ESSER Operation
-
Upload
nikko-christian-perez -
Category
Documents
-
view
485 -
download
47
description
Transcript of ESSER Operation
-
ESSER Fire Alarm System
-
Honeywell Proprietary 2 Document control number
History of Esser
1973 Establishment of Electronic Fire Alarm Systems in Hamburg 1975 Acquisition by Klaus Esser GmbH in Neuss 1985 Integration of Intruder Alarm 1993 Acquisition by Caradon plc, 2001 renamed in Novar 2005 Acquisition by Honeywell
-
Honeywell Proprietary 3 Document control number
Leading Technology
High Speed processor. ESSER IQ8QUAD. De-Centralized Intelligence. Built-in isolator. Powered Loop Devices 3.5Km Loop length 10,000 events log 3 level networking Dual Battery circuit in Panels 127 Devices per loop
essernet
Main Panel(MP)
Sub Panel(SP)
Sub Panel(SP)
Example switch off
Control (AE)Main detector (MFAB)Test operation
Switch-offessernet Panel
(ENP)
Operation
-
Honeywell Proprietary 4 Document control number
esserbus PLus
esserbus PLus (LOOP)
Monitor Control
-
Honeywell Proprietary 5 Document control number
Features
Short circuit Isolator integrated in every detector Automatic addresses Additional operation indicator LED Aesthetically pleasing CPU failure mode Temperature range of 20deg to 70deg C. EMI tested for 50 V/M
IQ8Quad Detector
-
Honeywell Proprietary 6 Document control number
Series IQ8Quad detectors Smoke Detector
Heat Detector black ring
LASER barcode label
LED green Indicating operation
-
Honeywell Proprietary 7 Document control number
Alarming Normal Operation
IQ8Quad Operation
-
Honeywell Proprietary 8 Document control number
The Small MCP
MCP (without 2nd micro switch) with isolator only Small and stylish design Approval acc. to EN 54 Part 11 Fix to existing flush-mounting box possible Additional green LED for normal operation of bus
detector Exchangeable label on housing Pictogram instead of wording Three key-functions
Reset Test Alarm Open housing
IP 43, IP55 with surface mounting box and protective cover
IQ8MCP
-
Honeywell Proprietary 9 Document control number
Esserbus Transponder
The Esserbus transponder works as a loop device on the multifunctional loop. It can monitor and control 3rd Party devices.
up to 31 Esserbus transponders 4 zones / 2 relays and/or 12 relay on one multifunctional primary loop
max. 100 transponders per fire alarm control panel
max. 127 detector zones per analog loop
-
Honeywell Proprietary 10 Document control number
Esserbus Transponder
The IQ8TAL is equipped with an integrated loop isolator, a contact input and a relay output. The relay can be optionally configured as a normally-closed contact or as a normally-open contact. The IQ8TAL does not need a separate voltage supply.
-
Honeywell Proprietary 11 Document control number
IQ8 Alarm Sounder
Completely bus supplied alarm device
Powered loop compatible
Up to 32 alarm devices for each powered loop
Each alarm device with built-in isolator
Acoustic pressure up to 99 dB(A) @ 1 m
Volume programmable in 8 steps via tools 8000 20 different signaling tones
-
Honeywell Proprietary 12 Document control number
Venturi Air Duct Detector
Easy maintenance Air stream visible OT Blue inside Inlet and drain of air in one tube
-
Honeywell Proprietary 16 Document control number
General view of the display and operating elements
Single zone indicator unit (GEA) Common display FIRE
Common display PRE-ALARM Common display TROUBLE
Common display disconnection Alphanumeric display Key switch Operating elements Function keys and keyboard
Opening for Programming connector
-
Honeywell Proprietary 17 Document control number
Configuration example IQ8Control M
Con
nect
or 1
Con
nect
or 2
Basic module IQ8Control
Extension module with 3 micro module slots
esse
rnet
m
odul
e
Analog loop module 1
Extension module with 3 micro module slots
Analog loop module 2
Analog loop module 3
Analog loop module 4
Analog loop module 5
Analog loop module 6
-
Honeywell Proprietary 18 Document control number
Operation
The common display >Fire< is activated if at least one fire alarm has been detected. The originating detector or detector zone will be shown on the alphanumeric display
Fire Condition
Acknowledgement of the control panel buzzer. This key remains active when the keyboard is locked. The buzzer is reactivated in the case of a further event.
All detected fire alarms, detector zones, displays and technical alarm signals are cancelled and returned to normal condition.
-
Honeywell Proprietary 19 Document control number
Operation..cont. Trouble Condition
The common display Trouble is activated if at least one malfunction has been detected. The reason will be shown on the alphanumeric display.
A component of the fire alarm control panel or a monitored relay output such as an external
alarm device has malfunctioned.
The power supply (battery or mains voltage) is connected. The fire alarm control panel is in an
operative condition.
The fire alarm control panel is only partially operative due to a malfunction of the control panel
functions. Display or operation of the control panel is no longer
possible
The power supply (battery or mains voltage) is out of order.
-
Honeywell Proprietary 20 Document control number
Operation..cont.
Disconnect a detector
Switch ON/ reset a detector
-
Honeywell Proprietary 21 Document control number
Transponder
-
Honeywell Proprietary 22 Document control number
Trouble codes
-
Honeywell Proprietary 23 Document control number
Trouble codes..Cont
-
Honeywell Proprietary 24 Document control number
Trouble codes..Cont
-
Honeywell Proprietary 25 Document control number
Esser by Honeywell
Thank you for your Time & Attention
Slide Number 1Slide Number 2Leading Technologyesserbus PLusSlide Number 5Series IQ8Quad detectorsSlide Number 7Slide Number 8Slide Number 9Slide Number 10Slide Number 11Venturi Air Duct DetectorGeneral view of the display and operating elements Configuration example IQ8Control MOperationOperation..cont.Operation..cont.TransponderTrouble codesTrouble codes..ContTrouble codes..ContEsser by Honeywell