dennisbuilding.com.audennisbuilding.com.au/img/download/04 Drawings...a3 not to scale plans &...
Transcript of dennisbuilding.com.audennisbuilding.com.au/img/download/04 Drawings...a3 not to scale plans &...
SCALE :
PROJECT MGR :
DATE :
DRAWN :
DRG SIZE :
DESIGN :
WWW.JONESNICHOLSON.COM.AU
THE CONCEPTS AND INFORMATION CONTAINED IN THEDOCUMENT ARE THE COPYRIGHT OF JONES NICHOLSONPty. Ltd. USE OR COPYING OF THE DOCUMENT WITHOUTWRITTEN PERMISSION OF JONES NICHOLSON Pty. Ltd.CONSTITUTES AN INFRINGEMENT OF COPYRIGHT STRUCTURAL DESIGN
ABN: 51 003 316 032CIVIL STRUCTURAL BUILDING SERVICES. .
LAND & HOUSING
CORPORATION
NOV '14
GS
GS
GS
A3NOT TO SCALE
PLANS &DETAILS
Elizabeth St, Kettle & Walker St. 130277
GENERAL
1. THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL ARCHITECTURAL
AND OTHER CONSULTANTS' DRAWINGS AND SPECIFICATION AND WITH SUCH
OTHER WRITTEN INSTRUCTION AS MAY BE ISSUED DURING THE COURSE OF
THE CONTRACT. ANY DISCREPANCY SHALL BE REFERRED TO THE
SUPERINTENDENT BEFORE PROCEEDING WITH THE WORK.
2. ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE
RELEVANT AND CURRENT AUSTRALIAN STANDARDS AND THE NATIONAL
CONSTRUCTION CODE SERIES EXCEPT WHERE VARIED BY THE PROJECT
SPECIFICATION.
3. ALL DIMENSIONS SHOWN SHALL BE VERIFIED BY THE BUILDER ON SITE.
ENGINEERS' DRAWINGS SHALL NOT BE SCALED FOR DIMENSIONS.
4. DURING CONSTRUCTION THE STRUCTURE SHALL BE MAINTAINED IN A STABLE
CONDITION AND NO PART SHALL BE OVERSTRESSED. TEMPORARY BRACING
SHALL BE PROVIDED BY THE BUILDER TO KEEP THE WORKS AND
EXCAVATIONS STABLE AT ALL TIMES.
5. THE BUILDER SHALL GIVE 48 HOURS NOTICE FOR ALL ENGINEERING
INSPECTIONS.
6. THE BUILDER SHALL LOCATE ALL EXISTING SERVICES PRIOR TO
COMMENCEMENT OF CONSTRUCTION. ENGINEER TO BE NOTIFIED.
7. UNLESS NOTED OTHERWISE ALL LEVELS ARE IN METRES AND ALL DIMENSIONS
ARE IN MILLIMETRES.
8. ALL PROPRIETY ITEMS TO BE INSTALLED IN ACCORDANCE WITH
MANUFACTURES SPECIFICATIONS & DETAILS.
FOUNDATIONS & EARTHWORKS
1. THIS FOUNDATION MATERIAL SHALL BE UNIFORM AND BE APPROVED BY A
GEOTECHNICAL ENGINEER FOR THE ALLOWABLE BEARING PRESSURE BEFORE
PLACING REINFORCEMENT OR CONCRETE. PIERS OR BLOCKDOWNS SHALL BE
USED TO ACHIEVE UNIFORM BEARING WHERE NECESSARY.
2. THIS SITE CLASS HAS BEEN DESIGNED IN ACCORDANCE WITH AS 2870
(WHERE APPLICABLE). CONFIRMATION OF SITE CLASSIFICATION IS REQUIRED
BY A GEOTECHNICAL ENGINEER PRIOR TO CONSTRUCTION COMMENCING ON
SITE.
3. FOOTINGS SHALL BE CONCRETED ON THE DAY OF APPROVAL UNLESS
PERMISSION IS GIVEN OTHERWISE.
4. FOOTINGS SHALL BE LOCATED CENTRALLY UNDER WALLS AND COLUMNS
UNLESS NOTED OTHERWISE.
5. BACKFILL TO RETAINING WALLS SHALL BE FREE DRAINING GRANULAR
MATERIAL. PROVIDE SUBSOIL DRAIN AT BASE OF WALL. DO NOT BACKFILL
UNTIL 14 DAYS AFTER CORE FILLING, OR IF APPLICABLE, AFTER RESTRAINING
SLAB OVER HAS BEEN POURED AND CURED FOR 7 DAYS. BACKFILL SHALL BE
COMPACTED TO 98% STANDARD MAXIMUM DRY DENSITY AT OPTIMUM
MOISTURE CONTENT ±2%.
6. FOOTING LEVELS WHERE SHOWN ARE ESTIMATES ONLY AND WILL BE
ESTABLISHED DURING SITE INSPECTION OF WORK IN PROGRESS.
7. PROVIDE ADEQUATE BATTERS OR SHORING TO THE SIDE OF ALL
EXCAVATIONS. REFER TO GEOTECHNICAL ENGINEER FOR RELEVANT ADVICE.
FOOTING
BEARING SURFACE
PIERS IF REQUIRED
2
1
EXCAVATION
I00
EXCAVATION IN ROCK
1. THE CONTRACTOR SHALL SUBMIT HIS PROPOSAL FOR EXCAVATION TO THE
SUPERINTENDENT PRIOR TO COMMENCEMENT OF WORK.
2. THE METHOD SHALL COMPLY WITH ALL THE REQUIREMENTS OF THE DA
CONDITIONS, PARTICULARLY IN RELATION TO NOISE LEVELS, VIBRATION AND
WORK HOURS.
3. VIBRATIONS SHALL NOT EXCEED THAT SPECIFIED IN THE GEOTECHNICAL
REPORT AND ALARMS SHALL BE INSTALLED TO MONITOR THESE
VIBRATIONS. U.N.O.
4. ALL THE REQUIREMENTS OF THE GEOTECHNICAL REPORT FOR THE SITE
SHALL BE OBSERVED AND MET.
CONTRACTOR DESIGNED PILES
1. THE PILES ARE TO BE DESIGNED, INSTALLED AND CERTIFIED BY THE
CONTRACTOR FOR THE LOADS INDICATED ON THE DRAWINGS.
2. THE DESIGN LIFE OF THE PILES IS TO BE A MINIMUM OF 50 YEARS UNLESS
NOTED OTHERWISE IN THE PROJECT INFORMATION TABLE.
3. DESIGN AND INSTALLATION OF PILES IS TO BE IN ACCORDANCE WITH AS2159
AND TO INCLUDE ALLOWANCE FOR INDUCED MOMENTS IN PILES DUE TO
CONSTRUCTION TOLERANCES.
INSITU BORED CONCRETE PILES
1. ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH
AS2159 PILING DESIGN & INSTALLATION CURRENT EDITIONS WITH
AMENDMENTS, EXCEPT WHERE VARIED BY THE CONTRACT DOCUMENTS.
2. ALL DESIGN AND INSTALLATION SHALL BE COMPLETED BY AN EXPERIENCED
CONTRACTOR SPECIALISING IN FOUNDATION ENGINEERING AND SHALL BE IN
ACCORDANCE WITH AS2159.SUBMIT DETAILS OF PROPOSED DRILLING
METHODS, EQUIPMENT AND SEQUENCE. GIVE NOTICE SO THAT INSPECTION
MAY BE MADE OF THE FOLLOWING AS APPLICABLE:
- AT COMPLETION OF EXCAVATION OF PIERS
- REINFORCEMENT OF PIER
3. SETTING OUT - PEG THE POSITION OF EACH PILE AND ESTABLISH A GRID
OF RECOVERY PEGS TO ENABLE THE SETTING OUT TO BE CHECKED AT ANY
TIME. PILES AND OR PIERS SHALL BE LOCATED WITHIN 75mm OF THE PLAN
LOCATIONS AS SHOWN ON THE ENGINEERING DRAWINGS.
4. PIERS SHALL BE POURED WITHIN 24 HOURS OF EXCAVATION UNLESS
OTHERWISE AGREED.
5. PIER WALL SHALL BE MAINTAINED STABLE PRIOR TO POURING CONCRETE.
6. PIER BASES SHALL BE LEVEL AND FREE OF ALL LOOSE MATERIAL.
7. REMOVE ALL FREE WATER FROM PIERS BEFORE POURING.
8. CONFIRM BEARING PRESSURE AT BASE OF ALL PIERS BY GEOTECHNICAL
TESTING/INSPECTIONS.
9. CONCRETE SHALL BE PLACED IN SUCH A MANNER SO AS TO AVOID
SEGREGATION.
10. REFER ALSO TO CONCRETE NOTES.
11. THE PILE DEPTHS SHOWN ON THE ENGINEERS DRAWINGS ARE PROVISIONAL.
ACTUAL PILE LENGTHS ARE TO BE MEASURED BY THE CONTRACTOR AND
APPROVED BY THE SUPERINTENDENT.
12. OBSERVE SAFE-WORKING PRACTICES, INCLUDING THE RELEVANT PRACTICES
RECOMMENDED IN AS2159 APPENDIX B.
13. PROVIDE & INSTALL FACILITIES NECESSARY FOR INSPECTION OF PILING
INCLUDING SAFE ACCESS, LIGHTING, VENTILATION AND THE LIKE.
14. REFER TO DRAWINGS FOR ALL OTHER PIER INFORMATION.
15. RECORD THE RELEVANT INFORMATION AS LISTED IN AS2159. AND FORWARD
TO ENGINEER/SUPERINTENDENT COPIES OF EACH RECORD TO THE
SUPERINTENDENT.
16. PROVIDE A SURVEY OF ALL PILES/PIERS AFTER INSTALLATION INCLUDING
THE LENGTH FROM THE UNDERSIDE OF THE PILE CAP OR FOUNDATION,
BEAM TO THE TOE OF THE PILE/PIER AND THE LEVEL OF THE
SURROUNDING GROUND AT THE TIME WHEN THE PILE IS INSTALLED.
TEMPORARY ANCHORS AND ROCKBOLTS
1. TEMPORARY GROUND ANCHORS AND ROCKBOLTS ARE TO BE DESIGNED,
INSTALLED, TESTED AND CERTIFIED BY THE CONTRACTOR FOR THE LOADS
INDICATED ON THE DRAWINGS.
2. THE DESIGN LIFE OF THE TEMPORARY ANCHORS IS TO BE A MINIMUM OF 2
YEARS UNLESS NOTED OTHERWISE.
3. PROVIDE DESIGN DETAILS, INSTALLATION METHOD STATEMENTS AND TESTING
PROPOSAL TO ENGINEER FOR REVIEW BEFORE COMMENCING ON SITE.
4. CONTRACTORS DESIGN TO INCLUDE ALL PARTS OF THE GROUND ANCHORS,
ANCHOR HEADS AND BEARING PLATES ETC.
5. ANCHORS ARE TO BE INSTALLED WITH THE RESIDUAL LOAD AS SPECIFIED ON
THE DRAWINGS. IF NO RESIDUAL LOAD IS STATED, REQUEST CLARIFICATION
FROM THE ENGINEER.
6. REFER TO GEOTECHNICAL REPORT FOR DESIGN PARAMETERS.
CONCRETE
1. ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS
3600 AND AS 3610 CURRENT EDITIONS WITH AMENDMENTS, EXCEPT WHERE
VARIED BY THE CONTRACT DOCUMENTS.
2. PROJECT CONTROL TESTING SHALL BE CARRIED OUT IN ACCORDANCE WITH
AS 3600.
3. CONCRETE TO BE PROPORTIONED TO LIMIT DRYING SHRINKAGE TO SATISFY
PROJECT INFORMATION TABLE.
4. NO ADMIXTURES SHALL BE USED IN CONCRETE UNLESS APPROVED IN
WRITING.
5. CLEAR CONCRETE COVER TO ALL REINFORCEMENT SHALL BE AS NOTED IN
THE PROJECT INFORMATION TABLE UNLESS SHOWN OTHERWISE.
6. WHERE CONCRETE IS POURED ON A VAPOUR PROOF MEMBRANE 0.2mm
MINIMUM THICKNESS, THE COVER TO CONCRETE CAST AGAINST GROUND MAY
BE REDUCED BY 10mm.
7. CONCRETE SIZES SHOWN DO NOT INCLUDE THICKNESS OF APPLIED FINISHES.
NO FINISH WHICH DECREASES COVER IS ALLOWED WITHOUT THE WRITTEN
APPROVAL OF THE ENGINEER.
8. DEPTHS OF BEAMS ARE GIVEN FIRST AND INCLUDE SLAB THICKNESS.
9. FOR CHAMFERS DRIP GROOVES, REGLETS, ETC. REFER TO ARCHITECT'S
DETAILS. MAINTAIN COVER TO REINFORCEMENT AT THESE DETAILS.
10. NO HOLES, CHASES, BLOCKOUTS, DUCTS OR EMBEDMENT OF PIPES OTHER
THAN THOSE SHOWN ON THE STRUCTURAL DRAWINGS SHALL BE MADE IN
CONCRETE MEMBERS WITHOUT THE PRIOR WRITTEN APPROVAL OF THE
ENGINEER.
11. CONSTRUCTION JOINTS WHERE NOT SHOWN SHALL BE LOCATED TO THE
APPROVAL OF THE ENGINEER.
12. ALL CONCRETE COLUMNS GREATER THAN 1.2 METRES IN HEIGHT SHALL BE
POURED A MINIMUM OF 4 HOURS PRIOR TO SLAB OR BEAM OVER.
13. CONCRETE SHALL BE MECHANICALLY VIBRATED TO ACHIEVE A DENSE
HOMOGENEOUS MASS COMPLETELY FILLING THE FORMWORK THOROUGHLY
EMBEDDING THE REINFORCEMENT AND FREE OF STONE POCKETS OR VOIDS.
ALL CONCRETE INCLUDING SLABS ON GROUND AND FOOTINGS SHALL BE
COMPACTED WITH MECHANICAL VIBRATORS.
14. CURING OF ALL CONCRETE IS TO BE ACHIEVED BY KEEPING SURFACES
CONTINUOUSLY WET FOR A PERIOD OF THREE DAYS, AND THE PREVENTION
OF LOSS OF MOISTURE FOR A TOTAL OF 7 DAYS FOLLOWED BY A
GRADUAL DRYING OUT. CURING COMPOUNDS MAY BE USED BUT MUST BE
COMPATIBLE WITH THE PROPOSED FLOOR FINISHED & BE INSTALLED IN
ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS. POLYTHENE SHEETING
OR WET HESSIAN MAY BE USED IF PROTECTED FROM WIND AND TRAFFIC.
15. CONSTRUCTION SUPPORT PROPPING IS TO BE LEFT IN PLACE WHERE
NEEDED TO AVOID OVERSTRESSING THE STRUCTURE DUE TO CONSTRUCTION
LOADING. NO BRICKWORK OR PARTITION WALLS ARE TO BE CONSTRUCTED
ON SUSPENDED LEVELS UNTIL SEVEN DAYS AFTER PROPPING HAS BEEN
REMOVED AND THE SLAB PRE-LOADED WITH THE BRICKS OR UNITS TO BE
USED IN THE WALL.
16. REPAIRS TO CONCRETE SHALL NOT BE ATTEMPTED WITHOUT THE
PERMISSION OF THE ENGINEER.
17. CAST-IN FIXINGS, BOLTS ETC. SHALL NOT BE ALTERED WITHOUT THE
PERMISSION OF THE ENGINEER.
18. THE CONCRETE SHALL BE PLACED IN SUCH A MANNER AS TO AVOID
SEGREGATION OR LOSS OF MATERIALS. MAXIMUM FALL OF CONCRETE =
1500mm OR USE ENCLOSED CHUTES OR SIMILAR.
19. SULPHATE RESISTANT CONCRETE TO BE USED IN ALL FOOTINGS, PILES AND
PILE CAPS IF REQUIRED BY THE PROJECT DESIGN INFORMATION.
REINFORCEMENT
1. REINFORCEMENT IS REPRESENTED DIAGRAMMATICALLY AND NOT
NECESSARILY IN TRUE PROJECTION.
2. SPLICES IN REINFORCEMENT SHALL BE MADE ONLY IN POSITIONS SHOWN OR
0THERWISE APPROVED IN WRITING BY THE ENGINEER. LAPS SHALL BE IN
ACCORDANCE WITH THE LAP TABLE.
3. WELDING OF REINFORCEMENT SHALL NOT BE PERMITTED UNLESS SHOWN ON
THE STRUCTURAL DRAWINGS OR APPROVED BY THE ENGINEER.
4. FABRIC SHALL BE LAPPED 2 TRANSVERSE WIRES PLUS 50mm. WHERE
FABRIC LAPS, SHEETS TO HAVE MAXIMUM 2 LAYERS AT ANY POINT, CUT
BACK FABRIC AT CORNERS AS REQUIRED.
5. BUNDLED BARS SHALL BE TIED TOGETHER AT 30 BAR DIAMETER CENTERS
WITH 3 WRAPS OF THE WIRE.
6. FIRE RATING MESH F41 SHALL BE GALVANISED, HAVE 20mm COVER AND BE
TIED USING GALVANISED TIE WIRE
7. WHERE TRANSVERSE TIE BARS ARE NOT SHOWN PROVIDE N12-400 LAPPED
AS REQUIRED.
8. JOGGLES TO BARS SHALL COMPRISE A LENGTH OF 12 BAR DIAMETERS
BETWEEN BEGINNING AND END OF AN OFFSET OF 1 BAR DIAMETER.
9. ALL REINFORCEMENT SHALL BE FIRMLY SUPPORTED ON MILD STEEL
PLASTIC TIPPED CHAIRS, PLASTIC CHAIRS OR CONCRETE CHAIRS AT NOT
GREATER THAN 1 METRE CENTRES BOTH WAYS, AND 800 EACH WAY FOR
FABRIC. WHEN POURED ON GROUND PROVIDE PLATES UNDER ALL BAR
CHAIRS. PLASTIC TIPPED STEEL CHAIRS SHALL NOT BE USED ON EXPOSED
FACES.
10. REINFORCEMENT WITHIN FLOOR OR WALL ELEMENT OF A WET AREA SHALL
BE BONDED TO THE EARTHING SYSTEM IF CONDUCTIVE PIPING EXISTS WITHIN
THE ELEMENT. IT SHALL BE BONDED IN ACCORDANCE WITH AS 3000.
11. REINFORCEMENT SYMBOLS:
R- GRADE 250 R HOT ROLLED PLAIN BARS TO AS 4671
S- GRADE 230 S HOT ROLLED DEFORMED BARS TO AS 4671
N- DEFORMED BAR NORMAL DUCTILITY TO AS/NZS 4671 GRADE D500N
L- DEFORMED BAR LOW DUCTILITY TO AS/NZS 4671 GRADE D500L
RN- RECTANGULAR WIRE MESH NORMAL DUCTILITY TO AS/NZS 467
RL- RECTANGULAR WIRE MESH LOW DUCTILITY TO AS 4671
SN- SQUARE WIRE MESH NORMAL DUCTILITY TO AS 467
SL- SQUARE WIRE MESH LOW DUCTILITY TO AS/NZS 4671
12. THE LAP TABLES ARE BASED ON 32MPa CONCRETE WITH 25mm MINIMUM
COVER GENERALLY & 30mm COVER FOR BEAMS & COLUMNS.
TENSION LAP LENGTH FOR DEFORMED BARS IN
WALLS & SLABS LESS THAN 300mm THICK
N12
500
N16
700
N20
950
N24
1250
N28
-
N32
-
N36
-
TENSION LAP LENGTH FOR DEFORMED BARS IN
BEAMS, COLUMNS & SLABS GREATER THAN 300mm THICK
N12
600
N16
900
N20
1200
N24
1550
N28
1950
N32
2300
N36
2700
13. INCREASE TABULATED VALUES BY NOMINATED % IN THE FOLLOWING CASES
• 25MPa CONCRETE 15%
• SLIP FORM CONSTRUCTION INCREASE BY 30%
• LIGHTWEIGHT CONCRETE 30%
• 3 BUNDLE BARS 20%
• 4 BUNDLE BARS 33%
FORMWORK
1. THE DESIGN, CONSTRUCTION AND PERFORMANCE OF THE FORMWORK AND
FALSEWORK IS THE RESPONSIBILITY OF THE BUILDER.
2. DESIGN AND CONSTRUCTION AND STRIPPING TIMES SHALL COMPLY WITH AS
3610 AND AS 3600 UNLESS OTHERWISE APPROVED BY THE ENGINEER.
3. DURING CONSTRUCTION, SUPPORT PROPPING SHALL BE PROVIDED WHERE
LOADS FROM STACKED MATERIALS, FORMWORK AND OTHER SUPPORTED
SLABS INDUCE LOADS IN A SLAB OR BEAM WHICH EXCEED THE DESIGN LOAD
FOR STRENGTH OR SERVICEABILITY AT THAT AGE. ONCE THE NOMINATED 28
DAYS STRENGTH HAS BEEN ATTAINED, THESE LOADS SHALL NOT EXCEED
THE DESIGN SUPERIMPOSED LOADS SET OUT IN THE GENERAL NOTES.
4. IN MULTI-STOREY CONSTRUCTION SUFFICIENT PROPPING SHALL BE PROVIDED
AT LEVELS BELOW THE FLOOR BEING CAST. PROP REMOVAL IS TO BE
PROGRAMMED TO AVOID DISTRESS TO PREVIOUSLY CAST FLOORS. RE-SHORING
OR BACK-PROPPING IS SUBJECT TO THE APPROVAL OF THE PROJECT DESIGN
ENGINEER.
5. AREAS THAT ARE SUBJECT TO HIGH LOAD, HIGH STRESS OR THAT ARE
DEFLECTION SENSITIVE (ie CANTILEVERS) SHOULD BE BACKPROPPED FOR THE
DURATION OF CONSTRUCTION AND THEN DE-PROPPED FROM THE TOP TO THE
BOTTOM WHEN FULL CHARACTERISTIC STRENGTH HAS BEEN ACHIEVED.
6. THE FORMWORK SHALL BE DESIGNED TO RELY ON NO RESTRAINT OR SUPPORT
FROM THE PERMANENT STRUCTURE WITHOUT PRIOR APPROVAL FROM THE
PROJECT DESIGN ENGINEER.
7. FORMWORK SHALL BE DESIGNED TO ACCOMMODATE MOVEMENTS DUE TO
POST-TENSIONING.
8. DESIGN INFORMATION CONCERNING THE FOUNDATION FORMWORK SHALL BE
DETERMINED FROM THE CONDITIONS EXISTING ON SITE AT THE TIME OF
CONSTRUCTION. REFER ALSO TO THE GEOTECHNICAL REPORT WHERE
AVAILABLE.
9. UNLESS NOTED OTHERWISE PROVIDE UPWARD CAMBER TO FORMWORK OF
CANTILEVERS OF L/120, WHERE L IS THE SHORTEST PROJECTION BEYOND
COLUMN OR WALL FACE, AND TO FORMWORK OF SLABS WHERE NOTED ON
PLAN. MAINTAIN THE SLAB AND BEAM DEPTHS SHOWN.
10. FOR CONCRETE FINISHES & FORMWORK CLASS REFER TO ARCHITECTURAL
DOCUMENTATION.
CONSTRUCTION JOINTS
1. CONSTRUCTION JOINTS SHALL BE USED ONLY WHERE SHOWN ON THE
DRAWINGS, AND NO CONSTRUCTION JOINT SHOWN ON THE DRAWINGS SHALL
BE OMITTED UNLESS APPROVED IN WRITING BY THE SUPERINTENDENT.
LOCATION OF CONSTRUCTION JOINTS ARE SHOWN THUS CJ.
2. CONSTRUCTION JOINTS WHERE NOT SHOWN SHALL BE LOCATED TO THE
APPROVAL OF THE DESIGN ENGINEER.
LINTELS
1. UNLESS OTHER SUPPORT IS SPECIFIED, PROVIDE PROPRIETY LINTEL (PRE-
CAST OR GALINTEL) INSTALLED TO MANUFACTURERS SPECIFICATIONS FOR
ALL OPENINGS UNDER 3000mm
2. ALTERNATIVELY PROVIDE LINTELS IN ACCORDANCE WITH TABLE BELOW
(ONE TO EACH LEAF OF WALL)
3. REFER TO PROJECT DESIGN INFORMATION TABLE FOR DURABILITY
REQUIREMENT.
UP TO 1500mm
1500mm TO 2100mm
2100mm TO 3000mm
OVER 3000mm
SPAN
90 x 90 x 6 EA
100 x 100 x 6 EA
150 x 90 x 8 UA
REFER TO DETAILS
LINTEL
230mm LONGER THAN 0PENING
LENGTH
450mm LONGER THAN 0PENING
450mm LONGER THAN 0PENING
REFER TO DETAILS
STEELWORK
1. ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS 4100
AND AS 1554 EXCEPT WHERE VARIED BY THE CONTRACT DOCUMENTS.
2. ALL STEEL SHALL BE IN ACCORDANCE WITH AS 3678 AND AS 3679 TO GRADE
250 UNLESS NOTED.
3. A PDF COPY OF WORKSHOP FABRICATION DRAWINGS SHALL BE SUBMITTED TO
THE ENGINEER FOR REVIEW AT LEAST 14 DAYS PRIOR TO COMMENCEMENT OF
FABRICATION AND PERMISSION TO USE OBTAINED PRIOR TO FABRICATION.
PERMISSION TO USE DOES NOT RELIEVE THE BUILDER OF THE FULL
RESPONSIBILITY FOR DIMENSIONS, FIT AND COMPLIANCE WITH ARCHITECTURAL
AND ENGINEERING DRAWINGS.
4. ALL WELDS SHALL BE 6mm CONTINUOUS FILLET TYPE GP (GENERAL PURPOSE)
UNLESS NOTED OTHERWISE. BUTT WELDS SHALL BE COMPLETE PENETRATION
WELDS TO AS 1554. FOR STEEL LESS THAN 6mm THICK, FILLET WELD
THICKNESS TO MATCH THE BASE METAL THICKNESS.
5. ALL PLATES SHALL BE 10mm THICK UNLESS NOTED OTHERWISE.
6. STEELWORK TO BE CONCRETE ENCASED SHALL BE WRAPPED WITH F41
STEELWIRE FABRIC AND SHALL BE 50mm MINIMUM CONCRETE COVER TO THE
STRUCTURAL STEEL.
7. PROVIDE SEAL PLATES TO ALL HOLLOW SECTIONS. PROVIDE VENT HOLES TO
HOLLOW MEMBERS AND DRAIN HOLES TO ALL MEMBERS TO BE HOT DIP
GALVANISED.
8. STRUCTURAL STEELWORK SHALL HAVE THE SURFACE TREATMENT SPECIFIED
IN THE PROJECT INFORMATION TABLE.
9. THE BUILDER SHALL PROVIDE ALL CLEATS AND DRILL ALL HOLES NECESSARY
FOR FIXING STEEL TO STEEL AND TIMBER TO STEEL WHETHER OR NOT
DETAILED ON THE DRAWINGS.
10. ALL STRUCTURAL STEEL MEMBERS TO BE PROVIDED WITH THE FIRE RATING
TO NCC BCA REQUIREMENTS. PCA (or ARCHITECT) TO CONFIRM.
11. PURLINS & GIRTS - ALL GIRTS AND PURLINS TO BE PROVIDED WITH BRIDGING
AS SPECIFIED ON THE DRAWINGS. e.g. 2 ROWS OF BRIDGING INDICATES THAT
EACH SPAN OF THE PURLINS TO HAVE 2 ROWS OF BRIDGING. WHERE NO
BRIDGING IS DETAILED ON THE DRAWINGS PROVIDE THE MINIMUM BRIDGING
REQUIRED BY THE MANUFACTURER. MAXIMUM SPACING OF BRIDGING NOT TO
EXCEED 20 x DEPTH OF PURLIN.
12. WHERE A CONTINUOUS INSULATION LAYER IS REQUIRED ABOVE THE PURLINS
PROVIDE A BRADFORD ASHGRID SYSTEM (OR APPROVED EQUIVALENT)
INSTALLED IN ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS
13. BOLTS:-
• 4.6/S: COMMERCIAL BOLTS OF GRADE 4.6 TO AS 111, SNUG TIGHTENED.
• 8.8/S: HIGH STRENGTH STRUCTURAL BOLTS OF GRADE 8.8 TO AS 1252, SNUG
TIGHTENED.
• 8.8/TB: HIGH STRENGTH STRUCTURAL BOLTS OF GRADE 8.8 TO AS 1252
FULLY TENSIONED TO AS 41000 AS A BEARING JOINT.
• 8.8/TF: HIGH STRENGTH STRUCTURAL BOLTS OF GRADE 8.8 TO AS 1252 FULLY
TENSIONED AS A FRICTION JOINT WITH FACING SURFACES LEFT UNCOATED.
• ALL BOLTS SHALL BE M20 GRADE 8.8/S UNLESS NOTED OTHERWISE.
• NO CONNECTION SHALL HAVE LESS THAN 2 BOLTS.
• ALL BOLTS, NUTS AND WASHERS TO BE GALVANISED TO AS 4680 TABLES 1
& 2.
• TB AND TF BOLTS TO BE INSTALLED USING APPROVED LOAD INDICATING
WASHERS, OR BY TURN OF NUT CONTROL OF TENSIONING.
TIMBER
1. ALL TIMBER DESIGN AND CONSTRUCTION SHALL BE TO AS 1720 OR AS 1684
WHERE APPROPRIATE. ALL SOFTWOOD SHALL BE GRADE MGP10 UNLESS
NOTED OTHERWISE. ALL HARDWOOD SHALL BE MINIMUM GRADE F11 U.N.O.
2. DURABILITY GRADE OF ALL TIMBERS TO COMPLY WITH THE PROJECT
INFORMATION TABLE.
3. ALL BOLTS IN TIMBER CONSTRUCTION SHALL BE MINIMUM M16 UNLESS NOTED
OTHERWISE AND SHALL BE GALVANISED. BOLTS SHALL BE RETIGHTENED AT
THE END OF THE MAINTENANCE PERIOD. ALL TRUSSES AND RAFTERS SHALL
BE FIXED TO TOP PLATE WITH METAL PLATE CONNECTORS
FRAMING AND BRACING
1. ALL BRACING AND TIE DOWNS TO BE IN ACCORDANCE WITH AS1684
2. UNLESS NOTED OTHERWISE PROVIDE THE MINIMUM FOR
3. ROOFS AND HORIZONTAL BRACING - USE DIAGONAL CROSS STRAP
BRACING THROUGHOUT ROOF. SCREW FIX TO EACH RAFTER,PURLIN OR
TRUSS AND SECURELY FASTEN TO TOP PLATE/BEAM AT ENDS.
4. STUD WALLS - STRAP TOP & BOTTOM PLATE TO A MINIMUM OF EVERY
SECOND STUD SECURE FLOOR PLATE TO SLAB BELOW WITH M12 CHEMICAL
ANCHORS AT 1200mm MAX CTS OR SECURE EVERY SECOND STUD TO
FLOOR BEARERS BELOW
5. MASONRY WALLS - FASTEN TOP PLATE TO BRICKWORK USING ROOF
STRAPS (SIMILAR M.E.T. 7.1 OR APPROVED EQUIVALENT) AT A MAXIMUM
OF 1200mm SPACING ANCHORED 15 C/S DOWN PROVIDE STRAPS EACH
SIDE OF ALL OPENINGS PROVIDE ADDITIONAL HOLD DOWNS AS DETAILED
6. VERTICAL BRACING - PROVIDE VERTICAL BRACING IN ACCORDANCE WITH
AS 1684. PROVIDE ADDITIONAL VERTICAL BRACING WHERE SHOWN AND AS
DETAILED ON THESE DRAWINGS
CONCRETE DESIGN
CEMENT TYPE
LIMIT DRYING SHRINKAGE AT 56 DAYS
SULPHATE RESISTANCE CONCRETE BELOW GROUND
PROVIDE 50mm SIDE COVER TO TIES FOR ALL BEAMS U.N.O.
ELEMENT STRENGTH COVER EXT COVER INT
- "GP"
- 800 MICRONS
- NO
PROJECT INFORMATION TABLE
STEELWORK FINISHES
INTERNAL
BUILT INTO MASONRY
EXTERNAL
LOCATION TYPE CODE
• FOR FINISH TYPE & CODE REFER TO STANDARD AS/NZS 2312
• FOR DECORATIVE FINISH REFER TO ARCHITECTURAL OR OWNERS
SPECIFICATIONS
ALK4
HDG 600
HDG 600
PAINT SYSTEM
GALVANISED
GALVANISED
GEOTECHNICAL INFORMATION
COMPANY REPORT No. DATED
NOT AVAILABLE
FOUNDATIONS
SITE CLASSIFICATION FOUNDATION MATERIAL ALLOW BEARING CAP
"M" CLAY 100 kPa
FOOTINGS
SLAB ON GROUND
25 MPa
32 MPa
50
40
-
25
THE TABLES BELOW ARE TO BE READ IN CONJUNCTION WITH THE
ADJACENT NOTES
EARTHQUAKE DESIGN PARAMETERS
IMPORTANCE LEVEL
SITE SUB-SOIL CLASS
ACCELERATION CO-EFFICIENT
DESIGN CATEGORY
= 2
= Be
= 0.08
= II
WIND DESIGN PARAMETERS
REGION
IMPORTANCE LEVEL
REGIONAL WIND SPEED
TERRAIN CATEGORY
TOPOGRAPHIC MULTIPLIER
= A2
= 2
= V500 = 45m/s
= 3
= 1.0
SAFETY IN DESIGNTHERE ARE INHERENT RISKS WITH CONSTRUCTING, MAINTAINING, OPERATING,
DEMOLISHING, DISMANTLING AND DISPOSING THIS DESIGN THAT ARE TYPICAL
OF SIMILAR DESIGNS. AS FAR AS IS REASONABLY PRACTICABLE RISKS HAVE
BEEN ELIMINATED OR MINIMISED THROUGH THE DESIGN PROCESS. HAZARD
CONTROLS MUST STILL BE IMPLEMENTED BY THE CONTRACTOR, OWNER OR
OPERATOR TO ENSURE THE SAFETY OF WORKERS.
• JONES NICHOLSON'S ASSESSMENT DID NOT IDENTIFY ANY UNIQUE RISKS
ASSOCIATED WITH THE DESIGN
Job No.
COOPER ST, MOREHEAD ST, WALKER ST REDFERN NSW
130277
STRUCTURAL DRAWING LIST
No. DRAWING LIST
S001 COVER SHEET
S002 DETAILS
COMPOSITE METAL DECKING1. PANELS TO BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS DETAILS.
2. BEFORE PANELS ARE LAID, TOP COURSE OF BRICKWORK IS TO BE STRAIGHT
AND LEVEL. IF REQUIRED PROVIDE LAYER OF SMOOTH HARD MORTAR. SLIP
JOINTS SHALL BE PROVIDED AT ALL MASONRY SUPPORTS UNLESS NOTED
OTHERWISE.
3. BEFORE CONCRETE IS PLACED, ANY ACCUMULATED DEBRIS, GREASE OR ANY
OTHER SUBSTANCE WILL NEED TO BE REMOVED TO ENSURE CLEAN BONDING
SURFACE. ANY PONDED RAINWATER SHOULD BE REMOVED.
4. UNLESS NOTED OTHERWISE PROPPING OF METAL DECKING SHALL BE IN
ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS.
5. PROPS SHOULD NOT BE REMOVED UNTIL CONCRETE HAS REACHED SPECIFIED
DESIGN STRENGTH
SAFETY UPGRADE WORKS STAGE 3 REDFERN
REDFERN STAGE 3 SAFETY UPGRADE
TENDER ISSUE
AMDT DATE BY DESCRIPTION
1 11.11.14 GS FOR TENDER2 22.11.14 GS Amended to attend architects comments
ST3 S10
SCALE :
PROJECT MGR :
DATE :
DRAWN :
DRG SIZE :
DESIGN :
WWW.JONESNICHOLSON.COM.AU
THE CONCEPTS AND INFORMATION CONTAINED IN THEDOCUMENT ARE THE COPYRIGHT OF JONES NICHOLSONPty. Ltd. USE OR COPYING OF THE DOCUMENT WITHOUTWRITTEN PERMISSION OF JONES NICHOLSON Pty. Ltd.CONSTITUTES AN INFRINGEMENT OF COPYRIGHT STRUCTURAL DESIGN
ABN: 51 003 316 032CIVIL STRUCTURAL BUILDING SERVICES. .
LAND & HOUSING
CORPORATION
NOV '14
GS
GS
GS
A3NOT TO SCALE
PLANS &DETAILS
Elizabeth St, Kettle & Walker St. 130277REDFERN STAGE 3 SAFETY UPGRADE
1N12 edge barall around
Typical edgethickening
All footings to be poured on natural, firm ground free fromroots and/or organic material, with a safe bearing capacityof 100 kPa
CONCRETE STRENGTH
RAFT SLABS f'c = 25 MPa
BONDEK SLAB f'c = 32 MPa
COVER TOREINFORCEMENTFootings 50 mmSlab on ground 40 mm topBondek 30 mm top
ACCESS WALKWAY TO No 60 - 62
PROPOSED RAFT SLAB UNDER RAMP
B
B
C
C
Proposed brick retainingwall over slab
Raft slab edgethickenings
Raft slabinternalthickenings
For reinforcement details, dimensions, recommendations, usesimilar details as per the typical garbage bay slab details.
B
B
Ramp up
CC
Expansion jointin Bondek
Expansion jointin Bondek
Direction ofBondek ribs
PROPOSED 130 THICK BONDEK SLAB RAMP
AMDT DATE BY DESCRIPTION
1 11.11.14 GS FOR TENDER
TENDER ISSUE
120 Thick slab SL82Top fabric, pouredon well compactedground
N12 bent barsat 200 mm ctsTotal length >=2000 mm
2 22.11.14 GS Amended to attend architects comments
BJ
BJ
ST3 S11
SCALE :
PROJECT MGR :
DATE :
DRAWN :
DRG SIZE :
DESIGN :
WWW.JONESNICHOLSON.COM.AU
THE CONCEPTS AND INFORMATION CONTAINED IN THEDOCUMENT ARE THE COPYRIGHT OF JONES NICHOLSONPty. Ltd. USE OR COPYING OF THE DOCUMENT WITHOUTWRITTEN PERMISSION OF JONES NICHOLSON Pty. Ltd.CONSTITUTES AN INFRINGEMENT OF COPYRIGHT STRUCTURAL DESIGN
ABN: 51 003 316 032CIVIL STRUCTURAL BUILDING SERVICES. .
LAND & HOUSING
CORPORATION
NOV '14
GS
GS
GS
A3NOT TO SCALE
PLANS &DETAILS
Elizabeth St, Kettle & Walker St. 130277REDFERN STAGE 3 SAFETY UPGRADE
100 100
10mm Abelflex with 10x10mastic sealant
1N12 edge barboth sides of joint
EXPANSION JOINT DETAILIN BONDEK SLAB (RAMP)
Install flashing tocreate drip
100 mm conventionalformwork each side of joint
Provide adequate ventilation tovoid under Bondek slab
SL82 Top fabric
230
Waterproofingby others`
350
Ag. line, gravelencased andconnected to freeoutlet`
110VOID`
For reinforcement use similar details as pergarbge bay slabs
1.0mm BondekSlip jointSLO (typ)
10mm Abelflex with 10x10mastic sealant
130 slab, SL82top fabric
N12 cross rods
Balustrade to BCAby others
N12-300 'L' bars,hob reinforcement.Height of hob toarchitects details
SECTION B-B
For slip joints 'SLO' overbrick walls use 2 layers ofmalthid
Raft slab
BUTT JOINT BJ10mm Abelflex with 10x10mastic sealant
Mass concrete
Massconcrete
SECTION C-CRAMP START
VOID
BONDEK
CONCRETEf'c = 25 MPa
CONCRETE f'c = 25 MPa
75mm minimumthickness ofconcrete topping
Provide 'BJ' type of jointsbetween all new concretetoppings and all surroundingvertical surfaces
SL82 Top and bottom forall topping thicknessest >= 150 mm
SL82 Top and bottom forall topping thicknesses150 > t >= 75 mm
EXISTING CONCRETE SLAB
BJ
Thin special topping,refer to separate detail
TYPICAL TOPPING DETAILS
For location of topping slabs refer to architectural plans
75
mm
ma
x
DETAIL FOR THIN TOPPINGSt < = 75 mm
Install a vapour proof membranethroughout to separate oldconcrete slab surface from newconcrete topping. Do NOT installmembrane in area where thintopping t < 75mm is required.
AMDT DATE BY DESCRIPTION
1 11.11.14 GS FOR TENDER
TENDER ISSUE
150
2 22.11.14 GS Amended to attend architects comments
SCALE :
PROJECT MGR :
DATE :
DRAWN :
DRG SIZE :
DESIGN :
WWW.JONESNICHOLSON.COM.AU
THE CONCEPTS AND INFORMATION CONTAINED IN THEDOCUMENT ARE THE COPYRIGHT OF JONES NICHOLSONPty. Ltd. USE OR COPYING OF THE DOCUMENT WITHOUTWRITTEN PERMISSION OF JONES NICHOLSON Pty. Ltd.CONSTITUTES AN INFRINGEMENT OF COPYRIGHT STRUCTURAL DESIGN
ABN: 51 003 316 032CIVIL STRUCTURAL BUILDING SERVICES. .
LAND & HOUSING
CORPORATION
NOV '14
GS
GS
GS
A3NOT TO SCALE
PLANS &DETAILS
Elizabeth St, Kettle & Walker St. 130277
For locations of new footpaths refer to architectural plans
AMDT DATE BY DESCRIPTION
1 11.11.14 GS FOR TENDER
TENDER ISSUE
REDFERN STAGE 3 SAFETY UPGRADE2 22.11.14 GS Amended to attend architects comments
ST3 S13
SCALE :
PROJECT MGR :
DATE :
DRAWN :
DRG SIZE :
DESIGN :
WWW.JONESNICHOLSON.COM.AU
THE CONCEPTS AND INFORMATION CONTAINED IN THEDOCUMENT ARE THE COPYRIGHT OF JONES NICHOLSONPty. Ltd. USE OR COPYING OF THE DOCUMENT WITHOUTWRITTEN PERMISSION OF JONES NICHOLSON Pty. Ltd.CONSTITUTES AN INFRINGEMENT OF COPYRIGHT STRUCTURAL DESIGN
ABN: 51 003 316 032CIVIL STRUCTURAL BUILDING SERVICES. .
LAND & HOUSING
CORPORATION
NOV '14
GS
GS
GS
A3NOT TO SCALE
PLANS &DETAILS
Elizabeth St, Kettle & Walker St. 130277AMDT DATE BY DESCRIPTION
1 11.11.14 GS FOR TENDER
TENDER ISSUE
LETTER BOXES
SF1 PF1
SF1 PF1
450
450
4-L12 TM Top
R6 Ties - 600 cts
4-L12 TM Btm
STRIP FOOTING 'SF1'
All footings to be poured on natural, firm ground free fromroots and/or organic material, with a safe bearing capacityof 100 kPa
REDFERN STAGE 3 SAFETY UPGRADE
LETTER BOXES & ISOLATED PIERS TYPICAL PLAN
LETTER BOXES & ISOLATED PIERS TYPICAL ELEVATIONS
Pad footing 'PF1' to be 500square x 450 deep massconcrete
2 22.11.14 GS Amended to attend architects comments
ST3 S14
SCALE :
PROJECT MGR :
DATE :
DRAWN :
DRG SIZE :
DESIGN :
WWW.JONESNICHOLSON.COM.AU
THE CONCEPTS AND INFORMATION CONTAINED IN THEDOCUMENT ARE THE COPYRIGHT OF JONES NICHOLSONPty. Ltd. USE OR COPYING OF THE DOCUMENT WITHOUTWRITTEN PERMISSION OF JONES NICHOLSON Pty. Ltd.CONSTITUTES AN INFRINGEMENT OF COPYRIGHT
ABN: 51 003 316 032CIVIL STRUCTURAL BUILDING SERVICES. .
LIGHTING SCHEDULE
TYPE DESCRIPTION LAMP MODEL MANUFACTURE (SUPPLIER)
B1 NEW VANDAL PROOF, SURFACE MOUNTED, VERTICALLY ALIGNED LED BATTEN AT 3000 AFFL 12W LED 4000K VANDALED PIERLITE
E-B1 REPLACE EXISTING BATTEN WITH NEW VANDAL PROOF, SURFACE MOUNTED, VERTICALLY ALIGNED LED BATTEN AT 3000 AFFL
12W LED 4000K VANDALED PIERLITE
E-B2 REPLACE EXISTING BATTEN NEW VANDAL PROOF LED BATTEN, MOUNTED ON EXISTING OUTREACH POLE AT 3000 AFFL
12W LED 4000K VANDALED PIERLITE
E-B3 REPLACE EXISTING BATTEN NEW VANDAL PROOF, CEILING MOUNTED, LED BATTEN AT 3000 AFFL
12W LED 4000K VANDALED PIERLITE
P1 NEW LED FITTING ON 4M ROUND MATT BLACK POLE TO MATCH 36W LED 4200K HEDO LED – 36 LED AURORA LIGHTING
E-P1 REPLACE EXISTING POLE AND FITTING WITH NEW LED FITTING ON 4M ROUND MATT BLACK POLE TO MATCH
36W LED 4200K HEDO LED – 36 LED AURORA LIGHTING
E-W1 REPLACE EXISTING WALL MOUNTED FLOOD LIGHT WITH NEW WALL MOUNTED FLOOD LIGHT AT 9000 AFFL
24W LED 4100K HUNTSMAN PIERLITE
D-B DELETE EXISTING BATTEN, MOUNTING KIT, WIRING AND CONDUIT AND MAKE SURFACE GOOD
D-P DELETE EXISTING POLE, LUMINAIRE AND MAKE SURFACE GOOD
DTDT
SEPT 14A1
1:100TS
STAGE 3 SAFTEY UPGRADE
Elizabeth St, Walker St & Kettle St,Redfern
FACS
130277E01 A
ELECTRICAL DESIGNNOTES, SCHEDULE &
LEGEND1 12.09.14 DT PRELIMINARY ISSUE
LIGHT POLE TO BE DESIGNED
AND DETAILED BY OTHERS
LIGHT POLE TO FOOTING
CONNECTION TO
MANUFACTURES SPECIFICATION
CABLES AND CONDUITS
IN GROUND
MARKER TAPE
TYPICAL POLE LAYOUTTYPICAL CONDUIT IN TRENCH DETAIL
FINISH GROUND/ CARPARK
PAVEMENT SURFACE
IDENTIFICATION TAPE
BEDDING AND BACK FILL TO
TRENCH TO BE COMPACTED
IN 100mm LAYER TO 100%
SMD min
MIN
150
250
500
1. THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL ARCHITECTURAL
AND OTHER CONSULTANTS DRAWINGS AND SPECIFICATION AND WITH SUCH
OTHER WRITTEN INSTRUCTION AS MAY BE ISSUED DURING THE COURSE OF THE
CONTRACT. ANY DISCREPANCY SHALL BE REFERRED TO THE SUPERINTENDENT
BEFORE PROCEDDING WITH THE WORK.
2. ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE
RELEVANT AND CURRENT AUSTRALIAN STANDARDS AND THE BUILDING CODE OF
AUSTRALIA EXCEPT WHERE VARIED BY THE PROJECT SPECIFICATION. REFER TO
16.
3. ALL DIMENSIONS SHOWN SHALL BE VERIFIED BY THE CONTRACTOR ON SITE.
ENGINEERS DRAWINGS SHALL NOT BE SCALED FOR DIMENSIONS.
4. THE CONTRACTOR SHOULD REPORT ANY DISCREPANCIES ON THE DRAWINGS TO
THE ENGINEER RESPONISBLE FOR THE DESIGN.
5. UNLESS NOTED OTHERWISE ALL LEVELS ARE IN METRES AND ALL DIMENSIONS
ARE IN MILLIMETRES.
6. CONTRACTOR IS NOT TO ENTER UPON NOR DO ANY WORK WITHIN ADJACENT
LANDS WITHOUT THE PERMISSION OF THE OWNER. SURPLUS EXCAVATED
MATERIAL SHALL BE PLACED WHERE DIRECTED OR REMOVED FROM SITE.
7. ALLOW TO CO-ORDINATE WITH THE EXISTING STRUCTURE AND SERVICES IN THE
BUILDING, ALLOWING FOR ANY ADDITIONAL WORKS THAT MAY BE REQUIRED TO
CO-ORDINATE WITH THESE SERVICE.
8. ALLOW FOR OUT OF HOURS WORKS,
9. ELECTRICAL CONTRACTOR TO CLEAN ALL FITTINGS AT PRACTICAL COMPLETION.
GENERAL NOTES
1. ALL EXTERNAL LIGHTING TO BE CONTROLLED VIA A PE CELL AND TIMECLOCK
AS PER BCA SECTION J6
2. ALL SURFACE MOUNTED BATTEN IN THE INTERNAL COMMON AREA TO BE
REPLACED WITH TYPE B2 FITTINGS
LIGHTING
STAGE 3 SAFTEY UPGRADEELIZABETH ST, WALKER ST & KETTLE ST, REDFERN
3D RENDER OF LIGHT CALCULATION
ELIZABETH ST
KETTLE ST
LOCATION PLAN
WALKER ST
ELIZABETH ST
KETTLE ST
AMDT DATE BY DESCRIPTION
A 24.11.14 DT TENDER ISSUE
SCALE :
PROJECT MGR :
DATE :
DRAWN :
DRG SIZE :
DESIGN :
WWW.JONESNICHOLSON.COM.AU
THE CONCEPTS AND INFORMATION CONTAINED IN THEDOCUMENT ARE THE COPYRIGHT OF JONES NICHOLSONPty. Ltd. USE OR COPYING OF THE DOCUMENT WITHOUTWRITTEN PERMISSION OF JONES NICHOLSON Pty. Ltd.CONSTITUTES AN INFRINGEMENT OF COPYRIGHT
ABN: 51 003 316 032CIVIL STRUCTURAL BUILDING SERVICES. .
DTDT
SEPT 14A1
1:100TS
STAGE 3 SAFTEY UPGRADE
Elizabeth St, Walker St & Kettle St,Redfern
FACS
130277E02 A
ELECTRICAL DESIGNEXTERNAL LIGHTING
P1
DP
EP1
EP1
EP1
EP1
DP
EP1
DP
EP1
EP1EP1
EP1
EP1
EP1
EP1
P1P1
P1P1
P1
P1
P1
P1
P1
P1
P1
EP1
EP1
EP1
EB1
DB1
DB1
EB1
EB2
EB2
DB
DB
EB3
EB3
EB3
EB3
EB3
EB3
EB3
EB3
EB3
EB3
EB3
EB3
EB3
EB3
EB3
EB2
DB
RB1
EB1
DB
DB
EB1
EB1
EB1
EB1
EB3
EB1
EW1
EB1
B1
B1
P1
B1
EP1
EB3
EB3
1 12.09.14 DT PRELIMINARY ISSUEAMDT DATE BY DESCRIPTION
A 24.11.14 DT TENDER ISSUE