Distribution System Power Flow Analysis -...
Transcript of Distribution System Power Flow Analysis -...
Chapter - 2
Distribution SystemPower Flow Analysis
18
CHAPTER - 2
Radial Distribution System Load Flow
2.1 Introduction
Load flow is an important tool [66] for analyzing electrical power system network
performance. Load flow is used at the time of solving optimization problem. So, load flow
should be fast and efficient. The distribution network is radial in nature having high R/X
value which makes it ill conditioned. The conventional Gauss Seidel (GS) and Newton
Raphson (NR) method does not converge for the distribution networks.
As discussed in chapter –1(section - 1.5.1), several limitations exist in radial load flow
techniques presently reported in the literature such as complicated bus numbering schemes,
convergence related problems, and the inability to handle modifications to existing
distribution system in a straight forward manner. This motivated the development of a radial
distribution load flow solution method.
Most of the conventional load flow methods consider power demands as specified
constant values. This should not be assumed because in distribution system bus voltages are
not controlled. Loads are specified by constant power, current or impedance requirements.
There are several load flow methods based on backward – forward sweep technique.
These method basically use -
1. Current summation methods
2. Power summation methods
19
Current summation method is more convenient and faster than the Power summation
method because it uses only ‘V’ and ‘I’ instead of ‘P’ and ‘Q’.
Basically, load flow is used for the determination of the distribution system operating
point at steady state under given conditions of loads. First of all, all bus voltages are
calculated. From these bus voltages, it is possible to directly calculate currents, active &
reactive power flows, active & reactive system losses and other steady state quantities.
In this chapter, a backward – forward sweep method is presented for solving the load
flow problem of a distribution system. The mathematical formulation of the above method is
explained in Section 2.2. In this Section, derivation of voltage, angle, active and reactive
power losses, voltage deviation and voltage stability index from single line diagram of
distribution system are discussed. The steps of load flow algorithm calculation are presented
in Section 2.3. In Section 2.4, the effectiveness of the proposed method is tested with 33 and
69 bus radial distribution systems and the results are compared with the existing methods. In
Section 2.5, conclusions of the proposed method are presented.
2.2 Mathematical Formulation
2.2.1 Assumption
In this section, circuit model of radial distribution system (RDS) is presented. It is
assumed that the three phase radial distribution system is balanced and can be represented by
an equivalent single – line diagram. The line shunt capacitance at distribution voltage level is
negligibly small and, hence neglected. The voltage magnitude and phase angle of the source
should to be specified. Also, the complex values of load demands at each bus along the feeder
should be given. Initially, a flat voltage profile is assumed at all buses i.e., 1.0 pu. The Fig. 2.1
shows the single line diagram of n-bus RDS.
Fig. 2.1: Single - line diagram of n-bus RDS
20
2.2.2 Bus indexing (numbering) scheme
Generally, most load flow formulations are the set of equations and unknowns,
associated with individual buses. So the formulations are arranged by appropriate bus
indexing. But in radial distribution system, the equations and unknowns can be reduced such
that the equations and unknowns become corresponding to the laterals. So lateral indexing is
needed for radial distribution system load flow.
A radial distribution system can be structured as a main feeder with laterals and these
laterals may also have sub- laterals, which themselves may have sub- laterals, etc. Each bus is
assigned an index ( l ,m , n ) , where l , m and n corresponds to level of lateral, lateral index
and bus index respectively. The reverse breadth-first (RBF) ordering of the laterals, found by
sorting the lateral indices in descending order, first by level, then by lateral index. The RBF
ordering is typically used for backward sweep type operations. If the laterals are sorted in
ascending order, the result is a breadth-first (BF) ordering, typically used for forward sweep
type operations.
2.2.3 Backward and Forward sweep based load flow algorithm
Iterations of backward and forward sweep based load flow algorithm:
1. First the bus and lateral indexing are done.
2. Then RBF ordering of end nodes are done according to the indexing.
3. All the end nodes voltages are initialized for the three phases (considering the
nominal voltage as base voltage).
4. According to the RBF ordering the backward sweep for the first iteration starts.
5. In backward sweep –
(a) The end node of lowest RBF order is considered.
(b) As the node voltage is known, so the current injecting at this node by
loads, shunt capacitors and DGs can be calculated.
(c) Then the current injection at the node is calculated by applying KCL at
current nod. As this is the end node, no current should be added by the
incoming downstream branch.
21
(d) Then by the initialized voltage and the total current injection at the
current node, using the update formulae, voltage at the next node and the
current injection at the next node through the branch between current
node and next node are calculated.
(e) Go to 5(b) and follow the same process until the branch off node of
current sub lateral or lateral has reached.
(f) The calculation of voltage and current at the current sub lateral or lateral
are stopped and the RBF order is incremented by one and goes to 5 (b)
until source node has reached.
(g) If the node is source node, and RBF order value becomes maximum, it
means that the backward sweep for first iteration ends.
(h) So from backward sweep the branch off current of laterals and sub
laterals are stored for computing the node voltages in forward sweep.
6. In forward sweep -
(a) The forward sweep starts with the specified substation secondary voltage,
and the current injected by the substation to the network which was stored
as branch off current of the main feeder during the backward sweep.
(b) It is therefore easy to calculate the voltage of the downstream node and
the current flowing through the downstream branches of the main feeder
one by one using the update formulae (and the branch off current stored
during backward sweep and the branch off voltages stored during the
calculation of the previous main feeders or laterals is used except for
main feeder calculation) until the end node of that main feeder or laterals
or sub laterals reaches.
(c) During this, voltages at the points from where the laterals are branching
off from this main feeder or laterals or sub laterals are stored as branch
off voltages of corresponding laterals.
(d) Now if the end node of that main feeder or the lateral or the sub lateral
reaches, RBF order is decreased by one and go to 6 (b) until the
calculation of the lateral of RBF order one reaches.
22
7. After completion of the backward and forward sweep for the first iteration, end
node voltages are updated.
8. This new end node voltage is compared with the previous initialized end node
voltages (only for first iteration) or the end node voltages of the previous iteration.
9. If these compared end node voltages values are less than a small error value, it
means that the load flow has converged otherwise go to 5 and do the backward
and forward sweep repeatedly considering the new end node voltages.
2.2.4 Load Flow Calculation
The load flow of a single source network can be solved iteratively from two sets of
recursive equations. The first set of equations for calculation of the power flow through the
branches by starting from the ending buses and moving in the backward direction towards the
source bus (substation bus). The other set of equations are for calculating the voltage
magnitude and angle of each node starting from the slack bus (substation bus) and moving in
the forward direction towards the ending bus. These recursive equations are derived as follows.
The fig. 2.1 shows the single – line diagram of n-bus radial distribution system.
Consider a branch ‘ ij ’ is connected between the buses ‘ i’ and ‘ j ’.
2.2.4.1 Backward sweep
The updated effective power flows in each branch are obtained in the backward sweep
computation by considering the bus voltages of previous iteration. It means the voltage values
obtained in the forward path are held constant during the backward sweep and updated power
flows in each branch are transmitted backward along the feeder using backward path. This
indicates that the backward sweep starts at the extreme end bus and proceeds towards source
bus (substation bus). The active and reactive power flows are calculated in backward direction.
The effective active (iP ) and reactive (
iQ ) powers that of flowing through branch ‘ ij ’
from node ‘ i ’ to node ‘ j ’ can be calculated backwards from the ending bus and is given as,
( )' 2' 2
2i
j j
j L j ij
j
QPRP P P
V
+= + + ⋅ (2.1)
( )' 2' 2
2
j j
iji L jj
j
QPQQ Q X
V
+= + + ⋅ (2.2)
23
Where 'Ljj j PP P += and
'
Ljj jQ QQ +=
LjP and LjQ are loads that are connected at bus ‘ j ’
jP and jQ are the effective real and reactive power flows from bus ‘ j ’.
2.2.4.2 Forward sweep
The purpose of the forward sweep is to calculate the voltages at each bus starting from the
feeder source bus (substation bus). The feeder substation voltage is set at its actual value. During the
forward propagation the effective power in each branch is held constant to the value obtained in
backward walk. The voltage magnitude and angle at each bus are calculated in forward direction.
Consider a voltage iV iδ at bus ‘ i ’ and jV jδ at bus ‘ j ’, then the current flowing
through the branch ‘ ij ’ having an impedance, ij i ji j
R j XZ += connected between ‘ i ’
and ‘ j ’ is given as,
( )i ji j
i j
i j i j
VVI
jR X
δ δ−=
+
(2.3)
And
( )i j
i i
i i
jQPI
V δ
−=
−
(2.4)
On equating the equation (2.3) and (2.4), we have
( ) ( )i i i jji
i j i ji i
VVjQP
jV R X
δ δ
δ
−−=
+−
(2.5)
( ) ( )( )2
i i i jj ii j i jijXjQV P RV V δ δ− = − +−
(2.6)
By equating real and imaginary parts on both sides of equation (2.6), we have
( ) ( )2
cos ii j i ij i i j i jV V R Q XV Pδ δ− = − + (2.7)
( )sini j i i i j i i jj
Q R P XVV δ δ− = − (2.8)
Squaring and adding equations (2.7) and (2.8), we get
( ) ( )2 2 22
i ii j ii i j i j i i j i jV R X Q R XQV V P P= + − + − (2.9)
( ) ( ) ( )( )2 2 24 2 2 22i j i i j i j ii i ii i j i j
V R XQ QVV V P R X P= − + + + + (2.10)
24
( ) ( ) ( )1
222
2 2 2
22
i i
iij i j i ji i ji ji
QPXQRV V P R X
V= +
− + + +
(2.11)
and voltage angle , jδ can be derived on diving equations (2.8) and (2.7)
( )( )2
tani i j i i j
j i
i ii i j i j
Q R P X
V R XQPδ δ
−− =
− +
(2.12)
( )
1
2tan
ii i j i jj i
i ii i j i j
Q R XP
V R XQPδ δ −
−= +
− +
(2.13)
The magnitude and the phase angle equations can be used recursively in a forward direction to
find the voltage and angle respectively of all buses of radial distribution system.
2.2.4.3 Convergence criterion
The voltages calculated in the previous and present iterations are compared. In the
successive iterations if the maximum mismatch between the voltages is less than the specified
tolerance i.e., 0.0001, the solution is said to be converged. Otherwise new effective power
flows in each branch are calculated through backward walk with the present computed
voltages and then the procedure is repeated until the solution is converged
2.2.4.4 Active and Reactive power losses calculation
The active and reactive power losses of branch ‘ ij ’can be calculated as,
22
2( , )
iL o s s
ii j
i
QPi jP R
V
+= ⋅ (2.14)
22
2( , )
i ii jL o s s
i
QPi jQ X
V
+= ⋅ (2.15)
The total active and reactive power loss of radial distribution system can be calculated as,
( ) ( )2 22 21
, 2 21 1
n nbi ii i
T Loss i j i ji j i j
i i
Q QP PP R R
V V
−
= =
+ += ⋅ = ⋅∑ ∑ (2.16)
( ) ( )2 22 2
1
, 2 21 1
n nbi ii i
i j i jT Lossi j i j
i i
Q QP PQ X X
V V
−
= =
+ += ⋅ = ⋅∑ ∑ (2.17)
25
2.2.4.5 Voltage deviation calculation
The voltage deviation of the system is defined as
,
1
n
i nom ii
V VVD=
= −∑ (2.18)
where , , 1 .i nom i rated p uV V= =
(2.19)
2.2.4.6 Voltage stability index calculation
From Fig.2.1, current that of flowing through branch ‘ ij ’from bus ‘ i ’ to bus ‘ j ’ can
be calculated as
i ji j
i j i j
V VI
jR X
−=
+ (2.20)
*' '
i jjj jj V IQP − = (2.21)
Eq. (2.22) gives the voltage stability index at all buses in RDS, was proposed by Chakravorty
et al [67]. Using eq. (2.20) and (2.21) :
2 24 4 4j j ijj ij ijj ji iij
V VQ QX R RSI P P X = − − − + (2.22)
0jSI > , indicates stable operation of RDS.
Objective function for improving voltage stability index is given by (2.23):
1
j
VSISI
=
, 2, 3, ......j n= (2.23)
The maximum value of jSI gives minimum value of objective function (VSI ). So, minimum
values of objective function indicate improvement of voltage stability index. .
26
2.3 Algorithm for Load Flow Calculation
The flow chart for load flow is shown in fig.2.2. The backward forward sweep load
flow algorithm is given below
Start
Read line & load data
Set flat voltages [1 p.u] for all buses (nodes)
Computer effective real & reactive power flows of
all branches using backward sweep from equations
[2.1] & [2.2]
Update bus voltages & phase angles using forward sweep
from equations [2.11] &[2.13]
Is load flow
converged
Compute branch power losses, total system losses, total system voltage
deviation, total system voltage stability index & print the results.
Stop
No
Yes
Fig.2.2: Flow chart for Radial Distribution Load Flow
27
Step 1 : Read distribution system line and load data. Assume initial bus voltages are 1
p.u and set ε = 0.0001.
Step 2 : Start iteration count, IT =1.
Step 3 : Initialize active power loss and reactive power loss vectors to zero.
Step 4 : Calculate the effective active and reactive power flow in each branch using
equations (2.1) and (2.2).
Step 5 : Calculate bus voltages, active and reactive power loss of each branch using
equations (2.11), (2.14), and (2.15) respectively.
Step 6 : Check for convergence i.e., max
V∆ < ε in successive iterations.
If it is converged go to next step otherwise increment iteration number and go to step 4.
Step 7 : Calculate the active and reactive power losses for all branches, total real and
reactive power loss, voltage deviation of each bus, total voltage deviation,
voltage stability index of each bus and voltage stability index of system.
Step 8 : Print voltage at each node, the active and reactive power losses of all branches,
total active and reactive loss, total voltage deviation and voltage stability index
of system.
Step 9 : Stop.
2.4 Simulation Results and Analysis
The proposed method computes the load flow solution for the given RDS. The
effectiveness of the proposed method is tested on 33 and 69 bus RDS.
2.4.1 Test system -1 (33 bus RDS)
The test system -1 is a 12.66 kV, 33 bus RDS consisting of 33 buses configured with
one substation, one main feeder, 3 laterals and 32 branches. The total active and reactive loads
on this system are 3715 kW and 2300 kVAr, respectively. It is demonstrated in Fig. A.1 [68].
The line and load data of this system is given in appendix Table A.1 & A.2 .
28
Table 2.1 gives results of voltage magnitude and angles at different buses of this system. The
voltage magnitude and angles at different buses of this system are given in Fig.2.3 & Fig.2.4
respectively. The minimum voltage is 0.9042 p.u at bus 18 and maximum voltage regulation
is 9.58%.
Table 2.1: Voltage magnitudes and angles of 33 bus RDS
Bus No. Voltage Magnitude (p.u) Voltage Angle
1 1.0000 0
2 0.9970 0.0002
3 0.9829 0.0017
4 0.9754 0.0028
5 0.9680 0.0040
6 0.9496 0.0024
7 0.9462 -0.0017
8 0.9326 -0.0046
9 0.9262 -0.0060
10 0.9204 -0.0073
11 0.9195 -0.0072
12 0.9180 -0.0070
13 0.9119 -0.0088
14 0.9096 -0.0102
15 0.9082 -0.0109
16 0.9068 -0.0114
17 0.9048 -0.0128
18 0.9042 -0.0130
19 0.9965 0.0000
20 0.9929 -0.0011
21 0.9922 -0.0015
22 0.9916 -0.0018
23 0.9793 0.0011
24 0.9727 -0.0004
25 0.9693 -0.0012
26 0.9477 0.0031
27 0.9452 0.0042
28 0.9338 0.0058
29 0.9256 0.0073
29
30 0.9220 0.0092
31 0.9179 0.0078
32 0.9169 0.0074
33 0.9167 0.0073
Fig.2.3: Bus voltage magnitude (p. u.) of each bus in 33 bus RDS
Fig.2.4: Bus voltage angle (deg.) of each bus in 33 bus RDS
0 5 10 15 20 25 30 350.9
0.92
0.94
0.96
0.98
1
1.02
1.04
1.06
Bus No.
Voltage m
agnitude (p.u.)
0 5 10 15 20 25 30 35-0.06
-0.04
-0.02
0
0.02
0.04
0.06
Bus No.
Voltage angle (deg.)
30
Table 2.2 gives results of active power and reactive power losses of each branch of the
system. The real power and reactive power losses of each branch of the system are given in
Fig. 2.5 & Fig. 2.6 respectively. The total active and reactive power losses of the system are
210.07 kW and 142.53 kVAr respectively. The active and reactive power losses are 5.65%
and 6.19% of their total loads.
Table 2.2: Power loss of 33-bus RDS
Br. No. Bus Active power loss
PLoss (kW)
Reactive power loss
Q Loss (kVAr) SE RE
1 1 2 12.2467 6.3359
2 2 3 51.8257 26.3964
3 3 4 19.9247 10.1474
4 4 5 18.7226 9.5357
5 5 6 38.2964 33.0593
6 6 7 1.9441 6.4265
7 7 8 11.8608 8.5598
8 8 9 4.2612 3.0614
9 9 10 3.6291 2.5724
10 10 11 0.5642 0.1865
11 11 12 0.8980 0.2969
12 12 13 2.7177 2.1382
13 13 14 0.7433 0.9784
14 14 15 0.3641 0.3241
15 15 16 0.2870 0.2096
16 16 17 0.2566 0.3426
17 17 18 0.0542 0.0425
18 18 19 0.1610 0.1536
19 19 20 0.8322 0.7499
20 20 21 0.1008 0.1177
21 21 22 0.0436 0.0577
22 22 23 3.1816 2.1739
23 23 24 5.1438 4.0618
24 24 25 1.2875 1.0074
25 25 26 2.5950 1.3218
26 26 27 3.3223 1.6916
31
27 27 28 11.2810 9.9462
28 28 29 7.8210 6.8135
29 29 30 3.8896 1.9812
30 30 31 1.5934 1.5748
31 31 32 0.2132 0.2485
32 32 33 0.0132 0.0205
Total loss 210.0756 142.5337
Fig.2.5: Active power loss (kW) of each branch in 33 bus RDS
Fig.2.6: Reactive power loss ( kVAr) of each branch in 33 bus RDS
0 5 10 15 20 25 30 350
10
20
30
40
50
60
Branch No.
Active power loss
( kW
)
0 5 10 15 20 25 30 350
5
10
15
20
25
30
35
Branch No.
Reactive power loss
( kW
)
32
Comparison of load flow results between the proposed method and the existing method [69] is
given in Table 2.3. The total active and reactive power losses are reduced and the minimum
voltage is improved in the proposed method.
Table 2.3: Comparison of load flow results of 33 bus RDS
Description
Total active
power loss ,
P Loss (kW)
Total reactive
power loss,
Q Loss ( kVAr )
Minimum
Voltage and it’s
bus number
CPU
time(s)
Existing method [69] 210.80 143.11 0.9038 at bus 18 2.944659
Proposed method 210.07 142.53 0.9042 at bus 18 2.822436
Table 2.4 gives results of voltage deviation and voltage stability index of the system. The
voltage deviations of each bus of the system is given in Fig. 2.7. The voltage stability index of
each bus of the RDS is given in Fig. 2.8.
Table 2.4 : Voltage deviation & Voltage stability index of 33 bus RDS
System VD in p.u. VSI
33 bus 0.1338 1.4960
Fig. 2.7: Bus voltage deviation ( VD ) in p.u of each bus in 33 bus RDS
0 5 10 15 20 25 30 350
0.02
0.04
0.06
0.08
0.1
0.12
0.14
Bus No.
Volt
age d
evia
tion ( p
.u. )
33
Fig.2.8: Voltage stability index (VSI ) of each bus in 33 bus RDS
2.4.2 Test system -2 (69 bus RDS)
The test system -2 is a 12.66 kV, 69 bus large scale RDS consisting of 69 buses
configured with one substation, one main feeder, 7 laterals and 68 branches. The total active
and reactive loads on this system are 3802.19 kW and 2694.6 kVAr, respectively. It is
demonstrated in Fig. A.2 [70]. The line and load data of this system is given in appendix
Table A.3 & A.4 .
Table 2.5 gives results of voltage magnitude and angles at different buses of this system. The
voltage magnitude and angles at different buses of this system are given in Fig.2.9 & Fig.2.10
respectively. The minimum voltage is 0.9101 pu at bus 65 and maximum voltage regulation is
8.99%.
Table 2.5: Voltage magnitudes and angles of 69 bus RDS
Bus No. Voltage Magnitude Voltage Angle
1 1.0000 0
2 1.0000 -0.0000
3 0.9999 -0.0000
4 0.9998 -0.0001
5 0.9990 -0.0003
6 0.9901 0.0012
7 0.9809 0.0027
8 0.9787 0.0031
9 0.9776 0.0033
0 5 10 15 20 25 30 351
1.1
1.2
1.3
1.4
1.5
1.6
Bus No.
Voltage sta
bility index (p.u)
34
10 0.9726 0.0048
11 0.9715 0.0052
12 0.9683 0.0062
13 0.9654 0.0070
14 0.9626 0.0079
15 0.9597 0.0087
16 0.9592 0.0089
17 0.9583 0.0092
18 0.9583 0.0092
19 0.9578 0.0093
20 0.9575 0.0094
21 0.9570 0.0096
22 0.9570 0.0096
23 0.9570 0.0096
24 0.9568 0.0097
25 0.9566 0.0097
26 0.9566 0.0098
27 0.9566 0.0098
28 0.9999 -0.0000
29 0.9999 -0.0001
30 0.9998 -0.0000
31 0.9997 -0.0000
32 0.9997 0.0000
33 0.9995 0.0001
34 0.9992 0.0002
35 0.9992 0.0003
36 0.9999 -0.0001
37 0.9997 -0.0002
38 0.9996 -0.0002
39 0.9995 -0.0002
40 0.9995 -0.0002
41 0.9988 -0.0004
42 0.9986 -0.0005
43 0.9985 -0.0005
44 0.9985 -0.0005
45 0.9984 -0.0005
46 0.9984 -0.0005
47 0.9998 -0.0001
48 0.9985 -0.0009
35
49 0.9947 -0.0034
50 0.9942 -0.0037
51 0.9786 0.0031
52 0.9786 0.0031
53 0.9748 0.0038
54 0.9716 0.0044
55 0.9671 0.0052
56 0.9628 0.0060
57 0.9407 0.0140
58 0.9298 0.0180
59 0.9256 0.0196
60 0.9206 0.0217
61 0.9133 0.0233
62 0.9130 0.0233
63 0.9126 0.0234
64 0.9107 0.0238
65 0.9102 0.0240
66 0.9714 0.0052
67 0.9714 0.0052
68 0.9680 0.0063
69 0.9680 0.0063
Fig.2.9: Bus voltage magnitude (p. u.) of each bus in 69 bus RDS
0 10 20 30 40 50 60 70
0.92
0.94
0.96
0.98
1
1.02
1.04
Bus No.
Voltage m
agnitude (p.u.)
36
Fig.2.10: Bus voltage angle (deg.) of each bus in 69 bus RDS
Table 2.6 gives results of active power and reactive power losses of each branch of the
system. The active power and reactive power losses of each branch of the system are given in
Fig. 2.11 & Fig. 2.12 respectively. The total active and reactive power losses of the system are
224. 54 kW and 101.96 kVAr respectively. The active and reactive power losses are 5.91%
and 3.78% of their total loads.
Table 2.6: Power loss of 69 bus RDS
Br.
No.
Bus P Loss (kW) Q Loss (kVAr)
SE RE
1 1 2 0.0746 0.1792
2 2 3 0.0746 0.1792
3 3 4 0.1947 0.4673
4 4 5 1.9333 2.2645
5 5 6 28.1910 14.3574
6 6 7 29.2967 14.9213
7 7 8 6.8821 3.5082
8 8 9 3.3687 1.7151
9 9 10 4.7716 1.5771
10 10 11 1.0135 0.3351
11 11 12 2.1886 0.7233
12 12 13 1.2837 0.4237
13 13 14 1.2449 0.4114
0 10 20 30 40 50 60 70-0.04
-0.02
0
0.02
0.04
0.06
Bus No.
Voltage angle (deg.)
37
14 14 15 1.2040 0.3978
15 15 16 0.2237 0.0740
16 16 17 0.3202 0.1059
17 17 18 0.0026 0.0009
18 18 19 0.1041 0.0344
19 19 20 0.0669 0.0219
20 20 21 0.1074 0.0355
21 21 22 0.0005 0.0002
22 22 23 0.0051 0.0017
23 23 24 0.0112 0.0037
24 24 25 0.0060 0.0020
25 25 26 0.0025 0.0008
26 26 27 0.0003 0.0001
27 3 28 0.0003 0.0007
28 28 29 0.0021 0.0051
29 29 30 0.0041 0.0014
30 30 31 0.0007 0.0002
31 31 32 0.0036 0.0012
32 32 33 0.0087 0.0029
33 33 34 0.0060 0.0020
34 34 35 0.0005 0.0002
35 3 36 0.0014 0.0034
36 36 37 0.0151 0.0369
37 37 38 0.0173 0.0202
38 38 39 0.0050 0.0058
39 39 40 0.0002 0.0002
40 40 41 0.0487 0.0569
41 41 42 0.0201 0.0235
42 42 43 0.0027 0.0031
43 43 44 0.0005 0.0006
44 44 45 0.0061 0.0077
45 45 46 0.0000 0.0000
46 4 47 0.0233 0.0575
47 47 48 0.5828 1.4265
48 48 49 1.6334 3.9968
49 49 50 0.1159 0.2835
50 8 51 0.0018 0.0009
51 51 52 0.0000 0.0000
52 9 53 5.7695 2.9378
38
53 53 54 6.6977 3.4116
54 54 55 9.1058 4.6362
55 55 56 8.7717 4.4685
56 56 57 49.5807 16.6423
57 57 58 24.4380 8.2011
58 58 59 9.4858 3.1370
59 59 60 10.6484 3.2323
60 60 61 13.9966 7.1293
61 61 62 0.1118 0.0569
62 62 63 0.1346 0.0685
63 63 64 0.6597 0.3360
64 64 65 0.0411 0.0209
65 11 66 0.0026 0.0008
66 66 67 0.0000 0.0000
67 12 68 0.0233 0.0077
68 68 69 0.0000 0.0000
Total loss 224. 5407 101. 9661
Fig.2.11: Active power loss (kW) of each branch in 69 bus RDS
0 10 20 30 40 50 60 700
10
20
30
40
50
60
Branch No.
Real pow
er loss
(kW
)
39
Fig. 2.12 : Reactive power loss ( kVAr) of each branch in 69 bus RDS
The load flow results of the proposed method are compared with the existing method
[69] in Table 2.7. The total active and reactive power losses are reduced and the minimum
voltage is improved by the proposed method.
Table 2.7: Comparison of load flow results of 69 bus RDS
Description
Total active
power loss ,
P Loss (kW)
Total reactive
power loss ,
Q Loss (kVAr)
Minimum
Voltage and it’s
bus number
CPU
time (s)
Existing method [69] 224.79 102.28 0.9092 at bus 65 4.471
Proposed method 224.54 101.96 0.9102 at bus 65 3.936
Table 2.8 gives results of voltage deviation and voltage stability index of the system. The
voltage deviations of each bus of the system is given in Fig. 2.13. The voltage stability index
of each bus of the RDS is given in Fig. 2.14.
Table 2.8: Voltage deviation & Voltage stability index of 69 bus RDS
System VD in p.u. VSI
69 bus 0.0993 1.4571
0 10 20 30 40 50 60 700
5
10
15
20
Branch No.
Reactive p
ow
er loss
( k
W )
40
Fig.2.13: Bus voltage deviation ( VD ) of each bus in 69 bus RDS
Fig.2.14: Voltage stability index (VSI ) of each bus in 69 bus RDS
2.5 Conclusions
In this chapter radial distribution load flow method is described. It is tested over two
balanced radial distribution systems. The proposed backward and forward sweep technique
gives advantages over the other load flow techniques. It does not employ complicated
calculations, i.e. the derivatives of the power flow equations. It is flexible and easily
accommodates changes that may occur in any RDS. These changes could be modifications or
0 10 20 30 40 50 60 700
0.02
0.04
0.06
0.08
0.1
Bus No.
Voltage devia
tion (p.u.)
0 10 20 30 40 50 60 701
1.1
1.2
1.3
1.4
1.5
Bus No.
Voltage sta
bility index (p.u)
41
additions of transformers, capacitors, distributed generators, other systems or both to the
distribution system.
The proposed backward and forward sweep technique is easy to program and has the
fastest CPU computation time when compared to other radial and conventional power flow
methods. Such advantages make the backward and forward sweep technique a suitable choice
for planning and real-time computations. The iterative techniques commonly used in
transmission networks are not suitable for distribution power flow analysis because of poor
convergence characteristics. It is found that the propose load flow method is suitable for fast
convergence characteristics.