Extended Run Time “NB” Model N1C L-Series UPS · • Eliminate UPS Battery Replacements •...

2
“Disrupting the Uninterruptible Power Industry” N1C L-Series UPS Lithium-Ion (LiFePO 4 ) Online Double Conversion UPS Systems 2 kVA Model with External Battery Module 110/120VAC or 208/220/230/240VAC Rack and Tower Mountable Lower Total Cost of Ownership vs. Most Competitors Connect up to 5 External Battey Modules 60+ Minutes of backup time at 100% Load per EBM FAR More Run Time than Lead Acid Eliminate UPS Battery Replacements 15-Year Battery Life Expectancy 10-Year Replacement Warranty Included KEY BENEFITS of Lithium-Ion High Power Density - Lithium-Ion batteries have over 5 times the energy and take up about 1/3 the space of a VRLA-based solution that delivers the same power. This means more power in the same or smaller footprint. More power also means longer backup run times for your critical loads! Smaller Footprint - A smaller footprint translates to reduced cooling requirements, as well as about two-thirds reduction in weight. This offers the installation flexibility needed by many IT Departments. Heat Tolerant - L-Series UPS units can handle working temperatures of up to 140ºF. Where VRLA battery life is reduced by half for every 10ºF over 71ºF, Li-Ion battery life is largely unaffected. Life Span - The average life span of a VRLA battery is 3-5 years in ideal conditions. N1C Lithium-Ion battery life is 10-15 years in nearly all conditions. Long life batteries reduce the burden and cost of down time and maintenance. Environmentally Friendly - Other than the obvious — that Lithium- Ion batteries do not use lead — there are many other “green” benefits. Lithium-Ion batteries require less charging time and power, need to be replaced less often, and use less energy to produce and transport. N1 Critical Technologies, Inc. “Leaders In Lithium” 211 N. Parker Drive Janesville, WI 53545 855-208-0011 [email protected] lithium-ion-ups.com Extended Run Time “NB” Model

Transcript of Extended Run Time “NB” Model N1C L-Series UPS · • Eliminate UPS Battery Replacements •...

Page 1: Extended Run Time “NB” Model N1C L-Series UPS · • Eliminate UPS Battery Replacements • 15-Year Battery Life Expectancy • 10-Year Replacement Warranty Included KEY BENEFITS

“Disrupting the Uninterruptible Power Industry”

N1C L-Series UPSLithium-Ion (LiFePO4)

Online Double Conversion UPS Systems

• 2 kVA Model with External Battery Module• 110/120VAC or 208/220/230/240VAC• Rack and Tower Mountable• Lower Total Cost of Ownership vs. Most Competitors• Connect up to 5 External Battey Modules

• 60+ Minutes of backup time at 100% Load per EBM• FAR More Run Time than Lead Acid • Eliminate UPS Battery Replacements• 15-Year Battery Life Expectancy• 10-Year Replacement Warranty Included

KEY BENEFITS of Lithium-IonHigh Power Density - Lithium-Ion batteries have over 5 times the energy and take up about 1/3 the space of a VRLA-based solution that delivers the same power. This means more power in the same or smaller footprint. More power also means longer backup run times for your critical loads!

Smaller Footprint - A smaller footprint translates to reduced cooling requirements, as well as about two-thirds reduction in weight. This offers the installation flexibility needed by many IT Departments.

Heat Tolerant - L-Series UPS units can handle working temperatures of up to 140ºF. Where VRLA battery life is reduced by half for every 10ºF over 71ºF, Li-Ion battery life is largely unaffected.

Life Span - The average life span of a VRLA battery is 3-5 years in ideal conditions. N1C Lithium-Ion battery life is 10-15 years in nearly all conditions. Long life batteries reduce the burden and cost of down time and maintenance.

Environmentally Friendly - Other than the obvious — that Lithium- Ion batteries do not use lead — there are many other “green” benefits. Lithium-Ion batteries require less charging time and power, need to be replaced less often, and use less energy to produce and transport.

N1 Critical Technologies, Inc.“Leaders In Lithium”211 N. Parker DriveJanesville, WI [email protected]

Extended Run Time “NB” Model

Page 2: Extended Run Time “NB” Model N1C L-Series UPS · • Eliminate UPS Battery Replacements • 15-Year Battery Life Expectancy • 10-Year Replacement Warranty Included KEY BENEFITS

MODEL N1C.L2000NB + EBM N1C.L2000GNB + EBM

INPU

T Voltage (Vac) 110/120 selectable 208/220/230/240 selectable

Frequency (Hz) 50/60±5% (±10% is selectable)

Power Factor 0.9

OU

TPU

T

Capacity (VA/W) 2000/1800

Voltage (Vac) 110/120±2% 208/220/230/240±2%

Frequency (Hz) 50/60±0.2% (battery mode)

Waveform Sine wave, THD<3% at linear load

Transfer Time 0 ms

Overload 105~129% for 60 seconds, 130~150% for 30 seconds, >150% for 300 ms

Input Connection 5-20P (3ft) L6-20P (3ft)

Outlets (6) 5-15/20R (6) C13 + (1) C19

BATT

ERY

Voltage (Vdc) 48Vdc

EBM Connection Connect up to 5 EBMs. Locking, inter-connect battery cabling included.

Run Time (HH:MM:SS) at 25% Load / 50% Load / 100% Load

1 EBM4:46:30 / 2:18:20 / 1:09:10

2 EBMs9:13:00 / 4:36:40 / 2:18:15

3 EBMs14:19:30 /6:56:06 /3:27:30

4 EBMs19:06:00 /9:13:20 /4:36:40

5 EBMs23:52:30 / 11:31:50 /

5:45:50

Battery Capacity (Ah) 50Ah per EBM

Charger Current (A) Max 6A, Battery Monitoring System Included

Battery Life 10+ year design life (77ºF) & 4500+ charge/discharge cycles

OTH

ER

Communication Interface SNMP Network Card, USB, EPO

Topology Online Double Conversion

Alarm Low battery, Abnormal AC input, UPS failure

Protection Low battery, overload, short-circuit and over temperature

Working Temperature 32-140ºF (UPS) / 32-122ºF (EBM)

Relative Humidity 0~95%, No condensation

Dimensions (HxWxD) (in)* 3.4” (2U) x 17.2” x 22.6” (UPS) / 3.4” (2U) x 17.2” x 16.2” (EBM)

Net Weight (lb) 22 (UPS) / 53 (EBM)

Technical Specifications

L-Series Lithium-Ion UPS with EBM

Specifications are subject to change without prior notice* Please allow approximately 3” additional depth for power cords

N1 Critical Technologies, Inc.855-208-0011 | [email protected]

2U UPS Head Unit

2U External Battery

Interlocking Rack-Mount Kit Available Separately

Most Power,Smallest SpaceTo get 60+ minutes of battery run-time at 100% load you would need: • 4 EBMs from APC (67 mins)• 3 EBMs from CyberPower (79 mins)• 3 EBMs from TrippLite (90 mins)• 3 EBMs from Vertiv (62 mins)• 2 EBMs from Eaton (61 mins)• 1 EBM from N1C (69 mins)

N1C.L2000NB vs. Eaton 9PX2000RT, CyberPower OL2200RTXL2U, TrippLite SU2200RTXLCD2U, Vertiv GTX4-2000RT120, APC SRT2200RMXLA. All competitors’ runtimes collected from competitors’ product websites.