 44: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

44

Proposed changes to §695 for the 2010 NEC

Coordination with 2007 NFPA-20 still in doubt.Several proposed changes to extract text

accepted.

Proposals to update extract text rejected as of now.

Use of EMT in the pump room accepted.

Junction Boxes per NFPA-20 may get added.

Page 45: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

45

Salient Changes to Articles 700 & 701

700.6(C) ATS (600 Vac or less) shall be Listed. 700.9(B)(5) Separate wiring and sections for

Legally Required circuits (from other Legally Required or Standby circuits).

700.9(D)(1)(4) fire rated ass'y must be Listed 1-hour

700.9(D)(3) Gen-set control wiring separated 700.12(B)(6) Outdoor Gen-Set Disconnect per

225.36 700.23 Dimmer Systems with Emergency

Lighting 700.27 (Selective Coord.) Exception: (1) Xfmr. Single

Pri. & Sec. OCP, and, (2) Identical Series OCP's.

Page 46: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

46

Salient Changes to §700 & 701 - cont'd

701.7 (C) ATS (600 Vac or less) shall be Listed. 701.10(B)(5) Outdoor Gen-Set Disconnect per

225.36 701.18 (Selective Coord.) Exception: (1) Xfmr.

Single Pri. & Sec. OCP, and, (2) Identical Series OCP's.

And also in Article 702:

702.11(B)(5) Outdoor Gen-Set Disconnect per 225.36

Page 47: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

47

Brief introduction to new §708 - Critical Operations Power Systems (COPS)

I. General -- Note: First of five sections. 708.1 Scope. …installation, operation, monitoring, control, and

maintenance of the portions of the premises wiring … to designated critical operations areas (DCOA)… Critical operations power systems are … classed by … codes by any gov'al agency having jurisdiction or by facility engineering documentation establishing the necessity for such a system. These systems include but are not limited to power systems, HVAC, fire alarm, security, communications, and signaling for designated critical operations areas.

708.2 708.2 Definitions.Commissioning. Critical Operations Power Systems (COPS). Designated Critical Operations Areas (DCOA).Supervisory Control and Data Acquisition (SCADA).

708.3 Application of Other Articles. Except as modified by this article, all applicable articles of this Code shall apply.

708.4 Risk Assessment. 708.5 Physical Security. 708.6 Testing and Maintenance. 708.8 Commissioning.

Page 48: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

48

Brief introduction to new §708 - Critical Operations Power Systems (COPS)

II. Circuit Wiring and Equipment III. Power Sources and Connection IV. Overcurrent ProtectionV. System Performance and Analysis 708.52 Ground-Fault Protection of Equipment.

(D) Selectivity. Ground-fault protection for operation of the service and feeder disconnecting means shall be fully selective such that the feeder device, but not the service device, shall open on ground faults on the load side of the feeder device. A six-cycle minimum separation between the service and feeder ground-fault tripping bands shall be provided. Operating time of the disconnecting devices shall be considered in selecting the time spread between these two bands to achieve 100 percent selectivity.

708.54 Coordination. Critical operations power system(s) overcurrent devices shall be selectively coordinated with all supply side overcurrent protective devices.

Page 49: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

49

New requirements for junction boxes and wiring protective systems.

Requirements for how to install is per NFPA-20 Section 9.3.6.

When required is per Per NFPA-20 Section 9.3.7.

Note: These junction boxes are ahead of the fire pump controller.

Page 50: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

50

Junction Box Required when…

9.3.7.1* Where single conductors (individual conductors) are used, they shall be terminated in a separate junction box. Single conductors (individual conductors) shall not enter the fire pump enclosure separately.

These are typically MI cables with solid wire.

- Splices to Stranded Wire Required (Breaker Lugs are Rated only for Stranded Wire.

- Separate cables will create a magnetically induced (eddy) current in ferrous metal (steel). This can easily heat #14 gage steel to red hot.

- A nonferrous (Aluminum) junction box or plate is used since no current is generated.

- Controllers were being hacked up, which violates both their NEMA Enclosure Type rating and the WIC rating.

Page 51: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

51

Junction Box Required when…9.3.7.2* Where required by the manufacturer

of a listed electrical circuit protective system or by NFPA70, National Electrical Code, or by the listing, the raceway between a junction box and the fire pump controller shall be sealed at the junction box end as required and in accordance with the instructions of the manufacturer.

This is usually for type Type RHW Listed High Temperature Wire. These give off flammable smoke when routed thru the fire zone. The controller is an arcing (sparking) device (open contactors); and, therefore requires a junction box and seal to keep smoke from entering the controller thru the incoming conduit.

Page 52: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

52

Power Supply requirements of NFPA-20-2007

1 - Applicable Standards 2 - Power Source(s) for Fire Pumps 3 - Continuity of Power to a Fire Pump 4 - Transformers in the Fire Pump Circuit 5 - Power Wiring to a Fire Pump 6 - Other Requirements 7 - Rules of Thumb (For Reference Only) 8 - Fault Current Considerations

Page 53: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

53

1 - Applicable StandardsNFPA 20 Fire Pump Standard -and-

NFPA 70, the NEC®Article 695 NFPA-20 - Chapter 9 - Electric Drive for Pumps NFPA-70 (NEC®) Section 695 - Installation of

Electrical Equipment NFPA-25 - Inspection, Testing, and Maintenance

of Water-Based Fire Protection Systems- also -

Local Codes, E.g.: - Chicago Electrical Code (CEC ) - 2008 (2002 NEC)- Chicago Fire Prevention Code - 1999 (1993 NFPA 20)

Insurance Company Requirements (F.M. & etc.)

Page 54: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

54

Power Source(s) forElectric Motor Drive Fire Pumps

General Philosophy Permitted power source(s) Individual power sources(s) Multiple power sources Power source(s) performance

Maximum Voltage Drops

Page 55: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

55

General Philosophy . . . of Article 695 -and- NFPA-20 Fire Pump sources and components

must be Reliable, and

Should the Fire Pump Be Called Upon to Function, It Is Considered Sacrificial*

NFPA 20 and 695.3

* Sacrificial is best summed up by the phrase: "Run it to destruction."

E.g.: Never stop a running fire pump if it might still deliver fire water.

Page 56: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

56

2 - Power Sources forElectric Motor Driven Fire Pumps Requirements focus on the continuous

uninterrupted operation of the fire pump. Electrical safety is considered a

secondary objective. Fire pump equipment is considered

sacrificial. As such, Equipment and Conductors

constitute a fire hazard. Fire Protection of the premise and

occupants of paramount importance. Protection of the premise and operators

from shock and arc-flash hazard and fire hazard from the installation.

Page 57: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

57

Permitted Types of Power Sources for Electric Motor Driven Fire Pumps

Individual Power SourceUtility Service On-Site Power Production Plant

Multiple (other) Power SourcesAbove twoStand-by Gen-setFeeder Sources(Campus like Complexes)

Page 58: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

58

Summary of Power Supply Requirements

Power to be supplied by a (one) reliable source

Or by at least two approved independent (other) sources.

-- however --

Where height of building is beyond pumping capacity of the fire department, an emergency or back-up power supply is mandatory.

-and- Additional Chicago Requirements

Page 59: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

59

Reliable Electric Power Source . . .

To consist of Electrical Service or Private Power Station - where -

Infrequent disruption from environmental or man-made conditions

Contains a separate service connection -or- connection to the supply side of the building’s service entrance disconnect means

Determination of reliability up to discretion of the AHJ (Authority Having Jurisdiction).

Page 60: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

60

Individual Power Sources . . .

1. Separate Service, or

2. Tap Ahead of the Premise

(Plant or Building) Service Equipment

- or -

3. On-Site Power Production Facility

(On-Site “24-7” Power Plant)

695.3(A)695.3(A)

Page 61: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

61

Separate Service as an Individual Power Source.

Separate utility service dedicated to the fire pump

Permitted by Section 230.2 Shall comply with all applicable rules of Chapters 1-4, including Article 250.

Page 62: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

62

Each Individual Power Source

Must be Located –

and Arranged to Minimize Possibility of Damage By Fire.

“…sufficiently remote…” 230.72(B)

And, both must have signs at both location. 230.2(E)

Page 63: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

63

Power Supply Arrangement

Power supply to pump is to be maintained when building normal power is disconnected.

Exception for feeder circuit serving as one source - disconnection of plant power to fire pumps permitted if alternate source is continually available

Page 64: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

64

Tap Ahead of the Building Service

Equipment requirements are the same as for a separate service

Installed according to Part D of Article 230, service entrance conductors; e.g.: 230.82(4), 230.2(A)(1), 230.72(B),

Be capable of carrying the locked-rotor current (LRC) of the Fire Pump and all connected all equipment loads continuously

Be "…from a connection located ahead of and not within the same cabinet, enclosure, or vertical switchboard section as the service disconnecting means…"

695.3(A)(1) & 695.6(D)695.3(A)(1) & 695.6(D)

Page 65: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

65

On-site Power Production Facility

A facility (e.g. a power plant) that produces its own power on a Continuous basis

Similar to separate service requirements

Located and protected to to minimize the risk of damage by fire

Not a standby gen-set

695.3(A)(2)695.3(A)(2)

Page 66: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

66

Multiple Power Sources - When Needed

The Term “Reliable” Is a Decision for “The Authority Having Jurisdiction”.

“Reliable” Is Defined as “Capable of Being Relied On; Dependable, or Trustworthy”.

All Sources Must Be Approved by “The Authority Having Jurisdiction”.

ReliableDependable

Trustworthy

695.3(B)

Page 67: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

67

Multiple Power Sources -- Other Electric Power Sources

Where a Reliable Power Source is NOT available, redundant (Multiple) supplies are to be provided as follows:Another Service or Private Power StationOn-site standby GeneratorCombination of Feeders from Two

Separate Utility SourcesCombination of One or More Feeders

and an Onsite GeneratorDiesel Engine driven Fire PumpSteam Turbine driven Fire Pump

Page 68: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

68

Examples of Multiple Power Sources

1) Dual Utility Service 2) Utility Service plus On-Site

Gen-Set 3) Combination of Feeders from

separate Services ** 4) Combination of Feeder and On-

site standby generator **

** Only allowed on multi-building, campus style complexes.

Page 69: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

69

Examples of Multiple Power Sources NFPA-20 Section 9.2, Power Sources

(1) Combination of Services and/or On-site Power Facilities.

Fire Pump Controller

Service #1 Service #2

MFire Pump

Motor

Page 70: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

70

Examples of Multiple Power Sources NFPA-20 Section 9.2, Power Sources

(2) Combination of Service or OPF and On-site standby generator.

Note: Emergency side Circuit Breaker becomes Mandatory in the 2010 Edition.

M

Service On-site standby Generator

G

Fire Pump Controller

Page 71: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

71

Examples of Multiple Power Sources NFPA-20 Section 9.2, Power Sources

(3) Combination of Feeders from separate Services.

Only allowed on multi-building, campus style complexes.

Service #2Service #1

High Voltage

Substation

Feeders

Fire Pump Controller

M

Page 72: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

72

Examples of Multiple Power Sources NFPA-20 Section 9.2, Power Sources

(4) Combination of Feeder and On-site standby generator.

Only allowed on multi-building, campus style complexes.

On-site Standby Generator

Service

FeedersFire Pump Controller

M

High Voltage Substation

G

Page 73: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

73

Examples of Multiple Power Sources NFPA-20 9.2, Power Sources (Tap Ahead . . .)

The fire pump power supply shall not be disconnected when plant power is disconnected.

The exception permits this only for multi-building, campus-style complexes that automatically ensure alternate power is still available.

Service

FeedersFire Pump Controller

M

Plant Power Disconnect

Page 74: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

74

Multiple Power Sources -On-site Generator

Generators to be of sufficient capacity to allow normal starting and running of the motor(s) driving the fire pump(s) while supplying all other simultaneously operated load(s).

Where protective devices are installed, they must allow instantaneous pickup of full pump room load. E.g. Across-the-Line Starting of all pumps.

Transfer of power to take place in the pump room

Meet Both Voltage Drop Requirements (15% & 5%)

Page 75: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

75

Arrangement IController - Xfer. Switch

Combination

A “Combination Fire Pump Controller and Power Transfer Switch” unit must . . .

Be Listed as a coordinated designed and factory assembled and wired complete unit

Need have only Normal Side Breaker unless the Emergency Source is a Utility (need to specify Emergency Side Breaker when needed).

Will already meet all requirements of NFPA-20, Section 10.8

Page 76: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

76

Arrangement IITransfer Switch Ahead of

ControllerA transfer switch ahead of a fire pump must . . . Be a Listed “Fire Pump Power Transfer Switch” Be Listed and Rated for the Available Fault

Current. NFPA 20, 9.1.2.2 Be Protected by Listed Service Equipment Meet all requirements of NFPA-20, Sections

10.8.1, 10.8.2.2 & 10.8.3

Approximately 31 clauses including interconnections and WIC Short Circuit Coordination. See Nasby Application Notes.

mastercontrols.com/EngInfo/Articles/Nasby/EFPXS-2B_WP5.PDF

Page 77: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

77

Arrangements I & II

Note: “Alternate Source” may be a “Hot Emergency Bus” as often employed in hospitals.

In these systems, multiple MVA size gen-sets are used along w/ additional upstream Transfer Switches with a path to one or more Utility Connections.

This often results in very high fault currents on the Alternate Source Side.

Also note that two C/Bs will be required in all Arrangement I units per 2010 Edition of NFPA-20.

Page 78: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

78

Multiple Power Sources - Summary

Where Reliable Power Cannot Be Obtained from a Single Source,

Two or More Sources Shall Be Required.

The Sources to Select from are Limited to Those Covered in Section 695.3.

Multiple Sources are Required Where Building Height Exceeds Fire Department Pumping Capacity.

695.3(B)695.3(B)

Page 79: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

79

Maximum Allowed Voltages Drops – Motor Starting

NEC Chapter 9 Table 9 Note 2 must be used for motor starting cable voltage drops. To wit:

2. Effective Z is defined as R cos(θ) + X sin(θ), …effective impedance (Ze) can be calculated from R and XL values given in this table as follows: Ze = R × PF + XL sin[arccos(PF)].

Note: Typical Motor Locked Rotor Impedance is 0.30 to 0.40. Use 0.30 for worse case, especially for larger motors.

Voltage Drop Calculations must include:Transformer, if used

Cables: Normal, Emergency (gen-set) & Transformer Primary

Utility Source (Utility transformer)9.4 & 695.79.4 & 695.7

Page 80: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

80

Maximum Allowed Voltages Drops – Motor Running

During Motor Running at 115% of Motor FLA, a 5% Maximum Voltage Drop at the Motor Terminals.

Note: This is to Prevent Motor Overheating. See NEC Chapter 9, Table 9 for cable A.C. Impedances

(Resistance & Reactance).

Note: The 0.85 PF column may be used for the 115% running voltage

drop; but, NOT for the starting voltage drop. See NEMA ICS-14 for example of voltage drop calculations.

Available at: mastercontrols.com/EngInfo/Standards/ICS-14.PDF

-or- www.nema.org/stds/ics14.cfm [Requires log-in]

Note: The Starting drop is often worse than the Running drop but not always.

9.4 & 695.79.4 & 695.7

Page 81: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

81

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd

NEMA ICS-14 - Table of ContentsApplication Guide for Electric Fire Pump Controllers

1. GENERAL2. DESIGN CONSIDERATIONS2.1 Power Conductors Connected To The Fire Pump Controller And

MotorNote: 2.1.1 is a suggested procedure for properly sizing power

supply conductors to the fire pump controller and motor to meet the 5% & 15% Voltage Drop requirements.

2.2 Environmental Considerations For Enclosures2.3 Transformer Sizing2.4 Transfer Switch Considerations [Note "Arrangement IV]See: mastercontrols.com/EngInfo/Articles/Nasby/EFPXS-2B_WP5.PDF

2.5 Considerations For Specifying Short Circuit Rating (RMS Sym)Note: Includes tables for conductor lengths -versus- Short Circuit Circuits.

Important since 100 KAmp controller Short Circuit Rating (WIC) is no longer standard.

Page 82: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

82

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd

NEMA ICS-14 Table of Contents -- Continued.

2.6 Reduced Voltage Starting Methods2.7 Limited Service Controller Limitations 2.8 Listed Fire Pump Motor Applications2.9 Pressure Recorders2.10 Controlling Engine Dampers2.11 Stand-by Generator Sizing for Fire Pumps2.12 Medium Voltage Fire Pump Controllers3. INSTALLATION CONSIDERATIONS

3.1 Phase Sequence3.2 Normal Starting with On-site Generators3.3 Induced Voltages on Alarm Contacts

4. OTHER CONSIDERATIONS4.1 Listed and Approved Equipment4.2 Testing and Maintenance

Page 83: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

83

3 - Continuity of Power

Goal – Minimize risk of inadvertent disconnection from supply.

Connect fire pump directly to electric supply (Controller used as Service Entrance)*-or-

Limit number of disconnecting means Supervision - Monitor Fire Pump Power

circuit disconnecting means status

* Most or all Electric Motor Drive Fire Pump Controllers are Listed as Suitable for Use as Service Entrance (SUSE).

695.4695.4

Page 84: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

84

Physical Protection of Electric Power Supplies

Power sources to be located and arranged to minimize the possibility of damage by fire from within the premises and exposing hazards.

Private Power Station may be given consideration as an acceptable supply where located in a separate power house or cut off from main buildings

Multiple power sources to be arranged so a fire at one source will not cause an interruption at the other source.

Supply conductors to be dedicated and protected to resist possible damage by fire, structural failure, or operational accident especially overhead lines. See 9.4.3(2).

Page 85: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

85

Methods of Achieving Continuity

Direct Connection

Supervised Connection (Upstream OCP)

M

FIRE PUMP CONTROLLER

XSERVICE POINT

FIRE PUMP

FIRE PUMP CONTROLLER

FIRE PUMP

XSERVICE POINT

SERVICE DISCONNECTING

MEANS

M

695.4

Page 86: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

86

The Overcurrent Protection . . . The Overcurrent Protection Is Set to carry

indefinitely the sum of the locked rotor current of the fire pump, jockey pump motors and full-load current of associated fire pump equipment

Exception: Additional devices for campus style feeder sources - to comply with NFPA 70 §695

Note: The F.P.C. Internal overcurrent protection (except for Limited Service units) is set to: - Never trip below 300% of motor FLA -and- - Locked rotor tripping time set between 8 seconds and 20 seconds

Page 87: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

87

Typical Fire Pump Controller Breaker Curve

EC Series - "F" Frame Breaker Trip Curve

0.001

0.01

0.1

1

10

100

1000

10000

1 10 100 1,000 10,000

Multiples of Range Setting

Tri

p T

ime

(Sec

onds

)

8 to 20 Seconds at LRA

Page 88: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

88

Fire Pump Controller Circuit Breaker

The Circuit Breaker within a Fire Pump Controller: Won't trip below 300% of motor FLA LRA trip time between 8 seconds and 20

seconds Rated at a minimum of 115% of FLAE.g.: FLA can be up to 87% of breaker frame rating. Ditto

for the I/S (Isolating Switch) Most or all EFPC C/B's are molded case

switches with external CT's and trip circuitry. Series devises (I/S & C/B) often result in

controller Short Circuit Ratings (WIC) well above the I.C. (Interrupt Capacity) of the molded case device (switch).

Note: One EFPC Mfr. has been using jacks in lieu of an I/S.

Page 89: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

89

Additional Disconnect Requirements

A Key Is Placed at the Fire Pump Controller, if the Disconnecting Means Is Locked, and

A Placard is Installed on the Disconnecting Means, and

An Additional Placard Is Installed at the Fire Pump Controller, and

The Disconnecting Means Is Supervised in the Closed (“ON”) Position

FIRE PUMP CONTROLLER

FIRE PUMP

XSERVICE POINT

SERVICE DISCONNECTING

MEANS

M

695.4(B)695.4(B)

Page 90: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

90

4 - Transformers for Fire Pump Circuits

A Transformer is Permitted Where the Supply Voltage Is Different from the Fire Pump and Controller Requirements

It is Dedicated to Fire Pump and Associated Equipment or

Except that Transformers on Multi-Building Complexes are Permitted to Supply Other Loads

695.5695.5

Page 91: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

91

Transformers for Fire Pump Circuits

Service at Other than Utilization Voltage

Where “Service” is Above 600 Volts either a:

Listed Medium Voltage Fire Pump Controller(s) and Motor(s) if below 7.2 kV -or-

A Transformer(s) is allowed per NFPA-20 9.3.2.2(5) if it complies with 9.2.3

(Supervised Connection) and withNEC Article 695.5 (Transformers).

Page 92: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

92

Power

Supply

Arrangement

'A' & 'B'

for

Normal Source

Note:

Figure number should be A.9.2.2(5).

Page 93: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

93

MM

JockeyPump Disconnect, Overcurrent Protection, and Motor Controller

Jockey PumpFire Pump

Listed Fire Pump Controller

Primary Overcurrent Protection Only

Dedicated Transformer

Jockey Pump Tap Conductors

Secondary Conductors, Overcurrent Protection NOT Permitted

Transformer Dedicated to Fire Pump

695.5695.5

Page 94: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

94

Transformer Sizing Minimum Sizing Shall Be at Least 125%* of the

Sum of: The Full Load of the Fire Pump Motor(s), Plus The Full Load of the Jockey Pump Motor(s) (if applicable), Plus The Full Load of Any Associated Equipment (if applicable). Secondary Side Overcurrent Protection (OCP) is

Not Permitted. E.g.: Line side protection only.

695.5(A)695.5(A)

Note: *125% is almost always too small to meet both voltage drop requirements.

Page 95: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

95

Transformer Overcurrent Protection

The Minimum Selection and Setting of the Primary OCP Shall Be Large Enough to Carry Indefinitely the Equivalent Secondary Currents of the Following:

The Locked-Rotor (600%) Current of the Fire Pump Motor(s), Plus

The Locked-Rotor (600%) Current of the Jockey Pump Motor(s) (if applicable), Plus

The Full Load (100%) Current(s) of Any Associated Equipment (if applicable).

695.5(B)

Page 96: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

96

5 - Power Wiring Service Conductors (Electric Utility) Supply Conductors (On-site Power

Production) Feeder Conductors connected to:

1. On-site standby generator

2. Supervised disconnecting means Feeder Conductors for multi-building (campus style) complexes

695.6695.6

Page 97: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

97

Power Wiring (The Supply Conductors) Shall Be . . . Installed As Service Entrance

Conductors, and Physically Routed Outside the

Building, or where not possible . . . Permitted to Be Routed Through

Building if Installed Under, Or Enclosed Within, Not Less Than 2 Inches of Concrete (See Section 230.6 ).

695.6695.6

Page 98: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

98

Power Wiring - Circuit Conductors on Load Side of Disconnect and

Overcurrent Protection-Within the Building

Shall be protected to resist damage from fire, structural damage or operational failure and

Encased in not less than 2 inches of concrete, or

Installed within 2-hour* fire resistance rated enclosed construction dedicated to the fire pump circuit(s), or

Installed within listed electrical circuit protective systems having a minimum 2-hour (was 1-hour) fire resistance rating.

Remember that these conductors are sacrificial and also are a Fire Hazard*.

* 125% conductors; but, no less than 300% OCP in FPC.

Page 99: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

99

Listed Electrical Circuit Protective Systems

Permitted to Be Routed Through Building if Installed in Listed Electrical Circuit Protective Systems With A Minimum of 2-Hour Fire Resistance.

Note: Not approved in all jurisdictions for Service.

Mineral Insulated Cable

695.6(B)695.6(B)

Page 100: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

100

Electrical Circuit Protective System May Consist of a . . .

2-inch Rigid Conduit with 250 kcmil XHHW, Copper Conductors Installed with a U.L. Listed (Classified) Overall Covering of a 2-Hour* Fire Resistance Blanket System, or

* Was 1-Hour Listed (Classified) Fire-Resistive

Mineral Insulated (MI) Cable Systems,

- and -

Page 101: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

101

Electrical Circuit Protective System May Consist of a . . .

Other Systems and Configurations Are also Listed (Classified).

See “Fire Tests for Electrical Circuit Protective Systems”, UL Subject 1724-1991 for Exact Information.

See U.L. CCN (Guide) FHIT. Details at: www.ul.com Online Certifications

Directory

Page 102: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

102

Section 695.6(B) Exception - Electric and Fire Pump Rooms

Supply Conductors Are Exempt from Fire-Resistance Ratings Only:

In the Electrical Switchgear Room, and In the Fire Pump Room.

Electric Room Fire Pump Room

695.6(B) Exc.695.6(B) Exc.

Page 103: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

103

Wiring Methods for Power Circuits – Within the Pump Room Rigid Metal Conduit Intermediate Metal Conduit Liquidtight Flexible Metal Conduit* Liquidtight Flexible Nonmetallic Conduit (LFNC-B) ** 6 ft. max. per 430.223 Conductor Enclosures Adjacent to

Motors. Listed MC Cable (w/ Impervious Covering) Mineral Insulated Cable (MI) Wiring Method for Control Circuits Are Essentially

the Same.Note: Most common violation is use of BX for motor

whip.

695.6(E)695.6(E)

Page 104: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

104

Fire Pump Controller Controller May Not Be Used As a

Junction Box for Other Circuits. Jockey Pump Connections Not Allowed

to Be Made in Fire Pump Controller.Note: Either Fire Pump Circuit or Local

Branch Power may be used for the Jockey Pump.

695.6(F)695.6(F)

Page 105: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

105

Fire Pump Controller Jockey Pump Controller and Separate Junction Box

695.6(F)695.6(F)

Page 106: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

106

Fine Stranded Wire (Cable) Warning Some Wire and Cable Mfr’s are Making

Multiple Rated Cable, Such as: AWM, MTW & TEW, among other ratings. TEW is a fine stranded type of cable and AWM may be.

Circuit Breakers (Isolating Switch) Incoming Lugs are Not Tested nor Rated for Fine Strand Wire

Ditto for Contactor (Outgoing) Lugs This applies to both Field and Factory

Wiring

Page 107: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

107

6 - Other Requirements

External Control Circuits No Sensors or Remote-Control

Devices Control Wiring Multiple Pumps - Sequential

Starting

695.14695.14

Page 108: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

108

External Fire Pump Control Circuits (Remote Start, Deluge Valve Start, etc.)

Arranged So That Failure of Any External Control Circuit Shall Not Prevent the Operation of The Pump(s) by Other Means.

Circuit Failures Such As Opens, Shorts, Grounds, or Loss of Power Are Permitted to Cause the Pump to Run, but

These Failures Cannot Prevent the Fire Pump from Running.

Note: These are mainly controller responsibilities.

10.5.2.6, 1205.2.5 & 695.14(A)10.5.2.6, 1205.2.5 & 695.14(A)

Page 109: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

109

Prohibited Sensors & Control Devices

Undervoltage, Phase Loss, Frequency Sensitive, or Other Sensors Are Not Permitted, Except…

Motor Single Phase Start Attempt Protection is permitted as part of the fire pump controller.

Remote Devices in the Control Circuit Are Not Permitted if they prevent the automatic operation of the Transfer Switch.

10.4.5.6 & 695.14(b) & (c)10.4.5.6 & 695.14(b) & (c)

Page 110: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

110

Wiring Methods for Control Circuits Rigid Metal Conduit (Threaded) Intermediate Metal Conduit (also

Threaded) Liquidtight Flexible Metal Conduit Listed MC Cable (w/ Impervious Covering) Mineral Insulated Cable (MI) There Are No Exceptions to These Wiring

Methods Not Allowed:

Flexible Metal Conduit (BX & etc.)Thin Wall ConduitRomex or Any Other Bare Cable

695.14(E)695.14(E)

Page 111: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

111

Specify Sequencing of Multiple Pumps when . . .

Automatic sequencing of pumps required in accordance with 9.6.3 (and required by 10.5.2.5).

Note: This eases the starting electrical load. Automatic sequencing of fire pumps

needed for pumps in parallel or in seriesAny pump supplying suction to another pump starts before it (High Zone Delayed Start) -or- if water requirements call for more than one pumping unit to operate (pumps in parallel).

Pumps to start at intervals of 5 to 10 seconds. Failure of any one pump not allowed to prevent others from starting.

Page 112: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

112

7 - Rough Rules of Thumb Transformer or Gen-Set Sizing – 125% almost never

enough Full Voltage (A-T-L) Starting

Often needs 300% to 500% Sizing Reduced Inrush Starting

Often needs 250% to 400% Sizing Depending on:

Device Impedance and Voltage Drops of: Transformer Source and Primary

Wiring Run and Wiring Run to Controller Sizing for Variable Speed depends on Bypass Start

method.For More info. see: mastercontrols.com/EngInfo/Articles/Nasby/Motor-Starting-

Parameters_WP0.pdfFrom: mastercontrols.com/AboutFPC/MCSldA00.htm And: mastercontrols.com/EngInfo/MCEngInf.htm#TechArts

Why not to specify Wye-Delta Starting:mastercontrols.com/EngInfo/Articles/Nasby/Wye-Delta_Starting_White_Paper.pdf

Page 113: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

113

Induction Motor Locked Rotor Codes

Table M-02 -- Motor Locked Rotor Code KVA Data and Allowed Horsepowers

"F" "G" "H" "J" Code Letter

Min. Max. Min. Max. Min. Max. Min. Max.

KVA per Hp 5.00 5.59 5.60 6.29 6.30 7.09 7.10 7.99 LRA/FLA 482% 540% 540% 608% 608% 685% 685% 772% Allowed Hp 15 Hp and up 15 Hp and up 5 thru 10 Hp 5 Hp only

Note: The LRA/FLA ratios shown are approximate for illustration only.

Page 114: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

114

Starting Methods -vs- Motor

Types

Table M-04 - Motor and Starting Types

Starting Type Motor Type Starting Type Motor Type

Full voltage Standard/Any Primary Reactor Standard/Any

Part Winding Part Winding Primary Resistor Standard/Any

Wye Delta - Closed Delta Run Autotransformer Standard/Any

Wye Delta - Open Delta Run Soft Start (SCR) Standard/Any

Neutral Reactor Wye Running Wound Rotor Wound rotor

Page 115: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

Motor Starting Characteristics

Parameter Chart

Fire Pump Starting Type Characteristics - for - Electric Fire Pump Motors and Controllers

Starting Characteristics (at Stall) -- Typical Values -for- Fully Load Pump (1) Starting Starting Starting Accelerate Motor Motor Amps Amps Starting Power Starting Full Load Type Contactors Closed & KVA & KVA Power % F.L. Torque to Starting Type Note Note (3) Transition % LRA % FLA Factor Note (4) % ATL Full Speed Notes Across-the-Line Any 1 N/A 100% 600% 40% 240% 100% Yes (a)

Part Winding Special (2) 2 Yes 65 390 40 156 48 Usually (b) Primary Resistor Any 2 Yes 65 390 80 314 42 Yes (c)

Primary Reactor Any 2 Yes 65 390 28 111 42 Yes (c) Neutral Reactor 6/12 Lead 2 Yes 65 390 28 111 42 Yes (c)

Wye-Delta Open 6/12 Lead 3 No 33/100 200/600 40 80/240 33 No (d) Wye-Delta Closed 6/12 Lead 4 Yes 33/100 200/600 40 80/240 33 No (d)(e)

Soft Start/Stop Any 1/2 Yes 40/67 240/400 Varies Ramps 16/44 Yes (f) Autotransformer Any 3 Yes 46 276 40 110 42 Yes (c)(g)

Page 116: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

Motor Starting Characteristics

Parameter Notes to Chart

Motor Starting Characteristics Chart Notes (1) Refer to Factory details. (2) Part Winding Motors must be wound specifically for this service. Some motors may not

accelerate to full speed in the starting mode. See Note (b). (3) Units with two or more contactors have two basic steps (Accelerate & Run) with steps three

and four being for transitions. (4) Starting KW Power as a percent of motor full load power requirement. (a) Also called "A-T-L" or Direct-On-Line. Motor Power Factor taken as 40%. Other values

shown are due to the effects of the controller. (b) Part Winding Parameters vary with the motor. Starting Amps & KVA vary from around

60% to 70%, Starting Torque from around 45% to 50%. The motor can start a fully loaded pump if it has no large torque dip or cusp. See the text discussion on Part Winding Starting for details.

(c) Figures are for tap set at 65% which yields a motor voltage of 65% of line (mains) voltage. (d) The Dual Figures are for Starting and Transition. The transition values are to finish

accelerating a fully loaded pump. Examples include deluge or open systems, re-starting a fully loaded pump after a power failure or interruption, and failure of another pump feeding the same system.

(e) Ignores the momentary transition resistor loads. (f) Varies with pump load and particular Soft Starter used. Values shown are initial and

maximum for a typical fully loaded pump. MCS uses the second (Start) contactor for isolation. Others use only the Bypass contactor.

(g) The 46% Starting Amps & KVA figures include the Autotransformer exciting current.

Page 117: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

117

Variable Speed Motor Drive Controller

Model ECVRTZ-125-46-*

Page 118: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

118

8 - Fault Current Considerations Controller Short Circuit (WIC) Rating Must

exceed the “Available Short Circuit Current”

Ditto for Arrangement II Upstream Xfer SwitchThis almost always requires upsizing the Xfer

Switch to coordinate with the 600% (Minimum) upstream OCP (Over Current Protection)

Controller and Xfer Switch must be marked with the Short Circuit Rating and be “Suitable” for same.

10.1.2.210.1.2.2

Page 119: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

119

NFPA-20 2007 Chapter 9Electric Drive for Pumps - Cont'd

Motor Starting Slide Show Link: mastercontrols.com/EngInfo/Articles/Nasby/Slide_Shows/

IFPA_Motors_20050111b.ppsFrom: mastercontrols.com/AboutFPC/MCSldA00.htm

Other cited links: mastercontrols.com/EngInfo/Standards/ICS-14.PDF www.nema.org/stds/ics14.cfm [Requires log-in]Also available at: www.nema.org/standards

mastercontrols.com/EngInfo/Articles/Nasby/EFPXS-2B_WP5.PDF mastercontrols.com/EngInfo/Articles/Nasby/Motor-Starting-

Parameters_WP0.pdf mastercontrols.com/EngInfo/Articles/Nasby/Wye-Delta_Starting_White_Paper.pdf

From: mastercontrols.com/EngInfo/MCEngInf.htm#TechArts

www.ul.com Online Certifications Directory

Page 120: Fire Pumps, Controllers & Associated Electrical Distribution Aspects

120

Questions ?

[email protected]

847-677-3468