Elandflex DC Cables Data Sheet

1
[email protected] www.eland.co.uk tel +44 (0)20 7241 8787 fax +44 (0)20 7241 8700 Find this product online at www.eland.co.uk | Electrical Cable | PVC Flexible Cable Eland Product Group A2F Dimensions Eland Part Number No. Cores x Nominal Cross Sectional Area mm² Nominal Diameter of Strands mm Nominal Thickness of Insulation mm Nominal Overall Diameter mm Nominal Weight kg/Km A2F016 1 x 16 0.3 1.4 8.7 200 A2F025 1 x 25 0.3 1.5 10.5 300 A2F035 1 x 35 0.3 1.7 12.0 410 A2F050 1 x 50 0.3 1.7 13.8 565 A2F070 1 x 70 0.3 1.9 15.9 780 A2F095 1 x 95 0.3 2.0 18.2 1050 A2F120 1 x 120 0.3 2.0 20.1 1300 Electrical Characteristics Current Carrying Capacity (amperes) and Resistance Values (ohms per kilometre) Nominal Cross Sectional Area mm² Electrical Resistance at 20°C Max. ohms/Km Insulation Resistance at 70°C Min. Mohms/Km Current Rating Amps Pipe Open Duct 10 1.910 0.0056 50 57 16 1.310 0.0046 65 73 25 0.850 0.0044 85 97 35 0.595 0.0038 106 121 50 0.419 0.0037 129 145 70 0.297 0.0032 164 184 95 0.219 0.0032 201 225 120 0.175 0.0029 229 258 Conductor Flexible plain copper conductor Sheath PVC (Polyvinyl Chloride) Sheath Colour Black or Red Voltage Rating 450/750V Temperature Rating Fixed: -30°C to +70°C Flexing: +5°C to +70°C Minimum Bending Radius 6 x overall diameter Elandflex Cable ISSUE 04.0910 Application Highly flexible single core conductors with a great variety of industrial applications, such as cable harnesses, panel wiring and power generation. Standards IEC 60332-1 Technical Data The information contained within this datasheet is for guidance only. When selecting accessories such as cleats, glands, etc please note that actual cable dimensions may vary due to manufacturing tolerances. PAGE 1 OF 1

description

Elandflex DC Cables Data Sheet

Transcript of Elandflex DC Cables Data Sheet

Page 1: Elandflex DC Cables Data Sheet

[email protected] www.eland.co.uk tel +44 (0)20 7241 8787 fax +44 (0)20 7241 8700

Find this product online at www.eland.co.uk | Electrical Cable | PVC Flexible Cable

Eland Product Group A2F

Dimensions

Eland Part Number No. Cores x Nominal Cross Sectional Area

mm²

Nominal Diameter of Strands

mm

Nominal Thickness of Insulation

mm

Nominal Overall Diameter

mm

Nominal Weightkg/Km

A2F016 1 x 16 0.3 1.4 8.7 200A2F025 1 x 25 0.3 1.5 10.5 300A2F035 1 x 35 0.3 1.7 12.0 410A2F050 1 x 50 0.3 1.7 13.8 565A2F070 1 x 70 0.3 1.9 15.9 780A2F095 1 x 95 0.3 2.0 18.2 1050A2F120 1 x 120 0.3 2.0 20.1 1300

Electrical Characteristics

Current Carrying Capacity (amperes) and Resistance Values (ohms per kilometre)

Nominal Cross Sectional Areamm²

Electrical Resistance at 20°C Max.

ohms/Km

Insulation Resistance at 70°C Min. Mohms/Km

Current RatingAmps

Pipe Open Duct10 1.910 0.0056 50 5716 1.310 0.0046 65 7325 0.850 0.0044 85 9735 0.595 0.0038 106 12150 0.419 0.0037 129 14570 0.297 0.0032 164 18495 0.219 0.0032 201 225

120 0.175 0.0029 229 258

Conductor Flexible plain copper conductor

Sheath PVC (Polyvinyl Chloride)

Sheath Colour Black or Red

Voltage Rating 450/750V

Temperature Rating Fixed: -30°C to +70°C Flexing: +5°C to +70°C

Minimum Bending Radius 6 x overall diameter

Elandflex Cable

Iss

uE

04

.091

0

ApplicationHighly flexible single core conductors with a great variety of industrial applications, such as cable harnesses, panel wiring and power generation.

standardsIEC 60332-1

Technical Data

The information contained within this datasheet is for guidance only. When selecting accessories such as cleats, glands, etc please note that actual cable dimensions may vary due to manufacturing tolerances.

PAgE 1 oF 1