DESIGN GUIDELINES Division 22 PLUMBING

40
DESIGN GUIDELINES Division 22 PLUMBING Release 3.0 April 2017 Released by: Cleveland Clinic Facilities and Construction 9500 Euclid Ave. Cleveland OH 44195 All information within this Document is considered CONFIDENTIAL and PROPRIETARY. By receipt and use of this Document, the recipient agrees not to divulge any of the information herein and attached hereto to persons other than those within the recipients’ organization that have specific need to know for the purposes of reviewing and referencing this information. Recipient also agrees not to use this information in any manner detrimental to the interests of Cleveland Clinic.

Transcript of DESIGN GUIDELINES Division 22 PLUMBING

DESIGN GUIDELINES

Division 22 – PLUMBING

Release 3.0 April 2017 Released by: Cleveland Clinic Facilities and Construction 9500 Euclid Ave. Cleveland OH 44195

All information within this Document is considered CONFIDENTIAL and PROPRIETARY. By receipt and use of this Document, the recipient agrees not to divulge any of the information herein and attached hereto to persons other than those within the recipients’ organization that have specific need to know for the purposes of reviewing and referencing this information. Recipient also agrees not to use this information in any manner detrimental to the interests of Cleveland Clinic.

Cleveland Clinic

Design Guidelines Copyright © 2017

By Cleveland Clinic These Specifications, or parts thereof, may not be reproduced in any form without the permission of Cleveland Clinic.

Cleveland Clinic

Cleveland Clinic Design Guidelines: Division 22 - Plumbing

The following pages contain guidelines for the design and construction of new and

renovated facilities at all domestic Cleveland Clinic locations. They shall be used by A/E

firms in the preparation of drawings and specifications for construction of facilities.

The general purpose of each Design Guideline is to provide minimal criteria for

construction materials and equipment at Cleveland Clinic facilities regarding Codes and

FM Global compliance, warranty, approved products, execution, and uniformity.

The Guidelines are not Contract Specifications, but are used to prepare more detailed,

project-specific specifications. The Guidelines are intended to be used to address system

design aspects of equipment that Cleveland Clinic desires to standardize among facilities,

and identify prohibited materials and construction practices.

The use of these Guidelines is mandatory for all design or maintenance projects. Deviations

are discouraged. If project conditions arise which require a deviation, it shall be thoroughly

documented by the user and submitted to Cleveland Clinic for review and approval using

the Design Standard Deviation Request Form.

DESIGN STANDARDS WAIVER REQUEST FORM

From:

Department or Firm:

Phone:

E-mail:

Date:

Standard Name:

Specification, Guideline, or Detail Number:

Section, Page, Paragraph Number(s) or Detail Number:

BRIEF DESCRIPTION OF WAIVER:

DESCRIBE REASON FOR WAIVER:

HAS THIS REQUEST BEEN DISCUSSED WITH CC STAFF? IF SO PLEASE PROVIDE

NAME OF PERSON:

APPROVED APPROVED WITH COMMENTS NOT APPROVED

COMMENTS:

SIGN: DATE:

Bottom Portion for Design Standards Review Committee

Design Guidelines: Division 22 – Plumbing

1. Plumbing Drawing and Equipment Naming Requirements

2. Domestic Water Distribution

3. Sanitary Waste

4. Storm Drainage

5. Domestic Water Heating Equipment

6. Plumbing Fixtures

7. Plumbing Insulation and Labeling

8. Gas and Vacuum Systems

9. Facility Natural Gas Piping

10. Laboratory Water and Waste Systems

** End of List **

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 1. Plumbing Drawing and Equipment Naming Requirements

April 2017 1 - 1

1.1 Plumbing Drawing Requirements

A. The following drawing naming structure shall be followed on all projects. Naming structure shall

supersede all architectural naming structures. If conflict exists with architectural naming, discuss

with project team. The goal of a structured naming convention is that all drawings, regardless of

project type and project team, shall be consistent and searchable for Cleveland Clinic staff.

B. Follow naming structure most applicable to project size. Not all drawing numbers will be required

for every job.

Large Project

Drawing Series Drawing Content Sample Drawing Name

P-0XX General Notes & Legend Plumbing General Notes and Symbol Legend

PD-XXX Demolition Plumbing xx Floor Demolition Plan

P-1XX Sanitary and Storm Drainage Plumbing xx Floor Drainage Plan

P-2XX Domestic Water Plumbing xx Floor Domestic Water Plan

P-3XX Medical Gas xx Floor Medical Gas Plan

P-4XX Sections Sections

P-5XX Details Plumbing Details

P-6XX Schedules Plumbing Schedules

P-7XX Flow Diagrams & Isometrics Plumbing Isometric Diagrams

P-8XX Miscellaneous (Enlarged Plans, etc.) Enlarged xx Floor Plan

M-9XX* Temperature Control Diagrams and

Sequences -

*Include Plumbing Temperature Control Diagrams on Mechanical Drawing Series M9-XXX

Small Project

To avoid creating unnecessary sheets (e.g., separate plumbing sheets for single sink

replacement), combining mechanical and plumbing scope on a single sheet is acceptable,

provided mechanical and plumbing scope each have a unique plan on that sheet.

When combined plumbing sheets are utilized, at a minimum the following sheets shall be

utilized: P-0XX, P-1XX, and P-6XX

On combined sheets, all disciplines shall be named in title block, making it easily

searchable (e.g., Partial 1st Floor Plumbing and Medical Gas Plan).

Drawing Series Drawing Content Sample Drawing Name

P-0XX General Notes, Legend, & Specifications Plumbing General Notes, Symbol

Legend and Specifications

PD-XXX

Demolition

If project is small enough, demolition

scope can be included on P-1XX

Plumbing xx Floor Demolition Plan

P-1XX Plumbing & Medical Gas Plumbing xx Floor Plumbing Plans

P-5XX Details Plumbing Details

P-6XX Schedules, Diagrams & Isometrics Plumbing Schedules and Diagrams

C. Indicate all applicable codes followed on General Notes Sheet (P-001).

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 1. Plumbing Drawing and Equipment Naming Requirements

April 2017 1 - 2

1.2 Equipment Naming Requirements

A. The following plumbing equipment nomenclature shall be used to identify all plumbing

equipment.

Plumbing Equipment Type Equipment Tag

Area Drain AD

Backflow Preventer BFP

Clinic Sink CS

Domestic Water Heater DWH

Domestic Booster Pump DBP

Emergency Eyewash Fountain EEW

Emergency Shower ES

Emergency Shower/Eyewash ESE

Electric Water Cooler EWC

Floor Drain FD

Floor Sink FS

Frost-Proof Wall Hydrant FPWH

Frost-Proof Ground Hydrant FPGH

Frost-Proof Roof Hydrant FPRH

Grease Interceptor GI

Grease Trap GT

Hose Bibb HB

Lavatory L

Mop Basin MB

Pressure Regulating Valve PRV

Recirculating Hot Water Pump RHWP

Roof Drain RD

Shower SH

Sink S

Sewage Ejector SE

Sump Pump SP

Temperature Mixing Valve TMV

Urinal U

Wall Box WB

Water Closet WC

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 1. Plumbing Drawing and Equipment Naming Requirements

April 2017 1 - 3

Medical Gas Equipment Type Equipment Tag

Area Alarm Panel AAP

Master Alarm Panel MAP

Medical Air Compressor MAC

Medical Vacuum Pump MVP

Zone Valve Box ZVB

B. The following plumbing piping labels shall be used to identify all piping on design drawings.

Plumbing Piping System Piping Label

Compressed Air Piping CA

Acid Vent Piping AV

Acid Waste Piping AW

Carbon Dioxide Piping CO2

Deionized Water Piping DE

Domestic Cold Water Piping CW

Domestic Hot Water Piping HW

Domestic Recirculating Hot Water Piping RHW

Equipment Air Piping EQA

Instrument Air Piping IA

Medical Air Piping MA

Medical Air Intake Piping MAI

Medical Vacuum Piping MV

Medical Vacuum Discharge Piping MVD

Natural Gas Piping NG

Nitrogen Piping N2

Nitrous Oxide Piping N2O

Non-Potable Cold Water Piping NPCW

Non-Potable Hot Water Piping NPHW

Non-Potable Recirculating Hot Water Piping NPRHW

Oxygen Piping O2

Overflow Storm Piping OST

Purified Water Piping PW

Sanitary Sewer SAN

Storm Sewer ST

Tempered Hot Water Piping THW

Vent Piping V

Waste Anesthetic Gas Disposal WAGD

140°F Hot Water Piping 140°F HW

140°F Recirculating Hot Water Piping 140°F RHW

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 2. Domestic Water Distribution

April 2017 2 - 1

1.1 General Domestic Water Distribution Requirements

A. Building domestic water distribution systems shall be metered and isolated from the municipal

water supply in accordance with the municipality’s requirements.

B. The design of building supply and distribution systems shall provide a volume of water at the

required flows, pressures, and temperatures to ensure safe, efficient, and code-compliant

operation during periods of peak demand.

Domestic Water Piping Sizing

System Sizing Criteria (Feet Per Second)

Domestic Cold Water Velocity not to exceed 6 fps

Domestic Hot Water Velocity not to exceed 4 fps

C. Domestic hot water systems shall be designed to reasonably assure an expeditious flow of hot

water at all outlets. Pumped circulating systems are required for all patient care areas. Electric

heat maintenance cable is only acceptable in administration facilities.

1. Size hot water return lines by the heat loss method as outlined in the ASHRAE Systems

and Equipment Data Book, not to exceed 4–5°F heat loss. Developed length of branch

piping from fixture outlet to circulated mains shall not exceed 25 feet with the following

exceptions:

a. Hot water piping serving public lavatory faucets shall be circulated to within 18

inches of the fixture hot water supply stop.

b. Provide a check valve, strainer, and flow control valve at the end of each circuit.

c. A single point-of-use instantaneous electric water heater shall serve no more than

three (3) lavatory faucets. The length of hot water piping from the heater to each

faucet stop shall not exceed 36 inches.

D. Main distribution piping risers shall utilize chases within the building footprint for vertical routing

to multiple floor levels where possible.

E. Provide line shut-off valves at locations required for proper operation, servicing, and

troubleshooting of the domestic water distribution system and connected components. Locations

shall include, but not be limited to, the following:

1. At each fixture and piece of equipment

2. At each branch take-off from mains

3. At the base of each riser

4. At each battery of fixtures, where recommended by equipment manufacturers

5. At strategic locations to allow sectional isolation while limiting disruption of services to

large portions of the system

F. Accessible full size capped valves shall be provided where required for future connections.

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 2. Domestic Water Distribution

April 2017 2 - 2

G. All valves shall be accessible for operation and servicing. Provide access panels for all concealed

valves. Coordinate the location of access panels with the architectural features of the building,

and obtain approval of locations from the Architect.

H. On new projects and major renovations, a water sample shall be collected and tested. Based on

results of sample, provide all required water treatment to satisfy project’s water requirements.

I. Provide frost-proof wall hydrants with integral vacuum breaker on exterior walls a maximum of

150 feet apart, at loading docks, near building entrances, at mechanical yards, and within 50 feet

of exterior grease interceptors. Hydrants should be located at approximately 18 inches above

finished grade. Coordinate the location of all wall hydrants with the architectural features of the

building, and obtain approval of locations from the Architect.

J. Provide frost-proof wall hydrant with backflow preventer on at least one exterior wall of the roof

penthouse and/or a frost-proof roof hydrant to cover entire roof area. Hydrants shall be located

only where necessary. Coordinate all locations with CC Engineer during design.

K. In each mechanical room, provide a hose bib 24 inches above finished floor with integral vacuum

breaker and a minimum of one floor drain. Provide additional hose bibs located within 100 feet

of adjacent hose bib.

L. Provide accessible check valves in the individual cold and hot water fixture supply lines serving

thermostatic mixing valves or assemblies having hose connection outlets that are not equipped

with integral check stops.

M. Trap priming devices that rely upon line pressure differential shall be used for patient toilet rooms.

Electronic trap priming devices shall be used in mechanical rooms and provided with an

accessible/serviceable strainer immediately upstream of the device solenoid valve.

N. Static pressure at plumbing fixtures

1. Minimum design: 40 PSIG

2. Preferred design: 55 PSIG

3. Maximum design: 80 PSIG

O. Pressure Regulating Valves (PRV)

1. Provide redundant pressure regulating valves for main building service and building

pressure zones.

2. Provide additional pressure regulating valves as required for proper operation of individual

equipment.

3. Provide isolation valve, pressure gauge, and strainer upstream of PRV.

4. Provide isolation valve and pressure gauge downstream of PRV.

5. Documentation of PRV testing shall be provided with plumbing equipment start-up reports

and included in project close-out documentation.

P. Domestic Booster Pump Design

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 2. Domestic Water Distribution

April 2017 2 - 3

1. A packaged domestic water booster pump system shall elevate the incoming water pressure

as required to serve fixtures and equipment. Selection of pumping system type shall be

based upon flow and pressure demand, as well as efficiency of operation, life expectancy,

and maintenance requirements of the equipment.

2. Multi-stage booster pumps are the preferred pump type. End suction pumps are acceptable.

All pumps shall be provided with a variable frequency drive.

3. Domestic water for all building types shall be provided using, at a minimum, a duplex

pump.

a. Booster pump systems shall be designed to deliver calculated peak flow at required

pressure with one pump out of service.

4. On projects where emergency power is provided, connect booster pump system to

emergency power system.

Q. Backflow Preventers

1. Backflow preventer test ports shall be accessible. They shall not be located more than 72

inches above the finished floor or permanent platform.

2. Pipe relief from backflow preventer indirectly to drain of sufficient size to evacuate

maximum flow discharge.

3. Provide integral strainers on all principle or primary type backflow preventers.

R. Vacuum Breakers

1. Do not install vacuum breakers above equipment, concealed within walls, or at any location

where water leakage can cause damage. Above ceiling vacuum breakers shall be ASSE

approved 1056 anti-spill.

2. Vacuum breakers (including vacuum breakers that are integral with faucets) shall not be

installed under exhaust hoods or similar locations that may contain toxic fumes or vapors.

3. Vacuum breakers for hose connections in health care or laboratory areas shall be a

minimum of 72 inches above the floor, with the following exceptions:

a. Vacuum breakers integral with faucets or equipment.

b. Vacuum breakers for bedpan washer hoses shall be a minimum of 60 inches above

the floor.

S. Non-potable system shall have the following:

1. Cold and hot water for dedicated equipment services shall be separated from the domestic

water distribution system by backflow prevention.

2. Avoid providing individual backflow preventers for each piece of equipment where

possible.

3. All piping downstream of the backflow preventers shall be identified as non-potable water.

4. Provide signage at all fixtures on non-potable system.

T. Water hammer arrestors shall be provided at quick closing valves (e.g., washing machines, hoses,

specialty equipment, etc.). Arrestors shall be accessible.

U. Valves provided for future connections shall not extend more than 24 inches from an active main.

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 2. Domestic Water Distribution

April 2017 2 - 4

V. Where permanently disconnecting domestic water supplies serving fixtures or equipment, remove

all associated piping back to active main to avoid stagnation.

W. Coordinate utility meters and any allowable deduct meters with purveyor and sub-meters with

Cleveland Clinic.

1.2 Hospital Domestic Water Distribution Requirements

A. Building service pressure reducing valves shall have a bypass with a throttling valve.

B. Hospitals shall be provided with redundant water services to building.

1. Each service shall be provided with backflow preventer.

1.3 Ambulatory Healthcare Facility Domestic Water Distribution Requirements

A. Building service PRVs shall have a bypass with a throttling valve.

B. Building service shall be provided with redundant backflow preventers.

1.4 Outpatient Facility Domestic Water Distribution Requirements

A. Building service PRVs shall have a bypass with a throttling valve.

B. Building service shall be provided with redundant backflow preventers.

1.5 Administration Facility Domestic Water Distribution Requirements

A. Building service PRVs shall have a bypass with a throttling valve.

See the following page for Plumbing Application Schedule.

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 2. Domestic Water Distribution

April 2017 2 - 5

1.6 Plumbing Application Schedule (All Facility Types)

Pipe and Joining Application Schedule

Piped System Pipe Size

Range

Pipe Specified

Type(s)

Joining Specified

Method(s)

Domestic Water Underground

Service 2” and smaller Soft Copper “Without Joints”

Domestic Water Underground

Service 3” and larger Ductile Iron Push Joint

Domestic Water Inside Building 2” and smaller Copper Soldered or Pressed Fitting

System

Domestic Water Inside Building 2 ½” – 4” Copper

Brazed, Pressed Fitting

System, or Grooved

Joining System

Domestic Water Inside Building 5” and larger Stainless Steel (Sch.

10) or Copper Grooved Joining System

Trap Primer Feed Piping Within

Ceilings/Above Floors ½” Copper

Soldered or Pressed Fitting

System

Pipe Valve Application Schedule

Piped System Pipe Size Range Valve Type

Domestic Water (Hot and Cold) 4” and smaller Ball Valve

Domestic Water (Hot and Cold) 5” and larger Double Lug Butterfly Valve

1.7 Manufacturers

A. Refer to CC Equipment Supplier List located on Buildings and Properties Website for

acceptable equipment manufacturers. (http://portals.clevelandclinic.org/ocm)

*****

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 3. Sanitary Waste

April 2017 3 - 1

1.1 Sanitary Waste Requirements

A. Waste and vent systems shall be designed using fixture drain loads that are code compliant for

sizing and provide proper operation during periods of peak demand.

B. Where possible, main waste and vent stacks shall utilize chases or be located adjacent to columns

for vertical routing to multiple floor levels.

C. The use of double wye sanitary fittings is prohibited.

D. Laundry utility boxes shall be provided where connections to laundry equipment are required.

Provide 3-inch lateral branch pipe to the base of the box’s standpipe. Standpipe shall be 24 inches

of 2-inch pipe and a 2 inch trap.

E. Where possible, ice machine drain connections shall discharge into a hub drain with wall box. If

drain connection connects to sink, drain connection shall be above floor level/rim of sink attached.

F. Dialysis waste piping shall be acid resistant (refer to Plumbing Application Schedule, below, for

material type). Acid resistant waste piping shall be used from dialysis waste wall box to closest

sanitary stack with regularly flowing waste.

G. Trap primers shall be provided to floor drains/floor sinks that may be susceptible to trap seal

evaporation.

H. Public restrooms shall be provided with 3 inch or 4 inch floor drains.

I. The building system is anticipated to flow by gravity to the exterior municipal sanitary sewer.

Sanitary drains that cannot be discharged by gravity shall be routed to a sump and be pumped out

to a point in the sanitary system that is capable of flowing by gravity.

J. Elevator Pit Sump Pumps

1. Cast iron body submersible pumps are acceptable for elevator sumps.

2. Pump shall be provided with mechanical float.

3. Provide sump pump sized per elevator code.

4. Only metallic piping allowed within hoistway.

5. Discharge of elevator pit sump pump shall be either located outside (with splash block) or

into an open-end standpipe in a janitor’s closet. Discharge into a standard mop basin is not

acceptable.

K. Sewage Ejectors

1. Cast iron body submersible or shaft-mounted pumps are acceptable for sumps.

2. Provide duplex, lead-lag pumps. Pump’s high water alarms shall have local lights and

audible alarm in addition to being sent to building management system. High water alarm

shall be separate circuit, independent of pump circuit.

3. Locate gate and check valves outside of the pit.

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 3. Sanitary Waste

April 2017 3 - 2

L. Provide cleanouts at the base of each vertical sanitary stack and at intervals not exceeding 75 feet

in horizontal building drain. All interior cleanouts shall be accessible from walls or floors. Provide

wall cleanouts in lieu of floor cleanouts wherever possible. A floor cleanout shall be installed

only where installation of a wall cleanout is not practical. Provide a wall cleanout for each water

closet or battery of water closets. Locate wall cleanouts above the flood level rim of the highest

water closet but no more than 24 inches above the finished floor. For horizontal cleanouts, provide

an access door and blind plug. For vertical cleanouts, provide an access door, wye, and blind plug.

Plumbing Engineer is responsible for coordinating access door locations for incorporation on the

architectural plans.

M. No buried waste line shall be smaller than 3 inches. No buried vent line shall be smaller than the

full size of the sanitary pipe that it is serving. No above ground vent line shall be smaller than

1 ½ inches. No roof vent terminal shall be smaller than 3 inches. Waste piping serving water

closets shall not be smaller than 4 inches.

N. All sanitary vent terminals shall comply with local code and required minimum distances. Avoid

locating drains above sensitive equipment (e.g., MRIs, CTs, radiology imaging equipment) or

areas where water leakage would cause major property loss or contamination. Where this is

unavoidable, provide a stainless steel drain pan with drain and leak detection alarms tied into

building management system. Coordinate water tight flooring (with Architect) for rooms above

sensitive equipment.

O. Do not locate drainage or vent piping within stairways, electrical rooms, or telecommunications

rooms. Where this is unavoidable, provide a stainless steel drain pan with drain and leak detection

alarms tied into the building management system. Coordinate water tight flooring (with Architect)

for rooms above sensitive equipment.

P. Do not locate floor drains within pharmacy drug preparation areas, operating rooms, or areas

where hazardous materials are handled or stored.

See the following page for Plumbing Application Schedule.

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 3. Sanitary Waste

April 2017 3 - 3

1.2 Plumbing Application Schedule (All Facility Types)

Pipe and Joining Application Schedule

Piped System Pipe Size

Range

Pipe Specified

Type(s)

Joining Specified

Method(s)

Sanitary Drainage, Waste and Vent

Piping – Above Ground 1 ½” – 15” No-Hub Cast Iron No-Hub Coupling

Sanitary Drainage, Waste and Vent

Piping -Underground 2” – 15” PVC Solvent Weld

Boiler Room Sanitary Drainage

Waste Piping – Underground 2” – 15”

Service Weight Cast

Iron Push Joint

Kitchen Grease Waste and

Sanitary Drainage, Waste and Vent

Piping - Underground

2” – 15” Service Weight Cast

Iron Push Joint

Kitchen Grease Waste Drainage,

Waste and Vent Piping –

Underground (Acceptable

Alternative)

2” – 8” Stainless Steel

(316L) Push Joint System

Kitchen Grease Waste Drainage,

Waste and Vent Piping - Above

Ground (Acceptable Alternative)

1 ½” – 8” Stainless Steel (304

or 316L) Push Joint System

HVAC Equipment Condensate

Drains & Ice Maker Drains ½” – 1 ½” Copper

Soldered, or Pressed Fitting

System

Dialysis RO Rejection Waste and

Vent Underground 1 ½” – 6”

Chemical Resistant

CPVC Solvent Weld

Dialysis RO Rejection Waste and

Vent Above Ground, NOT in

HVAC Plenums

1 ½” – 6” Chemical Resistant

CPVC Solvent Weld

Dialysis RO Rejection Waste and

Vent Above Ground within HVAC

Plenums

1 ½” – 6” Plenum Rated Acid

Waste PVDF

Manufacturer’s Mechanical

Joint

Waste Water Pumped Discharge

Above Ground 1 ¼” – 6”

Galvanized Steel

(Sch. 40)

Threaded, Flanged, or

Pressed Fitting System

1.3 Manufacturers

A. All cast-iron piping and fittings shall be American made.

B. Refer to CC Equipment Supplier List located on Buildings and Properties Website for acceptable

equipment manufacturers. (http://portals.clevelandclinic.org/ocm)

*****

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 4. Storm Drainage

April 2017 4 - 1

1.1 Facility Storm Drainage Requirements

A. Primary and secondary roof drain systems shall be designed using the applicable rainfall rate in

conjunction with code established areas-to-pipe sizes allowed.

B. Storm water drainage systems shall be provided to convey rainwater from roof and area drains to

the site municipal storm sewer system. Secondary emergency overflow systems shall be installed

to protect parapeted roof structures in the event of primary system blockage.

C. Avoid locating sumps or piping above sensitive equipment (e.g., MRIs, CTs, radiology imaging

equipment) or areas where water leakage would cause major property loss or contamination.

Where this is unavoidable, provide a stainless steel drain pan with drain and leak detection alarms

tied into the building management system. Coordinate water tight flooring (with Architect) for

rooms above sensitive equipment.

D. Do not locate drain sumps or piping within stairways, electrical rooms, or telecommunications

rooms. Where this is unavoidable, provide a stainless steel drain pan with drain and leak detection

alarms tied into the building management system. Coordinate water tight flooring (with Architect)

for rooms above sensitive equipment.

E. No roof drain shall have an outlet connection smaller than 3 inches.

F. Storm drains that cannot be discharged by gravity shall be routed to a sump and be pumped out

to a point in the storm system that is capable of flowing by gravity.

G. Sump Pumps

1. Cast iron body submersible or shaft-mounted pumps are acceptable for sumps.

2. Pump shall be provided with a mechanical float.

3. Provide duplex, lead-lag pumps in sump pits where there is predicted constant water flow.

Pump’s high water alarms shall have local lights and audible alarm in addition to being

sent to building management system. High water alarm shall be on separate circuit,

independent of pump circuit.

4. Locate gate and check valves outside the pit.

H. Provide cleanouts at the base of each vertical downspout and at intervals not exceeding 75 feet in

horizontal building drain. All interior cleanouts shall be accessible from walls or floors. For

horizontal cleanouts, provide an access door and blind plug. For vertical cleanouts, provide an

access door, wye, and blind plug. Plumbing Engineer is responsible for coordinating access door

locations for incorporation on the architectural plans.

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 4. Storm Drainage

April 2017 4 - 2

1.2 Plumbing Application Schedule (All Facility Types)

Pipe and Joining Application Schedule

Piped System Pipe Size

Range Pipe Specified Type(s)

Joining Specified

Method(s)

Storm Drainage Piping, Underground 3” – 15” Service Weight Cast

Iron Push Joint

Storm Drainage Piping, Underground 3” – 15” PVC Solvent Weld

Storm Drainage Piping, Above Ground 3” – 15” No-hub Cast Iron No-Hub Coupling

1.3 Manufacturers

A. All cast-iron piping and fittings shall be American made.

B. Refer to CC Equipment Supplier List located on Buildings and Properties Website for acceptable

equipment manufacturers. (http://portals.clevelandclinic.org/ocm)

*****

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 5. Domestic Water Heating Equipment

April 2017 5 - 1

1.1 Domestic Water Heating Equipment Requirements

A. Where steam boilers are provided or centralized steam is available, utilize semi-instantaneous

type with steam to hot-water or hot-water to hot-water double wall heat exchangers. Natural gas

fired heaters may be provided where natural gas service is readily available and when considered

applicable by the Design Team and approved by Cleveland Clinic. Condensing domestic water

heaters are acceptable.

B. Kitchens may be served from building hot water system, but shall have a dedicated branch line

tied into the building hot water system upstream of central thermostatic mixing valve.

1. Provide alternate hot water temperatures (as required) for food service and dishwasher

equipment. Discharge water temperature from service equipment shall be cooled in

accordance with local code requirements prior to entering sanitary system.

C. Hot water heating equipment serving areas other than food service may be generated by

centralized heaters or point-of-use heaters. All hot water shall be generated to 140° F and mixed

to 122°F – 123°F before distribution. Return hot water temperature shall be 115°F – 116°F.

1. Reduce temperature at plumbing fixture outlet as required by local code.

2. Sterilization water that is not exposed to general staff shall be 160°F.

3. Separate water heating equipment and circulation pumps shall be provided for each

pressure zone within a high-rise building. All high-rise plumbing distribution designs shall

be reviewed with CC Engineer during schematic design of project.

D. Provide pre-pressurized steel thermal expansion tank with membrane on the cold water supply

line of all water heating equipment where cold water service contains check valves, pressure

reducing valves, or backflow preventers. Thermal expansion tanks shall meet all pressure vessel

standards applicable to the connected hot water system.

1.2 Hospital Domestic Water Heater Requirements

A. Domestic water heating equipment shall include 20% extra capacity for future renovations.

B. The building shall be supplied with a fully redundant domestic water system (N+1), including

heat exchangers/heaters and recirculating pumps.

1. Natural gas fired domestic water heaters shall be capable of dual fuel operation.

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 5. Domestic Water Heating Equipment

April 2017 5 - 2

1.3 Ambulatory Healthcare Facility Domestic Water Heater Requirements

A. Domestic water heating equipment shall include 10 – 15% extra capacity for future renovations.

Extra capacity shall be reviewed with CC Engineer during project design.

B. Dual fuel requirement shall be determined based on facility’s emergency operational plan.

1. If dual fuel is required, domestic heat exchanger/heater requirements shall match those

listed in Hospital Requirements.

2. If dual fuel is not required, domestic water shall be produced using high efficiency

domestic water heaters.

a. Condensing style domestic water heaters shall be considered for increased

efficiency, but system shall be designed for optimum efficiency.

1.4 Outpatient Facility Domestic Water Heater Requirements

A. Domestic water heating equipment shall include 10% extra capacity for future renovations. Extra

capacity shall be reviewed with CC Engineer during project design.

B. Dual fuel will not typically be required, but shall be reviewed with CC Engineer during project

design.

C. Condensing style domestic water heaters shall be considered for increased efficiency, but return

shall be designed for optimum efficiency.

1.5 Administration Facility Domestic Water Heater Requirements

A. Review domestic water heating equipment requirements with CC Engineer during project design.

B. Condensing style domestic water heaters shall be considered for increased efficiency, but system

shall be designed for optimum efficiency.

1.6 Manufacturers

A. Refer to CC Equipment Supplier List located on Buildings and Properties Website for acceptable

equipment manufacturers. (http://portals.clevelandclinic.org/ocm)

*****

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 6. Plumbing Fixtures

April 2017 6 - 1

1.1 Plumbing Fixture Requirements

A. Fixtures and trim specified for renovation of existing facilities shall match existing installation

where possible.

B. Fixtures, trim, and accessories shall be institutional/commercial grade quality.

C. Vitreous china plumbing fixtures shall be white or bone in color with chrome-plated brass fixture

trim and accessories.

D. Wall mounted fixtures shall be supported with commercial carriers, bolted to the floor.

1. Wall hung water closets installations shall be capable to withstand a minimum of 500 lbs.

Provide vitreous china fixtures compliant to ASME A11.2.19.2.2M 500 lb. load test, and

install using a heavy duty 500 lb. rated carrier. Standard 300 lb. rated carriers are not

acceptable.

a. All carriers shall be installed and anchored in accordance with the manufacturer’s

published instructions.

E. Bariatric fixtures and associated carriers shall be reviewed with CC Engineer during design.

F. Fixtures exposed to the public shall be provided with vandal resistant trim.

G. Electric water coolers shall be recessed in wall and provided with bottle filling station.

H. Water flows indicated in guideline are Cleveland Clinic standard flow rates. Low flow rates may

be required based on project requirements (LEED, etc.). Any deviation from standard flow rates

shall be reviewed with CC Engineer.

1.2 Electronic Sensor Activated Fixture Trim

A. Where electronic sensor faucets and flush valves are required, sensors shall be battery powered.

Batteries shall have a three (3) year minimum life expectancy.

B. All electronic flush valve sensors shall be provided with a manual override button except when

located within specimen collecting toilet rooms.

1.3 Sinks

A. General

1. Stainless steel sinks shall be 18 gauge Type 304 stainless steel with insulation

undercoating.

2. Fixture trim and accessories shall be chrome-plated.

3. All faucets shall be provided with ceramic disc cartridges.

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 6. Plumbing Fixtures

April 2017 6 - 2

4. All sinks primarily used for hand washing shall be provided with grid strainer drain with

5/16-inch holes. Drain stoppers or crumb-cup strainers shall only be used for break rooms.

B. Patient Room

1. Sink style shall be coordinated with CC Architectural Standards and project requirements.

2. Faucet

a. Manual operation with 4 inch minimum wrist blade handles

b. Gooseneck spout (with outlet a minimum of 5 inches above floor level rim of fixture)

c. Laminar flow outlet. Standard flow shall be 1.0 GPM, but reduced flow outlets are

acceptable. Hot water delivery time shall be considered if reduced flow outlet is

used.

C. Medical Staff General Use

1. Sink style shall be coordinated with CC Architectural Standards and project requirements.

2. Faucet

a. Manual operation with 4 inch minimum wrist blade handles.

1) Electronic sensor faucet is acceptable.

b. Gooseneck spout (with outlet a minimum of 5 inches above floor level rim of fixture)

c. Laminar flow outlet. Standard flow shall be 1.0 GPM, but reduced flow outlets are

acceptable. Hot water delivery time shall be considered if reduced flow outlet is

used.

D. Surgery Scrub Sink

1. Provide with electronic sensor controls.

E. Lab

1. Lab sinks used for general research shall be provided with manually operated faucets

served with cold water only. If hot water is required, a separate non-potable hot water

system shall be provided.

a. Sink shall be labeled as non-potable.

2. Sinks located in BSL-2 or higher tissue culture rooms shall be provided with foot pedal or

electronic sensor activated faucets with programmable run time.

1.4 Lavatories

A. General

1. Fixture trim and accessories shall be chrome-plated.

2. All faucets shall be provided with ceramic disc cartridges.

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 6. Plumbing Fixtures

April 2017 6 - 3

3. Lavatories shall be provided with grid strainer drain with 5/16-inch holes. Drain stoppers

or mechanical (pop-up) waste fittings will not be acceptable.

B. Public Bathroom

1. Lavatory style shall be coordinated with CC Architectural Standards and project

requirements.

2. Electronic sensor faucet (0.5 GPM)

C. Staff Bathroom

1. Lavatory style shall be coordinated with CC Architectural Standards and project

requirements.

2. Electronic sensor faucet (1.0 GPM)

D. Patient Room

1. Lavatory style shall be coordinated with CC Architectural Standards and project

requirements.

2. Faucet

a. Manual operation with 4 inch minimum wrist blade handles

b. Gooseneck spout (with outlet a minimum of 5 inches above floor level rim of fixture)

c. Laminar flow outlet. Standard flow shall be 1.0 GPM, but reduced flow outlets are

acceptable. Hot water delivery time shall be considered if reduced flow outlet is

used.

3. Lavatory faucets located in specimen collecting toilet rooms shall be provided with AC

powered electronic sensors. The electrical power shall be controlled by a wall switch

located outside of the toilet room to allow nursing staff to prevent use of faucet during

collection of specimen. Coordinate with Cleveland Clinic staff for exact location of wall

switch.

1.5 Mop Basins

A. Mop basin faucets in housekeeping closets shall be provided with automatic return stems that

require the handle to be manually held open for water to flow.

B. Provide accessible pipeline check valves on hot and cold piping to all housekeeping/service sink

faucets or mixing hose bibs. Housekeeping/service sink faucets shall be provided with vacuum

breaker.

1.6 Clinic Sinks

A. When possible, bedpan cleansing shall occur in patient room toilet. Where not applicable (e.g.,

ICU, PACU, ED, etc.), bedpan cleansing shall occur in soiled utility room. In soiled utility rooms

where bedpan cleansing will occur, clinic sinks shall be provided with the following accessories:

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 6. Plumbing Fixtures

April 2017 6 - 4

1. Wall mounted china is preferred. Floor mounted with terrazzo floor base is acceptable.

2. Flush valve (6.5 gallon flush)

3. Foot pedal operated, hand-held hose spray bed pan washer

4. Service sink faucet with 6 inch wrist blade handles

B. Locations and accessories of all clinic sinks shall be reviewed with CC Engineer during design.

1.7 Water Closets

A. General Design

1. Toilets shall be wall mounted vitreous china with elongated bowl, siphon jet flushing

action, and 1 ½ inch top inlet spud.

2. Flush valves shall be chrome-plated brass, exposed type.

3. Seats shall have open front and stainless steel self-sustaining check hinges.

4. Refer to wall carrier requirements in Section 1.1 Plumbing Fixture Requirements.

B. Patient Bathroom

1. Water closets shall be mounted at ADA height, expect in pediatric areas.

2. Water closets shall be provided with integral bedpan lugs.

3. Flush valves shall be manually operated (1.6 gallon flush).

a. Coordinate requirements for fold-down bedpan washer on a per project basis for

patient room toilets. Flush valve height shall be coordinated with grab bar locations

to avoid interference. Offset flush valves for bedpan washers are typically required

to avoid grab bar interference.

4. Flush valves located in specimen collecting toilet rooms shall be provided with AC

powered electronic sensors. The electrical power shall be controlled by a wall switch

located outside of the toilet room to allow nursing staff to prevent use of faucet during

collection of specimen. Coordinate with Cleveland Clinic staff for exact location of wall

switch.

C. Public and Staff Bathroom

1. Flush valves shall be electronic sensor operated (1.6 gallon flush).

1.8 Urinals

A. Urinals shall be wall mounted with carrier, vitreous china with elongated rim (14 inch minimum),

washout flushing action, and ¾ inch top inlet spud.

B. Waterless urinals are prohibited.

C. Urinal flush valves shall be 0.5 GPM, electronic sensor operated, chrome plated brass exposed

type.

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 6. Plumbing Fixtures

April 2017 6 - 5

1.9 Showers And Bathtubs

A. Shower and bathtub mixing valves shall be combination thermostatic and pressure-balancing type

with water temperature limit stops set at 110°F. Mixing valves shall have integral check stops

accessible for servicing.

B. Shower heads shall have a flow of 1.5 GPM.

C. Shower finished floor and bathtub bottom shall be slip resistant.

D. Bathtubs shall be enameled cast iron or high strength composite material with porcelain finish.

Enameled steel bathtubs are not acceptable.

1.10 Emergency Showers and Eyewashes

A. Emergency shower and eyewash equipment design, installation, and location shall meet current

ANSI Z358.1, NFPA 99-11.6 and OSHA 29 CFR 1910.151 standards and deliver clean water to

users. All locations shall be reviewed with CC Engineer and Environmental Health and Safety

department.

B. Coordinate location of safety drenching equipment on upper levels with spaces below to avoid

areas where water leakage would cause major property loss or contamination, including but not

limited to computer data centers, MRI rooms, electrical rooms, telecommunications rooms, food

preparation, food storage, food serving, critical patient care areas, etc.

C. A handheld drench hose or personal eyewash station may be installed in laboratory or shop areas

as a supplement, not a substitute, for eyewash devices.

D. Emergency eye wash and shower equipment shall be provided with mixing valves that are factory

set to deliver tepid water outlet flow (60°F – 100°F).

E. Safety drenching equipment shall be identified with a highly visible sign, and area lighting shall

be adequate to facilitate use.

F. Provide an accessible ball type shutoff valve and check valves in individual water supply line

serving safety drenching equipment. Valves shall be labeled for identification and locked in the

open position.

G. Floor drains/floor sinks are required for emergency showers.

H. Provide emergency eye wash station adjacent to chemical treatment areas in mechanical rooms.

1.11 Manufacturers

A. Refer to CC Equipment Supplier List located on Buildings and Properties Website for acceptable

equipment manufacturers. (http://portals.clevelandclinic.org/ocm)

*****

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 7. Plumbing Insulation and Labeling

April 2017 7 - 1

1.1 Plumbing Insulation Requirements

A. General Design

1. All insulation shall have a system fire and smoke hazard rating as tested by procedure

ASTM-E-84, NFPA 255, and UL 723 not exceeding Flame Spread 25 and Smoke

Developed 50. The system rating shall be based on insulation, jacket, adhesives, coatings,

fittings, and cements. Any treatment of jackets or facings to impede flame and/or smoke

shall be permanent. The use of water-soluble treatments is prohibited.

B. Piping Insulation

1. All piping shall be insulated per the latest edition of ASHRAE 90.1.

2. The maximum temperature limit of the insulation must be above the maximum operating

temperature of piping. Surface temperature of insulation for heated piping in still ambient

air at 80°F shall not be above 110°F at the pipe operating temperature below 400°F.

3. Thickness of insulation for cold piping shall be selected to prevent condensation on the

surface of insulation with ambient temperature is 50°F above the pipe temperature. Specify

that insulation be installed with a continuous unbroken and un-punctured factory applied

vapor barrier.

4. Fittings, flanges, unions, and valves shall be insulated. Insulation shall be beveled down to

unions with all exposed ends sealed. Insulation covers shall be either prefabricated or

fabricated of pipe insulation. Insulation efficiency shall not be less than that of the

adjoining piping.

5. Hangers, supports, and anchors secured directly to cold surfaces must be adequately

insulated and vapor sealed to prevent condensation.

1.2 Plumbing Application Schedule (All Facility Types)

Piping Insulation Application Schedule

Piped System Minimum Insulation

Thickness Insulation Type

Domestic Cold Water Per ASHRAE 90.1 Fiberglass Insulation

Domestic Hot Water Per ASHRAE 90.1 Fiberglass Insulation

Domestic Recirculating Water Per ASHRAE 90.1 Fiberglass Insulation

Horizontal Storm Conductors 1” Fiberglass Insulation

Sanitary Piping carrying A/C

condensate drainage from drain

body to sanitary riser

1” Closed-Cell Insulation

1. All piping labels shall have direction of flow indicated.

2. Review non-potable water labeling requirements with CC Engineer during design.

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 7. Plumbing Insulation and Labeling

April 2017 7 - 2

Labeling Schedule

System Label Description Label Type/Material

Compressed Air COMPRESSED AIR Snap-Around Label

Acid Vent ACID VENT Snap-Around Label

Acid Waste ACID WASTE Snap-Around Label

Carbon Dioxide CARBON DIOXIDE Snap-Around Label

Deionized Water DEIONIZED WATER Snap-Around Label

Domestic Cold Water DOMESTIC COLD WATER Snap-Around Label

Domestic Hot Water DOMESTIC HOT WATER Snap-Around Label

Domestic Recirculating Hot Water DOMESTIC RECIRCULATING

HOT WATER Snap-Around Label

Natural Gas NATURAL GAS Snap-Around Label

Medical Air MEDICAL AIR Snap-Around Label

Medical Air Intake MEDICAL AIR INTAKE Snap-Around Label

Medical Vacuum MEDICAL VACUUM Snap-Around Label

Medical Vacuum Discharge MEDICAL VACUUM

DISCHARGE Snap-Around Label

Nitrogen Piping NITROGEN Snap-Around Label

Nitrous Oxide NITROUS OXIDE Snap-Around Label

Non-Potable Cold Water NON-POTABLE COLD WATER Snap-Around Label

Non-Potable Hot Water NON-POTABLE HOT WATER Snap-Around Label

Non-Potable Recirculating Hot

Water

NON-POTABLE

RECIRCULATING HOT WATER Snap-Around Label

Oxygen OXYGEN Snap-Around Label

Overflow Storm Drainage OVERFLOW STORM Snap-Around Label

Process Air PROCESS AIR Snap-Around Label

Purified Water PURIFIFED WATER Snap-Around Label

Sanitary Drainage SANITARY Snap-Around Label

Storm Drainage STORM Snap-Around Label

Tempered Hot Water TEMPERED HOT WATER Snap-Around Label

Vent VENT Snap-Around Label

Waste Anesthetic Gas Disposal WAGD Snap-Around Label

140°F Hot Water Piping 140°F HOT WATER Snap-Around Label

140°F Recirculating Hot Water

Piping

140°F RECIRCULATING HOT

WATER Snap-Around Label

1.3 Manufacturers

A. Refer to CC Equipment Supplier List located on Buildings and Properties Website for acceptable

equipment manufacturers. (http://portals.clevelandclinic.org/ocm)

*****

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 8. Gas and Vacuum Systems

April 2017 8 - 1

1.1 Hospital Gas and Vacuum Systems Requirements

A. Vacuum and gas systems shall be designed in accordance with current editions of FGI Guidelines

for Design and Construction of Hospitals and Healthcare Facilities, NFPA 55, NFPA 99,

Compressed Gas Association Standards, and ASSE 6000.

B. Review the location, quantity, and type of gas outlets, inlets, and alarm panels with Cleveland

Clinic gas commissioning consultant during the design development phase of the project.

C. Medical vacuum and gas systems serving patients shall be independent of all other vacuum and

gas systems serving laboratory, research, and/or animal areas.

D. Medical and laboratory compressed air systems serving patients or labs shall not be used to serve

non-respiratory equipment such as sterilizers, pneumatic doors, operating room service columns,

etc.

E. Design medical gas and vacuum systems to deliver nominal pressures in accordance with NFPA

99. If an existing facility operates at different pressures, coordinate all pressures with existing

facility and medical gas verifier.

F. Coordinate the requirement for the use of ventilators with Cleveland Clinic user groups. Design

the oxygen and medical air systems to accommodate required flow demands.

G. Include waste anesthetic gas disposal (WAGD) terminal inlets and piping where appropriate. The

source for WAGD inlets shall be an independent system from the medical vacuum system.

H. Provide at least one instrument air/nitrogen control panel (ICP) within rooms containing

instrument air outlets used for equipment. Verify need for instrument air / nitrogen / electric for

surgical tools with Cleveland Clinic on each project.

I. For surgical boom brakes within hospitals that require a pressure reducing valve on incoming gas,

provide redundant pressure reducing valves for manual switch-over located outside operating

room in accessible ceiling.

J. Locate station inlets and outlets at an appropriate height to prevent physical damage to attached

equipment and accessories. Station inlets and outlets located above countertops shall be provided

with sufficient space to allow usage and attachment of equipment without interferences by

countertop, backsplash, or overhead cabinets. All other station inlets and outlets having centerline

located less than 60 inches above finished floor shall be protected by guardrails, recessing into

walls, or by other means approved by Cleveland Clinic. Outlets shall be free and clear for testing.

K. Provide sufficient spacing between station inlets and outlets to allow simultaneous use with

vacuum collection bottles, regulators, adaptors, or any other equipment attached. Provide slide

retainer bracket for collection bottle attachment adjacent to each vacuum station inlet.

Renovations shall be updated so that they are installed the same as installing new.

L. Oxygen outlets for Series B type shall be provided with integral “hook plate” outlet cover.

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 8. Gas and Vacuum Systems

April 2017 8 - 2

M. Ensure that all vacuum and gas source equipment and alarm systems are provided with both

normal and emergency electrical power supply.

N. Drawings shall indicate all valves and pressure sensor locations.

O. All sourcing equipment shall be able to report to the master alarm panel.

P. Central Supply Systems

1. Locate air compressors and vacuum pumps in a dedicated mechanical room in accordance

with NFPA 99. Mechanical room shall provide a clean, relatively cool environment (i.e.,

not to exceed 100°F ambient temperature). Equipment shall be located with adequate

access space for regular monitoring and servicing. Provide floor drain adjacent to

equipment pads. Floor drains serving vacuum pumps shall be provided with smooth, acid

resistant interior coating. Provide a hose bib within mechanical room.

2. Terminate vacuum exhaust discharge outdoors above roof level, at least 25 feet

horizontally (may be more depending upon prevailing wind direction and velocity) from

all air intakes, doors, windows, louvers, or any other building openings. Combine exhaust

from each vacuum pump into one discharge pipe, sized for no restriction while flowing

maximum discharge possible, and provide with an isolation valve at the header for each

pump served. Avoid traps, but where installed provide low point drains. Exhaust piping for

vacuum pumps shall be sized using the total SCFM for the system (both lead and lag

pumps) and the total developed length of run. Exhaust piping shall be sized and arranged

to prevent moisture and back-pressure from entering pump. Provide valved drip-leg at base

of exhaust stacks. Coordinate with vacuum pump system technical representative and

verify that proposed sizing of exhaust piping complies with manufacturer’s

recommendations.

3. Air compressors and vacuum pumps shall be multiplexed with receiver tanks and sized

such that 100% of the design load is carried when the largest single is unit out of service.

Increase the calculated (SCFM) load by 20% to accommodate future system expansion.

4. In designing a medical air system where ventilators are expected to be utilized, add the

ventilator requirement for each ventilator in use to the compressor sizing.

5. Design air dryers, filters, and pressure regulators for the air system in triplex, each sized

for 100% of the load using duplex twin tower desiccant dryers. Include continuous line

dew point and carbon monoxide monitoring with sample connections on the discharge

piping downstream of the filters and regulators. Locate monitors at, or integral with, the

control panel.

6. Rooms for gas cylinder storage and manifolded systems shall be sized, ventilated, and

constructed in accordance with NFPA 99. Coordinate with Cleveland Clinic to determine

space required for storage of additional non-manifolded cylinders. Gas cylinder storage

rooms shall be located at a readily accessible location and provided with a minimum 42

inch door. Allow for 25% expansion.

7. Provide local user alarms for cylinder manifolds.

8. Bulk liquid oxygen supply systems shall be designed and located in accordance with NFPA

55 and closely coordinated with Cleveland Clinic and designated oxygen supplier. Provide

emergency oxygen inlet on exterior wall of building served. Insure that location of inlet

allows truck access and that concrete pavement is provided where truck will park during

transfer of oxygen. Provide with user alarm wiring to report to alarm system.

Q. Alarm Systems

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 8. Gas and Vacuum Systems

April 2017 8 - 3

1. To ensure continuous responsible observation, provide two master system alarms, in

separate warning locations, monitored 24/7, for all vacuum and gas source equipment

systems. Coordinate both master alarm panel locations with the user facility and the other

design services. When selecting alarm locations, consider emergency power circuits,

engineering control center data relay interface locations, and the facility’s established

procedures for monitoring alarm signals. The master alarm shall have extra wires for future

capacity to be coordinated with Cleveland Clinic engineering. Extend master alarm wiring

in separate conduits for redundancy.

a. The primary warning location shall be located to assure 24-hour constant

surveillance, such as in a security office or other continuously staffed location. The

secondary warning location shall be supervised by engineering personnel and is

required to be located at one of the following (in order of priority): Boiler plant

control office, engineering control center, or in the office or principal working area

of the individual responsible for the maintenance of the vacuum and gas systems.

2. Provide local area alarms for all branches serving medical vacuum and gas station outlets

and inlets. Locate area alarms at nurse stations visible and accessible to staff for

monitoring.

a. Provide alarm sensors in zone valve boxes.

1) For anesthetizing and critical care locations, review all alarm sensor locations

with CC Engineer.

3. Provide high/low line pressure/vacuum sensors at most remote points from source

equipment in each system. Status of remote monitoring points shall be annunciated at both

master system alarm locations.

R. Piping Systems

1. Design pressure piping systems, except nitrogen, not to exceed 35 kPa (5 PSI) loss from

source to point of use. Design nitrogen piping systems not to exceed 138 kPa (20 PSI) loss

from source to point of use. Design vacuum piping systems not to exceed 10 kPa (3 inches

Hg) from source to point of use.

2. Include ventilator demand in sizing calculations for oxygen and compressed air piping.

Ventilator usage shall be based upon full flow with no diversity for each ventilator from

the outlet back to the source.

3. Bulk oxygen vaporizers shall be based on full flow with no diversity.

4. Design medical gas and vacuum piping systems based upon the following minimum flow

rates for any pipe section.

Gas Minimum Flow Rate

Oxygen 200 L/min (7 SCFM)

Medical Air 200 L/min (7 SCFM)

Vacuum 85 L/min (3 SCFM)

Nitrous Oxide 28 L/min (1 SCFM)

Carbon Dioxide 28 L/min (1 SCFM)

Nitrogen 425 L/min (15 SCFM)

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 8. Gas and Vacuum Systems

April 2017 8 - 4

5. Include a 25% calculated (SCFM) load for sizing distribution mains to accommodate future

system expansion.

6. Distribution piping shall be designed in accordance with the following minimum size

parameters to allow for future expansion and minimize service interruptions during

renovations.

a. Pressure Gases

1) Branch lines and drops to individual outlets for the pressure gases shall be a

minimum of ½ inch.

2) Branch lines serving zone valve or more than one room shall be a minimum

of ¾ inch.

b. Vacuum

1) Branch lines and drops to individual vacuum inlets shall be a minimum of ¾

inch.

2) Branch lines serving a zone valve or more than one room shall be a minimum

of 1 inch.

7. Design carbon dioxide distribution piping for total load, no diversity.

S. Renovation Projects

1. Survey current installation and coordinate with CC Engineer to verify type, location, size,

and capacities of existing piping and source equipment for determining adequate tie-in

points.

2. Survey current installation to ascertain the type of existing alarms, gas station outlets, and

vacuum terminal inlets. All new alarms shall match and be compatible with the existing

installation. All new outlets and inlets shall match the existing terminal connections and

not require the use of secondary adapters. In cases where existing alarms, station outlets,

or terminal inlets are no longer available, not U.L. approved, or are not NFPA 99 compliant,

the Design Team shall coordinate with CC Engineer to determine types to be specified

within Contract Documents. Outlets shall be DISS or quick connect, BeaconMedaes style.

3. Review the proposed alarm, outlet and inlet types, and connection locations to existing

piping and alarms with CC Engineer during the design development phase of the project.

4. Provide a shut-off valve at the connection of new line to existing line.

1.2 Laboratory Gas and Vacuum System Requirements

A. Laboratory gas and vacuum systems shall match requirements listed in 1.1 Hospital Gas and

Vacuum, except where indicated in this section.

B. Laboratory gases for vivarium labs shall be hospital grade quality.

C. Master alarm panels are not required for laboratories. Provide area alarm panels for local

alarming.

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 8. Gas and Vacuum Systems

April 2017 8 - 5

1.3 Ambulatory Healthcare Facility Gas and Vacuum System Requirements

A. Shall follow all hospital requirements.

1.4 Outpatient Healthcare Facility Gas and Vacuum System Requirements

A. Shall follow all hospital requirements, with the following exception:

1. Medical air compressors and vacuum pumps shall be duplex.

1.5 Installation and Verification Requirements:

A. Medical gas installers shall be ASSE 6010 certified.

B. Medical gas verifiers shall be ASSE 6030 certified.

1. Installation reports shall integrate into existing facility’s database software.

1.6 Manufacturers

A. Refer to CC Equipment Supplier List located on Buildings and Properties Website for acceptable

equipment manufacturers. (http://portals.clevelandclinic.org/ocm)

*****

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 9. Facility Natural Gas Piping

April 2017 9 - 1

1.1 Natural Gas Distribution Requirements

A. All natural gas piping on the customer side of the utility meter shall be designed, installed and

tested in accordance with NFPA 54 and International Fuel Gas Code (most current edition).

B. Building natural gas distribution shall be metered and valved in accordance with the gas supplier’s

requirements.

C. Building supply and distribution systems design shall provide a volume of gas at the required

flows and pressures to ensure safe, efficient, and code-compliant operation during periods of peak

demand. Piping shall be sized in accordance with referenced codes and standards.

D. Natural gas pressures shall not exceed 5 PSIG on customer side of the meter, for non-utility

buildings.

E. Provide readily accessible manual shut-off valve outside of building at service entrance.

F. Avoid locating gas piping within confined or unventilated spaces where leaking gas might collect.

G. Do not locate gas piping within stairways, electrical rooms, or telecommunications rooms.

H. Exposed and accessible shut-off valves shall be provided for proper operation and servicing of

system. Valves located above ceilings shall not be located in concealed areas or shall be provided

with access panels in hard ceilings. Locations shall include, but not be limited to, the following:

at the base of each riser, at each branch connection to risers, at each piece of equipment, where

recommended by equipment manufacturer, and at strategic locations to allow sectional isolation

while limiting disruption of services to large portions of the system. Provide pressure gauges on

each side of the valve. Provide valve on riser to each pressure gauge.

I. Valves, regulators, flanges, unions, and similar appurtenances shall be accessible for operation

and servicing. They are not be located above ceilings, within partitions, or in spaces utilized as

return air plenums.

J. Natural gas piping, including service drops, shall be no smaller than ¾ inches inside diameter.

Exception: Local connections to individual equipment and outlets may be smaller than ¾ inches

as required for that particular component. Transition and valve within 12 inches of connection.

K. Provide a manual shut-off valve in each line serving individual laboratory rooms for maintenance

and isolation of natural gas serving each room. Room manual isolation valves shall be labeled to

indicate the room being controlled and located to be accessible to maintenance staff.

L. Within each laboratory, and adjacent to room exit, provide an emergency shut-off valve. Locate

the valve exposed on wall, 54 inches above finished floor.

M. Butterfly valves are not acceptable.

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 9. Facility Natural Gas Piping

April 2017 9 - 2

1.2 Natural Gas Application Schedule

Pipe and Joining Application Schedule

Piped System Pipe Size

Range

Pipe Specified

Type(s) Joining Specified Method(s)

Natural Gas Inside Building or Outside

Building (Above Ground and Accessible)

2” and

smaller Black Steel (Sch. 40) Threaded

Natural Gas Inside Building or Outside

Building (Above Ground)

2 ½” and

larger Black Steel (Sch. 40) Welded

1.3 Manufacturers

A. Refer to CC Equipment Supplier List located on Buildings and Properties Website for acceptable

equipment manufacturers. (http://portals.clevelandclinic.org/ocm)

*****

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 10. Laboratory Water and Waste Systems

April 2017 10 - 1

1.1 Laboratory Water Systems Requirements

A. Laboratory reverse osmosis (RO) water system shall be provided for analysis equipment and

testing locations within the laboratory.

B. A dedicated laboratory cold water and hot water system shall be provided for laboratory use at

dirty sinks and where back siphonage can occur. These systems shall be separated from the normal

domestic cold and hot water system using duplex reduced pressure backflow preventer.

C. Building domestic cold and hot water shall be used for remaining clean sink locations and for

safety shower/eyewash tempering valves.

D. Central tempering valves shall be provided to serve multiple safety units on systems with more

than three (3) safety shower or eyewash units.

1.2 Laboratory Waste Systems Requirements

A. Laboratory waste and vent systems shall be provided for all fixtures, floor drains, and equipment

that may discharge corrosive liquids, spent acids, or other harmful chemicals that could

potentially destroy or injure cast iron or copper drainage and vent piping.

1. Sinks which are designated as “clean” sinks shall connect to the sanitary system.

B. The Design Team shall obtain all necessary information from CC Engineer to determine system

design, materials selection, and waste treatment requirements. A proposed system design in either

diagrammatic or narrative form shall be submitted to CC Engineer during the schematic phase of

the project.

C. Chemically resistant waste and vent piping is required for all lab sinks, dirty sinks, cup sinks, hub

drains, and floor drains within laboratory areas in the event that chemicals are discharged into the

piping system.

D. Double containment piping shall be used for high hazard drainage, such as in BSL3 labs.

E. When effluent is expected to have a pH less than 6 or more than 10, waste treatment shall be

provided to render the waste to a neutral pH before discharging into building sanitary or municipal

sewer systems.

1. Treatment system shall be installed with a pH monitoring and leak detection system.

2. Treatment tanks shall be double wall construction and be located in non-patient areas with

adequate service space.

F. All piping shall be selected based upon the characteristics of the effluent expected to be

introduced and be of such material and design as to adequately perform its intended function as

required by code and to the satisfaction of Cleveland Clinic.

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 10. Laboratory Water and Waste Systems

April 2017 10 - 2

G. All materials located within spaces utilized as air plenums shall meet ASTM E84 25/50 for flame

spread and smoke development and UL 723 and UL 910 for flame propagation and smoke density

in environmental spaces.

H. Waste and vent systems shall be designed using fixture drain loads established by code and

equipment manufacturers’ discharge flow rates. Waste and vent systems design shall provide

proper operation during periods of peak demand.

I. Main waste and vent stacks shall utilize chases or be located adjacent to columns where possible

for vertical routing through multiple floor levels.

J. Capped waste and vent connections for future extensions shall be located accessibly and not

extend more than 24 inches from an active line. Waste and vent connections shall be located at

elevations that will allow future installation of properly sloped piping without the need to

dismantle or relocate installed ductwork, piping, conduit, light fixtures, etc.

K. Provide cleanouts at the base of each vertical sanitary stack and at intervals not exceeding 75 feet

in horizontal building drain. All interior cleanouts shall be accessible from walls or floors. Provide

wall cleanouts in lieu of floor cleanouts wherever possible. A floor cleanout shall be installed

only where installation of a wall cleanout is not practical. Locate wall cleanouts no more than 24

inches above the finished floor. For horizontal cleanouts, provide an access door and blind plug.

For vertical cleanouts, provide an access door, wye, and blind plug. Plumbing Engineer is

responsible for coordinating access door locations for incorporation on the architectural plans.

L. No buried laboratory waste line shall be smaller than 3 inches. No buried vent line shall be smaller

than the full size of the sanitary pipe that it is serving. No aboveground vent line shall be smaller

than 1 ½ inches. No roof vent terminal shall be smaller than 3 inches.

M. Avoid locating drains above sensitive equipment or areas where water leakage would cause major

property loss or contamination. Where this is unavoidable, provide a stainless steel drain pan with

drain and leak detection alarms tied into building management system. Coordinate water tight

flooring (with Architect) for rooms above sensitive equipment.

N. Do not locate drainage or vent piping within stairways, electrical rooms, telecommunications

rooms, or to-be-leased spaces. Where this is unavoidable, provide a stainless steel drain pan with

drain and leak detection alarms tied into the building management system. Coordinate water tight

flooring (with Architect) for rooms above sensitive equipment.

O. Do not locate floor drains within pharmacy drug preparation areas or areas where hazardous

materials are handled or stored.

P. Provide trap primers for all floor and hub drains that may be susceptible to trap seal evaporation.

Trap primers shall be placed in accessible locations.

Q. Laboratory waste and vent piping shall be independent of all other waste and vent systems within

the building.

Cleveland Clinic Design Standards Plumbing Systems Design Guidelines 10. Laboratory Water and Waste Systems

April 2017 10 - 3

1.3 Manufacturers

A. Refer to CC Equipment Supplier List located on Buildings and Properties Website for acceptable

equipment manufacturers. (http://portals.clevelandclinic.org/ocm)

*****

Cleveland Clinic Design Standards

PLUMBING EQUIPMENT

Domestic Water Heaters

PVI PVI N/A N/A N/A

Leslie Controls Leslie Controls

Patterson-Kelly Patterson-Kelly

Aerco Aerco

PVI PVI PVI PVI PVI

A.O. Smith A.O. Smith A.O. Smith A.O. Smith A.O. Smith

Lochinvar Lochinvar Lochinvar Lochinvar Lochinvar

Aerco Aerco Aerco Bradford White Bradford White

State State

PVI PVI PVI N/A N/A

A.O. Smith

Grundfos Grundfos Grundfos Grundfos Grundfos

SyncroFlo SyncroFlo SyncroFlo SyncroFlo SyncroFlo

Bell & Gossett Bell & Gossett Bell & Gossett Bell & Gossett Bell & Gossett

Domestic Water Piping

Viega Propress Viega Propress Viega Propress Viega Propress Viega Propress

Victaulic Victaulic Victaulic Victaulic Victaulic

Anvil Anvil Anvil Anvil Anvil

Grinnell Grinnell Grinnell Grinnell Grinnell

Shurjoint Shurjoint Shurjoint Shurjoint Shurjoint

Interior Domestic Water Piping Specialties

Ames Ames Ames Ames Ames

Conbraco Conbraco Conbraco Conbraco Conbraco

Wilkins Wilkins Wilkins Wilkins Wilkins

Watts Watts Watts Watts Watts

Bell & Gossett Bell & Gossett Bell & Gossett Bell & Gossett Bell & Gossett

Armstrong Pumps Armstrong Pumps Armstrong Pumps Armstrong Pumps Armstrong Pumps

Taco Taco Taco Taco Taco

Amtrol Amtrol Amtrol Amtrol Amtrol

Pentair Pump Group Pentair Pump Group Pentair Pump Group Pentair Pump Group Pentair Pump Group

A.O. Smith A.O. Smith A.O. Smith A.O. Smith A.O. Smith

State Industries State Industries State Industries State Industries State Industries

Taco Taco Taco Taco Taco

John Wood John Wood John Wood John Wood John Wood

Bell & Gossett Bell & Gossett Bell & Gossett Bell & Gossett Bell & Gossett

Armstrong Pumps Armstrong Pumps Armstrong Pumps Armstrong Pumps Armstrong Pumps

ELBI ELBI ELBI ELBI ELBI

Cla-Val Cla-Val Cla-Val Cla-Val Cla-Val

Watts Watts Watts Watts Watts

Willkins Willkins Willkins Willkins Willkins

Lawler Lawler Lawler Lawler Lawler

Lenoard Lenoard Lenoard Lenoard Lenoard

Armstrong Armstrong Armstrong Armstrong Armstrong

Powers Powers Powers Powers Powers

Leonard Leonard Leonard Leonard Leonard

Armstrong Armstrong Armstrong Armstrong Armstrong

Lawler Lawler Lawler Lawler Lawler

Bradley Bradley Bradley Bradley Bradley

Josam Josam Josam Josam Josam

MIFAB MIFAB MIFAB MIFAB MIFAB

Prier Prier Prier Prier Prier

J.R. Smith J.R. Smith J.R. Smith J.R. Smith J.R. Smith

Wade Wade Wade Wade Wade

Watts Watts Watts Watts Watts

Woodford Woodford Woodford Woodford Woodford

Zurn Zurn Zurn Zurn Zurn

Apollo Apollo Apollo Apollo Apollo

Hammond Hammond Hammond Hammond Hammond

Nibco Nibco Nibco Nibco Nibco

Jomer (Copper) Jomer (Copper) Jomer (Copper) Jomer (Copper) Jomer (Copper)

Johns Manville Johns Manville Johns Manville Johns Manville Johns Manville

Owens-Corning Owens-Corning Owens-Corning Owens-Corning Owens-Corning

Knauf Knauf Knauf Knauf Knauf

Manson Manson Manson Manson Manson

Armacell - Armaflex Armacell - Armaflex Armacell - Armaflex Armacell - Armaflex Armacell - Armaflex

Cleveland Clinic Approved Manufacturer(s)

LaboratoryHospital Ambulatory Healthcare Facility Outpatient Facility Administration Building

Natural Gas / Fuel Oil Dual Fuel

Wall & Yard Hydrants

Water Pressure Booster Pumping System

Expansion Tanks

Plumbing Piping Insulation

Copper Pressed Fitting Method

Central Digital Mixing Center

Backflow Preventers

Hot Water Recirculating Pumps

Pre-Piped Central Thermostatic Control Station

Pressure Regulating Valves

Steam

Natural Gas/Electric

General Duty Valves For Plumbing Piping

Stainless Steel Piping (Grooved Piping)

APRIL 2017 Page 1 of 3

Cleveland Clinic Design Standards

PLUMBING EQUIPMENT

Cleveland Clinic Approved Manufacturer(s)

LaboratoryHospital Ambulatory Healthcare Facility Outpatient Facility Administration Building

Drainage Systems Specialties

Zurn Zurn Zurn Zurn Zurn

Josam Josam Josam Josam Josam

MIFAB MIFAB MIFAB MIFAB MIFAB

Watts Watts Watts Watts Watts

J.R. Smith J.R. Smith J.R. Smith J.R. Smith J.R. Smith

Wade Wade Wade Wade Wade

Sanitary Drainage Piping

Clamp-All 125 Clamp-All 125 Clamp-All 125 Clamp-All 125** Clamp-All 125**

Clamp-All 80 Clamp-All 80

Husky 2000 Husky 2000

Ideal MD Ideal MD

Mission HW Mission HW

**Buildings over 2 stories **Buildings over 2 stories

Match Existing Facility Match Existing Facility Match Existing Facility Match Existing Facility Match Existing Facility

Zoeller Zoeller

Weil Weil Weil Weil Weil

Bell & Gossett Bell & Gossett Bell & Gossett Bell & Gossett Bell & Gossett

Barnes Barnes Barnes Barnes Barnes

Grundfos Grundfos Grundfos Grundfos Grundfos

Plumbing Fixtures

American Standard American Standard American Standard American Standard American Standard

Kohler Kohler Kohler Crane Crane

Zurn Zurn Zurn Gerber Gerber

Kohler Kohler

Mansfield Mansfield

Sloan Sloan

Zurn Zurn

American Standard American Standard American Standard American Standard American Standard

Bemis Bemis Bemis Bemis Bemis

Church Church Church Church Church

Jones Stephens Corp. Jones Stephens Corp. Jones Stephens Corp. Jones Stephens Corp. Jones Stephens Corp.

Kohler Kohler Kohler Kohler Kohler

Olsonite Olsonite Olsonite Olsonite Olsonite

Zurn Zurn Zurn Zurn Zurn

Sloan Sloan Sloan Sloan Sloan

Moen Commercial Moen Commercial Moen Commercial Moen Commercial Moen Commercial

Zurn Zurn Zurn Zurn Zurn

Delany Delany Delany Delany Delany

Elkay Elkay Elkay Elkay Elkay

Just Just Just Just Just

Moen Moen

Kohler Kohler

Chicago Chicago American Standard American Standard American Standard

T&S Brass T&S Brass Bradley Corp. Bradley Corp. Bradley Corp.

Zurn Zurn Chicago Chicago Chicago

T&S Brass T&S Brass T&S Brass

Zurn Zurn Zurn

Kohler Elkay Elkay

Moen Commercial Just Manufacturing Just Manufacturing

Kohler Kohler

Moen Commercial Moen Commercial

Acorn Engineering Acorn Engineering Acorn Engineering Acorn Engineering Acorn Engineering

Crane Crane Crane Crane Crane

Florestone Florestone Florestone Florestone Florestone

Stern Williams Stern Williams Stern Williams Stern Williams Stern Williams

Zurn Zurn Zurn Zurn Zurn

Fiat Fiat Fiat Fiat Fiat

Elkay Elkay Elkay Elkay Elkay

Halsey Taylor Halsey Taylor Halsey Taylor Halsey Taylor Halsey Taylor

Chicago Chicago Chicago Chicago Chicago

Powers Powers Powers Powers Powers

Lawler Lawler Lawler Lawler Lawler

Leonard Leonard Leonard Leonard Leonard

N/A American Standard American Standard American Standard American Standard

Chicago Chicago Chicago Chicago

Moen Moen Moen Moen

Kohler Kohler Kohler Kohler

Powers Powers Powers Powers

Haws Haws Haws Haws Haws

Flush Valves

Water Coolers

Toilet Seats

Plumbing Pumps - Drainage

China

Stainless Steel Sinks

Mop Basins

Floor Drains, Roof Drains, Cleanouts, Carriers

Shower Valves (Combination

Thermostatic/Pressure Balance Type)

Emergency Equipment

Shower Valves (Thermostatic-Only Type)

Domestic Water Softeners

Cast Iron Fittings

Faucets

APRIL 2017 Page 2 of 3

Cleveland Clinic Design Standards

PLUMBING EQUIPMENT

Cleveland Clinic Approved Manufacturer(s)

LaboratoryHospital Ambulatory Healthcare Facility Outpatient Facility Administration Building

Guardian Guardian

Badger Meter Badger Meter Badger Meter Badger Meter Badger Meter

Interior Gas Piping

Actaris Actaris Actaris Actaris Actaris

American Meter Company American Meter Company American Meter Company American Meter Company American Meter Company

Fisher Fisher Fisher Fisher Fisher

Invensys Invensys Invensys Invensys Invensys

Richards Industries Richards Industries Richards Industries Richards Industries Richards Industries

Maxitrol Maxitrol Maxitrol Maxitrol Maxitrol

Flowserve Flowserve Flowserve Flowserve Flowserve

Homestead Homestead Homestead Homestead Homestead

Milliken Milliken Milliken Milliken Milliken

McDonald McDonald McDonald McDonald McDonald

Mueller Mueller Mueller Mueller Mueller

R&M Energy Systems R&M Energy Systems R&M Energy Systems R&M Energy Systems R&M Energy Systems

BrassCraft BrassCraft BrassCraft BrassCraft BrassCraft

Conbraco Conbraco Conbraco Conbraco Conbraco

Lyall Lyall Lyall Lyall Lyall

Perfection Corp. Perfection Corp. Perfection Corp. Perfection Corp. Perfection Corp.

Medical Gas and Vacuum Systems

Beacon Medaes Beacon Medaes Beacon Medaes Beacon Medaes N/A

Beacon Medaes Beacon Medaes Beacon Medaes Beacon Medaes N/A

Beacon Medaes Beacon Medaes Beacon Medaes Beacon Medaes N/A

Beacon Medaes Beacon Medaes Beacon Medaes Beacon Medaes N/A

NFPA 99 Compliant NFPA 99 Compliant NFPA 99 Compliant NFPA 99 Compliant N/A

Emergency Equipment

Pipeline Valves

Alarms

Vacuum Pumps

Gas Pressure Regulators

Gas Valves (Plug & Ball)

Terminal Outlets

Compressors

Domestic Water Sub-Meter

APRIL 2017 Page 3 of 3