Distribution systems

40
DISTRIBUTION SYSTEMS

Transcript of Distribution systems

Page 1: Distribution systems

DISTRIBUTION SYSTEMS

Page 2: Distribution systems

ELECTRICAL POWER SYSTEM

• The distribution system is a part of the power system, existing between distribution sub-stations and the consumers.

Page 3: Distribution systems

DISTRIBUTION SYSTEMS

Page 4: Distribution systems

INTRODUCTION(DISTRIBUTION SYSTEMS)• Distribution

systemsTo distribute the electric power among the consumer.

Below a certain voltage

General distribution scheme

Page 5: Distribution systems

Requirements of good distribution systems

• Continuity in the power supply must be ensured.• Voltage must not vary more than the prescribed limits.(.• Efficiency of line must be high as possible.• Safe from consumer point of view.• Layout should not effect the appearance of locality.• Line should not be overloaded.

Page 6: Distribution systems

Distribution system is further classified on the basis of voltage

1.primary distribution systems

2.secondary distribution systems • Primary Distribution:-The part of the electrical-supply system

existing between the distribution substations and the distribution transformers is called the primary system.

• Secondary Distribution:-The secondary distribution system receives power from the secondary side of distribution transformers at low voltage and supplies power to various connected loads via service lines.

Page 7: Distribution systems

Distribution system

DC Distribution

system

D.C Three wire system

1.General Distribution

system

AC Distribution

system

Ring main Distribution

system

Radial Distribution

system

Page 8: Distribution systems

DC Distribution system 1.General Distribution system

2. D.C Three wire system1.General Distribution system• Feeder are used to feed the electrical

power from the generating station to the substation.

• Distributors are used to distribute the supply further from the substation.

• Service mains are connected to the distributors so as to make the supply available at the consumers.(simplest two wire distribution system)

Page 9: Distribution systems

2.D.C Three wire system• Voltage level can not be increased readily like a.c.• Method:-two generators are connected in series -each is generating a voltage of V volts -common point is neutral from where neutral wire is run.(too expensive , use to double the transmission voltage)• Demand :-consumers demanding higher voltage are

connected to the two lines. -consumers demanding less voltage are connected between any one line and neutral.

Page 10: Distribution systems

D.C Three wire system

Page 11: Distribution systems

• Balanced:-One line carries current I1 while the other current I2.when the load is balanced(loads connected on either sides of the neutral wire are equal) .neutral current is zero.

• Out of balance current:-I1 is greater than I2 then neutral wire carries current equal to I1-I2

-I2 is greater than I1 then neutral wire carries current equal to I2-I1.(Direction).neutral potential will not remain half of that between the 2 lines.

Page 12: Distribution systems

Single generator having twice the line• Two small d.c machines are

connected across the line in series which are mechanically coupled to a common shaft . These are called balancers.

• load is balanced:-machines work as the d.c motors.

• Out of balance:-machine connected to lightly loaded side acts as motor , heavily loaded side acts as generator.

Energy is transferred from lightly loaded side to heavily loaded side as machine as motor drives the machine as generator.

Page 13: Distribution systems

AC Distribution system 1.Radial Distribution system 2.Ring main

Distribution system

1.Radial Distribution system• only one/single path is connected between each Distributor and substation

is called radial Distribution system.• Fault occurs either on feeder or a distributor, all the consumers connected

to that distributor will get affected.• In India, 99% of distribution of power is by radial distribution system only.

Page 14: Distribution systems

Advantages:• Its initial cost is minimum.• Simple in planning, design and operation.• Useful when the generation is at low voltage..• Station is located at the center of the loadDisadvantages:• Distributor nearer to the feeding end is heavily loaded.• The consumers at the far end of the feeder would be subjected

to series voltage fluctuations with the variations in load.

Page 15: Distribution systems

2.Ring main Distribution system• Feeder covers the whole area of supply in the ring fashion and

finally terminates at the substation from where it is started.• Closed loop form and looks like a ring.

Page 16: Distribution systems

Advantages:• Less conductor material is required as each part of the ring

carries less current than in the radial system.• Less voltage fluctuations.Disadvantage:• It is difficult to design when compared to the designing of a

radial system.

Page 17: Distribution systems

Types of D.C DistributorsD.C

Distributors

Concentrated loads

Fed at both the end

Ends at Unequal voltages

End at Equal

voltages

Fed at one end

Distributed loads

Fed at one end

Fed at both the end

End at Equal

voltages

Ends at Unequal voltages

Page 18: Distribution systems

• Concentrated loads:-load which are acting at particular points of the distributor are called concentrated loads.

• Distributed loads:-load which spread over the particular distance of the distributor are called distributed load.(no load condition practical)

D.C Distributor with Concentrated loads• Classified 1. Fed at one end 2.Fed at both the ends

Page 19: Distribution systems

1.Fed at one end(Concentrated loads)

Page 20: Distribution systems

• Fed at one end A-A’.• Applying KCL at various points we get, i1=I1+I2+I3,i2=I2+I3 and i3=I3

• the wire A’B’ is the return wire of the distributor r’=resistance per unit length of conductor in Ω• Voltage drop tabulated as,

section Drop section DropAa i1l1r’ A’a’ i1l1r’ab i2(l2-l1)r’ a’b’ i2(l2-l1)r’bc i3(l3-l2)r’ b’c’ i3(l3-l2)r’

Page 21: Distribution systems

• In practice , the resistance of go and return conductor per unit length is assumed to be r=2r’.

• r1=2r1’, r2=2r2’, r3=2r3’• The total drop in the distributor is =r1i1l1+r2i2(l2-l1)+r3i3(l3-l2)

Page 22: Distribution systems

Current loading and voltage drop diagram

Page 23: Distribution systems

2.Fed at both the ends(Concentrated loads)

1.End at Equal voltages• A and B maintained at equal voltage• ‘b’ be the point of minimum potential(the load point where the current

are coming from both the side of distributor is the point of minimum potential.

Let x be supplied by point A while y be supplied by point B,

y=I2-x

Page 24: Distribution systems

• As both the point A and B are maintained at same voltage, drop in section Aa must be equal to drop in section Bb.

i1r1+i2r2=i3r3+i4r4

(I1+x)r1+xr2=(I2-x)r3+(I2+I3-x)r4

• All current known , x and voltage drop can be calculated

Current loading and voltage drop diagram

Page 25: Distribution systems

2.Ends at Unequal voltages• A and B maintained at different voltage• ‘b’ be the point of minimum potential.• Let x be supplied by point A while y be supplied by point

B, y=I2-x• Voltage drop between A and B = Voltage drop over AB• If voltage of A is V1 and is greater than voltage of B which

is V2 then, V1-V2=drop in all the section of AB• The same equation can be written as, V1-drops over Ab= V2-drops over Bb

Page 26: Distribution systems

V1-i1r1-i2r2=V2-i3r3-i4r4

V1-(I1+x)r1-xr2=V2-(I2-x)r3-(I2+I3-x)r4

Here V1 and V2 are known ,obtain x

Current loading and voltage drop diagram

Page 27: Distribution systems

D.C Distributor with Uniformly Distributed load• Classified 1. Fed at one end 2.Fed at both the ends

1.Fed at one end (Distributed load )• Uniformly distributed load on 2 wire distributor , fed at one end I amperes per meterTotal voltage drop is to be obtained by considering a point C(distance x),feeding end A• Current tapped at point C is =total current – current up to point ‘C’=i=i(l

Page 28: Distribution systems

• dx near point C , its resistance rdx dV=i(l-x)rdxTotal voltage drop upto point C

Upto B, x=l

𝑉 𝐴𝐶=∫0

𝑥

𝑖 (𝑙−𝑥 )𝑟 𝑑𝑥=𝑖𝑟∫0

𝑥

(𝑙−𝑥 )  𝑑𝑥=𝑖𝑟 ¿¿¿

=) volts equation of parabola

(il)(rl)

𝑉 𝐴𝐵=12 𝐼𝑅

Page 29: Distribution systems

• Power loss=I2R,elementary length dx• At point C

X=l

𝑑𝑃=¿

𝑃=∫0

𝑙

𝑖2 [𝑙2−2 𝑙𝑥+𝑥2 ]𝑟 𝑑𝑥=𝑟   𝑖2(𝑙2 𝑥− 2 𝑙𝑥2

2+ 𝑥3

3)

𝑃=𝑖2 𝑟 𝑙3

3

Page 30: Distribution systems

2.Fed at both the ends (Uniformly Distributed load)

1.End at Equal voltagesfed at point A and B are maintained at equal voltageThe total current to be supplied is il amperes.As two end voltage are equal ,each end will supply half the required current i.e .Midpoint distance l/2,point C at a distance x , current feeding is il/2 (A) Current at C=Voltage drop over length dx is,

Page 31: Distribution systems

• Upto point C is,

Maximum voltage drop at midpoint x=l/2

¼ drop of fed at one endPower loss ,point c

Page 32: Distribution systems

• 2.Ends at Unequal voltages• Let point C be the point of minimum potential which at a

distance x from feeding point A• The current supplied by the feeding point A is ix• The current supplied by the feeding point B is i(l-x)• V1-drops over AC= V2-drops over BC• In case of distributed load the drop is given by for a length of l

X?

Page 33: Distribution systems

Ring main distributor with interconnection

• Cable is arranged in the Loop fashion,fed at only one point

• Use for large area hence voltage drop across the various section become larger(excessive voltage drop).

• Solution:-distant point of ring distributor are joined together by a conductor this is called interconnection.

• Thevenin’s theorem

Page 34: Distribution systems

AC Distribution• Advantages of AC • Cheaper transformation between voltages• Easy to switch off• Less equipment needed• More economical in general• Rotating field

Page 35: Distribution systems

Methods of solving A.C Distribution problem

• 1.power factor referred to receiving end voltage• Resistance R , reactance X• Impedance of section PR is given by, • Impedance of section RQ is given by, • The load current at point R is • The load current at point Q is • Current in section RQ is nothing but • Current in section PR is =+

Page 36: Distribution systems

1.power factor referred to receiving end voltage

Page 37: Distribution systems

• Voltage drop in section RQ, =[].[ ]Voltage drop in section PR , =[][Sending end voltage Sending end current

Page 38: Distribution systems

2. power factor referred to respective load voltages

Page 39: Distribution systems

• 2. power factor referred to respective load voltages

Voltage drop in section RQ is given, =[].[ ]drop of voltage in section RQ=. w.r.t voltage ) w.r.t voltage

=) +=[) +].[]Sending end voltage