Electronic Leak Detection: Sound Science, Not a Magic Wand · to “wave the magic wands” and...

5
D ue to its many advantages over food testing, mem- brane integrity testing with electronic leak detection (ELD) has rapidly become the frst choice for owners, manufacturers, specifers, consultants, and contractors around the world. ELD on roof- ing and waterproofng membranes is prov- ing to be faster, safer, more accurate, and often less expensive than food testing. However, as with all new technologies, there are growing pains. When frst introduced, ELD was largely utilized for membrane integrity testing on vegetative roofng assemblies and other inverted roof membrane assemblies (IRMAs) that would receive overburden. Now that the benefts of ELD are more widely rec- ognized, it is being specifed for a much broader range of roofng and waterproofng projects. However, the vast array of roofng and waterproofng materials and construc- tions means there can be confusion as to what constitutes a testable assembly. Increasingly, testing frms are being asked to “wave the magic wands” and pinpoint leak locations in systems that can be chal- lenging or impossible to test. This article will address some of the factors affecting the testability of com- monly employed roofng and waterproofng assemblies, the benefts of installing alter- native grounding media, and the challenges involved in leak detection on systems with overburden. ELD ON CONVENTIONAL INSULATED ROOFING SYSTEMS Electronic leak detection requires three conditions for accurate testing: a grounding medium beneath the membrane to receive the electric current (typically a structural concrete deck, metal deck, or alternative grounding medium), a membrane that is electrically nonconductive, and no electri- cally insulating materials between the membrane and the ground. ELD testing has always been straightforward on membranes applied direct- ly to a highly conductive substrate such as a struc- tural concrete deck (Figure 1). Now ELD is often the go-to integrity test on con- ventional roofng systems, with insulation installed between the membrane and the conductive deck. However, the same proper- ties that make insulations and coverboards thermal- ly insulating also create electrical resistance to the current utilized with ELD (Figure 2). The presence of these poorly conductive and noncon- ductive materials typically requires that an alternative ground be placed in the system. Two commonly available ground materials are lightweight wire grid and electrically conductive primer. However, there are dif- ferences of opinion regarding the reliability of leak detection utilizing these alternative grounds. In 2014, ASTM released Standard D7877, providing guidelines for ELD testing on conventional insulated systems: Figure 1 – ELD test results are extremely reliable when the membrane is applied directly to a highly conductive structural concrete deck. 2 0 R C I I N T E R F A C E J U L Y 2 0 1 7

Transcript of Electronic Leak Detection: Sound Science, Not a Magic Wand · to “wave the magic wands” and...

Page 1: Electronic Leak Detection: Sound Science, Not a Magic Wand · to “wave the magic wands” and pinpoint . leak locations in systems that can be chal-lenging or impossible to test.

Due to its many advantages over flood testing, mem-brane integrity testing with electronic leak detection (ELD) has rapidly become the first choice for owners,

manufacturers, specifiers, consultants, and contractors around the world. ELD on roof-ing and waterproofing membranes is prov-ing to be faster, safer, more accurate, and often less expensive than flood testing. However, as with all new technologies, there are growing pains.

When first introduced, ELD was largely utilized for membrane integrity testing on vegetative roofing assemblies and other inverted roof membrane assemblies (IRMAs) that would receive overburden. Now that the benefits of ELD are more widely rec-ognized, it is being specified for a much broader range of roofing and waterproofing projects. However, the vast array of roofing and waterproofing materials and construc-tions means there can be confusion as to what constitutes a testable assembly. Increasingly, testing firms are being asked to “wave the magic wands” and pinpoint leak locations in systems that can be chal-lenging or impossible to test.

This article will address some of the factors affecting the testability of com-monly employed roofing and waterproofing assemblies, the benefits of installing alter-native grounding media, and the challenges

involved in leak detection on systems with overburden.

eld on Conventional insulated Roofing systeMs

Electronic leak detection requires three conditions for accurate testing: a grounding medium beneath the membrane to receive the electric current (typically a structural concrete deck, metal deck, or alternative grounding medium), a membrane that is electrically nonconductive, and no electri-cally insulating materials between the membrane and the ground.

ELD testing has always been straightforward on membranes applied direct-ly to a highly conductive substrate such as a struc-tural concrete deck (Figure 1). Now ELD is often the go-to integrity test on con-ventional roofing systems, with insulation installed between the membrane and the conductive deck. However, the same proper-ties that make insulations and coverboards thermal-ly insulating also create electrical resistance to the current utilized with ELD (Figure 2). The presence

of these poorly conductive and noncon-ductive materials typically requires that an alternative ground be placed in the system. Two commonly available ground materials are lightweight wire grid and electrically conductive primer. However, there are dif-ferences of opinion regarding the reliability of leak detection utilizing these alternative grounds. In 2014, ASTM released Standard D7877, providing guidelines for ELD testing on conventional insulated systems:

Figure 1 – ELD test results are extremely reliable when the membrane is applied directly to a highly conductive structural concrete deck.

2 0 • R C I I n t e R f a C e J u l y 2 0 1 7

Page 2: Electronic Leak Detection: Sound Science, Not a Magic Wand · to “wave the magic wands” and pinpoint . leak locations in systems that can be chal-lenging or impossible to test.

“In roof assemblies where the mem-brane is installed over electric insu-lating material such as insulating foam or a protection board, or both, the electric path to any conductive deck is interrupted. The situation can be remedied by placing a con-ductive material directly under the membrane. The conductive material provides the return path for the test currents.”

There are two commonly employed responses to the requirements of D7877. An electrically conductive primer can be applied directly under the membrane (Figure 3), or conductive wire grids can be installed directly under some membrane products (Figure 4). However, while some manufac-turers have approved the use of conductive primer in their assemblies, others are still performing compatibility testing with their materials. Also, some membrane manufac-turers have not approved the installation of wire grid directly under their membranes. This often leads to the placement of the metal grid between the coverboard and the

insulation, rath-er than directly under the mem-brane (Figure 4).

The effective-ness of placing wire grids under c o v e r b o a r d s remains in dis-pute. While some ELD vendors express confi-dence in testing assemblies where a wire grid is installed under the coverboard, other service pro-viders have found

Figure 2 – When electrically insulating materials are present between the membrane and the conductive deck, breaches can remain undetected unless an alternative grounding medium is installed.

that commonly employed coverboards such as fiber-rein-forced gypsum are insulators and interrupt the flow of current to ground unless the coverboards are wet. This calls into ques-tion the accuracy of ELD testing on systems with the wire grid between the coverboard and the insulation, unless the assembly has

experienced significant rain events. It would greatly benefit the entire industry if these testability questions were resolved through an independent evaluation of a wide variety of membranes, insulations, coverboards, structural decks, and grounding media.

J u l y 2 0 1 7 R C I I n t e R f a C e • 2 1

Page 3: Electronic Leak Detection: Sound Science, Not a Magic Wand · to “wave the magic wands” and pinpoint . leak locations in systems that can be chal-lenging or impossible to test.

eld on systeMs With oveRBuRden Ideally, ELD integrity testing of a new

assembly is performed on an exposed mem-brane. Once overburden materials such as vegetation, pavers, ballast, etc. are installed, leak investigations are subject to a number of practical limitations.

Assemblies that will receive overburden are typically fitted with on-demand leak detection systems when the initial integrity test is performed. These systems consist of conductive wire loops installed on the

surface of the membrane and connection boxes installed above the overburden to provide access to the wire loops at a later date. Specifications typically require that the loops be installed in area increments not exceeding 7000 sq. ft. However, there are many factors that can impair the accuracy of testing through overburden.

Low-voltage ELD is required on systems with overburden installed. (High-voltage ELD relies on direct contact between the electrically charged brushes and the mem-

RCI DoCument CompetItIon - RaIse the BaR -

Do you have reports and construction documents you are proud of? Raise the bar in the building envelope industry by showcasing your talent, and gain the respect of your peers by entering the 2018 RCI Document Competition.

There is no fee to enter. Entries will be accepted in four categories that include reports and construction documents directly

Download Your Entry Form Today!

RCI, Inc. 800-828-1902 rci-online.org

entRy DeaDlIne septemBeR 30, 2017

Winners receive awards and recognition at the 33rd RCIInternational Convention and Trade Show in Houston, TX, March 22-27, 2018.

Winning documents will befeatured in RCI Interface.

rci-online.org/document-competition

Charles Sietmann (left) receives a document competition award from Christopher Giffin.

brane and is not an option on assem-blies with overburden.) Low-voltage testing involves generating and interpreting elec-trical patterns on the membrane surface at low levels of voltage and amperage. To achieve accurate test results, these rela-tively subtle patterns must be sensed and interpreted through the overburden mate-rial. The membrane surface must be wet, which may require large volumes of water; dry areas of membrane will not be tested. In some cases, the type and/or thickness of the overburden can negatively impact the testing. The difficulty of interpreting these patterns increases with the depth of the overburden, and thick layers of insulation and/or vegetation can weaken and even disrupt the signal.

Electrical interference within the over-burden can also adversely affect the test results. Some assemblies contain elec-trically insulating protection membranes between the overburden and waterproofing membrane. Lightning protection systems, roof drains, metal conduit, and other unin-tended metal grounds in the overburden can create false positives or disrupt the patterns so that accurate testing cannot be performed. Metal counterflashings that con-tact the overburden can also cause uninten-tional grounding.

Pavers in setting beds involve unique challenges, while pavers on pedestals are not reliably testable assemblies. The pros-pects for a successful test of a membrane in the middle of a split slab are also poor due to their monolithic nature. Also, topping slabs often contain reinforcing steel, which disrupts the electrical patterns.

Unfortunately, many of these poten-tial pitfalls may not be recognized due to the presence of the overburden, and often the testability of an assembly can only be established on-site as the ELD technician conducts the low-voltage procedure.

If the plan is to employ ELD on the sys-tem after the overburden installation, the design team must be certain that it is using material and design approaches that will not interfere with any subsequent testing. Designers can benefit from utilizing expe-rienced ELD service providers to provide guidance in the selection of materials and techniques.

On-demand leak detection systems are relatively inexpensive and are often includ-ed in the base cost when quality assur-ance ELD testing is performed on a newly installed membrane. They can prepare the

2 2 • R C I I n t e R f a C e J u l y 2 0 1 7

Page 4: Electronic Leak Detection: Sound Science, Not a Magic Wand · to “wave the magic wands” and pinpoint . leak locations in systems that can be chal-lenging or impossible to test.

7.50W X 5H.indd 1 1/23/17 2:23 PM

Figure 3 – Electrically conductive primer is system for future installed directly under the membrane and meets testing without ASTM Standard D7877. the expense of

moving overbur-den to install the wire at a Figure 4 – In some assemblies,later date. While lightweight wire grids can be installed the presence of directly under the membrane, but due the system does to manufacturer’s concerns, they are not guarantee often placed between the insulation successful leak and a coverboard. detection with the overburden in place, they are recommended in most assemblies, as they can often locate leaks and can help avoid the costs involved in remov- Even with everyone’s best efforts ing and replacing overburden to perform to design and install an ELD-visual leak inspections. compatible assembly, all parties

Since there are several factors that can should be made aware that the negatively impact the success and accuracy presence of the wire loops does of leak detection through overburden, it is not necessarily guarantee that important that consultants, contractors, an accurate leak test can be per-and leak detection service providers care- formed through the overburden. fully manage the customer’s expectations. Technically advanced auto-

J u l y 2 0 1 7 R C I I n t e R f a C e • 2 3

Page 5: Electronic Leak Detection: Sound Science, Not a Magic Wand · to “wave the magic wands” and pinpoint . leak locations in systems that can be chal-lenging or impossible to test.

-

-

-

mated leak detection systems are also available. Typically these systems use leak detection sensors that are installed in the roof assembly during construction, and allow continuous monitoring of roof assem-bly performance. Any developing mainte-nance issues are quickly identified and reported for action. While more expensive than simple “on-demand” systems, they are often specified for critical roof applications such as hospitals, data centers, museums, and government facilities.

nontestaBle MeMBRanes ELD requires a nonconductive mem-

brane to separate the positive and neutral sides of the circuit. If there are no breaches, the circuit will never be completed. When breaches are present, the ELD instruments can determine the location where the cur-rent has grounded through a breach in the membrane.

Ethylene propylene diene monomer (EPDM) membranes are manufactured with an electrically conductive carbon black fill-er, and will not function as an insulat-

ing material between the two sides of the circuit. Other examples of materials that can’t be tested are metal flashings and membranes with metallic coatings. Butyl membranes are also conductive and cannot be tested with ELD.

Electronic leak detection has quickly become standard practice on roofing and waterproofing membranes and has been specified on some of the nation’s most pres-tigious buildings. All stakeholders—own-ers, manufacturers, designers and contrac-tors—benefit greatly from sound, watertight installations. Properly applied, ELD testing will help us all deliver higher-quality, more trouble-free assemblies.

RefeRenCes 1. ASTM D7877-14, Standard Guide

for Electronic Methods for Detecting and Locating Leaks in Waterproof Membranes. ASTM International.

2. Sika Sarnafil Technical Bulletin #15-8, “Electronic Leak Detection Testing Limitations,” 8/11/2015, https://s3.us-east-2.amazonaws.

com/roo f ing - techn ica l -down-l o a d / T e c h n i c a l + B u l l e t i n s / W a t e r p r o o f i n g / 1 5 - 8 + E L D + Testing+Limitations.pdf.

Peter Brooks is president of IR Analyzers/Vector Mapping. He has over 35 years of experience in non-destructive testing and has worked closely with hun-dreds of architects, engineers, consul-tants, and contrac-tors and performed infrared, nuclear,

and ELD testing and analysis in a wide vari-ety of built environments. Brooks has written a number of articles on the technical and practical aspects of applied infrared ther-mography and ELD. He is a former director of Region I of RCI.

Peter Brooks

At your own pace, on your own time, at your fingertips ...

Roof Drainage Design and Calculations

Roof System Thermal and Moisture Design

Roofing Basics

Roofing Technology and Science I

Roofing Technology and Science II

Rooftop Quality Assurance

Wind Design for Low Slope Roofs - Part I:

Understanding ASCE 7-05 Wind Load Calculations

Wind Design forLow Slope Roofs - Part I:

Understanding ASCE 7-10 Wind Load Calculations

Wind Design for Low Slope Roofs - Part II: FM

Global Guidelines and Best Practice Considerations

Online Educational Programs

www.rci-e-learning.org

2 4 • R C I I n t e R f a C e J u l y 2 0 1 7