DSE4410/20 AUTO START & AUTO MAINS FAILURE CONTROL MODULES DSEGenset ® 1ph 2ph 3ph N 1ph 2ph 3ph N 4 2 PC VOLTS 3 + DEUTZ ISUZU PERKINS CATERPILLAR MTU VOLVO CUMMINS SCANIA D + W/L GENERATOR SENSING VOLTS USB PORT CONFIGURABLE INPUTS DC OUTPUTS ANALOGUE SENDERS DC POWER SUPPLY 8-35V ELECTRONIC ENGINES OR MAGNETIC PICK-UP FUEL & CRANK OUTPUTS (Flexible with CAN) CHARGE ALTERNATOR MAINS (UTILITY) SENSING DSE4420 ONLY ISSUE 4 + 1 1 DC OUTPUTS COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETY OF GEN-SET APPLICATIONS 7 OTHER DSE4410/20 + + The DSE4410 is an Auto Start Control Module and the DSE4420 is an Auto Mains (Utility) Failure Control Module with 3 phase sensing, suitable for a wide variety of single, diesel or gas, gen-set applications. Monitoring, speed, frequency, voltage, oil pressure, coolant temperature and fuel level, the modules will display warnings, shutdown and engine status information on the back-lit LCD screen and illuminated LED. Both modules offer electronic (CAN) and non-electronic (magnetic pick-up/alternator sensing) engine versions and offer a number of flexible inputs, outputs and engine protections so the system can be easily adapted to suit a wide range of application demands. The modules can be easily configured using the DSE Configuration Suite PC software. Selected front panel editing is also available. FEATURES ENVIRONMENTAL TESTING STANDARDS ELECTRO-MAGNETIC COMPATIBILITY BS EN 61000-6-2 EMC Generic Immunity Standard for the Industrial Environment BS EN 61000-6-4 EMC Generic Emission Standard for the Industrial Environment ELECTRICAL SAFETY BS EN 60950 Safety of Information Technology Equipment, including Electrical Business Equipment TEMPERATURE BS EN 60068-2-1 Ab/Ae Cold Test -30 o C BS EN 60068-2-2 Bb/Be Dry Heat +70 o C VIBRATION BS EN 60068-2-6 Ten sweeps in each of three major axes 5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn HUMIDITY BS EN 60068-2-30 Db Damp Heat Cyclic 20/55 o C @ 95% RH 48 Hours BS EN 60068-2-78 Cab Damp Heat Static 40 o C @ 93% RH 48 Hours SHOCK BS EN 60068-2-27 Three shocks in each of three major axes 15 gn in 11 mS DEGREES OF PROTECTION PROVIDED BY ENCLOSURES BS EN 60529 IP65 - Front of module when installed into the control panel with the supplied sealing gasket.

description

http://www.esgon-ce.es/files/Deep/dse4410-20-data-sheet.pdf

Transcript of dse4410-20-data-sheet

Page 1: dse4410-20-data-sheet

DSE4410/20AUTO START & AUTO MAINS FAILURECONTROL MODULES

DSEGenset

®

1ph2ph3phN

1ph2ph3phN

4 2

PC

VOLTS

3

+

DEUTZISUZUPERKINSCATERPILLARMTUVOLVOCUMMINSSCANIA

D +W/L

GENERATORSENSING

VOLTS

USBPORT

CONFIGURABLEINPUTS

DC OUTPUTS ANALOGUESENDERS

DC POWER SUPPLY 8-35V

ELECTRONICENGINES ORMAGNETIC PICK-UP

FUEL & CRANKOUTPUTS(Flexible with CAN)

CHARGEALTERNATOR

MAINS (UTILITY) SENSINGDSE4420 ONLY

ISSUE 4

+

1 1

DC OUTPUTS

COMPREHENSIVE FEATURE LIST TO SUIT AWIDE VARIETY OF GEN-SET APPLICATIONS

7

OTHER

DSE4410/20

++

The DSE4410 is an Auto StartControl Module and the DSE4420is an Auto Mains (Utility) FailureControl Module with 3 phasesensing, suitable for a wide varietyof single, diesel or gas, gen-setapplications.

Monitoring, speed, frequency,voltage, oil pressure, coolanttemperature and fuel level, themodules will display warnings,shutdown and engine statusinformation on the back-lit LCDscreen and illuminated LED.

Both modules offer electronic(CAN) and non-electronic (magneticpick-up/alternator sensing) engineversions and offer a number offlexible inputs, outputs and engineprotections so the system can beeasily adapted to suit a wide rangeof application demands.

The modules can be easilyconfigured using the DSEConfiguration Suite PC software.Selected front panel editing is alsoavailable.

FEATURES

ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITYBS EN 61000-6-2EMC Generic Immunity Standard for the Industrial EnvironmentBS EN 61000-6-4EMC Generic Emission Standard for the Industrial Environment

ELECTRICAL SAFETYBS EN 60950Safety of Information Technology Equipment, including Electrical Business Equipment

TEMPERATUREBS EN 60068-2-1Ab/Ae Cold Test -30 oCBS EN 60068-2-2Bb/Be Dry Heat +70 oC

VIBRATIONBS EN 60068-2-6Ten sweeps in each of three major axes5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn

HUMIDITYBS EN 60068-2-30Db Damp Heat Cyclic 20/55 oC@ 95% RH 48 HoursBS EN 60068-2-78Cab Damp Heat Static 40 oC@ 93% RH 48 Hours

SHOCKBS EN 60068-2-27Three shocks in each of three major axes15 gn in 11 mS

DEGREES OF PROTECTIONPROVIDED BY ENCLOSURESBS EN 60529IP65 - Front of module when installed into thecontrol panel with the supplied sealing gasket.

Page 2: dse4410-20-data-sheet

DEEP SEA ELECTRONICS PLC UKHighfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PHTELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303EMAIL [email protected] WEBSITE www.deepseaplc.com

DEEP SEA ELECTRONICS INC USA3230 Williams Avenue, Rockford, IL 61101-2668 USATELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708EMAIL [email protected] WEBSITE www.deepseausa.com

055-068/08/10 (4)

KEY FEATURES• CAN and magnetic pick-up/Alt.sensing versions (specify onordering)

• 3 phase generator monitoring• Four digital inputs/threeanalogue inputs

• Six outputs (all six configurableon CANbus version, fourconfigurable on magnetic pick-up version)

• Three phase sensing• Event log (5)• 50/60 Hz calibration setting• Configurable timers• Automatic shutdown or warningwhen fault conditions aredetected

• Overspeed protection• Manual and remote start

• Engine pre-heat• Protected Solid State Outputs(PSS)

• Advanced metering capability• Front panel/PC programming• Hours counter• LED indicators• Back-lit character icon LCDdisplay

KEY BENEFITS• Automatically transfers betweenmains (utility) and generatorpower (DSE4420 only)

• Hours counter providesaccurate information formonitoring and maintenanceperiods

• User-friendly set-up and buttonlayout

• Multiple engine parametersare monitored simultaneously

• Module can be configured tosuit individual applications

• Compatible with a wide rangeof CAN engines

• IP65 rating offers advancedresistance to water ingresswhen the gasket is fitted

• License-free PC software.

RELATED MATERIALSTITLE PART NO’SDSE4410 Installation Instructions 053-078DSE4420 Installation Instructions 053-079DSE4400 Quick Start Guide 057-103DSE4400 Operator Manual 057-111DSE4400 Configuration Suite PC Manual 057-093

SPECIFICATION

DC SUPPLYCONTINUOUS VOLTAGE RATING8 V to 35 V Continuous

CRANKING DROPOUTSAble to survive 0 V for 50 mS, providing supply was at least 10V before dropout and supply recovers to 5 V. This is achievedwithout the need for internal batteries. LEDsand backlight will not be maintained duringcranking.

MAXIMUM OPERATING CURRENT150 mA at 12 V, 80 mA at 24 V

MAXIMUM STANDBY CURRENT50 mA at 12 V, 30 mA at 24 V

CHARGE FAIL/EXCITATION RANGE0 V to 35 V

MAGNETIC PICK UPVOLTAGE RANGE+/- 0.5 V to 70 V

FREQUENCY RANGE10,000 Hz (max)

OUTPUTSOUTPUT A (FUEL)2 Amp DC at supply voltage

OUTPUT B (START)2 Amp DC at supply voltage

AUXILIARY OUTPUTS C,D,E,F2 Amp DC at supply voltage

MAINS (UTILITY) DSE74420 ONLYVOLTAGE RANGE15 V - 333 V AC (L-N)

FREQUENCY RANGE3.5 Hz to 75 Hz

GENERATORVOLTAGE RANGE 15 V - 333 V AC (L-N)

FREQUENCY RANGE3.5 Hz to 75 Hz

DIMENSIONSOVERALL180 mm x 116 mm x 42 mm7.1” x 4.6” x 1.7”

PANEL CUT-OUT154 mm x 98 mm6” x 3.9”

MAXIMUM PANEL THICKNESS8 mm (0.3”)

DSE4410/20AUTO START & AUTO MAINS FAILURECONTROL MODULES

®

DSEGenset

DSE4410

DSE4420

Registered in England & Wales No.01319649VAT No.316923457

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to changethe details shown on this data sheet without prior notice. The contents are intended for guidance only.

FEATURES