FIGURE 1 - Fullriver Battery · FIGURE 1 CHARGE VOLTAGE REFERENCE For a 6V battery, divide the...

2
0.35 0.30 0.25 CURRENT (X C20 RATE) VOLTAGE PER CELL CHARGING TIME: NO LIMIT BULK ABSORPTION U = 2.45V/Cell (+/- .025V/Cell) 0 Current will taper down I = 0.15 - 0.35 x C 1 20 I = 0.012 - 0.02 x C 2 20 Minimum float time = 8 hrs. Maximum absorption time = 8 hrs. Temperature: 25˚C (77˚F) FLOAT 0.20 0.15 0.10 0.05 0.00 2.70 2.60 2.50 2.40 2.30 2.20 2.10 2.00 Temperature Coefficient: -4mV/ C/cell (-2mV/ F/cell) 0 0 U = 2.275V/Cell (+/- .025V/Cell) FIGURE 1

Transcript of FIGURE 1 - Fullriver Battery · FIGURE 1 CHARGE VOLTAGE REFERENCE For a 6V battery, divide the...

Page 1: FIGURE 1 - Fullriver Battery · FIGURE 1 CHARGE VOLTAGE REFERENCE For a 6V battery, divide the voltage by 2. REFRESH CHARGE If Fullriver batteries are properly charged they should

0.35

0.30

0.25CU

RREN

T (X

C20

RAT

E)

VOLT

AGE

PER

CELL

CHARGING TIME: NO LIMIT

BULK ABSORPTION

U = 2.45V/Cell (+/- .025V/Cell)0

Current will taper down

I = 0.15 - 0.35 x C1 20

I = 0.012 - 0.02 x C2 20

Minimum float time = 8 hrs.

Maximum absorption time = 8 hrs.

Temperature: 25˚C (77˚F)

FLOAT

0.20

0.15

0.10

0.05

0.00

2.70

2.60

2.50

2.40

2.30

2.20

2.10

2.00Temperature Coefficient: -4mV/ C/cell (-2mV/ F/cell)0 0

U = 2.275V/Cell (+/- .025V/Cell)

FIGURE 1

Page 2: FIGURE 1 - Fullriver Battery · FIGURE 1 CHARGE VOLTAGE REFERENCE For a 6V battery, divide the voltage by 2. REFRESH CHARGE If Fullriver batteries are properly charged they should

CHARGE VOLTAGE REFERENCE

For a 6V battery, divide the voltage by 2.

REFRESH CHARGEIf Fullriver batteries are properly charged they should never require an equalizing charge. If they were not properly charged and there is a decrease in capacity, recharge the batteries and make sure they complete the entire charge cycle. If the batteries are stored for extended periods of time, recharge them as follows:

Storage Temperature Refresh Charge Interval

Below 68˚F (20˚C) 9 Months

68˚F (20˚C) - 86˚F (30˚C) 6 Months

Higher than 86˚F (30˚C) 3 Months

OTHER CHARGERSThere are many types of chargers and inverters available for charging lead-acid batteries. If you are not sure if your charger meets the recommended charging characteristics or if you need help programming your charger, please contact your local Fullriver Battery distributor for assistance.

12V Battery Charge Voltage Float Voltage

32˚F (0˚C) 15.30 14.25

50˚F (10˚C) 15.06 14.01

50˚F (10˚C) 14.82 13.77

77˚F (25˚C) 14.70 13.65

86˚F (30˚C) 14.58 13.53

104˚F (40˚C) 14.34 13.29

0.35

0.30

0.25

CURR

ENT

(X C

20 R

ATE)

VOLT

AGE

PER

CELL

CHARGING TIME: <=20 HRS

BULK ABSORPTION

U = 2.45V/Cell (+/- .05V/Cell)

I = 0.012 - 0.02 x C 202

Voltage varies with ageto a maximum of 2.7V/Cell

Termination: dV/dT= 2.5mV/Cell/hror 105-110% recharge

Temperature: 25˚C (77˚F)

TERMINATION

0.20

0.15

0.10

0.05

0.00

2.70

2.60

2.50

2.40

2.30

2.20

2.10

2.00Temperature Coefficient: -4mV/ C/cell (-2mV/ F/cell)0 0

Maximum absorption time = 8 hrs.

Maximum termination time = 8 hrs.

I = 0.15 - 0.35 x C1 20

FIGURE 2