Electrical Notes & Articles Sharing Abstracts,Notes on various Electrical Engineering Topics. Electrical Q&A Part-3 1) What is the reason of grounding or earthing of equipment? with a ground path, in case of short circuit the short circuit current goes to the body of the equipment & then to the ground through the ground wire. Hence if at the moment of fault if a person touches the equipment body he will not get a shock cause his body resistance (in thousands of ohms) will offer a high resistance path in comparison to the ground wire. Hence the fault current will flow thru the ground wire & not thru human body. Providing a ground path helps in clearing the fault. A CT in the ground connection detects the high value fault current hence the relay connected to the CT gives breaker a trip command. Grounding helps in avoiding arcing faults. IF there would have been no ground then a fault with the outer body can cause a arcing to the ground by breaking the air. This is dangerous both for the equipment & the human beings. 2) A type-C MCB has thermo magnetic capability 5In to 10In that means a short circuit current will be interrupted as the value will reach between 5In to 10In but the MCB breaking capacity is (for example) define as 10kA. 5In to 10In is the pickup threshold for the magnetic trip element. The MCB will trip instantaneously when the current is between these limits. 10kA is the short circuit withstands capacity of the MCB. Under normal condition, a current limiting type MCB will trip on short circuit (magnetic trip) and the current during circuit interruption will be much less than the prospective current. However, the MCBs have to have a short circuit capacity more than or equal to the fault level at the location where it is installed. 3) What is Ferrari Effect? Ferranti Effect is due to the rise in voltage at the receiving end than that of the sending end. This occurs when the load on the system reduces suddenly. Transmission line usually consists of line inductance, line to earth capacitance and resistance. Resistance can be neglected with respect to the line inductance .When the load on the system falls the energy stored in the capacitance gets discharged. The charging current causes inductive reactance voltage drop. This gets added vector ally to the sending end voltage and hence causes the voltage at the receiving end to raise A Long transmission line draws significant amount of charging current. If such line is open circuited or very lightly loaded at the receiving end, the voltage at the receiving end may become greater than sending end voltage. This effect is known Ferranti effect and is due to the voltage drop across the line inductance (due to charging current) being in phase with the sending end voltages. Therefore both capacitance and inductance is responsible to produce this phenomenon. The capacitance (charging current) is negligible in short lines, but significant in medium and long transmission line. Hence, this phenomenon is applicable for medium and long transmission line. The main impact of this phenomenon is on over voltage protection system, surge protection system, insulation level etc.

description

fadfs

Transcript of Electrical Q&A Part-3 _ Electrical Notes & Articles

  • Electrical Notes & Articles

    Sharing Abstracts,Notes on various Electrical Engineering Topics.

    Electrical Q&A Part-3

    1) What is the reason of grounding or earthing of equipment?

    with a ground path, in case of short circuit the short circuit current goes to the body of the equipment &then to the ground through the ground wire. Hence if at the moment of fault if a person touches theequipment body he will not get a shock cause his body resistance (in thousands of ohms) will offer a highresistance path in comparison to the ground wire. Hence the fault current will flow thru the ground wire &

    not thru human body.Providing a ground path helps in clearing the fault. A CT in the ground connection detects the high valuefault current hence the relay connected to the CT gives breaker a trip command.

    Grounding helps in avoiding arcing faults. IF there would have been no ground then a fault with the outerbody can cause a arcing to the ground by breaking the air. This is dangerous both for the equipment & thehuman beings.

    2) A type-C MCB has thermo magnetic capability 5In to 10In that means a short circuit current will

    be interrupted as the value will reach between 5In to 10In but the MCB breaking capacity is (forexample) define as 10kA.

    5In to 10In is the pickup threshold for the magnetic trip element. The MCB will trip instantaneously when

    the current is between these limits. 10kA is the short circuit withstands capacity of the MCB.Under normal condition, a current limiting type MCB will trip on short circuit (magnetic trip) and thecurrent during circuit interruption will be much less than the prospective current. However, the MCBs

    have to have a short circuit capacity more than or equal to the fault level at the location where it isinstalled.

    3) What is Ferrari Effect?

    Ferranti Effect is due to the rise in voltage at the receiving end than that of the sending end. This occurswhen the load on the system reduces suddenly.Transmission line usually consists of line inductance, line to earth capacitance and resistance. Resistancecan be neglected with respect to the line inductance .When the load on the system falls the energy stored in

    the capacitance gets discharged. The charging current causes inductive reactance voltage drop. This getsadded vector ally to the sending end voltage and hence causes the voltage at the receiving end to raiseA Long transmission line draws significant amount of charging current. If such line is open circuited orvery lightly loaded at the receiving end, the voltage at the receiving end may become greater than sendingend voltage. This effect is known Ferranti effect and is due to the voltage drop across the line inductance(due to charging current) being in phase with the sending end voltages. Therefore both capacitance and

    inductance is responsible to produce this phenomenon.The capacitance (charging current) is negligible in short lines, but significant in medium and longtransmission line. Hence, this phenomenon is applicable for medium and long transmission line.The main impact of this phenomenon is on over voltage protection system, surge protection system,insulation level etc.

  • 4) Can single phase transformers be used for three phase applications?

    Yes. Three phase transformers are sometimes not readily available whereas single phase transformers cangenerally be found in stock. Three single phase transformers can be used in delta connected primary andwye or delta connected secondary. They should never be connected wye primary to wye secondary, sincethis will result in unstable secondary voltage. The equivalent three phase capacity when properlyconnected of three single phase transformers is three times the nameplate rating of each single phasetransformer.

    5) What is BIL and how does it apply to transformers?

    BIL is an abbreviation for Basic Impulse Level. Impulse tests are dielectric tests that consist of theapplication of a high frequency steep wave front voltage between windings, and between windings andground. The BIL of a transformer is a method of expressing the voltage surge that a transformer willtolerate without breakdown.

    6) Where Auto-recloser is used?

    For Generator protection / Transformer Protection / Transmission Line / Bus bar protection.Many faults on overhead transmission lines are transient in nature 90% of faults are used by birds, treebranches. These condition results in arching faults and the arc in the fault can be extinguished by de-energizing the lines by opening of CB on the both ends of the lines.Open-0.3 second-Close-3minute-Close this is the sequence of AR. i.e.-OPEN,C-CLOSEDwhenever faults occurs CB opens, then after 0.3 sec it closes automatically, if faults persists then it will openafter 3 min it closes and if still fault persists. It remains in open condition.Auto reclosure is generally used for Transmission lines where the general types of faults are transient innature.It can be three phase auto-reclosure or single pole auto-reclosure.The single pole auto reclosures are generally for 400kV line below this three pole auto- reclosures are used.The reason for a line the single pole reclosures provides a better stability of the system since some part ofpower is still transferred through the healthy phases.

    Also 400kV breaker till date has a independent drive/ trip/ close coils for the three poles, below that allbreakers have common drive/ trip / closing coils for the three poles.

    7) What is difference between power transformers & distribution transformers?

    Distribution Transformers are designed for a maximum efficiency at 50% of load. Whereas powertransformers are designed to deliver max efficiency ay 90% and above loads.The distributions transformers have low impedance so as to have a better regulation power transformershave higher so as to limit the SC current.Power transformers are used to step up voltages from 11 KV which is the generating voltage to 132 orwhatever will be the transmission voltage levels. Power transformers are having Star-Delta connection. Itwill be located at power generating stations.Distribution transformers are used to step down voltages from transformer levels to 11 KV/415 V. Will behaving Delta-Star. It will be located in substations near load centers.The main basic difference lies in the Design stage itself as power transformer are to operate at near full loadso there sensing is such that they achieve equal. of copper losses & iron losses at full loads whereas this is

    achieved in the design itself at about 50% loading in dist transformer but friends there is a dilemma as ourdist. transformer are almost fully loaded & beyond so they never go operate at their full eff. & also poorvoltage regulation.The difference between power and distribution transformers refers to size & input voltage. Distributiontransformers vary between 25 kVA and 10 MVA, with input voltage between 1 and 36 kV. Powertransformers are typically units from 5 to 500 MVA, with input voltage above 36 kV. Distribution

  • transformer design to have a max efficiency at a load lower than full load. Power transformer design tohave a max efficiency at full load

    8) What will be happen if the neutral isolator will be open or close during the running condition ofpower?

    During normal condition the neutral isolating switch should be kept close. In case it is kept open, underbalanced load conditions the current through neutral will not flow & nothing harmful will take place but incase an earth fault takes place then there will be no earth fault current flowing through the system & thegenerator will run as a ungrounded generator. Thus the earth fault will not be cleared.If more number of generators are connected parallel. We will have a close loop and hence negative

    sequence current will flow. This will increase the rotor temperature. Hence if more number of generatorsare connected then only one is earthed and others are open.In case of Two or more generators connected to a common bus without a transformer in between, basicallyin hydro stations, one of the Neutral Isolation Switch(NIS) is kept closed & rest are opened to preventcirculating currents to flow between generators. Hence the above explanation will not be valid for suchsystems.Sometime we may want to test generator and may want to isolate the neutral from ground. like forexample meggaring etc. In such case we would like to open ground connection cable in case we want toremove the NIS? we will certainly not like to open all the bolted connections for just a small test likechecking insulation with a meggar etc. for such things we need a NIS.Neutral isolator is required if we have delta transmission system and at the time to connection with theGrid Neutral isolation is required.

    If we ungrounded the neutral then the generator is connected to the ground via Phase to earthcapacitances. Hence during faults arcing grounds can take place. Which are dangerous both to human &

    equipment.When we provide earthed neutral, for a fault, earth fault current will start flowing through the neutral,

    which we can sense thru a CT & relay & hence can immediately identify & clear the fault in about 100 msby opening the associated breaker/prime mover/excitation. Quicker the fault clearance less is the damage.

    9) Why shorting type terminal required for CT?

    During maintenance or secondary injection you will need to bypass the CT & for the same you needshorting link. During sec. injection you will short circuit the main CT & bypass it. Open circuiting the CT

    will saturate it & damage it.

    10) Why fuse is given for only PT and not CT?

    Fuse if given for CT blows off due to a fault then rather than protecting the CT it will make it opencircuited hence it will be saturated & damaged. For PT it gives overload & SC protection.

    11) Why is insulating base required for LA?

    The LA is provided with a dedicated Prper earthing which may be in the form of a buried treated electrodenext to it.LA connection is securely made with the electrode via a surge counter. If we directly earth the LA

    through structure then the surge counter will not be able to measure the no of surges. For lesser rating thecounter is not provided, hence we can bypass the insulated base. But then proper earthing has to be

    assured.

    12) Can 60 Hz transformers be operated at 50 Hz?

    Transformers 1 KVA and larger, rated at 60 Hz, should not be used on 50 Hz service due to higher losses

    and resultant heat rise. However, any 50 Hz transformer will operate on 60 Hz service.

  • 13) Can transformers be used in parallel?

    Single phase transformers can be used in parallel only when their voltages are equal. If unequal voltagesare used, a circulating current exists in the closed network between the two transformers which will cause

    excess heating and result in a shorter life of the transformer. In addition impedance values of eachtransformer must be within 7.5% of each other.

    14) Can Transformers be reverse connected?

    Dry type distribution transformers can be reverse connected without a loss of KVA rating, but there arecertain limitations. Transformers rated 1 KVA and larger single phase, 3 KVA and larger three phases can

    be reverse connected without any adverse effects or loss in KVA capacity.

    15) Why short circuit do not take place when electrode is touched to ground.

    Basically during welding we force a short-circuit at the electrode tip. The fault condition produces large

    magnitude currents. Greater the Current value have greater I2R heat produced. The arcing energy elevatesthe temperature & hence melts the electrode material over the joint.

    The transformer is designed to withstand such high currents. But welding is a very complex & detailedphenomenon. Besides there are many principles on which welding operates. Some may be a welding, dc

    welding, arc, constant voltage, constant current etc

    16) Whats the difference between generator breaker and simple breaker?

    Breaker is one which disconnects the circuit in fault condition and It is similar for all equipment. Based onthe equipment voltage and maximum short circuit current the ratings will be decided. For better

    understanding we call generator or transformer or line etc breakers.

    17) What is accuracy Class of the instrument?

    Generally the class indicates the accuracy with which the meter will indicate or equipment will measure

    with respect to its input.The accuracy of different equipment will depend on number of factors.

    For example for a PT accuracy will depend on its leakage reactance & winding resistance. For a PTaccuracy gives the voltage & phase error & it varies with the VA burden of secondary. Also better core

    material will give better heat dissipation & reduce error. class of accuracy will give the voltage error for aPT

    different type of PTs available are:0.1, 0.2, 0.5, 1, 5 & error values will be: class% voltage error(+/_) phasedisplacement

    Similarly indicating instruments shall have accuracies & accordingly application as depicted below for

    testing the following values are generally used:for routine tests : accuracy class 1

    for type tests : accuracy class 0.5 or better.indicating meters generally will have accuracy of 1.

    18) First pole to clear factor-Circuit breakers

    The first pole to clear factor (kpp) is depending on the earthing system of the network. The first pole toclear factor is used to calculating the transient recovery voltage for three phase faults. In general following

    cases apply:-1. kpp = 1.3 corresponds to three phase faults in system with an earthed neutral.

    2. kpp = 1.5 corresponds to three phase faults in isolated or resonant earthed system.3. kpp = 1.0 corresponds to special cases e.g. railway systems.

    A special case is when there is a three phase fault without involving earth in a system with earthed neutral.

  • This case responds to kpp = 1.5 . This special case is however not normally considered in the standards.

    19) Why we use a resistance to ground the neutral when we need always low resistivity for the

    grounding?

    If we ground the generator directly then whenever a fault will take place at any phase with ground thefault current flowing throw the faulted phase-to ground-to neutral will be very high cause there will be no

    resistance to limit the value of fault current. Hence we insert a resistance in the neutral circuit to limit thisfault current. Also we need to reduce the fault current to such a value that the protection CTs are able to

    identify the fault current without saturating the CTs. Communicate it to the protection relays & hence therelays can then isolate the system from the fault; so that the system is isolated from the fault before the

    harm is done by the fault current. That is the reason that all the equipment will be designed for fault KAvalues for 1 sec so that the total operation(CT sensing-relay functioning-circuit breaker operation ) time will

    be less than 1 sec. hence the Breakers will isolate the fault before 1 sec i.e. within the time period the

    equipment are designed to carry the fault current. Thus all your objectives of:preventing the arcing.

    limiting the fault current.isolating the faulted system are achieved

    20) Why are NGRs rated for 10sec?

    NGR are placed in the neutral circuit & hence will be energized only in the fault conditions thus theircontinuous loading is not expected. Hence they are selected for intermittent rating. Similarly when we

    place a transformer in the neutral grounding circuit the KVA rating obtained after the calculation ismultiplied by a diversity factor to obtain smaller rating cause the therefore It will not be continuously

    rated.NIS is also provided to cut the circulating negative sequence current in 2 more generators connected in

    parallel.in some grid conditions they ask to keep neutral isolated after being connected to grid.

    21) How to calculate knee point voltage and significance of knee point voltage?

    Knee point voltage: That point on the magnetizing curve (BH curve) where an increase of 10% in the flux

    density (voltage) causes an increase of 50% in the magnetizing force (current). Its significance lies mainlyin PS class core of CTs used for diff protection

    22) Design method for neutral grounding resistor?

    NGR design basics:Capacitive coupling of generator, equipment and the ground

    -Generator to ground capacitance.-Generator cable to ground capacitance (or bus duct as the case may be)

    -Low voltage winding of trafo & ground capacitance.-Surge arrestor capacitance.

    The total capacitance is then obtained from the above values & then we calculate from that the capacitive

    reactance. The capacitive current then produced is calculated from the generator voltage & the capacitivereactance obtained above. Once the current is obtained we can then calculate the electrostatic KVA from

    the current multiplied with voltage.

    23) Criterion is there for selection of Insulation Disc in Transmission and Distribution Line.

    11kV is the phase to earth voltage for 220kV =220/ (sqrt(3)*11)=12 Nos of disc are suitable.The numbercan be increased to increase the creep age distance.

  • While selecting the disc insulators one has to keep in mind the following things:1. EM-strength of the string. All the forces coming on to the string & the ability of the string to withstand

    them.

    2. Sufficient Cree page distance so as not to cause a flashover .

    3. Interface with the type of conductor used (moose, tarantula, zebra etc)

    So we will get the value of no of discs by dividing the phase to earth voltage with 1.732. Once that is donethen we need to see its suitability with respect to EM strength.

    After this we need to consider the force that the stack has to bear. If we have a strain type of fitting i.e. the

    stack has to bear horizontal conductor tension, weight load of the conductor, wind load, ice load etc then

    the number of insulator discs required may be more.But for a suspension type system which has to bear only the weight then number of discs required may be

    less than what we get by dividing by 11. That is the reason we have seen only 23/24 discs in 400 kv line

    cause in that case the creep age obtained must have been enough & also the strain requirement.

    33kv insulators are generally used in a vertical installation & are not stacked together because that willmake the suspension very rigid

    24) Do taps work the same when a transformer is reverse fed?

    Taps are normally in the primary winding to adjust for varying incoming voltage. If the transformer is

    reverse fed, the taps are on the output side and can be used to adjust the output voltage.

    25) Why may I get the wrong output voltage when installing a step up transformer?

    Transformer terminals are marked according to high and low voltage connections. An H terminal signifies

    a high voltage connection while an X terminal signifies a lower voltage connection. A commonmisconception is that H terminals are primary and X terminals secondary. This is true for step down

    transformers, but in a step up transformer the connections should be reversed. Low voltage primary would

    connect to X terminals while high voltage secondary would connect on the H terminals.

    26) Can a single phase transformer be used on a three phase source?

    Yes. Any single phase transformer can be used on a three phase source by connecting the primary leads toany two wires of a three phase system, regardless of whether the source is three phase 3-wire or three phase

    4-wire. The transformer output will be single phase.

    27) Why in Double circuit wire are transposed (R B, Y Y, B R)

    This is done to avoid

    1. Proximity effect2. Skin effect

    3. Radio interference

    4. Reduction in noise in communication Signals

    28) Selection of LA

    The voltage rating of LA is selected as: Line voltage x sqrt(2)/ sqrt(3) so for 11kV line its 9kV

    In that case also the values would not differ much if We takes the TOV factor as 1.4. However, we can takethe value of 1.56 as TOV to be more precise.

    29) Which is more dangerous AC or DC

    Low frequency (50 60 Hz) AC currents can be more dangerous than similar levels of DC current since

    the alternating fluctuations can cause the heart to lose coordination, inducing ventricular fibrillation, which

    then rapidly leads to death.

  • However any practical distribution system will use voltage levels quite sufficient to ensure a dangerous

    amount of current will flow, whether it uses alternating or direct current. Since the precautions against

    electrocution are similar, ultimately, the advantages of AC power transmission outweighed this theoreticalrisk, and it was eventually adopted as the standard.

    30) What all are the applications where high speed grounding switches are used.

    Generator neutral is earthed directly or through distribution transformer. This neutral earthing is through

    done through a switch. This is general practice for only one generator.

    For two generators in parallel to a bus the neutral earthing is different. If both the neutral earthing is closed

    the negative sequence current will be flowing though both the generator taking earth as path. This leads toincrease in loss and increase in temperature (This may leads to false tripping also). Hence once the second

    generator is synchronized with the bus or grid the neutral is isolated.

    Neutral grounding switch we do not need a high speed grounding switch. A normal switch with the

    correct rating capacity would also work.

    31) What is Skin Effect and how does it happen??

    According to faradays law of electromagnetic induction, a conductor placed in a changing magnetic field

    induces an emf. The effect of back emf is maximum at the centre because of maximum lines of field there.

    Hence the maximum opposition of current at inner side of conductor and minimum opposition at the

    surface. Hence the current tries to follow at the surface. It is due to this reason that we take hollow tubeconductors in bus duct.

    Taking into account the inductance effect, its simple consider the DC current. Since its constant & not

    varying hence no back emf but if we gradually start increasing the frequency then the flux cutting the

    conductor goes on increasing, hence greater the frequency greater the alternating flux cutting the

    conductor & hence greater the back emf & therefore greater the skin effect.

    32) Why we ground the sheath of single core power cables and to avoid grounded at both the ends?

    A single core cable with a sheath is nothing but a conductor carrying current surrounded by another

    conductor (sheath). Hence the Alternative current in the conductor induces voltages in the sheath or the

    armour. Hence grounding these cables at both ends will cause the potential of the armour to be same as

    ground potential & hence shall become safe for the personnel.But grounding the cables at both the end will cause a problem. In that case the circulating currents will

    start flowing with the armor, the ground & with the two ends of the grounding completing the circuit. This

    will also provide path for the fault currents to flow. Hence this whole thing will cause the cable to produce

    some I2R losses, hence heating & hence the current carrying capacity will be de rated. This system of cableearthing is called both-end bonding. This system is suggested only when one wants to avoid the voltage

    development because can either go with the de rated cable or if one updates the cable in advance.

    When only one end of the cable sheath is grounded then there is no path for the circulating current to flow.

    Hence the current carrying capacity of the cable will be good. But in this case potential will be induced

    between sheath & ground. This potential is proportional to the length of the cable & hence this will limitthe length of the cable used. This method is called single point bonding. This is thus used only for short

    lengths.

    There is another system called the cross bonding system in which the sheath are sectionaliosed & cross

    connected so that the circulating currents are minimized. Although some potential will also exist betweensheath & ground, the same being maximum at the link boxes where bonding is done. This method

    provides maximum possible current carrying capacity with the maximum possible lengths.

    33) What is EDO & MDO type breaker?

    In the Breakers for the operation spring charging is must.

    In EDO breaker the spring charging is done with a motor and draw out manually by hand. so EDO

  • means Electrically spring charged Draw Out breakerIn MDO breaker the spring charging is also done by hand manually and draw out about also by hand

    only. so MDO means Manual spring charge Draw Out breaker

    34) Why transformer rating is in KVA or KW?

    Because power factor of the load is not defined in case of transformer thats why it is not possible to rate

    transformer in KW.The losses (cu loss and iron loss) of the transformer depends on current and voltage purely, not on load i.e,

    phase angle between the current and voltage i.e. why transformer rated in kVA

    Transformer is not a load and having no effect on P.F (thats why no change in its power factor) and it

    only transfer the constant power from one voltage level to another voltage level without changingfrequency. since both the losses viz copper loss(depends on current) and iron loss(depends on voltage) are

    independent of power factor, that is why a Transformers rating is not on kW, but on KVA

    35) Why the secondary of CT never open when burden is connected on the CT.?

    secondary of CT is never opened as because CT is always connected to the line so opening the secondary

    will mean there will be no counter mmf to balance the primary current as a result of which a very high

    induced emf may appear in the secondary as flux is very high and no counter mmf and this will bedangerous for the personnel in the secondary side and for pt if it is shorted then with full voltage applied to

    the primary.

    If we short the secondary then much high current will circulate in the secondary due to high induced emf

    much higher than the actual full load current as a result of which the transformers secondary windingmay burn out.

    36) Distance relay setting

    Step1:

    Get the conductor Details (i.e Positive Sequence Impedance (Z), Zero Sequence Impedance(Z0)) which is

    in Primary value. Convert in terms of secondary values.Step 2 :

    Based upon the calculated value divide into various zones

    Zone 1 (Forward) means 80% of your protected line length.

    Zone 2 (Forward) means 100% of protected line length + 20% Adjacent Shortest line

    Zone 3 (Forward) means 100% of protected line length + 50% Adjacent Longest line.Zone 4 (Reverse) means 10% of protected line.

    37) Difference between CT class 0.2 and 0.2S?

    0.2S & 0.5S: Special type of measurement CTs they guarantee the declared accuracy, even with

    20% loading. And some definite error can be defined even with a load as low as 1%. Thus they are suitable

    for industries where loads are commissioned in steps or stages. Also for tariff metering purposes.0.2S: Special class for metering. It is more accurate than 0.2 classes. Generally if we use 0.2s class CT than

    VA burden of core is also come down.

    In 0.2 classes CT, ratio & phase angle errors must be within the specified limits at 5%, 20%, 100% & 120%

    of rated secondary current. Whereas in 0.2s class CT, ratio & phase angle errors must be within thespecified limits at 1%, 5%, 20%, 100% & 120% of rated secondary current. Also in 0.2s class, Ratio & Phase

    angle errors limits are lower than 0.2 classes.

    38) Why we use inductors

    Inductors have the property to oppose sudden changes in Current. When connected to the primary side

    of transformer, if any sudden short circuit (very high) current flows due to some fault in the system, the

  • inductor will oppose the flow of that current saving the transformer.

    Secondly, for the problem of lagging current. Capacitors are connected across the inductor to improve thelagging current. So Mainly Inductor is used to (i) protected the transformer, (ii) solved the problem of

    lagging current.

    39) Why do we need a bigger breaker when reverse feeding a transformer?

    Typically the output winding is wound first and is therefore closest to the core. When used as exciting

    winding a higher inrush current results. In most cases the inrush current is 10 to 12 times the full load

    current for 1/10 of a second. When the transformer is reverse fed the inrush current can be up to 16 timesgreater. In this case a bigger breaker with a higher AIC rating must be used to keep the transformer

    online.

    40) How many types of Neutral grounding system?

    There are primarily three types of grounding system which are:

    (1)Solid grounding The neutral point of the system is grounded without any resistance. If the groundfault occurs, high ground current passes through the fault. Its use is very common in low voltage system,

    where line to neutral voltage is used for single phase loads.

    (2) Low Resistance grounding (LRG) This is used for limiting the ground fault current to minimize theimpact of the fault current to the system. In this case, the system trips for the ground fault. In this system,

    the use of line to neutral (single phase) is prohibited. The ground fault current is limited to in the rage from

    25A to 600A.

    (3) High Resistance Grounding (HRG) It is used where service continuity is vital, such as process plantmotors. With HRG, the neutral is grounded through a high resistance so that very small current flows to

    the ground if ground fault occurs. In the case of ground fault of one phase, the faulty phase goes to the

    ground potential but the system doesnt trip. This system must have a ground fault monitoring system.

    The use of line to neutral (single phase) is prohibited (NEC, 250.36(3)) in HRG system, however, phase toneutral is used with using the additional transformer having its neutral grounded. When ground fault

    occurs in HRG system, the monitoring systems gives alarm and the plant operators start the standby

    motor and stop the faulty one for the maintenance. This way, the process plant is not interrupted. The

    ground fault current is limited to 10A or less.

    There are other two types such as Corner Grounding (for Delta system) and ungrounded system but theyare not commonly used.

    18 Responses to Electrical Q&A Part-3

    Prakashan says:

    May 20, 2011 at 7:17 am

    Thanks Jignesh,

    Its a woderful collection and question answers are very good

    Keep it up for your efforts..

    Reply

    Manikandan P S says:

    June 26, 2011 at 5:30 pm

    Hai This is Manikandan P S , now i am working as Electrical Estimation Engineer in Low Voltage