Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project

download Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project

of 12

Transcript of Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project

  • 7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project

    1/12

    Evaluation of the flood mitigation effect of a Paddy Field Dam project

    N. Yoshikawa a,*, N. Nagao b, S. Misawa c

    a Research Center for Natural Hazard and Disaster Recovery, Niigata University, 8050 Ikarashi 2-no-cho, Nishi-ku, Niigata 950-2181, Japanb Toyama Prefectural Federation of Land Improvement Association, 17 Kurosaki, Toyama 939-8214, Japanc Faculty of Agriculture, Niigata University, 8050 Ikarashi 2-no-cho, Nishi-ku, Niigata 950-2181, Japan

    1. Introduction

    Recent climatic change has brought about a significant increase

    in the frequency of unusually heavy rain events in Asian monsoon

    regions. According to the Fourth Assessment Report of the

    Intergovernmental Panel on Climate Change (IPCC, 2007), it is

    very likely that heavy rainfall events will continue to become more

    frequent at middle and high latitudes. The Extreme Weather

    Report 2005 written by the Japan Meteorological Agency (2005)

    also reported on the basis of an analysis of the rainfall pattern for

    104 recent years that the numbers of days with intense

    precipitation exceeding 100 and 200 mm have increased 1.19

    and 1.46 times, respectively, when comparing the first 30 years of

    thelast century (19011930) with themost recent30 years (1975

    2004).

    There has been a recent increase in the risk of flood disaster in

    Japan owing not only to the changes in frequency and intensity of

    rainfall, but also to changes in land use and modernization of

    agriculture leading to the expansion of impervious areas and

    shortening of the arrival time of floods. Although investments have

    been made in infrastructure for protection against flood damage

    such as dam construction, bank heightening, river widening, and/

    or channel dredging, further investment in such large-scale

    structural measures is not realistic owing to increasing concern

    about the negative impact on the natural environment, in addition

    to the huge costs to the government.

    To overcome these problems, making use of paddy fields as a

    flood control system has been highlighted. The paddy fields

    themselves are considered to possess an innate flood mitigation

    function (Abler, 2004; Matsuno, 2006; Groenfeldt, 2006; Kimet al.,

    2006; Huang et al., 2006). Various studies at national and regional

    scales have been carried out to evaluate this flood control function.

    Shimura (1982), for the first time, estimated the flood water

    storage capacity of all paddy fields at 8.1 billion m3, which by far

    exceeds 2.4 billion m3, the total flood detention capacity of flood

    control dams in Japan. Regional cases have also been investigated

    taking into consideration topographical features; for example, the

    cases of terraced paddy fields in sloped areas (Onishi et al., 2004)

    and paddy fields in low-lying flat areas (Nakamura et al., 1994;

    Hiramatsu and Shikasho, 2001). Most of these regional case studies

    concluded that paddy fields play an important role in increasing

    the water storage capacity of river basins and lower the peak flows

    of rivers to a certain extent, but not to the same degree as Shimura

    (1982) estimated. Some studies found a significant rise in peak

    Agricultural Water Management 97 (2010) 259270

    A R T I C L E I N F O

    Article history:

    Received 21 January 2009

    Received in revised form 24 September 2009Accepted 26 September 2009

    Available online 25 October 2009

    Keywords:

    Paddy field

    Runoff control devices

    Flood control function

    Unsteady flow model

    Kinematic wave model

    Water balance analysis

    A B S T R A C T

    To mitigate flood damage due to a recent increase in the frequency and magnitude of heavy rainfall

    events, the Kamihayashi district in Niigata prefecture, Japan, has undertaken flood mitigation measures

    using paddy fields by installingrunoff control devices in drainage boxes of paddy field plots.The purpose

    of this study is to evaluate theflood mitigation performance of thePaddyField Dam project in terms of a

    decrease in discharge volume, drop in channel water level and reduction of inundation damage using

    combined hydrologic analyses and flood routing. The model constructed for runoff analysis is composed

    of three modules: a hilly/residential area module in which the overland flow is estimated using the

    kinematic wave method, a paddy field module in which runoff from paddy fields is calculated using

    water balance analysis, and a channel network module in which flood routing is performed using a one-

    dimensional unsteadyflow model.The outputs of thefirsttwo modules arethe input of thethirdmodule.

    The result of the simulation shows the main channel discharge decreased by 26% and the water level

    dropped by 0.17 m in the case of the largest observed rainfall event. The simulated effect was larger for

    larger rainfall events. In terms of flood water volume, the runoff control devices have the effect of

    reducing the flood damage due to the 50-year return period rainfall event to almost that due to the 10-

    year return period rainfall event.

    2009 Elsevier B.V. All rights reserved.

    * Corresponding author. Tel.: +81 25 262 6653; fax: +81 25 262 6653.

    E-mail address: [email protected](N. Yoshikawa).

    Contents lists available at ScienceDirect

    Agricultural Water Management

    j o u r n a l h o m e p a g e : w w w . e l s e v i e r . c o m / l o c a t e / a g w a t

    0378-3774/$ see front matter 2009 Elsevier B.V. All rights reserved.

    doi:10.1016/j.agwat.2009.09.017

    mailto:[email protected]://www.sciencedirect.com/science/journal/03783774http://dx.doi.org/10.1016/j.agwat.2009.09.017http://dx.doi.org/10.1016/j.agwat.2009.09.017http://www.sciencedirect.com/science/journal/03783774mailto:[email protected]
  • 7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project

    2/12

    runoff with the transformation of paddy fields to other land uses

    such as upland dry fields or the abandonment of cultivation (Chiba

    et al., 1997; Masumoto et al., 1997; Wu et al., 2001; Masumoto

    et al., 2003). To standardize the evaluation of the flood controlfunction, Masumoto et al. (2006) proposed a method and an index

    at a macro scale using the relationship between drainage and

    storage capacity.

    These studies have contributed to the understanding of the

    flood mitigating role of paddy fields and suggest that haphazard

    urbanization and abandonment of paddy cultivation may increase

    the negative impact on therunoff characteristic. However,it seems

    clear that mere conservation of the existing paddy fields will at

    most maintain the status quo.

    To address the recent increase in the flood risk, an unconven-

    tional measure for flood mitigation has been recently introduced

    using existing paddy fields with enhanced flood control function as

    an inexpensive and environmentally sustainable technique. This

    measure is termed the Paddy Field Dam, in which rain water isintentionally stored in the paddy fields temporarily at times of

    intense rainfall by installing runoff control devices in the drainage

    boxes of paddy field plots. Although paddy fields are not deep,

    usually surrounded by a levee 1530 cm high, the areal extentover

    which they spread is large and they therefore provide ample water

    storage potential.

    The purpose of this study is to evaluate the flood mitigation

    performance of the Paddy Field Dam, paddy fields with runoff

    control devices, using combined hydrologic analyses and flood

    routing. The effect is presented by the changes in flow volume and

    water level of thedrainagechannel andthe inundation volumeand

    duration at the city center.

    2. The Paddy Field Dam project

    2.1. Description of the Paddy Field Dam project

    The Paddy Field Dam is an experimental flood control measure

    launched in 2002 in Kamihayashi village, Niigata prefecture, Japan,

    takingadvantage of thepondingcharacteristics of paddyfields. The

    paddy fields within theproject site areinstalled with runoffcontrol

    devices in theform of orifice restriction platesto reinforcethe flood

    control function that they innately possess. The reason for the

    project being termed the Paddy Field Dam is that the paddy fields

    with the reinforced function store excessive rainwater and thus

    lowers the peak discharge just like ordinary flood control dams do,

    even though it does not fall into the definition of a dam, strictly

    speaking.

    The basic structure of the paddy fields in the study area is

    almost uniform in terms of shape and size as a result of the land

    consolidation and reallocation work in the 1980s: 5000 m2 plots

    equipped with two concrete drainage boxes, which are connectedto a drainage channel with a 150 mm inner diameter pipe. In

    general, the water level in the paddy fields is maintained at

    approximately 5 cm above the paddy field surface during the

    ponding season by placing a rectangular weir at the inlet of

    the drainage boxes just as for standard paddy fields in Japan. The

    excess water then flows into the drainage channel along the paddy

    field plots.

    The runoff control devices are structurally simple; 300 mm 300 mm wooden orifice restriction plates with 50 mm orifices are

    installed on the bottom of the drainage boxes, approximately

    40 cm below the paddy field surface. This shrinks the drain orifice

    of the boxes from the original pipe size of 15050 mm, reducing

    the orifice area to one-ninth that of the original pipe as illustrated

    in Fig. 1.One may worry about possible negative impacts on the rice

    production due to the retardation of drainage. However, there may

    be little damage to the rice crops unless they are completely

    submerged for several days since rice is one of the most tolerant

    crops against submergence (Inoue, 1999). Since the maximum

    ponding depth inside the paddy fields is the height of the levees,

    complete submergence occurs only when the water level of the

    drainage channel adjacent to the paddy fields increases above the

    height of the levees. It means that inundation would be

    unavoidable whether or notthe runoff control devices are installed

    because the effect of the Paddy Field Dam is rather to lower the

    water level of the drainage channel by controlling the runoff from

    paddy fields.

    Although temporary complete submergence may occur whenthe top of the rice plant is still below the top of the levees of the

    paddy fields, approximately 1 month after the transplantation in

    the beginning of May in Japan, rice plants would already have

    grown higher than the levees by the rainy season, which begins in

    the middle of June.

    2.2. Mechanism of surface runoff control for the Paddy Field Dam

    When the runoff control devices are not installed during the

    ponding season, the volume of surface water runoff from a paddy

    field plot is determined only by the height and length of the

    rectangular weir set at the inlet of a drainage box and the overflow

    depth above the rectangular weir, which in turn determines the

    ponding depth of the paddy field. On the other hand, in the case of

    Fig. 1. Paddy field drainage system. Two drainage boxes are installed and equipped with a runoff control device for each 0.5 ha standard-size paddy field plot.

    N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270260

  • 7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project

    3/12

    runoff control devices being installed, the runoff is regulated by

    either the rectangular weir or the orifice size of the runoff control

    devices depending upon the water depth of thepaddyfield. That is,

    the runoff control devices function only when the water inflow

    from the paddy field to the drainage box exceeds the outflow

    capacity of the orifice; otherwise, the surface runoff is regulated by

    theoverflowing runoff above the rectangular weir regardless of the

    existence of the devices. Therefore, the surface runoff QS (m3 s1)

    can be expressed by

    QS

    RectangularWeir Equation

    QW 2EbH03=2 2EbH D3=2 when QW QOOrifice Equation

    QO 2CaOffiffiffiffiffiffiffiffiffiffi

    2gh0

    q 2CaO

    ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi2gH d

    qwhen QW>QO

    8>>>>>:

    (1)

    where QWis the surface overflow runoffabovethe rectangular weir

    (m3 s1), Eis the weir coefficient, b is the weir length (m), H is the

    head above the top of the weir (m), H is the water depth of the

    paddy field (m), D is the height of the weir (m), QO is the discharge

    via the orifice (m3 s1), C is the orifice coefficient, aO is the area of

    the orifice (m2), gis the gravitational acceleration (m s2), h0 is thevertical distance between the water surface of the paddy field and

    the bottom of the drainage box (m), and d is the vertical distancebetween the paddy field surface and the bottom of the drainage

    box (m) (Fig. 1). The number 2 in both equations indicates that

    each standard-size paddy field is equipped with two drainage

    boxes.

    The regulating factors may differ during the season of

    midsummer drainage, a common practice of paddy cultivation

    in Japan in which paddy fields are dried out for about 10 days

    between the end of June and the beginning of July to control

    surplus tillering and supply plant roots with oxygen. In this period,

    the rectangular weirs are removed to release all the ponded water

    and several shallow furrows are excavated on the paddy field

    surface toward the drainage boxes to promote quick drainage of

    the remaining water. Since the soil dries up during this period, the

    surface runoff begins as soon as the soil surface is saturated whenheavy rainfall occurs. In this case, the factors determining the

    rainfallrunoff relations are more complex and need to be

    quantified without using the rectangular weir equation, although

    once the water inflow from the paddy field to the drainage box

    exceeds the outflow capacity of the orifice, the orifice size of the

    runoff control devices becomes the regulating factor. Because of

    the variations in the density and depth of the furrows made on the

    surfaces of paddy fields, the runoff characteristics may differ with

    respect to each paddy field plot. Therefore, the average rainfall

    runoff relations before the runoff control devices come into effect

    need to be derived somehow. In this study, a tank model

    (Sugawara, 1972) in which the runoff from the control devices

    is incorporated is adopted for this purpose.

    3. Materials and methods

    3.1. Study area

    The study was carried out in the Ishikawa River watershed,

    Kamihayashi village, Niigata prefecture, Japan. The Ishikawa River

    drains the entire 60.6 km2 watershed, which comprises hilly areas

    (69%), paddy fields (26%) and residential areas (5%) (Fig. 2). The

    Ishikawa River then flows into the Sea of Japan. The watershed can

    be divided into two areas by drainage systems: an area of

    gravitational drainage and an area of pumping drainage. The city

    center of Kamihayashi village is situated in the lower part of the

    watershed of the Fuefuki River (6.24 km2), one of the tributaries of

    the Ishikawa River, which largely coincides with the gravitational

    drainage area. Most of the remaining area coincides with the

    pumping drainage area. After flowing through the city center, the

    Fuefuki River joins the mainstream of the Ishikawa River. The city

    center area (approximately0.099 km2) has an altitude only slightly

    above sea level and is, therefore, subject to frequent flood water

    damage from the upstream water as well as from backwater

    caused by the rising of the Ishikawa River when intensive rainfall

    events occur.

    The project site comprising paddy fields (3.54 km2) and

    residential areas (0.88 km2) is located within the Fuefuki River

    watershed. Forthe purpose of this study,the inclusion of thewhole

    Ishikawa River watershed in the analysis was necessary because

    the water level and discharge of the Fuefuki River are significantly

    influenced by the water level of the Ishikawa River, which is in part

    determined by thetidalcondition of theSea of Japan.Therefore, the

    Fuefuki River watershed is treated as an inner drainage basin and

    the Ishikawa River watershed as an outer river basin because the

    analysis for the latter was performed only to determine the water

    level boundary condition of the Fuefuki River watershed.

    3.2. Field measurements

    The study period was 2 years between April 2006 and March

    2008. The channel water level was continuously measured andrecorded at 10 min intervals at six important sites in the study

    watershed using water level sensors (Hi-net,HTV-020KP) and data

    loggers (HIOKI, 3635-55). Precipitation was also measured with a

    tipping bucket rain gauge (Davis Instruments, Rain collector II) at

    10 min intervals. The channel flow velocity was intensively

    measured where the water level sensors were installed when

    heavy rainfall events occurred.

    3.3. Field experiment

    To investigate the surface runoff characteristics of the paddy

    fields with and without the runoff control devices, field experi-

    ments using standard-size paddy field plots were implemented.

    The paddy fields plots were intentionally ponded with irrigationwater as deep as possible by clogging the drainage outlets, and

    then the ponded water was released from the paddy field plots

    through the twodrainage boxes of each paddy field plot. The water

    level was continuously recorded with the water level sensors and

    data loggers.

    In general, the output components of the water budget of a

    paddy field plot include percolation and evapotranspiration

    besides the surface runoff. However, evapotranspiration is not

    taken into consideration in this study on the assumption that

    evapotranspiration is negligible during heavy rainfall events.

    Percolation was measured by filling the paddy field with water

    with the drainage outlets clogged and recording the fall in the

    water level at night. This experiment was implemented twice for

    different water levels: 120 and 50 mm.

    3.4. Observed rainfall event and design hyetographs

    The only heavy rainfall event during the study period occurred

    on the 29th of July 2007. Fig. 3 is the hyetograph of the observed

    rainfall event. The total rainfall depth was 101.8 mm, the return

    period of which is determined as being approximately equivalent

    to 3.7 years by fitting the Gumbel distribution to the available 85-

    year annual maximum rainfall data. Although the total depth does

    not seem to be outstandingly large, about 80% of the rainfall was

    concentrated within 8 h between 5.00 and 12.00 a.m.

    To evaluate the flood mitigation function of the runoff control

    devices forlarger rainfall events, the design storms for 10-year and

    50-year return periods were generated using the alternating block

    N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270 261

  • 7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project

    4/12

    method from intensitydurationfrequency (IDF) curves (Chowet al., 1988) (Fig. 4). The IDF curves for the study area were

    obtained from the Niigata prefectural government.

    4. Model development

    4.1. Watershed model and analytical framework

    Runoff analyses were conducted to quantify the effect of the

    runoff control devices in terms of the fall in water level and

    decrease in discharge of channels. The model constructed for the

    runoff analysis is composed of three modules: a paddy field

    module in which runoff from the paddy fields is calculated by

    water balance analyses, a hilly/residential area module in which

    the overland flow is estimated using the kinematic wave method,

    anda channel network module in which flood routing is performedusing a one-dimensional unsteady flow model. The outputs of the

    first two modules are the input of the third module.

    4.2. Paddy field module

    Using the coefficients of the rectangular weir and orifice of the

    runoff control devices determined through the field experiment,

    the runoff from a paddy field plot is simulated by

    I O dSdt

    ; (2)

    where I is the rainfall inflow to the paddy field, O is the outflow

    consisting of the runoff volumevia therectangularweirs or orifices

    Fig. 2. Description of the study area.

    N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270262

  • 7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project

    5/12

    and the percolation loss, Sis the ponded volume and tis time. The

    ponded volume can be approximated as

    S1 S2 DH 12R1 R2Dt

    1

    2

    QS1

    QS2AP

    12 qPER1 qPER2 Dt (3)where subscripts 1 and 2 denote the time steps of each variable at

    t= t1 and t= t2, R is the rainfall depth (m), QS is the surface runoff

    volume (m3 s1), qPER is the depth of the loss caused by percolation

    (m) and AP is the area of the paddy field plot (m2).

    In the case of the ponding season, the value of QS is calculated

    using either the rectangular weir equation or the orifice equation

    depending upon the ponded water depth whereas it is calculated

    using the tank model with the runoff through the runoff control

    devices as shown in Fig. 5 in the case of the midsummer drainage

    season.

    The constructed tank model reproduces the actual paddy field

    structure, where aTis therunoff coefficient, qSrepresents the depth

    of surface runoff from the study paddy field block (m), qPERrepresents the percolation depth (m), His the ponded water depth

    (m) and HI is the initial ponded water depth (m). To offset the

    individual specificity of the paddy fields, the model was applied to

    the study paddy field block comprising 12 standard-size paddy

    field plots, and the results are compared with the runoff observed

    at the channel outlet of the study block. The parameter aT was

    optimized using the least squares method to reproduce the

    observed runoff. qS is always proportional to the ponded water

    depth in the case without the runoff control devices. On the other

    hand, the regulating factors of qS shift in the case with runoff

    control devices depending upon the ponded water depth;that is, qSis regulated to be proportional to the ponded water depth when qT

    (the runoff calculated using the tank model) qO (the runoffcalculated using theorifice equation)and determined by theorifice

    of the runoff control devices when qT> qO. The value ofqPER is the

    percolation depth observed in the field measurement.

    4.3. Hilly/residential area module

    4.3.1. Basic concept of a kinematic wave model

    A kinematic wave model (Chow et al., 1988; Vieux et al., 1990;

    Singh, 1996) was used to simulate the flow in the hilly and

    residential areas. The kinematic wave equations can be written in

    the form of the continuity equation:

    @h

    @t @QK

    @x re (4)

    and momentum equation:

    QK ahm; (5)

    where QKis the runoff volume (m3 s1), h is the flow depth (m), tistime (s), x is the down slope position, and re is effective rainfall

    depth (m). a and m are the kinematic wave parameter and

    exponent, respectively. Given that Mannings principle is satisfied,

    a and m can respectively be written as

    a ffiffi

    Ip

    n; (6)

    m 53; (7)

    where I is the longitudinal bed slope and n is the equivalent

    roughness.

    Fig. 3. Observed rainfall on the 29th of June 2007.Fig. 5. Tankmodel reproducing the paddyfield block.qTand qO represent qScalculated

    by the tank model and by the orifice equation at an arbitrary ponded water depth,

    respectively. The regulating factors switch depending on the ponded water depth.

    Fig. 4. Design hyetographs for the 10-year (left) and 50-year (right) return periods generated using the alternating block method.

    N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270 263

  • 7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project

    6/12

    4.3.2. Subcatchments of the hilly area

    Since the hilly area comprises several subcatchments, the

    runoff from each subcatchment eventually flows into different

    channel sections as lateral inflow. To determine the destination of

    runoff, the hilly area was divided into subcatchments using a

    digital elevation model and a GIS (ESRI, ArcGIS 9.2).

    The average longitudinal bed slope (I) of each subcatchment

    was also calculated using the GIS. The equivalent roughness

    coefficient (n) was determined on the basis of calibration usingsubcatchment A (Fig. 2), where discharge was continuously

    measured and applied to all other subcatchments assuming the

    surface roughness is similar throughout the hilly area of the study

    watershed.

    4.3.3. Subcatchments of residential areas

    Residential areas including the city center were identified on

    the basis of a plan of the drainage channel network obtained from

    the local water management office. The average slope of each

    district was determined using the digital elevation model. The

    equivalent roughness coefficient was assumed to be 0.1, a common

    hydraulic recommendation for residential areas (Japanese Ministry

    of Construction, 1976) since no direct measurement for calibration

    was taken.

    4.4. Channel network module

    4.4.1. Basic concept of the unsteady flow model

    The basic governing equations of an unsteady open channel

    flow are the continuity equation:

    @aC@t

    @QC@xC

    QLAT (8)

    and momentum equation:

    1

    g

    @vC

    @t @hC@xC

    12g

    @v2C

    @xC @z@xC

    n2Q2C

    a2

    C

    R4=3 0; (9)

    where aC is the cross-sectional area of flow (m2), QC is the flow

    volume passing through the cross-section (m3 s1), QLAT is the

    lateral inflow per unit length along the channel (m2 s1), t is time

    (s), xC is the longitudinal distance along the channel (m), vC is the

    average flow velocity (m s1), hC is the water level (m), R is

    the hydraulic radius (m),gis gravitational acceleration (m s2),zis

    the bottom elevation of the channel section and n is Mannings

    roughness coefficient. The numerical scheme adopted to approx-

    imate the solution of these partial differential equations was theexplicit finite difference method representing a central difference

    approximation for both temporal and spatial derivatives.

    4.4.2. Channel network system

    The channel network system of the study area was modeled on

    the basis of the map of the drainage channel network obtained

    from the local water management office (Fig. 6). The total of 59

    drainage channels within the study watershed comprised 200 m

    longitudinal distance sections (dx), resulting in 299 sections being

    created. A 200 m section collects floodwater as lateral inflow from

    approximately 10 standard-size (40 m 125 m) paddy field plots.The bed slope of each channel section was determined by the

    difference between the altitude of the section and that of one

    section upstream, where the altitude information was obtainedfrom longitudinal profile drawings for the main channels and

    Global Positioning System (GPS) survey results for small but

    important channels. The cross-sectional geometry, approximated

    by two trapezoids with a main channel and floodplain for

    simplicity, was obtained from cross-sectional profile drawings

    and surveyed cross-sections.

    The values of Mannings roughness coefficient (n) were

    calculated as composite values determined depending upon the

    ratio of the wetted perimeter of compound channels and the

    roughness coefficient, adopted from the literature as 0.015 for

    the concrete flume, 0.03 for the natural main channel, and 0.05 for

    the vegetation-covered flood plain (Dingman, 2002).

    The lateral inflow (QLAT) was calculated as the sum of the inflow

    from paddy fields (QP), hilly areas and residential areas (QK). In

    Fig. 6. Description of the modeled stream network.Each channel sectioncontains information on thecross-sectional geometry andaltitude.The lateral inflows to the channel

    sections are identified using the map of the drainage channel network and field surveys. The values of lateral inflow are determined by the paddy field module and hilly/

    residential area module.

    N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270264

  • 7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project

    7/12

    addition, the rainfall directly falling on the river and channel was

    treated as direct lateral inflow and calculated as the product of the

    rainfall intensity, the width and the longitudinal distance reaches

    of each river and channel section.

    4.4.3. Time steps

    A time step was set to satisfy the following criterion to avoid

    divergence of the numerical calculation:

    DtDxC

    vmax ffiffiffiffiffiffiffiffiffiffiffiffiffighmax

    p ; (10)where vmax (m s

    1) and hmax (m) are the assumed maximum flow

    velocity and maximum stage, respectively. The maximum values

    obtained by the field measurement were vmax 1:6 m s1 andhmax = 1.8 m, and thus Dt= 34.5 s given Dx = 200 m. Although 30 s

    would be a sufficiently small time step to satisfy the criteriongiven

    above, assuming a larger rainfall event, Dt was set at 10 s.

    4.4.4. Inverted siphon

    There are two inverted siphons crossing a drainage channel

    within the project site (Fig. 6). The discharge volume in the section

    of the inverted siphon was calculated by estimating the friction

    loss using the DarcyWeisbach equation with Mannings friction

    coefficient:

    vS2gDhS

    2n2Sg=R1=3S l=RS

    ( )1=2; (11)

    where vS is the flow velocity (m s1) in the inverted siphon, DhS is

    the head difference between the entrance and exit of the inverted

    siphon (m), nS is Mannings roughness coefficient, RS is the

    hydraulic radius (m), and l is the length of the inverted siphon (m).

    4.4.5. Drainage pumps

    There are three pumping stations in the pumping drainage area

    outside the project site. The discharge volume of the actual

    pumping stations is dependent on thewaterlevel of thechannel. In

    the simulation, pump discharge volumes were determined

    according to the channel water levels that reproduced the actual

    pumping operations as listed in Table 1.

    4.4.6. Boundary conditions

    The downstream boundary condition was defined by the

    oceanic tide stage recorded by the tide gauge at the mouth of the

    Ishikawa River. The upstream boundary conditions were set at the

    most upstream channel section of each channel and given by the

    lateral inflow calculated as outcomes of the hilly/residential area

    module. In addition, the water levels of the channel sectionsadjacent to the pumping stations and the inverted siphon were

    treated as boundary conditions.

    4.4.7. Inundation depth in the city center

    The 99,000 m2 city center area is subject to frequent inundation

    damage (Fig. 2). The overflow of the channel water begins when

    the water level exceeds 2.0 m, the depth of the shallowest channel

    in the city. In the model, the channel depth was tentatively set as

    greater than 2.0 m to calculate the overflow depth. The overflow

    water volume was simply calculated as the channel stage

    exceeding 2.0 m multiplied by the width and the flow velocity

    of the channel section calculated in the unsteady flow analysis:

    QOFt HCCt 2:0Bv

    CCt; (12)where QOF is the overflow water volume (m

    3 s1), HCC is the

    channel water level with an imaginary channel height (m), B is

    the channel width (3.5 m), vCC is the flow velocity (m s1). The

    inundation depth was determined by dividing the accumulated

    overflow water volume by the city center area, assuming the city

    center area is perfectly flat and overflow water spreads over the

    area instantaneously:

    INUNt X QOFtDt

    ACC; (13)

    where INUNis the inundation depth (m), Dtis the time interval of

    the simulation (10 s), and ACC is the area subject to inundation

    damage (99,000 m2).

    Table 1

    Programs of pump operations in the study watersheds.

    Pump 1 Pump 2 Pump 3

    Water level Discharge Water level Discharge Water level Discharge

    Start H>1.00 m 1.80 m3 s1 Start H>0.85 m 0.67 m3 s1 Start H>1.70 m 2.18 m3 s1

    Stop H1.80 m 15.29 m3 s1

    Stop H1.90 m 3.87 m3 s1

    Stop H

  • 7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project

    8/12

    QOF can take a positive or negative value. As long as INUN is

    greater than zero and QOF is negative, INUN decreases as flood

    water flows downstream.

    5. Results and discussion

    5.1. Paddy field module

    5.1.1. Percolation rate

    As a result of the percolation measurement,the percolation rate

    was found to be higher at the higher water level. The relationship

    between the depth of the percolation loss (qPER) (m) and the water

    level (H0) (m) can be expressed by

    qPER 0:00154exp0:0164H0 (14)

    5.1.2. Discharge coefficient of the orifice and rectangular weir

    Fig. 7 shows the results of the surface runoff experiments.

    Fig. 7(a) and (b) presents the ponded water depth changes with

    time in the cases with and without the runoff control devices

    where the regulating factors of the surface runoff are the orifices

    and rectangular weirs, respectively. The best-fitting discharge

    coefficient for the orifice was calculated as 0.88. Although this

    value seems to be a little larger than the textbook value (in general,

    C is approximately 0.6), the value includes leakage from the

    inevitable slight gap between the runoff control device and the

    floorof the drainage box. This gap is due tothe control device being

    merely placed into the drainage box without the use of any

    adhesives. The discharge coefficient of the rectangular weir, on the

    other hand, was calculated as 1.90.

    5.1.3. Runoff from a paddy field plot

    The results of the runoff from a paddy field plot are shown in

    Fig. 8. The runoff in the case of the ponding season was simulated

    by merely applying the rectangular weir and orifice equations with

    the identified coefficients (Fig. 8(a)).

    For the analysis of the midsummer drainage season, the tank

    modelparametersfor thesurface runoffhole (aT) andinitial surface

    water depth (HI) were carefully adjusted by trial and error, and

    Fig. 8. Calculated runoff per5000 m2 standard-size paddyfield plotwith andwithoutthe runoff control devicesresponding to the observed rainfallfor (a) thepondingseason

    and (b) the midsummer drainage season.

    Fig. 10. Calculated runoff per 5000 m2 standard-size paddy field with and without the runoff control devices responding to 10-year and 50-year return periods for (a) the

    ponding season and (b) the midsummer drainage season.

    Fig. 9. Comparison between the observed and calculated discharges from the 12

    paddy fields without the runoff control devices.

    N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270266

  • 7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project

    9/12

    determined as 0.081 and 15.9 mm, respectively. The result thatthe initial surface water depth takes a negative value implies an

    initial rainfall loss storedin the unsaturated zone of the paddy field

    top soil and no contribution to the surface runoff. The calculated

    discharge from the 12 paddy fields without the runoff control

    devices had good accordance with the observed discharge as

    shown in Fig. 9.

    The surface runoff from a paddy field plot with the runoff

    control devices was calculated. Here, the regulating factor is first

    the surface runoff hole of the tank model at a low ponded water

    level and then the orifice of the runoff control device as soon as the

    water level reaches a certain depth (calculated as 35.5 mm) where

    discharge from the tank model exceeds that from the orifice. The

    calculated runoffs per 5000 m2 standard-size paddy field plot with

    and without the runoff control devices during the midsummer

    drainage season are shown in Fig. 8(b).

    Fig. 10 shows the runoff from a paddy field plot in the case of

    the ponding season (Fig. 10(a)) and midsummer drainage season

    (Fig. 10(b)) when the design hyetographs of the 10-year and 50-

    year return periods are applied. It is important to note the peak

    runoff volumes with the runoff control devices being installed

    (approximately 0.011 m3 s1) do not differ significantly regard-

    less of the rainfall intensity or season. This is because (1) the

    runoff control devices are installed on the bottom of the 400 mmdeep drainage boxes, and the change in the paddy field surface

    water depth is small in comparison with the total water depth

    (the depth of the drainage boxes plus the paddy field surface

    water depth) that determines the runoff from the orifice and (2)

    the runoff from the runoff control devices is proportional to the

    1/2 power of the total water depth according to Eq. (1). On the

    other hand, the runoff reacts sensitively when the runoff control

    devices are not installed since the runoff depends directly on the

    paddy field surface water level, being proportional to the 3/2

    power of the paddy field surface water depth in the case of the

    ponding season and the first power in the case of the midsummer

    drainage season.

    5.2. Hilly/residential area module

    The peak discharge and time series discharge behavior of the

    representative hilly subcatchment that was simulated by the

    kinematic wave model had fairly good agreement with those of

    the observed surface runoff (Fig. 11) applying the calibrated

    equivalent roughness (0.62). Likewise, the runoff from residential

    areas was simulated using the kinematic wave model. These

    results added to the base discharge were used as the input of the

    lateral inflow to the corresponding channel reach sections of the

    channel network module.

    5.3. Results of integrated runoff analysis by the channel network

    module

    5.3.1. Model validation

    To validate the performance of the developed algorithms and

    calculation procedures, the model was tested using the simulated

    flood waterlevel anddischargefor therainfall event of the29th of

    June 2007 under the actual installed runoff control devices of 80%.

    The simulation results were compared with the observed

    hydrograph where the water level sensors are located; that is,

    Fig. 11. Comparison between the observed and calculated discharges fromthe hilly

    subwatershed A.

    Fig. 12. Results of the model validation. The observed and calculated water levels

    and discharges are in good accordance. (a) Observed and calculated water levels at

    observation site 1. The cable of the water level sensor was cut by the flood water

    around 19:00. (b) Observed and calculated water levels at observation site 2. (c)

    Observed and calculated discharges at observation site 2.

    N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270 267

  • 7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project

    10/12

    atobservationsite1 onthe Fuefuki Riverand observationsite2 on

    the main drainage channel from the paddy field area (Fig. 12(a)

    and (b)).

    The simulated time series of the water level reproduce well the

    observed fluctuation. Although there were only two discharge

    measurements taken at observation site 2 (Fig. 12(c)) owing to

    time constraints,thesevalues arein accordance with thesimulated

    values. Since the time series water level and discharge are

    simulated successively on the basis of the continuity and

    momentum equations (Eqs. (8) and (9)), continuous observation

    of the water level and two discharge measurements are sufficient

    to validate the model, given that the boundary conditions and theparameters are correctly defined.

    5.3.2. Evaluation of the flood mitigation function of the runoff

    control devices

    To evaluate the effect of the Paddy Field Dam project, a runoff

    simulation using the constructed model was conducted without

    (0%) and with (100%) runoff control devices. Since the difference in

    the peak runoff from paddy fields between the ponding season and

    midsummer drainage season is not significant, the evaluation is

    made for the midsummer drainage season. The results for two

    representative sites (observation site 1 and the city center

    simulation site in Fig. 2) are presented and compared below.

    Observation site 1 is located on theFuefuki River approximately

    400 m upstream of the confluence with the Ishikawa River, andthere is no inflow between the confluence and this site. Therefore,

    all flood water from the 528 ha Fuefuki River watershed collects at

    this point. The cross-sectional geometry of the river is two

    trapezoids with a 17 m width at the top and 3.3 m depth at the

    center.

    The city center simulation site is the channel section near the

    outlet at the city center where the flood water most frequently

    overflows the channel. Overflow occurs in this section because of

    its small cross-sectional geometry, a rectangle of 3.5 m width and

    2.0 m height. Since this section is a dugout channel without a bank

    along the channel, as soon as the water level exceeds the height of

    the channel, overflowing water spreads over the city center,

    leading to inundation.

    5.3.3. Channel stage, flow volume and inundation scale in

    the case of observed rainfall

    The simulation results for observation site 1 show that the

    maximum water level and runoff volumereduced from 2.24 m and

    16.06 m3 s1 with 0% installedrunoff control devices to 2.07 m and

    11.84 m3 s1 with 100% installed runoff control devices applying

    the observed rainfall pattern (Figs. 13(a) and (b)). The differences

    between cases with and without the runoff control devices are

    0.17 m in water level and 4.22 m3 s1 in runoff volume (Table 2).

    With respect to the discharge volume, a peak runoff reduction of

    more than one-quarter can be expected by installing the runoff

    control devices to all paddy field plots.

    At the city center simulation site, the maximum water levelwith 100% installed runoff control devices is calculated as 1.88 m

    Fig. 13. Simulation results for the actual rainfall. (a) Water level at observation site 1. (b) Discharge at observation site 1. (c) Water level at the city center simulation site. (d)

    Discharge at the city center simulation site.

    Table 2

    Comparison of the simulated maximum water level and discharge at observation site 1 and the city center simulation site.

    Observation site 1 City center simulation site

    Actual rainfall 50-year return period Actual rainfall 50-year return period

    Without

    devices

    With

    devices

    Without

    devices

    With

    devices

    Without

    devices

    With

    devices

    Without

    devices

    With

    devices

    Max water level (m) 2.24 2.07 3.07 2.70 2.07 1.88 2.77 2.13

    Difference (m) 0.171 0.364 0.190 0.637

    Max discharge (m3 s1) 16.06 11.84 35.64 18.98 2.15 1.55 6.18 3.40

    Difference (m3 s1) 4.22 16.66 0.60 2.78

    Difference (%) 26.3% 46.7% 27.9% 45.0%

    N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270268

  • 7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project

    11/12

    (Fig. 13(c)). On the other hand, the maximum water level would

    have exceeded the channel depth (2.0 m) in the case of no

    installation according to the simulation.

    The effect of the flood control measure on inundation is

    summarized in Table 3. The maximum total inundation volume,

    depth and inundation duration for the 0% installation case are

    calculated as 205 m3, 0.002 m and 2.07 h (Table 3). Because of the

    irregular topography of the ground surface and existence of

    buildings in reality, the actual inundation depth in some areas

    would have been greater than the simulated value.

    Although inundation is not great, what is important is that the

    installation of the runoff control devices could have preventedinundation. In fact, the water level did not reach the overflow level

    on the day considered with the actual installed runoff control

    devices of 80%. According to the officials of the local water

    management office, who monitor the water level in this area,

    overflow was usually observed with a similar pattern and scale of

    rainfall event before the flood control measure was implemented.

    5.3.4. Channel stage, flow volume and inundation depth in the case of

    the design hyetographs

    Applying the design rainfall of the 50-year return period, the

    maximum water level at observation site 1 was simulated as being

    reduced by 0.36 m from 3.07 to 2.70 m. Since the depth of the

    channel is 3.30 m, there is only 23 cmextra bank height in the case

    of no flood control measure. With regard to the discharge, the peakdischarge is expected to be reduced by as much as 16.7 m3 s1,

    accounting for approximately 47% of the peak discharge without

    the flood control measure (Table 2).

    At the city center, the maximum total inundation volumes and

    depths are 6539 m3 and 0.066 m with the installation of runoff

    control devices and 18,223 m3 and 0.184 m without the installa-

    tion. The inundation durations are 14.9 and 37.3 h, respectively

    (Table 3). Since the maximum total inundation volume for the 10-

    year return period rainfall event is simulated to be 6281 m3

    without the installation of the devices, the runoff control devices

    have the effect of reducing the flood damage due to the 50-year

    return period rainfall event to almost that due to the 10-year

    return period rainfall event.

    6. Conclusion

    This study quantifiedand evaluatedthe effectof the Paddy Field

    Dam project, a flood control measure taking advantage of the

    ponding function of paddy fields, at the watershed scale using

    combined hydrologic analyses and flood routing. The simulation

    results show that installing runoff control devices would reduce

    the discharge of the river responsible for the drainage of the

    watershed by 26% and lower the water level by 0.17 m in the case

    ofan observed rainfall event,and by47% and 0.36 m in the case ofa

    50-year return period design rainfall event. As a result, inundation

    damage to the city center would be significantly mitigated. These

    results confirmed that the flood control measure is functioning

    effectively, as far as the study area is concerned.

    The effect of the Paddy Field Damproject would, as a matter-of-

    course, depend on the characteristics of the watershed under

    study,such as topography, land useand drainage systems, of which

    the fraction of paddy field area in a watershed is of the highest

    importance. It is crucial, therefore, to select a suitable site for the

    Paddy Field Dam project before its application. Further study will

    be required fordeveloping a simpler methodto select suitable sites

    for the prevalence of the flood control measure in the Paddy Field

    Dam project.

    Since large-scale investments such as constructing floodcontrol

    dams aredifficult owing to budget constraints of national and local

    governments, this project is presently attractive to policy makersnationwide as an inexpensive countermeasure to the recent

    increase in the frequency and magnitude of heavy rainfall events.

    Indeed, some local governments are now exploring the possibility

    of introducing the Paddy Field Dam in their paddy field areas. The

    project is applicable not only in Japan, but in many Asian monsoon

    regions with regular flood damage and where paddy fields are the

    primary means of producing food.

    References

    Abler, D., 2004. Multifunctionality, agricultural policy, and environmental policy.Agricultural and Resource Economics Review 33 (1), 817.

    Chiba, K., Koga, K., Baba, H., 1997. Soil physical properties of uncultivated paddyfields located in semi-wet sloping land and the simulation of their response to

    heavy rain. Transactions of the Japanese Society of Irrigation, Drainage andRural Engineering 65 (4), 6170 (in Japanese with English abstract).

    Chow, V.T., Maidment, D.R., Mays, L.W., 1988. Applied Hydrology. McGraw-Hill,New York, p. 572.

    Dingman, S.L., 2002. Physical Hydrology, 2nd ed. Prentice-Hall, Englewood Cliffs.Groenfeldt, D., 2006. Multifunctionality of agricultural water: looking beyond food

    production and ecosystem services. Irrigation and Drainage 55, 7383.Hiramatsu, K., Shikasho, S., 2001. Flood mitigation function estimates of a flat low-

    lying agricultural area along the lower reach of the Chikugo River. ScienceBulletin Faculty of Agriculture, Kyushu University 56 (1), 18 (in Japanese).

    Huang, C.C., Tsai, M.H., Lin, W.T., Ho, Y.F., Tan, C.H., 2006. Multifunctionality ofpaddy fields in Taiwan. Paddy and Water Environment 4 (4), 199204.

    Inoue, H., 1999. Fielddrainage. In: Advanced Paddy FieldEngineering.The JapaneseSocietyof Irrigation, Drainageand Reclamation Engineering, Shizan-sha Science& Technology Publishing Co., Ltd., Tokyo, pp. 323339.

    IPCC (Intergovernmental Panel on Climate Change), 2007. Fourth assessmentreport, http://www.ipcc.ch/pdf/assessment-report/ar4/syr/ar4_syr.pdf.

    Japanese Ministry of Construction, 1976. Construction Standards for River and SaboEngineering: Planning Aspects, River Bureau (ed.). Japan River Association,

    Sankaido, Tokyo (in Japanese).Japan Meteorological Agency, 2005. Extreme weather report 2005, http://www.

    data.kishou.go.jp/climate/cpdinfo/climate_change/2005/pdf/2005_all.pdf (inJapanese).

    Kim, T.C., Gim, U.S., Kim, J.S., Kim, D.S., 2006. The multi-functionality of paddyfarming in Korea. Paddy and Water Environment 4 (4), 169179.

    Masumoto, T., Yoshida, T., Kubota, T., 2006. An index for evaluating the flood-prevention function of paddies. Paddy and Water Environment 4 (4), 205210.

    Masumoto, T.,Nozoe, M.,Yoshimura,A., Matsuda,S., 2003. A paddy runoffmodel inhilly rural areas for evaluating runoff change due to abandoned ricecultivation.Transactions of the Japanese Society of Irrigation, Drainage and Rural Engineer-ing 71 (2), 3544 (in Japanese with English abstract).

    Masumoto, T., Takaki, K., Yoshida, S., Adachi, K., 1997. Effects of abandoned paddiesin hilly rural areas on runoff. Transactions of the Japanese Society of Irrigation,Drainage and Rural Engineering 65 (3), 5968 (in Japanese with Englishabstract).

    Matsuno, Y., 2006. Prospects for multifunctionality of paddy rice cultivation inJapan and other countries i n monsoon Asia. Paddy and Water Environment 4

    (4), 189197.

    Table 3

    Comparisons of the inundation durations, maximum volumes and depths with and without runoff control devices at the city center simulation site.

    Actual rainfall 10-year return period 50-year return period

    Without

    devices

    With

    devices

    Without

    devices

    With

    devices

    Without

    devices

    With

    devices

    Max volume (m3) 205 0 6281 501 18223 6539

    Difference (m3) 205 5779 11684

    Max depth (m) 0.002 0.000 0.063 0.005 0.184 0.066

    Difference (m) 0.0021 0.0584 0.1180

    Duration (h) 2.07 0.00 10.98 3.78 37.27 14.87Difference (h) 2.07 7.20 22.40

    N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270 269

    http://www.ipcc.ch/pdf/assessment-report/ar4/syr/ar4_syr.pdfhttp://www.data.kishou.go.jp/climate/cpdinfo/climate_change/2005/pdf/2005_all.pdfhttp://www.data.kishou.go.jp/climate/cpdinfo/climate_change/2005/pdf/2005_all.pdfhttp://www.data.kishou.go.jp/climate/cpdinfo/climate_change/2005/pdf/2005_all.pdfhttp://www.data.kishou.go.jp/climate/cpdinfo/climate_change/2005/pdf/2005_all.pdfhttp://www.ipcc.ch/pdf/assessment-report/ar4/syr/ar4_syr.pdf
  • 7/29/2019 Evaluation of the Flood Mitigation Effect of a Paddy Field Dam Project

    12/12

    Nakamura, Y., Amezawa, E., Terada, Y., Sato, T., 1994. Drainage characteristics andrunoff relaxation by paddy fields in the Kokai River downstream basin. Journalof the Japanese Society of Irrigation Drainage and Reclamation Engineering 62(10), 712 (in Japanese).

    Onishi, T.,Horino, H.,Mitsuno,T.,2004.A casestudyon storage property ofterracedpaddy fields. Transactions of the Japanese Society of Irrigation, Drainage andReclamation Engineering 72 (2), 5359 (in Japanese with English abstract).

    Shimura, H., 1982. Evaluation on flood control functions of paddy fields and uplandcrop farms, Journal of the Society of Irrigation. Drainage and ReclamationEngineering 50 (1), 2529 (in Japanese).

    Singh, V.P., 1996. Kinematic Wave Modeling in Water Resources, EnvironmentalHydrology. Wiley-Interscience.

    Sugawara, M., 1972. River Discharge Analyses. Kyoritsu Press, Tokyo, pp. 1257 (inJapanese).

    Vieux, B.E., Bralts, V.F., Segerlind, L.J., Wallace, R.B., 1990. Finite element watershedmodeling:one-dimensionalelements. Journal of Water Resources PlanningandManagement 116, 803819.

    Wu, R.S.,Sue, W.R., Chien, C.B., Chen, C.H., Channg,J.S., Lin, K.M., 2001. A simulationmodel for investigating the effects of rice paddy fields on the runoff system.Mathematical and Computer Modelling 33 (67), 649658.

    N. Yoshikawa et al. / Agricultural Water Management 97 (2010) 259270270