Diagnostico Bus TermoKing

download Diagnostico Bus TermoKing

of 75

Transcript of Diagnostico Bus TermoKing

  • 8/13/2019 Diagnostico Bus TermoKing

    1/75

  • 8/13/2019 Diagnostico Bus TermoKing

    2/75

    CONVERSIONS ENGLISH TO METRIC

    1 Btu = 252 Gram-calories1 Btu/Hr =.252 K cal/Hr

    1 Btu/Hr-F =.453 K cal/Hr.C

    1 Btu/Hr-Ft2-F = 4.88 K cal/Hr-M2-C

    1 Cfm = 28.32 Liters/Minute

    1 Cfm = 1.7 Cubic Meters/Hr

    5/9 (F-32) = C

    1 Foot =.3048 Meter

    1 Square Foot =.0929 Square Meter

    1 Cubic Foot =.0283 Cubic Meter

    1 Gallon = 3.785 Liter1 Inch = 2.54 Centimeters

    1 Square Inch = 6.452 Square

    Centimeters

    1 Cubic Inch = 16.39 Cubic Centimeters

    1 Inch H20 = 2.54 Grams/CM2

    1 Pound = 453.6 Grams

    1 PSI =.07031 Kg/CM2

    1 Watt = 3.413 Btu/Hr

    Micron =.0000001 Meters

    This Manual is published for informational purposesonly and the information so provided should not be

    considered as all-inclusive or covering all contingencies.

    If further information is required, Thermo King

    Corporation should be consulted.

    Thermo Kings warranty will not apply to any equipment

    which has been so repaired or altered outside the

    manufacturers plants as, in the manufacturers

    judgment to effect its stability.

    No warranties, express or implied, including

    warranties of fitness for a particular purpose ormerchantability, or warranties arising from course

    of dealing or usage of trade, are made regarding the

    information, recommendations, and descriptions

    contained herein. Manufacturer is not responsible

    and will not be held liable in contract or in tort

    (including negligence) for any special, indirect or

    consequential damages, including injury or damage

    caused to vehicles, contents or persons, by reason

    of the installation of a Thermo King product or its

    mechanical failure.

  • 8/13/2019 Diagnostico Bus TermoKing

    3/75

    Table of Contents

    1

    Safety Cautions 3

    Responsible Refrigerant Handling 5

    T-series Flow Diagram 6

    R-series Flow Diagram 7

    Diagnosing A System With an EPR Valve 8

    Diagnosing A System Without an EPR Valve 9

    EPR Non-Mechanical Cooling Problems 10

    Conditions That Cause High Discharge Pressure 11

    Conditions That Cause Low Discharge Pressure 11

    Diagnosing Using The Liquid Line 11

    Refrigeration System Access Tools 12-13

    Compressor Service Valves 14

    Gauge Manifold Installation (Standard Hose Fittings) 15-16

    Gauge Manifold Installation (Low Loss Fittings) 17

    Gauge Manifold Removal 18

    Refrigerant Level Check 19-20

    Adding Refrigerant 21

    Charging An Evacuated Unit By Weight 22-23

    EPR Valve Adjustment 24-27

    Low Side Pump Down 28-29

    Compressor Pump Down 30

    Compressor Oil Pressure Check 31

    Compressor Oil Level Check 32

    Removing Compressor Oil 33

    Adding Compressor Oil 34-35

    Compressor Efficiency Test 36

    Air Gap Adjustment 37

    Testing For Air In System 38-39

    Superheat 40-41

    (Continued)

    SAFETY

    DIAGNOSTICS AND SERVICE TOOLS

    SERVICE PROCEDURES

  • 8/13/2019 Diagnostico Bus TermoKing

    4/75

    Table of Contents

    2

    Refrigerant Leak Check Tools 43

    Leak Characteristics 44

    Recommended Solders and Soldering Procedures 45-46

    Refrigerant Recovery 47

    Recovery From A Working Unit Without an Orit 10 Valve 48

    Recovery From A Working Unit With an Orit 10 Valve 49

    Recovery From Non-working Unit 50

    System Evacuation and Clean Up 51-52

    Multiple Evacuation 52

    Compressor Oil Acid Test 53

    Compressor Oil Filter Kit 54

    Suction Line Filter 54

    Refrigerant Types and Properties 55

    Temperature Pressure Relationships Chart 56-57

    Bus Refrigeration Terminology 59-72

    LEAK TESTING / SOLDERING / CLEAN UP

    REFRIGERANT TYPES AND PROPERTIES

    TEMPERATURE CHARTS

    GLOSSARY

  • 8/13/2019 Diagnostico Bus TermoKing

    5/75

    3

    Safety

    DO NOT EXPOSE REFRIGERANTTO OPEN FLAME AS TOXIC FUMES

    MAY BE RELEASED

    CAUTION: STAY CLEAR

    OF FANS AND OTHER

    MOVING PARTSAJA785

    CAUTION

    ALL SERVICE VALVES MUST BE

    BACK SEATED PRIOR TOREMOVING SERVICE PORT CAPS.

    NOTE: SOME VALVES MAY NOT

    HAVE A BACK SEAT.

    HAZARDOUS VOLTAGE

    CAN CAUSE SEVERE

    INJURY OR DEATH AJA786

  • 8/13/2019 Diagnostico Bus TermoKing

    6/75

    4

    Safety

    ALWAYSWear Eye Protection

    and Protective Clothing

    When Handling Refrigerant

    ALWAYSWear Eye and Ear

    Protection When ServicingRefrigeration Units

    CAUTION

    Bus climate control systems are controlled by a

    thermostat that may cycle the unit ON or OFF with

    no prior warning. Condenser and evaporator fanswill start when the unit is cycled ON by the thermo-

    stat. Do not wear loose fitting clothing or equip-

    ment around operating climate control systems.

    Always disconnect power to the unit before per-

    forming any maintenance procedures.

    AJA787

  • 8/13/2019 Diagnostico Bus TermoKing

    7/75

    5

    Safety

    Responsible Refrigerant Handling

    Knowledge and Skills

    Vital to Human Health

    Scientific Evidence indicates that CFC refrigerantscon-

    tribute to the depletion of the ozone layer and permits

    an increasein the harmful ultraviolet raysthat reach the

    earth.

    Protecting the ozone layer through responsible refrigerant

    handling is the responsibility of all refrigeration and air con-

    ditioning service technicians.

    Service Tools --Use the proper service tools. Gaugemanifold sets should include appropriate shutoff valves

    or disconnects near the end of each service line.

    Recovery Equipment -- Recovery equipment must be

    used. Proper recovering, storing and recycling of refrig-

    erants is an important part of all service work.

    Service Procedures -- Recommended procedures

    must be used to minimize refrigerant loss.

    Components may be isolated by closing service valves

    and performing system pump-downs.

    Components unable to be isolated for service must be

    repaired only after refrigerant is properly recovered.

    ALWAYSHANDLE REFRIGERANT RESPONSIBLY

    AND PREVENT REFRIGERANT LOSS

    TO THE ATMOSPHERE.

  • 8/13/2019 Diagnostico Bus TermoKing

    8/75

    6

    Diagnostics and Service Tools

    T SERIESBUS CLIMATE CONTROL SYSTEM

    AJA789

    AJA788

  • 8/13/2019 Diagnostico Bus TermoKing

    9/75

    7

    Diagnostics and Service Tools

    R SERIESBUS CLIMATE CONTROL SYSTEM

    AJA791

  • 8/13/2019 Diagnostico Bus TermoKing

    10/75

    8

    Diagnostics and Service Tools

    Diagnosing a System with a EPR Valve

    SUCTIONLINE

    A. COMPRESSOR SUCTION PRESSURE

    Condition Low High

    Frosty/Cold 1. Normal operation: Bus iscontrolling thermostat withlight load and/or at higherspeeds.

    2. EPR valve set too high.3. Airflow through evap. is low.

    Air filter dirty. Evaporator coil dirty.

    4. EPR valve set too low: Coil frosted up.

    5. Evaporator Blower Motor. Low Voltage.

    ElectricalMalfunction.

    Fan Blades -Damaged, Location,Direction.

    1. Normal operation: Heavy load on the

    evaporator2. Expansion valve malfunction:

    Feeler bulb making poorcontact with suction line

    Needle erodedvalvecan not control properly

    Adjustment has beenincorrectly set (lowsuperheat)

    Dry/Warm 1. Low refrigerant charge.2. Restriction in liquid line.3. Expansion valve malfunction:

    Inlet screen plugged. Adjustment has been

    incorrectly set (highsuperheat).

    Feeler bulb lostcharge.

    4. Too much oil in system.5. Restricted suction line.6. Airflow through condenser

    coil too cold.

    1. Compressor malfunction: Leaking discharge

    valves. Leaking piston reeds. Worn piston/sleeve

    assembly (blow-by).2. Heavy load on evaporator:

    Compressor turning tooslowly.

    Belts slipping. Clutch slipping.

    B. COMPRESSOR DISCHARGE PRESSURE

    Low High

    Suction LineConditionDoes Not

    Apply

    1. Low refrigerant charge.2. Light load on evaporator:

    Bus interiortemperature cool.

    Dirty air filters. EPR set too lowcoil

    frosted up. Airflow through

    evaporator is low forsome reason.

    3. EPR valve incorrectlyadjustedtoo high causinglow refrigerant flow.

    4. Compressor speed low.5. Airflow through condenser is

    cold.6. Restrictions to refrigerant

    flow: Liquid line restricted Suction line blockage

    1. Airflow into the condenser is lowor restricted: Dirty coil. Debris in the coi l in let .

    2. Condenser fan or motorproblem: Motor running on low

    speed. Motor not running

    electrical malfunction. Fan blade(s) broken or

    incorrectly adjusted.3. Restriction on high side of the

    system: In-line service valve

    partially closed.4. Non-condensables in system:

    Air, ni trogen, and othergases(?).

    5. Hot air entering the condensercoil.

  • 8/13/2019 Diagnostico Bus TermoKing

    11/75

    9

    Diagnostics and Service Tools

    Diagnosing a System without a EPR Valve

    SUCTIONLINE

    A. SUCTION PRESSURE

    Condition Low High

    Frosty/Cold 1. Restricted airflow throughthe evaporator coil Iced up evaporator

    coil Dirty evaporator

    coil Plugged evaporator

    filter2. Evaporator blower motor

    Low voltage Electrical

    malfunction

    Fan bladesdamage, location,direction

    1. Expansion valve malfunction: Feeler bulb making poor

    contact Valve adjustmentopen

    too much (lowsuperheat)

    Valve needle eroded2. Overcharge of refrigerant

    Dry/Warm 1. Low refrigerant charge2. Restricted drier3. Expansion valve

    malfunction:Plugged screendirt, waxValve adjustmentclosedtoo much (high superheat)Internally frozenexpansion valveice frommoistureFeeler bulb lost charge

    4. Overfill of compressor oil5. Restricted line in low side6. Airflow through condenser

    coil too cold

    1. Leaking discharge valve plates2. Leaking piston reed3. Worn piston/sleeve assembly

    blow-by4. Heavy load on evaporator5. Compressor turning slowly6. Belt or clutch slipping

    B. DISCHARGE PRESSURE

    Low High

    N/A 1. Low refrigerant charge2. Cold air across condenser

    coil3. Discharge valve plates

    leaking4. Piston reed leaking5. Inadequate compressor rpm6. Low side restrictions

    1. Overcharge of refrigerant2. Air in the system3. Airflow restricted across

    condenser coil: Dirty condenser coil

    4. Condenser motor: Low voltage Electrical malfunct ion Fan blade damage/

    location5. Restriction in discharge side6. Nitrogen left in system7. Hot air across condenser coil

    N/A Does not apply.

  • 8/13/2019 Diagnostico Bus TermoKing

    12/75

    10

    Diagnostics and Service Tools

    Non-Mechanical Cooling Problems

    Check the suction line near the compressor. A cool, moist

    line is normal. When line condition and refrigeration pres-

    sures are near normal, look for problems outside of the

    refrigeration system.

    1. Excess Cooling Load.a. Open doors.

    b. Open windows.

    c. Open escape hatch.

    d. Large load of passengers.

    e. Damaged, deteriorated insulation.

    2. Dirty return air filter and/or evaporator coil.

    The suction lineshould feel cool orcool and moist

    AJA793

    AJA794

  • 8/13/2019 Diagnostico Bus TermoKing

    13/75

    11

    Diagnostics and Service Tools

    Conditions that can cause High Discharge Pressure

    1. Air or non-condensables in system.

    2. Restricted air flow across condenser, dirty condenser

    fins, slow fan speed, fans running backwards, etc.

    3. A restriction in the high pressure line between the com-

    pressor and the receiver tank.

    4. Overcharge of refrigerant during warm ambients.

    5. Incorrect refrigerant.

    6. High ambient temperature.

    7. Heavy heat load in bus.

    Conditions that can cause Low Discharge Pressure

    1. Low refrigerant charge.2. Lowside restriction.

    3. Worn compressor.

    4. Cold ambient temperature.

    5. Incorrect refrigerant.

    6. Light heat load in bus.

    7. EPR valve closing too soon.

    8. Restricted drier.

    DiagnosingUsing the

    Liquid Line1. The liquid lineshould be

    slightly warmer

    than the sur-

    rounding air.

    a. A low refriger-

    ant charge may

    cause the liquid

    line

    to be warmer

    than normal.

    b. A liquid line

    restriction will

    cause the line to

    become cold

    after the point of

    restriction.

    The Liquid lineshould be warmerthan the surrounding air

    AJA795

  • 8/13/2019 Diagnostico Bus TermoKing

    14/75

    12

    Diagnostics and Service Tools

    Refrigeration System Access Tools

    ACCESS VALVE ACTUATOR TK 204-625

    Use the access valveactuator to removerefrigerant or oil from1/4 in. male flare fittings.

    Taking a compressor oil sample

    QUICK DISCONNECT ACCESS VALVE-TK 204-679Low loss fittings and quick disconnects keep pressure

    in the gauge lines when the gauge manifoldis removed from the system.

  • 8/13/2019 Diagnostico Bus TermoKing

    15/75

    13

    Diagnostics and Service Tools

    Use the gauge adapter fitting with pressure gauges to readpressures with minimal refrigerant or oil loss.

    GAUGE ADAPTER FITTING TK 204-626

    AJA799

    Compressor Oil Pressure Receiver Tank Pressure

    AJA804

  • 8/13/2019 Diagnostico Bus TermoKing

    16/75

    Service Procedures

    14

    COMPRESSOR SERVICE VALVES

    The suction service valve (SSV) is generally larger than the

    discharge service valve (DSV) but is built the same.

    Full Out-Valve Back Seated

    In 1/2 way-Valve Mid-seated

    WARNING: Service valve stems and service ports

    must be properly capped and torqued with seals or

    O-rings installed. STEMS AND PORTS NOT PROP-

    ERLY CAPPED WILL LEAK REFRIGERANT.

    AJA803

    Full Out,1/4 turn in-Cracked Open to Service Port

    Full In-Valve Front Seated

    AJA800 AJA802

    AJA801

    Service PortCap

    ServiceValve

    Stem Cap

    AJA805

  • 8/13/2019 Diagnostico Bus TermoKing

    17/75

    Service Procedures

    15

    Gauge Manifold Installation(Standard Hose Fittings)1. Remove the large service valve stem caps from the

    discharge and suction service valves. DO NOT remove

    the small service port caps!

    2. Turn both service valves fully counterclockwise to

    back-seat the valves and close the service ports.

    3. Remove the small service port caps from both service

    valves.

    4. Attach the low pressure gauge line to the suction ser-

    vice port. Leave the fitting loose. (This loose connec-

    tion will be used to purge air from the gauge manifold.)

    5. Attach the high pressure line to the discharge service

    port and secure the line finger tight.

    (Continued)

    DischargeServiceValve

    SuctionServiceValve

    AJA806

  • 8/13/2019 Diagnostico Bus TermoKing

    18/75

    Service Procedures

    16

    6. Turn the discharge service valve stem 1/4-turn clock-

    wise to open the service port. (The high pressure

    gauge should indicate pressure in the discharge side of

    the system.)

    7. Open the high side hand valve on the gauge manifo-

    fold. Purge air from the gauge manifold service line

    (yellow) and tighten the line fitting to the manifold hoseanchor.

    8. Open the low side hand valve on the gauge manifold

    and allow a small amount of refrigerant to escape from

    the loose suction service port fitting and tighten hose

    on SSV (This will purge air from the gauge manifold

    and the red and blue gauge manifold lines).

    9. Close both gauge manifold hand valves.

    10. Turn the suction service valve stem 1/4-turn clockwise

    to open the service port. (The low pressure gauge

    should indicate pressure in the suction side of the sys-

    tem.)

    WARNING! NEVER operate the compressor with the

    discharge service valve front seated. The valve is frontseated when the service valve stem is turned fully

    clockwise.

    connect tomanifold

    DSVvalvecracked

    SSVvalveback

    seated

    AJA807

  • 8/13/2019 Diagnostico Bus TermoKing

    19/75

    Service Procedures

    17

    Gauge ManifoldInstallation (LowLoss Fittings)

    1. Remove the large ser-

    vice valve stem caps

    from the discharge and

    suction service valves.

    DO NOT remove the

    small service port

    caps!

    2. Turn both service

    valves fully counter-clockwise to back seat

    the valves and close

    the service ports.

    3. Remove the small ser-

    vice port caps from

    both service valves.

    4. Attach the high pres-

    sure line (red) to the discharge service port and secure

    the line finger tight.

    5. Turn the discharge service valve stem 1/4-turn clock-

    wise to open the service port. (The high pressure

    gauge should indicate pressure in the discharge side of

    the system.)

    6. Open both hand valves on the gauge manifold.

    7. Purge the gauge manifold yellow service line. This is

    accomplished by slowly screwing a 1/4 inch flare fitting

    into the low loss fitting on the gauge manifold yellow

    service line. Allow a small amount of refrigerant to

    escape from the service line and then remove 1/4 flare

    fitting. Tighten the yellow service line fitting to the

    gauge manifold hose anchor. (See illustration)

    8. To purge the gauge manifold and low pressure line,

    slowly screw a 1/4 inch flare fitting into the low loss fit-

    ting on the low pressure (blue) line.

    9. Close both gauge manifold hand valves.10. Install the gauge manifold low pressure line (blue) on

    the suction service port.

    11. Turn the suction service valve stem 1/4-turn clockwise

    to open the service port. (The low pressure gauge indi-

    cates pressure in the suction side of the system.),

    WARNING! NEVER operate the compressor with the

    discharge service valve front seated. The valve is front

    seated when the service valve stem is turned fully

    clockwise.

    AJA808

  • 8/13/2019 Diagnostico Bus TermoKing

    20/75

    Service Procedures

    18

    Removing the Gauge Manifold

    NOTE:Minimize oil and refrigerant transfer. Use the fol-

    lowing gauge manifold removal procedure to maintain

    system integrity without the need to use a different

    gauge manifold for each type of refrigerant.

    1. Jumper the low pressure cut out.

    2. Operate the unit in the cool mode.

    3. Back seat the discharge service valve.

    4. Open both manifold hand valves.

    5. Front seat the suction service valve and pump down

    the compressor to a 20 vacuum. Turn the unit off.

    6. Establish compressor crankcase pressure between 1and 3 psig.

    7. Remove the gauge line from the suction service valve

    and cap the service port.

    8. Remove the gauge line from the discharge service

    valve and cap the service port.

    9. Back seat the suction service valve and cap the valve

    stem.

    10. Cap the discharge service valve stem.

    11. Secure all manifold lines to manifold hose anchors

    when the manifold is not in use.

    12. Remove low pressure jumper and reconnect wiring.

  • 8/13/2019 Diagnostico Bus TermoKing

    21/75

    Service Procedures

    19

    Check Refrigerant Charge Level

    The charge level is very important to the efficient operation

    of the unit, therefore, it must be checked as part of the

    MONTHLY MAINTENANCE. This service procedure

    addresses the method for checking and adding charge as

    necessary.

    Purpose: To have a charging procedure which will allow an

    air conditioning technician to properly charge the system,

    without over charging or under charging it, in all weather

    conditions.

    Scope: This bulletin supersedes all previous charging bul-

    letins. This procedure only covers T-Series units with sightglass indicators with a floating ball in the upper half of the

    receiver tank.

    Procedure:

    During a visual check, when the receiver tank ball is not

    floating in the upper sight glass, use the following "Top Off

    Procedure" to check and replace the required reserve

    charge (Locate and repair all leaks to stop further leakage).

    1. Follow standard Thermo King procedures and connect

    your service gauges to the compressor service valves

    or standard access ports. Be sure to purge the air from

    your lines.

    2. Start the bus and run the engine in the FAST IDLE

    MODE with the air conditioning turned on. This shouldbe between 1200 and 1600 compressor rpm. For

    buses without the fast idle mode, elevate engine speed

    until compressor speed is between 1200 and 1600

    rpm.

    NOTE: On some applications, a regular low idle engine

    speed will not allow you to see the correct refrigerant

    level and may result in an improperly charged system.

    3. If the system has not been running you must run the

    system long enough to separate the compressor oil

    from the refrigerant AND pull the bus INTERIOR down

    (or up) to WITHIN THE 65 TO 75 DEGREE RANGE.

    This may take sometime if conditions are extreme, buta minimum of 15 minutes should be allowed before

    checking the charge level.

    4. If the COMPRESSOR DISCHARGE PRESSURE is not

    ABOVE 250 psig, use a piece of cardboard to partially

    cover the condenser coil inlet grille.Do not shut off

    condenser fans to raise pressure.This will drive the

    pressure up into the range REQUIRED FOR CHECK-

    ING AND CHARGING.

  • 8/13/2019 Diagnostico Bus TermoKing

    22/75

    Service Procedures

    20

    5. Once the conditions of steps 2, 3 and 4 above have

    been met, check the ball in the receiver tank upper

    sight glass. The proper charge level for this "Top Off"

    procedure will have the ball floating at the top of the

    upper receiver tank sight glass.

    6. If the ball is not at the top of the sight glass, follow stan-

    dard Thermo King charging methods, add charge to

    the system until the ball floats to the top of the sight

    glass.

    Note: If the system is low on charge, leak check and

    repair accordingly.

    Note: Add liquid refrigerant on the low side,increasing the suction pressure no more than 25 psi.

    When charging the system from a properly "Evacuated"

    condition, (Refer to "Evacuating a System" procedure), we

    strongly recommend that you weigh in the charge. This will

    save you time and ensure the full reserve charge.

    NOTE: Refer to unit maintenance manual specification

    section for proper weight charge.

    CAUTION: Air in the system will tend to collect in the

    receiver tank forcing the refrigerant level down. If youhave air in your system, floating the ball may over-

    charge the system. Check your system for air before

    letting it go back into service.

    CAUTION: AIR IN THE SYTEM WILL ELEVATE OPER-

    ATING PRESSURES AND TEMPERATURES, which in

    turn will begin a severe degradation process. AND,

    which, if left unchanged, will result in system failure

    which is NOT COVERED UNDER YOUR THERMO KING

    WARRANTY.

  • 8/13/2019 Diagnostico Bus TermoKing

    23/75

    Service Procedures

    21

    Adding Refrigerant

    Todays refrigerants must be added as a liquid. Use this

    procedure to add liquid refrigerant to the low side of an

    operating unit. Bus should be at fast idle mode, 1200 to

    1600 RPM in compressor.

    1. Crack the discharge service valve (DSV) and open it to

    the service port.

    2. Mid-seat the suction service valve (SSV).

    3. Set the refrigerant bottle to withdraw liquid refrigerant.

    4. Operate the unit in cool and read the suction pressure.

    5. Slowly open the gauge manifold low pressure hand

    valve until suction pressure rises approximately 25 psigabove the normal operating pressure.

    6. Gauge must show 250 lbs. discharge pressure with R-

    22 and R-407C refrigerant.

    Gauge must show 150 lbs discharge pressure with R-

    12 and R-134A refrigerant.

    7. Closely watch the receiver tank top sight glass. Imme-

    diately stop adding refrigerant when refrigerant is seen

    at the top of the sight glass.

    8. Close the refrigerant bottle hand valve.

    9. Remove the gauge manifold in the recommended man-

    ner.

    Adding Refrigerant

    SSVMidseated

    DSVCrackedopen

    AJA809

  • 8/13/2019 Diagnostico Bus TermoKing

    24/75

    Service Procedures

    22

    Charging an Evacuated Unit by Weight

    1. Install a gauge manifold. Keep the unit off.

    2. Recover the refrigerant and evacuate the system.

    3. Place the refrigerant bottle on a scale and attach the

    manifolds service line.

    4. Open the bottle to withdraw liquid. Purge air from the

    service line as required.

    5. Record total refrigerant and container weight.

    6. Check the unit data plate or unit Maintenance Manual

    for refrigerant weight required.

    7. Mid seat the compressor discharge service valve.

    8. Open the discharge hand valve all the way on thegauge manifold and begin charging the unit. Refriger-

    ant flow can be felt as small pulsations on the manifold

    service line.

    9. Watch the scale and close the hand valve at the refrig-

    erant bottle when the correct charge has been added.

    10. If refrigerant flow stops before charging is complete,

    close discharge manifold hand valve and return the

    DSV to the cracked position. Add Liquid refrigerant into

    the SSV with the unit running as described in the Add-

    ing Refrigerant Procedure.

  • 8/13/2019 Diagnostico Bus TermoKing

    25/75

    Service Procedures

    23

    UNIT

    NOT

    RUNING

    Drawing shows liquidrefrigerant being added.

    DSVvalvemid-seated

    SSVvalvecracked

    open

    AJA810

    To charge an evacuated unit, add liquid refrigerant to

    the receiver tank or through the discharge service

    valve. KEEP THE UNIT OFF.

    To charge a running unit, add liquid through the

    suction service valve. Control refrigerant flow toincrease suction pressure approximately 25 psi.

    UNIT

    RUNNING

    IN COOL

    Drawing shows liquidrefrigerant being added.

    SSVvalvemid-seated

    DSVvalvecracked open

    AJA811

  • 8/13/2019 Diagnostico Bus TermoKing

    26/75

    Service Procedures

    24

    Date: October 3, 1997

    Service Bulletin

    Subject: Evaporator Pressure

    Regular (EPR) Adjustment

    Application: ALL Thermo King Bus

    units which are equipped with an

    EPR valve.

    (THIS PROCEDURE SUPERSEDES ALL PREVIOUS

    EPR VALVE ADJUSTMENT PROCEDURES)

    Read Me First:The purpose of the EPR valve is to limit how low the pres-

    sure inside of the units evaporator coil will go. Holding the

    pressure at or above a set value also limits how low the coil

    temperature can fall.The pressure and temperature, once

    they have moved above the EPR valve setting, are depen-

    dent on the heat load being accepted by the unit. The EPR

    valve should not allow the pressure to fall below the point of

    condensate freezing on the coil. To achieve that, the EPR

    valve will stop or restrict the flow of refrigerant to hold the

    pressure at or above the set point of the valve.

    Once this valve is properly set it does not get out ofadjustment. The valve is factory set, but should be

    checked as part of the delivery checkout procedure.

    Adjustment if required, should be done by qualified

    personnel only. NOTE: Improper adjustment of this

    valve may cause damage to the system.

    NOTE: The ambient temperature and the bus interior

    must be above 80 F.

    CAUTION: Do Not attempt to adjust this valve if the

    ambient and bus interior temperatures are not above

    80 F. Improper setting, and damage to the system may

    result.

  • 8/13/2019 Diagnostico Bus TermoKing

    27/75

    Service Procedures

    25

    Procedure For Checking And Adjusting The EPR Valve.

    1. Install service gauges on the compressor and jumper

    the low pressure cutout.

    2. Install a compound gauge on the pressure tap on the

    evaporator side of the EPR valve.

    3. Replace all covers removed to install the compound

    gauge on the EPR valve.

    4. Be careful not to pinch the hose on the compound

    gauge, seal all areas that will leak air when the unit is

    running.

    5. Start the Bus, run at either fast or slow idle for at least

    ten minutes. This will return the oil to the compressor.

    6. If necessary, turn the heat mode on and raise the inte-rior temperature above 80 F. Then return the unit to the

    cool mode.

    Note: you will need two people to finish the test.

    7. One person raises the engine/compressor speed to

    maximum governed speed. (If not governed 2/3-throttle

    point.)

    Caution: You must increase the compressor speed

    (step #7). If you dont, the set point will not be cor-

    rect and damage to the refrigeration system may

    result.

    (continued)

  • 8/13/2019 Diagnostico Bus TermoKing

    28/75

    Service Procedures

    26

    8. When the Bus engine is maintained at high speed, shut

    off the evaporator fan motor(s).

    9. Watch the compound gauge installed on the EPR

    valve. The pressure will drop and stabilize. This should

    take one minute or less.

    10. When the compound gauge stabilizes this is the set

    point. The set point should be at the pressure stated on

    the following table.

    11. There should be a large difference between the com-

    pound gauge [EPR valve] and the suction service valve

    gauge readings (20-30 PSI or the compressor may

    even go into a vacuum).

    Note: You may need to jumper the low side pres-sure cutout switch to be able to complete this set-

    ting procedure.

    Lower the engine/compressor speed to high idle and

    switch the evaporator fan motor(s) back on.

    12. Run the unit at high idle for more than 5 minutes to

    clear the liquid refrigerant in the coil or compres-

    sor damage may occur.

    13. If the EPR valve requires adjustment, turn the adjusting

    screw CW to increase the setting (raising coil tempera-

    ture/pressure) and CCW to decrease the setting (low-

    ering the coil temperature/pressure). Do not turn more

    than 1/4 turn at a time.

  • 8/13/2019 Diagnostico Bus TermoKing

    29/75

    Service Procedures

    27

    14. After every adjustment all covers must be reinstalled

    and then run for at least 5 minutes before retesting.

    15. If the setting is still incorrect, repeat steps 13 and 14.

    16. When the setting is correct, recheck the setting twice

    (steps #6 thru #13], you should get the same reading.

    17. When the test is complete remove all gauges, jumper

    wires and reinstall all covers back.

    18. Check the refrigerant charge, oil level and return to ser-

    vice.

    Filed: F:\Bus\Usrefdat\procedur\eprset.doc

    Type of EPR

    valve:

    ORIT-15 Large

    type

    ORIT-10 Small type

    Refrigerant: Set pressures: Set pressures:

    R-134a 24 +/-1 psig 24 +/-1 psig

    R-22 50 +/-1 psig 50 +/-1 psig

    R-407C 50+/-1 psig 50 +/-1 psig

    R-12 27+/-1 psig 27 +/-1 psig

  • 8/13/2019 Diagnostico Bus TermoKing

    30/75

    Service Procedures

    28

    Low Side Pump Down

    Purpose: To test for internal (high side to low side) leaks

    and to perform service on the low side without refrigerant

    loss.

    1. Check gauge manifold hose gaskets. They must not

    leak during this test or the system may be contami-

    nated with air!

    2. Jumper out low pressure cut out (LPCO).

    3. Install a calibrated gauge manifold on the SSV & DSV.

    4. On units with Orit 10 EPR valve, mount the service

    hose from the manifold gauge to the EPR service port.

    Then open the low side hand valve.On units with the Orit 15 EPR valve, shut the hand

    valve on the pilot valve.

    5. Run the unit in cool for ten minutes or longer.

    6. Front-seat the receiver tank outlet valve (RTOV).

    7. Pump down the lowside to a 25" vacuum.

    8. Stop the unit.

    9. Observe the low side gauge. Low side pressure should

    remain below a 15" vacuum for two minutes or longer.

    If pressure rises to zero and stops, there is a low side

    leak to the atmosphere.

    If pressure continues to rise above zero, the following

    may be responsible -

    Refrigerant boiling out of the compressor oil. (Restartunit and pump down to 25" vacuum.)

    High side to low side leaks at the compressor dis-

    charge valve plates or hot gas bypass valve if

    equipped.

    The following services can be performed with the low side

    pumped down and a slight positive pressure established on

    the low side:

    Add or remove refrigerant oil.

    Clean the expansion valve screen.

    Change the expansion valve.

    Replace the liquid line drier.

    Replace the compressor oil filter. Replace lowside tubing.

    Replace EPR valve.

  • 8/13/2019 Diagnostico Bus TermoKing

    31/75

    Service Procedures

    29

    Shut The HandValve on thePilot Valve(Orit 15 only)

    AJA813

  • 8/13/2019 Diagnostico Bus TermoKing

    32/75

  • 8/13/2019 Diagnostico Bus TermoKing

    33/75

    Service Procedures

    31

    Compressor Oil Pressure Check

    1. Install suction pressure gauge

    2. Install gauge on compressor port A. It may be neces-

    sary to pump down system and use a gauge line with a

    schrader valve depresser.

    3. With unit running observe gauge reading at compres-

    sor oil pump, this is both suction pressure and com-

    pressor oil pressure.

    4. Read the suction pressure gauge.

    5. Calculate oil pressure using the following sample as a

    guide:

    Pressure from port A 60 PSISuction pressure gauge reading - 25 PSI

    Net oil pressure* = 35 PSI*

    *Recommended net oil pressure should be

    between 15&45 PSI.

    PortA

    SchraderValvein fitting

    60 PSI 15-45PSI

    Suction pressureGauge

  • 8/13/2019 Diagnostico Bus TermoKing

    34/75

  • 8/13/2019 Diagnostico Bus TermoKing

    35/75

    Service Procedures

    33

    5. Ensure the unit is in COOL cycle. Check the oil level

    with a flashlight while unit is operating. The compressor

    oil level sight glass should indicate 1/4 to 1/2 full. If indi-

    cator reading is low, oil must be added; proceed to

    Adding Compressor Oil. If indicator reading exceeds

    1/2 level, oil must be removed; proceed to Removing

    Excess Oil.

    NOTE: The compressor must be pumped down if oil is

    added or removed. Pumping down the compressor

    causes the oil to indicate lower than during normal

    operation. Therefore, it is necessary to carefully note

    the difference in oil level between normal operation

    and when it is pumped down. Be sure to take this dif-ference into account when adding or removing com-

    pressor oil.

    Removing Excess Oil

    1. Pump the compressor down. Refer to Low Side Pump

    Down Procedure or Compressor Pump Down Proce-

    dure.

    2. After stopping the compressor use the manifold gauge

    set to adjust the compressor (low side) pressure to 1 to

    3 psi. (Pressure measured at the compressor suction

    service valve port).

    3. Loosen the drain plug (DO NOT REMOVE) allowingthe oil to drain SLOWLY while watching the level in the

    compressor sight glass.

    NOTE: Heavy foaming of the oil as it leaves the com-

    pressor may indicate an excess of refrigerant in the oil.

    Run the system longer to insure a warm sump. Then

    recheck level.

    4. Tighten the drain plug and leak check.

    5. Run the system again and confirm the refrigerant

    charge level as well as recheck the oil level before

    allowing the bus to return into service.

  • 8/13/2019 Diagnostico Bus TermoKing

    36/75

    Service Procedures

    34

    Adding Compressor Oil

    1. Estimate how much oil will be required to make the

    level adjustment.

    2. Perform a compressor pump down by following the

    procedure indicated in this manual.

    3. Stop the bus engine, turn off the bus power and operat-

    ing safety switch to insure that no one can start the bus

    while you are working on it.

    4. Front seat the compressor discharge service valve in

    addition to the suction service valve which was front

    seated in step #2 above.

    5. Balance pressures toestablish positive pressure

    and recover excess refrig-

    erant pressure.

    6. Confirm which oil is to be

    added to this system.

    7. Hook up a vacuum pump

    to your service gauges

    which were connected in

    step #2.

    8. Hook up another service

    hose to the oil pressure

    port on top of the compres-

    sor oil pump at the top rearof the compressor.

    9. Open the oil container.

    Never leave oil contain-

    ers open to the air for

    long periods of time.

    10. Put the hose from the oil pressure port into the con-

    tainer of oil. Turn on the vacuum pump and lower the

    pressure inside of the compressor to pull the oil into the

    sump through the compressor oil pump until the oil

    level is correct.

    11. Secure the oil pump pressure port and replace the cap.

    Continue evacuating the compressor sump area toremove all air and noncondensable gasses which were

    pulled in with the oil.

    Balance System

    bothvalvesfront-seated

    AJA815

  • 8/13/2019 Diagnostico Bus TermoKing

    37/75

    Service Procedures

    35

    12. When evacuation is complete, back seat all system

    valves, start the bus and A/C system and recheck the

    compressor oil level.

    13. Confirm the system refrigerant charge level, following

    the correct procedures (noted in this manual) adjust

    charge as required before allowing the bus to return to

    service.

    CAUTION: Always confirm which oil is in the system

    you are servicing before you add oil. The wrong oil can

    cause severe damage.

    1. Oil Drain Plug 7. Service Manifold Gauge

    2. Oil Fill Plug 8. Micron Gauge

    3. Oil Pump Port 9. Vacuum Pump

    4. Shut-off Valve 10. Measuring Container

    Filled w/ Compressor

    Oil

    5. Discharge Service Port 11. Compressor Oil Sight

    Glass

    6. Suction Service Port

  • 8/13/2019 Diagnostico Bus TermoKing

    38/75

    Service Procedures

    36

    Compressor Efficiency Test

    Purpose:

    Check the discharge valve plate reeds for leakage.

    Check the piston reeds for leakage.

    Check the piston to sleeve clearance.

    1. Install gauge manifold set to monitor system pressures.

    2. Bypass the Low Pressure Cutout (LPCO) to prevent

    the clutch from disengaging.

    3. Start and run the unit at fast idle for 15 minutes to stabi-

    lize system pressures.

    EXAMPLE: On an 80 F day, your discharge pressure

    will be approximately 240 psig.(With R-22 or407-C refrigerant.)

    4. Cover the inlet side of the condenser coil to increase

    the discharge pressure 70-100 psig higher than nor-

    mal.

    EXAMPLE: If your discharge pressure is 240 psig after

    15 minutes of operation, increase it 310-340 psig.

    5. Front seat the suction service valve.

    6. When the compressor reaches a 10 vacuum, observe

    the discharge pressure. It should read as follows:

    A. R-12 & R-134a 125 psig or higher

    B. R-22 & R-407C 190 psig or higher

    NOTE: If you cant increase the discharge pressurehigher than normal, check the following:

    Piston reed(s) or discharge valve plate reed (s) may be

    defective.

    Compressor may have excessive piston to sleeve

    clearance.

    Unit may be low on refrigerant.

    NOTE: If the compressor will not pull at least a 15 vac-

    uum, the piston reed may be defective or the piston to

    sleeve clearance may be excessive.

    If the compressor will pull a deep vacuum, but not stay

    below 15 of vacuum for at least 15 seconds after unitis turned off, the discharge valve reed(s) are defective.

  • 8/13/2019 Diagnostico Bus TermoKing

    39/75

    Service Procedures

    37

    Air Gap Adjustment

    1. Loosen the lock nuts on the three adjustment screws.

    2. Using a 3/32 in. (2.4 mm) Allen wrench, turn each

    adjustment screw in clockwise (CW) until the armature

    bottoms out on the pulley.

    3. Back each adjusting screw out counterclockwise

    (CCW) 1-1/2 turns. This equals a .045 in. (1.143 mm)

    air gap.

    4. Double check air gap with feeler gauge per procedure

    in step 3 of checking air gap (new clutch only).

    5. Tighten the lock nuts. Make sure the adjusting screw

    does not turn by holding it with an Allen

    wrench.

    6. Check the air gap in three different places 120 apart.

    NOTE: The clutch should be checked monthly dur-

    ing high usage periods

    Allen ScrewBottoms OutArmature

    AJA817

    Wrench Tightening Locknut

    3/32 in. (2.4 mm) Allen Wrench

  • 8/13/2019 Diagnostico Bus TermoKing

    40/75

    Service Procedures

    38

    Testing For Air In The System

    Ice Bath Sample Method Test

    This inexpensive method requires that a small amount of

    the systems refrigerant be placed in a sample bottle and

    the bottle submerged in an ice bath.

    Required Tools

    Manifold Set, Sampling Bottle, Micron Gauge, Vacuum

    Pump, Thermometer, Ice Water Bath Consisting of 75%

    Ice,

    Set of Refrigeration Wrenches to open and close valves.

    Manifold Set Hookup Procedure

    Attach manifold set as follows:

    1. Connect low side hose to sample bottle.

    2. Connect center hose to receiver tank service valve.

    Valve remains closed.

    3. Connect high side hose to evacuation pump.

    CAUTION: If hoses are not connected properly, gauge

    readings will be inaccurate.

    Ice Bath Test Procedure

    1. Open manifold gauges and evacuate all hoses, mani-

    fold and sample bottle to 500 microns.CAUTION: Check for leaks in the system.

    (continued)

    AJA819

    AJA820

  • 8/13/2019 Diagnostico Bus TermoKing

    41/75

    Service Procedures

    39

    2. Run the compressor to circulate any air that may be in

    the system.

    3. Close the high side gauge valve to isolate the micron

    gauge and pump.

    4. Open the receiver tank service valve to a count of four

    (4). Then close the valve and count four (4) again.

    5. Then close the low side gauge valve.

    6. Place the sample bottle into the ice bath for 15 to 20

    minutes. Stir the ice mixture occasionally.

    NOTE: An ice water bath must be 75% ice in small

    pieces and it should completely cover the sample. The

    smaller the tank, the faster the temperature will equal

    that of the ice water bath.CAUTION: The procedure of taking the sample is

    extremely important to avoid contaminating the

    sample.

    7. Compare low side gauge reading with your pressure/

    temperature chart for 32F (0C).

    R-12 = 30 psig (207.5 kPa)

    R-22 = 57.5 psig (396.4 kPa)

    R-134a = 27.3 psig (188.3 kPa)

    R-407c = 50.9 psig (356.3 kPa)

    READING MUST BE +/- ONE (1) psig (7 kPa).

    If pressures exceed specifications, the refrigerant must be

    reclaimed and the unit totally evacuated according toproper evacuation procedures. After the system has been

    evacuated, leak tested, and recharged with clean refriger-

    ant, reconfirm the system operation. If system operation is

    satisfactory, return the bus to service.

    CAUTION: If the air and other non-condensables are

    not removed, premature system failure will result.

    AJA821

    AJA822

  • 8/13/2019 Diagnostico Bus TermoKing

    42/75

    Service Procedures

    40

    Superheat

    Expansion Valve Measure (Superheat)

    NOTE. Be sure the temperature reading instrument and

    compound pressure gauge are accurately calibrated.

    Procedure:

    1. Pump down the low side into the receiver tank. Open

    the receiver tank outlet valve to bleed the pressure

    back to 1 to 3 psi in low side.

    2. Install pressure gauge in the expansion valve external

    equalizer line. This will indicate the pressure directly

    and accurately. Use the Temperature Pressure Chart inthis manual to convert the pressure reading into tem-

    perature.

    Measure suction line temperature at point where feeler

    bulb is attached.(See drawing)

    3. Open the receiver tank outlet valve and operate the

    unit for 15 minutes.

    4. Subtract temperature reading obtained by Temperature

    Pressure Chart conversion from the suction line tem-

    perature to obtain the expansion valve setting (Super-

    heat).

    Thermo Bulb Suction Line Temperature (F)

    -Suction Pressure Temperature Conversion (F)Superheat (F)

    NOTE: To establish stable condition, run the unit at

    least 15 minutes at 1000 rpm engine speed so the

    evaporator air inlet temperature reaches 70.0 to

    80.0 (F) (21.0 to 27.0 C). Read pressure and tempera-

    ture readings simultaneously. Temperature difference

    should be 10.0 to 15.0 (F) (5.5 to 8.0 C).

    CAUTION - Thermo King expansion valves are Factory

    preset and do not require adjustment. Itis very difficult

    to establish controlled conditions in the field to accu-

    rately adjust superheat. If it is verified that the super-

    heat is out of range and before attempting to adjust theexpansion valve, the following three causes for an out

    of range reading MUST be carefully checked.

    Check the following:

    1. Dirty air filters, or other cause of reduced air flow.

    2. Sensing bulb leaking, bulb placed improperly (on refrig-

    erant line, or bulb is not properly wrapped with insulat-

    ing tape.

    3. Kinked capillary tube.

  • 8/13/2019 Diagnostico Bus TermoKing

    43/75

    Service Procedures

    41

    After these items have been checked and expansion valve

    adjustment is unable to bring the superheat measurement

    into range, then replace the expansion valve with factory

    preset part.

    Superheat Adjustment

    1. Remove the cap over the adjusting stem.

    2. To reduce superheat, turn the adjusting stem counter-

    clockwise.

    3. Make no more than one 1/4 turn of the stem at one

    time, and observe the change in superheat closely to

    prevent overshooting the desired setting.As much as

    30 minutes may be required to obtain the new bal-ance after the adjustment has been made.

    4. When proper readings have been achieved, pump

    down the low side into the receiver tank.

    5. Remove the pressure gauge from the equalizer line

    and thermometer.

    6. Install the equalizer line, open the receiver tank and

    check for leaks.

    WHATS YOUR SUPERHEAT?

    52

    12

    40

    66# 52

    Example: R-22 Refrigerant

    To the suction pressure of 66PSIG

    (at compressor)Add estimated suction line loss 2 PSITo obtain suction pressure....68 PSIG (at Bulb)

    converted to Temp

    Your Superheat is

    AJA823

  • 8/13/2019 Diagnostico Bus TermoKing

    44/75

    Notes

    42

  • 8/13/2019 Diagnostico Bus TermoKing

    45/75

    Leak Testing/Soldering/Clean-Up

    43

    Refrigerant Leak Check Toolsand Recommended Testing Procedures

    Units low on refrigerant must be tested for leaks and the

    leaks must be repaired before adding refrigerant. Following

    are recommended tools and testing procedures:

    AC & DC Powered Electronic Detectors

    DC detectorsnormally use a heated tip and convectional

    currents to pull air samples across the sensor. Pumps used

    are usually low capacity.

    Travel Rate1/2 inch per second.SensitivityAs little as 1/2 oz. refrigerant loss per year.

    AC poweredelectronic detectors normally react faster and

    are the most reliable. A built-in pump pulls air across the

    sensor.

    Travel Rate1/2 to 1 inch per second.

    Sensitivity1 /10 oz. refrigerant loss per year or less.

    Liquid Leak Check Solutions

    Leak check solutions are generally acceptable in areas thatare easily reached or where the air is saturated with refrig-

    erant. However, several factors determine how well a solu-

    tion will work. A good solution should:

    Be bubble free

    Have a high surface tension

    Adhere to and not break away from the joint

    Work for several minutes without evaporating

    Be commercially made for leak detection

  • 8/13/2019 Diagnostico Bus TermoKing

    46/75

    Leak Testing/Soldering/Clean-Up

    44

    Leak Characteristics

    Multiple leaksmay exist. Leak check beyond the first leak.

    Component or line temperaturemay determine leak or

    leak size. Leak test before and after running the unit.

    Circulating refrigerant oil may temporarily plug leaks on

    a unit that is operated. When possible, leak check before

    running the unit.

    Leak Testing Recommendations

    Observe lines and components for an oil and dirt accu-

    mulationindicating leak location.

    Apply liquidbubble solution with soft brushto preventbubbles from forming. Allow several minutes to work,

    Blow outconfined areas with compressed air to remove

    refrigerant accumulations.

    In windy conditions, shieldthe leak area for leak testing.

    Electronic Detectors

    Calibratefrequently with a standardto be sure of reliabil-

    ity.

    Calibrate in fresh air toincrease sensitivity.

    Calibrate in slightly contaminated air to

    reduce sensitivity.Keep sensorfree of dirtand refrigerant oil.

    Movesensor slowly(1/2 inch per second).

    Start leak testingat the topand work down.

  • 8/13/2019 Diagnostico Bus TermoKing

    47/75

  • 8/13/2019 Diagnostico Bus TermoKing

    48/75

    Leak Testing/Soldering/Clean-Up

    46

    Good soldering connections are frequently the result of

    extensive practice. However, several factors and tech-

    niques if properly observed will help ensure success for

    even the inexperienced.

    Tubing Fit

    Too tight a fit between two pieces of swedged tubing may

    not permit the solder to flow throughout the joint. Too loose

    a fit will also weaken the connection.

    A five thousandths of an inch space is recommended

    between two pieces of a swedge joint. This is about equal

    to two pieces of notebook or typing paper.

    Cleanliness

    Remove all grease or oil with solvent or clean rags.

    Remove oxides from the tubing with scotch brite pads.

    Sandpaper and steel wool are not recommended as they

    may contaminate the connection or remove excess metal.

    Wipe away loose oxide and abrasive particles to prevent

    contamination.

    Proper Flux

    Use recommended fluxes to reduce oxide formation, to aid

    in cleaning the connection and to help the solder flow.

    AVOID getting flux inside the tubing.

    Heat Control

    Speed is important. Use a neutral flame large enough to

    finish the job quickly and prevent oxide formation.

    On swedge connections, heat the male tubing first, then

    heat the entire connection evenly.

    Cool slowly. Never cool with water or wet rags.

  • 8/13/2019 Diagnostico Bus TermoKing

    49/75

    Leak Testing/Soldering/Clean-Up

    47

    Refrigerant Recoveryand Methods of Recovery

    Whenever refrigerant is removed from a refrigeration unit

    for service or after leak testing the unit, it must be recov-

    ered to limit the potential harm it could cause to the envi-

    ronment if it were allowed to escape to the atmosphere.

    The following terms are used to refer to the process of

    removing, storing and cleaning or purifying refrigerant:

    Recovery . The process of removing refrigerant from a unit

    and storing it in an external container for later processing.

    Recycling . The process of removing moisture and/or oil

    from refrigerant to prepare it for reuse.

    Reclaiming . The process of cleaning refrigerant to meet

    the standards of new refrigerant.

  • 8/13/2019 Diagnostico Bus TermoKing

    50/75

  • 8/13/2019 Diagnostico Bus TermoKing

    51/75

    Leak Testing/Soldering/Clean-Up

    49

    Recovery from a Working UnitWith An Orit 10 ValveIf a unit is operable and the compressor functions, the

    refrigerant should be removed as a liquid. This is the fast-

    est and most efficient method. Proceed as follows to

    remove refrigerant as a liquid:

    1. Install a gauge manifold on the SSV and the RTOV.

    Install the service line onto the access port on the Orit

    10 EPR valve.

    2. Open the manifold low side hand valve.

    3. Complete a low side pump down.

    4. When you have achieved a 20 vacuum, close the low

    side hand valve on the gauge set.5. Remove the service hose from the EPR valve and

    attach to the recovery device. (Note: low loss fittings

    must be used.)

    6. Set the recovery machine for liquid recovery and open

    high pressure gauge hand valve. Remove the refriger-

    ant through the receiver tank outlet service valve.

    7. Recover refrigerant until proper recovery level is

    achieved.

    Connect serviceline to Orit valveduring low sidepump downonly

    Recovery Unit

    AJA825

  • 8/13/2019 Diagnostico Bus TermoKing

    52/75

    Leak Testing/Soldering/Clean-Up

    50

    Recovery from a Non-functioning Unit

    When a unit is inoperable or the compressor will not func-

    tion, the refrigerant must be removed as a vapor. It can be

    removed from almost any convenient service port on the

    compressor or receiver tank. Because refrigerant must

    evaporate in the unit before removal, it is less efficient and

    more time consuming than the liquid removal process.

    1. On units equipped with an Orit 15 valve or no EPR

    valve, attach gauge manifold hoses to the SSV and

    DSV. If equipped with an Orit 10 valve, attach the man-

    ifold hoses to the discharge valve and to the access

    valve on the Orit 10 EPR valve.

    2. Open both manifold hand valves.3. Recover vapor refrigerant until proper EPA recovery

    levels have been achieved.

    Recovery Unit

    AJA826

  • 8/13/2019 Diagnostico Bus TermoKing

    53/75

    Leak Testing/Soldering/Clean-Up

    51

    System Evacuation and Clean-up

    Refrigeration systems that have had service performed

    with the system open to the atmosphere must be evacu-

    ated to remove air and moisture that may have entered

    during service.

    In addition, systems that have been open to the atmo-

    sphere for an extended period may require multiple evacu-

    ations to be sure all air and moisture are removed.

    Refrigeration systems that have had major service or

    repairs, and systems suspected of having air, moisture, or

    foreign particle contamination, must follow procedures out-

    lined in TK 40229, "Clean-up of Refrigeration Systems withThermo King Compressors," and TK 40612, "Evacuation

    Station Operation and Field Application

    Normal Evacuation Procedure

    1. Recover and totally recycle refrigerant making sure

    contaminates are removed from the refrigerant using a

    certified reclaiming / recycling machine.

    2. Properly install evacuation pump and hoses. Attach

    one evacuation hose to the receiver tank service valve

    (high side) and the other hose to the suction side (low

    side) Try to avoid evacuating from schrader valves.

    Note: Units with EPR valves must be evacuated from

    both sides of EPR valve. Refer to Service Bulletin No.362 dated August, 1989.

    3. Properly install micron gauge.

    4. Install and tighten stem caps on service valves.

    5. Evacuate to 500 microns. Once 500 microns are

    reached, evacuate for 30 additional minutes.

    (continued)

  • 8/13/2019 Diagnostico Bus TermoKing

    54/75

    Leak Testing/Soldering/Clean-Up

    52

    6. Close off unit from pump, shut pump off.

    7. Observe micron gauge. Micron level should not exceed

    1500 microns within 5 minutes. Address problem if

    gauge exceeds 1500 microns and re-evacuate. Use

    nitrogen to purge system before re-evacuating.

    Note: Leaks or high levels of moisture are common

    reasons for a poor evacuation. Also, check evacuation

    equipment and connections, and make sure schrader

    valves and service valves are capped. Refer to Service

    Bulletin No. 392, dated January, 1990.

    8. Weigh in unit charge. (Check unit maintenance manual

    for proper charge).

    9. Check operating pressures. Ensure the temperature,pressure relation vs. RPMs are within specifica-

    tion.Your failure to perform the proper clean-up of the

    system may effect unit warranty.

    Multiple Evacuation

    Perform a multiple evacuation if a system has been open to

    the atmosphere for an extended period or as recom-

    mended in TK 40229 "Clean-up of Refrigeration Systems

    with Thermo King Compressors".

    1. Check the evacuation equipment and repair as

    required.

    2. Open the shut-off valve and place the unit servicevalves in the mid-seat position.

    3. Evacuate the system to 2000 microns for 30 minutes.

    4. Break the vacuum with nitrogen until a 2 to 5 lb. posi-

    tive pressure is established.

    5. Allow the nitrogen to remain in the system for 10 min-

    utes or more.

    6. Evacuate the refrigeration system to 1500 microns for

    30 minutes.

    7. Break the vacuum with nitrogen until a 2 to 5 lb. posi-

    tive pressure is established

    8. Change the liquid line drier.

    9. Evacuate the system to 500 microns then continue to

    evacuate for 30 minutes.

    10. Close the hand valves on the gauge manifold.

    11. Remove the vacuum pump and charge the unit with

    refrigerant.

    12. Prepare the unit for service.

  • 8/13/2019 Diagnostico Bus TermoKing

    55/75

    Leak Testing/Soldering/Clean-Up

    53

    Compressor Oil Acid Test (Kit TK 203-346)

    An acid test of the compressor oil must be done whenever

    an acid condition is suspected. Perform an acid test when-

    ever a unit has a substantial refrigerant loss, a noisy com-

    pressor or dark/dirty oil as noted in TK 40229 "Clean-up of

    Refrigeration Systems with Thermo King Compressors".

    To complete an oil acid test:

    1. Use an access valve (TK 204-625) on the compressor

    oil pump service port and draw an oil sample.

    Note: Two Thermo King acid test kits are available -

    one for alkybenzene (synthetic) compressor oil and

    one for polyolester compressor oil. Be sure to use thecorrect test kit.

    Clear Oil Appearance of good oil.

    Black Oil Carbonization from operating a unit with

    air and moisture in the system.

    Brown Oil Results from moisture in the system

    causing an acid condition and sub-

    sequent copper plating.

    Gray/Metallic Caused by wear metal from pistons

    bearings, cylinders, etc.

    2. Add oil to the test bottle up to the line on the neck.

    3. Replace the cover and shake.

    4. Compare the oil kit color with the color test strip.

  • 8/13/2019 Diagnostico Bus TermoKing

    56/75

  • 8/13/2019 Diagnostico Bus TermoKing

    57/75

    Refrigerant Types and Pressures

    55

    Refrigerant Types/Properties

    During unit cooling, refrigerant is the vehicle within the

    refrigeration system that picks up the heat inside the bus. It

    then carries the heat outside where it can be given up to

    the outside air. Following are characteristics of refrigerants

    and oils presently used in Thermo King units:

    WARNING: Some autos, trucks and other air condition-

    ing systems use PAG Polyalkylene Glycol compressor

    lubricant. DO NOT mix with Thermo King Ester Base

    Oils.

    NOTE: Check unit maintenance manual for proper oil

    to use on ShuttleAire.

    Refrigerant Types/Properties

    R-12 Container Color White

    Oil Type Mineral Base TK 64-426, or Syn-thetic TK 67-404

    Leak Testing Liquid Bubble Solution or CFC

    Electronic Detectors

    R-22 Container Color Green

    Oil Type Synthetic TK 67-404

    Leak Testing Liquid Bubble Solution and CFC

    Electronic Detectors

    R-134a Container Color Light Blue or Brown

    Oil Type Polyolester TK 203-413

    Leak Testing Liquid Bubble Solution or Halogen

    Electronic Detector

    R-407C Container Color Medium Brown

    Oil Type Polyolester TK 203-413

    Leak Testing Liquid Bubble Solution or Halogen

    Electronic Detector

  • 8/13/2019 Diagnostico Bus TermoKing

    58/75

    Temperature Pressure Relationships

    56

  • 8/13/2019 Diagnostico Bus TermoKing

    59/75

    Temperature Pressure Relationships

    57

  • 8/13/2019 Diagnostico Bus TermoKing

    60/75

    Notes

    58

  • 8/13/2019 Diagnostico Bus TermoKing

    61/75

    Glossary

    59

    Bus Air Conditioning Terminology

    Absolute Pressure

    The pressure above a perfect vacuum, expressed in

    pounds per square inch absolute (psia) or kilopascals

    (kPa).

    Ambient Air

    The air surrounding an object.

    Ambient Temperature Sensor

    Measures outside air temperature and selects the tempera-

    ture where the compressor is disabled.

    Ambient Temperature

    Temperature of the air surrounding an object.

    Atmospheric Pressure

    The atmosphere surrounding the earth extends many miles

    above the surface of the earth. The weight of that atmo-

    sphere pressing down on the earth is relatively constant

    except for minor changes due to changing weather condi-

    tions. As a basic reference for comparison, the atmo-

    spheric pressure at sea level has been universally

    established at 14.7 psi (100 kPa) and is equivalent to thepressure exerted by a column of mercury 29.92 inches

    high. At altitudes above sea level, the depth of the atmo-

    spheric blanket surrounding the earth is less; therefore, the

    atmospheric pressure is less.

    Back Seated Service Valve

    The valve stem is backed all the way out (counterclock-

    wise). In this position, the valve outlet is open and the ser-

    vice port is closed.

    Boiling Point

    The temperature at which a liquid vaporizes upon the addi-

    tion of heat or by the reduction of pressure.

    Boost Pump

    Increases the flow of engine coolant to the heating coil.

  • 8/13/2019 Diagnostico Bus TermoKing

    62/75

    Glossary

    60

    Box Temperature

    A term use in transport refrigeration that refers to the tem-

    perature within a bus body. Box temperature is the same as

    return air temperature.

    British Thermal Unit (BTU)

    The amount of heat required to increase the temperature of

    a pound of water one degree Fahrenheit.

    Brushless Motor

    An alternating current (AC) motor having no commutator or

    brushes.

    Calorie

    The amount of heat required to raise temperature of one

    gram of water one degree Celsius.

    Capacity

    Rate of heat transfer measured in tons, BTUs per hour, K

    cal per hours, or Watts. Example: The refrigeration capacity

    with R-22 is 125,000 BTU per hour at 2000 RPM and with

    R-134a is 100,000 BTU per hour at 2000 RPM

    Change of State

    The process of changing from a liquid to a gas, gas to liq-uid, solid to liquid, or liquid to solid.

    Charge

    1) The amount of refrigerant in a system.

    2) The process of adding refrigerant to a system.

    Check Valve

    A valve that allows refrigerant to flow in only one direction.

    Coil Drop

    The term is often used in reference to the temperature dif-

    ference of air entering the evaporator coil versus the tem-

    perature out. Coil Drop can also be referred to as

    Temperature Differential (TD).

    Coil Temperature Sensor

    Measures coil temperature, usually on the evaporator coil

    to control freezing.

  • 8/13/2019 Diagnostico Bus TermoKing

    63/75

    Glossary

    61

    Compound Gauge

    A gauge that is calibrated in both pounds and inches to

    measure pressure and vacuum. This gauge is normally

    used to measure low side pressures.

    Compressor

    The refrigeration component that compresses refrigerant

    vapor and creates refrigerant flow.

    Compressor Capacity/Efficiency Test

    A test used to check the condition of compressor piston

    reeds, piston-to-cylinder wall clearance, piston and cylinder

    condition, and compressor performance capability.

    Compressor Pump Down

    A service procedure used to check for internal leaks

    through the discharge valve plates, and to perform service

    work on the compressor.

    Condenser

    An arrangement of tubing in which the vaporized and com-

    pressed refrigerant is liquefied as heat is removed.

    Conduction

    Heat transfer between two substances in physical contact.

    Convection

    Heat transfer between substances through the movement

    of a fluid (gas or liquid).

    Coolant Valve

    Controls coolant flow to the heater coil.

    Cool Mode (Reheat Position)

    When the unit reaches set point, the clutch remains

    engaged while the boost pump operates.

    Cool Mode (Cycling Clutch)

    When the unit reaches set point, the clutch cycles off. The

    unit operates in vent.

    Compressor Discharge Sensor

    Active above 250F. Senses temperature of discharge gas

    leaving the compressor.

  • 8/13/2019 Diagnostico Bus TermoKing

    64/75

    Glossary

    62

    Dehydration

    Process or removing moisture from a refrigeration system

    or product. A refrigeration system is considered fully dehy-

    drated when it can maintain a 2000 micron vacuum for five

    minutes or longer.

    Dehydrator

    A device used to remove moisture from refrigerant. Drier.

    Receiver drier.

    Discharge Pressure

    Operating pressure measured in the discharge line at the

    compressor outlet.

    Discharge Temperature

    The temperature of refrigerant at the compressor outlet.

    Distributor

    A device located between the expansion valve and evapo-

    rator coil designed to divide the flow of liquid refrigerant

    among several parallel paths in the evaporator coil.

    Drier

    (See Dehydrator)

    DSV

    Discharge Service Valve

    EPROM

    Erasable Programmable Read-Only Memory. A program-

    mable software chip that can be erased and repro-

    grammed.

    EPR Valve

    Evaporator Pressure Regulator. Controls evaporator coil

    temperature to prevent freezing.

    Evacuation

    The removal of non-condensable gases from the refrigera-

    tion system.

    Evaporation

    A change of state from liquid to vapor.

  • 8/13/2019 Diagnostico Bus TermoKing

    65/75

    Glossary

    63

    Evaporator

    The part of the refrigeration system, located in the bus

    interior, that absorbs heat during the cooling cycle.

    Expansion Valve

    A device that meters liquid refrigerant to the distributor and

    evaporator coil in direct response to heat load on the evap-

    orator.

    Flash Gas

    The instantaneous vaporization of refrigerant caused by

    the reduction of pressure on liquid refrigerant when it

    passes through a pressure reducing device.

    Foaming

    A condition caused by refrigerant boiling out of the com-

    pressor oil. Foaming of the compressor oil is often seen

    through the compressor oil sight glass for several minutes

    after a unit is started.

    Fractionation

    When a refrigerant blend in the vapor form separates into

    its individual refrigerant components.

    Freeze PointThe temperature at which a liquid makes a physical change

    to a solid. For water this change occurs at 32F (OC).

    Freeze Thermostat

    Senses and corrects coil freeze-up.

    Freeze-Up

    1. The formation of ice at the expansion valve.

    2. The formation of a solid ice mass over the evaporator

    coil reducing air flow.

    Front Seated

    When the stem of a service valve is turned in (fully clock-

    wise) to stop refrigerant flow through the valve. The service

    port is open when the valve is front seated.

  • 8/13/2019 Diagnostico Bus TermoKing

    66/75

    Glossary

    64

    Frosting Back

    1. The condition of frost formation on the suction line dur-

    ing the cooling cycle. This happens when the suction

    line temperature is below the dew point.

    2. The formation of frost on the suction line, or any portion

    of the compressor during the cooling or heating cycle

    indicating liquid refrigerant is vaporizing at these loca-

    tions.

    Gas

    Common terminology for refrigerant in the gaseous state.

    See Vapor.

    Gauge Pressure

    The pressure reading measured on a gauge calibrated to

    read zero psi (zero kPa) at atmospheric pressure.

    Head Pressure

    A term commonly used to mean discharge pressure.

    Heat

    Heat is a form of energy. Heat is often defined as energy in

    transfer, for it is never content to stand still, but always

    moving from a warm body to a colder body. The terms

    warmer and colder are only comparative. Heat exists at anytemperature above absolute zero, even though it may be in

    extremely small quantities.

    Heat Exchanger

    The component in which heat is transferred from one fluid

    to the other. Normally, it transfers heat from the liquid line to

    the suction line.

    Heat Mode

    The evaporator fan motor runs at selected speed, the boost

    pump and coolant valve are activated, and the condenser

    fan motor is stopped.

    Heat of Compression

    Heat added to refrigerant gas as a result of the work energy

    used in compression.

    Heat Radiation

    Heat transfer through a substance without changing the

    substance temperature.

  • 8/13/2019 Diagnostico Bus TermoKing

    67/75

    Glossary

    65

    Heat Transfer

    Heat always travels from a warm object to a colder object.

    The rate of heat travel is in direct proportion to the temper-

    ature difference between the two bodies. Heat can travel in

    any of three ways: radiation, conduction, or convection.

    Hertz

    A unit of electrical frequency equal to one cycle per sec-

    ond.

    High Pressure Cut Out

    A pressure-operated switch that opens to stop unit opera-

    tion when discharge pressure reaches a predeterminedmaximum.

    High Pressure Relief Valve

    A safety valve on the refrigeration system that allows refrig-

    erant to escape from the system if pressures exceed a pre-

    determined value.

    High Side

    The portion of the refrigeration system operating under

    condensing pressure. That portion of a refrigeration system

    between the compressor output and the expansion valve.

    Hot Gas Bypass Valve

    A solenoid valve controlled by a pressure switch used to

    reduce condenser pressure. Excess condenser pressure is

    piped to the evaporator inlet.

    Inches of Vacuum

    Pressure below atmospheric pressure.

    Latent Heat

    The heat added or removed from a substance that

    accounts for a change in state without any measurable

    change in temperature. For some substances there are two

    conditions where latent heat is required to make the

    change of state. They are - changing from a solid to a liquid

    called fusion, and from liquid to vapor, or vapor to liquid

    called vaporization or condensation.

  • 8/13/2019 Diagnostico Bus TermoKing

    68/75

    Glossary

    66

    Latent Heat of Evaporation

    A change of substance from a liquid to a vapor, or from a

    vapor back to a liquid involves the latent heat of condensa-

    tion. Since boiling is only a rapid evaporating process, it

    might also be called the latent heat of boiling, the latent

    heat of vaporization, or for the reverse process, the latent

    heat of condensation. When one pound of water boils or

    evaporates, it absorbs 970 BTU (1023 joules) and to con-

    dense one pound of steam to water 970 BTU (1023 joules)

    must be extracted from it.

    Latent Heat of Fusion

    A change of substance from a solid to a liquid, or from a liq-uid to a solid involves the latent heat of fusion. When one

    pound of ice melts, it absorbs 144 BTUs, and if one pound

    of water is to be frozen into ice, 144 BTUs must be

    removed from the water.

    Latent Heat of Sublimation

    A change in state directly from a solid to a vapor without

    going through the liquid phase. The most common example

    is the use of dry ice (solid carbon dioxide) for cooling. The

    same process can occur with ice below the freezing point,

    and is also utilized in some freeze-drying processes at

    extremely low temperatures and high vacuums. The latentheat of sublimation is equal to the sum of the latent heat of

    fusion and the latent heat of evaporation.

    LED

    Light Emitting Diode. A small, neon bulb that operates at

    low voltage (3 to 4 volts).

    Liquid Line

    The tube carrying liquid refrigerant from the receiver tank to

    the expansion valve.

    Load

    1. The people being cooled and transported.

    2. The amount of heat that is being removed by the refrig-

    eration system.

    3. The power output of a generator.

    4. The resistance of a device to which power is delivered.

  • 8/13/2019 Diagnostico Bus TermoKing

    69/75

    Glossary

    67

    Low Pressure Cut Out

    A pressure-operated switch that opens to stop unit opera-

    tion when suction pressure reaches a predetermined mini-

    mum.

    Low Side

    The part of a refrigeration system normally under low pres-

    sure during the cool mode. (This includes the liquid line

    during a low side pump down.)

    Motor Driver

    DC to AC inverter used to supply voltage to the brushless

    AC motor.

    Perfect Vacuum

    29.92 Hg (29.92 inches of mercury)

    Piston Reeds

    Ring-shaped reeds (one way valves) located on top of each

    piston in a reciprocating compressor. As the piston moves

    down in the cylinder, the reed opens to allow refrigerant

    gas to move from the crankcase area to the area above the

    piston. As the piston moves up in the cylinder, the reed

    closes to trap refrigerant gas above the piston. The com-

    pressor capacity test is used to check the condition of pis-ton reeds.

    Pressure

    The push exerted against container walls by a liquid or gas,

    usually measured in pounds per square inch or kilopascals

    (kPa).

    Pressure Drop

    1. Loss in line pressure from one point to another due to

    restriction.

    2. Loss of pressure due to condensing vapor.

    3. Loss of pressure due to a leak in the system.

    Product

    The cargo being temperature-controlled.

    PSIA

    Pound per square inch - Absolute. See Absolute Pressure.

  • 8/13/2019 Diagnostico Bus TermoKing

    70/75

    Glossary

    68

    PSIG

    Pounds per Square Inch Gauge. Pressure in pounds per

    square inch as displayed by a gauge calibrated to zero

    when open to the atmosphere.

    Pump Down

    A procedure used to service a refrigeration system. Refrig-

    erant in a charged unit is pumped and stored in one part of

    the system while servicing another part of the system.

    Purging

    Releasing a vapor through a refrigeration system to atmo-

    sphere to remove contaminants from the system. The rec-ommended vapor used for purging dry nitrogen.

    Radiation

    Radiation is the transfer of heat by waves similar to light

    waves or radio waves. For example, the suns energy is

    transferred to the earth by radiation.

    Receiver Tank

    A refrigerant storage tank.

    Reclaim

    The process of cleaning refrigerant to like-new condition. Aprocess normally done by a licensed reclaiming service not

    an infield practice.

    Reclaimer

    A machine used for removing refrigerant from a unit,

    removing contaminants from the refrigerant, and placing

    the refrigerant into a storage container.

    Recover

    To remove refrigerant from a system and store it in an

    external container without testing or processing it.

    Recycle

    A procedure that removes refrigerant from a unit, cleans

    the refrigerant through a series of filters, and returns the

    refrigerant to the unit or a bottle.

    To clean refrigerant for reuse by removing oil and contami-

    nants through single or multiple passes through moisture

    absorption devices such as replaceable core filter driers.

    Considered an infield practice.

  • 8/13/2019 Diagnostico Bus TermoKing

    71/75

    Glossary

    69

    Refrigerant

    The fluid or vehicle used to carry heat from one point to

    another in the refrigeration system. It picks up heat as it

    vaporizes and gives up heat as it condenses.

    Return Air Sensor

    Measures coach interior air temperature, usually mounted

    in the return air flow of the evaporator.

    Return Air Temperature

    See Box Temperature.

    RTOVAn abbreviation for Receiver Tank Outlet Valve, which is

    the service valve on the recovery tank.

    Saturated Vapor

    The condition when a refrigerant has liquid form present

    with the vapor. This occurs in the evaporator when refriger-

    ant is making the change from liquid to vapor or in the con-

    denser when the refrigerant is condensing.

    Saturation Temperature

    The condition where temperature and pressure allow both

    liquid and vapor to exist simultaneously. A saturated liquidor vapor is one at its boiling point, and for water at sea

    level, the saturation temperature is 212 F (I00 C). At higher

    pressure, the saturation temperature increases, and with a

    decrease in pressure, the saturation temperature

    decreases.

    Sensible Heat

    The heat required to change temperature of a substance.

    When the temperature of water is raised from 32 F to 212

    F, an increase in sensible heat content is taking place.

    Set Point

    The temperature selected on a thermostat or micro control-

    ler. This is normally the desired temperature.

    Short Cycling

    The circulation of air from the evaporator outlet and back to

    the evaporator inlet without properly circulating through the

    load. Short cycling is normally caused by improper ducting

    practices. This may also refer to improper clutch operation.

  • 8/13/2019 Diagnostico Bus TermoKing

    72/75

    Glossary

    70

    Sight Glass

    A system component that permits visual inspection of oil

    and/or refrigerant level and condition.

    Slugging

    The return of either refrigerant or oil to the compressor in a

    liquid condition. Slugging can cause knocking and com-

    pressor damage. Sometimes called liquid slugging.

    Solenoid Valve

    An electromagnet valve that can be opened or closed elec-

    trically.

    Specific Gravity

    Specific gravity (sp.gr.) is a ratio comparing the weight of a

    substance to the weight of an equal volume of water. Water

    is considered to have a specific gravity of one. Objects

    which float on water have a specific gravity of less than

    one. Objects which sink in water have a specific gravity

    greater than one.

    Specific Heat

    Heat required to change the temperature of a given unit of

    a substance compared to the amount of heat required to

    change the temperature of an identical amount of water. Itis expressed in BTUs per pound per degree Fahrenheit or

    joules per kilogram kelvin.

    SSV

    Suction Service Valve.

    Suction Line

    A flexible line, to absorb vibration, that carries refrigerant

    from the evaporator back to the compressor.

    Suction Reeds

    See Piston Reeds

    Superheated Vapor

    Vapor that has heat added to it after it has changed from a

    liquid to a vapor without any additional change in pressure.

  • 8/13/2019 Diagnostico Bus TermoKing

    73/75

    Glossary

    71

    TD

    The abbreviation for Temperature Differential or Tempera-

    ture Difference. The term is often used in reference to the

    temperature difference of air entering the evaporator coil

    versus the temperature out. TD can also be referred to as

    Coil Drop.

    Temperature

    Temperature is the word used to describe the intensity of

    heat. In the United States, temperature is normally mea-

    sured in degrees Fahrenheit, but the Celsius scale is widely

    used in other parts of the world.

    Thermodynamics

    Thermodynamics is the branch of science that explains the

    mechanical action of heat. There are several fundamental

    laws of thermodynamics. The first and most important of

    these laws is that energy can neither be created nor

    destroyed, but can be converted from one type to another.

    Thermostat

    Controls electrical devices in bus based on temperature.

    Ton

    The common unit used to measure refrigeration effect. Theamount of heat absorbed by one ton (2000 lb.) of ice as it

    changes to liquid over a 24-hour period. It is the refrigerat-

    ing equivalent of 12,000 BTUs per hour. (One pound of ice

    absorbs 144 B.t.u. As it melts. One ton of ice absorbs

    288,000 B.t.u. When one ton of ice melts in 24 hours, the

    rate is 288,000 (24 or 12,000 B.t.u. per hour.)

    Unloader Valve

    Used on some compressors to limit capacity by either shut-

    ting off suction gas or bypassing gas back to the suction

    side of the compressor.

    Valve Plate (Discharge Valve Plate)

    An internal part of the compressor located above each pis-

    ton. It operates as a check valve, allowing refrigerant gas to

    leave the area above the piston while preventing its return

    when the piston is on the down-stroke. The compressor

    pump down procedure is used to check valve plate condi-

    tion.

  • 8/13/2019 Diagnostico Bus TermoKing

    74/75

    Glossary

    72

    Vapor

    Common terminology for refrigerant in a gaseous state.

    See Gas.

    Vent Mode

    Coach interior air is recirculated.

    Volumetric Efficiency

    The ratio of actual volume of refrigerant gas pumped by the

    compressor to the volume displaced by the compressor

    pistons.

    WattA term defining the cooling ability of a unit.

    One Watt = 3.42 BTU

  • 8/13/2019 Diagnostico Bus TermoKing

    75/75