  • CASE STUDY FOR

    EXPLOSION, IMPLOSION

    FIRE

    I n d u s t r i a l l o s s e s r e p o r t e d u n d e r

    S t a n d a r d F i r e P o l i c y

    ( M a t e r i a l D a m a g e )

  • E x p l o s i o n i n J e t d y e i n g m a c h i n e

    (Textile processing plant)

  • WHAT HAPPENED

    Re process ing o f dyed fabr ic was

    undertaken in the Jet Dyeing (which i s a

    normal pract i ce ) to ad just qual i ty .

    After loading fabr ic in je t dye ing , operator

    s tarted heat ing and c i rculat ion o f the

    fabr ic and moved towards the contro l panel

    f or set t ing temperature and other

    parameters .

    At that instant , there was a sudden

    explos ion in the je t dye ing machine .

    What could be route cause o f explos ion?

  • WHAT HAPPENED

    Due to explosion upper portion of theJet Dyeing m/c was flown in mainprocessing plant & Jet Dyeing m/cwas found deformed.

    Due to flowing of material controlpanel at near by was damaged,Building roof was damaged. Stock atnear by were torn due to fall ing ofmaterial and damaged property

    Some o f proper ty in ma in process ing p lant a l so damaged .

  • INCIDENT PHOTOS

    D a m a g e d J e t D y e i n g M a c h i n e a n d s u r r o u n d i n g p r o p e r t y .

  • INCIDENT PHOTOS

    P o r t i o n o f J e t D y e i n g m a c h i n e t h r o w n o f f d u e t o e x p l o s i o n

  • INCIDENT PHOTOS

    Damage to surrounding property - 1

  • INCIDENT PHOTOS

    Damage to surrounding property- 2

  • I m p l o s i o n i n S p r a y d r y e r u n i t

    C e r a m i c P l a n t G u j a r a t

  • INCIDENT

    450 TPD Spray dryer was in operation formanufacturing of clay.

    Evaporation rate of Sprayer dryer was 8000 Kg/Hr.and operating at 650 to 7000C.

    Unit was hollow vessel (cone type at bottom)insulated with sera wool.

    Clay slurry was sprayed through spray guns and hotair was blown

    Spray dryer was shut down after completion of lot.Within few minutes dryer imploded severely

    There was no fire or smoke observed nor adjoiningproperty damaged nor human injury reported

  • PROBABLE CAUSE

    After the shutdown of the dryer, heaters mighthave been stopped, but the air blowers mighthave been kept on.

    Subsequently, due to flow of cool air inside thedryer, the hot gases/vapors which were notescaped, the dryer (probably due to stoppage ofexhaust) might have cooled suddenly resultinginto an - Implosion.

  • DAMAGES

    Main chamber of spray dryer was badly incompressed condition with insulation.

    Internally, entire steel fabricated structure wasfound badly deformed & compressed to greatextent.

    External aluminum sheet with sera wool inside,used was also badly damaged and deformed,pressed inside.

  • PHOTOGRAPHS

  • PHOTOGRAPHS

  • PHOTOGRAPHS

  • E x p l o s i o n i n f u e l s t o r a g e d e p o t d u e t o

    f u e l o v e r f l o w f r o m t a n k u n d e r f i l l i n g

    - B u n c e f i e l d f u e l d e p o t

  • PLANT SITE BEFORE INCIDENT

  • WHAT HAPPENED

    Out o f ser ies o f tank ,one tank fu l ly loaded

    with Petro l was igni ted due to a spark .

    Due to spark i t got igni ted and exploded

    v io lent ly and subsequent ly f i re generated

    which last for four days .

    In addi t ion to depot destruct ion , extens ive

    nearby property damage , and smoke

    nuisance further loca l ground water was

    contaminated by foamy f i re water runof f .

    Huge quant i ty o f impounded runof f was

    decontaminated and was to be d isposed o f f

  • THE INCIDENT

    Somewhere in 2005 depot erupted in

    explos ion and f i re .

    This was one o f the s trongest explos ion &

    probably largest in Europe

    Inc ident cont inued for four days

    About 20 tanks were destroyed

    43 People destroyed

    Many nearby establ ishment destroyed

    Ground water contaminated

    Near by land fer t i l i ty los t

  • SITE AFTER INCIDENT

  • INCIDENT

    Fi l l ing o f two tanks were s tarted in

    morning thro p ipe l ine and was

    expected to cont inue for next

    At near by truck loading was go ing on

    One o f these tank was f i l l ed to leve l

    and leve l indicator s topped changing

    but f i l l ing was cont inued(Not s topped)

    This tank over f i l l ed excess ive ly and

    s tarted to over f low and drain in bund

    Immediate ly vapor c loud f lowing

    observed f rom bund in a l l d i rect ion

  • INCIDENT

    Meanwhi l e o ther tank f in i shed f i l l ing and

    c l o sed supp ly va lve hence i t cause

    increase in f l ow ra te t o f i r s t tank whi ch

    l ead t o excess ive over f l ow

    In be tween one o f t ruck dr iver sme l l fue l

    odor & S imul taneous ly opera to r observed

    l eakage .

    Star ted d iver t ing the fue l f i l l ing and

    opera t ing the va lves f o r c l o s ing supp ly

    One o f opera to r s tar ted f i r e pump. In the

    course o f s tar t up probab ly vapor i gn i ted

    l ead t o the exp los i on & subsequent ly

    genera te the f i r e s in the tank fa rm.