Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project
-
Upload
mastura405 -
Category
Documents
-
view
220 -
download
0
Transcript of Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project
-
7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project
1/12
Evaluation of the flood mitigation effect of a Paddy Field Dam project
N. Yoshikawa a,*, N. Nagao b, S. Misawa c
a Research Center for Natural Hazard and Disaster Recovery, Niigata University, 8050 Ikarashi 2-no-cho, Nishi-ku, Niigata 950-2181, Japanb Toyama Prefectural Federation of Land Improvement Association, 17 Kurosaki, Toyama 939-8214, Japanc Faculty of Agriculture, Niigata University, 8050 Ikarashi 2-no-cho, Nishi-ku, Niigata 950-2181, Japan
1. Introduction
Recent climatic change has brought about a significant increase
in the frequency of unusually heavy rain events in Asian monsoon
regions. According to the Fourth Assessment Report of the
Intergovernmental Panel on Climate Change (IPCC, 2007), it is
very likely that heavy rainfall events will continue to become more
frequent at middle and high latitudes. The Extreme Weather
Report 2005 written by the Japan Meteorological Agency (2005)
also reported on the basis of an analysis of the rainfall pattern for
104 recent years that the numbers of days with intense
precipitation exceeding 100 and 200 mm have increased 1.19
and 1.46 times, respectively, when comparing the first 30 years of
thelast century (19011930) with themost recent30 years (1975
2004).
There has been a recent increase in the risk of flood disaster in
Japan owing not only to the changes in frequency and intensity of
rainfall, but also to changes in land use and modernization of
agriculture leading to the expansion of impervious areas and
shortening of the arrival time of floods. Although investments have
been made in infrastructure for protection against flood damage
such as dam construction, bank heightening, river widening, and/
or channel dredging, further investment in such large-scale
structural measures is not realistic owing to increasing concern
about the negative impact on the natural environment, in addition
to the huge costs to the government.
To overcome these problems, making use of paddy fields as a
flood control system has been highlighted. The paddy fields
themselves are considered to possess an innate flood mitigation
function (Abler, 2004; Matsuno, 2006; Groenfeldt, 2006; Kimet al.,
2006; Huang et al., 2006). Various studies at national and regional
scales have been carried out to evaluate this flood control function.
Shimura (1982), for the first time, estimated the flood water
storage capacity of all paddy fields at 8.1 billion m3, which by far
exceeds 2.4 billion m3, the total flood detention capacity of flood
control dams in Japan. Regional cases have also been investigated
taking into consideration topographical features; for example, the
cases of terraced paddy fields in sloped areas (Onishi et al., 2004)
and paddy fields in low-lying flat areas (Nakamura et al., 1994;
Hiramatsu and Shikasho, 2001). Most of these regional case studies
concluded that paddy fields play an important role in increasing
the water storage capacity of river basins and lower the peak flows
of rivers to a certain extent, but not to the same degree as Shimura
(1982) estimated. Some studies found a significant rise in peak
Agricultural Water Management 97 (2010) 259270
A R T I C L E I N F O
Article history:
Received 21 January 2009
Received in revised form 24 September 2009Accepted 26 September 2009
Available online 25 October 2009
Keywords:
Paddy field
Runoff control devices
Flood control function
Unsteady flow model
Kinematic wave model
Water balance analysis
A B S T R A C T
To mitigate flood damage due to a recent increase in the frequency and magnitude of heavy rainfall
events, the Kamihayashi district in Niigata prefecture, Japan, has undertaken flood mitigation measures
using paddy fields by installingrunoff control devices in drainage boxes of paddy field plots.The purpose
of this study is to evaluate theflood mitigation performance of thePaddyField Dam project in terms of a
decrease in discharge volume, drop in channel water level and reduction of inundation damage using
combined hydrologic analyses and flood routing. The model constructed for runoff analysis is composed
of three modules: a hilly/residential area module in which the overland flow is estimated using the
kinematic wave method, a paddy field module in which runoff from paddy fields is calculated using
water balance analysis, and a channel network module in which flood routing is performed using a one-
dimensional unsteadyflow model.The outputs of thefirsttwo modules arethe input of thethirdmodule.
The result of the simulation shows the main channel discharge decreased by 26% and the water level
dropped by 0.17 m in the case of the largest observed rainfall event. The simulated effect was larger for
larger rainfall events. In terms of flood water volume, the runoff control devices have the effect of
reducing the flood damage due to the 50-year return period rainfall event to almost that due to the 10-
year return period rainfall event.
2009 Elsevier B.V. All rights reserved.
* Corresponding author. Tel.: +81 25 262 6653; fax: +81 25 262 6653.
E-mail address: [email protected](N. Yoshikawa).
Contents lists available at ScienceDirect
Agricultural Water Management
j o u r n a l h o m e p a g e : w w w . e l s e v i e r . c o m / l o c a t e / a g w a t
0378-3774/$ see front matter 2009 Elsevier B.V. All rights reserved.
doi:10.1016/j.agwat.2009.09.017
mailto:[email protected]://www.sciencedirect.com/science/journal/03783774http://dx.doi.org/10.1016/j.agwat.2009.09.017http://dx.doi.org/10.1016/j.agwat.2009.09.017http://www.sciencedirect.com/science/journal/03783774mailto:[email protected] -
7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project
2/12
runoff with the transformation of paddy fields to other land uses
such as upland dry fields or the abandonment of cultivation (Chiba
et al., 1997; Masumoto et al., 1997; Wu et al., 2001; Masumoto
et al., 2003). To standardize the evaluation of the flood controlfunction, Masumoto et al. (2006) proposed a method and an index
at a macro scale using the relationship between drainage and
storage capacity.
These studies have contributed to the understanding of the
flood mitigating role of paddy fields and suggest that haphazard
urbanization and abandonment of paddy cultivation may increase
the negative impact on therunoff characteristic. However,it seems
clear that mere conservation of the existing paddy fields will at
most maintain the status quo.
To address the recent increase in the flood risk, an unconven-
tional measure for flood mitigation has been recently introduced
using existing paddy fields with enhanced flood control function as
an inexpensive and environmentally sustainable technique. This
measure is termed the Paddy Field Dam, in which rain water isintentionally stored in the paddy fields temporarily at times of
intense rainfall by installing runoff control devices in the drainage
boxes of paddy field plots. Although paddy fields are not deep,
usually surrounded by a levee 1530 cm high, the areal extentover
which they spread is large and they therefore provide ample water
storage potential.
The purpose of this study is to evaluate the flood mitigation
performance of the Paddy Field Dam, paddy fields with runoff
control devices, using combined hydrologic analyses and flood
routing. The effect is presented by the changes in flow volume and
water level of thedrainagechannel andthe inundation volumeand
duration at the city center.
2. The Paddy Field Dam project
2.1. Description of the Paddy Field Dam project
The Paddy Field Dam is an experimental flood control measure
launched in 2002 in Kamihayashi village, Niigata prefecture, Japan,
takingadvantage of thepondingcharacteristics of paddyfields. The
paddy fields within theproject site areinstalled with runoffcontrol
devices in theform of orifice restriction platesto reinforcethe flood
control function that they innately possess. The reason for the
project being termed the Paddy Field Dam is that the paddy fields
with the reinforced function store excessive rainwater and thus
lowers the peak discharge just like ordinary flood control dams do,
even though it does not fall into the definition of a dam, strictly
speaking.
The basic structure of the paddy fields in the study area is
almost uniform in terms of shape and size as a result of the land
consolidation and reallocation work in the 1980s: 5000 m2 plots
equipped with two concrete drainage boxes, which are connectedto a drainage channel with a 150 mm inner diameter pipe. In
general, the water level in the paddy fields is maintained at
approximately 5 cm above the paddy field surface during the
ponding season by placing a rectangular weir at the inlet of
the drainage boxes just as for standard paddy fields in Japan. The
excess water then flows into the drainage channel along the paddy
field plots.
The runoff control devices are structurally simple; 300 mm 300 mm wooden orifice restriction plates with 50 mm orifices are
installed on the bottom of the drainage boxes, approximately
40 cm below the paddy field surface. This shrinks the drain orifice
of the boxes from the original pipe size of 15050 mm, reducing
the orifice area to one-ninth that of the original pipe as illustrated
in Fig. 1.One may worry about possible negative impacts on the rice
production due to the retardation of drainage. However, there may
be little damage to the rice crops unless they are completely
submerged for several days since rice is one of the most tolerant
crops against submergence (Inoue, 1999). Since the maximum
ponding depth inside the paddy fields is the height of the levees,
complete submergence occurs only when the water level of the
drainage channel adjacent to the paddy fields increases above the
height of the levees. It means that inundation would be
unavoidable whether or notthe runoff control devices are installed
because the effect of the Paddy Field Dam is rather to lower the
water level of the drainage channel by controlling the runoff from
paddy fields.
Although temporary complete submergence may occur whenthe top of the rice plant is still below the top of the levees of the
paddy fields, approximately 1 month after the transplantation in
the beginning of May in Japan, rice plants would already have
grown higher than the levees by the rainy season, which begins in
the middle of June.
2.2. Mechanism of surface runoff control for the Paddy Field Dam
When the runoff control devices are not installed during the
ponding season, the volume of surface water runoff from a paddy
field plot is determined only by the height and length of the
rectangular weir set at the inlet of a drainage box and the overflow
depth above the rectangular weir, which in turn determines the
ponding depth of the paddy field. On the other hand, in the case of
Fig. 1. Paddy field drainage system. Two drainage boxes are installed and equipped with a runoff control device for each 0.5 ha standard-size paddy field plot.
N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270260
-
7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project
3/12
runoff control devices being installed, the runoff is regulated by
either the rectangular weir or the orifice size of the runoff control
devices depending upon the water depth of thepaddyfield. That is,
the runoff control devices function only when the water inflow
from the paddy field to the drainage box exceeds the outflow
capacity of the orifice; otherwise, the surface runoff is regulated by
theoverflowing runoff above the rectangular weir regardless of the
existence of the devices. Therefore, the surface runoff QS (m3 s1)
can be expressed by
QS
RectangularWeir Equation
QW 2EbH03=2 2EbH D3=2 when QW QOOrifice Equation
QO 2CaOffiffiffiffiffiffiffiffiffiffi
2gh0
q 2CaO
ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi2gH d
qwhen QW>QO
8>>>>>:
(1)
where QWis the surface overflow runoffabovethe rectangular weir
(m3 s1), Eis the weir coefficient, b is the weir length (m), H is the
head above the top of the weir (m), H is the water depth of the
paddy field (m), D is the height of the weir (m), QO is the discharge
via the orifice (m3 s1), C is the orifice coefficient, aO is the area of
the orifice (m2), gis the gravitational acceleration (m s2), h0 is thevertical distance between the water surface of the paddy field and
the bottom of the drainage box (m), and d is the vertical distancebetween the paddy field surface and the bottom of the drainage
box (m) (Fig. 1). The number 2 in both equations indicates that
each standard-size paddy field is equipped with two drainage
boxes.
The regulating factors may differ during the season of
midsummer drainage, a common practice of paddy cultivation
in Japan in which paddy fields are dried out for about 10 days
between the end of June and the beginning of July to control
surplus tillering and supply plant roots with oxygen. In this period,
the rectangular weirs are removed to release all the ponded water
and several shallow furrows are excavated on the paddy field
surface toward the drainage boxes to promote quick drainage of
the remaining water. Since the soil dries up during this period, the
surface runoff begins as soon as the soil surface is saturated whenheavy rainfall occurs. In this case, the factors determining the
rainfallrunoff relations are more complex and need to be
quantified without using the rectangular weir equation, although
once the water inflow from the paddy field to the drainage box
exceeds the outflow capacity of the orifice, the orifice size of the
runoff control devices becomes the regulating factor. Because of
the variations in the density and depth of the furrows made on the
surfaces of paddy fields, the runoff characteristics may differ with
respect to each paddy field plot. Therefore, the average rainfall
runoff relations before the runoff control devices come into effect
need to be derived somehow. In this study, a tank model
(Sugawara, 1972) in which the runoff from the control devices
is incorporated is adopted for this purpose.
3. Materials and methods
3.1. Study area
The study was carried out in the Ishikawa River watershed,
Kamihayashi village, Niigata prefecture, Japan. The Ishikawa River
drains the entire 60.6 km2 watershed, which comprises hilly areas
(69%), paddy fields (26%) and residential areas (5%) (Fig. 2). The
Ishikawa River then flows into the Sea of Japan. The watershed can
be divided into two areas by drainage systems: an area of
gravitational drainage and an area of pumping drainage. The city
center of Kamihayashi village is situated in the lower part of the
watershed of the Fuefuki River (6.24 km2), one of the tributaries of
the Ishikawa River, which largely coincides with the gravitational
drainage area. Most of the remaining area coincides with the
pumping drainage area. After flowing through the city center, the
Fuefuki River joins the mainstream of the Ishikawa River. The city
center area (approximately0.099 km2) has an altitude only slightly
above sea level and is, therefore, subject to frequent flood water
damage from the upstream water as well as from backwater
caused by the rising of the Ishikawa River when intensive rainfall
events occur.
The project site comprising paddy fields (3.54 km2) and
residential areas (0.88 km2) is located within the Fuefuki River
watershed. Forthe purpose of this study,the inclusion of thewhole
Ishikawa River watershed in the analysis was necessary because
the water level and discharge of the Fuefuki River are significantly
influenced by the water level of the Ishikawa River, which is in part
determined by thetidalcondition of theSea of Japan.Therefore, the
Fuefuki River watershed is treated as an inner drainage basin and
the Ishikawa River watershed as an outer river basin because the
analysis for the latter was performed only to determine the water
level boundary condition of the Fuefuki River watershed.
3.2. Field measurements
The study period was 2 years between April 2006 and March
2008. The channel water level was continuously measured andrecorded at 10 min intervals at six important sites in the study
watershed using water level sensors (Hi-net,HTV-020KP) and data
loggers (HIOKI, 3635-55). Precipitation was also measured with a
tipping bucket rain gauge (Davis Instruments, Rain collector II) at
10 min intervals. The channel flow velocity was intensively
measured where the water level sensors were installed when
heavy rainfall events occurred.
3.3. Field experiment
To investigate the surface runoff characteristics of the paddy
fields with and without the runoff control devices, field experi-
ments using standard-size paddy field plots were implemented.
The paddy fields plots were intentionally ponded with irrigationwater as deep as possible by clogging the drainage outlets, and
then the ponded water was released from the paddy field plots
through the twodrainage boxes of each paddy field plot. The water
level was continuously recorded with the water level sensors and
data loggers.
In general, the output components of the water budget of a
paddy field plot include percolation and evapotranspiration
besides the surface runoff. However, evapotranspiration is not
taken into consideration in this study on the assumption that
evapotranspiration is negligible during heavy rainfall events.
Percolation was measured by filling the paddy field with water
with the drainage outlets clogged and recording the fall in the
water level at night. This experiment was implemented twice for
different water levels: 120 and 50 mm.
3.4. Observed rainfall event and design hyetographs
The only heavy rainfall event during the study period occurred
on the 29th of July 2007. Fig. 3 is the hyetograph of the observed
rainfall event. The total rainfall depth was 101.8 mm, the return
period of which is determined as being approximately equivalent
to 3.7 years by fitting the Gumbel distribution to the available 85-
year annual maximum rainfall data. Although the total depth does
not seem to be outstandingly large, about 80% of the rainfall was
concentrated within 8 h between 5.00 and 12.00 a.m.
To evaluate the flood mitigation function of the runoff control
devices forlarger rainfall events, the design storms for 10-year and
50-year return periods were generated using the alternating block
N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270 261
-
7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project
4/12
method from intensitydurationfrequency (IDF) curves (Chowet al., 1988) (Fig. 4). The IDF curves for the study area were
obtained from the Niigata prefectural government.
4. Model development
4.1. Watershed model and analytical framework
Runoff analyses were conducted to quantify the effect of the
runoff control devices in terms of the fall in water level and
decrease in discharge of channels. The model constructed for the
runoff analysis is composed of three modules: a paddy field
module in which runoff from the paddy fields is calculated by
water balance analyses, a hilly/residential area module in which
the overland flow is estimated using the kinematic wave method,
anda channel network module in which flood routing is performedusing a one-dimensional unsteady flow model. The outputs of the
first two modules are the input of the third module.
4.2. Paddy field module
Using the coefficients of the rectangular weir and orifice of the
runoff control devices determined through the field experiment,
the runoff from a paddy field plot is simulated by
I O dSdt
; (2)
where I is the rainfall inflow to the paddy field, O is the outflow
consisting of the runoff volumevia therectangularweirs or orifices
Fig. 2. Description of the study area.
N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270262
-
7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project
5/12
and the percolation loss, Sis the ponded volume and tis time. The
ponded volume can be approximated as
S1 S2 DH 12R1 R2Dt
1
2
QS1
QS2AP
12 qPER1 qPER2 Dt (3)where subscripts 1 and 2 denote the time steps of each variable at
t= t1 and t= t2, R is the rainfall depth (m), QS is the surface runoff
volume (m3 s1), qPER is the depth of the loss caused by percolation
(m) and AP is the area of the paddy field plot (m2).
In the case of the ponding season, the value of QS is calculated
using either the rectangular weir equation or the orifice equation
depending upon the ponded water depth whereas it is calculated
using the tank model with the runoff through the runoff control
devices as shown in Fig. 5 in the case of the midsummer drainage
season.
The constructed tank model reproduces the actual paddy field
structure, where aTis therunoff coefficient, qSrepresents the depth
of surface runoff from the study paddy field block (m), qPERrepresents the percolation depth (m), His the ponded water depth
(m) and HI is the initial ponded water depth (m). To offset the
individual specificity of the paddy fields, the model was applied to
the study paddy field block comprising 12 standard-size paddy
field plots, and the results are compared with the runoff observed
at the channel outlet of the study block. The parameter aT was
optimized using the least squares method to reproduce the
observed runoff. qS is always proportional to the ponded water
depth in the case without the runoff control devices. On the other
hand, the regulating factors of qS shift in the case with runoff
control devices depending upon the ponded water depth;that is, qSis regulated to be proportional to the ponded water depth when qT
(the runoff calculated using the tank model) qO (the runoffcalculated using theorifice equation)and determined by theorifice
of the runoff control devices when qT> qO. The value ofqPER is the
percolation depth observed in the field measurement.
4.3. Hilly/residential area module
4.3.1. Basic concept of a kinematic wave model
A kinematic wave model (Chow et al., 1988; Vieux et al., 1990;
Singh, 1996) was used to simulate the flow in the hilly and
residential areas. The kinematic wave equations can be written in
the form of the continuity equation:
@h
@t @QK
@x re (4)
and momentum equation:
QK ahm; (5)
where QKis the runoff volume (m3 s1), h is the flow depth (m), tistime (s), x is the down slope position, and re is effective rainfall
depth (m). a and m are the kinematic wave parameter and
exponent, respectively. Given that Mannings principle is satisfied,
a and m can respectively be written as
a ffiffi
Ip
n; (6)
m 53; (7)
where I is the longitudinal bed slope and n is the equivalent
roughness.
Fig. 3. Observed rainfall on the 29th of June 2007.Fig. 5. Tankmodel reproducing the paddyfield block.qTand qO represent qScalculated
by the tank model and by the orifice equation at an arbitrary ponded water depth,
respectively. The regulating factors switch depending on the ponded water depth.
Fig. 4. Design hyetographs for the 10-year (left) and 50-year (right) return periods generated using the alternating block method.
N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270 263
-
7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project
6/12
4.3.2. Subcatchments of the hilly area
Since the hilly area comprises several subcatchments, the
runoff from each subcatchment eventually flows into different
channel sections as lateral inflow. To determine the destination of
runoff, the hilly area was divided into subcatchments using a
digital elevation model and a GIS (ESRI, ArcGIS 9.2).
The average longitudinal bed slope (I) of each subcatchment
was also calculated using the GIS. The equivalent roughness
coefficient (n) was determined on the basis of calibration usingsubcatchment A (Fig. 2), where discharge was continuously
measured and applied to all other subcatchments assuming the
surface roughness is similar throughout the hilly area of the study
watershed.
4.3.3. Subcatchments of residential areas
Residential areas including the city center were identified on
the basis of a plan of the drainage channel network obtained from
the local water management office. The average slope of each
district was determined using the digital elevation model. The
equivalent roughness coefficient was assumed to be 0.1, a common
hydraulic recommendation for residential areas (Japanese Ministry
of Construction, 1976) since no direct measurement for calibration
was taken.
4.4. Channel network module
4.4.1. Basic concept of the unsteady flow model
The basic governing equations of an unsteady open channel
flow are the continuity equation:
@aC@t
@QC@xC
QLAT (8)
and momentum equation:
1
g
@vC
@t @hC@xC
12g
@v2C
@xC @z@xC
n2Q2C
a2
C
R4=3 0; (9)
where aC is the cross-sectional area of flow (m2), QC is the flow
volume passing through the cross-section (m3 s1), QLAT is the
lateral inflow per unit length along the channel (m2 s1), t is time
(s), xC is the longitudinal distance along the channel (m), vC is the
average flow velocity (m s1), hC is the water level (m), R is
the hydraulic radius (m),gis gravitational acceleration (m s2),zis
the bottom elevation of the channel section and n is Mannings
roughness coefficient. The numerical scheme adopted to approx-
imate the solution of these partial differential equations was theexplicit finite difference method representing a central difference
approximation for both temporal and spatial derivatives.
4.4.2. Channel network system
The channel network system of the study area was modeled on
the basis of the map of the drainage channel network obtained
from the local water management office (Fig. 6). The total of 59
drainage channels within the study watershed comprised 200 m
longitudinal distance sections (dx), resulting in 299 sections being
created. A 200 m section collects floodwater as lateral inflow from
approximately 10 standard-size (40 m 125 m) paddy field plots.The bed slope of each channel section was determined by the
difference between the altitude of the section and that of one
section upstream, where the altitude information was obtainedfrom longitudinal profile drawings for the main channels and
Global Positioning System (GPS) survey results for small but
important channels. The cross-sectional geometry, approximated
by two trapezoids with a main channel and floodplain for
simplicity, was obtained from cross-sectional profile drawings
and surveyed cross-sections.
The values of Mannings roughness coefficient (n) were
calculated as composite values determined depending upon the
ratio of the wetted perimeter of compound channels and the
roughness coefficient, adopted from the literature as 0.015 for
the concrete flume, 0.03 for the natural main channel, and 0.05 for
the vegetation-covered flood plain (Dingman, 2002).
The lateral inflow (QLAT) was calculated as the sum of the inflow
from paddy fields (QP), hilly areas and residential areas (QK). In
Fig. 6. Description of the modeled stream network.Each channel sectioncontains information on thecross-sectional geometry andaltitude.The lateral inflows to the channel
sections are identified using the map of the drainage channel network and field surveys. The values of lateral inflow are determined by the paddy field module and hilly/
residential area module.
N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270264
-
7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project
7/12
addition, the rainfall directly falling on the river and channel was
treated as direct lateral inflow and calculated as the product of the
rainfall intensity, the width and the longitudinal distance reaches
of each river and channel section.
4.4.3. Time steps
A time step was set to satisfy the following criterion to avoid
divergence of the numerical calculation:
DtDxC
vmax ffiffiffiffiffiffiffiffiffiffiffiffiffighmax
p ; (10)where vmax (m s
1) and hmax (m) are the assumed maximum flow
velocity and maximum stage, respectively. The maximum values
obtained by the field measurement were vmax 1:6 m s1 andhmax = 1.8 m, and thus Dt= 34.5 s given Dx = 200 m. Although 30 s
would be a sufficiently small time step to satisfy the criteriongiven
above, assuming a larger rainfall event, Dt was set at 10 s.
4.4.4. Inverted siphon
There are two inverted siphons crossing a drainage channel
within the project site (Fig. 6). The discharge volume in the section
of the inverted siphon was calculated by estimating the friction
loss using the DarcyWeisbach equation with Mannings friction
coefficient:
vS2gDhS
2n2Sg=R1=3S l=RS
( )1=2; (11)
where vS is the flow velocity (m s1) in the inverted siphon, DhS is
the head difference between the entrance and exit of the inverted
siphon (m), nS is Mannings roughness coefficient, RS is the
hydraulic radius (m), and l is the length of the inverted siphon (m).
4.4.5. Drainage pumps
There are three pumping stations in the pumping drainage area
outside the project site. The discharge volume of the actual
pumping stations is dependent on thewaterlevel of thechannel. In
the simulation, pump discharge volumes were determined
according to the channel water levels that reproduced the actual
pumping operations as listed in Table 1.
4.4.6. Boundary conditions
The downstream boundary condition was defined by the
oceanic tide stage recorded by the tide gauge at the mouth of the
Ishikawa River. The upstream boundary conditions were set at the
most upstream channel section of each channel and given by the
lateral inflow calculated as outcomes of the hilly/residential area
module. In addition, the water levels of the channel sectionsadjacent to the pumping stations and the inverted siphon were
treated as boundary conditions.
4.4.7. Inundation depth in the city center
The 99,000 m2 city center area is subject to frequent inundation
damage (Fig. 2). The overflow of the channel water begins when
the water level exceeds 2.0 m, the depth of the shallowest channel
in the city. In the model, the channel depth was tentatively set as
greater than 2.0 m to calculate the overflow depth. The overflow
water volume was simply calculated as the channel stage
exceeding 2.0 m multiplied by the width and the flow velocity
of the channel section calculated in the unsteady flow analysis:
QOFt HCCt 2:0Bv
CCt; (12)where QOF is the overflow water volume (m
3 s1), HCC is the
channel water level with an imaginary channel height (m), B is
the channel width (3.5 m), vCC is the flow velocity (m s1). The
inundation depth was determined by dividing the accumulated
overflow water volume by the city center area, assuming the city
center area is perfectly flat and overflow water spreads over the
area instantaneously:
INUNt X QOFtDt
ACC; (13)
where INUNis the inundation depth (m), Dtis the time interval of
the simulation (10 s), and ACC is the area subject to inundation
damage (99,000 m2).
Table 1
Programs of pump operations in the study watersheds.
Pump 1 Pump 2 Pump 3
Water level Discharge Water level Discharge Water level Discharge
Start H>1.00 m 1.80 m3 s1 Start H>0.85 m 0.67 m3 s1 Start H>1.70 m 2.18 m3 s1
Stop H1.80 m 15.29 m3 s1
Stop H1.90 m 3.87 m3 s1
Stop H
-
7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project
8/12
QOF can take a positive or negative value. As long as INUN is
greater than zero and QOF is negative, INUN decreases as flood
water flows downstream.
5. Results and discussion
5.1. Paddy field module
5.1.1. Percolation rate
As a result of the percolation measurement,the percolation rate
was found to be higher at the higher water level. The relationship
between the depth of the percolation loss (qPER) (m) and the water
level (H0) (m) can be expressed by
qPER 0:00154exp0:0164H0 (14)
5.1.2. Discharge coefficient of the orifice and rectangular weir
Fig. 7 shows the results of the surface runoff experiments.
Fig. 7(a) and (b) presents the ponded water depth changes with
time in the cases with and without the runoff control devices
where the regulating factors of the surface runoff are the orifices
and rectangular weirs, respectively. The best-fitting discharge
coefficient for the orifice was calculated as 0.88. Although this
value seems to be a little larger than the textbook value (in general,
C is approximately 0.6), the value includes leakage from the
inevitable slight gap between the runoff control device and the
floorof the drainage box. This gap is due tothe control device being
merely placed into the drainage box without the use of any
adhesives. The discharge coefficient of the rectangular weir, on the
other hand, was calculated as 1.90.
5.1.3. Runoff from a paddy field plot
The results of the runoff from a paddy field plot are shown in
Fig. 8. The runoff in the case of the ponding season was simulated
by merely applying the rectangular weir and orifice equations with
the identified coefficients (Fig. 8(a)).
For the analysis of the midsummer drainage season, the tank
modelparametersfor thesurface runoffhole (aT) andinitial surface
water depth (HI) were carefully adjusted by trial and error, and
Fig. 8. Calculated runoff per5000 m2 standard-size paddyfield plotwith andwithoutthe runoff control devicesresponding to the observed rainfallfor (a) thepondingseason
and (b) the midsummer drainage season.
Fig. 10. Calculated runoff per 5000 m2 standard-size paddy field with and without the runoff control devices responding to 10-year and 50-year return periods for (a) the
ponding season and (b) the midsummer drainage season.
Fig. 9. Comparison between the observed and calculated discharges from the 12
paddy fields without the runoff control devices.
N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270266
-
7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project
9/12
determined as 0.081 and 15.9 mm, respectively. The result thatthe initial surface water depth takes a negative value implies an
initial rainfall loss storedin the unsaturated zone of the paddy field
top soil and no contribution to the surface runoff. The calculated
discharge from the 12 paddy fields without the runoff control
devices had good accordance with the observed discharge as
shown in Fig. 9.
The surface runoff from a paddy field plot with the runoff
control devices was calculated. Here, the regulating factor is first
the surface runoff hole of the tank model at a low ponded water
level and then the orifice of the runoff control device as soon as the
water level reaches a certain depth (calculated as 35.5 mm) where
discharge from the tank model exceeds that from the orifice. The
calculated runoffs per 5000 m2 standard-size paddy field plot with
and without the runoff control devices during the midsummer
drainage season are shown in Fig. 8(b).
Fig. 10 shows the runoff from a paddy field plot in the case of
the ponding season (Fig. 10(a)) and midsummer drainage season
(Fig. 10(b)) when the design hyetographs of the 10-year and 50-
year return periods are applied. It is important to note the peak
runoff volumes with the runoff control devices being installed
(approximately 0.011 m3 s1) do not differ significantly regard-
less of the rainfall intensity or season. This is because (1) the
runoff control devices are installed on the bottom of the 400 mmdeep drainage boxes, and the change in the paddy field surface
water depth is small in comparison with the total water depth
(the depth of the drainage boxes plus the paddy field surface
water depth) that determines the runoff from the orifice and (2)
the runoff from the runoff control devices is proportional to the
1/2 power of the total water depth according to Eq. (1). On the
other hand, the runoff reacts sensitively when the runoff control
devices are not installed since the runoff depends directly on the
paddy field surface water level, being proportional to the 3/2
power of the paddy field surface water depth in the case of the
ponding season and the first power in the case of the midsummer
drainage season.
5.2. Hilly/residential area module
The peak discharge and time series discharge behavior of the
representative hilly subcatchment that was simulated by the
kinematic wave model had fairly good agreement with those of
the observed surface runoff (Fig. 11) applying the calibrated
equivalent roughness (0.62). Likewise, the runoff from residential
areas was simulated using the kinematic wave model. These
results added to the base discharge were used as the input of the
lateral inflow to the corresponding channel reach sections of the
channel network module.
5.3. Results of integrated runoff analysis by the channel network
module
5.3.1. Model validation
To validate the performance of the developed algorithms and
calculation procedures, the model was tested using the simulated
flood waterlevel anddischargefor therainfall event of the29th of
June 2007 under the actual installed runoff control devices of 80%.
The simulation results were compared with the observed
hydrograph where the water level sensors are located; that is,
Fig. 11. Comparison between the observed and calculated discharges fromthe hilly
subwatershed A.
Fig. 12. Results of the model validation. The observed and calculated water levels
and discharges are in good accordance. (a) Observed and calculated water levels at
observation site 1. The cable of the water level sensor was cut by the flood water
around 19:00. (b) Observed and calculated water levels at observation site 2. (c)
Observed and calculated discharges at observation site 2.
N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270 267
-
7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project
10/12
atobservationsite1 onthe Fuefuki Riverand observationsite2 on
the main drainage channel from the paddy field area (Fig. 12(a)
and (b)).
The simulated time series of the water level reproduce well the
observed fluctuation. Although there were only two discharge
measurements taken at observation site 2 (Fig. 12(c)) owing to
time constraints,thesevalues arein accordance with thesimulated
values. Since the time series water level and discharge are
simulated successively on the basis of the continuity and
momentum equations (Eqs. (8) and (9)), continuous observation
of the water level and two discharge measurements are sufficient
to validate the model, given that the boundary conditions and theparameters are correctly defined.
5.3.2. Evaluation of the flood mitigation function of the runoff
control devices
To evaluate the effect of the Paddy Field Dam project, a runoff
simulation using the constructed model was conducted without
(0%) and with (100%) runoff control devices. Since the difference in
the peak runoff from paddy fields between the ponding season and
midsummer drainage season is not significant, the evaluation is
made for the midsummer drainage season. The results for two
representative sites (observation site 1 and the city center
simulation site in Fig. 2) are presented and compared below.
Observation site 1 is located on theFuefuki River approximately
400 m upstream of the confluence with the Ishikawa River, andthere is no inflow between the confluence and this site. Therefore,
all flood water from the 528 ha Fuefuki River watershed collects at
this point. The cross-sectional geometry of the river is two
trapezoids with a 17 m width at the top and 3.3 m depth at the
center.
The city center simulation site is the channel section near the
outlet at the city center where the flood water most frequently
overflows the channel. Overflow occurs in this section because of
its small cross-sectional geometry, a rectangle of 3.5 m width and
2.0 m height. Since this section is a dugout channel without a bank
along the channel, as soon as the water level exceeds the height of
the channel, overflowing water spreads over the city center,
leading to inundation.
5.3.3. Channel stage, flow volume and inundation scale in
the case of observed rainfall
The simulation results for observation site 1 show that the
maximum water level and runoff volumereduced from 2.24 m and
16.06 m3 s1 with 0% installedrunoff control devices to 2.07 m and
11.84 m3 s1 with 100% installed runoff control devices applying
the observed rainfall pattern (Figs. 13(a) and (b)). The differences
between cases with and without the runoff control devices are
0.17 m in water level and 4.22 m3 s1 in runoff volume (Table 2).
With respect to the discharge volume, a peak runoff reduction of
more than one-quarter can be expected by installing the runoff
control devices to all paddy field plots.
At the city center simulation site, the maximum water levelwith 100% installed runoff control devices is calculated as 1.88 m
Fig. 13. Simulation results for the actual rainfall. (a) Water level at observation site 1. (b) Discharge at observation site 1. (c) Water level at the city center simulation site. (d)
Discharge at the city center simulation site.
Table 2
Comparison of the simulated maximum water level and discharge at observation site 1 and the city center simulation site.
Observation site 1 City center simulation site
Actual rainfall 50-year return period Actual rainfall 50-year return period
Without
devices
With
devices
Without
devices
With
devices
Without
devices
With
devices
Without
devices
With
devices
Max water level (m) 2.24 2.07 3.07 2.70 2.07 1.88 2.77 2.13
Difference (m) 0.171 0.364 0.190 0.637
Max discharge (m3 s1) 16.06 11.84 35.64 18.98 2.15 1.55 6.18 3.40
Difference (m3 s1) 4.22 16.66 0.60 2.78
Difference (%) 26.3% 46.7% 27.9% 45.0%
N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270268
-
7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project
11/12
(Fig. 13(c)). On the other hand, the maximum water level would
have exceeded the channel depth (2.0 m) in the case of no
installation according to the simulation.
The effect of the flood control measure on inundation is
summarized in Table 3. The maximum total inundation volume,
depth and inundation duration for the 0% installation case are
calculated as 205 m3, 0.002 m and 2.07 h (Table 3). Because of the
irregular topography of the ground surface and existence of
buildings in reality, the actual inundation depth in some areas
would have been greater than the simulated value.
Although inundation is not great, what is important is that the
installation of the runoff control devices could have preventedinundation. In fact, the water level did not reach the overflow level
on the day considered with the actual installed runoff control
devices of 80%. According to the officials of the local water
management office, who monitor the water level in this area,
overflow was usually observed with a similar pattern and scale of
rainfall event before the flood control measure was implemented.
5.3.4. Channel stage, flow volume and inundation depth in the case of
the design hyetographs
Applying the design rainfall of the 50-year return period, the
maximum water level at observation site 1 was simulated as being
reduced by 0.36 m from 3.07 to 2.70 m. Since the depth of the
channel is 3.30 m, there is only 23 cmextra bank height in the case
of no flood control measure. With regard to the discharge, the peakdischarge is expected to be reduced by as much as 16.7 m3 s1,
accounting for approximately 47% of the peak discharge without
the flood control measure (Table 2).
At the city center, the maximum total inundation volumes and
depths are 6539 m3 and 0.066 m with the installation of runoff
control devices and 18,223 m3 and 0.184 m without the installa-
tion. The inundation durations are 14.9 and 37.3 h, respectively
(Table 3). Since the maximum total inundation volume for the 10-
year return period rainfall event is simulated to be 6281 m3
without the installation of the devices, the runoff control devices
have the effect of reducing the flood damage due to the 50-year
return period rainfall event to almost that due to the 10-year
return period rainfall event.
6. Conclusion
This study quantifiedand evaluatedthe effectof the Paddy Field
Dam project, a flood control measure taking advantage of the
ponding function of paddy fields, at the watershed scale using
combined hydrologic analyses and flood routing. The simulation
results show that installing runoff control devices would reduce
the discharge of the river responsible for the drainage of the
watershed by 26% and lower the water level by 0.17 m in the case
ofan observed rainfall event,and by47% and 0.36 m in the case ofa
50-year return period design rainfall event. As a result, inundation
damage to the city center would be significantly mitigated. These
results confirmed that the flood control measure is functioning
effectively, as far as the study area is concerned.
The effect of the Paddy Field Damproject would, as a matter-of-
course, depend on the characteristics of the watershed under
study,such as topography, land useand drainage systems, of which
the fraction of paddy field area in a watershed is of the highest
importance. It is crucial, therefore, to select a suitable site for the
Paddy Field Dam project before its application. Further study will
be required fordeveloping a simpler methodto select suitable sites
for the prevalence of the flood control measure in the Paddy Field
Dam project.
Since large-scale investments such as constructing floodcontrol
dams aredifficult owing to budget constraints of national and local
governments, this project is presently attractive to policy makersnationwide as an inexpensive countermeasure to the recent
increase in the frequency and magnitude of heavy rainfall events.
Indeed, some local governments are now exploring the possibility
of introducing the Paddy Field Dam in their paddy field areas. The
project is applicable not only in Japan, but in many Asian monsoon
regions with regular flood damage and where paddy fields are the
primary means of producing food.
References
Abler, D., 2004. Multifunctionality, agricultural policy, and environmental policy.Agricultural and Resource Economics Review 33 (1), 817.
Chiba, K., Koga, K., Baba, H., 1997. Soil physical properties of uncultivated paddyfields located in semi-wet sloping land and the simulation of their response to
heavy rain. Transactions of the Japanese Society of Irrigation, Drainage andRural Engineering 65 (4), 6170 (in Japanese with English abstract).
Chow, V.T., Maidment, D.R., Mays, L.W., 1988. Applied Hydrology. McGraw-Hill,New York, p. 572.
Dingman, S.L., 2002. Physical Hydrology, 2nd ed. Prentice-Hall, Englewood Cliffs.Groenfeldt, D., 2006. Multifunctionality of agricultural water: looking beyond food
production and ecosystem services. Irrigation and Drainage 55, 7383.Hiramatsu, K., Shikasho, S., 2001. Flood mitigation function estimates of a flat low-
lying agricultural area along the lower reach of the Chikugo River. ScienceBulletin Faculty of Agriculture, Kyushu University 56 (1), 18 (in Japanese).
Huang, C.C., Tsai, M.H., Lin, W.T., Ho, Y.F., Tan, C.H., 2006. Multifunctionality ofpaddy fields in Taiwan. Paddy and Water Environment 4 (4), 199204.
Inoue, H., 1999. Fielddrainage. In: Advanced Paddy FieldEngineering.The JapaneseSocietyof Irrigation, Drainageand Reclamation Engineering, Shizan-sha Science& Technology Publishing Co., Ltd., Tokyo, pp. 323339.
IPCC (Intergovernmental Panel on Climate Change), 2007. Fourth assessmentreport, http://www.ipcc.ch/pdf/assessment-report/ar4/syr/ar4_syr.pdf.
Japanese Ministry of Construction, 1976. Construction Standards for River and SaboEngineering: Planning Aspects, River Bureau (ed.). Japan River Association,
Sankaido, Tokyo (in Japanese).Japan Meteorological Agency, 2005. Extreme weather report 2005, http://www.
data.kishou.go.jp/climate/cpdinfo/climate_change/2005/pdf/2005_all.pdf (inJapanese).
Kim, T.C., Gim, U.S., Kim, J.S., Kim, D.S., 2006. The multi-functionality of paddyfarming in Korea. Paddy and Water Environment 4 (4), 169179.
Masumoto, T., Yoshida, T., Kubota, T., 2006. An index for evaluating the flood-prevention function of paddies. Paddy and Water Environment 4 (4), 205210.
Masumoto, T.,Nozoe, M.,Yoshimura,A., Matsuda,S., 2003. A paddy runoffmodel inhilly rural areas for evaluating runoff change due to abandoned ricecultivation.Transactions of the Japanese Society of Irrigation, Drainage and Rural Engineer-ing 71 (2), 3544 (in Japanese with English abstract).
Masumoto, T., Takaki, K., Yoshida, S., Adachi, K., 1997. Effects of abandoned paddiesin hilly rural areas on runoff. Transactions of the Japanese Society of Irrigation,Drainage and Rural Engineering 65 (3), 5968 (in Japanese with Englishabstract).
Matsuno, Y., 2006. Prospects for multifunctionality of paddy rice cultivation inJapan and other countries i n monsoon Asia. Paddy and Water Environment 4
(4), 189197.
Table 3
Comparisons of the inundation durations, maximum volumes and depths with and without runoff control devices at the city center simulation site.
Actual rainfall 10-year return period 50-year return period
Without
devices
With
devices
Without
devices
With
devices
Without
devices
With
devices
Max volume (m3) 205 0 6281 501 18223 6539
Difference (m3) 205 5779 11684
Max depth (m) 0.002 0.000 0.063 0.005 0.184 0.066
Difference (m) 0.0021 0.0584 0.1180
Duration (h) 2.07 0.00 10.98 3.78 37.27 14.87Difference (h) 2.07 7.20 22.40
N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270 269
http://www.ipcc.ch/pdf/assessment-report/ar4/syr/ar4_syr.pdfhttp://www.data.kishou.go.jp/climate/cpdinfo/climate_change/2005/pdf/2005_all.pdfhttp://www.data.kishou.go.jp/climate/cpdinfo/climate_change/2005/pdf/2005_all.pdfhttp://www.data.kishou.go.jp/climate/cpdinfo/climate_change/2005/pdf/2005_all.pdfhttp://www.data.kishou.go.jp/climate/cpdinfo/climate_change/2005/pdf/2005_all.pdfhttp://www.ipcc.ch/pdf/assessment-report/ar4/syr/ar4_syr.pdf -
7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project
12/12
Nakamura, Y., Amezawa, E., Terada, Y., Sato, T., 1994. Drainage characteristics andrunoff relaxation by paddy fields in the Kokai River downstream basin. Journalof the Japanese Society of Irrigation Drainage and Reclamation Engineering 62(10), 712 (in Japanese).
Onishi, T.,Horino, H.,Mitsuno,T.,2004.A casestudyon storage property ofterracedpaddy fields. Transactions of the Japanese Society of Irrigation, Drainage andReclamation Engineering 72 (2), 5359 (in Japanese with English abstract).
Shimura, H., 1982. Evaluation on flood control functions of paddy fields and uplandcrop farms, Journal of the Society of Irrigation. Drainage and ReclamationEngineering 50 (1), 2529 (in Japanese).
Singh, V.P., 1996. Kinematic Wave Modeling in Water Resources, EnvironmentalHydrology. Wiley-Interscience.
Sugawara, M., 1972. River Discharge Analyses. Kyoritsu Press, Tokyo, pp. 1257 (inJapanese).
Vieux, B.E., Bralts, V.F., Segerlind, L.J., Wallace, R.B., 1990. Finite element watershedmodeling:one-dimensionalelements. Journal of Water Resources PlanningandManagement 116, 803819.
Wu, R.S.,Sue, W.R., Chien, C.B., Chen, C.H., Channg,J.S., Lin, K.M., 2001. A simulationmodel for investigating the effects of rice paddy fields on the runoff system.Mathematical and Computer Modelling 33 (67), 649658.
N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270270