FCU-6000 system manual

download FCU-6000 system manual

of 68

Transcript of FCU-6000 system manual

  • 8/10/2019 FCU-6000 system manual

    1/68

    Fire Alarm Control Panel

    N 6000

    Manual

    REV B

    DATE 2007-08-08

  • 8/10/2019 FCU-6000 system manual

    2/68

  • 8/10/2019 FCU-6000 system manual

    3/68

    against telephone line failure, backup radio transmission

    systems are recommended.

    The most common causeof fire alarm malfunction is

    inadequate maintenance. To keep the entire fire alarm

    system in excellent working order, ongoing maintenance

    is required per the manufacturer's recommendations.

    Environments with large amounts of dust, dirt or high air

    velocity require more frequent maintenance. A

    maintenance agreement should be arranged through the

    local manufacturer's representative. Maintenance should

    be scheduled or as required by National and/or local fire

    codes and should be performed by authorized professional

    fire alarm installers only. Adequate written records of all

    inspections should be kept.

  • 8/10/2019 FCU-6000 system manual

    4/68

    Installation Precautions

    Adherence to the following will aid in problem-free installation with long-term reliability:

    Several different sources of power can be

    connected to the fire alarm control panel. Disconnectall

    sources of power before servicing. Control unit and

    associated equipment may be damaged by removing

    and/or inserting cards, modules, or interconnecting cables

    while the unit is energized. Do not attempt to install, service,

    or operate this unit until this manual is read and

    understood.

    System Reacceptin g Test after Software

    Changes. To ensure proper system operation, thisproduct

    must be tested after any programming operation or change

    in site-specific software.

    All components, circuits, system operations, or software

    functions known to be affected by a change must be 100%

    tested. In addition, to ensure that other operations are not

    inadvertently affected, at least 10% of initiating devices that

    are not directly affected by the change, up to a maximum of

    50 devices, must also be tested and proper system

    operation verified.

    Verify that w ire sizes are adequate for all initiating and

    indicating device loops. Most devices cannot tolerate more

    than a 10% I.R. drop from the specified device voltage.

    Like all solid state electronic devices, this system may

    operate erratically or can be damaged when subjected to

    lightning-induced transients. Although no system is

    completely immune from lightning transients and

    interferences, proper grounding will reduce susceptibility.

    Overhead or outside aerial wiring is not recommended,

    due to an increased susceptibility to nearby lightning strikes.

    Consult with the Technical Services Department if any

    problems are anticipated or encountered.

    Disconnect AC power and batteries prior to removing

    or inserting circuit boards. Failure to do so can damage

    circuits.

    Remove all electronic assemblies prior to any drilling,

    filing, reaming, or punching of the enclosure. When

    possible,

    make all cable entries from the sides or rear. Before making

    modifications, verify that they will not interfere with battery,

    transformer, and printed circuit board location.

  • 8/10/2019 FCU-6000 system manual

    5/68

    Table of ContentSection 1:About This Manual ................................................................................................................. 6

    1.1Notes, Cautions & Warnings......................................................................................................... 6

    1.2Font Definition .............................................................................................................................. 6Section 2:System Overview.................................................................................................................... 7

    2.1Introduction ................................................................................................................................... 7

    2.2Characteristics of the Product........................................................................................................ 7

    Section 3:System Configuration & Installation ...................................................................................... 9

    3.1Features Main Performances ......................................................................................................... 9

    3.2Electrical Specifications................................................................................................................ 9

    3.3System Configuration.................................................................................................................... 9

    3.4System Block Diagram................................................................................................................ 10

    3.5Installation & Connection ........................................................................................................... 11

    3.5.1Enclosures............................................................................................................................ 11

    3.5.2Connection Requirements.................................................................................................... 12

    3.5.3Connection of Circuit Board Terminals............................................................................... 12

    3.5.3.1CPU Diagram............................................................................................................... 12

    3.5.3.2Power Supply Connection............................................................................................ 15

    3.5.3.3NIC-EC......................................................................................................................... 17

    3.5.3.4Loop Control Module Connection................................................................................ 19

    3.5.3.5MCU-16B Annunciator Control Module Connection.................................................. 21

    3.6Equipment Debugging ............................................................................................................ 23

    3.6.1Connection Inspection..................................................................................................... 23

    3.6.2Power-on Inspection........................................................................................................ 24

    3.6.3External Connection........................................................................................................ 24

    3.6.4Important Points .............................................................................................................. 24

    3.6.5Inspection Methods for Addressable Device Connections.............................................. 25

    Section 4:Operation .............................................................................................................................. 26

    4.1LED Indicators and Keys ............................................................................................................ 26

    4.1.1Control Panel Display LED Indicators and Keys ................................................................ 26

    4.1.2Annunciator Control Module LED Indicators and Keys ..................................................... 29

    4.2Power-on ..................................................................................................................................... 304.3System Self-test........................................................................................................................... 30

    4.4Event Display .............................................................................................................................. 32

    4.4.1Trouble Screen..................................................................................................................... 32

    4.4.2Fire Alarm Screen................................................................................................................ 33

    4.4.3Supervisory Screen .............................................................................................................. 34

    4.4.4Point Disabled Screen.......................................................................................................... 35

    4.4.5CBE Screen.......................................................................................................................... 36

    4.4.6Pre-alarm Screen.................................................................................................................. 36

    4.4.7Horn / strobe Screen ............................................................................................................ 37

    4.4.8Feedback Screen .................................................................................................................. 37

  • 8/10/2019 FCU-6000 system manual

    6/68

    Section 5:Programming ........................................................................................................................ 38

    5.1Menu....................................................................................................................................... 38

    5.2System Management............................................................................................................... 40

    5.2.1System setting ................................................................................................................. 41

    5.2.2Password modification .................................................................................................... 425.2.3Main Reset....................................................................................................................... 43

    5.3Device Configuration.............................................................................................................. 44

    5.3.1Loop card......................................................................................................................... 45

    5.3.1.1Parameter setting .......................................................................................................... 45

    5.3.1.2Auto Programming....................................................................................................... 47

    5.3.1.3Point Programming....................................................................................................... 49

    5.3.2Annunciator Control Module .......................................................................................... 50

    5.3.2.1Parameter setting .......................................................................................................... 51

    5.3.2.2Point Programming....................................................................................................... 51

    5.3.3Remote Display ............................................................................................................... 52

    5.3.3.1Parameter setting .......................................................................................................... 53

    5.3.3.2Label Download ........................................................................................................... 53

    5.3.3.3Point Programming....................................................................................................... 54

    5.3.4CBE Programming............................................................................................................... 54

    5.3.4.1General Zone ................................................................................................................ 55

    5.3.4.2Logic Zone ................................................................................................................... 55

    5.3.5Device Control..................................................................................................................... 56

    5.3.5.1Manual Output.............................................................................................................. 57

    5.3.5.2Status Tracking............................................................................................................. 58

    5.3.5.3Walk Test ..................................................................................................................... 58

    5.3.5.4Loop Drill ..................................................................................................................... 60

    5.3.5.5Power Supply Management.......................................................................................... 60

    5.3.6History Events .......................................................................................................................... 61

    Section 6:Miscellaneous ....................................................................................................................... 62

    6.1Safety Protection Device............................................................................................................. 62

    6.2Usage and Maintenance............................................................................................................... 62

    6.3Common Troubles....................................................................................................................... 62

    6.4Transportation & Storage ............................................................................................................ 636.5Out-of-box Audit......................................................................................................................... 63

    Appendix A........................................................................................................................................... 64

  • 8/10/2019 FCU-6000 system manual

    7/68

    Section 1:About This Manual

    1.1Notes, Cautions & Warnings

    The following graphics appear in this manual to indicate a note, a caution, or

    warning:

    Note:Information that highlights an important part of the preceding orsubsequent text or illustration.

    Cautions:Information about procedures that could cause programming

    errors, runtime errors, or equipment damage.

    Warnings: Indicates information about procedures that could causeirreversible damage to the control panel, irreversible loss of programming data or

    personal injury.

    1.2Font Definition

    Special font styles used in this manual are listed in Table 1-1, Specifications of

    Manual Characters:

    Font Meaning Example

    Bold

    Key on the control panel Press the key Signals

    Silenced

    Script Name of document N-6000 User Manual

    Table 1-1 Specifications of Manual Characters

  • 8/10/2019 FCU-6000 system manual

    8/68

    Section 2:System Overview

    2.1Introduction

    The N-6000 is a new generation intelligent fire alarm control panel recently

    released by Notifier. This panel satisfies all related requirements defined in

    GB4717-2005.

    This control panel combines both alarm and CBE control functions. The N-6000

    can also be programmed off-line when using a PC with Notifier Verifire Tools

    (NVT).

    The N-6000 fire alarm control panel has many intelligent characteristics; these

    include but are not limited to drift compensation, sensitivity adjustment andself-optimizing alarm.

    The N-6000 control panel with CBE (control by event) control can manage both

    alarm paging and gas extinguishing systems. The N-6000 connected with a CRT

    display terminal forms a comprehensive and reliable fire alarm control system,

    perfect for medium to large-scale facilities.

    2.2Characteristics of the Product

    Large LCD Display

    This system uses a large 320x240 pixel LCD display. To ensure accurate and

    timely detection the LCD displays a full Chinese interface (up to 320 Chinese

    characters), equipment type, location, alarm level, loop number and address

    number upon alarming.

    User Friendly Interface

    The Menu contains all programming options. Software supports both English and

    Chinese input, full suggest and user friendly dialogue prompts. A user can

    conveniently toggle between the alarm information and CBE information screens.

    Convenient Programming Options

    Multilevel pre-alarm and alarm sensitivity enable localizing detector sensitivity for

    different applications. Have the function of trouble disenable also can choose to

    disenable any addressing unit in loop bus. Auto programming allows the N-6000

    to learn what devices are physically connected and automatically load them in

    the program with default values for all parameters. The functions mentioned above

    significantly ease system operation while reducing daily maintenance.

    Real-time Analogue Display Curve

    Real-time threshold value variation monitoring is possible for both intelligent

    analogue detectors and/or compound detectors.

    Powerful CBE Equations

  • 8/10/2019 FCU-6000 system manual

    9/68

    Accurate and Detailed Event Records

    The system automatically and categorically stores and records the latest fire alarm,

    trouble or system event. It can display and store up to 8000 historical events.

    Automatic Compensation Functions

    Drift compensation allows the detector to retain its original ability to detect actualsmoke, and resist false alarms, even as dirt or dust accumulates. It reduces

    maintenance requirements by allowing the system to automatically perform

    periodic sensitivity measurements. Smoothing filters are also provided by software

    to remove transient noise signals, usually caused by electrical interference.

    Printing Settings

    The system can be networked and prompted to print the latest alarm event using a

    Chinese printer.

    Equipped With 8 Bus Control Modules.

    Built-in Degraded Mode option. In the event of a CPU failure, the system iscapable of general alarm if a fire condition is present.

    Off-line Programming and CRT display terminal

    Connected with PC through the RS-232 interface, Screen of the control panel to

    realize programming setting on circuit configuration, CBE control relation of the

    control panel. Also can be connected with NCS through this Screen to carry out

    centralized management.

  • 8/10/2019 FCU-6000 system manual

    10/68

    Section 3:System Configuration &Installation

    3.1Features Main Performances

    Supports 1 to 30 Signaling Line Circuits (SLCs). Up to 199 detectors and 99modules (N.O. manual stations, two-wire smoke, notification or relay) per

    SLC

    Loop connection ports available, expandable up to 15 loop circuit cards

    Supports up to 64 remote LCD displays

    Supports up to 32 MCU control card

    Micro printer port

    N-CRT port provided - seamless connection to a third party system

    Fire alarm output and trouble output relays

    Real-time clock

    3.2Electrical Specifications

    Voltage range

    Input voltage: 220 VAC

    Output voltage:

    Two 24 VDC non-resetable outputs

    One 24 VDC resetable output

    Two 5 VDC outputs

    Several dry contacts - power supply trouble relay output

    Maximum output current: 14.6A

    3.3System Configuration

    Intelligent control panel: N-6000

    Remote display: LCD-100B, LDM-64B

    Intelligent detectors:

    Intelligent photoelectric smoke detector: ND-751P

    Intelligent heat detector: ND-751T

    Intelligent laser smoke detector: FSL-751

  • 8/10/2019 FCU-6000 system manual

    11/68

    Intelligent smoke detector: FSB-200S

    Intelligent base:

    B601

    B501

    Intelligent modules:

    Intelligent monitor module: MMX-7

    Intelligent monitor/control module: CMX-7

    Intelligent control module: CMX-7C

    Monitor module for two-wire 24 VDC conventional detectors:MMX-7P

    Isolator: ISO-7

    Intelligent manual call point: M500K

    Intelligent manual call point: M700K

    Micro printer: uPRT-380S

    Chinese graphic and text management software: N-NCS, N-VFT

    3.4System Block Diagram

    Fig. 3-1 System Block Diagram

    If there are many addressable units in the loop bus, user should install the

    shortcut isolator in front of the loop bus. The addressable units are less than 25

    units between adjacent two isolators.

  • 8/10/2019 FCU-6000 system manual

    12/68

    3.5Installation & Connection

    3.5.1Enclosures

    Wall-mount designs use a standard NOTIFIER C-type cabinet. This cabinet is

    shown in Fig. 3-2 Cabinet Appearance:

    Fig. 3-2 Cabinet Appearance

    Detailed cabinet dimensions are shown in Fig. 3-3:

    Fig. 3-3 C-type Cabinet Dimension Diagram

    All NOTIFIER cabinets are fabricated from 16-gauge steel. The cabinet assemblyconsists of two basic parts: a backbox and a locking door. The backbox has been

  • 8/10/2019 FCU-6000 system manual

    13/68

    engineered to provide ease-of-entry for the installer. Knockouts are positioned at

    numerous points to aid the installer in bringing a conduit into the enclosure.

    3.5.2Connection Requirements

    All incoming/outgoing external conduits should use the control panel cabinetsbottom knockout or opening for terminal connections.

    Loop transmission line adopts twisted pair cable, the type and specification are:

    RVSP21.5mm2

    Loop resistance (refers to loop resistance between the machine and two leads ofthe farthest addressing unit) should be less than 50 .

    Power wiring should use two-color multiple plastic cable, red for male terminal,

    black for female terminal. The type and specification are: RV-22.5mm2

    3.5.3Connection of Circuit Board

    Terminals

    3.5.3.1CPU Diagram

    Control panel includes in a circuit board, it has CPU and extend device interface.

    You can order the board supports for 8, 16, 30 loops. The connections terminals,

    jumper and status lights are showed below:

  • 8/10/2019 FCU-6000 system manual

    14/68

    Fig. 3-4 CPU Diagram

    Connections terminal illuminate table:

    Terminal Illumination

    TB1 System Event Relay1programmableDefault is fire alarm trigger

    TB2 System Event Relay12programmableDefault is trouble trigger

    TB3 System Event Relay13programmableDefault is reset trigger

    TB4 24VDCPower

    TB5 RS-232 Micro printer port

    TB6 RS-232 NIC port

    TB7 N-CRT PortVFTthird party system

    TB8 RPT port

    TB9 Loop communication port

    TB10 Extended device portMCU/POM-8C/MPS

    J10 Loudspeaker see J15

    J13 Power, loop and extended device channel aggregate terminal

  • 8/10/2019 FCU-6000 system manual

    15/68

    J15 Buzzer; user can select J10 or J15 to be system sound component

    Table 3-1 CPU-6000 Board Terminal Illuminate

    Jumper illuminate table:

    Terminal Illumination

    JP2 System Event Relay 1output selection 24Vor trunk node

    JP3 System Event Relay 2output selection 24Vor trunk node

    JP5 System Event Relay 3output selection 24Vor trunk node

    JP9 ISP program write down jumper, user should cover jumper cap whenISP upgrade program

    JP18 Loop RS485 communication match terminal resistance selection

    jumper

    JP19 Loop RS485 communication match terminal capacitance selection

    jumper

    JP21 Extended device RS485 communication match terminal resistanceselection jumper

    JP22 Extended device RS485 communication match terminal capacitance

    selection jumper

    JP23 RPT RS485 communication match terminal resistance selectionjumper

    JP24 RPT RS485 communication match terminal capacitance selectionjumper

    Table 3-2 CPU-6000 Board Jumper Illuminate

    LED status illuminate table:

    Terminal Illumination

    LED1 System status normalGreen

    LED2 System fire alarm and CBE eventRed

    LED3 System trouble eventYellow

    LED4 System supervise eventBlue

    LED5 Relay1relay close is green

    LED6Relay2

    relay close is green

    LED7 Relay3relay close is green

    LED8 24VDCGreen

    LED9 5VDCGreen

    LED10 Micro printer channel signal send; signal on is green

    LED11 N-CRT protocol channel signal send; signal on is green

    LED12 Micro printer channel signal receive; signal on is green

    LED13 N-CRT protocol channel signal receive; signal on is green

    LED15 RPT channel signal receive; signal on is green

  • 8/10/2019 FCU-6000 system manual

    16/68

    LED17 RPT channel signal send; signal on is green

    LED18 Extended device channel signal receive; signal on is green

    LED19 Loop channel signal receive; signal on is green

    LED20 Extended device channel signal send; signal on is green

    LED21 Loop channel signal send; signal on is green

    Table 3-3 CPU-6000 Status Light Illumination

    3.5.3.2Power Supply Connection

    The N-6000 fire alarm control panel is powered by the MPS-350W power supply

    module. This power module provides multi-path 24 VDC and 5 VDC outputs.

    During a power loss the MPS-350W battery will automatically engage and provide

    power. LED displays indicate the status of multiple functions, including: main

    power trouble, reserve power trouble, grounding trouble, storage battery chargingtrouble and power supply relay output trouble.

    Refer to the MPS-350W user manual for additional information regarding function,

    connection and/or application of the MPS-350W power supply.

    Fig. 3-5 Power Supply Connection Diagram

    Connections terminal illuminate table:

    Terminal Illumination

  • 8/10/2019 FCU-6000 system manual

    17/68

    TB1 Non-resetable 24VDC terminal

    TB2 Non-resetable 24VDC terminal

    TB3 Resetable 24VDC terminal

    TB4 Non-resetable 24VDC terminal

    TB5 Non-resetable 24VDC terminal

    TB12 Trouble relay trunk node terminal

    TB13 RS-485 serial communication port terminal

    TB14 Extended system supervise signal terminal

    Table 3-4 MPS-350 Terminal Illumination

    Jumper illuminate table:

    Terminal Illumination

    JP1 Program jumper, user can not change

    JP2 RS-485 bus terminal match capacitance

    JP3 RS-485bus terminal match resistance

    JP4/ JP5 Earth trouble function enable, disable

    Table 3-5 MPS-350 Jumper Illumination

    LED status illuminate table:

    LED Illumination

    LED1 Non-resetable 24VDC fuse melt indication

    LED2 Non-resetable 24VDC fuse melt indication

    LED3 Resetable 24VDC fuse melt indication

    LED13 Non-resetable 5VDC fuse melt indication

    LED19 Non-resetable 5VDC fuse melt indication

    LED23 Battery cut protect indication

    LED24 Battery fuse melt indication

    LED25 Power normal indication

    LED26 Power trouble indication

    LED27 Battery normal indication

    LED28 Battery trouble indication

    LED29 System running indication

    LED30 Earth trouble indication

    Table 3-6 MPS-350 Status Light Illumination

  • 8/10/2019 FCU-6000 system manual

    18/68

    3.5.3.3NIC-EC

    When N-6000 connect into N-NET fire alarm network, each control panel must

    install a NIC-EC card. Connection terminal, jumper and indicative show as below:

    Fig. 3-6 NIC-EC Connection Diagram

    Connections terminal illuminate table:

    Terminal Illumination

    TB1 Network port A

    TB2 24VDC power port

    TB3 NIC-EC and CPU-6000 communication portRS232

    TB5 Network port A

    Table 3-7 NIC-EC Terminal Illumination

    Jumper illuminate table:

    Terminal Illumination

    JP6 RS232 modeleave factory set, not to change

    JP7 Open leave factory set, not to change

    JP8 Open leave factory set, not to change

    JP9 RS232 modeleave factory set, not to change

    Table 3-8 NIC-EC Jumper Illumination

    LED status illuminate table:

  • 8/10/2019 FCU-6000 system manual

    19/68

    LED1 Green Port B signal outputBlink when signal output

    otherwise off

    LED2 Green Port B signal inputBlink when signal input

    otherwise off

    LED23 Green Port B informationstatus

    Status overturn after send or

    receive a frame informationcorrectly

    LED24 Yellow Port B troubleLED on when send or receive aframe information wrongly or

    check out communication error

    LED25 Red Port B circuit trouble LED on when any trouble occur

    LED3 Green Port A signal outputBlink when signal output

    otherwise off

    LED4 Green Port A signal inputBlink when signal input

    otherwise off

    LED20 GreenPort A information

    status

    Status overturn after send or

    receive a frame informationcorrectly

    LED21 Yellow Port A trouble

    LED on when send or receive a

    frame information wrongly orcheck out communication error

    LED22 Red Port A circuit trouble LED on when any trouble occur

    LED5 GreenSystem running

    indicationBlink when running normally

    LED6 YellowControl panel type

    indicationLED on when connect to

    CPU-6000

    LED7 RedControl panel type

    indicationLED on when connect to N-NCS

    LED8 Green+24V power status

    lightLED on when +24V power

    supply normally

    LED9 Green+5V power status

    lightLED on when +5V power supply

    normally

    LED10 GreenTB3 port signal

    inputBlink when signal input

    otherwise off

    LED11 Green J9 signal inputindication

    Blink when signal inputotherwise off

    LED12 GreenTB3 port signal

    outputBlink when signal output

    otherwise off

    LED13 GreenJ9 signal output

    indication

    Blink when signal output

    otherwise off

    LED14 Green Function reserve

    LED15 Green Function reserve

    LED16 Red Function reserve

    LED17 Green TB3 portinformation

    Status overturn after send or

    receive a frame information

  • 8/10/2019 FCU-6000 system manual

    20/68

    correctly

    LED18 Yellow TB3 port troubleLED on when receive

    information error

    LED19 RedTB3 port circuit

    troubleLED on when receive

    information error

    LED26 Blue Function reserve

    Table 3-9 NIC-EC Indicative Light Illumination

    DIP switch network address setting table:

    SW2 status Function

    ON1

    OFF

    ON2

    OFFON

    3OFF

    ON4

    OFF

    ON5

    OFF

    ON6

    OFF

    1~6bits switch

    ON for 1OFF for 0

    Composing a 6 bits binary number,

    this number infer network cardaddress. Network card address

    range is the number between 0~63.

    Network card address must be same

    as the connect devices address.

    ON Relay mode7

    OFF Bus mode

    ON N-NCS8

    OFF CPU-6000

    Table 3-10 NIC-EC Address Setting

    3.5.3.4Loop Control Module Connection

    N-6000 support 15 LCM-2 cards, and 30 loops. LCM-2 support style 4 or T-type

    wiring. TB2 in LCM-2 board connect to CUP-6000 interface, the rest connect each

    other. LCM-2 can connect with twisted shielded pair cable: signal connect to TB2,

    power connect to TB3; also can connect each other through J2 and J4.

  • 8/10/2019 FCU-6000 system manual

    21/68

    Fig. 3-7 Loop Control Module Connection Diagram

    Connection terminal illuminate table:

    Terminal Illumination

    TB2 Connect to CPU-6000RS485also can connect to LCM card

    TB3 24VDC power port

    TB4 Loop 1 portthe loop number is SW1s value

    TB5 Loop 2 portthe loop number is SW1s value1

    J2 Interlink port

    J4 Interlink port

    Table 3-11 LCM-2 Card Terminal Illumination

    Jumper illuminate table:

    Terminal Illumination

    JP1 Communication to CPU-6000 port terminal resistance (normal open)

    JP2 Communication to CPU-6000 port terminal capacitance (normalopen)

    JP4 Switch to RS232 modeleave factory set, not to change

    JP5 Switch to RS232 modeleave factory set, not to change

    Table 3-12 LCM-2 Card Jumper Illumination

    LED Status Illuminate table:

    Terminal Illumination

    LED1 3.3V system power supply indication

    LED2 24 V system power supply indication

  • 8/10/2019 FCU-6000 system manual

    22/68

    LED3 5 V system power supply indication

    LED4 CPU-6000 communication/LCM card local mode indecation

    LED5 Loop 1 running indication

    LED6 Loop 1 trouble indication

    LED7 Loop 1 fire alarm indication

    LED8 Loop 2 running indication

    LED9 Loop 2 trouble indication

    LED10 Loop 2 fire alarm indication

    LED11 Communication to CPU-6000send indication

    LED12 Communication to CPU-6000send indication

    Table 3-13 LCM-2 Card Status Light Illumination

    DIP Switch Loop Number Setting table:

    SW1~8 1~8bits switch

    ON for 1OFF for 0

    Composing a 8 bits binary number, infer LCM card

    address. SW1 setting range is the odd number between1~29

    Table 3-14 LCM-2 Loop Number Setting

    3.5.3.5MCU-16B Annunciator Control Module

    ConnectionN-6000 can connect MCU-16B. Support the manual control to output point of

    control module, and use LED to show the status of controlled points.

    MCU-16B includes 16 output indicative light, 16 feedback statuses light, 16 button

    to manual control, a complex function button, a enable/disable button and a

    manual/auto status light.

    Each manual control module can be programmed to any control module. Each

    feedback statuses light can be programmed to control an input device.

    Enable/disable button use to enable or disable 16 manual control buttons.

    MCU-16B connects to N-6000 by RS-485 port, this port can support 32MCU-16B.

  • 8/10/2019 FCU-6000 system manual

    23/68

    Fig. 3-8 Annunciator Control Module Connection Diagram

    Connection terminal illuminate table:

    Terminal Illumination

    TB1 24VDC power port

    TB2 Connect to CPU-6000RS485

    J1 Interlink port

    J3 Interlink port

    Table 3-15 MCU-16B Terminal Illumination

    Jumper illuminate table:

    Terminal Illumination

    JP1Open

    leave factory set, not to change

    JP2 Communication to CPU-6000 port terminal resistance (normalopen)

    JP3 Communication to CPU-6000 port terminal capacitance (normal

    open)

    JP4 Switch to RS232 modeleave factory set, not to change

    JP5 Switch to RS232 modeleave factory set, not to change

    JP6 Buzzer switchdefault shortcut, enable

    Table 3-16 MCU-16B Jumper Illumination

    LED Status Illuminate table:

  • 8/10/2019 FCU-6000 system manual

    24/68

    Terminal Illumination

    LED1 24 V system power supply indication

    LED2 5 V system power supply indication

    LED3 3.3 V system power supply indication

    LED4 System running indication

    LED39 Communication to CPU-6000send indication

    LED40 Communication to CPU-6000send indication

    Table 3-17 MCU-16B Status Light Illumination

    DIP Switch Loop Number Setting table:

    SW2 status function

    ON1

    OFF

    ON2

    OFF

    ON3

    OFF

    ON4

    OFF

    ON5

    OFF

    1~8bits switch

    ON for 1OFF for 0

    Composing a 5 bits binary number, thisnumber +1 infer MCUs address.

    MCUs address range is the numberbetween 1~29

    ON6

    OFFNONE

    ON7

    OFFNONE

    8 ON NONE

    Table 3-18 MCU-16B Network address setting

    3.6Equipment Debugging

    3.6.1Connection Inspection

    Visually inspect the control panel condition

    Visually inspect the external connection ports

    Open the control panel and visually inspect all connections. Confirm connectionsare correct, that there are no loose connections, no short circuits, unplugged or

  • 8/10/2019 FCU-6000 system manual

    25/68

    disconnected connectors as well as confirm the power supply does not have

    any short circuit trouble.

    Visually inspect the jumpers in the circuit to confirm there are no duplicatenumbers.

    3.6.2Power-on Inspection

    After you have finished the visual inspection, power-on the battery power supply.

    With the battery started a buzzer should be heard and the LCD should temporarily

    function normally. Once the control panel enters normal operation status, a buzzer

    and LED horn/strobe will indicate a troubled status because main power is not

    connected. Power-down and disconnect the battery power supply then connect and

    power on the main power supply. Once the control panel enters normal operation

    status, a buzzer and LED horn/strobe will indicate a troubled status because the

    battery power supply is not connected. At this time, connect the battery power

    supply. Soon after the control panel will return to normal operating status.

    During normal operation, if both the main and battery power supplies are

    connected the power supply status lamp (on the main panel of the control panel)

    will maintain normal illumination.

    When the main power supply fails because of loss of power, poor power

    connection, an over-voltage or under-voltage of 5V and 24V, or a short circuit with

    rack earth and communication trouble with the mainframe, the power supply status

    lamp (on main panel of the control panel) illumination will stop. Then both a

    buzzer and LED horn/strobe will indicate a troubled status while additional

    information will be shown on the control panel LCD.

    3.6.3External Connection

    Look for any short-circuits or disconnections to and from the control panel. Once

    everything has been inspected, connect the control panel.

    Batch installation -- connecting 10-20 detectors or modules on the loop per time --

    is highly recommended. After installing the detectors or modules restart the control

    panel to ensure the newly installed devices are recognized and installed correctly.

    If the control panel gives a trouble signal recheck the circuit and addressable

    devices are installed properly. Once the trouble signal has been solved, continuebatch installation and power testing. After all the devices have been installed, the

    simulated trouble, fire alarm and CBE event functions maybe tested. Confirm that

    the control panel alarms normally, properly links field equipment and accurately

    prints corresponding alarm information. Continue testing and adjusting until panel

    maintains normal operating status.

    3.6.4Important Points

    Avoid touching the circuit board IC chip during installation

    Pay attention to polarity during connection and installation

  • 8/10/2019 FCU-6000 system manual

    26/68

    Before starting the system, check for short circuits, disconnection or reversepolarity

    Connectors among leads shall be wielded and inter-line insulation shall beguaranteed.

    3.6.5Inspection Methods for Addressable Device

    Connections

    To test the function of the multi-meter, connect the loop in reverse polarity (the

    positive pole connects with the loop negative and the negative pole connects with

    the loop positive). The multi-meter should indicate a bias value for the diode.

    Then connect the multi-meter normally (positive pole connects with the loop

    positive and negative pole connects with the loop negative). The multi-meter

    should indicate a low resistance value that increases with the charging of the loop

    capacitor. If after proper polarity connection the multi-meter still indicates a biasvalue for the diode, there is one or more addressable device(s) connected in reverse

    polarity.

  • 8/10/2019 FCU-6000 system manual

    27/68

    Section 4:Operation

    4.1LED Indicators and Keys

    4.1.1Control Panel Display LED

    Indicators and Keys

    The N-6000 is an intelligent addressable Fire Alarm Control Panel (FACP) with

    advanced features ideal for a variety of applications. The CPU-6000 includes a

    front display/keypad enabling localized control panel viewing and programming.The display/keypad provides an easy-to-use keypad and large LCD (liquid crystal

    display) that simplifies the programming process.

    The display is 53 characters wide by 20 lines long and displays all programming

    screens. These include the events, history, devices as well as other additional

    information.

    Fields may be entered or changed and commands may be issued using the display

    keypad.

    Fig. 4-1 Display/Keypad Diagram

  • 8/10/2019 FCU-6000 system manual

    28/68

    LED Lamp Status

    LED Indicator Color Functions

    Fire alarm Red Illuminates when at least one fire alarm event exists. It will

    flash if any of these events are unacknowledged.

    Pre-alarm Red Illuminates when at least one pre-alarm event exists. It will

    flash if any of these events are unacknowledged.

    Trouble Yellow Illuminates when at least one trouble event exists. It will flash

    if any of these events are unacknowledged.

    Power Green Indicates current status of the power supply. During normal

    communication with the power supply, the lamp will flash.

    Self-test Yellow Indicates the system is in self-test status. The LED will

    remain lit during the self-test.

    CBE Red I/O module is functioning properly or there is a feedback

    signal.

    Delay Red If the control panel has a delayed control output the LED will

    remain illuminated throughout the delay period. It will turn

    off upon termination of the delay period.

    Signal Silenced Yellow Illuminates if NFS-3030 Notification Appliances have been

    silenced. It flashes if some but not all of the N-6000 NACs

    have been silenced.

    Point Disabled Yellow Illuminates when at least one device has been disabled. It will

    flash until all disabled points have been acknowledged.

    Supervisory Red Illuminates when at least one supervisory event exists. It will

    flash if any of these events are unacknowledged.

    CPU Failure Yellow Illuminates if there is an abnormal hardware or software

    condition. Contact technical support. The panel is out of

    service when this LED is illuminated or flashing.

    Table 4-1 LED Indicator Description

    Operation Keys:

    A-a: Caps lock key

    Space: During programming, change the status of the check boxto and change back to when finished

    Backspace: Backspace key

    Menu: Press to enter the menu

    Help: Help key

    PREV/NEXT: Press to skip to the previous/next control screen

  • 8/10/2019 FCU-6000 system manual

    29/68

    ESC: Escape key

    Enter: Key to acknowledge input

    TAB: Switch key, same as the NEXTkey

    : Previous page/next page/ : Previous event/next event

    Fixed Function Keys:

    Acknowledge: Acknowledge event operation

    Signals Silenced:

    1. Press for less than 1 second: carries out silencing operation onperipheral equipment

    2. Press for longer than 1 second: system exercise (please refer to

    relevant topics under loop card setting)

    Fire alarm/Pre-alarm:

    1. Press for less than 1 second: query fire alarm event

    2. Press for longer than 1 second: query pre-alarm event

    Trouble/ Horn / Strobe: Carry out query operation during troubleevent

    1. Press for less than 1 second: query trouble event

    2. Press for longer than 1 second: query horn/strobe event

    Supervision/Feedback: Carry out query operation on supervisionevent

    1. Press for less than 1 second: query supervision event

    2. Press for longer than 1 second: query feedback event

    CBE/Delay:

    1. Press for less than 1 second: query CBE event information

    2. Press for longer than 1 second: query the logic zone in delay status

    with a logic value of TRUE

    Manual/Automatic: Control manual/automatic execution link

    Lamp inspection/Self-test: System lamp inspection/self-test

    Reset: Reset system operation

  • 8/10/2019 FCU-6000 system manual

    30/68

    4.1.2Annunciator Control Module LED

    Indicators and Keys

    Fig. 4-2 Bus Control Module Schematic Diagram

    The annunciator control module has a total of 32 indicating lamps, 16 keys and 16

    feedback signals.

    One composite button: Time function key has 3 functions

    1Press for about 1 second: LED lamp below the key will illuminate locking thecontrol key module

    2Press for more than 1 second: LED lamp on the right side of the key willilluminate with manual/automatic allowed

    3Press for more than 4 seconds: horn/strobe self-test

    No. 1-16 Start Keys:

    -Press a key and the corresponding feedback signal a (Lamp 1-16) flash, whichmeans corresponding key has been pressed.

  • 8/10/2019 FCU-6000 system manual

    31/68

    -When a feedback indicating lamp (Lamp 1-16) flashes, it indicates that anoperational signal from CBE equipment has been received and the

    corresponding CBE equipment will be started.

    4.2Power-onConnect 220V AC power, and then turn on the main power supply using the switch

    inside the cabinet. Power-on Screen is shown in Fig. 4-4:

    Fig.4-3 Power-on Screen

    4.3System Self-test

    Fig. 4-4 System Self-test Screen

    After the N-6000 has been turned on, it will self-test both the hardware and

    software of the system. During the self-test all LED indicating lamps on the left

    side of the mainframe panel will flash. Once the self-test has finished a buzzer willsound and LEDs will temporarily illuminate after which the panel will return to a

  • 8/10/2019 FCU-6000 system manual

    32/68

    normal operation status. Additionally, the system will show the display screen

    while the power supply indicating lamp continues to flash.

    After a self-test, the system will show the following screen:

    Fig. 4-5 Normal System Screen

    The normal system screen is divided into three bars; these include the event

    statistics bar, the alarm screen bar and the status bar. The event statistics bar shows

    fire alarms, trouble alarms, supervision, CBE and point disabled locations. The

    status bar shows the node number, manual/automatic status, transmission

    equipment status, main or reserved power supply status, the current date/delay

    status of the latest logic zone as well as the current time.

    Manual/Automatic Status

    System in manual status

    System in automatic status

    Transmission Equipment Status

    Both delivery and feedback

    Transmission equipment in delivery status

    Transmission equipment in feedback status

    Transmission equipment in normal status without delivery or feedback

    Transmission equipment in Point disabled status

    Transmission equipment in trouble status

    Operation Status of the Main or Reserved Power Supply

    Main power normal

    Low voltage in main power

    Trouble in main power

    Battery normal

  • 8/10/2019 FCU-6000 system manual

    33/68

    Low voltage in battery

    Battery disconnected

    Current date/delay status of the latest logic zone, this item can show the current

    date. When CBE appears, it will also show delay status information of the latest

    logic zone. For example: , where ZL0099 means logic zonenumber 99 and 00001 means that CBE will output after a 1 second delay.

    4.4Event Display

    Event Order:

    First: Fire alarm, CBE, feedback

    Second: Supervision

    Third: Trouble

    Fourth: Point Disabled - disabled

    4.4.1Trouble Screen

    Fig. 4-6 Trouble Screen

    When the control panel detects a failing power supply or other trouble, it will

    execute a series of operations:

    A trouble relay will be activated and the control panel will alarm

    A system trouble indicating lamp on the control panel display will flash and theLCD will show a trouble screen

    Detailed trouble type will show the exact geographic location and occurrencetime on the LCD

  • 8/10/2019 FCU-6000 system manual

    34/68

    A trouble event will be saved to the native Flash ROM and the printer will print arecord of the trouble event

    Press the key or the key on the main panel to review the previous or

    next trouble event and press thekey to page up or down. Press

    ACKkey on the main panel to acknowledge, and all trouble events will beshown one by one. Once the alarm has silenced and all trouble events have beenacknowledged, the system trouble indicating lamp on the main panel will return to

    its normal illumination.

    The most common trouble events include but are not limited to: equipment off-line,

    grounding the equipments positive terminal, grounding the equipments negative

    terminal, the equipments positive terminal is disconnected, the equipments

    negative terminal is disconnected, power supply shows low voltage, power supply

    shows high voltage, unmatched load types, low threshold values, database errors.

    4.4.2Fire Alarm Screen

    Fig. 4-7 Fire Alarm Screen

    When a detector or monitoring module is activated (fire alarm detected), the

    control panel will execute a series of operations:

    A system alarm relay will be activated and the control panel will alarm

    A fire alarm indicating lamp on control panel display will flash and the LCD willshow a fire alarm screen.

    Detailed fire alarm name will show the exact geographic location and occurrencetime on the LCD.

    Alarm information will be saved to the native Flash and the printer will print arecord of the alarm event.

    Press thekey or thekey on main panel to review the previous or next

    fire alarm event and press thekey to page up or down. Press

    the OKkey on main panel to acknowledge, and all fire alarm events will beshown one by one. Once the alarm has silenced and all fire alarm events have been

  • 8/10/2019 FCU-6000 system manual

    35/68

    acknowledged, the system fire alarm indicating lamp on the main panel will return

    to its normal illumination.

    4.4.3Supervisory Screen

    Fig. 4-8 Supervision Screen

    The monitoring modules produce monitoring style codes. Once a monitoring

    module has been activated, the control panel will execute a series of operations:

    A monitoring relay will be activated and the control panel will alarm

    A supervision indicating lamp on the control panel will flash and the display willshow the supervision screen

    Monitoring information will be saved to the native Flash and the printer will printa record of the supervision event

    Press the key or the key on main panel review the previous or next

    fire alarm event and press thekey to page up or down. Press

    theOKkey on main panel to acknowledge all supervision information has beenshown. Once the alarm has silenced and all the supervision events have been

    acknowledged, the supervision indicating lamp on the main panel will return to its

    normal illumination.

  • 8/10/2019 FCU-6000 system manual

    36/68

    4.4.4Point Disabled Screen

    Fig. 4-9 Point Disabled Screen

    When a point disabled location exists in a loop, each disabled point (detector,

    module, and loop) will be shown one by one (see Fig. 4-10). The control panel will

    execute a series of operations:

    A point disabled indicating lamp on the control panel will flash but the controlpanel will not alarm

    A point disabled indicating lamp will be illuminated

    The point disabled information will be saved to the native Flash and the printerwill print the current point disabled information

    Press thekey or thekey on main panel of the control panel to review

    the previous or next point disabled event and press the key

    to page up or down. Press OK key on main panel of the control panel toacknowledge all Point disabled information has been shown. Once the alarm has

    silenced and all point disabled events have been acknowledged, the point disabled

    indicating lamp on the main panel will return to its normal illumination.

  • 8/10/2019 FCU-6000 system manual

    37/68

    4.4.5CBE Screen

    Fig. 4-10 CBE Screen

    4.4.6Pre-alarm Screen

    To enter the pre-alarm screen and also query the pre-alarm screen keep pressing the

    Fire alarm/Pre-alarmcomposite key on the main panel. The pre-alarm screen isshown below:

    Fig. 4-11 Pre-alarm Screen

  • 8/10/2019 FCU-6000 system manual

    38/68

    4.4.7Horn / strobe Screen

    To enter the horn/strobe screen and also query the horn/strobe screen keep pressing

    the Trouble/Horn/Strobecomposite key on the main panel. The horn/strobe

    screen is shown below:

    Fig. 4-12 Horn/Strobe Screen

    4.4.8Feedback Screen

    To enter the supervision/feedback screen and also query the supervision/feedbackscreen keep pressing theSupervision/Feedbackcomposite key on the main panel.The supervision/feedback screen is shown below:

    Fig. 4-13 Feedback Screen

  • 8/10/2019 FCU-6000 system manual

    39/68

    Section 5:Programming

    5.1Menu

  • 8/10/2019 FCU-6000 system manual

    40/68

    System Management

    Device Configuration

    CBE Programming

    Device Control

    History Event

    System Setting

    Modify Password

    Main Reset

    LCM

    DCU

    MCU

    Remote Display

    General Zone

    Logic Zone

    Manual Output

    Status Track

    Walk Test

    Power Management

    Setting

    Auto Programming

    Point Programming

    Setting

    Point Programming

    Setting

    Point Programming

    Setting

    Point Programming

    Status Track

    Download Labels

    Menu

    Fig. 5-1 N-6000 Schematic Menu Diagram

  • 8/10/2019 FCU-6000 system manual

    41/68

    When programming the control panel or reviewing history events, press the

    Menukey to view thefollowing screen:

    Fig. 5-2 User Login Screen

    Once a user has entered the correct password, he/she will enter the main menu and

    view the following screen. In the main menu screen, he/she can update or change

    the system management, device configuration, CBE programming, device control

    and history events.

    Fig. 5-3 Main Menu Screen

    5.2System Management

    Under System management the operator has 3 options; (1) System setting, (2)

    Modify Password, or (3) Main Reset. The system management screen is shown as

    follows:

  • 8/10/2019 FCU-6000 system manual

    42/68

    Fig. 5-4 System Management Screen

    5.2.1System setting

    Under System Setting the following screen will be shown:

    Fig. 5-5 System Setting Screen

    Line 1: The node is the control panels address within the network while the label is

    a description of the control panel

    Line 2: If (YES) is selected for the time server option, then this control panel is

    the time master within the network and all other panels will synchronous

    accordingly. Click the button time & date to set the time and date of the control

    panel

    Line 3: Languagedetermines the language of the control panel display. At

    present two languages are currently available: Chinese and English

    Line 4: Backlightthe duration of time the LED display remains lit. There are fourchoices available: Normal Open, Normal Close, Off in 30 Seconds and No Display.

  • 8/10/2019 FCU-6000 system manual

    43/68

    Line 5 to Line 7: Relaysthere are 3 relays each with 7 operational modes:

    Disabledthe relay is disabled

    Fire alarm outputthe relay will close upon fire alarm

    Trouble outputthe relay will close during trouble status

    CBEthe relay will close during CBE

    Supervisionthe relay will close during supervision

    CBE logic outputthe relay will only be used in CBE output expression.When the value of located expression is true, the relay will close and re-open in

    the opposite condition

    Reset outputthe relay will close during normal operation or when the systemis being reset.

    Line 8& Line 9: COM2 serial ports each with 4 operational modes:

    Degradation CBE: (YES)/ (NO). The default status (YES) is

    Normal Open. Degradation CBE only works when enabled

    Fire Alarm Verification: (YES)/ (NO). The default status is (YES).

    This function has a time sensitive fire alarm, ensuring an alarmed status will be

    accurate. This setting can greatly reduce false alarms and improve system

    efficiency

    Failover: (YES)/ (NO). The default status is (NO). Failover is the

    trouble display switch for the whole control panel. If (YES) is chosen, all

    trouble signals will be disabled without any display or alarm although a history

    record is still maintainedMain Power Supply: (YES)/ (NO). The default status is (YES),

    which installs the main power supply for the control panel

    Reserved Power Supply: (YES)/ (NO). The default status is (YES),

    which installs the reserved power supply for the control panel

    Reset Verification: (YES)/ (NO). The default status is (NO). If

    (YES) is chosen, a password needs to be entered before resetting. If (NO) is

    chosen, a password does not need to be entered before resetting

    5.2.2Password modificationUnder Password modification, a user can modify his/her password according to

    their system status (Admin, Engineer, or Guest). The password modification screen

    is shown below:

  • 8/10/2019 FCU-6000 system manual

    44/68

    Fig. 5-6 Password Modification Screen

    The N-6000 has 3 different user levels, each level is password protected. The three

    levels are (ordered from highest to lowest) Administrator, Engineer and User. Each

    level has its own password. The Administrator user can modify any password in

    the system (including the Administrator level). The User can only operate on the

    4th setting, Device Control and the 5th setting, History event. The Engineer

    can operate all five settings in the menu but will be interrupted (exit programming)

    when an alarm event occurs. The Administrator can operate all five settings in the

    menu and will not be interrupted during an alarm event.

    Factory default passwords are as follows: 333333 for Administrator, 222222 for

    Engineer and 111111 for User.

    After the initial login the user will enter the password modification screen. He/she

    can change the password by entering a new password in the Enter new password

    dialogue box and then re-entering the new password in the Confirm new

    password dialogue box. Once the system has confirmed the two passwords are the

    same, the user should pressOKto confirm the password change. After the user

    has pressed OK the password will be successfully modified, to cancel the

    previous operation press the Cancelbutton.

    Note: If an incorrect password is entered, the system will show another dialogue

    box requesting the correct password be entered.

    5.2.3Main Reset

    In the System Setting screen choose Main Reset to reset the system to all

    default factory settings.

  • 8/10/2019 FCU-6000 system manual

    45/68

    Fig. 5-7 Main Reset Screen

    After the correct Administrator password has been entered, a dialogue box will

    prompt to verify the Main Reset choice. Press OK to confirm the reset and

    restore default factory settings. Press Cancel to cancel the operation and exit the

    screen.

    5.3Device Configuration

    Choose the Device Configuration screen to adjust the settings of the loop cards,

    multi-line control modules, annunciator control modules and repeaters. Screen

    shown below:

  • 8/10/2019 FCU-6000 system manual

    46/68

    Fig. 5-8 Device Configuration Screen

    5.3.1Loop card

    In the Device Configuration screen, choose the LCM option to enter the screen

    shown below in Fig. 4-23:

    Fig. 5-9 Loop Card Screen

    5.3.1.1Parameter setting

    In the LCM screen, to adjust the settings and program options, choose Setting,

    Auto Programming, or Point programming. The screen is shown in Fig. 4-24:

  • 8/10/2019 FCU-6000 system manual

    47/68

    Fig. 5-10 Parameter Setting Screen

    Line 1: LCM- Loop number.

    Line 2: Name- Loop Description

    Line 3: Installation status these include: Uninstalled, Normal, and Disabled.

    Line 4: Time Rapid Polling - the number of preferential in-process checks, the

    default value is 0. This option controls both the point and card level settings. The

    card level setting determines the preferential times while the point level setting

    determines whether the point needs the preferential in-process check. The loop

    card will carry out preferential in-process checks on the load points where

    Preferential in-process check has been activated.

    Line 5: Style 4 Wiring - (YES)/ (NO). The system default status is

    (YES). Using style 4 wiring the circuit status can be monitored through the

    ring circuit line voltage. The system will detect differences between the positive

    and negative circuits to monitor if a disconnection trouble within the loop occurs. If

    the wiring connection does not use style 4 configuration, the mainframe will report

    a disconnection trouble.

    Line 6: Local Mode - (YES)/ (NO). If (YES) is selected, the local

    CBE setting will be effective within the loop.

    Line 7: Silenceable - (YES)/ (NO). This option controls both the point and

    card level settings. By programming definition the point level setting is the same asthe card level setting. When (YES) is chosen and a horn/strobe alarm or alarm

    bell activates, the user can press Signals Silencedon main panel of the controlpanel to silence the alarmed equipment. If (NO) is selected, the user cannot

    silence the alarmed equipment using the Signals Silencedbutton.

    Line 8: Address Conflict - (YES)/ (NO). If (YES) is selected, during

    inspection the system will search for device address duplications within a loop. If

    duplication is found, the panel will show a prompt with further instructions. If

    (NO) is chosen, the detector will not report duplicate addresses.

    Line 9: L+ Ground Fault Detect - (YES)/ (NO). When (YES) is

    selected and a positive end of the loop is grounded, the system will report positive

  • 8/10/2019 FCU-6000 system manual

    48/68

    end grounding trouble. If (NO) is chosen, the system will not report positive

    end grounding trouble.

    There are three function keys, Sync, Save, and Quit in the status bar. The

    Sync button allows the operator to download parameter settings (both card level

    and point level settings). The Save button saves the changes that have been

    selected. The Quit button allows the user to quit without saving the changes.

    5.3.1.2Auto Programming

    Fig. 5-1 Automatic Login Screen

    Each loop has 3 status options: Installed, Uninstalled, and Disabled. During normalinstallation, the programmer may enter the Auto Programming screen. When

    he/she selects a loop number for automatic programming and then presses OK,

    the system will verify each device on the selected loop.

    Caution: When either a CMX-2 control module or a M500K call point are on

    a loop using Auto Programming the control panel will misidentify the CMX-2 as

    a CMX-7(C) and misidentify the M500K as an MMX-7. When this happens, the

    user should enter 4.5.2.1.3 Point Programming screen (device configuration

    LCMpoint programming) to modify the device identity by selecting the proper

    equipment type.

  • 8/10/2019 FCU-6000 system manual

    49/68

    Fig. 5-12 Automatic Programming

    Upon completion of auto-programming, the quantity, type, and status of each

    device on the loop will be automatically shown. This is a convenient time for

    system operators to inspect, check, and manage the connected field devices. Press

    thekey or thekey to review the address and type of each point installedon the loop. The screen is shown in Fig. 5-13:

    Fig. 5-13 Auto Programming

  • 8/10/2019 FCU-6000 system manual

    50/68

  • 8/10/2019 FCU-6000 system manual

    51/68

    Local Mode: (YES)/ (NO). The factory default setting is (NO). Thisoption controls both the point and card level settings. By programming

    definition the point level setting is the same as the card level setting. If the loop

    card and mainframe have a communication failure all selected modules

    (degradation mode) will automatically output a fire alarm signal.

    Silenceable: (YES)/ (NO). When (YES) is chosen and a horn/strobe

    alarm or alarm bell activates, the user can press Signals Silencedon mainpanel of the control panel to silence the alarmed equipment. If (NO) is

    selected, the user cannot silence the alarmed equipment using the Signals

    Silencedbutton.

    Switch Inhibited: (YES)/ (NO). When (YES) is chosen manualoutput point operation is inhibited.

    Resetable: (YES)/ (NO). When (YES) is selected, the equipmentwill automatically reset all output signals when the system is reset.

    Drift Compensation: (YES)/ (NO). When (YES) is selected, thesystem will restrain individual sensors from automatically performing drift

    compensation.

    Rapid Polling: (YES)/ (NO). When (YES) is selected, the systemwill increase the frequency of in-process inspection on the loop thus increasing

    the sensitivity of the equipment.

    Alarm Verification: (YES)/ (NO). When (YES) is selected, therewill be an adjustable delay in the alarm period after a preliminary alarm has

    registered, allowing time for the alarm to be verified before sending a general

    alarm. Should an alarm condition still exist after verification, the panel willthen go into alarm. Verification time is adjustable (in seconds intervals) and

    can be customized by using the edit feature on the right side of the alarm

    verification label.

    5.3.2Annunciator Control Module

    In the MCU screen, a programmer can access the Setting and Point

    programming options for an annunciator control module.

  • 8/10/2019 FCU-6000 system manual

    52/68

    Fig. 5-15 Annunciator Control Module Screen

    5.3.2.1Parameter setting

    Fig. 5-16 Parameter setting Screen

    Line 1: MCUSelect the MCU number.

    Line 2: DescriptionDescribe the selected MCU.

    Line 3: Set the current MCU status. These include: Uninstalled, Normal and

    Disabled.

    Press Save to save the current settings. If the user presses Exit without saving,

    the following dialogue box will be prompted. At this time the user can also save the

    current settings. The user can also exit the current screen to retain previous settings;

    the current settings will not be saved.

    5.3.2.2Point Programming

    Point Programming of MCU can access to set the relative module address of keys

    and feedback led.

  • 8/10/2019 FCU-6000 system manual

    53/68

    Fig. 5-17 Point Programming Screen

    5.3.3Remote Display

    In the Remote Display screen, a programmer can access the Setting,

    Download Label and Point Programming option screens. One N-6000 fire

    alarm control panel can have up to 64 remote displays.

    Fig. 5-18 Remote Display Screen

  • 8/10/2019 FCU-6000 system manual

    54/68

    5.3.3.1Parameter setting

    Fig. 5-19 Parameter setting Screen

    Line 1: Remote displayDisplays the remote display number.

    Line 2: DescriptionDescribes the selected remote display.

    Line 3: Set the current remote display status. These include: Normal, Disabled and

    Uninstalled.

    Press Save to save the current settings. If the user presses Exit without saving,

    the following dialogue box will be prompted. At this time the user can also save the

    current settings. The user can also exit the current screen to retain previous settings;

    the current settings will not be saved.

    5.3.3.2Label Download

    Fig. 5-20 Download Label Screen

    In the Download Label screen a programmer can view detailed information byselecting the desired floor repeater number and pressing OK. At this time, the

  • 8/10/2019 FCU-6000 system manual

    55/68

    system will download relative content for each point in the selected repeater floor

    display. If past events have occurred in the selected equipment points, all

    previously downloaded contents will also be shown on the remote display. This

    allows field operators to update equipment settings for optimal device function.

    5.3.3.3Point Programming

    Fig. 5-21 Point Programming Screen

    Line 1: Displays the remote display number, point number and installation status.

    These include: Uninstalled, Normal, and Disabled.

    Line 2: Displays the current remote display point description

    Line 3: Point MappingEach remote display can have up to 64 points. Each point

    must have a specific zone and loop address. After each point has been mapped,

    during an event (fire alarm, trouble, etc) the mapped equipments location and

    event will be shown on the relative remote display screen.

    Press Save to save the current settings. If the user presses Exit without saving,

    the following dialogue box will be prompted. At this time the user can also save the

    current settings. The user can also exit the current screen to retain previous settings;

    the current settings will not be saved.

    5.3.4CBE Programming

    In the CBE Programming screen programmers can access both the General

    Zone and Logic Zone setting screens.

  • 8/10/2019 FCU-6000 system manual

    56/68

    Fig. 5-22 CBE Programming Screen

    5.3.4.1General Zone

    Within the General Zone screen a user can select zones 0-499 to review the

    relative logic equation of a particular zone. Use the VFT programming software to

    modify the logic equations as necessary.

    Fig. 5-23 General Zone

    5.3.4.2Logic Zone

    Within the Logic Zone screen a user can select zones 0-999 to review the relative

    equation of a particular zone. Use the VFT programming software equation to

    modify the logic equations as necessary.

  • 8/10/2019 FCU-6000 system manual

    57/68

    Fig. 5-24 Logic Zone

    5.3.5Device Control

    In the Device Control screen a user can access the Point Output, Status

    Tracking, Walking Test, Loop Exercise and Power Supply Management

    setting screens.

    Fig. 5-25 Device Control Screen

  • 8/10/2019 FCU-6000 system manual

    58/68

    5.3.5.1Manual Output

    Fig. 5-26 Manual Output Screen

    Within the Point Output screen a user can set the loop number, address number,

    type of equipment, label and the inspection lamp ON/OFF status. Press the

    key or the key to review a points status.

    Line 1: Displays the current loop number, address and status. These include:

    Uninstalled, Normal and Disabled.

    Line 2 & Line 3: Displays the current point description and extended description.

    Line 4: Displays the current point alarm type. These include: Fire Alarm,Supervision, Feedback and General Output.

    Line 5 & Line 6: Displays the current equipment type and model.

    Line 7: Displays the selected output module status. If the user chooses Start and

    then presses OK, the point in the current loop will be output by the module; if set

    at Close, the point will not be output by the module.

  • 8/10/2019 FCU-6000 system manual

    59/68

    5.3.5.2Status Tracking

    Fig. 5-27 Status Tracking Screen

    Within the Status Track screen a user can set the loop number, address number,

    address type as well as monitor the point.

    Line 1: Displays the current loop number, loop address and its status. These include:

    Uninstalled, Normal and Disabled.

    Line 2 & Line 3: Displays the current point description and extended description.

    Line 4: Displays the current point alarm type. These include: Fire Alarm,

    Supervision, Feedback and General Output.

    Line 5 & Line 6: Display the current equipment type and model.

    Line 7: Displays the current point status.

    5.3.5.3Walk Test

    Fig. 5-28 Walk Test Screen

  • 8/10/2019 FCU-6000 system manual

    60/68

    Within the Walk Test screen a user can set the loop number, address number,

    address type as well as run a walking test on a particular loop.

    Line 1: Displays the loop number, current address and installation status. These

    include: Uninstalled, Normal and Disabled.

    Line 2 & Line 3: Displays the current point description and extended description.Line 4: Displays the current point alarm type. These include: Fire Alarm,

    Supervision, Feedback and General Output.

    Line 5 & Line 6: Displays the current equipment type and model.

    After adjusting the systems settings, pressing theLamp inspection/Self-testkeyon main panel will cause the control panel to run a self-test on the current loop.

    During this test, both the self-test indicating lamp and the load verification lamp

    will be normally illuminated. Press Review the Result to view every address in

    the current walk test, the addresses will be displayed on the right hand side of the

    walk test interface screen (Fig. 4-50).

    Fig. 5-29 Walk Test Address Screen

    Press OK to control current point set in the loop.

  • 8/10/2019 FCU-6000 system manual

    61/68

    5.3.5.4Loop Drill

    Fig. 5-30 Loop Drill Screen

    5.3.5.5Power Supply Management

    Fig. 5-31 Power Management Screen

    N-6000 fire alarm control panel uses the MPS-350W power supply. Within the

    Power Management screen the user can review the current status of each power

    supply.

    Line 1: Displays the currently connected power supply type. The MPS-350W is the

    primary power supply for the N-6000.

    Line 2: Displays the current status and voltage of the main power supply.

    Line 3: Displays the current status and voltage of the reserved power supply.

    Line 4: Press Dischargeto discharge the power supply. Press Stopto stop

    discharging. Press Exitto exit the power supply control screen.

  • 8/10/2019 FCU-6000 system manual

    62/68

    5.3.6History Events

    Within the History Events screen a user can access the systems history

    records/events. This screen is seen below:

    Fig. 5-32 History Event Screen

    Line 1: Displays the type of history event. History event types include but are not

    limited to: fire alarm, trouble, supervision, CBE and Isolation. When All Events

    is selected, detailed information will be provided for each event. If All Events is

    not selected the user must select a particular event to view the additional and

    detailed information.

    Line 2: Displays the total number of events that can be reviewed.

    Line 3: Displays the status of the current event. The operator may obtain detailed

    information about the current event including location, type, time of occurrence,

    serial number, as well as additional information from the following text box.

    Line 4: Press Exitto exit the history event screen.

    Pressing theNEXTkey or thePREVkey on main panel of the control panel,a user can review the detailed description of the next or previous history event.

    N-6000 can record and display up to 8000 individual history events.

  • 8/10/2019 FCU-6000 system manual

    63/68

    Section 6:Miscellaneous

    6.1Safety Protection Device

    The N-6000 has been designed with built-in safety devices to protect both the operator and

    control panel in case of improper use and/or installation. These devices include an anti-misplugterminal which can endure extremely high voltage and current ensuring the safety of both

    operators as well as the control panel. Additionally the control panel has current limitingprotection for the power supply, protection circuits for communication devices, and special

    grounding terminals provided within the cabinet.

    6.2Usage and MaintenanceTo ensure consistent and reliable operation the following items should be observed andfollowed:

    The control panel must be installed and debugged by qualified technicians

    The operator on duty should be familiar with the current building structure as well asunderstand all possible control panel events and operations

    An operator should monitor the control panel status to eliminate various trouble signals andprevent alarm signals when possible

    If a power failure exceeds 8 hours, the reserve power supply should be disconnected to avoid

    damage due to over-dischargeIf additional construction is performed in the protected building, shut down the control panel

    to ensure fire detection capabilities are not compromised

    During any status other than operation (transportation, storage, etc), the reserve power supplyshould be disconnected from the control panel

    6.3Common Troubles

    The N-6000 has advanced features such as self-diagnosis and self-protection; however even

    with the advanced technology an occasional trouble signal is unavoidable. Table 5-1 has

    additional information regarding common troubles.

    Trouble Cause analysis Solution

    Poor AC220V connectionRe-connect the AC220V

    power supplyMain power supply

    trouble Fuse blowing out due to external

    short circuit or over-currentReplace the fuse

    Poor plug connection Check connectorsReserved power

    supply trouble

    Reserved power supply damagedReplace reserved power

    supply

  • 8/10/2019 FCU-6000 system manual

    64/68

    Trouble Cause analysis Solution

    Fuse blowing out due to external

    short circuit or over-currentReplace the fuse

    Poor connection between LCD and

    display module cardCheck connectors

    Failure to regulate the luminance Regulate the luminanceLCD display fails

    Backlight socket connected

    improperly

    Disconnect and plug the

    socket in again

    Keypad failsSoft panel socket block connected

    improperly

    Disconnect and plug the

    socket in again

    No soundLoudspeaker socket connected

    improperly

    Disconnect and plug the

    socket in again

    Short circuit in loop bus Clear short circuit

    Short circuit in loop Reverse connection of addressing

    unit

    Check connection of the

    addressing unit

    Inaccurate clockClock chip M410T socket

    connected improperly or damagedReplace clock chip M410T

    Table 5-1 Common Troubles

    For additional trouble not found in Table 5-1 please contact the dealer or manufacturer directly.

    6.4Transportation & StorageAfter a post-factory inspection, the control panel can be stored. During storage the control

    panel must be stored under normal atmospheric condition, ambient temperature and in a dryroom for a maximum of 6-months. During transportation the control panel must be kept

    right-side up and protected from heavy overhead weight. The control panel can be transportedby train, truck, plane or ship.

    Once the control panel has been opened, the user must use the control panel in accordance withthis manual. When used in conjunction with this manual all operation results will meet the

    performance and functional requirements defined by this manual.

    6.5Out-of-box Audit

    When opening the control panel box for the first time the user should carry out an out-of-boxaudit to ensure the control panel is complete, untouched and undamaged from transportation.

    The control panel should include: a CPU, loop card, MCU, POM-8A, MPS-350W,complement keys and connecting wires, etc.

    Open the control panel door to ensure all internal connections are normal and that there are noloose connections, short circuits and/or disconnected items. Check the power supply status to

    ensure it is normal and does not have any short circuits, etc.

  • 8/10/2019 FCU-6000 system manual

    65/68

    Appendix A

    Alarm level cross-reference table for the ND682 photoelectric smoke detector:

    Alarm level setting

    Actual physical threshold range of

    alarm

    (Unit: 0.1 OBS%/FT)

    LEVEL 1 0 -2.5

    LEVEL 2 2.5 5

    LEVEL 3 5 - 7.5

    LEVEL 4 7.5 10

    LEVEL 5 10 -14

    LEVEL 6 14 16

    LEVEL 7 16 -18

    LEVEL 8 18 20

    LEVEL 9 over 20

    LEVEL 10 Over 20

    Table 1: Alarm level cross-reference table for the ND682

    Alarm level cross-reference table for the ND685 heat detector:

    Alarm level setting

    Actual physical threshold range ofalarm

    (Unit C)

    LEVEL 1 30 34

    LEVEL 2 34 37

    LEVEL 3 37 40

    LEVEL 4 40 45

    LEVEL 5 45 50

    LEVEL 6 50 55

    LEVEL 7 55 60

    LEVEL 8 60 65

    LEVEL 9 Over 65

    LEVEL 10 Over 65

    Table 2: Alarm level cross-reference table for the ND685

    Alarm level cross-reference table for the FSL-751 detector:

    Alarm level setting Actual physical threshold range of

  • 8/10/2019 FCU-6000 system manual

    66/68

    alarm

    (Unit: 0.01%/ft)

    LEVEL 1 0 2

    LEVEL 2 2 3

    LEVEL 3 3 10

    LEVEL 4 10 50

    LEVEL 5 50 100

    LEVEL 6 100 150

    LEVEL 7 150 200

    Table 3: Alarm level cross-reference table for FSL-751

    The following is the trouble level cross-reference table for drift compensation:

    Alarm level settingPhysical value of drift compensation

    (Unit: 0.01%/ft)

    LEVEL 1Warning 30

    LEVEL 2Warning 60

    LEVEL 3Trouble 90

    Table 4: Alarm level cross-reference table for FSL-751

  • 8/10/2019 FCU-6000 system manual

    67/68

    Limited Warranty

    NOTIFIERwarrants its products to be free from defects in materials and

    workmanship for eighteen (18) months from the date of manufacture, undernormal use and service. Products are date stamped at time of manufacture.The sole and exclusive obligation ofNOTIFIERis to repair or replace, at its

    option, free of charge for parts and labor, any part which is defective inmaterials or workmanship under normal use and service. For products notunder NOTIFIERmanufacturing datestamp control, the warranty is eighteen

    (18) months from date of original purchase byNOTIFIER 's distributor

    unless the installation instructions or catalog sets forth a shorter period, inwhich case the shorter period shall apply. This warranty is void if the productis altered, repaired or serviced by anyone other than NOTIFIERor its

    authorized distributors or if there is a failure to maintain the products andsystems in which they operate in a proper and workable manner. In case ofdefect, secure a Return Material Authorization form from our customerservice department. Return product, transportation prepaid, toNOTIFIER, 12

    Clintonville Road, Northford, Connecticut 06472-1653.

    This writing constitutes the only warranty made by NOTIFIERwith respect toits products. NOTIFIERdoes not represent that its products will prevent any

    loss by fire or otherwise, or that its products will in all cases provide theprotection for which they are installed or intended. Buyer acknowledges thatNOTIFIER

    is not an insurer and assumes no risk for loss or damages or the

    cost of any inconvenience,transportation, damage, misuse, abuse, accident or similar incident.

    NOTIFIERGIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF

    MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OROTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THEFACE HEREOF. UNDER NO CIRCUMSTANCES SHALL NOTIFIERBE

    LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT,INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, ORINABILITY TO USE NOTIFIERPRODUCTS. FURTHERMORE, NOTIFIER

    SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICHMAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL,COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS.

    This warranty replaces all previous warranties and is the only warranty madeby NOTIFIER. No increase or alteration, written or verbal, of the obligation of

    this warranty is authorized.

    "NOTIFIER" is a registered trademark.

  • 8/10/2019 FCU-6000 system manual

    68/68