Session E4: Energy Audi1ng Energy Audits In Ac1on Lonnie Russell, CEM

description

I recently gave this presentation at the World Energy Engineering Congress In Washington DC (Oct13) and it was well received. It shows a "big picture" approach and gives plenty of real world examples.

Transcript of Energy audits in action

Page 1: Energy audits in action

Session  E4:  Energy  Audi1ng  

Energy  Audits  In  Ac1on  Lonnie  Russell,  CEM  

Page 2: Energy audits in action
Page 3: Energy audits in action

   Energy  Audits  in  Ac/on    by    EnergyMan  LLC  

Page 4: Energy audits in action

Plan  of  A8ack  

The goal is to try to make the biggest impact possible with little or no

investment. Start with the largest

electrical loads and gas users.

Includes HVAC and hot water

50%

30%

20%

Building  Energy  Usage:  Non  Industrial Environmental  Control Ligh1ng Other

Page 5: Energy audits in action

Important Question: Why is this operating with no one here? Must do some of audit during non-occupied times

These items were found on 24/7 during non-occupied times. Programmable thermostat in override and set to

68F in the summer

Boiler

10 Air handlers with a combined horsepower of 68.5

Page 6: Energy audits in action

This  is  equipment  in  the  cabana;  only  used  

seasonally,  but  it  was  all  on;  3  refrigerators  were  empty  and  on,  stove  had  it’s  pilot  light  on  and  hot  water  heater  was    not  turned  off.  

Page 7: Energy audits in action

The  auditorium  is  a  very  large  space  to  leave  the  HVAC  system  running  when  the  room  is  not  in  use  

Page 8: Energy audits in action

Computer  monitors  leS  on  

Page 9: Energy audits in action

The  current  IT  PC  policy  is  not  helping  with  PC  power  consump/on,  as  can  be  observed  by  the  

hundreds  of  PC’s  that  are  leS  on  24/7.  

At  an  absolute  minimum,  the  monitors  should  be  set  to  to  go  to  standby.  Leaving  these  all  on  puts  a  heavy  load  on  the  HVAC  

system,  which  may  not  have  been  originally  designed  for  this  large  a  load.  

Page 10: Energy audits in action

8 cents / kWh 11 cents / kWh1 kW $611 $96410 kW $7,008 $9,63625 kW $17,520 $24,09050 kW $35,040 $48,1801 Hp $680 $93410 Hp $6,796 $9,34425 Hp $16,989 $23,36050 Hp $33,978 $46,720

Cost per YearMotor Size

Ini/al  motor  cost  is  only  about  5%  of  the  total  lifecycle  cost,  so  always  buy  an  efficient  motor!  

Page 11: Energy audits in action

Chiller and associated equipment

Cooling  Towers  

Why  does  equipment  not  get  turned  off?:  •     Lack  of  control  of  building  during  off  hours,  especially  in  buildings  with  mul/ple  users  •       System  was  set  up  that  way  from  the  beginning  and  no  one  on  site  knows  how  to  correct  it.  •       It  has  always  been  that  way  so  no  one  no/ces.  •       We  tried  that  once  but….  •       You  can’t  turn  that  off.  It  may  not  turn  back  on  (my  personal  favorite).  

This is not limited to smaller

facilities. Here are some sizable loads at a large

facility.

Chiller  Primary  and  Secondary  pumps  

Cooling  Tower  Pumps  

Page 12: Energy audits in action

Now  that  the  schedule  is  op/mized  how  do  we  make  our  HVAC  system  more  efficient?  •     Tighten  up  the  building  and  ductwork  •  Control  the  outside  air  (preferably  with  demand  controlled      

ven1la1on)  and  Economize,  if  possible  •         Install  VFD’s  where  possible  •         Ligh1ng    •         Energy  efficiency  products  •         Minimize,  or  eliminate  reheat  •   Op1mize  the  set  points  (room  temp,  chill  water,  hot  water,  non-­‐

occupied,  occupied  etc…)  •       ASHRAE  states  that  80%  of  all  occupants  will  be  comfortable  at  temperatures  of  68F  to  74F  in  the  winter  and  73F-­‐78F  in  the  summer  at  no  >  60%  RH.  

Page 13: Energy audits in action

SCGSAH  1st  year  Results  (opera/onal  changes  only!)  Electricity Usage

100,000150,000200,000250,000300,000350,000

Dec Jan Feb Mar Apr May Jun Jul

Time

KW

H

20082009

Natural Gas Usage

1,000

6,000

11,000

16,000

Dec Jan Feb Mar Apr May Jun Jul

Time

Ther

ms

20082009

YTD Electricity Cost

0

50000

100000

150000

2008 2009

Time

Dol

lars

YTD

YTD Natural Gas Cost

0

50000

100000

150000

2008 2009

Time

Dolla

rs

YTD

Reduc/on  of  60.4%  

Reduc/on  of  51.7%  

Reduc/on  of  28.6%  

Reduc/on  of  18.4%  

Page 14: Energy audits in action

Building  Envelope  Improvement  This  building  had  many  major  air  leaks  that  needed  to  be  addressed.  Major  leaks  included:  

• Exhaust  fans  with  no  dampers  so  they  would  be  wide  open  when  not  running  

• Overhead  doors  with  no  seals  • Bathroom  exhaust  fans  that  never  shut  off  

• Large  gaps  around  fan  shrouds  

• Large  louvers  that  were  open  to  the  outside  

BackdraS  Damper  Installa/ons  Open  Exhaust  Duct  

Page 15: Energy audits in action

Air infiltration repair (Overhead doors)

Before   Before  (sunlight  leaking  in)   ASer  

Curtain  for  frequently  used  door  

Brush  seal  

Brush  Seal  

Page 16: Energy audits in action

Missing    InsulationFaulty    Duct  Insulation

Open Roof Access

Building Envelope and Leaky ductwork examples

OA damper stuck open

Ductwork insulation in bad shape

No floor insulation in crawl space

Page 17: Energy audits in action

Negative Pressure from Bathroom Exhaust Fans Bathroom  Exhaust  fans  were  on  24/7.  When  HVAC  equipment  was  shut  down,  these  fans  

exhausted  2000  cfm  and  pulled  air  in  from  outside  causing  humidity  to  rise  at  night.  

Fan  switches  were  hidden  and  always  leS  on  

Sensors  were  installed  to  automate  the  bathroom  exhaust  fans  so  they  would  run  for  15  minutes  when  the  bathroom  became  

unoccupied  and  then  shut  off.  

Page 18: Energy audits in action

Outside  air  control  opportuni/es  Some  places,  such  as  churches  and  auditoriums,  have  high  outside  air  requirements  

because  of  the  per  person  ASRAE  ven/la/on  requirements.  This  is  partly  to  prevent  the  “sick  building  syndrome”  issues  that  occurred  when  buildings  did  not  ven/late  

adequately  in  the  past.  

Sanctuary  Outside  Air  Intake

Using  CO2  monitoring,  and  controlling  the  outside  air  intake  based  on  that,  allows  for  proper  outside  air  intake.  Otherwise,  you  could  be  bringing  in  the  outside  air  requirement  for  

hundreds  of  people  no  ma8er  how  small  the  occupancy  is.  This  technique  is  called  “demand  controlled  ven/la/on”.  The  price  to  do  this  type  of  control  has  dropped  substan/ally  in  the  last  few  years,  with  CO2  sensors  now  barely  over  $100.00  and  damper  controllers  for  about  

the  same.  

Page 19: Energy audits in action

Demand  Controlled  Ven/la/on  

AHUs were initially set at 10% - 15% OA damper open at all times. Especially in the hot humid summers of South Carolina, this can unnecessarily load the

system. CO2 sensors were installed and set to open the OA dampers if CO2 levels rise to levels > 1000 ppm.

Outside Air Dampers

Page 20: Energy audits in action

Economizer  possible  for  2309  to  3961  hours.  High  bays  maybe  an  addi/onal  1000  hours.  

Make  outside  air  your  friend!    Economize  (frequently  called  free  cooling)  for  your  winter  heat  loads.  Able  to  shut  down  all  but  the  air  moving  parts  of  the  HVAC  

systems  (chillers,  pumps,  compressors  etc…).  

Page 21: Energy audits in action

Outside  air  damper  can  only  be  open  or  closed:  cannot  be  modulated.  

Installed  Modulator  

Return  air  had  no  damper,  therefore  

ra/o  of  return  versus  outside  air  cannot  be  

controlled.  

Installed  Modula/ng  Damper  

Equipment  Modifica/ons/Requirements  to  Economize  

Page 22: Energy audits in action

HVAC  systems  are  generally  built  for  the  10  hoYest  and  10  coolest  days  of  the  year.  There  is  generally  overcapacity  for  all  other  condi[ons.  VFD’s  offer  the  ability  to  match  the  system  to  

the  load,  offering  tremendous  energy  savings  and  extending  equipment  life.    

A 50% reduction in flow actually reduces horsepower requirements by 87.5%

Advantages  of  a  Variable  Frequency  Drives  (VFD’s)  

Page 23: Energy audits in action

Pumping  power  is  wasted  (valves  are  par/ally  closed)  making  the  pumps  good  VFD  (variable  frequency  drive)  candidates.  The  pumps  (2)  also  run  con/nuously.  

Page 24: Energy audits in action

Variable  Frequency  Drive  HVAC  Applica/ons  

40  Hp  high  bay  air  handler.     30  Hp  high  bay  air  handler.    Cooling  Tower  Pump  VFD:  Since  the  small  chiller  only  needs  900  gpm  and  the  

exis/ng  pump  supplies  2000  gpm,  a  VFD  was  far  more  efficient  than  a  thro8le  

valve  (see  previous  slide).  

AHU’s:  Original  owner  of  Bldg.  needed  100%  OA  for  the  manufacturing  space.  New  owner  did  not  need  that  so  VFDs  were  used  to  thro8le  these  drives  down  significantly.  This  also  allowed  for  dehumidifica/on  control  (by  moving  the  air  very  slow  and  lowering  the  chill  water  temperature)  and  reduced  load  on  the  chiller  and  boiler.  

Page 25: Energy audits in action

Filter

Reheat  Reduc/on  using  variable  airflow    

Fan Reheat

Coil Cooling

Coil

RA damper

OA damper

Fast Airflow

Air Temp

Fan Reheat

Coil Cooling

Coil

RA damper

OA damper

Slow Airflow

Air Temp

Air Temp

Filter

Original Line-up (simplified with no exhaust): Air moved at max CFM across the cooling coil that had 42F chilled water going through it. This dropped the temperature. This colder air was then passed across a reheat coil that had 180F water going through it. This brought the air to a normal discharge temperature of 55F – 65F.

65F

New De-humidification line-up (simplified with no exhaust): Air moved at min CFM across the cooling coil that had 42F - 47F chilled water going through it. This drops the temperature significantly, condensing more water therefore reducing humidity. The need for reheat is reduced or eliminated. The reduced airflow helps keep the space from getting too cold, but a little reheat may be required if that occurs. As you can see the low discharge air temperature means the supply air duct definitely has to be insulated.

50F

Air Temp

Page 26: Energy audits in action

Elimina/ng  reheat  required  the  high  bay  ductwork  to  be  insulated  because  the  discharge  air  temp  would  drop  and  swea/ng  could  occur.  This  was  an  

$18,000  investment  with  a  payback  of  about  1  month!  

Page 27: Energy audits in action

Natural  gas  consump/on  has  been  the  largest  success  of  our  energy  management  efforts.  Overall  Results:  

•   Dekatherms  reduced  by  87.8%  

•   Cost  reduced    $239,728  for  a  cost  reduc/on  of    89.2%  

Natural Gas Consumption

0

500

1000

1500

2000

2500

1 2 3 4 5 6 7 8 9 10 11 12

Month

Deka

ther

ms

200620072008

228  CDD  

231  CDD  

320CDD  

Though  Nov08  was  very  cold,  with  a  28%  increase  in  CDD,  gas  usage  only  increased  12.8%  

Natural  Gas  Consump/on  Results  

Page 28: Energy audits in action

•  Electronic  Timers  should  be  installed  on  electric  water  heaters.  •  Many  facili/es  have  water  heaters  that  are  grossly  oversized  •  NG  should  be  used  if  available  (Far  less  expensive  to  heat  with  than  electric  resistance)    •  Tankless  NG  systems  are  ideal  for  low  or  variable  occupancy  applica/ons    •  Heat  Pump  water  heaters  are  good  for  hot  kitchens  

Domes/c  Hot  Water  

Page 29: Energy audits in action

When  water  heaters  are  turned  off,  their  associated  recircula/on  pumps  need  to  be  turned  off  also.  If  not,  they  will  cause  the  piping  system  to  act  as  a  large  

radiator,  removing  heat  from  the  hot  water  tank,  causing  the  water  heater  to  use  more  energy  on  start-­‐up  (to  reach  set  point).  This  energy  loss  is  in  addi/on  to  the  

energy  use  to  operate  the  pump  

HW  recircula/on  pumps  

Page 30: Energy audits in action

•  Install  Vending  Miser  on  soda  machines:    h8p://www.usatech.com/energy_management/energy_vm.php  

•  Shuts  down  the  compressor  and  lights  when  people  are  not  in  the  area  

•  Can  have  a  payback  of  less  than  one  year  •  Simple  to  install  requiring  li8le  technical  skills  •  Some/mes  soda  vendor  will  supply  for  free  •  Soda  s/ll  stays  cold  

Vending  Misers  

Page 31: Energy audits in action

Many  opportuni/es  for  vending  and  cooler  misers    

Page 32: Energy audits in action

“\`  Many  drink  coolers  have  very  bad  seal  

leaks  

A  vendor  supplies  these  coolers  to  this  golf  resort,  but  the  resort  s/ll  has  to  pay  the  u/lity  bill!    These  are  basically  opera/ng  with  the  door  leS  open.  

Page 33: Energy audits in action

Use  of  a  programmable  receptacle  can  reduce  water  

fountain    power  use  by  30%  

Refrigerated  Water  Fountains  

Page 34: Energy audits in action

The  hood  should  overhang  6”  over  the  cooking    equipment.  Either  the  equipment  needs  pushed  back  a  li8le  more  or  extensions  need  

installed  on  the  hood.  

Page 35: Energy audits in action

Dishwasher  sani/zing  heaters,  such  as  these  two  36  kW  models,  can  consume  up  to  30%  of  a  restaurants  total  power  use.  Should  consider  

a  NG  unit  or  a  chemical  dishwasher  

Page 36: Energy audits in action

Dishwasher  exhaust  is  on    when  dishwasher  is  not  opera/ng.  Best  fix  is  

an  interlock  

Page 37: Energy audits in action

Idle  /me  needs  to  be  reduced  whenever  possible  

Pilot  lights  should  be    shut  off  whenever  

possible  

Page 38: Energy audits in action

Pilot  lights  are  leS  on  con/nuously  

Assume  1,250  BTUs  for  commercial  pilot.  This  is  a  two-­‐fold  savings:  natural  gas  or  propane  to  fuel  the  pilot  and  the  electricity  saved  by  not  having  to  remove  the  heat  with  the  HVAC  system.  A  4  burner  stove  (they  are  usually  larger)  would  require  10  tons  of  

cooling  to  remove  the  heat  from  the  pilots!  

Page 39: Energy audits in action

Example  of  a  plas/c  

curtain  that  would  work  well  in  the  walk-­‐in  

coolers  and  freezers  

No  curtains    

Walk-­‐Ins    

Page 40: Energy audits in action

Ligh/ng  Opportuni/es  

Most  painless  energy  project!  Replace  

incandescent  exit  signs  with  LED  signs.  About  a  6  month  payback  and  no  

complaints!  

Too  much  aisle  light  

Incandescent  Auditorium  Lights  

500  T12  lights  on  at  0100  in  the  morning  in  a  large  library  

Page 41: Energy audits in action

Many  /mes  hallways  are  over-­‐illuminated.  Rarely  should  a  4  bulb  fixture  be  used  in  a  hallway.  The  Illumina/ng  Engineering  Society  of  

North  America  (IESNA)  maintains  that  10-­‐20  fc  is  adequate  for  hallways  and  aisles.  These  were  50  fc  or  higher.  

Page 42: Energy audits in action

This  is  an  inexpensive  way  to  secure  ligh/ng  that  does  not  have  switches.  This  example  is  for  high  bay  ligh/ng  (uses  much  more  energy  than  office  ligh/ng).  The  breakers  we  labeled  and  security  was  trained  to  turn  them  off  when  they  are  not  needed.  This  reduced  the  off-­‐shiS  load  by  35  –  50  KW  with  no  capital  required,  just  labeling  and  a  procedure.  The  lifespan  of  the  breakers  was  inves/gated  and  it  was  found  

that  they  should  last  over  11  years  if  they  are  cycled  twice  a  day.  

Reduced  Ligh/ng  Plan  on  the  cheap  

Page 43: Energy audits in action

Ligh/ng  Upgrades  

This  hi  bay  was  converted  from  250w  HPS  to  T8  fluorescent.  32  fixtures  were  replaced  with  16  4’s  and  16  6’s.  This  reduced  wa8age  by  3,242  wa8s  and  HVAC  by  1902  tons.  This  project  was  done  in  conjunc/on  with  installing  switches  that  allowed  for  all  but  6  lights  to  be  off  when  the  space  was  not  in  use.  This  allowed  for  a  1.4  yr  payback  and  allowed  for  a  much  be8er  work  environment.  The  5000K  ligh/ng  made  reading  prints  and  assembly  work  much  easier  than  the  yellowish  HPS.    It  helps  to  sell  a  ligh/ng  retrofit  if  switches  can  be  added  in.  Also,  do  not  forget  to  calculate  the  HVAC  savings,  which  can  be  substan/al.  New  ligh/ng  can  be  “brighter”  but  the  foot  candle  readings  may  be  

lower;  be  more  concerned  about  the  recep/on  of  the  ligh/ng.  

Page 44: Energy audits in action

!"#$%&%' (#%%#)* +,%#-./(0+1234 156 152 789:;:+1232 8 5; 1912:+734 42 11: 1196<6466.=#%%.>? 1; 4;4 1:9:;:+,%#- 1169526

!"#$%&%' (#%%#)* +,%#-./(0 @*A#%*.B*C.D&E%"C* F*%.G,H%.I#J0+732 156 8; 289646 K::L52 K4L67+732 8 8; ;88 K16L66 K27L66+732 42 8; 89864 K14L1; K2:L74+73; 1; 221 ;9:85 K;6L76 K1;4L26

/(0 M,--#CH+732 ;;9:87 K<9;:1 K1951;+73; <9664 K5:5 K29;2<+,%#- <:9:;2 K796<6 K49844

G,NA&$*O.P#'A#J/.Q&$.'*#CHR

S$&%&#-.S$T*H%N*$%

U#T&$)H

6L8;

IE&H%&$)..V&E%"C*HWB*C#%&$).G,H%

K169244K1:8K19217

K19<51K1:9:7<

P#'A#J/.Q'*#CHR

6L282L76

PC,B,H*O.$*=.D&E%"C*H

This  spreadsheet  is  a  very  handy  tool  in  obtaining  buy-­‐in  for  ligh/ng  projects.  Be  sure  to  research  any  available  rebates:  they  can  be  very  lucra/ve.  

Page 45: Energy audits in action

These  2  graphs  (water  and  sewer)  track  together  very  closely,  but  they  should  not.    Sewage  should  only  be  charged  for  water  that  goes  down  the  drain,  not  water  for  irriga/on  or,  in  this  case,  water  that  is  being  evaporated  in  a  cooling  tower.  For  the  small  price  of  installing  an  irriga/on  meter  ($340.00)  the  sewer  bill  will  drop  

at  least  50%.  

U/lity  Bill  Analysis  Findings  

Page 46: Energy audits in action

Water  and  Sewer  The  sewer  bill  at  this  facility  is  based  on  water  consump/on.  At  one  /me,  when  the  previous  owner  had  the  plant,  the  water  used  for  the  cooling  tower  and  the  irriga/on  system  was  

deducted  from  the  total  (since  this  water  never  went  to  sewage).  The  meters  below  were  read  by  the  County  Water  and  Sanita/on  Department  monthly  so  the  values  could  be  deducted  

from  the  usage  amount  reported  by  the  City  Water  System.  

These  had  not  been  read  since  the  new  owner  had  purchased  the  building.  You  can  see  this  by  looking  at  the  huge  increases  occurring  during  the  summer  months,  when  the  irriga/on  and  cooling  tower  load  were  at  their  max.  When  the  Sewer  Department  was  contacted,  they  did  not  want  to  do  the  readings  again  and  

offered  to  compromise  with  a  flat  rate.  This  resulted  in  an  annual  savings  of  over  $20,000.00.  

Page 47: Energy audits in action

This  school  district’s  newer  elementary  school  was  using  more  than  40%  more  energy  than  the  state  average,  and  far  more  than  older  schools  in  the  same  district.  Met  with  the  Energy  Management  System  contractor  and  spent  the  day  watching  

this  system  operate  in  detail.  

Page 48: Energy audits in action

60    Hp  Boiler  (2)  250  Ton  Chiller   50  Ton  Chiller  

•  Chillers  were  operated  by  a  flow  calcula/on  that  did  a  very  poor  job.  The  small  chiller  never  ran  at  all.    

•  No  low  OA  lock-­‐out  for  chiller  and  high  OA  lock-­‐out  for  boiler.  Large  chiller  came  on  when  it  was  47F  outside  

•  Only  one  call  for  heat  would  turn  on  the  whole  hea/ng  system  •  Set-­‐points  need  to  be  variable  •  Simultaneous  hea/ng  and  cooling  needs  to  be  eliminated  or              greatly  reduced  

Page 49: Energy audits in action

30  Hp  CHW  Pumps  

10  Hp  HW  Pumps  

CHW  Pump  Control  Pkg.  

 CHW  Pump  VSDs  (different  speeds?)  

Pumps  had  their  own  control  package:  they  were  not  controlled  by  the  EMS.  Pumps  would  not  shut  down  and  ran  at  different  speeds  at  the  same  /me.  

Page 50: Energy audits in action

Air  Handler   Blower  Coil  Units  

•  Though  EMS  showed  units  to  be  scheduled  off,  many  were  s/ll  opera/ng  due  to  hardware  communica/on  issues.  

•  OA  should  be  minimized;  why  run  dedicated  systems  when  the  building  is  unoccupied  

•  Thermostat  set  points  were  way  too  loose.  Need  to  use                ASHRAE  standard  

Page 51: Energy audits in action

EMS  (or  BAS)  U/liza/on  Many  /mes  an  EMS  is  used  for  nothing  more  than  a  fancy  /me-­‐  clock.  This  is  a  missed  opportunity  and  waste  of  money.  Control  strategies  can  reduce  energy  use  significantly.  Examples:  •  Op/mum  Start/Stop  •  SA/DA  reset  •  Sta/c  reset  •  HW  reset  •  CHW  reset  •  Demand  Controlled  Ven/la/on  •  OA  lockouts  •  Humidity  control  strategies  •  Advanced  scheduling  •  Variable  override  /mers  

Page 52: Energy audits in action

The  heat  from  the  walk  in  refrigerator  and  freezer  condensers  ejects  right  into  the  HVAC  condensers.    

Poor  Installa/on  

Page 53: Energy audits in action

Condensers  are  much  to  close  to  each  other  and  to  the  walls.  There  is  very  li8le  room  for  them  to  dissipate  heat  effec/vely.  

Page 54: Energy audits in action

This  valve  was  opened  a  few  years  ago  to  compensate  for  a  “water  hammer”  issue  that  occurred  by  accident.  Power  readings  taken  on  the  pump  with  this  valve  open  and  closed  showed  an  increase  from  66KW  to  82KW.  The  pump  consumed  16  more  KW  with  this  valve  

open.  Shuung  this  valve  saved  $7,140.00  a  yr.  

Improper  Valve  posi/on  Example  

Page 55: Energy audits in action

Single  Point  Bulle/ns  A  good  tool  to  drive  energy  awareness  

Page 56: Energy audits in action

Man-­‐fan  example  This  man-­‐fan  was  running  24/7  though  the  area  was  only  occupied  about  90  hours  a  week.  This  equates  to  just  over  $300.00  a  year.  Remember  man-­‐fans  do  not  lower  the  room  temperature,  they  are  only  helpful  if  you  are  there  to  feel  their  benefit.  How  many  of  these  have  you  seen  running  in  a  non-­‐occupied  space?  Many  man-­‐fans  at  this  facility  use  more  power  than  this  one.  

Page 57: Energy audits in action

Compressed  Air  Leak  examples  Let’s  assume  these  leaks  add  up  to  a  1/8”  leak  (probably  very  conserva/ve).  A  con/nuous    1/8”  leak  costs  and  unbelievable  $7,000.00  a  year.  This  is  totally  

preventable.  Maintenance  usually  repairs  these  within  one  day  if  they  are  no/fied.  The  next  /me  you  hear  the  hissing  sound,  remember  it  sounds  like  money!  

Page 58: Energy audits in action

Ligh/ng  example  If  the  ligh/ng  override  is  used,  it  should  be  turned  off  when  no  longer  needed  and  not  allowed  to  /me  out.  Some  of  these  /mers  are  2  hours  and  some  of  these  zones  can  cost  up  to  $15.00  for  just  one  hour  of  opera/on.    Knowing  your  zone  helps  

prevent  the  waste  associated  with  turning  every  zone  on,  just  to  make  sure  you  get  the  right  one  (this  does  happen).    

Page 59: Energy audits in action

Exhaust  fan  example  This  exhaust  fan  can  cost  over  $50.00  a  month  to  operate,  not  to  men/on  the  cost  of  

the  condi/oned  air  that  is  being  pumped  outside  the  building.  This  fan  was  not  turned  off  when  produc/on  ended.  

Page 60: Energy audits in action

Space  Heaters  

•       They  are  a  fire  hazard  •       They  consume  very  large  amounts  of  energy  •  They  affect  other  employees  comfort  by  causing  the  HVAC  system  to      work  

harder  in  the  summer  (making  it  colder  for  those  without  the  heaters)  and  less  in  the  winter  (having  a  thermostat  meet  temperature  when  the  whole  room  may  not  be  warm).  

Personal  fans,  on  the  other  hand,  do  not  change  building  temperature,    just  airflow,  and  do  not  use  much  electricity.  

!"#$%&'%#(%)*&*'+,-.&/%0%)&1%&#--+2%.&3+)&('%&3+--+24/5&)%#*+/*6&&78   9'%:&#)%&#&;)%&'#<#).&=8   9'%:&$+/*,>%&-#)5%&#>+,/(*&+3&%/%)5:&?8   9'%:&#@%$(&+('%)&%>"-+:%%*&$+>3+)(&1:&$#,*4/5&('%&ABCD&*:*(%>&(+&2+)E&'#).%)&4/&('%&

*,>>%)&F>#E4/5&4(&$+-.%)&3+)&('+*%&24('+,(&('%&'%#(%)*G&#/.&-%**&4/&('%&24/(%)&F'#04/5&#&('%)>+*(#(&>%%(&(%>"%)#(,)%&2'%/&('%&2'+-%&)++>&>#:&/+(&1%&2#)>G8&

&H%)*+/#-&3#/*I&+/&('%&+('%)&'#/.I&.+&/+(&$'#/5%&1,4-.4/5&(%>"%)#(,)%I&J,*(&#4)K+2I&#/.&.+&/+(&,*%&>,$'&%-%$()4$4(:8&

9'4*&2#*&3+,/.&4/&#/&+L$%&

!"#$%&'%#(%)*&#)%&-+$#(%.&(')+,5'+,(&('%&3#$4-4M%*&

Page 61: Energy audits in action

To  sell  an  energy  project,  think  like  a  life  insurance  salesman,  only  backwards!  

When  selling  a  policy  for  $275.00  a  year  it  is  presented  as  cos/ng  only  $.75  a  day.  When  working  with  energy  and  jus/fying  a  project,  think  the  opposite  (annually)!        This  is  especially  easy  when  looking  at  loads  that  run  24/7,  such  as  an  exit  sign.  

40  wa8s  –  4  wa8s  =  36  wa8s  *  8760  hrs  (hours  in  a  year)  =  315360/1000  (wa8s  in  a  kilowa8)  =  315.4  kWH  *  $.11  (price  per  kilowa8  hour)  =  $34.69  a  yr  in  savings  

Doesn’t  that  sound  be8er  than  saving  9.50  cents  a  day?  

Page 62: Energy audits in action