EPB1 Cable inner data

download EPB1 Cable inner data

of 3

description

EP81 Cable inner data

Transcript of EPB1 Cable inner data

  • PRODUCT SPECIFICATION

    EPB18581

    DEP 2011-12-09 Page 1/3

    Power Distribution Cable for Signalling Systems Enhanced unarmoured cables Rodent Protected

    Construction and testing according standards

    NetworkRail NR/L2/ELP/27408

    BS EN 60228 BS 7655-1.3 and BS 7655-6.1

    IEC IEC 60502-1

    Rated Voltage

    0,6/1kV

    Outer sheath colour

    BLACK

    Conductor Identification

    Brown, Black

    Marking on the outer sheath

    On the outer sheath by embossing on two primary

    lines with the following information (example) : Legend 1 (line 1):

    CABELTE ELECTRIC CABLE 600/1000 V

    NR/L2/ELP/27408 LS0H 2x50 Al YEAR H NMR

    Railway Catalogue number Property of Network Rail M.M.

    Legend 2 (line 2):

    CABELTE ELECTRIC CABLE 600/1000 V

    NR/L2/ELP/27408 LS0H 2x50 Al YEAR H NMR

    Railway Catalogue number Property of Network Rail

    Year - Year of manufacture

    M.M. - Metric Marking (shall be printed)

    Line 1 and line 2 are spaced ~180.

    The distance between the end of one element of marking

    and the beginning of the next identical element of marking

    is 550mm.

    SAC/XLPE/FGT/LS0H

    Circular conductors schematic design

    Shaped conductors schematic design

    1 Conductor Solid Aluminium Conductors (SAC), circular

    ( 35mm2) or shaped (> 35mm2), class 1, according to BS EN 60228.

    2 Insulation XLPE type GP 8 according to BS 7655-1.3.

    The two insulated conductors are stranded.

    3 Identification tape Polypropylene tape with a printed legend:

    Property of Network Rail CABELTE YEAR, applied over the stranded cores.

    Thickness = 50m | Minimum width = 5mm.

    4 Bedding (only in circular conductors design) LS0H compound.

    5 Rodent protection Fibreglass tape, helically applied with a minimum

    overlap of 15%. Weaving design: plain weave 1/1

    (272 tex). Nominal thickness of tape = 0,65mm.

    6 Outer sheath LS0H type LTS4 according to BS 7655-6.1.

    5

    3

    2

    1

    6

    4

    3

    2

    1

    5

    6

  • PRODUCT SPECIFICATION

    EPB18581

    DEP 2011-12-09 Page 2/3

    Technical Characteristics

    Cable designation SAC/XLPE/FGT/LS0H SAC/XLPE/FGT/LS0H SAC/XLPE/FGT/LS0H SAC/XLPE/FGT/LS0H SAC/XLPE/FGT/LS0H SAC/XLPE/FGT/LS0H SAC/XLPE/FGT/LS0H

    Voltage U0/U (kV) 0,6/1 0,6/1 0,6/1 0,6/1 0,6/1 0,6/1 0,6/1

    N of cores x conductor size (mm2) 2x16 2x25 2x35 2x50 2x70 2x95 2x120

    Conductor class and material Al Class 1 Al Class 1 Al Class 1 Al Class 1 Al Class 1 Al Class 1 Al Class 1

    Max. cond. dc resist. at 20C (/km) 1,91 1,20 0,868 0,641 0,443 0,320 0,253

    Nominal core to core capacitance (F/km) 0,125 0,141 0,153 0,184 0,217 0,243 0,271

    Nominal core to earth capacitance (F/km) 0,130 0,150 0,165 0,179 0,205 0,228 0,247

    Zero sequence impedance (/km) (1) 2,50+j2,29 1,59+j2,26 1,16+j2,24 0,87+j2,22 0,62+j2,19 0,46+j2,16 0,37+j2,14

    Positive sequence impedance (/km) (1) 2,45+j0,100 1,54+j0,0936 1,11+j0,0898 0,82+j0,0864 0,57+j0,0820 0,41+j0,0792 0,32+j0,0770

    Negative sequence impedance (/km) (1) 2,45+j0,100 1,54+j0,0936 1,11+j0,0898 0,82+j0,0864 0,57+j0,0820 0,41+j0,0792 0,32+j0,0770

    Inductance (mH/km) 0,319 0,298 0,286 0,275 0,261 0,252 0,245

    Reactance (/km) 0,100 0,0936 0,0898 0,0864 0,0820 0,0792 0,0770

    Impedance (cos = 0,8) (/km) 1,96 1,23 0,890 0,660 0,457 0,332 0,264

    Insulation material XLPE GP8 XLPE GP8 XLPE GP8 XLPE GP8 XLPE GP8 XLPE GP8 XLPE GP8

    Insulation nom. thickness (mm) 2,0 2,0 2,0 2,0 2,0 2,0 2,0

    Core identification colours BR-BK BR-BK BR-BK BR-BK BR-BK BR-BK BR-BK

    Sheath material LS0H LTS4 LS0H LTS4 LS0H LTS4 LS0H LTS4 LS0H LTS4 LS0H LTS4 LS0H LTS4

    Sheath min. average thickness (mm) 2,4 2,4 2,6 2,7 2,9 3,0 3,2

    Rodent protection FGT FGT FGT FGT FGT FGT FGT

    Internal identifying tape Yes Yes Yes Yes Yes Yes Yes

    Approximate overall diameter (mm) 25 27 29 27 29 32 34

    Bend Radius (mm) 200 216 232 216 232 256 272

    Weight of cable (kg/km) 660 810 970 810 1010 1220 1450

    Maximum drum length (m) (2) 4000 3000 3000 3000 2000 1500 1500

    Maximum pulling force per cond. (daN) 48 75 105 150 210 285 360

    BR - Brown

    BK - Black FGT- Fibre Glass Tape

    (1) Should be take only as approx. value. It is assumed that cable is installed in the ground (earth resistivity 100.m). (2) These values may suffer slight changes.

  • PRODUCT SPECIFICATION

    EPB18581

    DEP 2011-12-09 Page 3/3

    Technical Characteristics (cont.)

    Cable designation SAC/XLPE/FGT/PVC SAC/XLPE/FGT/PVC

    Voltage U0/U (kV) 0,6/1 0,6/1

    N of cores x conductor size (mm2) 2x150 2x185

    Conductor class and material Al Class 1 Al Class 1

    Max. cond. dc resist. at 20C (/km) 0,206 0,164

    Nominal core to core capacitance (F/km) 0,307 0,321

    Nominal core to earth capacitance (F/km) 0,269 0,284

    Zero sequence impedance (/km) (1) 0,32+j2,12 0,26+j2,11

    Positive sequence impedance (/km) (1) 0,27+j0,0751 0,21+j0,0738

    Negative sequence impedance (/km) (1) 0,27+j0,0751 0,21+j0,0738

    Inductance (mH/km) 0,239 0,235

    Reactance (/km) 0,0751 0,0738

    Impedance (cos = 0,8) (/km) 0,217 0,175

    Insulation material XLPE GP8 XLPE GP8

    Insulation nom. thickness (mm) 2,0 2,0

    Core identification colours BR-BK BR-BK

    Sheath material LS0H LTS4 LS0H LTS4

    Sheath min. average thickness (mm) 3,4 3,6

    Rodent protection FGT FGT

    Internal identifying tape Yes Yes

    Approximate overall diameter (mm) 36 39

    Bend Radius (mm) 288 312

    Weight of cable (kg/km) 1680 1950

    Maximum drum length (m) (2) 1400 1200

    Maximum pulling force per cond. (daN) 450 555

    BR - Brown

    BK - Black FGT- Fibre Glass Tape

    (1) Should be take only as approx. value. It is assumed that cable is installed in the ground (earth resistivity 100.m). (2) These values may suffer slight changes.