Fire Alarm Control Panel Df-52095

3
DF-52095 06/18/04 Page 1 of 2 GENERAL GENERAL GENERAL GENERAL GENERAL The MicroScan-2410B is a 24-volt, ten-zone, Style B (Class B), Conventional Fire Alarm Control Panel. Designed ex- clusively to meet the latest fire alarm market requirements, the highly cost-effective MS-2410B can be used in a vari- ety of low- to mid-sized applications, including: Local, Aux- iliary, Remote Station, and Proprietary Fire Alarm System. Provides supervised reverse polarity protection when us- ing a 4XTMF Transmitter Module. FEA FEA FEA FEA FEA TURES TURES TURES TURES TURES Ten Styl e B (Class B) I nitiat ing Devi ce Circuits (IDCs). Zones 1 - 10 accept t wo-wire smoke detectors and any normally-open contact devices. Zones 1 - 8 conf igured as g eneral alarm zones . Zones 9 and 10 pr ogrammable as s moke zones or supervisory alarm zones. Two built-in, Style Y (Class B) Notification Appliance (Bell) Circuits (NACs). NACs may be pr ogrammed: Silen ce abl e. Non-Silenceabl e. Aut o-Silence ( program 5 to 20 minutes ). 2.5 amps of NAC power, expandable to 5.0 amps. 3.6 amps of t otal sys tem power expandable to 6.6 amps. 24 VDC operati on. Supervised reverse polarity protection (using 4XTMF). Resettable four- wire smoke detector power @ 300 mA. Non-r esett able power @ 500 mA. Integ ral batt ery charger capable of charging up to 18 AH batteries (batteries over 12 AH require use of the FireLite BB-17F battery backbox). Alarm, Trouble and Su pervisory, Form-C relays standard. Fuseless, power- limited technology meets all the lat- est power-limiting requirements. Full y progr ammable via built- in keypad. Progr am mode pas sword an d cabinet secur ity key pr e- vent unauthorized access to ensure the integrity of the field program information. Progr ammab le Alarm Ver ifica tion (zones 1 through 3 with two-wire smoke detectors only). Last Event Recall feat ure traps unveri fied alar ms or in- termittent troubles. One-man walk-test programmable for silent or audible test. Disable/ Enable cont rol per IDC (zones). Programmable Trouble Reminder and Silence Inhibit capability. Slide-in labels for zone identification and pr ogramming options. Electronics and opera tional co ntrols f ully enc losed in lock- able cabinet capable of housing up to 12 AH batteries. Optional flush mount trim ring (TR-4-R). Opti onal dead-f ront dress panel ( DP-2410B). RTB Remote Trouble Buzzer option. Opti on al LED-10IM interface module provides EIA-485, two-wire, serial output for: Rel ay- by- zon e capabil ity wi th opt ional ACM-8RF. Optional LED-10 Series Remote Fire Annunciators. Optional AFM Series LED Annunciators. LDM Series Graphic Annunciator Drivers. Local energy or remote station connection wi th optio nal 4XTMF transmitter module. SPECIFICA SPECIFICA SPECIFICA SPECIFICA SPECIFICA TIONS TIONS TIONS TIONS TIONS 120 VAC, 60 Hz, 2.3 amps. Wi re si ze: minimum 14 AWG (2.0 mm²) with 600-volt insulation. Total 24 VDC syst em powe r: 3.6 amps (expandable to 6.6 amps). Notific ation appliance (bell ) circui t (NAC) power : 2.5 amps (expandable to 5.0 amps). Maximum curre nt per NAC: 1.25 amps (expandable to 2.5 amps). S624 MicroScan-2410B MicroScan-2410B MicroScan-2410B MicroScan-2410B MicroScan-2410B 10-Zone, Class B 10-Zone, Class B 10-Zone, Class B 10-Zone, Class B 10-Zone, Class B Fire Alarm Control Panel Fire Alarm Control Panel Fire Alarm Control Panel Fire Alarm Control Panel Fire Alarm Control Panel DF-52095 A2-425 June 18, 2004 Section: Conventional www.firelite.com MEA 299-00-E This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are sub-  ject to change without notice. For more information, contact FireLite Alarms, One Fire-Lite Place, Northford, Connecticut 06472. Phone: (800) 627- 3473, Toll-Free FAX: (877) 699-4105. Made in the U.S.A. 7165-0075:188 California State Fire Marshal

Transcript of Fire Alarm Control Panel Df-52095

Page 1: Fire Alarm Control Panel Df-52095

8/2/2019 Fire Alarm Control Panel Df-52095

http://slidepdf.com/reader/full/fire-alarm-control-panel-df-52095 1/2

DF-52095 06/18/04 Page 1 of 2

GENERALGENERALGENERALGENERALGENERALThe MicroScan-2410B is a 24-volt, ten-zone, Style B (Class

B), Conventional Fire Alarm Control Panel. Designed ex-clusively to meet the latest fire alarm market requirements,the highly cost-effective MS-2410B can be used in a vari-ety of low- to mid-sized applications, including: Local, Aux-iliary, Remote Station, and Proprietary Fire Alarm System.Provides supervised reverse polarity protection when us-ing a 4XTMF Transmitter Module.

FEA FEA FEA FEA FEA TURESTURESTURESTURESTURES Ten Style B (Class B) Initiating Device Circuits (IDCs).

Zones 1 - 10 accept two-wire smoke detectors andany normally-open contact devices.

Zones 1 - 8 configured as general alarm zones.

Zones 9 and 10 programmable as smoke zones orsupervisory alarm zones.

Two built-in, Style Y (Class B) Notification Appliance(Bell) Circuits (NACs).

NACs may be programmed:

S ilenceab le .

Non-Silenceable.

Auto-Silence (program 5 to 20 minutes).

2.5 amps of NAC power, expandable to 5.0 amps.

3.6 amps of total system power expandable to 6.6 amps.

24 VDC operation.

Supervised reverse polarity protection (using 4XTMF).

Resettable four-wire smoke detector power @ 300 mA.

Non-resettable power @ 500 mA.

Integral battery charger capable of charging up to 18 AH

batteries (batteries over 12 AH require use of theFireLite BB-17F battery backbox).

Alarm, Trouble and Supervisory, Form-C relays standard.

Fuseless, power-limited technology meets all the lat-est power-limiting requirements.

Fully programmable via built-in keypad.

Program mode password and cabinet security key pre-vent unauthorized access to ensure the integrity of thefield program information.

Programmable Alarm Verification (zones 1 through 3 withtwo-wire smoke detectors only).

Last Event Recall feature traps unverified alarms or in-termittent troubles.

One-man walk-test programmable for silent or audible

test. Disable/Enable control per IDC (zones).

Programmable Trouble Reminder and Silence Inhibitcapability.

Slide-in labels for zone identification and programmingoptions.

Electronics and operational controls fully enclosed in lock-able cabinet capable of housing up to 12 AH batteries.

Optional flush mount trim ring (TR-4-R).

Optional dead-front dress panel (DP-2410B).

RTB Remote Trouble Buzzer option.

Optional LED-10IM interface module provides EIA-485,two-wire, serial output for:

Relay-by-zone capability with optional ACM-8RF.

Optional LED-10 Series Remote Fire Annunciators.

Optional AFM Series LED Annunciators.

LDM Series Graphic Annunciator Drivers.

Local energy or remote station connection with optional4XTMF transmitter module.

SPECIFICA SPECIFICA SPECIFICA SPECIFICA SPECIFICA TIONSTIONSTIONSTIONSTIONS 120 VAC, 60 Hz, 2.3 amps.

Wire size: minimum 14 AWG (2.0 mm²) with 600-volt

insulation.

Total 24 VDC system power: 3.6 amps (expandable to6.6 amps).

Notification appliance (bell) circuit (NAC) power: 2.5amps (expandable to 5.0 amps).

Maximum current per NAC: 1.25 amps (expandable to2.5 amps).

S624

MicroScan-2410BMicroScan-2410BMicroScan-2410BMicroScan-2410BMicroScan-2410B10-Zone, Class B10-Zone, Class B10-Zone, Class B10-Zone, Class B10-Zone, Class B

Fire Alarm Control PanelFire Alarm Control PanelFire Alarm Control PanelFire Alarm Control PanelFire Alarm Control Panel

DF-52095 A2-425June 18, 2004

Section: Conventionalwww.firelite.com

MEA 299-00-E

This document is not intended to be used for installation purposes. We try tokeep our product information up-to-date and accurate. We cannot cover allspecific applications or anticipate all requirements. All specifications are sub-

  ject to change without notice. For more information, contact FireLite

Alarms, One Fire-Lite Place, Northford, Connecticut 06472. Phone: (800) 627-3473, Toll-Free FAX: (877) 699-4105.

Made in the U.S.A.

7165-0075:188

CaliforniaState Fire

Marshal

Page 2: Fire Alarm Control Panel Df-52095

8/2/2019 Fire Alarm Control Panel Df-52095

http://slidepdf.com/reader/full/fire-alarm-control-panel-df-52095 2/2

Page 2 of 2 DF-52095 06/18/04

Maximum battery charging capability: 18 AH.

Initiating Device Circuits (zones)Initiating Device Circuits (zones)Initiating Device Circuits (zones)Initiating Device Circuits (zones)Initiating Device Circuits (zones) Ten Style B (Class B).

Zones may be programmed for:

Two-wire smoke detectors and any normally opencontact device.

Zones 1 - 8 configured as general alarm zones only.

Zones 9 and 10 can be configured as smoke zonesor supervisory alarm zones.

All circuits are power-limited and supervised, meetingthe latest requirements using fuseless technology.

Notification Appliance (Bell) CircuitsNotification Appliance (Bell) CircuitsNotification Appliance (Bell) CircuitsNotification Appliance (Bell) CircuitsNotification Appliance (Bell) Circuits

(NACs)(NACs)(NACs)(NACs)(NACs) Two Style Y (Class B) @ 1.25 amps (expandable to 2.5

amps) each.

NACs may be programmed:

S ilenceab le .

Non-Silenceable.

Auto-Silence (program 5 to 20 minutes).

All circuits are power-limited and supervised, meetingthe latest requirements using fuseless technology.

Auxiliary OutputsAuxiliary OutputsAuxiliary OutputsAuxiliary OutputsAuxiliary Outputs Resettable four-wire smoke detector power @ 300 mA.

Non-resettable power @ 500 mA.

NOTE: Total current for auxiliary power outputs and two NACs

must not exceed 6.0 amps. Total system current in excess of 3.6

amps requires the optional XRM-24 transformer and 12 or 18 AH 

batteries.

Integral Form-C Alarm, Trouble and Supervisory relays,rated at: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30VAC (resistive).

EIA-485 Port, Compatible DevicesEIA-485 Port, Compatible DevicesEIA-485 Port, Compatible DevicesEIA-485 Port, Compatible DevicesEIA-485 Port, Compatible Devices

LED-10IM:  EIA-485 Interface Module. Provides MS-

2410B with EIA-485 output, capable of supporting up to 10

compatible EIA-485 devices.LED-10 Series: LED-type fire annunciators capable of 

displaying Alarm (red) and Trouble (yellow) LEDs for allten Initiating Device Circuits (IDCs).

AFM Series: LED-type fire annunciators capable of pro-

viding up to 16 zones of Alarm (red) annunciation and com-mon system trouble LED. Mount to 4-gang electrical box 

ONLY .

LDM Series:  Lamp Driver Module series for use with

custom graphic annunciators.

ACM-8RF: Remote Form-C relay module. Provides eight

mappable Form-C relays driven by EIA-485 for relay-by-zone capability (two minimum required for relay-by-zone).

Each requires ABS-8RF for mounting.NOTE: For more detailed information on Compatible EIA-485 

Devices for use with the MS-2410B, please refer to the LED-10,

 AFM/AFM-X, LDM or  ACM-8RF data sheets, document numbers

DF-51500, DF-51465, DF-51384, and DF-51555 respectively.

Cabinet SpecificationsCabinet SpecificationsCabinet SpecificationsCabinet SpecificationsCabinet SpecificationsSee diagrams below.

PRODUCT LINE INFORMA PRODUCT LINE INFORMA PRODUCT LINE INFORMA PRODUCT LINE INFORMA PRODUCT LINE INFORMA TIONTIONTIONTIONTIONMS-2410B 24-Volt, 10-zone, Class B, FACP.

XRM-24 120VAC, 100 VA transformer. Expands totalsystem power from 3.6 amps to 6.6 amps.

RTB Remote Trouble Buzzer.

4XTMF Remote station output or municipal box con-nection (reverse polarity application).

LED-10IM EIA-485 port interface module. Required for use with EIA-485 compatible devices  (seeabove).

DP-2410B Optional internal dead-front dress panel.

TR-4-R Flush mount trim ring.

BB-17F UL listed battery backbox. Required for usewith batteries over 12 AH.

ABS-8RF Metal enclosure for mounting each ACM-8RFmodule.

2410RB Replacement motherboard.

BAT-12120 Battery, 12 volt, 12.0 AH (two required).

BAT-12180 Battery, 12 volt, 18.0 AH (two required; requiresBB-17F battery backbox for mounting).