ECEN 667
Power System Stability
1
Lecture 9: Synchronous Machine Models
Prof. Tom Overbye
Dept. of Electrical and Computer Engineering
Texas A&M University, [email protected]
![Page 2: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/2.jpg)
Announcements
• Read Chapter 5 and Appendix A
• Homework 3 is posted, due on Thursday Oct 5
• Midterm exam is Oct 17 in class; closed book, closed
notes, one 8.5 by 11 inch hand written notesheet
allowed; calculators allowed
2
![Page 3: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/3.jpg)
etc
de d ed
de d ep
se s e
X X X
R R R
Chapter 5, Single Machine, Infinite
Bus System (SMIB)
Book introduces new variables by combining machine
values with line values
Usually infinite bus
angle, qvs, is zero
3
![Page 4: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/4.jpg)
s
ss
sst
HT
T
1
2
“Transient Speed”
Mechanical time
constant
A small parameter
Introduce New Constants
4
We are ignoring the exciter and governor for now; they
will be covered in much more detail later
![Page 5: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/5.jpg)
1 sin
1 cos
dese d t qe s vs
s
qese q t de s vs
s
oese o
dR I V
dt T
dR I V
dt T
dR I
dt
q
q
Stator Flux Differential Equations
5
![Page 6: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/6.jpg)
Elimination of Stator Transients
• If we assume the stator flux equations are much faster
than the remaining equations, then letting go to zero
allows us to replace the differential equations with
algebraic equations
6
0 sin
0 cos
0
se d qe s vs
se q de s vs
se o
R I V
R I V
R I
q
q
![Page 7: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/7.jpg)
Impact on Studies
7
Image Source: P. Kundur, Power System Stability and Control, EPRI, McGraw-Hill, 1994
Stator transients are not considered in transient stability
![Page 8: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/8.jpg)
3 fast dynamic states, now eliminated
, ,de qe oe
7 not so fast dynamic states
1 2, , , , ,q d d q t fdE E E
8 algebraic states
, , , , , , ,d q o d q t ed eqI I I V V V
Machine Variable Summary
8
We'll get
to the
exciter
and
governor
shortly
![Page 9: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/9.jpg)
2 2
sin
cos
t d q
d e d ep q s vs
q e q ep d s vs
V V V
V R I X I V
V R I X I V
q
q
Network Expressions
9
![Page 10: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/10.jpg)
sin
cos
d e d ep q s vs
q e q ep d s vs
V R I X I V
V R I X I V
q
q
These two equations can be written as one
complex equation.
vsjs
jqdepe
jqd
eV
ejIIjXRejVV
q
22
10
Network Expressions
![Page 11: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/11.jpg)
1
2
d s d dde de d q d
d s d s
q s q q
qe qe q d q
q s q s
oe oe o
X X X XX I E
X X X X
X X X XX I E
X X X X
X I
11
Stator Flux Expressions
![Page 12: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/12.jpg)
2
21
q s q q
d q q d q
q s q s
jd s d dq d
d s d s
X X X XE X X I
X X X X
X X X Xj E e
X X X X
E
E
12
Subtransient Algebraic Circuit
![Page 13: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/13.jpg)
Network Reference Frame
• In transient stability the initial generator values are set
from a power flow solution, which has the terminal
voltage and power injection
– Current injection is just conjugate of Power/Voltage
• These values are on the network reference frame, with
the angle given by the slack bus angle
• Voltages at bus j converted to d-q reference by
13
, ,
, ,
sin cos
cos sin
d j r j
q j i j
V V
V V
, ,
, ,
sin cos
cos sin
r j d j
i j q j
V V
V V
Similar for current; see book 7.24, 7.25
, , In book j r j i j i Di QiV V jV V V jV
![Page 14: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/14.jpg)
Network Reference Frame
• Issue of calculating , which is key, will be considered
for each model
• Starting point is the per unit stator voltages (3.215 and
3.216 from the book)
• Sometimes the scaling of the flux by the speed is
neglected, but this can have a major solution impact
• In per unit the initial speed is unity
14
d q d qEquivalently, V +jV +jI
d q s d
q d s q
s q d
V R I
V R I
R I j
![Page 15: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/15.jpg)
Simplified Machine Models
• Often more simplified models were used to represent
synchronous machines
• These simplifications are becoming much less common
but they are still used in some situations and can be
helpful for understanding generator behavior
• Next several slides go through how these models can be
simplified, then we'll cover the standard industrial
models
15
![Page 16: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/16.jpg)
Two-Axis Model
• If we assume the damper winding dynamics are
sufficiently fast, then T"do and T"qo go to zero, so there
is an integral manifold for their dynamic states
16
1
2
d q d s d
q d q s q
E X X I
E X X I
![Page 17: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/17.jpg)
Two-Axis Model
17
11
12
0
Which can be simplified to
ddo d q d s d
qdo q d d
d dd d d s d q fd
d s
qdo q d d d fd
dT E X X I
dt
dET E X X
dt
X XI X X I E E
X X
dET E X X I E
dt
Note this term
becomes zero
![Page 18: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/18.jpg)
Two-Axis Model
18
22
22
0
Which can simplified to
qqo q d q s q
dqo d q q
q qq q q s q d
q s
dqo d q q q
dT E X X I
dt
dET E X X
dt
X XI X X I E
X X
dET E I X X
dt
Note this term
becomes zero
![Page 19: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/19.jpg)
vssdqepqdes VEIXXIRR q sin0
vssqdepdqes VEIXXIRR q cos0
Two-Axis Model
19
![Page 20: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/20.jpg)
FWqddqqqddMs
s
qqqdd
qo
fddddqq
do
TIIXXIEIETdt
dH
dt
d
IXXEdt
EdT
EIXXEdt
EdT
2
Two-Axis Model
20
No saturation
effects are
included
with this
model
![Page 21: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/21.jpg)
2 2
0 sin
0 cos
sin
cos
s e d q ep q d s vs
s e q d ep d q s vs
d e d ep q s vs
q e q ep d s vs
t d q
R R I X X I E V
R R I X X I E V
V R I X I V
V R I X I V
V V V
q
q
q
q
Two-Axis Model
21
![Page 22: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/22.jpg)
Example (Used for All Models)
• Below example will be used with all models. Assume a
100 MVA base, with gen supplying 1.0+j0.3286 power
into infinite bus with unity voltage through network
impedance of j0.22
– Gives current of 1.0 - j0.3286 = 1.0526-18.19
– Generator terminal voltage of 1.072+j0.22 = 1.0946 11.59
22
Infinite Bus
slack
X12 = 0.20
X13 = 0.10 X23 = 0.20
XTR = 0.10
Bus 1 Bus 2
Bus 3
0.00 Deg 6.59 Deg
Bus 4
1.0463 pu
11.59 Deg
1.0000 pu
1.0946 pu -100.00 MW
-32.86 Mvar
100.00 MW
57.24 Mvar
Sign convention on
current is out of the
generator is positive
![Page 23: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/23.jpg)
Two-Axis Example
• For the two-axis model assume H = 3.0 per unit-
seconds, Rs=0, Xd = 2.1, Xq = 2.0, X'd= 0.3, X'q = 0.5,
T'do = 7.0, T'qo = 0.75 per unit using the 100 MVA base.
• Solving we get
23
1.0946 11.59 2.0 1.0526 18.19 2.81 52.1
52.1
E j
0.7889 0.6146 1.0723 0.7107
0.6146 0.7889 0.220 0.8326
d
q
V
V
0.7889 0.6146 1.000 0.9909
0.6146 0.7889 0.3287 0.3553
d
q
I
I
Sign convention on
current is out of the
generator is positive
![Page 24: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/24.jpg)
Two-Axis Example
• And
24
0.8326 0.3 0.9909 1.130
0.7107 (0.5)(0.3553) 0.533
1.1299 (2.1 0.3)(0.9909) 2.913
q
d
fd
E
E
E
Saved as case B4_TwoAxis
![Page 25: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/25.jpg)
Two-Axis Example
• Assume a fault at bus 3 at time t=1.0, cleared by
opening both lines into bus 3 at time t=1.1 seconds
25
![Page 26: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/26.jpg)
Two-Axis Example
• PowerWorld allows the gen states to be easily stored.
26
Graph shows
variation in
Ed’
![Page 27: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/27.jpg)
Flux Decay Model
• If we assume T'qo is sufficiently fast then
27
dqo d q q q
q
do q d d d fd
s
M d d q q q d d q FW
s
M q q q d q q q d d q FW
M q q q d d q FW
dET E X X I 0
dt
dET E X X I E
dt
d
dt
2H dT E I E I X X I I T
dt
T X X I I E I X X I I T
T E I X X I I T
This model
assumes that
Ed’ stays constant.
In previous example
Tq0’=0.75
![Page 28: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/28.jpg)
Flux Decay Model
This model is no longer common
28
![Page 29: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/29.jpg)
Rotor Angle Sensitivity to Tqop
• Graph shows variation in the rotor angle as Tqop is
varied, showing the flux decay is same as Tqop = 0
29
![Page 30: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/30.jpg)
Classical Model
• Has been widely used, but most difficult to justify
• From flux decay model
• Or go back to the two-axis model and assume
30
0 0
q d do
q
X X T
E E
( const const)
q d do qo
q d
X X T T
E E
2 20 0
00 1
0tan 2
q d
q
d
E E E
E
E
![Page 31: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/31.jpg)
Or, argue that an integral manifold exists for
Rffddq VREEE ,,,, such that const.qE
const qdqd IXXE
2 20 0 0 0
0 1tan 2
d q d q qE E X X I E
Classical Model
31
![Page 32: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/32.jpg)
j δ-π 2d qI + jI e
32
Classical Model
dts
d
0
0
0
2sins
M vs FWd ep
H d E VT T
dt X X
q
This is a pendulum model
![Page 33: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/33.jpg)
Classical Model Response
• Rotor angle variation for same fault as before
33
Notice that
even though
the rotor
angle is
quite different,
its initial increase
(of about 24
degrees) is
similar. However
there is no
damping
![Page 34: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/34.jpg)
Subtransient Models
• The two-axis model is a transient model
• Essentially all commercial studies now use subtransient
models
• First models considered are GENSAL and GENROU,
which require X"d=X"q
• This allows the internal, subtransient voltage to be
represented as
34
( )sE V R jX I
d q q dE jE j
![Page 35: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/35.jpg)
Subtransient Models
• Usually represented by a Norton Injection with
• May also be shown as
35
q dd q
d q
s s
jE jEI jI
R jX R jX
q d d q
d q q d
s s
j j jj I jI I jI
R jX R jX
In steady-state = 1.0
![Page 36: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/36.jpg)
GENSAL
• The GENSAL model has been widely used to model
salient pole synchronous generators
– In the 2010 WECC cases about 1/3 of machine models were
GENSAL; in 2013 essentially none are, being replaced by
GENTPF or GENTPJ
– A 2014 series EI model had about 1/3 of its machines models
set as GENSAL
• In salient pole models saturation is only assumed to
affect the d-axis
36
![Page 37: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/37.jpg)
GENSAL Block Diagram
37
A quadratic saturation function is used. For
initialization it only impacts the Efd value
![Page 38: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/38.jpg)
GENSAL Example
• Assume same system as before with same common
generator parameters: H=3.0, D=0, Ra = 0, Xd = 2.1, Xq
= 2.0, X'd = 0.3, X"d=X"q=0.2, Xl = 0.13, T'do = 7.0, T"do
= 0.07, T"qo =0.07, S(1.0) =0, and S(1.2) = 0.
• Same terminal conditions as before
• Current of 1.0-j0.3286 and generator terminal voltage of
1.072+j0.22 = 1.0946 11.59
• Use same equation to get initial
38
1.072 0.22 (0.0 2)(1.0 0.3286)
1.729 2.22 2.81 52.1
s qE V R jX I
j j j
j
Same delta as
with the other
models
![Page 39: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/39.jpg)
GENSAL Example
• Then as before
And
39
( )
1.072 0.22 (0 0.2)(1.0 0.3286)
1.138 0.42
sV R jX I
j j j
j
0.7889 0.6146 1.0723 0.7107
0.6146 0.7889 0.220 0.8326
d
q
V
V
0.7889 0.6146 1.000 0.9909
0.6146 0.7889 0.3287 0.3553
d
q
I
I
![Page 40: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/40.jpg)
GENSAL Example
• Giving the initial fluxes (with = 1.0)
• To get the remaining variables set the differential
equations equal to zero, e.g.,
40
0.7889 0.6146 1.138 0.6396
0.6146 0.7889 0.420 1.031
q
d
2 0.2 0.3553 0.6396
1.1298, 0.9614
q q q q
q d
X X I
E
Solving the d-axis requires solving two linear
equations for two unknowns
![Page 41: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/41.jpg)
GENSAL Example
41
0.4118
0.5882
0.17
Id=0.9909
d”=1.031
1.8
Eq’=1.1298d’=0.9614
3.460
Efd = 1.1298+1.8*0.991=2.912
![Page 42: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/42.jpg)
Comparison Between Gensal and
Flux Decay
42
![Page 43: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/43.jpg)
Nonlinear Magnetic Circuits
• Nonlinear magnetic models are needed because
magnetic materials tend to saturate; that is, increasingly
large amounts of current are needed to increase the flux
density
43
dt
dN
dt
dv
R
0
Linear Li
![Page 44: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/44.jpg)
Saturation
44
![Page 45: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/45.jpg)
Saturation Models
• Many different models exist to represent saturation
– There is a tradeoff between accuracy and complexity
• Book presents the details of fully considering saturation
in Section 3.5
• One simple approach is to replace
• With
45
'
' '
'
1( )
q
q d d d fd
do
dEE X X I E
dt T
'
' ' '
'
1( ) ( )
q
q d d d q fd
do
dEE X X I Se E E
dt T
![Page 46: ECEN 667 Power System Stability - Thomas Overbyeoverbye.engr.tamu.edu/wp-content/uploads/sites/146/20… · · 2017-10-18ECEN 667 Power System Stability 1 Lecture 9: Synchronous](https://reader034.fdocuments.us/reader034/viewer/2022042513/5ae2db337f8b9a7b218c63ad/html5/thumbnails/46.jpg)
Saturation Models
• In steady-state this becomes
• Hence saturation increases the required Efd to get a
desired flux
• Saturation is usually modeled using a quadratic
function, with the value of Se specified at two points
(often at 1.0 flux and 1.2 flux)
46
' ' '( ) ( )fd q d d d qE E X X I Se E
2
2
( )
( )An alternative model is
q
q
q
Se B E A
B E ASe
E
A and B are
determined from
the two data
points