United ~ Utilities ~~ing Hf e foW smoothy
Developer Services Wastewater S104 Support Guide
Developer Services Wastewater S104 Support Guide
I bullunited ~Utilities
~6 middott oW smootha ngh e
Introduction This guide informs applicants what information we require and how design submissions should look it gives supporting design information for multiple drawings which make up a Section 104 application This document should be read in conjunction with lsquoSewers for adoptionrsquo and the section 104 technical guidance document
Technical Guidance
Contents Page 1 Introduction Page 2-3 Drainage Plan Page 4 Long Section General Page 5 Manhole 120 Schematic General Page 6-7 Hydraulics Page 8-9 Pumping Station Submission Page 10 Land Registry Compliant drawings Page 11 Land Transfer drawing Page 12 Additional information Page 13 Adoptions Process Flow
Pre Development enquiries We strongly recommend you complete a pre development enquiry at an early stage so that the drainage strategy can be confirmed before completing your Section 104 application this can save a lot of time
See our website for our Pre Development Enquires
Design All design submissions must be in accordance with Sewers For Adoption and United Utilities Standard Details
bull Gravity Systems - Sewers for Adoption 6th Edition
bull Pumping Stations - Sewers for Adoption 7th Edition and United Utilities Pumping Station Addendum
bull Developer Services Construction Details
United Utilities feedback form Once you have made your application an engineer will respond using our unique feedback form it is essential that any further correspondence is resubmitted on the form and supplied in its original format this should allow a quicker acceptance to be issued
Naming Drawings It is important that drawings are supplied to us named correctly this helps us process the applications faster See good examples below We can clearly see what the drawings are without the need to open up the file All drawings should be provided in PDF format
Document Example of saved names
S104 Drainage Layout S104 Plan Rev 1
Longitudinal Section Long Section Sheet 1 ndash Roads 12 amp 14 Rev 1
Manhole Drawings Surface Water or Foul Manhole Sheet 1 Rev 1
Flow Control Manholes Flow Control Chamber Rev 1
Title Plan Land Registry Compliant Plan Rev 1
Hydraulic Files SW Network or SW Network 1m surcharge
Flood Routing Flood Route Rev 1
Flow Control Technical Sheets Flow Control Spec Rev 1
Ground Investigation SI Report SI Report
Private Plot Drainage Layout Private Drainage Rev 1
Disclaimer - This document has been produced for general guidance only
Page 1
D Flow contro S6 (24 ia 1 manhole)
CLmiddot 98869 middot Ilt Opt imum
Hydrobra e rnational) (by Hydro ln~00-1600-8000 SHE-0123-8
Design 6 head 81s 1- m
Posit ion and L been have d and
surveyed as confirme shown
1 bullunited ~Utilities
-1 ow smoothi amp1inglite
Drainage Plan The drainage plan and design must meet Sewers for Adoption 6th edition and Developer Services Construction Details whilst also meeting our legal requirements See Sewers For Adoption 6th edition Section 24 Layout Of Sewers Manholes amp Rising Mains for more information The below images show a good example of what is expected
Only new adoptable drainage coloured for adoption
Manholes and sewers required distance from kerblines ndash SFA 6th section 24 figure 3 page 21
Trees conforming with SFA 6th figure 23 page 33
Finished floor levels for each plotGreen boundary covering
developers land
Large storage pipes laid no flatter than 1400
Sewers proposed for adoption as per SFA 6th section 24 layout of sewers page 21
Culverted Watercourse Connection This also shows a sustainable drainage strategy and requires relevant consent as per section 11 ndash Application for adoption of new sewers
Key Points
Pipe diameter material and gradient clearly shown
manhole cover and Invert levels clearly shown
Flow control chamber specification detailed ndash flow control chambers must be located in an
accessible location for future operational activities
Existing connection point invert level surveyed
and confirmed
Easement provided in 3rd party land
Private 100yr offline storage located in an accessible location with spill pipe
set above the 30yr water level
Scale 1500 This is an ideal scale for apprisals
Page 2 Developer Services Wastewater S104 Support Guide
I I I I
- SW Foul Combined - --0- bull bull - I - -~ - -_r _ G -al J11 if li
---
-- bull bull
bull bull
I bullunited -1 ~ Utilities amp1ing life ow smoothi
C
Drainage Plan continued
A
3m3m
3m3m
Revision Comments Changes by Checked by Date Key Points Updated as per United Utiliities Appraisal form of 190518
B AL MW 200518 amending outfall level
All drawings must contain a Easements added AL MW 220518 comments table it is good
practice to have any design D Foul Connection Point amended due to asset clash AL MW 010618
amendments checked
Updated as per United Utiliities Appraisal form of 170618 A detailed explanation ofE AL MW 180618amended storage tank location changes must be contained
Easements shown in yellow with width dimensioned from the centre line of the sewer
B C D
Surface water outfall to watercourse should
show easement including headwall the outfall level must be considered and include an appropriate
freeboard allowance see Section 104 technical
guidance document section 335 for more information
Examples A Sewers coloured
as per SFA
Existing sewers coloured black
Abandoned sewer black with crosses also confirming the method of abandonment
Gullys black labelled ldquoGrdquo
B
C
D
Page 3 Developer Services Wastewater S104 Support Guide
~ ~ ~~ I I
I I I
9 9 _
la ~ - --- --- --5002
- ~002 - -~
~ OMJOm
- - - ~ - -
I =~npll
g
STOR lIApR 00IEJU EIIR
SfOnWil lt IN1pound1t ~
llpaS m
SHiWWER CIElM S CitMr CIAY
~le c~ s ooo ~ sumouncl
SiORllMTffi wlGfHS 31132
FOlJlWfflR C~~ POULW1_TER INERJ
~Dill Olii150 iOulWmi CJEfAPI$ eh 0 t
I ln$C S1ttmgm41luun
~ i--t~ __ __ __
~ ~ ~ ~ I I
r la d~tmg 6-rid I I rJ ~ll CDltJn 1
9 I
b b
_ ~-1111-- - --__ ____
I I
-- -~- ru bull -- 1- Dbull ~
~ - --~ - - -- - -
~ 5 )
-middot 2
I~ N N
~ sect bull e
~o([ll ilpaMl)(I i m Oiffl
QrcJ - CV einilr CL
Sttingm P8 Uim strenu IIUllm Cl1u S - 1 auoI 51JJm1DMI CbsB S lied~ WIWllllll
lt04~ 21~
Bi ~ i ~ - ~
II ii
pe S00 Pp_00
Olli~ Oa1~ CWWOA- C~CiAt
~~IJ kNm nfl
5trelglll CJ kNml -~ltI IIIQ =- bull cbull~~ ltgt ~-~
I I
Pipe 2 Di~ 225
cmiddot _ 1~r CLAY middot8
s tren~ ~5 k Im Glass s bed and SllIITOlmdl
STORMWATER COVER LEVEL
STORMWATER INVERT
-
o-------- bull
5002
H lco 5002
~
iii ~
-
I ~= I
_
V ~ -04~0middotrnmiddot ce~r~~~ ~~~e~~ ~i~e~
gt12m roverto sotfrt of se we1
_ _I
~~-
-- - --
--
--
--
--
I bullunited -1 ~ Utilities amp1ing life ow smoothy
Long Section General
All Connections must be soffit to soffit
30yr TWL Both foul and surface water sewers
shown on one long section
Key Points
PN Name pipe diameter material gradient and pipe
bedding shown for each pipe
Manhole cover and invert levels for each chamber
30yr critical storm top water level added
Any pipe crossing show the clearance achieved from invert of highest sewer to
soffit of lowest sewer Please note the minimum clearance is 300mm however this is site
specific and dependant on the pipe size crossings
Sewers in highway achieveing gt12m cover to
soffit of pipe ndash See SFA 6th figure 210 page 27
Page 4 Developer Services Wastewater S104 Support Guide
INDICATES tl001c600 CEAA OPEN ING MANHOLE COiER AND _ FRAME OVER 75llll6DD CLEAR OPENING N COJER SIAB ACCESSIS UNITED UTILITIES STANDARD DET L
INDICATES 600x600 CLEAR OPENING MANHOLE COVER AND FRAME OVER 750x600 CLEAR OPENING IN COVER SLAB ACCESS AS UNITED UTILITIES STANDARD DETAIL
--
I bullunited -1 ~ Utilities amp1ing life ow smoothy
Manhole 120 Schematic General All manholes should be constructed in accordance with United Utilities Developer Services Construction details Here are good examples
Key Points
When using 600 times 600 covers a 750 times 600 opening
in the cover slab must be used this can avoid any mistakes where ladders
are required
Rocker pipes shown or a general comment stating
rockers will be used in line with United Utiliities standard
detail variable features STND19010
Clay channel fittings used for pipes less than 375dia
Benching widths dimensioned
Manhole S1 MH Diameter 1500mm
Cover Level 107000
Invert Level 105000
MH Type 1
Depth to Soffit 1775
Depth to cut out NA
Cover Size 600 times 600mm
Cover Depth 150mm
Cover Spec D400
Ladder or Double Steps Double Steps
Safety Chain NA
Safety Rails NA
Invert Access Step NA
Hole Size in Cover Slab 600 times 750mm
Page 5 Developer Services Wastewater S104 Support Guide
1000 1 0000 1001 2 0000 2000 3 0000 2001 4 0000
2002 5 0000
1003 6 0000 1004 7 0000
MS-60 (mm) 18500 MADD Factor 2
Flow Control Manhole S7 - DS PN 1005 Unit Ref U U-0124-1000-2500-1000
Design Head 25
Sump Yes
Unit Diameter 124
Flow Control Invert 114515
65 74
20 22
25
7
12
1000 1001
2000
I J 1 middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot1
r middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot J
r I 1-middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot 1 Lmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot I r bullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullmiddotbullbulll L bullmiddot i
34m 25m
17m
P i pe N o
1 000
1 00 1
2 0 00
2 0 011
2 0 02
1 0 02
1 0 0 3
1 0 04
OK OK OK OK OK OK OK
1167 1167
1400
I mpe rme a b le Area (H a)
001 4H
0 10 6 H a
0 173H a
0 0 6 1 Ha
0 0 90H a
0063 H a
0 21 9 H a
0 104H a
T o ta l lm p e-mea b le A rea - O 8 30H a
0015 66244 67602 0025 66000 67600
0200 64500 67500
225 225
1200
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Hydraulics Where surface water sewers are proposed for adoption we require hydraulic calculations from a digital modelling software package See Sewers For Adoption 6th edition page 28 figure 213
Key Points
Design storm requirements bull No surcharge within the system in a 1 in 2
year Rank 1 storm event bull There is no flooding from the system
in a 1 in 30 year Rank 1 storm (against a surcharged outfall)
bull Please note the only pipe length expected to surcharge in the design storm is pipe downstream of the flow control manhole
Checking the simulation data and criteria bull Contributing impermeable areas (hard
standing areas) bull M5-M60 and Ratio Rndash Check Table of
hydraulics bull MADD Factor ndash No higher than 2
bull The cover and invert levels pipe lengths pipe diameter pipe gradients and contributing areas are consistent across all drawings
bull Online controls (flow control manholes ndash design head and pass forward flow)
bull Pond storage details are correct bull No private drainage lengths included
within network details
Impermeable areas Each impermeable area should represent a unique colour for the drainage area a
key should also be shown detailing the PN number and impermeable area in hectares
Page 6 Developer Services Wastewater S104 Support Guide
Developer Services Wastewater S104 Support Guide
1CL 15555 0 IL 155100
YES 30 1000 YES 40 1000 YES 50 1000
30 r YES 60 1000 30yr YES 70 1000
30 r YES 80 1000 30yr YES 90 1000 30 r YES 100 1000
I bullunited -1 ~ Utilities amp1ing life ow smoothy
Hydraulics continued
Page 7
Key Points
Standards to be checked within the results of the simulations
bull The results should show that the pipe velocities achieve a self-cleansing velocity
bull That high velocities are avoided (in excess of 4ms) - risk of scouring and erosion to benching and river banks
Additional check bull The water levels within the adoptable
manholes listed isnrsquot greater than any private drainage cover levels (for example where houses are lower than the relative level of the road)
1m Surcharge bull A 1m surcharge is to be applied to the soffit
of the receiving sewer with the 30yr storm simulated showing no flooding
Flood Routing bull A flood routing plan is required to support
your application showing that the layout and landscaping of the site aims to route water away from any vulnerable property National Planning Policy Framework usually explains that no flooding of properties should occur as a result of a one in 100 year storm event (including an appropriate allowance for climate change)
Velocity (ms) Result
159
256
250
263
229
tiQ s middot-s (U c 0 ltraquomiddot m tJmiddot E co bull m
10m Tanker Hardstanding
SEE U ILiTI DRA11NGAS SUPPUED BY O ER FOF leMCT ROIITES Of DUCTS
TMiKJER HARDSTANOING
12m Com10oundl lleneth
bull
bull
OS ANDING
J Cl Cl s 0 c E 0 u E
00
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Pumping Station Submission All Pump Station designs must be in line with Sewers for Adoption 7th edition and United Utilities Pumping Station Addendum Justification should always be provided with any submission which proposes a pumping station showing why a gravity soluction is not achievable Please ensure the below information is sent with Pumping Station applications
Typical example of a pumping station compound
bull All key areas show dimensions
bull Bollards for tanker safety
bull Full technical details expected on Pumping Station Design package
bull Non Rising Spindle Penstock chamber located within compound
Key Points
A full pumping station submission should include these documents drip feeding
documents is not acceptable
Document Provided Compound General Layout Drawing
Pumping Station General Arrangement Pumps
Hazardous Area Plan
Rising Main specification
Independent Rising Main Long Section Showing Air Valves and Washout Chambers where applicable (Air Valve to be suitable for Ww rising main)
Jointing Method ndash Fusion Welded confirmed
Surge Analysis (Rising Main Over 500m)
Floatation Check Calculations (Please note Ground Water is to be assumed from ground level) Flotation should be considered as an EQU limit state in accordance with BS EN 1997-1 Section 10 using partial load factors from table NAA12(A) of the UK National Annex to BS EN 1990
Storage Calculations and confirmation of storage location
Pump Calculations
Full Technical specification document
Penstock Isolation Chamber 120 Schematic showing non rising spindle
Tanker Swept Path Analysis drawing
Page 8 Developer Services Wastewater S104 Support Guide
Developer Services Wastewater S104 Support Guide
Sta~ion Typ e 3
iii Weill depth 42rn
iiil1 Well diameter 24m ivj Palisad1e fencing 18m
v) AH emeirgency stm rage
0011tained bulllt1-lrthin well
110mm HPPE SDR 17
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Pumping Station continued
Key Points
General comments Pumping Station location requires careful
consideration ideally away from SUDS features or watercourses Wet wells must be a minimum
distance from any habitable building as per SFA 7th table D1 page 62 with the clearance shown
on the drainage plan A note adjacent to the station should be
provided showing 1) PS Type 2) Well depth 3) Well diameter 4) Fencing type and height 5) Confirmation of Emergency Storage location
6) All electrical equipment should be sited above the 200 year storm level
Rising Main details Rising main specification must be shown on the drainage plan inlcluding
material diameter SDR rating Rising Main Bends Slow Long radius bends should be used avoiding sharp bends If thrust
blocks are required we require supporting calculations
Apparatus on Rising Mains Washout Air Valves (low points high points) must be shown on the drainage drawing and on the long section
Break Chamber The rising main should be kept to the minimum possible distance and
must terminate into a break chamber followed by a minimum 5m length of gravity sewer and a
connection at the soffit level of the existing sewer
Tanker Swept Path Analysis drawing showing an 8 wheel tanker can sufficiently and safely
turn then achieve a reverse manoeuvre into the compound and safely drive out
Rising Main details Rising Main Bends Apparatus on Rising Mains Break Chamber
Page 9
GRID REFERENCE 342587 E 439878 N
l===TI~
GR ID REFERENCE 342587 E 439878 N
C HUR C H V IEW
CHU R C H VIEW
-----------
CHURCHi VIIEW
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Land Registry Compliant drawings Land Registry Compliant drawings are required to enable United Utilities to aquire legal easements over new or existing sewers Drawing 1 shows on site easement examples Drawing 2 shows off site easement examples
Page 10 Developer Services Wastewater S104 Support Guide
Key Points
Scaled at 11250 or near as possible to fit on A3 sheet
Site boundary edged in green (must match
S104 Drainage Plan)
Exisitng road names or landmarks
North point
Easements clearly dimensioned either side from the centre line of the sewer
Drawing 1 ndash On site easements
Drawing 2 ndash Off site easements
J
__ ---
Legend
land ~o be transierred 0 United Ut itities
-~ bullmiddotmiddot bull middot _
L - middot middot middot hi
middot~ qe ~- us v~
I bullunited ~Utilities
~ 6 ow smoothy degtnghte
Land Transfer drawing Land Transfer drawings are required for Pumping Stations this enables United Utilities to transfer land ownership and obtain access rights
Key Points
Example of land trasnfer plan scaled at 1500 the drawing also includes an extract at
a greater scale to cover the drawing requirememts
Compound boundary edged in red
Existing road names landmarks
Any access rights to the station coloured brown (not shown on main example as the station is located off an
adoptable highway)
North point
Page 11 Developer Services Wastewater S104 Support Guide
Dear Mr Adoption
RE One permanent 300mm diameter surface water discharge connection (S57) into existing ordinary watercourse restricted to 321Js rate at UU Road Warrington
Thank you for you r application for Ordinary Watercour se Land Drainage Consent received by Any Other Counci(
I confirm t hat your proposals for the pe rman en t headwall are acce pt able to the Any Other Counci l shown on drawing number S104 Drainage Plan Rev 4
II
Samples arnd In Situ Testirng
Depth Type Results
030 ES
060 ES
0 90 ES
Depth Level (m) (m)
050
0 65
1()()
Stratum Description
MADE GROUND Brown sandy clayey set (Topsoil) with occasional roots and vey rare sub-rounded lo rounded lfrneston e pebbl es_
MADE GROUND Sofi brown sifiy sandy clay with rare sub-rounded to rounded to limestone and cllert pebb lemiddots_ 0 a nic odour
Light brownyellow clayey fine to medium SANO (Organ ic odou r)
End cf pit at 100 m
--
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Additional information
Ground conditions
TreesPlanting
Consents
Page 12 Developer Services Wastewater S104 Support Guide
Key Points
It is essential that thorough site investigation is undertaken as early as possible to avoid any
potential issues with new sewers
A full detailed SI report including trial pit borehole logs must be provided with a
Section 104 submission
Should you encounter challenging ground conditions (for example peat running sand or a fluctuating water table) you should provide
detailed information to justify your design proposals
Trial pit boreholes should be taken to a depth beneath the proposed invert level of any new
sewers to be laid
Should any planting be proposed adjacent to sewers these must conform to figure 23
page 33 SFA 6th
Sewers should be positioned to avoid TPO areas
bull Should your surface water sewers outfall to a watercourse please see Technical Guidance
Document Section 32
bull Formal Consent detailing acceptance of headwall and pass forward flow is required
Technical Guidance
Developer Services Wastewater S104 Support Guide
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Adoptions Process Flow
Initial Design Submitted
Progression to Technical Acceptance
Inspection Fees Paid
Legal Agreements Signed
Inspections as site progresses
Remedial list issued following 100 completion
of build and when occupancy above 50
Provisional Certificate Issued (12months
maintenance)
FinalVesting Certificate Issued
and bond fee released
Page 13
United Utilities Website httpwwwunitedutilitiescomdefaultaspx
Information and advice
Sewer Adoptions httpwwwunitedutilitiescomsewer-adoptions-buildaspx
United Utiliities Standard Details httpwwwunitedutilitiescomdocumentsdeveloper-services-construction-detailspdf
Site Sewer Construction Guide httpwwwunitedutilitiescomdocuments6805-contractors-guidepdf
Pre Development Enquiries httpwwwunitedutilitiescomplanning-wastewater-guidanceaspx
Developer Services Wastewater S104 Support Guide
0818SD7664
Developer Services Wastewater S104 Support Guide
I bullunited ~Utilities
~6 middott oW smootha ngh e
Introduction This guide informs applicants what information we require and how design submissions should look it gives supporting design information for multiple drawings which make up a Section 104 application This document should be read in conjunction with lsquoSewers for adoptionrsquo and the section 104 technical guidance document
Technical Guidance
Contents Page 1 Introduction Page 2-3 Drainage Plan Page 4 Long Section General Page 5 Manhole 120 Schematic General Page 6-7 Hydraulics Page 8-9 Pumping Station Submission Page 10 Land Registry Compliant drawings Page 11 Land Transfer drawing Page 12 Additional information Page 13 Adoptions Process Flow
Pre Development enquiries We strongly recommend you complete a pre development enquiry at an early stage so that the drainage strategy can be confirmed before completing your Section 104 application this can save a lot of time
See our website for our Pre Development Enquires
Design All design submissions must be in accordance with Sewers For Adoption and United Utilities Standard Details
bull Gravity Systems - Sewers for Adoption 6th Edition
bull Pumping Stations - Sewers for Adoption 7th Edition and United Utilities Pumping Station Addendum
bull Developer Services Construction Details
United Utilities feedback form Once you have made your application an engineer will respond using our unique feedback form it is essential that any further correspondence is resubmitted on the form and supplied in its original format this should allow a quicker acceptance to be issued
Naming Drawings It is important that drawings are supplied to us named correctly this helps us process the applications faster See good examples below We can clearly see what the drawings are without the need to open up the file All drawings should be provided in PDF format
Document Example of saved names
S104 Drainage Layout S104 Plan Rev 1
Longitudinal Section Long Section Sheet 1 ndash Roads 12 amp 14 Rev 1
Manhole Drawings Surface Water or Foul Manhole Sheet 1 Rev 1
Flow Control Manholes Flow Control Chamber Rev 1
Title Plan Land Registry Compliant Plan Rev 1
Hydraulic Files SW Network or SW Network 1m surcharge
Flood Routing Flood Route Rev 1
Flow Control Technical Sheets Flow Control Spec Rev 1
Ground Investigation SI Report SI Report
Private Plot Drainage Layout Private Drainage Rev 1
Disclaimer - This document has been produced for general guidance only
Page 1
D Flow contro S6 (24 ia 1 manhole)
CLmiddot 98869 middot Ilt Opt imum
Hydrobra e rnational) (by Hydro ln~00-1600-8000 SHE-0123-8
Design 6 head 81s 1- m
Posit ion and L been have d and
surveyed as confirme shown
1 bullunited ~Utilities
-1 ow smoothi amp1inglite
Drainage Plan The drainage plan and design must meet Sewers for Adoption 6th edition and Developer Services Construction Details whilst also meeting our legal requirements See Sewers For Adoption 6th edition Section 24 Layout Of Sewers Manholes amp Rising Mains for more information The below images show a good example of what is expected
Only new adoptable drainage coloured for adoption
Manholes and sewers required distance from kerblines ndash SFA 6th section 24 figure 3 page 21
Trees conforming with SFA 6th figure 23 page 33
Finished floor levels for each plotGreen boundary covering
developers land
Large storage pipes laid no flatter than 1400
Sewers proposed for adoption as per SFA 6th section 24 layout of sewers page 21
Culverted Watercourse Connection This also shows a sustainable drainage strategy and requires relevant consent as per section 11 ndash Application for adoption of new sewers
Key Points
Pipe diameter material and gradient clearly shown
manhole cover and Invert levels clearly shown
Flow control chamber specification detailed ndash flow control chambers must be located in an
accessible location for future operational activities
Existing connection point invert level surveyed
and confirmed
Easement provided in 3rd party land
Private 100yr offline storage located in an accessible location with spill pipe
set above the 30yr water level
Scale 1500 This is an ideal scale for apprisals
Page 2 Developer Services Wastewater S104 Support Guide
I I I I
- SW Foul Combined - --0- bull bull - I - -~ - -_r _ G -al J11 if li
---
-- bull bull
bull bull
I bullunited -1 ~ Utilities amp1ing life ow smoothi
C
Drainage Plan continued
A
3m3m
3m3m
Revision Comments Changes by Checked by Date Key Points Updated as per United Utiliities Appraisal form of 190518
B AL MW 200518 amending outfall level
All drawings must contain a Easements added AL MW 220518 comments table it is good
practice to have any design D Foul Connection Point amended due to asset clash AL MW 010618
amendments checked
Updated as per United Utiliities Appraisal form of 170618 A detailed explanation ofE AL MW 180618amended storage tank location changes must be contained
Easements shown in yellow with width dimensioned from the centre line of the sewer
B C D
Surface water outfall to watercourse should
show easement including headwall the outfall level must be considered and include an appropriate
freeboard allowance see Section 104 technical
guidance document section 335 for more information
Examples A Sewers coloured
as per SFA
Existing sewers coloured black
Abandoned sewer black with crosses also confirming the method of abandonment
Gullys black labelled ldquoGrdquo
B
C
D
Page 3 Developer Services Wastewater S104 Support Guide
~ ~ ~~ I I
I I I
9 9 _
la ~ - --- --- --5002
- ~002 - -~
~ OMJOm
- - - ~ - -
I =~npll
g
STOR lIApR 00IEJU EIIR
SfOnWil lt IN1pound1t ~
llpaS m
SHiWWER CIElM S CitMr CIAY
~le c~ s ooo ~ sumouncl
SiORllMTffi wlGfHS 31132
FOlJlWfflR C~~ POULW1_TER INERJ
~Dill Olii150 iOulWmi CJEfAPI$ eh 0 t
I ln$C S1ttmgm41luun
~ i--t~ __ __ __
~ ~ ~ ~ I I
r la d~tmg 6-rid I I rJ ~ll CDltJn 1
9 I
b b
_ ~-1111-- - --__ ____
I I
-- -~- ru bull -- 1- Dbull ~
~ - --~ - - -- - -
~ 5 )
-middot 2
I~ N N
~ sect bull e
~o([ll ilpaMl)(I i m Oiffl
QrcJ - CV einilr CL
Sttingm P8 Uim strenu IIUllm Cl1u S - 1 auoI 51JJm1DMI CbsB S lied~ WIWllllll
lt04~ 21~
Bi ~ i ~ - ~
II ii
pe S00 Pp_00
Olli~ Oa1~ CWWOA- C~CiAt
~~IJ kNm nfl
5trelglll CJ kNml -~ltI IIIQ =- bull cbull~~ ltgt ~-~
I I
Pipe 2 Di~ 225
cmiddot _ 1~r CLAY middot8
s tren~ ~5 k Im Glass s bed and SllIITOlmdl
STORMWATER COVER LEVEL
STORMWATER INVERT
-
o-------- bull
5002
H lco 5002
~
iii ~
-
I ~= I
_
V ~ -04~0middotrnmiddot ce~r~~~ ~~~e~~ ~i~e~
gt12m roverto sotfrt of se we1
_ _I
~~-
-- - --
--
--
--
--
I bullunited -1 ~ Utilities amp1ing life ow smoothy
Long Section General
All Connections must be soffit to soffit
30yr TWL Both foul and surface water sewers
shown on one long section
Key Points
PN Name pipe diameter material gradient and pipe
bedding shown for each pipe
Manhole cover and invert levels for each chamber
30yr critical storm top water level added
Any pipe crossing show the clearance achieved from invert of highest sewer to
soffit of lowest sewer Please note the minimum clearance is 300mm however this is site
specific and dependant on the pipe size crossings
Sewers in highway achieveing gt12m cover to
soffit of pipe ndash See SFA 6th figure 210 page 27
Page 4 Developer Services Wastewater S104 Support Guide
INDICATES tl001c600 CEAA OPEN ING MANHOLE COiER AND _ FRAME OVER 75llll6DD CLEAR OPENING N COJER SIAB ACCESSIS UNITED UTILITIES STANDARD DET L
INDICATES 600x600 CLEAR OPENING MANHOLE COVER AND FRAME OVER 750x600 CLEAR OPENING IN COVER SLAB ACCESS AS UNITED UTILITIES STANDARD DETAIL
--
I bullunited -1 ~ Utilities amp1ing life ow smoothy
Manhole 120 Schematic General All manholes should be constructed in accordance with United Utilities Developer Services Construction details Here are good examples
Key Points
When using 600 times 600 covers a 750 times 600 opening
in the cover slab must be used this can avoid any mistakes where ladders
are required
Rocker pipes shown or a general comment stating
rockers will be used in line with United Utiliities standard
detail variable features STND19010
Clay channel fittings used for pipes less than 375dia
Benching widths dimensioned
Manhole S1 MH Diameter 1500mm
Cover Level 107000
Invert Level 105000
MH Type 1
Depth to Soffit 1775
Depth to cut out NA
Cover Size 600 times 600mm
Cover Depth 150mm
Cover Spec D400
Ladder or Double Steps Double Steps
Safety Chain NA
Safety Rails NA
Invert Access Step NA
Hole Size in Cover Slab 600 times 750mm
Page 5 Developer Services Wastewater S104 Support Guide
1000 1 0000 1001 2 0000 2000 3 0000 2001 4 0000
2002 5 0000
1003 6 0000 1004 7 0000
MS-60 (mm) 18500 MADD Factor 2
Flow Control Manhole S7 - DS PN 1005 Unit Ref U U-0124-1000-2500-1000
Design Head 25
Sump Yes
Unit Diameter 124
Flow Control Invert 114515
65 74
20 22
25
7
12
1000 1001
2000
I J 1 middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot1
r middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot J
r I 1-middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot 1 Lmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot I r bullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullmiddotbullbulll L bullmiddot i
34m 25m
17m
P i pe N o
1 000
1 00 1
2 0 00
2 0 011
2 0 02
1 0 02
1 0 0 3
1 0 04
OK OK OK OK OK OK OK
1167 1167
1400
I mpe rme a b le Area (H a)
001 4H
0 10 6 H a
0 173H a
0 0 6 1 Ha
0 0 90H a
0063 H a
0 21 9 H a
0 104H a
T o ta l lm p e-mea b le A rea - O 8 30H a
0015 66244 67602 0025 66000 67600
0200 64500 67500
225 225
1200
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Hydraulics Where surface water sewers are proposed for adoption we require hydraulic calculations from a digital modelling software package See Sewers For Adoption 6th edition page 28 figure 213
Key Points
Design storm requirements bull No surcharge within the system in a 1 in 2
year Rank 1 storm event bull There is no flooding from the system
in a 1 in 30 year Rank 1 storm (against a surcharged outfall)
bull Please note the only pipe length expected to surcharge in the design storm is pipe downstream of the flow control manhole
Checking the simulation data and criteria bull Contributing impermeable areas (hard
standing areas) bull M5-M60 and Ratio Rndash Check Table of
hydraulics bull MADD Factor ndash No higher than 2
bull The cover and invert levels pipe lengths pipe diameter pipe gradients and contributing areas are consistent across all drawings
bull Online controls (flow control manholes ndash design head and pass forward flow)
bull Pond storage details are correct bull No private drainage lengths included
within network details
Impermeable areas Each impermeable area should represent a unique colour for the drainage area a
key should also be shown detailing the PN number and impermeable area in hectares
Page 6 Developer Services Wastewater S104 Support Guide
Developer Services Wastewater S104 Support Guide
1CL 15555 0 IL 155100
YES 30 1000 YES 40 1000 YES 50 1000
30 r YES 60 1000 30yr YES 70 1000
30 r YES 80 1000 30yr YES 90 1000 30 r YES 100 1000
I bullunited -1 ~ Utilities amp1ing life ow smoothy
Hydraulics continued
Page 7
Key Points
Standards to be checked within the results of the simulations
bull The results should show that the pipe velocities achieve a self-cleansing velocity
bull That high velocities are avoided (in excess of 4ms) - risk of scouring and erosion to benching and river banks
Additional check bull The water levels within the adoptable
manholes listed isnrsquot greater than any private drainage cover levels (for example where houses are lower than the relative level of the road)
1m Surcharge bull A 1m surcharge is to be applied to the soffit
of the receiving sewer with the 30yr storm simulated showing no flooding
Flood Routing bull A flood routing plan is required to support
your application showing that the layout and landscaping of the site aims to route water away from any vulnerable property National Planning Policy Framework usually explains that no flooding of properties should occur as a result of a one in 100 year storm event (including an appropriate allowance for climate change)
Velocity (ms) Result
159
256
250
263
229
tiQ s middot-s (U c 0 ltraquomiddot m tJmiddot E co bull m
10m Tanker Hardstanding
SEE U ILiTI DRA11NGAS SUPPUED BY O ER FOF leMCT ROIITES Of DUCTS
TMiKJER HARDSTANOING
12m Com10oundl lleneth
bull
bull
OS ANDING
J Cl Cl s 0 c E 0 u E
00
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Pumping Station Submission All Pump Station designs must be in line with Sewers for Adoption 7th edition and United Utilities Pumping Station Addendum Justification should always be provided with any submission which proposes a pumping station showing why a gravity soluction is not achievable Please ensure the below information is sent with Pumping Station applications
Typical example of a pumping station compound
bull All key areas show dimensions
bull Bollards for tanker safety
bull Full technical details expected on Pumping Station Design package
bull Non Rising Spindle Penstock chamber located within compound
Key Points
A full pumping station submission should include these documents drip feeding
documents is not acceptable
Document Provided Compound General Layout Drawing
Pumping Station General Arrangement Pumps
Hazardous Area Plan
Rising Main specification
Independent Rising Main Long Section Showing Air Valves and Washout Chambers where applicable (Air Valve to be suitable for Ww rising main)
Jointing Method ndash Fusion Welded confirmed
Surge Analysis (Rising Main Over 500m)
Floatation Check Calculations (Please note Ground Water is to be assumed from ground level) Flotation should be considered as an EQU limit state in accordance with BS EN 1997-1 Section 10 using partial load factors from table NAA12(A) of the UK National Annex to BS EN 1990
Storage Calculations and confirmation of storage location
Pump Calculations
Full Technical specification document
Penstock Isolation Chamber 120 Schematic showing non rising spindle
Tanker Swept Path Analysis drawing
Page 8 Developer Services Wastewater S104 Support Guide
Developer Services Wastewater S104 Support Guide
Sta~ion Typ e 3
iii Weill depth 42rn
iiil1 Well diameter 24m ivj Palisad1e fencing 18m
v) AH emeirgency stm rage
0011tained bulllt1-lrthin well
110mm HPPE SDR 17
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Pumping Station continued
Key Points
General comments Pumping Station location requires careful
consideration ideally away from SUDS features or watercourses Wet wells must be a minimum
distance from any habitable building as per SFA 7th table D1 page 62 with the clearance shown
on the drainage plan A note adjacent to the station should be
provided showing 1) PS Type 2) Well depth 3) Well diameter 4) Fencing type and height 5) Confirmation of Emergency Storage location
6) All electrical equipment should be sited above the 200 year storm level
Rising Main details Rising main specification must be shown on the drainage plan inlcluding
material diameter SDR rating Rising Main Bends Slow Long radius bends should be used avoiding sharp bends If thrust
blocks are required we require supporting calculations
Apparatus on Rising Mains Washout Air Valves (low points high points) must be shown on the drainage drawing and on the long section
Break Chamber The rising main should be kept to the minimum possible distance and
must terminate into a break chamber followed by a minimum 5m length of gravity sewer and a
connection at the soffit level of the existing sewer
Tanker Swept Path Analysis drawing showing an 8 wheel tanker can sufficiently and safely
turn then achieve a reverse manoeuvre into the compound and safely drive out
Rising Main details Rising Main Bends Apparatus on Rising Mains Break Chamber
Page 9
GRID REFERENCE 342587 E 439878 N
l===TI~
GR ID REFERENCE 342587 E 439878 N
C HUR C H V IEW
CHU R C H VIEW
-----------
CHURCHi VIIEW
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Land Registry Compliant drawings Land Registry Compliant drawings are required to enable United Utilities to aquire legal easements over new or existing sewers Drawing 1 shows on site easement examples Drawing 2 shows off site easement examples
Page 10 Developer Services Wastewater S104 Support Guide
Key Points
Scaled at 11250 or near as possible to fit on A3 sheet
Site boundary edged in green (must match
S104 Drainage Plan)
Exisitng road names or landmarks
North point
Easements clearly dimensioned either side from the centre line of the sewer
Drawing 1 ndash On site easements
Drawing 2 ndash Off site easements
J
__ ---
Legend
land ~o be transierred 0 United Ut itities
-~ bullmiddotmiddot bull middot _
L - middot middot middot hi
middot~ qe ~- us v~
I bullunited ~Utilities
~ 6 ow smoothy degtnghte
Land Transfer drawing Land Transfer drawings are required for Pumping Stations this enables United Utilities to transfer land ownership and obtain access rights
Key Points
Example of land trasnfer plan scaled at 1500 the drawing also includes an extract at
a greater scale to cover the drawing requirememts
Compound boundary edged in red
Existing road names landmarks
Any access rights to the station coloured brown (not shown on main example as the station is located off an
adoptable highway)
North point
Page 11 Developer Services Wastewater S104 Support Guide
Dear Mr Adoption
RE One permanent 300mm diameter surface water discharge connection (S57) into existing ordinary watercourse restricted to 321Js rate at UU Road Warrington
Thank you for you r application for Ordinary Watercour se Land Drainage Consent received by Any Other Counci(
I confirm t hat your proposals for the pe rman en t headwall are acce pt able to the Any Other Counci l shown on drawing number S104 Drainage Plan Rev 4
II
Samples arnd In Situ Testirng
Depth Type Results
030 ES
060 ES
0 90 ES
Depth Level (m) (m)
050
0 65
1()()
Stratum Description
MADE GROUND Brown sandy clayey set (Topsoil) with occasional roots and vey rare sub-rounded lo rounded lfrneston e pebbl es_
MADE GROUND Sofi brown sifiy sandy clay with rare sub-rounded to rounded to limestone and cllert pebb lemiddots_ 0 a nic odour
Light brownyellow clayey fine to medium SANO (Organ ic odou r)
End cf pit at 100 m
--
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Additional information
Ground conditions
TreesPlanting
Consents
Page 12 Developer Services Wastewater S104 Support Guide
Key Points
It is essential that thorough site investigation is undertaken as early as possible to avoid any
potential issues with new sewers
A full detailed SI report including trial pit borehole logs must be provided with a
Section 104 submission
Should you encounter challenging ground conditions (for example peat running sand or a fluctuating water table) you should provide
detailed information to justify your design proposals
Trial pit boreholes should be taken to a depth beneath the proposed invert level of any new
sewers to be laid
Should any planting be proposed adjacent to sewers these must conform to figure 23
page 33 SFA 6th
Sewers should be positioned to avoid TPO areas
bull Should your surface water sewers outfall to a watercourse please see Technical Guidance
Document Section 32
bull Formal Consent detailing acceptance of headwall and pass forward flow is required
Technical Guidance
Developer Services Wastewater S104 Support Guide
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Adoptions Process Flow
Initial Design Submitted
Progression to Technical Acceptance
Inspection Fees Paid
Legal Agreements Signed
Inspections as site progresses
Remedial list issued following 100 completion
of build and when occupancy above 50
Provisional Certificate Issued (12months
maintenance)
FinalVesting Certificate Issued
and bond fee released
Page 13
United Utilities Website httpwwwunitedutilitiescomdefaultaspx
Information and advice
Sewer Adoptions httpwwwunitedutilitiescomsewer-adoptions-buildaspx
United Utiliities Standard Details httpwwwunitedutilitiescomdocumentsdeveloper-services-construction-detailspdf
Site Sewer Construction Guide httpwwwunitedutilitiescomdocuments6805-contractors-guidepdf
Pre Development Enquiries httpwwwunitedutilitiescomplanning-wastewater-guidanceaspx
Developer Services Wastewater S104 Support Guide
0818SD7664
D Flow contro S6 (24 ia 1 manhole)
CLmiddot 98869 middot Ilt Opt imum
Hydrobra e rnational) (by Hydro ln~00-1600-8000 SHE-0123-8
Design 6 head 81s 1- m
Posit ion and L been have d and
surveyed as confirme shown
1 bullunited ~Utilities
-1 ow smoothi amp1inglite
Drainage Plan The drainage plan and design must meet Sewers for Adoption 6th edition and Developer Services Construction Details whilst also meeting our legal requirements See Sewers For Adoption 6th edition Section 24 Layout Of Sewers Manholes amp Rising Mains for more information The below images show a good example of what is expected
Only new adoptable drainage coloured for adoption
Manholes and sewers required distance from kerblines ndash SFA 6th section 24 figure 3 page 21
Trees conforming with SFA 6th figure 23 page 33
Finished floor levels for each plotGreen boundary covering
developers land
Large storage pipes laid no flatter than 1400
Sewers proposed for adoption as per SFA 6th section 24 layout of sewers page 21
Culverted Watercourse Connection This also shows a sustainable drainage strategy and requires relevant consent as per section 11 ndash Application for adoption of new sewers
Key Points
Pipe diameter material and gradient clearly shown
manhole cover and Invert levels clearly shown
Flow control chamber specification detailed ndash flow control chambers must be located in an
accessible location for future operational activities
Existing connection point invert level surveyed
and confirmed
Easement provided in 3rd party land
Private 100yr offline storage located in an accessible location with spill pipe
set above the 30yr water level
Scale 1500 This is an ideal scale for apprisals
Page 2 Developer Services Wastewater S104 Support Guide
I I I I
- SW Foul Combined - --0- bull bull - I - -~ - -_r _ G -al J11 if li
---
-- bull bull
bull bull
I bullunited -1 ~ Utilities amp1ing life ow smoothi
C
Drainage Plan continued
A
3m3m
3m3m
Revision Comments Changes by Checked by Date Key Points Updated as per United Utiliities Appraisal form of 190518
B AL MW 200518 amending outfall level
All drawings must contain a Easements added AL MW 220518 comments table it is good
practice to have any design D Foul Connection Point amended due to asset clash AL MW 010618
amendments checked
Updated as per United Utiliities Appraisal form of 170618 A detailed explanation ofE AL MW 180618amended storage tank location changes must be contained
Easements shown in yellow with width dimensioned from the centre line of the sewer
B C D
Surface water outfall to watercourse should
show easement including headwall the outfall level must be considered and include an appropriate
freeboard allowance see Section 104 technical
guidance document section 335 for more information
Examples A Sewers coloured
as per SFA
Existing sewers coloured black
Abandoned sewer black with crosses also confirming the method of abandonment
Gullys black labelled ldquoGrdquo
B
C
D
Page 3 Developer Services Wastewater S104 Support Guide
~ ~ ~~ I I
I I I
9 9 _
la ~ - --- --- --5002
- ~002 - -~
~ OMJOm
- - - ~ - -
I =~npll
g
STOR lIApR 00IEJU EIIR
SfOnWil lt IN1pound1t ~
llpaS m
SHiWWER CIElM S CitMr CIAY
~le c~ s ooo ~ sumouncl
SiORllMTffi wlGfHS 31132
FOlJlWfflR C~~ POULW1_TER INERJ
~Dill Olii150 iOulWmi CJEfAPI$ eh 0 t
I ln$C S1ttmgm41luun
~ i--t~ __ __ __
~ ~ ~ ~ I I
r la d~tmg 6-rid I I rJ ~ll CDltJn 1
9 I
b b
_ ~-1111-- - --__ ____
I I
-- -~- ru bull -- 1- Dbull ~
~ - --~ - - -- - -
~ 5 )
-middot 2
I~ N N
~ sect bull e
~o([ll ilpaMl)(I i m Oiffl
QrcJ - CV einilr CL
Sttingm P8 Uim strenu IIUllm Cl1u S - 1 auoI 51JJm1DMI CbsB S lied~ WIWllllll
lt04~ 21~
Bi ~ i ~ - ~
II ii
pe S00 Pp_00
Olli~ Oa1~ CWWOA- C~CiAt
~~IJ kNm nfl
5trelglll CJ kNml -~ltI IIIQ =- bull cbull~~ ltgt ~-~
I I
Pipe 2 Di~ 225
cmiddot _ 1~r CLAY middot8
s tren~ ~5 k Im Glass s bed and SllIITOlmdl
STORMWATER COVER LEVEL
STORMWATER INVERT
-
o-------- bull
5002
H lco 5002
~
iii ~
-
I ~= I
_
V ~ -04~0middotrnmiddot ce~r~~~ ~~~e~~ ~i~e~
gt12m roverto sotfrt of se we1
_ _I
~~-
-- - --
--
--
--
--
I bullunited -1 ~ Utilities amp1ing life ow smoothy
Long Section General
All Connections must be soffit to soffit
30yr TWL Both foul and surface water sewers
shown on one long section
Key Points
PN Name pipe diameter material gradient and pipe
bedding shown for each pipe
Manhole cover and invert levels for each chamber
30yr critical storm top water level added
Any pipe crossing show the clearance achieved from invert of highest sewer to
soffit of lowest sewer Please note the minimum clearance is 300mm however this is site
specific and dependant on the pipe size crossings
Sewers in highway achieveing gt12m cover to
soffit of pipe ndash See SFA 6th figure 210 page 27
Page 4 Developer Services Wastewater S104 Support Guide
INDICATES tl001c600 CEAA OPEN ING MANHOLE COiER AND _ FRAME OVER 75llll6DD CLEAR OPENING N COJER SIAB ACCESSIS UNITED UTILITIES STANDARD DET L
INDICATES 600x600 CLEAR OPENING MANHOLE COVER AND FRAME OVER 750x600 CLEAR OPENING IN COVER SLAB ACCESS AS UNITED UTILITIES STANDARD DETAIL
--
I bullunited -1 ~ Utilities amp1ing life ow smoothy
Manhole 120 Schematic General All manholes should be constructed in accordance with United Utilities Developer Services Construction details Here are good examples
Key Points
When using 600 times 600 covers a 750 times 600 opening
in the cover slab must be used this can avoid any mistakes where ladders
are required
Rocker pipes shown or a general comment stating
rockers will be used in line with United Utiliities standard
detail variable features STND19010
Clay channel fittings used for pipes less than 375dia
Benching widths dimensioned
Manhole S1 MH Diameter 1500mm
Cover Level 107000
Invert Level 105000
MH Type 1
Depth to Soffit 1775
Depth to cut out NA
Cover Size 600 times 600mm
Cover Depth 150mm
Cover Spec D400
Ladder or Double Steps Double Steps
Safety Chain NA
Safety Rails NA
Invert Access Step NA
Hole Size in Cover Slab 600 times 750mm
Page 5 Developer Services Wastewater S104 Support Guide
1000 1 0000 1001 2 0000 2000 3 0000 2001 4 0000
2002 5 0000
1003 6 0000 1004 7 0000
MS-60 (mm) 18500 MADD Factor 2
Flow Control Manhole S7 - DS PN 1005 Unit Ref U U-0124-1000-2500-1000
Design Head 25
Sump Yes
Unit Diameter 124
Flow Control Invert 114515
65 74
20 22
25
7
12
1000 1001
2000
I J 1 middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot1
r middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot J
r I 1-middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot 1 Lmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot I r bullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullmiddotbullbulll L bullmiddot i
34m 25m
17m
P i pe N o
1 000
1 00 1
2 0 00
2 0 011
2 0 02
1 0 02
1 0 0 3
1 0 04
OK OK OK OK OK OK OK
1167 1167
1400
I mpe rme a b le Area (H a)
001 4H
0 10 6 H a
0 173H a
0 0 6 1 Ha
0 0 90H a
0063 H a
0 21 9 H a
0 104H a
T o ta l lm p e-mea b le A rea - O 8 30H a
0015 66244 67602 0025 66000 67600
0200 64500 67500
225 225
1200
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Hydraulics Where surface water sewers are proposed for adoption we require hydraulic calculations from a digital modelling software package See Sewers For Adoption 6th edition page 28 figure 213
Key Points
Design storm requirements bull No surcharge within the system in a 1 in 2
year Rank 1 storm event bull There is no flooding from the system
in a 1 in 30 year Rank 1 storm (against a surcharged outfall)
bull Please note the only pipe length expected to surcharge in the design storm is pipe downstream of the flow control manhole
Checking the simulation data and criteria bull Contributing impermeable areas (hard
standing areas) bull M5-M60 and Ratio Rndash Check Table of
hydraulics bull MADD Factor ndash No higher than 2
bull The cover and invert levels pipe lengths pipe diameter pipe gradients and contributing areas are consistent across all drawings
bull Online controls (flow control manholes ndash design head and pass forward flow)
bull Pond storage details are correct bull No private drainage lengths included
within network details
Impermeable areas Each impermeable area should represent a unique colour for the drainage area a
key should also be shown detailing the PN number and impermeable area in hectares
Page 6 Developer Services Wastewater S104 Support Guide
Developer Services Wastewater S104 Support Guide
1CL 15555 0 IL 155100
YES 30 1000 YES 40 1000 YES 50 1000
30 r YES 60 1000 30yr YES 70 1000
30 r YES 80 1000 30yr YES 90 1000 30 r YES 100 1000
I bullunited -1 ~ Utilities amp1ing life ow smoothy
Hydraulics continued
Page 7
Key Points
Standards to be checked within the results of the simulations
bull The results should show that the pipe velocities achieve a self-cleansing velocity
bull That high velocities are avoided (in excess of 4ms) - risk of scouring and erosion to benching and river banks
Additional check bull The water levels within the adoptable
manholes listed isnrsquot greater than any private drainage cover levels (for example where houses are lower than the relative level of the road)
1m Surcharge bull A 1m surcharge is to be applied to the soffit
of the receiving sewer with the 30yr storm simulated showing no flooding
Flood Routing bull A flood routing plan is required to support
your application showing that the layout and landscaping of the site aims to route water away from any vulnerable property National Planning Policy Framework usually explains that no flooding of properties should occur as a result of a one in 100 year storm event (including an appropriate allowance for climate change)
Velocity (ms) Result
159
256
250
263
229
tiQ s middot-s (U c 0 ltraquomiddot m tJmiddot E co bull m
10m Tanker Hardstanding
SEE U ILiTI DRA11NGAS SUPPUED BY O ER FOF leMCT ROIITES Of DUCTS
TMiKJER HARDSTANOING
12m Com10oundl lleneth
bull
bull
OS ANDING
J Cl Cl s 0 c E 0 u E
00
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Pumping Station Submission All Pump Station designs must be in line with Sewers for Adoption 7th edition and United Utilities Pumping Station Addendum Justification should always be provided with any submission which proposes a pumping station showing why a gravity soluction is not achievable Please ensure the below information is sent with Pumping Station applications
Typical example of a pumping station compound
bull All key areas show dimensions
bull Bollards for tanker safety
bull Full technical details expected on Pumping Station Design package
bull Non Rising Spindle Penstock chamber located within compound
Key Points
A full pumping station submission should include these documents drip feeding
documents is not acceptable
Document Provided Compound General Layout Drawing
Pumping Station General Arrangement Pumps
Hazardous Area Plan
Rising Main specification
Independent Rising Main Long Section Showing Air Valves and Washout Chambers where applicable (Air Valve to be suitable for Ww rising main)
Jointing Method ndash Fusion Welded confirmed
Surge Analysis (Rising Main Over 500m)
Floatation Check Calculations (Please note Ground Water is to be assumed from ground level) Flotation should be considered as an EQU limit state in accordance with BS EN 1997-1 Section 10 using partial load factors from table NAA12(A) of the UK National Annex to BS EN 1990
Storage Calculations and confirmation of storage location
Pump Calculations
Full Technical specification document
Penstock Isolation Chamber 120 Schematic showing non rising spindle
Tanker Swept Path Analysis drawing
Page 8 Developer Services Wastewater S104 Support Guide
Developer Services Wastewater S104 Support Guide
Sta~ion Typ e 3
iii Weill depth 42rn
iiil1 Well diameter 24m ivj Palisad1e fencing 18m
v) AH emeirgency stm rage
0011tained bulllt1-lrthin well
110mm HPPE SDR 17
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Pumping Station continued
Key Points
General comments Pumping Station location requires careful
consideration ideally away from SUDS features or watercourses Wet wells must be a minimum
distance from any habitable building as per SFA 7th table D1 page 62 with the clearance shown
on the drainage plan A note adjacent to the station should be
provided showing 1) PS Type 2) Well depth 3) Well diameter 4) Fencing type and height 5) Confirmation of Emergency Storage location
6) All electrical equipment should be sited above the 200 year storm level
Rising Main details Rising main specification must be shown on the drainage plan inlcluding
material diameter SDR rating Rising Main Bends Slow Long radius bends should be used avoiding sharp bends If thrust
blocks are required we require supporting calculations
Apparatus on Rising Mains Washout Air Valves (low points high points) must be shown on the drainage drawing and on the long section
Break Chamber The rising main should be kept to the minimum possible distance and
must terminate into a break chamber followed by a minimum 5m length of gravity sewer and a
connection at the soffit level of the existing sewer
Tanker Swept Path Analysis drawing showing an 8 wheel tanker can sufficiently and safely
turn then achieve a reverse manoeuvre into the compound and safely drive out
Rising Main details Rising Main Bends Apparatus on Rising Mains Break Chamber
Page 9
GRID REFERENCE 342587 E 439878 N
l===TI~
GR ID REFERENCE 342587 E 439878 N
C HUR C H V IEW
CHU R C H VIEW
-----------
CHURCHi VIIEW
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Land Registry Compliant drawings Land Registry Compliant drawings are required to enable United Utilities to aquire legal easements over new or existing sewers Drawing 1 shows on site easement examples Drawing 2 shows off site easement examples
Page 10 Developer Services Wastewater S104 Support Guide
Key Points
Scaled at 11250 or near as possible to fit on A3 sheet
Site boundary edged in green (must match
S104 Drainage Plan)
Exisitng road names or landmarks
North point
Easements clearly dimensioned either side from the centre line of the sewer
Drawing 1 ndash On site easements
Drawing 2 ndash Off site easements
J
__ ---
Legend
land ~o be transierred 0 United Ut itities
-~ bullmiddotmiddot bull middot _
L - middot middot middot hi
middot~ qe ~- us v~
I bullunited ~Utilities
~ 6 ow smoothy degtnghte
Land Transfer drawing Land Transfer drawings are required for Pumping Stations this enables United Utilities to transfer land ownership and obtain access rights
Key Points
Example of land trasnfer plan scaled at 1500 the drawing also includes an extract at
a greater scale to cover the drawing requirememts
Compound boundary edged in red
Existing road names landmarks
Any access rights to the station coloured brown (not shown on main example as the station is located off an
adoptable highway)
North point
Page 11 Developer Services Wastewater S104 Support Guide
Dear Mr Adoption
RE One permanent 300mm diameter surface water discharge connection (S57) into existing ordinary watercourse restricted to 321Js rate at UU Road Warrington
Thank you for you r application for Ordinary Watercour se Land Drainage Consent received by Any Other Counci(
I confirm t hat your proposals for the pe rman en t headwall are acce pt able to the Any Other Counci l shown on drawing number S104 Drainage Plan Rev 4
II
Samples arnd In Situ Testirng
Depth Type Results
030 ES
060 ES
0 90 ES
Depth Level (m) (m)
050
0 65
1()()
Stratum Description
MADE GROUND Brown sandy clayey set (Topsoil) with occasional roots and vey rare sub-rounded lo rounded lfrneston e pebbl es_
MADE GROUND Sofi brown sifiy sandy clay with rare sub-rounded to rounded to limestone and cllert pebb lemiddots_ 0 a nic odour
Light brownyellow clayey fine to medium SANO (Organ ic odou r)
End cf pit at 100 m
--
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Additional information
Ground conditions
TreesPlanting
Consents
Page 12 Developer Services Wastewater S104 Support Guide
Key Points
It is essential that thorough site investigation is undertaken as early as possible to avoid any
potential issues with new sewers
A full detailed SI report including trial pit borehole logs must be provided with a
Section 104 submission
Should you encounter challenging ground conditions (for example peat running sand or a fluctuating water table) you should provide
detailed information to justify your design proposals
Trial pit boreholes should be taken to a depth beneath the proposed invert level of any new
sewers to be laid
Should any planting be proposed adjacent to sewers these must conform to figure 23
page 33 SFA 6th
Sewers should be positioned to avoid TPO areas
bull Should your surface water sewers outfall to a watercourse please see Technical Guidance
Document Section 32
bull Formal Consent detailing acceptance of headwall and pass forward flow is required
Technical Guidance
Developer Services Wastewater S104 Support Guide
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Adoptions Process Flow
Initial Design Submitted
Progression to Technical Acceptance
Inspection Fees Paid
Legal Agreements Signed
Inspections as site progresses
Remedial list issued following 100 completion
of build and when occupancy above 50
Provisional Certificate Issued (12months
maintenance)
FinalVesting Certificate Issued
and bond fee released
Page 13
United Utilities Website httpwwwunitedutilitiescomdefaultaspx
Information and advice
Sewer Adoptions httpwwwunitedutilitiescomsewer-adoptions-buildaspx
United Utiliities Standard Details httpwwwunitedutilitiescomdocumentsdeveloper-services-construction-detailspdf
Site Sewer Construction Guide httpwwwunitedutilitiescomdocuments6805-contractors-guidepdf
Pre Development Enquiries httpwwwunitedutilitiescomplanning-wastewater-guidanceaspx
Developer Services Wastewater S104 Support Guide
0818SD7664
I I I I
- SW Foul Combined - --0- bull bull - I - -~ - -_r _ G -al J11 if li
---
-- bull bull
bull bull
I bullunited -1 ~ Utilities amp1ing life ow smoothi
C
Drainage Plan continued
A
3m3m
3m3m
Revision Comments Changes by Checked by Date Key Points Updated as per United Utiliities Appraisal form of 190518
B AL MW 200518 amending outfall level
All drawings must contain a Easements added AL MW 220518 comments table it is good
practice to have any design D Foul Connection Point amended due to asset clash AL MW 010618
amendments checked
Updated as per United Utiliities Appraisal form of 170618 A detailed explanation ofE AL MW 180618amended storage tank location changes must be contained
Easements shown in yellow with width dimensioned from the centre line of the sewer
B C D
Surface water outfall to watercourse should
show easement including headwall the outfall level must be considered and include an appropriate
freeboard allowance see Section 104 technical
guidance document section 335 for more information
Examples A Sewers coloured
as per SFA
Existing sewers coloured black
Abandoned sewer black with crosses also confirming the method of abandonment
Gullys black labelled ldquoGrdquo
B
C
D
Page 3 Developer Services Wastewater S104 Support Guide
~ ~ ~~ I I
I I I
9 9 _
la ~ - --- --- --5002
- ~002 - -~
~ OMJOm
- - - ~ - -
I =~npll
g
STOR lIApR 00IEJU EIIR
SfOnWil lt IN1pound1t ~
llpaS m
SHiWWER CIElM S CitMr CIAY
~le c~ s ooo ~ sumouncl
SiORllMTffi wlGfHS 31132
FOlJlWfflR C~~ POULW1_TER INERJ
~Dill Olii150 iOulWmi CJEfAPI$ eh 0 t
I ln$C S1ttmgm41luun
~ i--t~ __ __ __
~ ~ ~ ~ I I
r la d~tmg 6-rid I I rJ ~ll CDltJn 1
9 I
b b
_ ~-1111-- - --__ ____
I I
-- -~- ru bull -- 1- Dbull ~
~ - --~ - - -- - -
~ 5 )
-middot 2
I~ N N
~ sect bull e
~o([ll ilpaMl)(I i m Oiffl
QrcJ - CV einilr CL
Sttingm P8 Uim strenu IIUllm Cl1u S - 1 auoI 51JJm1DMI CbsB S lied~ WIWllllll
lt04~ 21~
Bi ~ i ~ - ~
II ii
pe S00 Pp_00
Olli~ Oa1~ CWWOA- C~CiAt
~~IJ kNm nfl
5trelglll CJ kNml -~ltI IIIQ =- bull cbull~~ ltgt ~-~
I I
Pipe 2 Di~ 225
cmiddot _ 1~r CLAY middot8
s tren~ ~5 k Im Glass s bed and SllIITOlmdl
STORMWATER COVER LEVEL
STORMWATER INVERT
-
o-------- bull
5002
H lco 5002
~
iii ~
-
I ~= I
_
V ~ -04~0middotrnmiddot ce~r~~~ ~~~e~~ ~i~e~
gt12m roverto sotfrt of se we1
_ _I
~~-
-- - --
--
--
--
--
I bullunited -1 ~ Utilities amp1ing life ow smoothy
Long Section General
All Connections must be soffit to soffit
30yr TWL Both foul and surface water sewers
shown on one long section
Key Points
PN Name pipe diameter material gradient and pipe
bedding shown for each pipe
Manhole cover and invert levels for each chamber
30yr critical storm top water level added
Any pipe crossing show the clearance achieved from invert of highest sewer to
soffit of lowest sewer Please note the minimum clearance is 300mm however this is site
specific and dependant on the pipe size crossings
Sewers in highway achieveing gt12m cover to
soffit of pipe ndash See SFA 6th figure 210 page 27
Page 4 Developer Services Wastewater S104 Support Guide
INDICATES tl001c600 CEAA OPEN ING MANHOLE COiER AND _ FRAME OVER 75llll6DD CLEAR OPENING N COJER SIAB ACCESSIS UNITED UTILITIES STANDARD DET L
INDICATES 600x600 CLEAR OPENING MANHOLE COVER AND FRAME OVER 750x600 CLEAR OPENING IN COVER SLAB ACCESS AS UNITED UTILITIES STANDARD DETAIL
--
I bullunited -1 ~ Utilities amp1ing life ow smoothy
Manhole 120 Schematic General All manholes should be constructed in accordance with United Utilities Developer Services Construction details Here are good examples
Key Points
When using 600 times 600 covers a 750 times 600 opening
in the cover slab must be used this can avoid any mistakes where ladders
are required
Rocker pipes shown or a general comment stating
rockers will be used in line with United Utiliities standard
detail variable features STND19010
Clay channel fittings used for pipes less than 375dia
Benching widths dimensioned
Manhole S1 MH Diameter 1500mm
Cover Level 107000
Invert Level 105000
MH Type 1
Depth to Soffit 1775
Depth to cut out NA
Cover Size 600 times 600mm
Cover Depth 150mm
Cover Spec D400
Ladder or Double Steps Double Steps
Safety Chain NA
Safety Rails NA
Invert Access Step NA
Hole Size in Cover Slab 600 times 750mm
Page 5 Developer Services Wastewater S104 Support Guide
1000 1 0000 1001 2 0000 2000 3 0000 2001 4 0000
2002 5 0000
1003 6 0000 1004 7 0000
MS-60 (mm) 18500 MADD Factor 2
Flow Control Manhole S7 - DS PN 1005 Unit Ref U U-0124-1000-2500-1000
Design Head 25
Sump Yes
Unit Diameter 124
Flow Control Invert 114515
65 74
20 22
25
7
12
1000 1001
2000
I J 1 middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot1
r middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot J
r I 1-middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot 1 Lmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot I r bullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullmiddotbullbulll L bullmiddot i
34m 25m
17m
P i pe N o
1 000
1 00 1
2 0 00
2 0 011
2 0 02
1 0 02
1 0 0 3
1 0 04
OK OK OK OK OK OK OK
1167 1167
1400
I mpe rme a b le Area (H a)
001 4H
0 10 6 H a
0 173H a
0 0 6 1 Ha
0 0 90H a
0063 H a
0 21 9 H a
0 104H a
T o ta l lm p e-mea b le A rea - O 8 30H a
0015 66244 67602 0025 66000 67600
0200 64500 67500
225 225
1200
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Hydraulics Where surface water sewers are proposed for adoption we require hydraulic calculations from a digital modelling software package See Sewers For Adoption 6th edition page 28 figure 213
Key Points
Design storm requirements bull No surcharge within the system in a 1 in 2
year Rank 1 storm event bull There is no flooding from the system
in a 1 in 30 year Rank 1 storm (against a surcharged outfall)
bull Please note the only pipe length expected to surcharge in the design storm is pipe downstream of the flow control manhole
Checking the simulation data and criteria bull Contributing impermeable areas (hard
standing areas) bull M5-M60 and Ratio Rndash Check Table of
hydraulics bull MADD Factor ndash No higher than 2
bull The cover and invert levels pipe lengths pipe diameter pipe gradients and contributing areas are consistent across all drawings
bull Online controls (flow control manholes ndash design head and pass forward flow)
bull Pond storage details are correct bull No private drainage lengths included
within network details
Impermeable areas Each impermeable area should represent a unique colour for the drainage area a
key should also be shown detailing the PN number and impermeable area in hectares
Page 6 Developer Services Wastewater S104 Support Guide
Developer Services Wastewater S104 Support Guide
1CL 15555 0 IL 155100
YES 30 1000 YES 40 1000 YES 50 1000
30 r YES 60 1000 30yr YES 70 1000
30 r YES 80 1000 30yr YES 90 1000 30 r YES 100 1000
I bullunited -1 ~ Utilities amp1ing life ow smoothy
Hydraulics continued
Page 7
Key Points
Standards to be checked within the results of the simulations
bull The results should show that the pipe velocities achieve a self-cleansing velocity
bull That high velocities are avoided (in excess of 4ms) - risk of scouring and erosion to benching and river banks
Additional check bull The water levels within the adoptable
manholes listed isnrsquot greater than any private drainage cover levels (for example where houses are lower than the relative level of the road)
1m Surcharge bull A 1m surcharge is to be applied to the soffit
of the receiving sewer with the 30yr storm simulated showing no flooding
Flood Routing bull A flood routing plan is required to support
your application showing that the layout and landscaping of the site aims to route water away from any vulnerable property National Planning Policy Framework usually explains that no flooding of properties should occur as a result of a one in 100 year storm event (including an appropriate allowance for climate change)
Velocity (ms) Result
159
256
250
263
229
tiQ s middot-s (U c 0 ltraquomiddot m tJmiddot E co bull m
10m Tanker Hardstanding
SEE U ILiTI DRA11NGAS SUPPUED BY O ER FOF leMCT ROIITES Of DUCTS
TMiKJER HARDSTANOING
12m Com10oundl lleneth
bull
bull
OS ANDING
J Cl Cl s 0 c E 0 u E
00
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Pumping Station Submission All Pump Station designs must be in line with Sewers for Adoption 7th edition and United Utilities Pumping Station Addendum Justification should always be provided with any submission which proposes a pumping station showing why a gravity soluction is not achievable Please ensure the below information is sent with Pumping Station applications
Typical example of a pumping station compound
bull All key areas show dimensions
bull Bollards for tanker safety
bull Full technical details expected on Pumping Station Design package
bull Non Rising Spindle Penstock chamber located within compound
Key Points
A full pumping station submission should include these documents drip feeding
documents is not acceptable
Document Provided Compound General Layout Drawing
Pumping Station General Arrangement Pumps
Hazardous Area Plan
Rising Main specification
Independent Rising Main Long Section Showing Air Valves and Washout Chambers where applicable (Air Valve to be suitable for Ww rising main)
Jointing Method ndash Fusion Welded confirmed
Surge Analysis (Rising Main Over 500m)
Floatation Check Calculations (Please note Ground Water is to be assumed from ground level) Flotation should be considered as an EQU limit state in accordance with BS EN 1997-1 Section 10 using partial load factors from table NAA12(A) of the UK National Annex to BS EN 1990
Storage Calculations and confirmation of storage location
Pump Calculations
Full Technical specification document
Penstock Isolation Chamber 120 Schematic showing non rising spindle
Tanker Swept Path Analysis drawing
Page 8 Developer Services Wastewater S104 Support Guide
Developer Services Wastewater S104 Support Guide
Sta~ion Typ e 3
iii Weill depth 42rn
iiil1 Well diameter 24m ivj Palisad1e fencing 18m
v) AH emeirgency stm rage
0011tained bulllt1-lrthin well
110mm HPPE SDR 17
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Pumping Station continued
Key Points
General comments Pumping Station location requires careful
consideration ideally away from SUDS features or watercourses Wet wells must be a minimum
distance from any habitable building as per SFA 7th table D1 page 62 with the clearance shown
on the drainage plan A note adjacent to the station should be
provided showing 1) PS Type 2) Well depth 3) Well diameter 4) Fencing type and height 5) Confirmation of Emergency Storage location
6) All electrical equipment should be sited above the 200 year storm level
Rising Main details Rising main specification must be shown on the drainage plan inlcluding
material diameter SDR rating Rising Main Bends Slow Long radius bends should be used avoiding sharp bends If thrust
blocks are required we require supporting calculations
Apparatus on Rising Mains Washout Air Valves (low points high points) must be shown on the drainage drawing and on the long section
Break Chamber The rising main should be kept to the minimum possible distance and
must terminate into a break chamber followed by a minimum 5m length of gravity sewer and a
connection at the soffit level of the existing sewer
Tanker Swept Path Analysis drawing showing an 8 wheel tanker can sufficiently and safely
turn then achieve a reverse manoeuvre into the compound and safely drive out
Rising Main details Rising Main Bends Apparatus on Rising Mains Break Chamber
Page 9
GRID REFERENCE 342587 E 439878 N
l===TI~
GR ID REFERENCE 342587 E 439878 N
C HUR C H V IEW
CHU R C H VIEW
-----------
CHURCHi VIIEW
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Land Registry Compliant drawings Land Registry Compliant drawings are required to enable United Utilities to aquire legal easements over new or existing sewers Drawing 1 shows on site easement examples Drawing 2 shows off site easement examples
Page 10 Developer Services Wastewater S104 Support Guide
Key Points
Scaled at 11250 or near as possible to fit on A3 sheet
Site boundary edged in green (must match
S104 Drainage Plan)
Exisitng road names or landmarks
North point
Easements clearly dimensioned either side from the centre line of the sewer
Drawing 1 ndash On site easements
Drawing 2 ndash Off site easements
J
__ ---
Legend
land ~o be transierred 0 United Ut itities
-~ bullmiddotmiddot bull middot _
L - middot middot middot hi
middot~ qe ~- us v~
I bullunited ~Utilities
~ 6 ow smoothy degtnghte
Land Transfer drawing Land Transfer drawings are required for Pumping Stations this enables United Utilities to transfer land ownership and obtain access rights
Key Points
Example of land trasnfer plan scaled at 1500 the drawing also includes an extract at
a greater scale to cover the drawing requirememts
Compound boundary edged in red
Existing road names landmarks
Any access rights to the station coloured brown (not shown on main example as the station is located off an
adoptable highway)
North point
Page 11 Developer Services Wastewater S104 Support Guide
Dear Mr Adoption
RE One permanent 300mm diameter surface water discharge connection (S57) into existing ordinary watercourse restricted to 321Js rate at UU Road Warrington
Thank you for you r application for Ordinary Watercour se Land Drainage Consent received by Any Other Counci(
I confirm t hat your proposals for the pe rman en t headwall are acce pt able to the Any Other Counci l shown on drawing number S104 Drainage Plan Rev 4
II
Samples arnd In Situ Testirng
Depth Type Results
030 ES
060 ES
0 90 ES
Depth Level (m) (m)
050
0 65
1()()
Stratum Description
MADE GROUND Brown sandy clayey set (Topsoil) with occasional roots and vey rare sub-rounded lo rounded lfrneston e pebbl es_
MADE GROUND Sofi brown sifiy sandy clay with rare sub-rounded to rounded to limestone and cllert pebb lemiddots_ 0 a nic odour
Light brownyellow clayey fine to medium SANO (Organ ic odou r)
End cf pit at 100 m
--
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Additional information
Ground conditions
TreesPlanting
Consents
Page 12 Developer Services Wastewater S104 Support Guide
Key Points
It is essential that thorough site investigation is undertaken as early as possible to avoid any
potential issues with new sewers
A full detailed SI report including trial pit borehole logs must be provided with a
Section 104 submission
Should you encounter challenging ground conditions (for example peat running sand or a fluctuating water table) you should provide
detailed information to justify your design proposals
Trial pit boreholes should be taken to a depth beneath the proposed invert level of any new
sewers to be laid
Should any planting be proposed adjacent to sewers these must conform to figure 23
page 33 SFA 6th
Sewers should be positioned to avoid TPO areas
bull Should your surface water sewers outfall to a watercourse please see Technical Guidance
Document Section 32
bull Formal Consent detailing acceptance of headwall and pass forward flow is required
Technical Guidance
Developer Services Wastewater S104 Support Guide
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Adoptions Process Flow
Initial Design Submitted
Progression to Technical Acceptance
Inspection Fees Paid
Legal Agreements Signed
Inspections as site progresses
Remedial list issued following 100 completion
of build and when occupancy above 50
Provisional Certificate Issued (12months
maintenance)
FinalVesting Certificate Issued
and bond fee released
Page 13
United Utilities Website httpwwwunitedutilitiescomdefaultaspx
Information and advice
Sewer Adoptions httpwwwunitedutilitiescomsewer-adoptions-buildaspx
United Utiliities Standard Details httpwwwunitedutilitiescomdocumentsdeveloper-services-construction-detailspdf
Site Sewer Construction Guide httpwwwunitedutilitiescomdocuments6805-contractors-guidepdf
Pre Development Enquiries httpwwwunitedutilitiescomplanning-wastewater-guidanceaspx
Developer Services Wastewater S104 Support Guide
0818SD7664
~ ~ ~~ I I
I I I
9 9 _
la ~ - --- --- --5002
- ~002 - -~
~ OMJOm
- - - ~ - -
I =~npll
g
STOR lIApR 00IEJU EIIR
SfOnWil lt IN1pound1t ~
llpaS m
SHiWWER CIElM S CitMr CIAY
~le c~ s ooo ~ sumouncl
SiORllMTffi wlGfHS 31132
FOlJlWfflR C~~ POULW1_TER INERJ
~Dill Olii150 iOulWmi CJEfAPI$ eh 0 t
I ln$C S1ttmgm41luun
~ i--t~ __ __ __
~ ~ ~ ~ I I
r la d~tmg 6-rid I I rJ ~ll CDltJn 1
9 I
b b
_ ~-1111-- - --__ ____
I I
-- -~- ru bull -- 1- Dbull ~
~ - --~ - - -- - -
~ 5 )
-middot 2
I~ N N
~ sect bull e
~o([ll ilpaMl)(I i m Oiffl
QrcJ - CV einilr CL
Sttingm P8 Uim strenu IIUllm Cl1u S - 1 auoI 51JJm1DMI CbsB S lied~ WIWllllll
lt04~ 21~
Bi ~ i ~ - ~
II ii
pe S00 Pp_00
Olli~ Oa1~ CWWOA- C~CiAt
~~IJ kNm nfl
5trelglll CJ kNml -~ltI IIIQ =- bull cbull~~ ltgt ~-~
I I
Pipe 2 Di~ 225
cmiddot _ 1~r CLAY middot8
s tren~ ~5 k Im Glass s bed and SllIITOlmdl
STORMWATER COVER LEVEL
STORMWATER INVERT
-
o-------- bull
5002
H lco 5002
~
iii ~
-
I ~= I
_
V ~ -04~0middotrnmiddot ce~r~~~ ~~~e~~ ~i~e~
gt12m roverto sotfrt of se we1
_ _I
~~-
-- - --
--
--
--
--
I bullunited -1 ~ Utilities amp1ing life ow smoothy
Long Section General
All Connections must be soffit to soffit
30yr TWL Both foul and surface water sewers
shown on one long section
Key Points
PN Name pipe diameter material gradient and pipe
bedding shown for each pipe
Manhole cover and invert levels for each chamber
30yr critical storm top water level added
Any pipe crossing show the clearance achieved from invert of highest sewer to
soffit of lowest sewer Please note the minimum clearance is 300mm however this is site
specific and dependant on the pipe size crossings
Sewers in highway achieveing gt12m cover to
soffit of pipe ndash See SFA 6th figure 210 page 27
Page 4 Developer Services Wastewater S104 Support Guide
INDICATES tl001c600 CEAA OPEN ING MANHOLE COiER AND _ FRAME OVER 75llll6DD CLEAR OPENING N COJER SIAB ACCESSIS UNITED UTILITIES STANDARD DET L
INDICATES 600x600 CLEAR OPENING MANHOLE COVER AND FRAME OVER 750x600 CLEAR OPENING IN COVER SLAB ACCESS AS UNITED UTILITIES STANDARD DETAIL
--
I bullunited -1 ~ Utilities amp1ing life ow smoothy
Manhole 120 Schematic General All manholes should be constructed in accordance with United Utilities Developer Services Construction details Here are good examples
Key Points
When using 600 times 600 covers a 750 times 600 opening
in the cover slab must be used this can avoid any mistakes where ladders
are required
Rocker pipes shown or a general comment stating
rockers will be used in line with United Utiliities standard
detail variable features STND19010
Clay channel fittings used for pipes less than 375dia
Benching widths dimensioned
Manhole S1 MH Diameter 1500mm
Cover Level 107000
Invert Level 105000
MH Type 1
Depth to Soffit 1775
Depth to cut out NA
Cover Size 600 times 600mm
Cover Depth 150mm
Cover Spec D400
Ladder or Double Steps Double Steps
Safety Chain NA
Safety Rails NA
Invert Access Step NA
Hole Size in Cover Slab 600 times 750mm
Page 5 Developer Services Wastewater S104 Support Guide
1000 1 0000 1001 2 0000 2000 3 0000 2001 4 0000
2002 5 0000
1003 6 0000 1004 7 0000
MS-60 (mm) 18500 MADD Factor 2
Flow Control Manhole S7 - DS PN 1005 Unit Ref U U-0124-1000-2500-1000
Design Head 25
Sump Yes
Unit Diameter 124
Flow Control Invert 114515
65 74
20 22
25
7
12
1000 1001
2000
I J 1 middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot1
r middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot J
r I 1-middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot 1 Lmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot I r bullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullmiddotbullbulll L bullmiddot i
34m 25m
17m
P i pe N o
1 000
1 00 1
2 0 00
2 0 011
2 0 02
1 0 02
1 0 0 3
1 0 04
OK OK OK OK OK OK OK
1167 1167
1400
I mpe rme a b le Area (H a)
001 4H
0 10 6 H a
0 173H a
0 0 6 1 Ha
0 0 90H a
0063 H a
0 21 9 H a
0 104H a
T o ta l lm p e-mea b le A rea - O 8 30H a
0015 66244 67602 0025 66000 67600
0200 64500 67500
225 225
1200
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Hydraulics Where surface water sewers are proposed for adoption we require hydraulic calculations from a digital modelling software package See Sewers For Adoption 6th edition page 28 figure 213
Key Points
Design storm requirements bull No surcharge within the system in a 1 in 2
year Rank 1 storm event bull There is no flooding from the system
in a 1 in 30 year Rank 1 storm (against a surcharged outfall)
bull Please note the only pipe length expected to surcharge in the design storm is pipe downstream of the flow control manhole
Checking the simulation data and criteria bull Contributing impermeable areas (hard
standing areas) bull M5-M60 and Ratio Rndash Check Table of
hydraulics bull MADD Factor ndash No higher than 2
bull The cover and invert levels pipe lengths pipe diameter pipe gradients and contributing areas are consistent across all drawings
bull Online controls (flow control manholes ndash design head and pass forward flow)
bull Pond storage details are correct bull No private drainage lengths included
within network details
Impermeable areas Each impermeable area should represent a unique colour for the drainage area a
key should also be shown detailing the PN number and impermeable area in hectares
Page 6 Developer Services Wastewater S104 Support Guide
Developer Services Wastewater S104 Support Guide
1CL 15555 0 IL 155100
YES 30 1000 YES 40 1000 YES 50 1000
30 r YES 60 1000 30yr YES 70 1000
30 r YES 80 1000 30yr YES 90 1000 30 r YES 100 1000
I bullunited -1 ~ Utilities amp1ing life ow smoothy
Hydraulics continued
Page 7
Key Points
Standards to be checked within the results of the simulations
bull The results should show that the pipe velocities achieve a self-cleansing velocity
bull That high velocities are avoided (in excess of 4ms) - risk of scouring and erosion to benching and river banks
Additional check bull The water levels within the adoptable
manholes listed isnrsquot greater than any private drainage cover levels (for example where houses are lower than the relative level of the road)
1m Surcharge bull A 1m surcharge is to be applied to the soffit
of the receiving sewer with the 30yr storm simulated showing no flooding
Flood Routing bull A flood routing plan is required to support
your application showing that the layout and landscaping of the site aims to route water away from any vulnerable property National Planning Policy Framework usually explains that no flooding of properties should occur as a result of a one in 100 year storm event (including an appropriate allowance for climate change)
Velocity (ms) Result
159
256
250
263
229
tiQ s middot-s (U c 0 ltraquomiddot m tJmiddot E co bull m
10m Tanker Hardstanding
SEE U ILiTI DRA11NGAS SUPPUED BY O ER FOF leMCT ROIITES Of DUCTS
TMiKJER HARDSTANOING
12m Com10oundl lleneth
bull
bull
OS ANDING
J Cl Cl s 0 c E 0 u E
00
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Pumping Station Submission All Pump Station designs must be in line with Sewers for Adoption 7th edition and United Utilities Pumping Station Addendum Justification should always be provided with any submission which proposes a pumping station showing why a gravity soluction is not achievable Please ensure the below information is sent with Pumping Station applications
Typical example of a pumping station compound
bull All key areas show dimensions
bull Bollards for tanker safety
bull Full technical details expected on Pumping Station Design package
bull Non Rising Spindle Penstock chamber located within compound
Key Points
A full pumping station submission should include these documents drip feeding
documents is not acceptable
Document Provided Compound General Layout Drawing
Pumping Station General Arrangement Pumps
Hazardous Area Plan
Rising Main specification
Independent Rising Main Long Section Showing Air Valves and Washout Chambers where applicable (Air Valve to be suitable for Ww rising main)
Jointing Method ndash Fusion Welded confirmed
Surge Analysis (Rising Main Over 500m)
Floatation Check Calculations (Please note Ground Water is to be assumed from ground level) Flotation should be considered as an EQU limit state in accordance with BS EN 1997-1 Section 10 using partial load factors from table NAA12(A) of the UK National Annex to BS EN 1990
Storage Calculations and confirmation of storage location
Pump Calculations
Full Technical specification document
Penstock Isolation Chamber 120 Schematic showing non rising spindle
Tanker Swept Path Analysis drawing
Page 8 Developer Services Wastewater S104 Support Guide
Developer Services Wastewater S104 Support Guide
Sta~ion Typ e 3
iii Weill depth 42rn
iiil1 Well diameter 24m ivj Palisad1e fencing 18m
v) AH emeirgency stm rage
0011tained bulllt1-lrthin well
110mm HPPE SDR 17
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Pumping Station continued
Key Points
General comments Pumping Station location requires careful
consideration ideally away from SUDS features or watercourses Wet wells must be a minimum
distance from any habitable building as per SFA 7th table D1 page 62 with the clearance shown
on the drainage plan A note adjacent to the station should be
provided showing 1) PS Type 2) Well depth 3) Well diameter 4) Fencing type and height 5) Confirmation of Emergency Storage location
6) All electrical equipment should be sited above the 200 year storm level
Rising Main details Rising main specification must be shown on the drainage plan inlcluding
material diameter SDR rating Rising Main Bends Slow Long radius bends should be used avoiding sharp bends If thrust
blocks are required we require supporting calculations
Apparatus on Rising Mains Washout Air Valves (low points high points) must be shown on the drainage drawing and on the long section
Break Chamber The rising main should be kept to the minimum possible distance and
must terminate into a break chamber followed by a minimum 5m length of gravity sewer and a
connection at the soffit level of the existing sewer
Tanker Swept Path Analysis drawing showing an 8 wheel tanker can sufficiently and safely
turn then achieve a reverse manoeuvre into the compound and safely drive out
Rising Main details Rising Main Bends Apparatus on Rising Mains Break Chamber
Page 9
GRID REFERENCE 342587 E 439878 N
l===TI~
GR ID REFERENCE 342587 E 439878 N
C HUR C H V IEW
CHU R C H VIEW
-----------
CHURCHi VIIEW
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Land Registry Compliant drawings Land Registry Compliant drawings are required to enable United Utilities to aquire legal easements over new or existing sewers Drawing 1 shows on site easement examples Drawing 2 shows off site easement examples
Page 10 Developer Services Wastewater S104 Support Guide
Key Points
Scaled at 11250 or near as possible to fit on A3 sheet
Site boundary edged in green (must match
S104 Drainage Plan)
Exisitng road names or landmarks
North point
Easements clearly dimensioned either side from the centre line of the sewer
Drawing 1 ndash On site easements
Drawing 2 ndash Off site easements
J
__ ---
Legend
land ~o be transierred 0 United Ut itities
-~ bullmiddotmiddot bull middot _
L - middot middot middot hi
middot~ qe ~- us v~
I bullunited ~Utilities
~ 6 ow smoothy degtnghte
Land Transfer drawing Land Transfer drawings are required for Pumping Stations this enables United Utilities to transfer land ownership and obtain access rights
Key Points
Example of land trasnfer plan scaled at 1500 the drawing also includes an extract at
a greater scale to cover the drawing requirememts
Compound boundary edged in red
Existing road names landmarks
Any access rights to the station coloured brown (not shown on main example as the station is located off an
adoptable highway)
North point
Page 11 Developer Services Wastewater S104 Support Guide
Dear Mr Adoption
RE One permanent 300mm diameter surface water discharge connection (S57) into existing ordinary watercourse restricted to 321Js rate at UU Road Warrington
Thank you for you r application for Ordinary Watercour se Land Drainage Consent received by Any Other Counci(
I confirm t hat your proposals for the pe rman en t headwall are acce pt able to the Any Other Counci l shown on drawing number S104 Drainage Plan Rev 4
II
Samples arnd In Situ Testirng
Depth Type Results
030 ES
060 ES
0 90 ES
Depth Level (m) (m)
050
0 65
1()()
Stratum Description
MADE GROUND Brown sandy clayey set (Topsoil) with occasional roots and vey rare sub-rounded lo rounded lfrneston e pebbl es_
MADE GROUND Sofi brown sifiy sandy clay with rare sub-rounded to rounded to limestone and cllert pebb lemiddots_ 0 a nic odour
Light brownyellow clayey fine to medium SANO (Organ ic odou r)
End cf pit at 100 m
--
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Additional information
Ground conditions
TreesPlanting
Consents
Page 12 Developer Services Wastewater S104 Support Guide
Key Points
It is essential that thorough site investigation is undertaken as early as possible to avoid any
potential issues with new sewers
A full detailed SI report including trial pit borehole logs must be provided with a
Section 104 submission
Should you encounter challenging ground conditions (for example peat running sand or a fluctuating water table) you should provide
detailed information to justify your design proposals
Trial pit boreholes should be taken to a depth beneath the proposed invert level of any new
sewers to be laid
Should any planting be proposed adjacent to sewers these must conform to figure 23
page 33 SFA 6th
Sewers should be positioned to avoid TPO areas
bull Should your surface water sewers outfall to a watercourse please see Technical Guidance
Document Section 32
bull Formal Consent detailing acceptance of headwall and pass forward flow is required
Technical Guidance
Developer Services Wastewater S104 Support Guide
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Adoptions Process Flow
Initial Design Submitted
Progression to Technical Acceptance
Inspection Fees Paid
Legal Agreements Signed
Inspections as site progresses
Remedial list issued following 100 completion
of build and when occupancy above 50
Provisional Certificate Issued (12months
maintenance)
FinalVesting Certificate Issued
and bond fee released
Page 13
United Utilities Website httpwwwunitedutilitiescomdefaultaspx
Information and advice
Sewer Adoptions httpwwwunitedutilitiescomsewer-adoptions-buildaspx
United Utiliities Standard Details httpwwwunitedutilitiescomdocumentsdeveloper-services-construction-detailspdf
Site Sewer Construction Guide httpwwwunitedutilitiescomdocuments6805-contractors-guidepdf
Pre Development Enquiries httpwwwunitedutilitiescomplanning-wastewater-guidanceaspx
Developer Services Wastewater S104 Support Guide
0818SD7664
INDICATES tl001c600 CEAA OPEN ING MANHOLE COiER AND _ FRAME OVER 75llll6DD CLEAR OPENING N COJER SIAB ACCESSIS UNITED UTILITIES STANDARD DET L
INDICATES 600x600 CLEAR OPENING MANHOLE COVER AND FRAME OVER 750x600 CLEAR OPENING IN COVER SLAB ACCESS AS UNITED UTILITIES STANDARD DETAIL
--
I bullunited -1 ~ Utilities amp1ing life ow smoothy
Manhole 120 Schematic General All manholes should be constructed in accordance with United Utilities Developer Services Construction details Here are good examples
Key Points
When using 600 times 600 covers a 750 times 600 opening
in the cover slab must be used this can avoid any mistakes where ladders
are required
Rocker pipes shown or a general comment stating
rockers will be used in line with United Utiliities standard
detail variable features STND19010
Clay channel fittings used for pipes less than 375dia
Benching widths dimensioned
Manhole S1 MH Diameter 1500mm
Cover Level 107000
Invert Level 105000
MH Type 1
Depth to Soffit 1775
Depth to cut out NA
Cover Size 600 times 600mm
Cover Depth 150mm
Cover Spec D400
Ladder or Double Steps Double Steps
Safety Chain NA
Safety Rails NA
Invert Access Step NA
Hole Size in Cover Slab 600 times 750mm
Page 5 Developer Services Wastewater S104 Support Guide
1000 1 0000 1001 2 0000 2000 3 0000 2001 4 0000
2002 5 0000
1003 6 0000 1004 7 0000
MS-60 (mm) 18500 MADD Factor 2
Flow Control Manhole S7 - DS PN 1005 Unit Ref U U-0124-1000-2500-1000
Design Head 25
Sump Yes
Unit Diameter 124
Flow Control Invert 114515
65 74
20 22
25
7
12
1000 1001
2000
I J 1 middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot1
r middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot J
r I 1-middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot 1 Lmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot I r bullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullmiddotbullbulll L bullmiddot i
34m 25m
17m
P i pe N o
1 000
1 00 1
2 0 00
2 0 011
2 0 02
1 0 02
1 0 0 3
1 0 04
OK OK OK OK OK OK OK
1167 1167
1400
I mpe rme a b le Area (H a)
001 4H
0 10 6 H a
0 173H a
0 0 6 1 Ha
0 0 90H a
0063 H a
0 21 9 H a
0 104H a
T o ta l lm p e-mea b le A rea - O 8 30H a
0015 66244 67602 0025 66000 67600
0200 64500 67500
225 225
1200
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Hydraulics Where surface water sewers are proposed for adoption we require hydraulic calculations from a digital modelling software package See Sewers For Adoption 6th edition page 28 figure 213
Key Points
Design storm requirements bull No surcharge within the system in a 1 in 2
year Rank 1 storm event bull There is no flooding from the system
in a 1 in 30 year Rank 1 storm (against a surcharged outfall)
bull Please note the only pipe length expected to surcharge in the design storm is pipe downstream of the flow control manhole
Checking the simulation data and criteria bull Contributing impermeable areas (hard
standing areas) bull M5-M60 and Ratio Rndash Check Table of
hydraulics bull MADD Factor ndash No higher than 2
bull The cover and invert levels pipe lengths pipe diameter pipe gradients and contributing areas are consistent across all drawings
bull Online controls (flow control manholes ndash design head and pass forward flow)
bull Pond storage details are correct bull No private drainage lengths included
within network details
Impermeable areas Each impermeable area should represent a unique colour for the drainage area a
key should also be shown detailing the PN number and impermeable area in hectares
Page 6 Developer Services Wastewater S104 Support Guide
Developer Services Wastewater S104 Support Guide
1CL 15555 0 IL 155100
YES 30 1000 YES 40 1000 YES 50 1000
30 r YES 60 1000 30yr YES 70 1000
30 r YES 80 1000 30yr YES 90 1000 30 r YES 100 1000
I bullunited -1 ~ Utilities amp1ing life ow smoothy
Hydraulics continued
Page 7
Key Points
Standards to be checked within the results of the simulations
bull The results should show that the pipe velocities achieve a self-cleansing velocity
bull That high velocities are avoided (in excess of 4ms) - risk of scouring and erosion to benching and river banks
Additional check bull The water levels within the adoptable
manholes listed isnrsquot greater than any private drainage cover levels (for example where houses are lower than the relative level of the road)
1m Surcharge bull A 1m surcharge is to be applied to the soffit
of the receiving sewer with the 30yr storm simulated showing no flooding
Flood Routing bull A flood routing plan is required to support
your application showing that the layout and landscaping of the site aims to route water away from any vulnerable property National Planning Policy Framework usually explains that no flooding of properties should occur as a result of a one in 100 year storm event (including an appropriate allowance for climate change)
Velocity (ms) Result
159
256
250
263
229
tiQ s middot-s (U c 0 ltraquomiddot m tJmiddot E co bull m
10m Tanker Hardstanding
SEE U ILiTI DRA11NGAS SUPPUED BY O ER FOF leMCT ROIITES Of DUCTS
TMiKJER HARDSTANOING
12m Com10oundl lleneth
bull
bull
OS ANDING
J Cl Cl s 0 c E 0 u E
00
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Pumping Station Submission All Pump Station designs must be in line with Sewers for Adoption 7th edition and United Utilities Pumping Station Addendum Justification should always be provided with any submission which proposes a pumping station showing why a gravity soluction is not achievable Please ensure the below information is sent with Pumping Station applications
Typical example of a pumping station compound
bull All key areas show dimensions
bull Bollards for tanker safety
bull Full technical details expected on Pumping Station Design package
bull Non Rising Spindle Penstock chamber located within compound
Key Points
A full pumping station submission should include these documents drip feeding
documents is not acceptable
Document Provided Compound General Layout Drawing
Pumping Station General Arrangement Pumps
Hazardous Area Plan
Rising Main specification
Independent Rising Main Long Section Showing Air Valves and Washout Chambers where applicable (Air Valve to be suitable for Ww rising main)
Jointing Method ndash Fusion Welded confirmed
Surge Analysis (Rising Main Over 500m)
Floatation Check Calculations (Please note Ground Water is to be assumed from ground level) Flotation should be considered as an EQU limit state in accordance with BS EN 1997-1 Section 10 using partial load factors from table NAA12(A) of the UK National Annex to BS EN 1990
Storage Calculations and confirmation of storage location
Pump Calculations
Full Technical specification document
Penstock Isolation Chamber 120 Schematic showing non rising spindle
Tanker Swept Path Analysis drawing
Page 8 Developer Services Wastewater S104 Support Guide
Developer Services Wastewater S104 Support Guide
Sta~ion Typ e 3
iii Weill depth 42rn
iiil1 Well diameter 24m ivj Palisad1e fencing 18m
v) AH emeirgency stm rage
0011tained bulllt1-lrthin well
110mm HPPE SDR 17
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Pumping Station continued
Key Points
General comments Pumping Station location requires careful
consideration ideally away from SUDS features or watercourses Wet wells must be a minimum
distance from any habitable building as per SFA 7th table D1 page 62 with the clearance shown
on the drainage plan A note adjacent to the station should be
provided showing 1) PS Type 2) Well depth 3) Well diameter 4) Fencing type and height 5) Confirmation of Emergency Storage location
6) All electrical equipment should be sited above the 200 year storm level
Rising Main details Rising main specification must be shown on the drainage plan inlcluding
material diameter SDR rating Rising Main Bends Slow Long radius bends should be used avoiding sharp bends If thrust
blocks are required we require supporting calculations
Apparatus on Rising Mains Washout Air Valves (low points high points) must be shown on the drainage drawing and on the long section
Break Chamber The rising main should be kept to the minimum possible distance and
must terminate into a break chamber followed by a minimum 5m length of gravity sewer and a
connection at the soffit level of the existing sewer
Tanker Swept Path Analysis drawing showing an 8 wheel tanker can sufficiently and safely
turn then achieve a reverse manoeuvre into the compound and safely drive out
Rising Main details Rising Main Bends Apparatus on Rising Mains Break Chamber
Page 9
GRID REFERENCE 342587 E 439878 N
l===TI~
GR ID REFERENCE 342587 E 439878 N
C HUR C H V IEW
CHU R C H VIEW
-----------
CHURCHi VIIEW
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Land Registry Compliant drawings Land Registry Compliant drawings are required to enable United Utilities to aquire legal easements over new or existing sewers Drawing 1 shows on site easement examples Drawing 2 shows off site easement examples
Page 10 Developer Services Wastewater S104 Support Guide
Key Points
Scaled at 11250 or near as possible to fit on A3 sheet
Site boundary edged in green (must match
S104 Drainage Plan)
Exisitng road names or landmarks
North point
Easements clearly dimensioned either side from the centre line of the sewer
Drawing 1 ndash On site easements
Drawing 2 ndash Off site easements
J
__ ---
Legend
land ~o be transierred 0 United Ut itities
-~ bullmiddotmiddot bull middot _
L - middot middot middot hi
middot~ qe ~- us v~
I bullunited ~Utilities
~ 6 ow smoothy degtnghte
Land Transfer drawing Land Transfer drawings are required for Pumping Stations this enables United Utilities to transfer land ownership and obtain access rights
Key Points
Example of land trasnfer plan scaled at 1500 the drawing also includes an extract at
a greater scale to cover the drawing requirememts
Compound boundary edged in red
Existing road names landmarks
Any access rights to the station coloured brown (not shown on main example as the station is located off an
adoptable highway)
North point
Page 11 Developer Services Wastewater S104 Support Guide
Dear Mr Adoption
RE One permanent 300mm diameter surface water discharge connection (S57) into existing ordinary watercourse restricted to 321Js rate at UU Road Warrington
Thank you for you r application for Ordinary Watercour se Land Drainage Consent received by Any Other Counci(
I confirm t hat your proposals for the pe rman en t headwall are acce pt able to the Any Other Counci l shown on drawing number S104 Drainage Plan Rev 4
II
Samples arnd In Situ Testirng
Depth Type Results
030 ES
060 ES
0 90 ES
Depth Level (m) (m)
050
0 65
1()()
Stratum Description
MADE GROUND Brown sandy clayey set (Topsoil) with occasional roots and vey rare sub-rounded lo rounded lfrneston e pebbl es_
MADE GROUND Sofi brown sifiy sandy clay with rare sub-rounded to rounded to limestone and cllert pebb lemiddots_ 0 a nic odour
Light brownyellow clayey fine to medium SANO (Organ ic odou r)
End cf pit at 100 m
--
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Additional information
Ground conditions
TreesPlanting
Consents
Page 12 Developer Services Wastewater S104 Support Guide
Key Points
It is essential that thorough site investigation is undertaken as early as possible to avoid any
potential issues with new sewers
A full detailed SI report including trial pit borehole logs must be provided with a
Section 104 submission
Should you encounter challenging ground conditions (for example peat running sand or a fluctuating water table) you should provide
detailed information to justify your design proposals
Trial pit boreholes should be taken to a depth beneath the proposed invert level of any new
sewers to be laid
Should any planting be proposed adjacent to sewers these must conform to figure 23
page 33 SFA 6th
Sewers should be positioned to avoid TPO areas
bull Should your surface water sewers outfall to a watercourse please see Technical Guidance
Document Section 32
bull Formal Consent detailing acceptance of headwall and pass forward flow is required
Technical Guidance
Developer Services Wastewater S104 Support Guide
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Adoptions Process Flow
Initial Design Submitted
Progression to Technical Acceptance
Inspection Fees Paid
Legal Agreements Signed
Inspections as site progresses
Remedial list issued following 100 completion
of build and when occupancy above 50
Provisional Certificate Issued (12months
maintenance)
FinalVesting Certificate Issued
and bond fee released
Page 13
United Utilities Website httpwwwunitedutilitiescomdefaultaspx
Information and advice
Sewer Adoptions httpwwwunitedutilitiescomsewer-adoptions-buildaspx
United Utiliities Standard Details httpwwwunitedutilitiescomdocumentsdeveloper-services-construction-detailspdf
Site Sewer Construction Guide httpwwwunitedutilitiescomdocuments6805-contractors-guidepdf
Pre Development Enquiries httpwwwunitedutilitiescomplanning-wastewater-guidanceaspx
Developer Services Wastewater S104 Support Guide
0818SD7664
1000 1 0000 1001 2 0000 2000 3 0000 2001 4 0000
2002 5 0000
1003 6 0000 1004 7 0000
MS-60 (mm) 18500 MADD Factor 2
Flow Control Manhole S7 - DS PN 1005 Unit Ref U U-0124-1000-2500-1000
Design Head 25
Sump Yes
Unit Diameter 124
Flow Control Invert 114515
65 74
20 22
25
7
12
1000 1001
2000
I J 1 middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot1
r middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot J
r I 1-middotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot 1 Lmiddotmiddotmiddotmiddotmiddotmiddotmiddotmiddot I r bullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullmiddotbullbulll L bullmiddot i
34m 25m
17m
P i pe N o
1 000
1 00 1
2 0 00
2 0 011
2 0 02
1 0 02
1 0 0 3
1 0 04
OK OK OK OK OK OK OK
1167 1167
1400
I mpe rme a b le Area (H a)
001 4H
0 10 6 H a
0 173H a
0 0 6 1 Ha
0 0 90H a
0063 H a
0 21 9 H a
0 104H a
T o ta l lm p e-mea b le A rea - O 8 30H a
0015 66244 67602 0025 66000 67600
0200 64500 67500
225 225
1200
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Hydraulics Where surface water sewers are proposed for adoption we require hydraulic calculations from a digital modelling software package See Sewers For Adoption 6th edition page 28 figure 213
Key Points
Design storm requirements bull No surcharge within the system in a 1 in 2
year Rank 1 storm event bull There is no flooding from the system
in a 1 in 30 year Rank 1 storm (against a surcharged outfall)
bull Please note the only pipe length expected to surcharge in the design storm is pipe downstream of the flow control manhole
Checking the simulation data and criteria bull Contributing impermeable areas (hard
standing areas) bull M5-M60 and Ratio Rndash Check Table of
hydraulics bull MADD Factor ndash No higher than 2
bull The cover and invert levels pipe lengths pipe diameter pipe gradients and contributing areas are consistent across all drawings
bull Online controls (flow control manholes ndash design head and pass forward flow)
bull Pond storage details are correct bull No private drainage lengths included
within network details
Impermeable areas Each impermeable area should represent a unique colour for the drainage area a
key should also be shown detailing the PN number and impermeable area in hectares
Page 6 Developer Services Wastewater S104 Support Guide
Developer Services Wastewater S104 Support Guide
1CL 15555 0 IL 155100
YES 30 1000 YES 40 1000 YES 50 1000
30 r YES 60 1000 30yr YES 70 1000
30 r YES 80 1000 30yr YES 90 1000 30 r YES 100 1000
I bullunited -1 ~ Utilities amp1ing life ow smoothy
Hydraulics continued
Page 7
Key Points
Standards to be checked within the results of the simulations
bull The results should show that the pipe velocities achieve a self-cleansing velocity
bull That high velocities are avoided (in excess of 4ms) - risk of scouring and erosion to benching and river banks
Additional check bull The water levels within the adoptable
manholes listed isnrsquot greater than any private drainage cover levels (for example where houses are lower than the relative level of the road)
1m Surcharge bull A 1m surcharge is to be applied to the soffit
of the receiving sewer with the 30yr storm simulated showing no flooding
Flood Routing bull A flood routing plan is required to support
your application showing that the layout and landscaping of the site aims to route water away from any vulnerable property National Planning Policy Framework usually explains that no flooding of properties should occur as a result of a one in 100 year storm event (including an appropriate allowance for climate change)
Velocity (ms) Result
159
256
250
263
229
tiQ s middot-s (U c 0 ltraquomiddot m tJmiddot E co bull m
10m Tanker Hardstanding
SEE U ILiTI DRA11NGAS SUPPUED BY O ER FOF leMCT ROIITES Of DUCTS
TMiKJER HARDSTANOING
12m Com10oundl lleneth
bull
bull
OS ANDING
J Cl Cl s 0 c E 0 u E
00
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Pumping Station Submission All Pump Station designs must be in line with Sewers for Adoption 7th edition and United Utilities Pumping Station Addendum Justification should always be provided with any submission which proposes a pumping station showing why a gravity soluction is not achievable Please ensure the below information is sent with Pumping Station applications
Typical example of a pumping station compound
bull All key areas show dimensions
bull Bollards for tanker safety
bull Full technical details expected on Pumping Station Design package
bull Non Rising Spindle Penstock chamber located within compound
Key Points
A full pumping station submission should include these documents drip feeding
documents is not acceptable
Document Provided Compound General Layout Drawing
Pumping Station General Arrangement Pumps
Hazardous Area Plan
Rising Main specification
Independent Rising Main Long Section Showing Air Valves and Washout Chambers where applicable (Air Valve to be suitable for Ww rising main)
Jointing Method ndash Fusion Welded confirmed
Surge Analysis (Rising Main Over 500m)
Floatation Check Calculations (Please note Ground Water is to be assumed from ground level) Flotation should be considered as an EQU limit state in accordance with BS EN 1997-1 Section 10 using partial load factors from table NAA12(A) of the UK National Annex to BS EN 1990
Storage Calculations and confirmation of storage location
Pump Calculations
Full Technical specification document
Penstock Isolation Chamber 120 Schematic showing non rising spindle
Tanker Swept Path Analysis drawing
Page 8 Developer Services Wastewater S104 Support Guide
Developer Services Wastewater S104 Support Guide
Sta~ion Typ e 3
iii Weill depth 42rn
iiil1 Well diameter 24m ivj Palisad1e fencing 18m
v) AH emeirgency stm rage
0011tained bulllt1-lrthin well
110mm HPPE SDR 17
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Pumping Station continued
Key Points
General comments Pumping Station location requires careful
consideration ideally away from SUDS features or watercourses Wet wells must be a minimum
distance from any habitable building as per SFA 7th table D1 page 62 with the clearance shown
on the drainage plan A note adjacent to the station should be
provided showing 1) PS Type 2) Well depth 3) Well diameter 4) Fencing type and height 5) Confirmation of Emergency Storage location
6) All electrical equipment should be sited above the 200 year storm level
Rising Main details Rising main specification must be shown on the drainage plan inlcluding
material diameter SDR rating Rising Main Bends Slow Long radius bends should be used avoiding sharp bends If thrust
blocks are required we require supporting calculations
Apparatus on Rising Mains Washout Air Valves (low points high points) must be shown on the drainage drawing and on the long section
Break Chamber The rising main should be kept to the minimum possible distance and
must terminate into a break chamber followed by a minimum 5m length of gravity sewer and a
connection at the soffit level of the existing sewer
Tanker Swept Path Analysis drawing showing an 8 wheel tanker can sufficiently and safely
turn then achieve a reverse manoeuvre into the compound and safely drive out
Rising Main details Rising Main Bends Apparatus on Rising Mains Break Chamber
Page 9
GRID REFERENCE 342587 E 439878 N
l===TI~
GR ID REFERENCE 342587 E 439878 N
C HUR C H V IEW
CHU R C H VIEW
-----------
CHURCHi VIIEW
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Land Registry Compliant drawings Land Registry Compliant drawings are required to enable United Utilities to aquire legal easements over new or existing sewers Drawing 1 shows on site easement examples Drawing 2 shows off site easement examples
Page 10 Developer Services Wastewater S104 Support Guide
Key Points
Scaled at 11250 or near as possible to fit on A3 sheet
Site boundary edged in green (must match
S104 Drainage Plan)
Exisitng road names or landmarks
North point
Easements clearly dimensioned either side from the centre line of the sewer
Drawing 1 ndash On site easements
Drawing 2 ndash Off site easements
J
__ ---
Legend
land ~o be transierred 0 United Ut itities
-~ bullmiddotmiddot bull middot _
L - middot middot middot hi
middot~ qe ~- us v~
I bullunited ~Utilities
~ 6 ow smoothy degtnghte
Land Transfer drawing Land Transfer drawings are required for Pumping Stations this enables United Utilities to transfer land ownership and obtain access rights
Key Points
Example of land trasnfer plan scaled at 1500 the drawing also includes an extract at
a greater scale to cover the drawing requirememts
Compound boundary edged in red
Existing road names landmarks
Any access rights to the station coloured brown (not shown on main example as the station is located off an
adoptable highway)
North point
Page 11 Developer Services Wastewater S104 Support Guide
Dear Mr Adoption
RE One permanent 300mm diameter surface water discharge connection (S57) into existing ordinary watercourse restricted to 321Js rate at UU Road Warrington
Thank you for you r application for Ordinary Watercour se Land Drainage Consent received by Any Other Counci(
I confirm t hat your proposals for the pe rman en t headwall are acce pt able to the Any Other Counci l shown on drawing number S104 Drainage Plan Rev 4
II
Samples arnd In Situ Testirng
Depth Type Results
030 ES
060 ES
0 90 ES
Depth Level (m) (m)
050
0 65
1()()
Stratum Description
MADE GROUND Brown sandy clayey set (Topsoil) with occasional roots and vey rare sub-rounded lo rounded lfrneston e pebbl es_
MADE GROUND Sofi brown sifiy sandy clay with rare sub-rounded to rounded to limestone and cllert pebb lemiddots_ 0 a nic odour
Light brownyellow clayey fine to medium SANO (Organ ic odou r)
End cf pit at 100 m
--
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Additional information
Ground conditions
TreesPlanting
Consents
Page 12 Developer Services Wastewater S104 Support Guide
Key Points
It is essential that thorough site investigation is undertaken as early as possible to avoid any
potential issues with new sewers
A full detailed SI report including trial pit borehole logs must be provided with a
Section 104 submission
Should you encounter challenging ground conditions (for example peat running sand or a fluctuating water table) you should provide
detailed information to justify your design proposals
Trial pit boreholes should be taken to a depth beneath the proposed invert level of any new
sewers to be laid
Should any planting be proposed adjacent to sewers these must conform to figure 23
page 33 SFA 6th
Sewers should be positioned to avoid TPO areas
bull Should your surface water sewers outfall to a watercourse please see Technical Guidance
Document Section 32
bull Formal Consent detailing acceptance of headwall and pass forward flow is required
Technical Guidance
Developer Services Wastewater S104 Support Guide
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Adoptions Process Flow
Initial Design Submitted
Progression to Technical Acceptance
Inspection Fees Paid
Legal Agreements Signed
Inspections as site progresses
Remedial list issued following 100 completion
of build and when occupancy above 50
Provisional Certificate Issued (12months
maintenance)
FinalVesting Certificate Issued
and bond fee released
Page 13
United Utilities Website httpwwwunitedutilitiescomdefaultaspx
Information and advice
Sewer Adoptions httpwwwunitedutilitiescomsewer-adoptions-buildaspx
United Utiliities Standard Details httpwwwunitedutilitiescomdocumentsdeveloper-services-construction-detailspdf
Site Sewer Construction Guide httpwwwunitedutilitiescomdocuments6805-contractors-guidepdf
Pre Development Enquiries httpwwwunitedutilitiescomplanning-wastewater-guidanceaspx
Developer Services Wastewater S104 Support Guide
0818SD7664
Developer Services Wastewater S104 Support Guide
1CL 15555 0 IL 155100
YES 30 1000 YES 40 1000 YES 50 1000
30 r YES 60 1000 30yr YES 70 1000
30 r YES 80 1000 30yr YES 90 1000 30 r YES 100 1000
I bullunited -1 ~ Utilities amp1ing life ow smoothy
Hydraulics continued
Page 7
Key Points
Standards to be checked within the results of the simulations
bull The results should show that the pipe velocities achieve a self-cleansing velocity
bull That high velocities are avoided (in excess of 4ms) - risk of scouring and erosion to benching and river banks
Additional check bull The water levels within the adoptable
manholes listed isnrsquot greater than any private drainage cover levels (for example where houses are lower than the relative level of the road)
1m Surcharge bull A 1m surcharge is to be applied to the soffit
of the receiving sewer with the 30yr storm simulated showing no flooding
Flood Routing bull A flood routing plan is required to support
your application showing that the layout and landscaping of the site aims to route water away from any vulnerable property National Planning Policy Framework usually explains that no flooding of properties should occur as a result of a one in 100 year storm event (including an appropriate allowance for climate change)
Velocity (ms) Result
159
256
250
263
229
tiQ s middot-s (U c 0 ltraquomiddot m tJmiddot E co bull m
10m Tanker Hardstanding
SEE U ILiTI DRA11NGAS SUPPUED BY O ER FOF leMCT ROIITES Of DUCTS
TMiKJER HARDSTANOING
12m Com10oundl lleneth
bull
bull
OS ANDING
J Cl Cl s 0 c E 0 u E
00
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Pumping Station Submission All Pump Station designs must be in line with Sewers for Adoption 7th edition and United Utilities Pumping Station Addendum Justification should always be provided with any submission which proposes a pumping station showing why a gravity soluction is not achievable Please ensure the below information is sent with Pumping Station applications
Typical example of a pumping station compound
bull All key areas show dimensions
bull Bollards for tanker safety
bull Full technical details expected on Pumping Station Design package
bull Non Rising Spindle Penstock chamber located within compound
Key Points
A full pumping station submission should include these documents drip feeding
documents is not acceptable
Document Provided Compound General Layout Drawing
Pumping Station General Arrangement Pumps
Hazardous Area Plan
Rising Main specification
Independent Rising Main Long Section Showing Air Valves and Washout Chambers where applicable (Air Valve to be suitable for Ww rising main)
Jointing Method ndash Fusion Welded confirmed
Surge Analysis (Rising Main Over 500m)
Floatation Check Calculations (Please note Ground Water is to be assumed from ground level) Flotation should be considered as an EQU limit state in accordance with BS EN 1997-1 Section 10 using partial load factors from table NAA12(A) of the UK National Annex to BS EN 1990
Storage Calculations and confirmation of storage location
Pump Calculations
Full Technical specification document
Penstock Isolation Chamber 120 Schematic showing non rising spindle
Tanker Swept Path Analysis drawing
Page 8 Developer Services Wastewater S104 Support Guide
Developer Services Wastewater S104 Support Guide
Sta~ion Typ e 3
iii Weill depth 42rn
iiil1 Well diameter 24m ivj Palisad1e fencing 18m
v) AH emeirgency stm rage
0011tained bulllt1-lrthin well
110mm HPPE SDR 17
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Pumping Station continued
Key Points
General comments Pumping Station location requires careful
consideration ideally away from SUDS features or watercourses Wet wells must be a minimum
distance from any habitable building as per SFA 7th table D1 page 62 with the clearance shown
on the drainage plan A note adjacent to the station should be
provided showing 1) PS Type 2) Well depth 3) Well diameter 4) Fencing type and height 5) Confirmation of Emergency Storage location
6) All electrical equipment should be sited above the 200 year storm level
Rising Main details Rising main specification must be shown on the drainage plan inlcluding
material diameter SDR rating Rising Main Bends Slow Long radius bends should be used avoiding sharp bends If thrust
blocks are required we require supporting calculations
Apparatus on Rising Mains Washout Air Valves (low points high points) must be shown on the drainage drawing and on the long section
Break Chamber The rising main should be kept to the minimum possible distance and
must terminate into a break chamber followed by a minimum 5m length of gravity sewer and a
connection at the soffit level of the existing sewer
Tanker Swept Path Analysis drawing showing an 8 wheel tanker can sufficiently and safely
turn then achieve a reverse manoeuvre into the compound and safely drive out
Rising Main details Rising Main Bends Apparatus on Rising Mains Break Chamber
Page 9
GRID REFERENCE 342587 E 439878 N
l===TI~
GR ID REFERENCE 342587 E 439878 N
C HUR C H V IEW
CHU R C H VIEW
-----------
CHURCHi VIIEW
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Land Registry Compliant drawings Land Registry Compliant drawings are required to enable United Utilities to aquire legal easements over new or existing sewers Drawing 1 shows on site easement examples Drawing 2 shows off site easement examples
Page 10 Developer Services Wastewater S104 Support Guide
Key Points
Scaled at 11250 or near as possible to fit on A3 sheet
Site boundary edged in green (must match
S104 Drainage Plan)
Exisitng road names or landmarks
North point
Easements clearly dimensioned either side from the centre line of the sewer
Drawing 1 ndash On site easements
Drawing 2 ndash Off site easements
J
__ ---
Legend
land ~o be transierred 0 United Ut itities
-~ bullmiddotmiddot bull middot _
L - middot middot middot hi
middot~ qe ~- us v~
I bullunited ~Utilities
~ 6 ow smoothy degtnghte
Land Transfer drawing Land Transfer drawings are required for Pumping Stations this enables United Utilities to transfer land ownership and obtain access rights
Key Points
Example of land trasnfer plan scaled at 1500 the drawing also includes an extract at
a greater scale to cover the drawing requirememts
Compound boundary edged in red
Existing road names landmarks
Any access rights to the station coloured brown (not shown on main example as the station is located off an
adoptable highway)
North point
Page 11 Developer Services Wastewater S104 Support Guide
Dear Mr Adoption
RE One permanent 300mm diameter surface water discharge connection (S57) into existing ordinary watercourse restricted to 321Js rate at UU Road Warrington
Thank you for you r application for Ordinary Watercour se Land Drainage Consent received by Any Other Counci(
I confirm t hat your proposals for the pe rman en t headwall are acce pt able to the Any Other Counci l shown on drawing number S104 Drainage Plan Rev 4
II
Samples arnd In Situ Testirng
Depth Type Results
030 ES
060 ES
0 90 ES
Depth Level (m) (m)
050
0 65
1()()
Stratum Description
MADE GROUND Brown sandy clayey set (Topsoil) with occasional roots and vey rare sub-rounded lo rounded lfrneston e pebbl es_
MADE GROUND Sofi brown sifiy sandy clay with rare sub-rounded to rounded to limestone and cllert pebb lemiddots_ 0 a nic odour
Light brownyellow clayey fine to medium SANO (Organ ic odou r)
End cf pit at 100 m
--
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Additional information
Ground conditions
TreesPlanting
Consents
Page 12 Developer Services Wastewater S104 Support Guide
Key Points
It is essential that thorough site investigation is undertaken as early as possible to avoid any
potential issues with new sewers
A full detailed SI report including trial pit borehole logs must be provided with a
Section 104 submission
Should you encounter challenging ground conditions (for example peat running sand or a fluctuating water table) you should provide
detailed information to justify your design proposals
Trial pit boreholes should be taken to a depth beneath the proposed invert level of any new
sewers to be laid
Should any planting be proposed adjacent to sewers these must conform to figure 23
page 33 SFA 6th
Sewers should be positioned to avoid TPO areas
bull Should your surface water sewers outfall to a watercourse please see Technical Guidance
Document Section 32
bull Formal Consent detailing acceptance of headwall and pass forward flow is required
Technical Guidance
Developer Services Wastewater S104 Support Guide
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Adoptions Process Flow
Initial Design Submitted
Progression to Technical Acceptance
Inspection Fees Paid
Legal Agreements Signed
Inspections as site progresses
Remedial list issued following 100 completion
of build and when occupancy above 50
Provisional Certificate Issued (12months
maintenance)
FinalVesting Certificate Issued
and bond fee released
Page 13
United Utilities Website httpwwwunitedutilitiescomdefaultaspx
Information and advice
Sewer Adoptions httpwwwunitedutilitiescomsewer-adoptions-buildaspx
United Utiliities Standard Details httpwwwunitedutilitiescomdocumentsdeveloper-services-construction-detailspdf
Site Sewer Construction Guide httpwwwunitedutilitiescomdocuments6805-contractors-guidepdf
Pre Development Enquiries httpwwwunitedutilitiescomplanning-wastewater-guidanceaspx
Developer Services Wastewater S104 Support Guide
0818SD7664
tiQ s middot-s (U c 0 ltraquomiddot m tJmiddot E co bull m
10m Tanker Hardstanding
SEE U ILiTI DRA11NGAS SUPPUED BY O ER FOF leMCT ROIITES Of DUCTS
TMiKJER HARDSTANOING
12m Com10oundl lleneth
bull
bull
OS ANDING
J Cl Cl s 0 c E 0 u E
00
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Pumping Station Submission All Pump Station designs must be in line with Sewers for Adoption 7th edition and United Utilities Pumping Station Addendum Justification should always be provided with any submission which proposes a pumping station showing why a gravity soluction is not achievable Please ensure the below information is sent with Pumping Station applications
Typical example of a pumping station compound
bull All key areas show dimensions
bull Bollards for tanker safety
bull Full technical details expected on Pumping Station Design package
bull Non Rising Spindle Penstock chamber located within compound
Key Points
A full pumping station submission should include these documents drip feeding
documents is not acceptable
Document Provided Compound General Layout Drawing
Pumping Station General Arrangement Pumps
Hazardous Area Plan
Rising Main specification
Independent Rising Main Long Section Showing Air Valves and Washout Chambers where applicable (Air Valve to be suitable for Ww rising main)
Jointing Method ndash Fusion Welded confirmed
Surge Analysis (Rising Main Over 500m)
Floatation Check Calculations (Please note Ground Water is to be assumed from ground level) Flotation should be considered as an EQU limit state in accordance with BS EN 1997-1 Section 10 using partial load factors from table NAA12(A) of the UK National Annex to BS EN 1990
Storage Calculations and confirmation of storage location
Pump Calculations
Full Technical specification document
Penstock Isolation Chamber 120 Schematic showing non rising spindle
Tanker Swept Path Analysis drawing
Page 8 Developer Services Wastewater S104 Support Guide
Developer Services Wastewater S104 Support Guide
Sta~ion Typ e 3
iii Weill depth 42rn
iiil1 Well diameter 24m ivj Palisad1e fencing 18m
v) AH emeirgency stm rage
0011tained bulllt1-lrthin well
110mm HPPE SDR 17
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Pumping Station continued
Key Points
General comments Pumping Station location requires careful
consideration ideally away from SUDS features or watercourses Wet wells must be a minimum
distance from any habitable building as per SFA 7th table D1 page 62 with the clearance shown
on the drainage plan A note adjacent to the station should be
provided showing 1) PS Type 2) Well depth 3) Well diameter 4) Fencing type and height 5) Confirmation of Emergency Storage location
6) All electrical equipment should be sited above the 200 year storm level
Rising Main details Rising main specification must be shown on the drainage plan inlcluding
material diameter SDR rating Rising Main Bends Slow Long radius bends should be used avoiding sharp bends If thrust
blocks are required we require supporting calculations
Apparatus on Rising Mains Washout Air Valves (low points high points) must be shown on the drainage drawing and on the long section
Break Chamber The rising main should be kept to the minimum possible distance and
must terminate into a break chamber followed by a minimum 5m length of gravity sewer and a
connection at the soffit level of the existing sewer
Tanker Swept Path Analysis drawing showing an 8 wheel tanker can sufficiently and safely
turn then achieve a reverse manoeuvre into the compound and safely drive out
Rising Main details Rising Main Bends Apparatus on Rising Mains Break Chamber
Page 9
GRID REFERENCE 342587 E 439878 N
l===TI~
GR ID REFERENCE 342587 E 439878 N
C HUR C H V IEW
CHU R C H VIEW
-----------
CHURCHi VIIEW
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Land Registry Compliant drawings Land Registry Compliant drawings are required to enable United Utilities to aquire legal easements over new or existing sewers Drawing 1 shows on site easement examples Drawing 2 shows off site easement examples
Page 10 Developer Services Wastewater S104 Support Guide
Key Points
Scaled at 11250 or near as possible to fit on A3 sheet
Site boundary edged in green (must match
S104 Drainage Plan)
Exisitng road names or landmarks
North point
Easements clearly dimensioned either side from the centre line of the sewer
Drawing 1 ndash On site easements
Drawing 2 ndash Off site easements
J
__ ---
Legend
land ~o be transierred 0 United Ut itities
-~ bullmiddotmiddot bull middot _
L - middot middot middot hi
middot~ qe ~- us v~
I bullunited ~Utilities
~ 6 ow smoothy degtnghte
Land Transfer drawing Land Transfer drawings are required for Pumping Stations this enables United Utilities to transfer land ownership and obtain access rights
Key Points
Example of land trasnfer plan scaled at 1500 the drawing also includes an extract at
a greater scale to cover the drawing requirememts
Compound boundary edged in red
Existing road names landmarks
Any access rights to the station coloured brown (not shown on main example as the station is located off an
adoptable highway)
North point
Page 11 Developer Services Wastewater S104 Support Guide
Dear Mr Adoption
RE One permanent 300mm diameter surface water discharge connection (S57) into existing ordinary watercourse restricted to 321Js rate at UU Road Warrington
Thank you for you r application for Ordinary Watercour se Land Drainage Consent received by Any Other Counci(
I confirm t hat your proposals for the pe rman en t headwall are acce pt able to the Any Other Counci l shown on drawing number S104 Drainage Plan Rev 4
II
Samples arnd In Situ Testirng
Depth Type Results
030 ES
060 ES
0 90 ES
Depth Level (m) (m)
050
0 65
1()()
Stratum Description
MADE GROUND Brown sandy clayey set (Topsoil) with occasional roots and vey rare sub-rounded lo rounded lfrneston e pebbl es_
MADE GROUND Sofi brown sifiy sandy clay with rare sub-rounded to rounded to limestone and cllert pebb lemiddots_ 0 a nic odour
Light brownyellow clayey fine to medium SANO (Organ ic odou r)
End cf pit at 100 m
--
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Additional information
Ground conditions
TreesPlanting
Consents
Page 12 Developer Services Wastewater S104 Support Guide
Key Points
It is essential that thorough site investigation is undertaken as early as possible to avoid any
potential issues with new sewers
A full detailed SI report including trial pit borehole logs must be provided with a
Section 104 submission
Should you encounter challenging ground conditions (for example peat running sand or a fluctuating water table) you should provide
detailed information to justify your design proposals
Trial pit boreholes should be taken to a depth beneath the proposed invert level of any new
sewers to be laid
Should any planting be proposed adjacent to sewers these must conform to figure 23
page 33 SFA 6th
Sewers should be positioned to avoid TPO areas
bull Should your surface water sewers outfall to a watercourse please see Technical Guidance
Document Section 32
bull Formal Consent detailing acceptance of headwall and pass forward flow is required
Technical Guidance
Developer Services Wastewater S104 Support Guide
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Adoptions Process Flow
Initial Design Submitted
Progression to Technical Acceptance
Inspection Fees Paid
Legal Agreements Signed
Inspections as site progresses
Remedial list issued following 100 completion
of build and when occupancy above 50
Provisional Certificate Issued (12months
maintenance)
FinalVesting Certificate Issued
and bond fee released
Page 13
United Utilities Website httpwwwunitedutilitiescomdefaultaspx
Information and advice
Sewer Adoptions httpwwwunitedutilitiescomsewer-adoptions-buildaspx
United Utiliities Standard Details httpwwwunitedutilitiescomdocumentsdeveloper-services-construction-detailspdf
Site Sewer Construction Guide httpwwwunitedutilitiescomdocuments6805-contractors-guidepdf
Pre Development Enquiries httpwwwunitedutilitiescomplanning-wastewater-guidanceaspx
Developer Services Wastewater S104 Support Guide
0818SD7664
Developer Services Wastewater S104 Support Guide
Sta~ion Typ e 3
iii Weill depth 42rn
iiil1 Well diameter 24m ivj Palisad1e fencing 18m
v) AH emeirgency stm rage
0011tained bulllt1-lrthin well
110mm HPPE SDR 17
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Pumping Station continued
Key Points
General comments Pumping Station location requires careful
consideration ideally away from SUDS features or watercourses Wet wells must be a minimum
distance from any habitable building as per SFA 7th table D1 page 62 with the clearance shown
on the drainage plan A note adjacent to the station should be
provided showing 1) PS Type 2) Well depth 3) Well diameter 4) Fencing type and height 5) Confirmation of Emergency Storage location
6) All electrical equipment should be sited above the 200 year storm level
Rising Main details Rising main specification must be shown on the drainage plan inlcluding
material diameter SDR rating Rising Main Bends Slow Long radius bends should be used avoiding sharp bends If thrust
blocks are required we require supporting calculations
Apparatus on Rising Mains Washout Air Valves (low points high points) must be shown on the drainage drawing and on the long section
Break Chamber The rising main should be kept to the minimum possible distance and
must terminate into a break chamber followed by a minimum 5m length of gravity sewer and a
connection at the soffit level of the existing sewer
Tanker Swept Path Analysis drawing showing an 8 wheel tanker can sufficiently and safely
turn then achieve a reverse manoeuvre into the compound and safely drive out
Rising Main details Rising Main Bends Apparatus on Rising Mains Break Chamber
Page 9
GRID REFERENCE 342587 E 439878 N
l===TI~
GR ID REFERENCE 342587 E 439878 N
C HUR C H V IEW
CHU R C H VIEW
-----------
CHURCHi VIIEW
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Land Registry Compliant drawings Land Registry Compliant drawings are required to enable United Utilities to aquire legal easements over new or existing sewers Drawing 1 shows on site easement examples Drawing 2 shows off site easement examples
Page 10 Developer Services Wastewater S104 Support Guide
Key Points
Scaled at 11250 or near as possible to fit on A3 sheet
Site boundary edged in green (must match
S104 Drainage Plan)
Exisitng road names or landmarks
North point
Easements clearly dimensioned either side from the centre line of the sewer
Drawing 1 ndash On site easements
Drawing 2 ndash Off site easements
J
__ ---
Legend
land ~o be transierred 0 United Ut itities
-~ bullmiddotmiddot bull middot _
L - middot middot middot hi
middot~ qe ~- us v~
I bullunited ~Utilities
~ 6 ow smoothy degtnghte
Land Transfer drawing Land Transfer drawings are required for Pumping Stations this enables United Utilities to transfer land ownership and obtain access rights
Key Points
Example of land trasnfer plan scaled at 1500 the drawing also includes an extract at
a greater scale to cover the drawing requirememts
Compound boundary edged in red
Existing road names landmarks
Any access rights to the station coloured brown (not shown on main example as the station is located off an
adoptable highway)
North point
Page 11 Developer Services Wastewater S104 Support Guide
Dear Mr Adoption
RE One permanent 300mm diameter surface water discharge connection (S57) into existing ordinary watercourse restricted to 321Js rate at UU Road Warrington
Thank you for you r application for Ordinary Watercour se Land Drainage Consent received by Any Other Counci(
I confirm t hat your proposals for the pe rman en t headwall are acce pt able to the Any Other Counci l shown on drawing number S104 Drainage Plan Rev 4
II
Samples arnd In Situ Testirng
Depth Type Results
030 ES
060 ES
0 90 ES
Depth Level (m) (m)
050
0 65
1()()
Stratum Description
MADE GROUND Brown sandy clayey set (Topsoil) with occasional roots and vey rare sub-rounded lo rounded lfrneston e pebbl es_
MADE GROUND Sofi brown sifiy sandy clay with rare sub-rounded to rounded to limestone and cllert pebb lemiddots_ 0 a nic odour
Light brownyellow clayey fine to medium SANO (Organ ic odou r)
End cf pit at 100 m
--
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Additional information
Ground conditions
TreesPlanting
Consents
Page 12 Developer Services Wastewater S104 Support Guide
Key Points
It is essential that thorough site investigation is undertaken as early as possible to avoid any
potential issues with new sewers
A full detailed SI report including trial pit borehole logs must be provided with a
Section 104 submission
Should you encounter challenging ground conditions (for example peat running sand or a fluctuating water table) you should provide
detailed information to justify your design proposals
Trial pit boreholes should be taken to a depth beneath the proposed invert level of any new
sewers to be laid
Should any planting be proposed adjacent to sewers these must conform to figure 23
page 33 SFA 6th
Sewers should be positioned to avoid TPO areas
bull Should your surface water sewers outfall to a watercourse please see Technical Guidance
Document Section 32
bull Formal Consent detailing acceptance of headwall and pass forward flow is required
Technical Guidance
Developer Services Wastewater S104 Support Guide
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Adoptions Process Flow
Initial Design Submitted
Progression to Technical Acceptance
Inspection Fees Paid
Legal Agreements Signed
Inspections as site progresses
Remedial list issued following 100 completion
of build and when occupancy above 50
Provisional Certificate Issued (12months
maintenance)
FinalVesting Certificate Issued
and bond fee released
Page 13
United Utilities Website httpwwwunitedutilitiescomdefaultaspx
Information and advice
Sewer Adoptions httpwwwunitedutilitiescomsewer-adoptions-buildaspx
United Utiliities Standard Details httpwwwunitedutilitiescomdocumentsdeveloper-services-construction-detailspdf
Site Sewer Construction Guide httpwwwunitedutilitiescomdocuments6805-contractors-guidepdf
Pre Development Enquiries httpwwwunitedutilitiescomplanning-wastewater-guidanceaspx
Developer Services Wastewater S104 Support Guide
0818SD7664
GRID REFERENCE 342587 E 439878 N
l===TI~
GR ID REFERENCE 342587 E 439878 N
C HUR C H V IEW
CHU R C H VIEW
-----------
CHURCHi VIIEW
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Land Registry Compliant drawings Land Registry Compliant drawings are required to enable United Utilities to aquire legal easements over new or existing sewers Drawing 1 shows on site easement examples Drawing 2 shows off site easement examples
Page 10 Developer Services Wastewater S104 Support Guide
Key Points
Scaled at 11250 or near as possible to fit on A3 sheet
Site boundary edged in green (must match
S104 Drainage Plan)
Exisitng road names or landmarks
North point
Easements clearly dimensioned either side from the centre line of the sewer
Drawing 1 ndash On site easements
Drawing 2 ndash Off site easements
J
__ ---
Legend
land ~o be transierred 0 United Ut itities
-~ bullmiddotmiddot bull middot _
L - middot middot middot hi
middot~ qe ~- us v~
I bullunited ~Utilities
~ 6 ow smoothy degtnghte
Land Transfer drawing Land Transfer drawings are required for Pumping Stations this enables United Utilities to transfer land ownership and obtain access rights
Key Points
Example of land trasnfer plan scaled at 1500 the drawing also includes an extract at
a greater scale to cover the drawing requirememts
Compound boundary edged in red
Existing road names landmarks
Any access rights to the station coloured brown (not shown on main example as the station is located off an
adoptable highway)
North point
Page 11 Developer Services Wastewater S104 Support Guide
Dear Mr Adoption
RE One permanent 300mm diameter surface water discharge connection (S57) into existing ordinary watercourse restricted to 321Js rate at UU Road Warrington
Thank you for you r application for Ordinary Watercour se Land Drainage Consent received by Any Other Counci(
I confirm t hat your proposals for the pe rman en t headwall are acce pt able to the Any Other Counci l shown on drawing number S104 Drainage Plan Rev 4
II
Samples arnd In Situ Testirng
Depth Type Results
030 ES
060 ES
0 90 ES
Depth Level (m) (m)
050
0 65
1()()
Stratum Description
MADE GROUND Brown sandy clayey set (Topsoil) with occasional roots and vey rare sub-rounded lo rounded lfrneston e pebbl es_
MADE GROUND Sofi brown sifiy sandy clay with rare sub-rounded to rounded to limestone and cllert pebb lemiddots_ 0 a nic odour
Light brownyellow clayey fine to medium SANO (Organ ic odou r)
End cf pit at 100 m
--
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Additional information
Ground conditions
TreesPlanting
Consents
Page 12 Developer Services Wastewater S104 Support Guide
Key Points
It is essential that thorough site investigation is undertaken as early as possible to avoid any
potential issues with new sewers
A full detailed SI report including trial pit borehole logs must be provided with a
Section 104 submission
Should you encounter challenging ground conditions (for example peat running sand or a fluctuating water table) you should provide
detailed information to justify your design proposals
Trial pit boreholes should be taken to a depth beneath the proposed invert level of any new
sewers to be laid
Should any planting be proposed adjacent to sewers these must conform to figure 23
page 33 SFA 6th
Sewers should be positioned to avoid TPO areas
bull Should your surface water sewers outfall to a watercourse please see Technical Guidance
Document Section 32
bull Formal Consent detailing acceptance of headwall and pass forward flow is required
Technical Guidance
Developer Services Wastewater S104 Support Guide
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Adoptions Process Flow
Initial Design Submitted
Progression to Technical Acceptance
Inspection Fees Paid
Legal Agreements Signed
Inspections as site progresses
Remedial list issued following 100 completion
of build and when occupancy above 50
Provisional Certificate Issued (12months
maintenance)
FinalVesting Certificate Issued
and bond fee released
Page 13
United Utilities Website httpwwwunitedutilitiescomdefaultaspx
Information and advice
Sewer Adoptions httpwwwunitedutilitiescomsewer-adoptions-buildaspx
United Utiliities Standard Details httpwwwunitedutilitiescomdocumentsdeveloper-services-construction-detailspdf
Site Sewer Construction Guide httpwwwunitedutilitiescomdocuments6805-contractors-guidepdf
Pre Development Enquiries httpwwwunitedutilitiescomplanning-wastewater-guidanceaspx
Developer Services Wastewater S104 Support Guide
0818SD7664
J
__ ---
Legend
land ~o be transierred 0 United Ut itities
-~ bullmiddotmiddot bull middot _
L - middot middot middot hi
middot~ qe ~- us v~
I bullunited ~Utilities
~ 6 ow smoothy degtnghte
Land Transfer drawing Land Transfer drawings are required for Pumping Stations this enables United Utilities to transfer land ownership and obtain access rights
Key Points
Example of land trasnfer plan scaled at 1500 the drawing also includes an extract at
a greater scale to cover the drawing requirememts
Compound boundary edged in red
Existing road names landmarks
Any access rights to the station coloured brown (not shown on main example as the station is located off an
adoptable highway)
North point
Page 11 Developer Services Wastewater S104 Support Guide
Dear Mr Adoption
RE One permanent 300mm diameter surface water discharge connection (S57) into existing ordinary watercourse restricted to 321Js rate at UU Road Warrington
Thank you for you r application for Ordinary Watercour se Land Drainage Consent received by Any Other Counci(
I confirm t hat your proposals for the pe rman en t headwall are acce pt able to the Any Other Counci l shown on drawing number S104 Drainage Plan Rev 4
II
Samples arnd In Situ Testirng
Depth Type Results
030 ES
060 ES
0 90 ES
Depth Level (m) (m)
050
0 65
1()()
Stratum Description
MADE GROUND Brown sandy clayey set (Topsoil) with occasional roots and vey rare sub-rounded lo rounded lfrneston e pebbl es_
MADE GROUND Sofi brown sifiy sandy clay with rare sub-rounded to rounded to limestone and cllert pebb lemiddots_ 0 a nic odour
Light brownyellow clayey fine to medium SANO (Organ ic odou r)
End cf pit at 100 m
--
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Additional information
Ground conditions
TreesPlanting
Consents
Page 12 Developer Services Wastewater S104 Support Guide
Key Points
It is essential that thorough site investigation is undertaken as early as possible to avoid any
potential issues with new sewers
A full detailed SI report including trial pit borehole logs must be provided with a
Section 104 submission
Should you encounter challenging ground conditions (for example peat running sand or a fluctuating water table) you should provide
detailed information to justify your design proposals
Trial pit boreholes should be taken to a depth beneath the proposed invert level of any new
sewers to be laid
Should any planting be proposed adjacent to sewers these must conform to figure 23
page 33 SFA 6th
Sewers should be positioned to avoid TPO areas
bull Should your surface water sewers outfall to a watercourse please see Technical Guidance
Document Section 32
bull Formal Consent detailing acceptance of headwall and pass forward flow is required
Technical Guidance
Developer Services Wastewater S104 Support Guide
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Adoptions Process Flow
Initial Design Submitted
Progression to Technical Acceptance
Inspection Fees Paid
Legal Agreements Signed
Inspections as site progresses
Remedial list issued following 100 completion
of build and when occupancy above 50
Provisional Certificate Issued (12months
maintenance)
FinalVesting Certificate Issued
and bond fee released
Page 13
United Utilities Website httpwwwunitedutilitiescomdefaultaspx
Information and advice
Sewer Adoptions httpwwwunitedutilitiescomsewer-adoptions-buildaspx
United Utiliities Standard Details httpwwwunitedutilitiescomdocumentsdeveloper-services-construction-detailspdf
Site Sewer Construction Guide httpwwwunitedutilitiescomdocuments6805-contractors-guidepdf
Pre Development Enquiries httpwwwunitedutilitiescomplanning-wastewater-guidanceaspx
Developer Services Wastewater S104 Support Guide
0818SD7664
Dear Mr Adoption
RE One permanent 300mm diameter surface water discharge connection (S57) into existing ordinary watercourse restricted to 321Js rate at UU Road Warrington
Thank you for you r application for Ordinary Watercour se Land Drainage Consent received by Any Other Counci(
I confirm t hat your proposals for the pe rman en t headwall are acce pt able to the Any Other Counci l shown on drawing number S104 Drainage Plan Rev 4
II
Samples arnd In Situ Testirng
Depth Type Results
030 ES
060 ES
0 90 ES
Depth Level (m) (m)
050
0 65
1()()
Stratum Description
MADE GROUND Brown sandy clayey set (Topsoil) with occasional roots and vey rare sub-rounded lo rounded lfrneston e pebbl es_
MADE GROUND Sofi brown sifiy sandy clay with rare sub-rounded to rounded to limestone and cllert pebb lemiddots_ 0 a nic odour
Light brownyellow clayey fine to medium SANO (Organ ic odou r)
End cf pit at 100 m
--
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Additional information
Ground conditions
TreesPlanting
Consents
Page 12 Developer Services Wastewater S104 Support Guide
Key Points
It is essential that thorough site investigation is undertaken as early as possible to avoid any
potential issues with new sewers
A full detailed SI report including trial pit borehole logs must be provided with a
Section 104 submission
Should you encounter challenging ground conditions (for example peat running sand or a fluctuating water table) you should provide
detailed information to justify your design proposals
Trial pit boreholes should be taken to a depth beneath the proposed invert level of any new
sewers to be laid
Should any planting be proposed adjacent to sewers these must conform to figure 23
page 33 SFA 6th
Sewers should be positioned to avoid TPO areas
bull Should your surface water sewers outfall to a watercourse please see Technical Guidance
Document Section 32
bull Formal Consent detailing acceptance of headwall and pass forward flow is required
Technical Guidance
Developer Services Wastewater S104 Support Guide
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Adoptions Process Flow
Initial Design Submitted
Progression to Technical Acceptance
Inspection Fees Paid
Legal Agreements Signed
Inspections as site progresses
Remedial list issued following 100 completion
of build and when occupancy above 50
Provisional Certificate Issued (12months
maintenance)
FinalVesting Certificate Issued
and bond fee released
Page 13
United Utilities Website httpwwwunitedutilitiescomdefaultaspx
Information and advice
Sewer Adoptions httpwwwunitedutilitiescomsewer-adoptions-buildaspx
United Utiliities Standard Details httpwwwunitedutilitiescomdocumentsdeveloper-services-construction-detailspdf
Site Sewer Construction Guide httpwwwunitedutilitiescomdocuments6805-contractors-guidepdf
Pre Development Enquiries httpwwwunitedutilitiescomplanning-wastewater-guidanceaspx
Developer Services Wastewater S104 Support Guide
0818SD7664
Developer Services Wastewater S104 Support Guide
I bullunited -1 ~ Utilities amp1ing life ow smoothi
Adoptions Process Flow
Initial Design Submitted
Progression to Technical Acceptance
Inspection Fees Paid
Legal Agreements Signed
Inspections as site progresses
Remedial list issued following 100 completion
of build and when occupancy above 50
Provisional Certificate Issued (12months
maintenance)
FinalVesting Certificate Issued
and bond fee released
Page 13
United Utilities Website httpwwwunitedutilitiescomdefaultaspx
Information and advice
Sewer Adoptions httpwwwunitedutilitiescomsewer-adoptions-buildaspx
United Utiliities Standard Details httpwwwunitedutilitiescomdocumentsdeveloper-services-construction-detailspdf
Site Sewer Construction Guide httpwwwunitedutilitiescomdocuments6805-contractors-guidepdf
Pre Development Enquiries httpwwwunitedutilitiescomplanning-wastewater-guidanceaspx
Developer Services Wastewater S104 Support Guide
0818SD7664
United Utilities Website httpwwwunitedutilitiescomdefaultaspx
Information and advice
Sewer Adoptions httpwwwunitedutilitiescomsewer-adoptions-buildaspx
United Utiliities Standard Details httpwwwunitedutilitiescomdocumentsdeveloper-services-construction-detailspdf
Site Sewer Construction Guide httpwwwunitedutilitiescomdocuments6805-contractors-guidepdf
Pre Development Enquiries httpwwwunitedutilitiescomplanning-wastewater-guidanceaspx
Developer Services Wastewater S104 Support Guide
0818SD7664