Fault Location Principles
-
Upload
arun-prakash -
Category
Documents
-
view
225 -
download
0
Transcript of Fault Location Principles
-
7/28/2019 Fault Location Principles
1/13
ABBGroupMarch26,2012|Slide1
Fault Location
Principles
Dr. MURARI MOHAN SAHAABB AB
Vsters, SwedenKTH/EH2740 Lecture 4
ABBGroupMarch26,2012|Slide2
Dr. Murari Mohan Saha was born i n 1947 in Bangladesh. He receivedB.Sc.E.E. from Bangladesh Universit y of Technology (BUET), Dhaka in 1968
and compl eted M.Sc.E.E. in 1970. During 1969-1971, he was a lect urer at theE.E. dept.,BUET. In 1972 he compl eted M.S.E.E and in 1975 he was awardedwith Ph.D. from The Technical Universit y of Warsaw, Poland. He joined ASEA,Sweden in 1975 as a Development Engineer and currently is a SeniorResearch and Development Engineer at AB B AB, Vsters, Sweden. He is a
Senior Member of IEEE (USA) and a Fellow of IET (UK). He is a r egisteredEuropean Engineer (EUR ING) and a Chartered Engineer (CEng). His areas of
interest are measuring transformers, power system analysis and simulation,and digital protective relays. He holds 35 granted patents and produces morethan 200 technical papers. He is the co-author of a book, entit led, Faultlocation on Power Networks , published by Springer, January 2010.
Presenter
ABBGroupMarch26,2012|Slide3
Contents
Introduction
One-end fault location
Two-end/Multiterminal fault location
Fault location on distribution networks
Conclusions
Information aboutbookon FaultLocation
ABBGroupMarch26,2012|Slide4
Introduction
ABBGroupMarch26,2012|Slide5
It is a device or apparatus placed at one end of a station, which displays thedistance to fault (in km or in % of line) following a fault in a transmission line.
ZA ZB
ZL
Line
Relay
FaultLocator
Line
Relay
Line section length
Fault distance
Introduction What is a Fault Locator?
ABBGroupMarch26,2012|Slide6
Introduction
When a fault occurs on a line (distribution ortransmission), it is very important for the utility toidentify the fault location as quickly as possible forimproving the service reliability.
If a fault location cannot be identified quickly and thisproduces prolonged line outage during a period ofpeak load, severe economic losses may occur andreliability of service may be questioned.
All these circumstances have raised the greatimportance of fault-location research studies and thusthe problem has attracted widespread attention amongresearchers in power-system technology in recentyears.
-
7/28/2019 Fault Location Principles
2/13
ABBGroupMarch26,2012|Slide7
Introduction
Fault location is a process aimed at locating the
occurred fault with the highest possibly accuracy.
Fau lt l oc ator is mainly the supplementaryprotection equipment, which apply the fault-locationalgorithms for estimating the distance to fault.
When locating faults on the line consisting of morethan one section, i.e., in the case of a three-terminalor multi-terminal line, the faulted section has to beidentified and a fault on this section has to be located.
ABBGroupMarch26,2012|Slide8
Introduction
A fault-location function can be implemented into:
microprocessor-based protective relays
digital fault recorders (DFRs)
stand-alone fault locators
post-fault analysis programs
ABBGroupMarch26,2012|Slide9
Introduction
Fault locators versus protective relays differences related to the following features:
accuracy of fault location
speed of determining the fault position
speed of transmitting data from remote site
used data window
digital filtering of input signals and complexityof calculations
ABBGroupMarch26,2012|Slide10
Introduction
General division of fault location techniques:
technique based on fundamental-frequency currentsand voltages mainly on impedance measurement
technique based on traveling-wave phenomenon
technique based on high-frequency componentsof currents and voltages generated by faults
knowledge-based approaches
unconventional techniques (fault indicators installed either insubstations or on towers along the line; monitoring transients of
induced radiation from power-system arcing faults using both VLF
and VHF reception )
ABBGroupMarch26,2012|Slide11
Voltage & Current MeasurementChains
ABBGroupMarch26,2012|Slide12
Voltage & Current Measurement Chains
CURRENT
TRANSFORMERS
vp
ip
vs
is
v2(n)
i2(n)
POWER
SYSTEM
CTs
VTsMatching
Transformers
MatchingTransformers
Analogu eFilters
Analogu e
Filters
A/D
A/D
-
7/28/2019 Fault Location Principles
3/13
-
7/28/2019 Fault Location Principles
4/13
First Stand Alone NumericalFault Locator on Commercial Use
where:
FFLAA RIpZIU
A
FAF
D
II
SBLSA
SBLA
ZZZ
Zp)Z-(1D
EA
pZL
Fault Locator
Line section length
Fault distance
EB
ZSA ZSB(1-p)ZL
RF
IB
IA
IF
A B
One-end Fault Location Algorithm Compensatingfor Remote End Infeed Effect
where:
FA
FALAA R
D
IpZIU
L
SB
LA
A1
Z
Z
ZI
UK 1
0RKKpKp F3212
L
SB
LA
A2
Z
Z
ZI
UK 1
L
SBSA
LA
FA3
Z
ZZ
ZI
IK 1
One-end Fault Location Algorithm Compensatingfor Remote End Infeed Effect
where:
OAPOMFA
FALAA IZR
D
IpZIU
LSBSA
SBLSBSAA
ZZ2Z
ZZZp)(Z-(1D
2
)
ZL
ZSA
ZSB
pZL
FL
FL
P
IOAP
ZOM
RF
(1-p)ZL
One-end Fault LocationAlgorithm Compensating forRemote End InfeedEffect Case of Parallel Lines
Relay input Input transformers
Filter low pass
Multiplexer
Hold circuit
Analog/digital converter
Micro processor
Telemeter outputLed-indykator
Parameter setting
Data and program memory
Peripheral interface adapter
Printer output
Input signals from:Line protectionTrip Phase selection Currents Voltages
Collection of I0
inparallel lines
1) 2)
Measuring transformers
One-end Fault LocationAlgorithm Compensating for
Remote End InfeedEffect Hardware Configuration
One-end Fault LocationAlgorithm Compensating for
Remote End InfeedEffect Field Results Experienced
Installation Event Results
1 Sweden, 130 kV, 76 km P-E fault, July 1982 67.6 km67.0 km (error 0.8%)
2 USA, 138 kV, 23.3 km Five staged faul ts on paral lel Maximum error of 3%lines, Oc tober 1983 (wi thout compensat.)
3 Sp ai n, 400 k V, 135 k m P-E fau lt , Mar ch 1984 Di sp lay ed i n t he
93 to 99% of line range 93 to 99%4 It al y, 380 k V, 88 .5 k m P- E f au lt , Feb ru ar y 1984 16 % (n o er ro r)
16% of line
5 Norw ay , 45 kV, 29 .3 km P-P faul t, December 1984 77% (e rror 0.5%)77% of line
6 Fi nl an d, 1 10 k V, 130 k m P-E f au lt s, J un e 1985 Di sp lay ed i n t he78 to 90% of line range 78 to 90%
(error max 0.4%)
7 In di a, 400 kV , 23 6 k m P-E fau lt s, Dec em ber 1987 (n o er ro r)76 to 78% of line
-
7/28/2019 Fault Location Principles
5/13
Optimization of One-end FaultLocation
Optimization of One-end Fault Location
BA
dZL (1d)ZL
{iA}
ZAE
A
F
EB
ZB
FLd
{uA}
Aim :
improving fault location accuracy by introducingcompensation for shunt capacitances limiting influence of uncertain parameters on faultlocation accuracy to get simple formulae by applying generalized faultloop model and fault model
Optimization of One-end Fault Location
Symmetrical components approach appears as veryeffective technique for transposed lines and faultlocation algorithm is formulated in terms of thesecomponents (positive-, negative- and zero-sequence)
Ac
Ab
Aa
2
2
2A
1A
0A
aa1
aa1
111
3
1
V
V
V
V
V
V
)3/2exp(ja
Optimization of One-end Fault Location
0)(F0F0F2F2F1F1FA_P1LA_P
IaIaIaRIZdU
Generalized fault loop model:
d, RF unknown distance to fault (p.u.) and fault resistance
UA_P , IA_P fault loop voltage and current (dependent on fault type)
Z1L line impedance for the positive-sequence
IF1, IF2, IF0 symmetrical components of the ttotal fault current
aF1, aF2, aF0 weighting coefficients (dependent on fault type)
Optimization of One-end Fault Location
A00A22A11A_PUaUaUaU
A0
1L
0L0A22A11A_P
IZ
ZaIaIaI
AII0
1LI
0mAI0
1LI
0LI0AI22AI11A_P
IZ
ZI
Z
ZaIaIaI
a1, a2, a0 share coefficients (dependent on fault type)
Fault loop voltage and current (in terms of symmetrical components):
Fault loop voltage:
Fault loop current single line:
Fault loop current parallel lines:
Optimization of One-end Fault Location
F2F2F1F1F0F0F IaIaIaI
aF0, aF1, aF2 weighting coefficients (complex numbers),dependent on fault type and the assumed priority for usingparticular symmetrical components,
IF0, IF1, IF2 zero-, positive-and negative-sequencecomponents of total fault current, which are to be calculatedor estimated
Total fault current can be expressed as the weighted sumofits symmetrical components:
-
7/28/2019 Fault Location Principles
6/13
Optimization of One-end Fault Location
0F0001
2
2 RAAdAdA
1L12ZKA
A_P11L11ZKZLA
A_P10
ZLA
A_P
1A2F2A1F100
)(
I
MIaIaA
Fault location formula:
After resolving intoreal/imag parts theunknowns: d, RF aredetermined
Optimization of One-end Fault Location
0)(comp
F0F0
comp
F2F2
comp
F1F1F
comp
A01L
0Lsh
)1(00
comp
A2
sh
)1(22
comp
A1
sh
111L)(A_P)(
)1(
IaIaIaRI
Z
ZAaIAaIAaZdU
nn nnn
A1
th
1
'
L1)1(A1
comp
A1 )1(5.0 UAYdII
nn
A2
th
2
'
L2A2
comp
A2 )1()1(5.0 UAYdII
nn
A0
th
0
'
L0)1(A0
comp
A0 )1(5.0 UAYdII
nn
BA IAi
UAi
UFi
UBi
IBiF
IFi
IFi
IAAi
sh
L)( )1( ni
'
inAZd
th
L)1( )1(5.0
n
i
'
inAYd
sh
L)( )1()1(
ni
'
inBZd
th
L)1( )1()1(5.0
ni
'
inBYd
comp
AiI
Compensation for shunt capacitances of the line:
Optimization of One-end Fault Location
0 10 20 30 40 50 60
0.6
0.8
1
Dis
tancetofault(p.u.)
Fault time (ms)
No compensation
daver.
=0.7806 p.u.
0 10 20 30 40 50 60
0.6
0.8
1
Distancetofault(p.u.)
Fault time (ms)
With compensation
daver.
=0.8032 p.u.
Example: 400kV, 300km line; a-g fault, d=0.8 pu, RF=10
Due to compensation the error decreases from1.94% to 0.32%
Fault Location on Parallel Lineswith measurements at one-end
Fault Location on Parallel Lines under Availability of
Complete Measurements at One End
AB
IAB
IAA
VAA
AA
BB
BA
F
dFL
Fault Location on Parallel Lines under Availability of
Complete Measurements at One End
Traditional one-end FLs for parallel lines applythe following standard input signals:
phase voltages
phase currents from the faulted line
zero-sequence current from the healthy line(to compensate for the mutual coupling)
Limitationss of the traditional one-end FLs:
pre-fault measurements are required
remote source impedance data has to be provided
-
7/28/2019 Fault Location Principles
7/13
Two-end Fault Location
Two-end FaultLocation
One-terminal methods have some limitations due tonecessity of taking simplifying assumptions
Two-Terminal methods give better results but require
communications
Methods using Global Positioning Satellites (GPS)
- synchronized phasors from both ends
Methods requiring time-tagging of events
- no synchronized phasors
Low-speed communications needed for two-end faultlocation
Analyze data from two ends at a third, more convenient site
Two-end FaultLocation Synchronized Measurements
~
MUA
A B
~
MUB
GPS
FL
d,RF
RF
d[p.u.]
~
MUA
A B
~
MUB
FL
d,RF
RF
d[p.u.]
Two-end FaultLocation Unsynchronized Measurements
tA
tA=0
tB
t
tB=0
t
FLT
t=tB=0
()
(1t)
FLT DETECTION AT "A"
tFLT
FLT DETECTION AT "B"
sampling interval
TB-A
Need for phase alignment:
Two-end FaultLocation Unsynchronized Measurements Two-end FaultLocation use of incomplete measurements
Use of incomplete two-end measurements:
two-end currents and one-end voltage (2xI +1xV)
one-end current and two-end voltages (1xI +2xV)
two-end voltages (2xV)
two-end currents (2xI)
-
7/28/2019 Fault Location Principles
8/13
Fault location (FL) function added to current differential relay
Use of two-end synchronised measurements of three-phasecurrents and additionally providing the local three-phase voltage
SYSTEM A
A BF
DIFF
RELA
{iA}
SYSTEM B
DIFF
RELB
dA, R
FAFL
dA
ZL
(1dA)Z
L
{IB}
{vA}
{IA}
{iB}
Two-end FaultLocation use of: 2xI +1xV Two-end FaultLocation use of: 1xI +2xV
SYSTEM A
A B
F
FLCOMMUNICATION
SYSTEM B
SATUR.
dA, R
F
LAZd LA )1( Zd
jAeI
jAeV
BI
BV
pre
Immunity of fault locationto saturation of CTs at one lineside is assured by rejecting currents from saturated CTs
Three-end & Multi-end FaultLocation
Three-end FaultLocation
Use of measurements: synchronized three-phase currents from all (A, B, C) ends three-phase voltage at Fault Locatorbus A
A B
TI
A
VA
IB
FLRESULTS
CI
B
PROTECTIVERELAY'B'
PROTECTIVE
RELAY'C'
IC
IB
IC
IA
IC
IAPROTECTIVE
RELAY 'A'
FL
Solution
Fault location algorithm consists of three subroutines
(SUB_A, SUB_B, SUB_C) and the procedure for selecting
the valid subroutine
SYSTEM A
AB
T
FL
IA
SYSTEM B
VA
IB
SUB_A
FL RESULTS
CIC
dAdB
dCSYSTEM C
SUB_B
SUB_C
Selectionof faulted line section
1. Fault distance calculation assuming the fault
to be on t he AT, TB or TC segment: 3 different
results
2. Selection procedure is based on checking the
rejection conditions:
fault occurring outside the section range
calculated fault resistance has negative value
correctness of the estimated remote source
impedances
General algorithm:
-
7/28/2019 Fault Location Principles
9/13
FaultLocationExample
A B
TI
A
VA
IB
FL RESULTS
C
IC
PROTECTIVERELAY 'B'
PROTECTIVERELAY 'C'
FA FB
FC
IC
IB
IA
IB
IC
IA
FL
PROTECTIVERELAY 'A'
Network parameters:
Line: , (/km)
System A: ,
System B:
System C:
j0.3151)0276.0(L1 '
Z j1.0265)275.0(L0 '
Z
j3.693)+0.65125(SA1Z j6.5735)+1.159(SA0Z
SASB 2= ii ZZ
SASB 3= ii ZZ
F/km012.01 LC F/km008.00 LC
a-g fault at the section TB, dB=0.6 p.u., RFC=0.3
FaultLocationExample (1)
A BT
C
SUB_B
0 10 20 30 40 50 600
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
Post fault time [ms]
Distancetofault[p.u.]
(dB)av
=0.6042
(dA)av
=1.6933
(dC)av
=0.6726
0 10 20 30 40 50 60-1
-0.8
-0.6
-0.4
-0.2
0
0.2
0.4
0.6
0.8
1
Post fault time [ms]
(RFC
)AV
= 0.6721
(RFB
)AV
=0.3232
Faultresistance[]
SUB_B is selected as valid one
Four-end Fault Location
Use of measurements: synchronized three-phase currents fromall (A, B, C, D) ends three-phase voltage at Fault Locatorbus A
SYSTEMC
SYSTEMD
Fault Location in Distribut ion(Medium Voltage) Networks
Introduction
Fault location in MV networks differs from that in HV/EHVtransmission lines
When a current of a faulty line is not directly available in theFL, certain error is introduced when assumed the current atthe substation
MV line may be multi-terminal and/or contain loops whatcreates problem in single ended fault location
In the case of MV line, there are often loads located betweenfault point and the busbar. Since the loads change and areunknown to the FL it is difficult to compensate of them
Issues forDistribution Networks
Network grounding
ungrounded networks
Petersons coil
resistance grounded
Lack of measured data for tapped loads
fault on a main or on a tap?
Unbalanced network configuration and load
Dynamic change in a network configuration
Change in conductor impedance
Multiple faults
-
7/28/2019 Fault Location Principles
10/13
Algorithm Structure
Estimation of the
impedance
Estimation of the
distance
Which feeder
short-circuited?
Information from
relays and/or CBs
c urrents v olt ages
impedance
distance
Digital Fault Recorder
orEMTP/ATP simulator
Fault-Loop Impedance Measurement
Z1
Z2
Zk
Zm
kC
kB
kA
k
I
I
I
I
kC
kB
kA
k
V
V
V
V
Impedance Measured at the Faulty Feeder
Phase-phase fault lo op:
Phase-ground fault loo p:
I I Ikpp kA kB
V V Vpp A B
kZ Z
ZkN
0 1
13
I I I IkN kA kB kC
Z Z0 1, Fault -loo p im pedan ces for faul t at the consi dered nod e
ZV
Ik
pp
kpp
ZV
I k I
k
ph
kph kN kN
Distance to Fault Estimation
Zpk-1 Zpk
lfk-1
Zsk-1 (1-lfk-1 )Zsk-1
Rf
k-1 k
Equivalent diagram of the cable segment with fault:
EMTP/ATP simulation with anUtility Network
Scheme of the Considered Network
Substationgrounding
HV LV
150 kV/10 kV
Zsys
RtgRg
Vsys IS
IL
VS
-
7/28/2019 Fault Location Principles
11/13
Scheme of Distribution Network
equivalenta equivalentb
equivalentc equivalentd equivalente
1 2 3 4
5 6 7
89
10
1112
13
14
15
16 17 18 19
20
21
grounding systemconnection
Idea of the feeder model representation: Current measured at the faulty feeder: Feeder 2.08
Distance to Fault Calculation from the Recorded Data
No File Fault type Estimated Distance
to Fault, m
1 97031400.MAT A-B GAMR-RURW - 8867 mGAMR-BJCG - 8935 m
2 97031401.MAT A-B BETR-GAMR - 8491 m
3 97031402.MAT A-B GAMR-RURW - 8880 mGAMR-BJCG - 8918 m
4 97031403.MAT A-G GAMR-RURW - 8780 mGAMR-BJCG - 8776 m
5 97031404.MAT A-G BETR-GAMR - 8431 m
No File Fault type Estimated Distance
to Fault, m
1 97031400.MAT A-B GAMR-RURW - 8867 mGAMR-BJCG - 8935 m
2 97031401.MAT A-B BETR-GAMR - 8491 m
3 97031402.MAT A-B GAMR-RURW - 8880 mGAMR-BJCG - 8918 m
4 97031403.MAT A-G GAMR-RURW - 8780 mGAMR-BJCG - 8776 m
5 97031404.MAT A-G BETR-GAMR - 8431 m
Actual faultat 8999 m
Current measured at the substation: Feeder 2.08
No File Fault type Estimated Distance
to Fault, m
1 97031400.MAT A-B GAMR-RURW - 8854 mGAMR-BJ CG - 8762 m
2 97031401.MAT A-B GAMR-RURW - 8745 mGAMR-BJ CG - 8755 m
3 97031402.MAT A-G GAMR-RURW - 8776 mGAMR-BJ CG - 8772 m
4 97031403.MAT A-G GAMR-RURW - 8897 mGAMR-BJ CG - 8889 m
Distance to Fault Calculation from the Recorded Data
Actual faultat 8999 m
Comparison of EMTP/ATP simulationwith recorded Stage Fault
EMTP Simulation: Comparison with Recorded Stage Fault EMTP Simulation:Comparison with Recorded Stage Fault
-
7/28/2019 Fault Location Principles
12/13
Conclusions
Conlusions Benefits of Fault Location
Quick elimination of permanent fault to: minimize outage time facilitate service and maintenance minimize production losses reduce cost
Pinpointing of weak spots due to temporary
fault to: assist patrol in finding excessive tree growth allow rapid arrival at the site of vandalism
Conclusions
Accurate fault location is key to improved operations andlower maintenance cost
Selection of a fault location method depends on networkconfiguration, communications, and requirements
One-terminal methods have limited accuracy
Two-terminal methods give higher accuracy
Analysis at convenient site using data from existing Pdevices
The fault location algorithmcaneasily be expandedto coverlines with three-terminals and evenmore
Fault location algorithmfor Medium Voltage Network isbased on voltage and current phasor estimation. Thealgorithm was investigated and proved on the basis ofvoltage and current data obtained from EMTP/ATPsimulations as well as recorded at DFR experiences
Fault Location on Power NetworksBook Series Power SystemsISSN 1612-1287Publisher Springer LondonDOI 10.1007/978-1-84882-886-5Copyright 2010ISBN 978-1-84882-885-8 (Print) 978-1-84882-886-5 (Online)
Fault Location On Power Networks
Fault Location on Power Lines enables readers to pinpoint thelocation of a fault on power lines following a disturbance.The nine chapters are organised according to the design ofdifferent locators. The authors have compiled detailedinformation to allow for in-depth comparison.Fault Location on Power Lines describes basic algorithmsused in fault locators, focusing on fault location on overheadtransmission lines, but also covering fault location indistribution networks. An application of artificial intelligence in this field is alsopresented, to help the reader to understand all aspects of faultlocation on overhead lines, including both the design andapplication standpoints. Professional engineers, researchers, and postgraduate andundergraduate students will find Fault Location on PowerLines a valuable resource, which enables them to reproducecomplete algorithms of digital fault locators in their basicforms.
-
7/28/2019 Fault Location Principles
13/13
Tableof Contents
1. Fault Location - Basic Concepts and Characteristic ofMethods
2. Network Configurations and Models3. Power-line Faults - Models and Analysis4. Signal Processing for Fault Location5. Measurement Chains of Fault Locators6. One-end Impedance-based Fault-location Algorithms7. Two-end and Multi-end Fault-location Algorithms8. Fault Location in Distribution Networks9. Artificial Intelligence Application
References (352)