dse4410-20-data-sheet
description
Transcript of dse4410-20-data-sheet
DSE4410/20AUTO START & AUTO MAINS FAILURECONTROL MODULES
DSEGenset
®
1ph2ph3phN
1ph2ph3phN
4 2
PC
VOLTS
3
+
DEUTZISUZUPERKINSCATERPILLARMTUVOLVOCUMMINSSCANIA
D +W/L
GENERATORSENSING
VOLTS
USBPORT
CONFIGURABLEINPUTS
DC OUTPUTS ANALOGUESENDERS
DC POWER SUPPLY 8-35V
ELECTRONICENGINES ORMAGNETIC PICK-UP
FUEL & CRANKOUTPUTS(Flexible with CAN)
CHARGEALTERNATOR
MAINS (UTILITY) SENSINGDSE4420 ONLY
ISSUE 4
+
1 1
DC OUTPUTS
COMPREHENSIVE FEATURE LIST TO SUIT AWIDE VARIETY OF GEN-SET APPLICATIONS
7
OTHER
DSE4410/20
++
The DSE4410 is an Auto StartControl Module and the DSE4420is an Auto Mains (Utility) FailureControl Module with 3 phasesensing, suitable for a wide varietyof single, diesel or gas, gen-setapplications.
Monitoring, speed, frequency,voltage, oil pressure, coolanttemperature and fuel level, themodules will display warnings,shutdown and engine statusinformation on the back-lit LCDscreen and illuminated LED.
Both modules offer electronic(CAN) and non-electronic (magneticpick-up/alternator sensing) engineversions and offer a number offlexible inputs, outputs and engineprotections so the system can beeasily adapted to suit a wide rangeof application demands.
The modules can be easilyconfigured using the DSEConfiguration Suite PC software.Selected front panel editing is alsoavailable.
FEATURES
ENVIRONMENTAL TESTING STANDARDS
ELECTRO-MAGNETIC COMPATIBILITYBS EN 61000-6-2EMC Generic Immunity Standard for the Industrial EnvironmentBS EN 61000-6-4EMC Generic Emission Standard for the Industrial Environment
ELECTRICAL SAFETYBS EN 60950Safety of Information Technology Equipment, including Electrical Business Equipment
TEMPERATUREBS EN 60068-2-1Ab/Ae Cold Test -30 oCBS EN 60068-2-2Bb/Be Dry Heat +70 oC
VIBRATIONBS EN 60068-2-6Ten sweeps in each of three major axes5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn
HUMIDITYBS EN 60068-2-30Db Damp Heat Cyclic 20/55 oC@ 95% RH 48 HoursBS EN 60068-2-78Cab Damp Heat Static 40 oC@ 93% RH 48 Hours
SHOCKBS EN 60068-2-27Three shocks in each of three major axes15 gn in 11 mS
DEGREES OF PROTECTIONPROVIDED BY ENCLOSURESBS EN 60529IP65 - Front of module when installed into thecontrol panel with the supplied sealing gasket.
DEEP SEA ELECTRONICS PLC UKHighfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PHTELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303EMAIL [email protected] WEBSITE www.deepseaplc.com
DEEP SEA ELECTRONICS INC USA3230 Williams Avenue, Rockford, IL 61101-2668 USATELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708EMAIL [email protected] WEBSITE www.deepseausa.com
055-068/08/10 (4)
KEY FEATURES• CAN and magnetic pick-up/Alt.sensing versions (specify onordering)
• 3 phase generator monitoring• Four digital inputs/threeanalogue inputs
• Six outputs (all six configurableon CANbus version, fourconfigurable on magnetic pick-up version)
• Three phase sensing• Event log (5)• 50/60 Hz calibration setting• Configurable timers• Automatic shutdown or warningwhen fault conditions aredetected
• Overspeed protection• Manual and remote start
• Engine pre-heat• Protected Solid State Outputs(PSS)
• Advanced metering capability• Front panel/PC programming• Hours counter• LED indicators• Back-lit character icon LCDdisplay
KEY BENEFITS• Automatically transfers betweenmains (utility) and generatorpower (DSE4420 only)
• Hours counter providesaccurate information formonitoring and maintenanceperiods
• User-friendly set-up and buttonlayout
• Multiple engine parametersare monitored simultaneously
• Module can be configured tosuit individual applications
• Compatible with a wide rangeof CAN engines
• IP65 rating offers advancedresistance to water ingresswhen the gasket is fitted
• License-free PC software.
RELATED MATERIALSTITLE PART NO’SDSE4410 Installation Instructions 053-078DSE4420 Installation Instructions 053-079DSE4400 Quick Start Guide 057-103DSE4400 Operator Manual 057-111DSE4400 Configuration Suite PC Manual 057-093
SPECIFICATION
DC SUPPLYCONTINUOUS VOLTAGE RATING8 V to 35 V Continuous
CRANKING DROPOUTSAble to survive 0 V for 50 mS, providing supply was at least 10V before dropout and supply recovers to 5 V. This is achievedwithout the need for internal batteries. LEDsand backlight will not be maintained duringcranking.
MAXIMUM OPERATING CURRENT150 mA at 12 V, 80 mA at 24 V
MAXIMUM STANDBY CURRENT50 mA at 12 V, 30 mA at 24 V
CHARGE FAIL/EXCITATION RANGE0 V to 35 V
MAGNETIC PICK UPVOLTAGE RANGE+/- 0.5 V to 70 V
FREQUENCY RANGE10,000 Hz (max)
OUTPUTSOUTPUT A (FUEL)2 Amp DC at supply voltage
OUTPUT B (START)2 Amp DC at supply voltage
AUXILIARY OUTPUTS C,D,E,F2 Amp DC at supply voltage
MAINS (UTILITY) DSE74420 ONLYVOLTAGE RANGE15 V - 333 V AC (L-N)
FREQUENCY RANGE3.5 Hz to 75 Hz
GENERATORVOLTAGE RANGE 15 V - 333 V AC (L-N)
FREQUENCY RANGE3.5 Hz to 75 Hz
DIMENSIONSOVERALL180 mm x 116 mm x 42 mm7.1” x 4.6” x 1.7”
PANEL CUT-OUT154 mm x 98 mm6” x 3.9”
MAXIMUM PANEL THICKNESS8 mm (0.3”)
DSE4410/20AUTO START & AUTO MAINS FAILURECONTROL MODULES
®
DSEGenset
DSE4410
DSE4420
Registered in England & Wales No.01319649VAT No.316923457
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to changethe details shown on this data sheet without prior notice. The contents are intended for guidance only.
FEATURES