FieldCare SFE500 - Technical Information
Transcript of FieldCare SFE500 - Technical Information
TI00028S/04/en/01.11
71133183
Technical Information
FieldCare SFE500FDT-based Plant Asset Management tool
Application
FieldCare is Endress+Hauser's universal FDT-certified,
Windows-based tool for Plant Asset Management. It can
configure all intelligent field devices in a plant and
supports in managing them. By using status information,
it also provides a simple but effective means of checking
their health.
FieldCare is scalable, offering simple device setup, device
maintenance management, condition-based
maintenance and life-cycle management according to
license option. It can be upgraded at any time to extend
functionality.
Features and Benefits
• FDT-certified frame
• Supports HART, PROFIBUS, FOUNDATION fieldbus
and Endress+Hauser service protocols
• Supplied with a complete library of certified DTMs
(Device Type Manager) for operation of all
Endress+Hauser devices
• Has CommDTMs for HART, PROFIBUS,
FOUNDATION fieldbus, Endress+Hauser Service
communication interfaces
• Operates all third-party actuators, remote I/O systems
and sensors supporting the FDT standard
• Ensures full functionality for all Endress+Hauser and
third-party devices with DTMs
• Offers generic profile operation for any third-party
fieldbus device that does not have a vendor DTM
• Integrates all registered HART and FOUNDATION
fieldbus devices without DTMs through iDTM
technology (DD interpreter)
• Scans, identifies, assigns DTMs and adds devices to
network automatically
• Connects to W@M life cycle management database
FieldCare Plant Asset Management SFE500
2 Endress+Hauser
Function and System Design
Function
Field Device Tool (FDT)
System design
Network connection Depending upon the communcation interface offered by the device, FieldCare may be connected via a network
or point-to-point to a powered device. The software is installed on a personal or laptop computer, and the
connection made via a network card, an appropriate interface card or a USB or RS-232 modem. Access may
be via a gateway with CommDTM, or if it supports FDT, via a controller. The physical architecture is mirrored
by the nested CommDTMs and DeviceDTMs.
The devices are configured via DeviceDTMs. If the device does not have a native DTM, but is registered at a
fieldbus technology association, then it can be operated by the appropriate optional iDTM (this option is not
supported by FieldCare Device Setup). Interfaces such as PROFIBUS DP/PA couplers must be either
transparent or be supplied with a CommDTM if access is to be made to the connected devices. Devices with
4–20 mA, binary and pulse/frequency outputs cannot be operated.
Fig 1: FieldCare architecture showing central access to a HART, FOUNDATION fieldbus and PROFIBUS
network via gateway and Ethernet
FDT is a standardized interface specification that
allows the integration of intelligent devices into, for
example, asset management and process control
systems. All configuration and communication
information is carried in Device Type Management
(DTM) programs (DeviceDTMs and CommDTMs)
supplied by the vendor. The DTMs run under the
control of a FDT frame application:
• Open technology, independent of device and
system supplier
• Independent of device type (sensor, actuator,
remote I/O etc.)
• Full support of installed base
• Full device functionality
• Independent of communication protocol –
Ethernet, HART, PROFIBUS, FOUNDATION
fieldbus
• Vertical integration by nested communication
FDTFrameApplication• Network
Configuration
• Navigation
• UserManagement
• DTM Management
• Data Management
DeviceDTM
Plant AssetsSensors, Actuators, Drives, Low Voltage Switchgear,Gateways, Remote I/Os, Controllers, etc.
CommDTME.g. Ethernet, HART,PROFIBUS,FOUNDATION fieldbus
Ethernet
DCS Ethernet/FOUNDATIONfieldbusGatewaye.g. SFC162
PLC
RIOMC
M
Coupler(transparent)
FieldCare with iDTMs(PAM license)
Ethernet/PROFIBUSGatewaye.g. FXA720
Native DTM or CommDTM
No Native DTM, but DD, EDD
Not configurable with FDT
PROFIBUS DP
PROFIBUS PA
PROFIBUS
FOUNDATIONfieldbus H1
FOUNDATION fieldbus HART
Fie(PA
Ethernet/HARTGatewaye.g. FXA520
HARTMultiplexer
HART
RS-485
FieldCare Plant Asset Management SFE500
Endress+Hauser 3
HART point-to-point
connection
Fig. 2 shows a HART point-to-point connection via a HART power supply using the Commubox FXA195 USB/
HART modem. Since the power supply has a communication resistor, the communication resistor of the
FXA195 must be switched off. The connection can be made at the power supply module or the device terminals
as required.
Fig 2: Point-to-point connection to a HART device via a HART power supply
If there is no communication resistor in the 4–20 mA signal loop, the FXA195 USB modem must be connected
cross the HART terminals of the device with its communication resistor switched on.
Point-to-point connection to
WirelessHART adapter
Fig. 3 shows a point-to-point connection to a battery powered WirelessHART Adapter SWA70 using the
Commubox FXA195 USB/HART modem.
Fig 3: WirelessHART Adapter SWA70 connection
PROFIBUS point-to-bus
connection
Fig. 4 shows a PROFIBUS point-to-bus connection for setting up PROFIBUS DP and PROFIBUS PA devices on
the test bench or in the field using the PROFIusb PROFIBUS interface.
Fig 4: PROFIBUS point-to-bus connection
FOUNDATION fieldbus
point-to-bus connection
Fig. 5 shows a FOUNDATION fieldbus point-to-bus connection for setting up FOUNDATION fieldbus devices
on the test bench using a SFC162 module in controller mode. Further requirements are a power supply and
fieldbus power conditioner, which can be supplied with the SFC162.
Fig 5: FOUNDATION fieldbus point-to-bus connection
Switch Commubox FXA195
Commubox FXA195
270 Ω
Off
On
USB
4–20 mA/HART
HART power supplye.g. RMA422, RN221Nwith communicationresistor
FieldCare PAM license orDevice Setup (DTMs only)
USB port
Commubox FXA195
WirelessHARTAdapter
Terminals 5 and 6 or 7 and 8
FieldCare PAM license orDevice Setup (DTMs only)
Switch Commubox FXA195
270 Ω
Off
On
FieldCare PAM license orDevice Setup (DTMs only)
RIOMC
PROFIBUS DP
HART
Coupler
PROFIBUS PA
PROFIBUS
M
USB port
PROFIusb interface
FieldCare PAM license orDevice Setup (DTMs only)
FOUNDATION fieldbus H1Ethernet
SFC162with power supply and fieldbus conditioner
(crossover cable)
FieldCare Plant Asset Management SFE500
4 Endress+Hauser
System Integration
CommDTMs
FieldCare CommDTMs
3rd Party CommDTMs A number of DTMs for third party remote I/Os are known to work in FieldCare in connection with specific
component architectures. For more information, contact Endress+Hauser.
DeviceDTMs
FieldCare DTM library DTMs for all Endress+Hauser devices, update available four times a year
iDTM HART Interpreter DTM for all registered HART devices, available as option with FieldCare PAM license
iDTM FOUNDATION fieldbus Interpreter DTM for all registered FOUNDATION fieldbus devices, available as option with
FieldCare PAM license
3rd Party DTMs All 3rd party certified DTMs for FDT Version 1.2 should run in FieldCare without problem
Designation Protocol Application FieldCare Condition Monitoring
CDI Communication
FXA291
Service FXA291:
CDI service interface
N/A
IPC (Level, Pressure)
FXA193/FXA291
Service FXA193/FXA291:
IPC level/pressure service interface
N/A
PCP TXU10/FXA291 Service TXU10/FXA291:
PCP service interface
N/A
ISS (Flow) FXA193/
FXA291
Service FXA193/FXA291:
ISS flow service interface
N/A
FXA520 HART FXA520 Ethernet/HART gateway:
pass through connection to HART
devices
Certified for CM*
HART Communication HART FXA191, FXA195 or Mactek
(USB/HART or RS-232C/HART):
HART point-to-point connection
N/A
HART OPC Client HART HART OPC Client:
Connection to OPC Server
Released for CM
HART OPC
Communication
HART HART OPC Server:
Connection via OPC Client
HART IP Communication HART UDP SWG70: Wireless HART gateway Not certified for CM
DP/PA Link PROFIBUS Siemens DP/PA Link:
Connection to PROFIBUS PA
devices
Certified for CM*
• Does not support all hardware,
see T+H release notes on DVD
ET 200M PROFIBUS Siemens ET-200M:
RIO PROFIBUS DP/HART
Not certified for CM
• See T+H release notes on DVD
ET 200iSP PROFIBUS Siemens ET-200iSP:
RIO PROFIBUS DP/HART
Not certified for CM
• See T+H release notes on DVD
PROFIdtm DPV1 PROFIBUS FXA720/ PCMCIA PROFIBUS card:
Ethernet/PROFIBUS DP connection
Certified for CM*
PROFIBUS Master DP-V1 PROFIBUS Trebing+Himstedt xEPI2:
Ethernet/PROFIBUS DP connection
Certified for CM*
• Does not support all hardware,
see T+H release notes on DVD
SFC173 CommDTM PROFIBUS SFC173:
Ethernet/PROFIBUS DP connection
Not certified for CM
S-Mux Communication PROFIBUS P+F Multiplexer KFD2/2700 series Not certified for CM
FF H1 CommDTM FOUNDATION
fieldbus
National Instruments PCMCIA
FBUS card: connection to
FOUNDATION fieldbus H1
N/A
SFC162 CommDTM FOUNDATION
fieldbus
SFC162 Controller and Visitor:
Connection to FOUNDATION
fieldbus H1
Certified for CM*
*Tested by Endress+Hauser for CommDTM functionality, stability, failure and recovery behavior in FieldCare CM
FieldCare Plant Asset Management SFE500
Endress+Hauser 5
Interfaces to Endress+Hauser environment
W@M interface With a PAM license and W@M account, a user can connect to the W@M internet portal or W@M Enterprise
application via the "Device in Net" function. This allows access to the common equipment record, spare part
finder etc. as well as various W@M applications such as comparison of current to past configurations.
SOAP and e-mail interface The Condition Monitoring module, which is optionally available with the PAM license, can exchange data with
other tools via an e-mail or XML file.
Launch interface FieldCare can be embedded or started from any SCADA application by using the so-called launch interface.
Operability
Operation • Standard configurable Windows graphical user interface with icons, short cuts etc.
• Creation of projects in network (communication) and plant (logistic) views
• Projects created manually or automatically with a project set-up wizard
• Standard windows functions for saving, opening, printing, editing projects, changing workspace etc.
• FDT frame languages DE, EN, FR, IT, ES, CH, JP
• DTM graphical user interface and language dependent on device and supplier
Examples of screens
Ethernet
FieldCare(PAM license)
Device in Netvia Internet or Ethernet
Internetreplication
W@M Internet Portal(Endress+Hauserdatabase)
W@M Enterprise
Network connection
Fie(PA
W@(Eda
W@
Network and Plant View Optional iDTM HART
Condition Monitoring Device Report Connection to W@M portal through "Device in Net"
FieldCare Plant Asset Management SFE500
6 Endress+Hauser
Software Specification
FieldCare Device Setup Provides basic parameterization and diagnosis functions, and can be upgraded to the Plant Asset Management
version by purchasing the appropriate license. FieldCare Device Setup offers:
• FDT-certified frame, FDT-certified DTM libraries
• Configuration and commissioning of Endress+Hauser and third-party devices based on DTM technology
• Support of HART, PROFIBUS and FOUNDATION fieldbus
• Support of Endress+Hauser service protocol to access our instruments independent of fieldbus protocol
• Includes CommDTMs for HART, PROFIBUS, FOUNDATION fieldbus, Service Interface and Gateways for
remote service
• Seamlessly upgradable
If not supplied with a device, it can be downloaded free-of-charge from www.products.endress.com/fieldcare.
FieldCare Plant Asset
Management (PAM)
Offers all the functions of FieldCare Device Setup together with addition functions and options for plant asset
management:
• Plant View:
logical view of plant with tagging and archiving
• Document Management:
storage of key documents under the device tag
• Inventory View:
list of all devices in the plant
• W@M Connectivity:
ability to connect to W@M portal via Internet
• Project Management:
import/export of projects and settings
• Reports:
configurable and printable reports of device settings, plant configuration etc.
• User Management:
configurable list of users
Condition Monitoring (option) Extracts data from selected devices and, based on the way they are set up, creates alarms via e-mail or through
the operator workstation to alert users of a potential need for maintenance. The operator is given additional
device data to allow him to make informed decisions.
• Independent solution for the maintenance task
• Focus on critical devices and beneficial information
• NE107 compliant
FieldCare iDTM HART
(option)
• Operates 3rd party HART devices without DTM in FieldCare
• Contains more than 825 registered HART EDDs from about 110 device manufacturers
• Uses Nested Communication in a plant
• Combines both device integration technologies FDT/DTM and EDDL in one solution
FieldCare iDTM
FOUNDATION fieldbus
(option)
• Operates 3rd party FOUNDATION fieldbus devices without DTM in FieldCare
• Contains more than 500 registered FOUNDATION fieldbus devices from about 80 device manufacturers
• Uses Nested Communication in a plant
• Combines both device integration technologies FDT/DTM and EDDL in one solution
Supplied support software • Microsoft .NET Version 3.51)
• Microsoft Management Console Version 1.21)
• Microsoft SQL Server 2008 Express1)
• Microsoft Windows Installer 4.52)
1) Programs are automatically installed by FieldCare Installation Manager if not available or no compatible
release is already installed.
2) Programs are automatically installed by FieldCare Installation Manager if not available, except for
Windows Vista Service Pack1: please install manually.
FieldCare Plant Asset Management SFE500
Endress+Hauser 7
System Requirements
Operating system
Date marked with (*) defines the end of the standard support, an additional Microsoft extended support of five
years is possible.
Hardware
Documentation
Field of Activity
Competence Brochure
Innovation Brochure
Operating Instructions
Version Available since End of Microsoft support FieldCare support status
WinXP Professional SP2 August 2004 July 2010* OK
WinXP Professional SP3 April 2008 April 2010* OK
WinServer 2003 Standard R2 SP2 February 2007 OK
WinServer 2003 Enterprise R2 SP2 March 2007 OK
Vista 32 Ultimate SP1 February 2008 July 2011 OK
Vista 32 Ultimate SP2 May 2009 April 2017 OK
Vista 32 Business SP1 February 2008 July 2011 OK
Vista 32 Business SP2 May 2009 April 2017 OK
Vista 32 Enterprise SP1 February 2008 July 2011 OK
Vista 32 Enterprise SP2 May 2009 April 2017 OK
Windows 7 Professional (x32+x64) October 2009 New in FC2.08.00
Windows 7 Professional SP1 (x32+x64) February 2011 New in FC2.08.01
Windows 7 Ultimate (x32+x64) October 2009 New in FC2.08.00
Windows 7 Ultimate SP1 (x32+x64) February 2011 New in FC2.08.01
Windows 7 Enterprise (x32+x64) October 2009 New in FC2.08.00
Windows 7 Enterprise SP1 (x32+x64) February 2011 New in FC2.08.01
Item Minimum Recommended
Processor type Pentium IV 2 GHz CPU
AMD 2 GHz CPU
Pentium IV 3 GHz CPU
AMD 3 GHz CPU
Main memory (RAM) 1024 MB RAM 2048 MB RAM
Hard-disk (HDD) capacity
(Status January 2011 with FieldCare
package 1.12.00):
7.8 GB for full installation plus
4.5 GB in a temporary folder during installation on system partition
Partial installation as follows:
• 500 MB FieldCare
• 1.8 GB System Components
• 4.5 GB Endress+Hauser DTM libraries (HART, PROFIBUS, FOUNDATION
fieldbus)
• 700 MB Endress+Hauser Service DTM library
• 300 MB Endress+Hauser iDTM libraries (HART, FOUNDATION fieldbus)
Monitor resolution 1024 x 768, 64,000 colors 1024 x 768, 64,000 colors
Process Solutions
Field of Activities FA017S/04/en
Plant Asset Management
Field of Activities FA00024S/04/en
(in preparation)
FieldCare
Competence Brochure CP00001S/04/en
FDT - Field Device Tool
Competence Brochure CP010S/04/en
FieldCare PAM through Fieldgate
Competence Brochure CP011S/04/en
FieldCare iDTM HART
Innovation Brochure IN009S/04/en
FieldCare iDTM FOUNDATION fieldbus
Innovation Brochure IN013S/04/en
FieldCare
Getting Started BA027S/04/en
FieldCare iDTM
Getting Started BA059S/04/c4
FieldCare Plant Asset Management SFE500
Ordering Information
Product Structure SFE500 FieldCare software
License types
N
D
U
New license
Demo license (time limited, standard 1 month)
Update current license
Delivery type
E
P
B
E-mail: license (only) delivered per email
Paper Cover: license delivered with DVD in paper cover
Box: license delivered with DVD in Plastic Box
Number of device positions
A
B
C
D
E
F
G
K
16
32 s
64
128
256
512
1024
..... Number of DP tags
Number of condition monitoring (CM) tags (must be ≤ Number of device positions)
Remember to consult us ([email protected]) before ordering CM tags
Z
A
B
C
D
E
F
G
K
0
16
32
64
128
256
512
1024
..... Number of CM tags
iDTM HART
0
1
not used
used
iDTM PROFIBUS (in preparation)
0
1
not used
used
iDTM FOUNDATION fieldbus
0
1
not used
used
SFE500- Product designation
TI00028S/04/en/01.11
CCS/FM9.0
Instruments International
Endress+HauserInstruments International AGKaegenstrasse 24153 ReinachSwitzerland
Tel. +41 61 715 81 00Fax +41 61 715 25 [email protected]