Earth Fault Relay Settings

download Earth Fault Relay Settings

of 5

description

Ground fault Relay Instruction

Transcript of Earth Fault Relay Settings

  • #1

    Previous in Forum: DROOP Next in Forum: Photo Diodes

    Anonymous

    Poster Earth Fault Relay Settings

    03/31/2010 12:19 AM

    Hi All,

    I have newly joined a 33/11 KV sub-station as a maintenence engineer(as a

    trainee),one thing i noticed there is the overcurrent relay settings(the TMS

    and plug settings) for the phase over current unit is different for the different

    LVs of different feeders,but the earth fault unit settings is same for all the

    feeder LVs i.e the time multiplier is set at 0.03 and plug setting is 25% of the

    rated tab.

    Can anyone explain me the reason.

    Thanks in advance

    Interested in this topic? By joining CR4 you can "subscribe" to

    this discussion and receive notification when new comments are added.

    Join CR4, The Engineer's Place for News and Discussion!

    Comments rated to be "almost" Good Answers:Check out these comments that don't yet have enough votes to be "official" good answers and, if you agree withthem, rate them!

    #1 "Re: Earth Fault Relay Settings" by wareagle on 03/31/2010 9:12 PM (score 1)

    wareagleGuru

    Join Date: Jun 2008Location: AlabamaPosts: 1561Good Answers: 59

    Re: Earth Fault Relay Settings03/31/2010 9:12 PM

    The earth/ground fault relay setting has nothing to do with the phase setting.

    You may have a phase setting of 600, 800 or 1200 amps. This setting is

    dependent on the transformer capacity,load, phase conductor ampacity and

    other criteria. The earth/ground relay is set at a much lower setting such as

    250 amps. The actual earth fault is much lower that a 3 phase fault and the

    relay must be able to detect this low ampacity.

    No more "Almost" Good Answers.

    The Engineer's Place for News and Discussion Login | Register

    CR4 - Thread: Earth Fault Relay Settings http://cr4.globalspec.com/thread/52648/earth-fault-relay-settings

    1 of 5 6/20/2013 1:42 PM

  • #2In reply to #1

    #3

    #4

    #5In reply to #4

    Anonymous

    Poster Re: Earth Fault Relay Settings

    03/31/2010 11:51 PM

    I agree. I think your feeder over current relay is set to control the over load

    problem.

    SABNAVEESActive Contributor

    Join Date: Nov 2008Posts: 23

    Re: Earth Fault Relay Settings04/01/2010 3:06 AM

    The O/C setting depends on the Transformer rating & also the full load of the

    system. E/F relay setting has nothing to do with the O/C relay setting. its

    always advisable to set the E/F relay setting at the minimum as possible to

    avoid system instability because of heavy inrush current due to any earth

    fault.

    SHAMITHGAMBHIR1Power-User

    Join Date: Feb 2010Location: dubai,mangalore,bangalore.....Posts: 149Good Answers: 8

    Re: Earth Fault Relay Settings04/01/2010 4:12 AM

    oc relay settings depends on the different loads on different feeders .An

    overcurent relay is essentially a sensor that is connected between the

    power supply and the load and upon the detection of a overcurrent

    condition due to overloads or other electrical faults, disconnects the

    load from the power supply. An oc relay is usually designed to operate

    over a wide range of values and the user must set the trip current

    based upon the specifications of the loads in the feeder circuit where as

    the neutral wire of all feeders are connected to one common earth. so

    earth fault settings r similar for all feeders. let me explain you in detail

    abt earth fault.

    During balanced conditions, current through the neutral is 0. If there is

    an unbalanced fault (one phase or two phase to ground fault) the

    current through neutral is no longer zero . Presence of current in the

    neutral indicates that there is a fault present.So the ground relays can

    be set to low value to detect this current.

    __________________

    shamith gambhir, electrical engineer

    JansCommentator

    Join Date: Feb 2009Location: Tamil NaduPosts: 60

    Re: Earth Fault Relay Settings04/01/2010 10:41 AM

    idmt relays are generally non unit type protection- ie it may operate for

    faults out side the intended zones. it is an advantage and disadvantage.

    advantage-it can be set for back up.disadvantage-it has to be co ordinated

    hence may have to be time dalayed. since the positive sequence impedance

    is continuous and omnipresent phase fault relays usually have to be set

    higher to grade with starting currents of motors for example..zero sequence

    circuits get a break whenever a delta star trafo.is encounterd.hence grading

    can start a fresh at each discontinuity and e/f relays as such can be set

    usually set more sensitive.they have to grade only with fewer sections and

    spill currents. it is also incidentally more advantageous since earth faults

    CR4 - Thread: Earth Fault Relay Settings http://cr4.globalspec.com/thread/52648/earth-fault-relay-settings

    2 of 5 6/20/2013 1:42 PM

  • #6

    #8In reply to #6

    #9In reply to #8

    give rise to step and touch potentials communication interference ....with

    numerical relays one can easily build up interlocking hence the time settings

    can be small

    __________________

    Better not count the cent if the risk is many many dollars.

    Panneer

    SelvamCommentator

    Join Date: Jul 2009Location: chennai, IndiaPosts: 55Good Answers: 1

    Re: Earth Fault Relay Settings04/01/2010 12:48 PM

    Dear Guest, Different feeders can have different Phase current setting based

    on the size of cable and maximum permissible load current in that feeder.For

    example , Four feeders in a station may have over-current settings of 400A

    for three feeders and 300A for one feeder.The Over current relay will operate

    whenever the Fault current or load current exceeds this setting .

    Suppose in a feeder with setting 400A setting. There is a load current of 200A

    and ther accurs an earth fault of 100A ,the phase fault relay will not operate

    as the total current is lessthan the the set value for phase fault relay and

    therefore an E/F relay is required which is sensittive to clear such faults

    This is the purpose for which the E/F relay is included in the 11KV feeder

    protection scheme .

    The E/F relay will have current flow, only when there is an earth fault .That is

    why it possible to set E/F relay at minimum possible setting.

    That is the reason Why when phase fault protection settings are different for

    various feeder, the earth Fault relay is set at a minimum possible setting

    commonly in all the feeders

    The minimum setting is normally decided considering following factors 1)The

    burden of relay at set plug setting 2) The CT ratio adopted 3) The 11 KV fault

    level of Station 4) The Knee point Voltage of the CTS connected 5) The

    normal service leakage current, Etc

    Dont hesitste ask, if the above explanation not cleared your doubts .

    __________________

    There is nothing either good or bad, only thinking make it so -

    Anonymous

    Poster Re: Earth Fault Relay Settings

    07/05/2010 8:06 AM

    sir,

    I want to know the time Vs current retting setting.

    Say load current750 A, what willbe the earth fault current setting & its time

    to tripping. Also over current relay setting(current and time).

    How time setting is calculated

    Panneer Re: Earth Fault Relay Settings08/02/2010 6:27 AM

    CR4 - Thread: Earth Fault Relay Settings http://cr4.globalspec.com/thread/52648/earth-fault-relay-settings

    3 of 5 6/20/2013 1:42 PM

  • #7

    #10

    Reply to Forum Thread

    SelvamCommentator

    Join Date: Jul 2009Location: chennai, IndiaPosts: 55Good Answers: 1

    The over current relay 's time and current settins are designed to follow

    international standards, For example , the IEC curves are designed as

    follows

    t = TMS x 0.14 / (Ir power 0.02 - 1 )

    This is standard inverse Charecteristic is for 10/ 3 Sec curve

    Suppose You Have 1000/1 Amp CT and you want this relay to be

    set at 750 A, then you have to select 75% current setting or 0.75 A

    settings

    The time delay can be set in two different ways. You can have an external

    timer to trigger tripping as per the time delay intended.

    If the relay have designed operating characteristic like the one shown

    above,then you can set the time of opration by setting suitable TMS. For

    this you must Know the fault current

    Then Ir will be = Fault Current / (CT ratio x current setting )

    For example if you want a tripping ting time of 200ms, and the fault

    current expected is 3500A

    The equation to be solved is 0.2 = TMS x 0.14 / ( 3500 / (1000x 0.75) to

    the power of 0.02 - 1 )

    The above is Over current setting.

    For earth fault setting you can adopt 20 % as current setting and 0.05 as

    time lever setting

    __________________

    There is nothing either good or bad, only thinking make it so -

    rajukailasActive Contributor

    Join Date: Dec 2009Posts: 14

    Re: Earth Fault Relay Settings04/02/2010 9:27 AM

    Dear sir

    where are u working. You can go for lower setting.

    raju

    Anonymous

    Poster

    Re: Earth Fault Relay Settings02/01/2011 9:28 PM

    10 comments

    Back to top

    Interested in this topic? By joining CR4 you can "subscribe" to

    this discussion and receive notification when new comments are added.

    Join CR4, The Engineer's Place for News and Discussion!

    Comments rated to be "almost" Good Answers:Check out these comments that don't yet have enough votes to be "official" good answers and, if you agree with

    CR4 - Thread: Earth Fault Relay Settings http://cr4.globalspec.com/thread/52648/earth-fault-relay-settings

    4 of 5 6/20/2013 1:42 PM

  • Copy to Clipboard

    them, rate them!

    #1 "Re: Earth Fault Relay Settings" by wareagle on 03/31/2010 9:12 PM (score 1)

    Users who posted comments:

    Anonymous Poster (3); Jans (1); Panneer Selvam (2); rajukailas (1); SABNAVEES (1);

    SHAMITHGAMBHIR1 (1); wareagle (1)

    Previous in Forum: DROOP Next in Forum: Photo Diodes

    You might be interested in: Relay Boards (Multiple Relay Modules), Fault Detectors and Recorders,

    Fiber Optic Fault Locators

    "He who overcomes others has force; he who overcomes himself is strong." -- Lao-tzu, Chinese

    philosopher

    All times are displayed in US/Eastern (EDT) (Register to change time zone)

    2013 IHS.GlobalSpec, the GlobalSpec logo, SpecSearch, the Engineering Web,

    the Engineering Search Engine, CR4 and Conference Room 4 are registered trademarks of IHS.All other company and product names may be trademarks of their respective owners. No portionof this site may be copied, retransmitted, reposted, duplicated or otherwise used without the

    express written permission of IHS GlobalSpec, 30 Tech Valley Dr. Suite 102, East Greenbush, NY, 12061

    CR4 - Thread: Earth Fault Relay Settings http://cr4.globalspec.com/thread/52648/earth-fault-relay-settings

    5 of 5 6/20/2013 1:42 PM