DESIGN GUIDE FINAL-1
Transcript of DESIGN GUIDE FINAL-1
36 Design Guide
Armopanel™ Concrete Wall System
B-6.2. Interaction Diagrams for Structural Reinforced Armopanel™ Concrete Walls
k (effective length factor) =1 f'c=3,550 psi fy=60,000 psi
VERTICAL REINFORCEMENT # 5 @ 16" THICKNESS OF CONCRETECORE
SHEAR CAPACITY V (factored) 3.56 , kips / lin. Ft.
FLEXURE FACTORED LOAD STRENGTH IN HORIZONTAL DIRECTION per linear foot (factored) 1.23 , ft-kip / lin. Ft.
FLEXURE AND AXIAL STRENGTH IN VERTICAL DIRECTION per linear foot
Armopanel™ Concrete Wall. Interaction Diagram
6"
M vs. P (factored)
0
40
80
120
0 10
M , ft-kip / lin. Ft.
P ,
kip
/ lin
. Ft.
H=48 in. H=80 in. H=96 in. H=120 in. H=136 in. H=152 in.
HEIGHT OF WALL
NOTE: FIG. B-6.2.1 Vertical reinforcement should be placed within middle third of the concrete wall.
Design Guide 37
Armopanel™ Concrete Wall System
Concrete Strength = 3,500 psiSteel Strength = 60,000 psi
Vertical reinforcement should be placed
within middle third of the concrete wall
16 24 32 40 48 60 74 80
6,66,36
5,75,44,94,44,1
6,46,085,65,45
4,43,7
65,55
4,43,83
53,82,51,9
Loads are given per liner foot. FIG.B-6.2.2For Horizontal Reinforcement - Refer to Min. Reinforcement Requirements, of ACI 318-99
P , kip
6
Supplementary table to 6" Concrete Wall Interaction Diagram
Minimum Vertical Reinforcement Required
#5 @ 16"
D12 @ 8"
Design Required
Wall Height per Storey (ft)
Design Required#5 @ 16"
D12 @ 8"
#5 @ 16"
D12 @ 8"
M, kip·ft
Design Required
Design Required
8
10
12
#5 @ 16"
D12 @ 8"
1000[39 .4 "]
400[16"]
200[8 "] REBA R
67
[2 5
8"]
70
[2 3
4"]
150
[6"]
150
[6"]
38 Design Guide
Armopanel™ Concrete Wall System
NOTE: FIG. B-6.2.3 Vertical reinforcement should be placed within middle third of the concrete wall.
k (effective length factor) =1 f'c = 25 Mpa fy=400 Mpa
VERTICAL REINFORCEMENT: 15M @ 400 mm (10M @ 200 mm)THICKNESS OF CONCRETECORE
SHEAR CAPACITY V (factored) 5.30 tn /m ( 53.0 kN /m)
Armopanel™ Concrete Wall. Interaction Diagram
150 mmFLEXURE AND AXIAL STRENGTH IN VERTICAL DIRECTION per linear meter
FLEXURE FACTORED LOAD STRENGTH IN HORIZONTAL 0.56 tn-m /m ( 5.6 kN·m /m)DIRECTION per linear meter (factored)
M vs. P (factored)
0
40
80
120
160
0 2 4
M , tn-m / lin. m.
P ,
tn /
lin. m
.
H=122cm H=203cm H=244cm H=305cm H=345cm H=386cm
M vs. P (factored)
0
40
80
120
160
0 2 4M , tn-m /m
P ,
tn /m
H=122cm H=203cm H=244cm H=305cm H=345cm H=386cm
( M, kN·m / m ) (20)
HEIGHT OF WALL
(40) (P,
kN/
m)
(400)
(800)
(1200)
(1600)
Design Guide 39
Armopanel™ Concrete Wall System
Concrete Strength = 25 MPaSteel Strength = 400 MPa
Vertical reinforcement should be placedwithin middle third of the concrete wall
160 400 560 720 880 1120 1200
23,8232221
20,519
18,5
23,52221
19,518,517
2320181614
21,5
13
8,5
Loads are given per liner meter. FIG. B-6.2.4For Horizontal Reinforcement - Refer to Min. Reinforcement Requirements, of CSA A23.3-94
D12@200
15M@400 Design Required
15M@400
15M@400
Supplementary table to 150 mm Concrete Wall Interaction Diagram
Minimum Vertical Reinforcement Required
2,03
Wall Height per
Storey (m.)
15M@400
D12@200
Design Required
P , kN M, kN·m
Design Required
D12@200
2,44
3,05
D12@200
3,86
Design Required
1 0 0 0[3 9 .4 " ]
4 0 0[1 6 " ]
2 0 0[8 " ] R E B A R
67
[2 5
8"]
70
[2 3
4"]
150
[6"]
150
[6"]
40 Design Guide
Armopanel™ Concrete Wall System
k (effective length factor) =1 f'c=3,500 psi fy=60,000 psi
VERTICAL REINFORCEMENT: # 5 @ 16" EFTHICKNESS OF CONCRETECORE
Armopanel™ Concrete Wall. Interaction Diagram
8"FLEXURE AND AXIAL FACTORED LOAD STRENGTH IN VERTICAL DIRECTION
per linear foot
FACTORED SHEAR CAPACITY V 8.03 , kips / lin. Ft.
FLEXURE FACTORED LOAD STRENGTH IN HORIZONTAL
DIRECTION per linear foot2.84 , ft-kip / lin. Ft.
M vs. P
0
40
80
120
160
0 10 20
M , ft-kip / lin. Ft.
P ,
kip
/ lin
. Ft.
H=48 in. H=80 in. H=96 in. H=120 in. H=136 in. H=152 in.
HEIGHT OF WALL
NOTE: FIG. B-6.2.5 Vertical reinforcement should be covered by 1 ½” thick concrete
Design Guide 41
Armopanel™ Concrete Wall System
Concrete Strength = 3,500 psiSteel Strength = 60,000 psi
Clear concrete cover = 1 1/2"
24 40 56 72 85 102 112 118
10,213
15,515,813,810,5
97,9
10,213
15,514129,27,5
1012,213,3119
6,8
9,79,88,36,95,6
Loads are given per liner foot. FIG. B-6.2.6
D12 @ 8"
#5 @ 16"
D12 @ 8"
#5 @ 16"
D12 @ 8"
#5 @ 16"
D12 @ 8"
#5 @ 16"
6
Wall Height per Story (ft)
Design Required
Design Required
8
10
12
Design Required
Design Required
Supplementary table to 8" Concrete Wall Interaction Diagram
Reinforcing steel must be placed on the each side of the wall.
M, kip·ft
P , kip
Minimum Vertical Reinforcement Requierd
For Horizontal Reinforcement – Refer to Min. Reinforcement Requirements, of ACI 318-99
1000[39.4"]
40
[1 1
2"]
4 00[16"]4
0
[1 1
2"]
2 00[8"]
40
[1 1
2"]
40
[1 1
2"]
R EBAR
200
[8"]
200
[8"]
42 Design Guide
Armopanel™ Concrete Wall System
k (effective length factor) =1 f'c = 25 Mpa fy = 400 MPa
VERTICAL REINFORCEMENT: 15M @ 400 mm EF (10M @ 200 mm)THICKNESS OF CONCRETECORE
FACTORED SHEAR CAPACITY V 11.96 tn /m (119.6 kN /m)
FLEXURE FACTORED LOAD STRENGTH IN HORIZONTAL 1.29 tn-m /m ( 12.9 kN·m /m)DIRECTION per linear meter
Armopanel™ Concrete Wall. Interaction Diagram
200 mmFLEXURE AND AXIAL FACTORED LOAD STRENGTH IN VERTICAL DIRECTION per
linear meter
M vs. P
0
40
80
120
160
200
0 5 10M , tn-m / m
P ,
tn /m
H=122cm H=203cm H=244cm H=305cm H=345cm H=386cm
M, kN·m / m 50 100
P, k
N /
m
2000 1600
1200 800 400
NOTE: FIG. B-6.2.7 Vertical reinforcement should be covered by 40 mm thick concrete
HEIGHT OF WALL
Design Guide 43
Armopanel™ Concrete Wall System
Concrete Strength = 25 MPa Steel Strength = 400 MPa
560 800 1040 1280 1520 1680 176056 69 73 61 48 40 35 56 69 65 54 43 34 54 63 52 42 31 45 38 32 25
Loads are given per liner meter. FIG. B-6.2.8
Wall Height per
Storey (m.)
15M@400
D12@200
Design Required
Design Required
P , kN M, kN·m
Design Required
Design Required
2,03
2,44
3,05
15M@400
Supplementary table to 200 mm Concrete Wall Interaction Diagram
Minimum Vertical Reinforcement Required
3,86
15M@400
D12@200
15M@400D12@200
D12@200
1000[39.4"]
40
[1 1
2"]
400[16"]4
0[1
12"]
200[8"]
40
[1 1
2"]
40
[1 1
2"]
REBAR
200
[8"]
200
[8"]
For Horizontal Reinforcement – Refer to Min. Reinforcement Requirements, of CSA A23.3-94
Reinforcing steel must be placed on the each side of the wall. Clear concrete cover=40mm
44 Design Guide
Armopanel™ Concrete Wall System
k (effective length factor) =1 f'c=3,500 psi fy=60,000 psi
THICKNESS OF CONCRETECORE
FACTORED SHEAR CAPACITY V (factored) 10.90 , kips / lin. Ft.
Armopanel™ Concrete Wall. Interaction Diagram
FLEXURE FACTORED LOAD STRENGTH IN HORIZONTAL DIRECTION per linear foot 3.87 , ft-kip / lin. Ft.
FLEXURE AND AXIAL FACTORED LOAD STRENGTH IN VERTICAL DIRECTION per linear foot
VERTICAL REINFORCEMENT: # 5 @ 16" EF
10"
M vs. P (factored)
0
40
80
120
160
200
0 10 20 30 40
M , ft-kip / lin. Ft.
P ,
kip
/ lin
. Ft.
H=48 in. H=80 in. H=96 in. H=120 in. H=136 in. H=152 in.
HEIGHT OF WALL
NOTE: FIG. B-6.2.9 Vertical reinforcement should be covered by 1 ½” thick concrete.
Design Guide 45
Armopanel™ Concrete Wall System
Concrete Strength = 3,500 psiSteel Strength = 60,000 psi
Clear concrete cover = 1 1/2"
40 64 88 112 127 141 149 154
1722,527,521,519,516,514
12,8
1722,527,521,617,814,512,4
1722,521,518,514,811,7
1621
17,214,310,6
Loads are given per liner foot. Fig. B-6.2.10
D12 @ 8"
#5 @ 16"
#5 @ 16"
D12 @ 8"
D12 @ 8"
#5 @ 16"
D12 @ 8"
#5 @ 16"
6
Wall Height per Story (ft)
Design Required
Design Required
8
10
12
Design Required
Design Required
Supplementary table to 10" Concrete Wall Interaction Diagram
Reinforcing steel must be placed on the each side of the wall.
M, kip·ft
P , kip
Minimum Vertical Reinforcement Required
REBAR
1000[39.4"]
200[8"]4
0
[1 1
2"]
40
[1 1
2"]
40
[1 1
2"]
40
[1 1
2"]
400[16"]
250
[10"]
250
[10"]
For Horizontal Reinforcement – Refer to Min. Reinforcement Requirements, of ACI 318-99
46 Design Guide
Armopanel™ Concrete Wall System
k (effective length factor) =1 f'c = 25 Mpa fy = 400 Mpa
VERTICAL REINFORCEMENT: 15M @ 400 mm EF ( 10M @ 200 mm EF )THICKNESS OF CONCRETECORE
FACTORED SHEAR CAPACITY V (factored) 16.22, tn /m ( 162.2 kN /m )
Armopanel™ Concrete Wall. Interaction Diagram
250 mmFLEXURE AND AXIAL FACTORED LOAD STRENGTH IN VERTICAL DIRECTION per
linear meter
FLEXURE FACTORED LOAD STRENGTH IN HORIZONTAL 1.75, tn-m /m (17.5 kN·m /m )DIRECTION per linear meter
M vs. P (facotred)
0
40
80
120
160
200
240
280
0 5 10 15M, tn-m /m
P, t
n /m
H=122cm H=203cm H=244cm H=305cm H=345cm H=386cm
( M, kN·m /m ) (50) (100) (150)
HEIGHT OF WALL
(2800)
(2400)
(2000)
(1600)
(1200)
(800)
(400)
( P, kN /m )
NOTE: FIG. B-6.2.11Vertical reinforcement should be covered by 40 mm thick concrete
Design Guide 47
Armopanel™ Concrete Wall System
Concrete Strength = 25 MPa Steel Strength = 400 MPa
Clear concrete cover = 40 mm.
560 960 1280 1600 1890 210 222 22975 100 120 100 81 70 61 58 75 100 114 94 76 65 56 75 100 100 82 65 53 72 95 80 63 48
Loads are given per liner meter FIG. B-2.12. For Horizontal Reinforcement – Refer to Min. Reinforcement Requirements, of CSA A23.3-94 .
2.44
M, kN·m
15M@400
15M@400
D12@200
P , kN
2.03
Supplementary table to 250 mm Concrete Wall Interaction Diagram
Minimum Vertical Reinforcement Required
Reinforcing steel must be placed on the each side of the wall.
Design Required
Design Required
Wall
Height per Story (m.)
D12@200
3.05
3.86
D12@200
15M@400
D12@200
15M@400
Design Required
Design Required
REBAR
1000[39.4"]
200[8"]4
0
[1 1
2"]
40
[1 1
2"]
40
[1 1
2"]
40
[1 1
2"]
400[16"]
250
[10"]
250
[10"]
48 Design Guide
Armopanel™ Concrete Wall System
k (effective length factor) =1 f'c=3,550 psi fy=60,000 psi
VERTICAL REINFORCEMENT: # 5 @ 16" EFTHICKNESS OF CONCRETECORE
SHEAR CAPACITY V (factored) 13.76 , kips / lin. Ft.NOTE: FIG. B-2.13Vertical reinfircement should be covered by 1 1/2" thick concrete
Armopanel™ Concrete Wall. Interaction Diagram
FLEXURE AND AXIAL STRENGTH IN VERTICAL DIRECTION per linear foot
12"
FLEXURE FACTORED LOAD STRENGTH IN HORIZONTAL DIRECTION per linear foot (factored) 4.90 , ft-kip / lin. Ft.
M vs. P (factored)
0
40
80
120
160
200
240
0 10 20 30 40 50
M , ft-kip / lin. Ft.
P ,
kip
/ lin
. Ft.
H=48 in. H=80 in. H=96 in. H=120 in. H=136 in. H=152 in.
HEIGHT OF WALL
Design Guide 49
Armopanel™ Concrete Wall System
Concrete Strength = 3,500 psiSteel Strength = 60,000 psi
Clear concrete cover = 1 1/2"
40 96 120 144 166 177 184 188
2136
41,834262320
18,8
2136
39,232
24,521
18,4
2136
35,22821
17,7
213529
22,516,6
Loads are given per liner foot. FIG. B-2.14
D12 @ 8"
#5 @ 16"
D12 @ 8"
Supplementary table to 12" Concrete Wall Interaction Diagram
Reinforcing steel must be placed on the each side of the wall.
M, kip·ft
P , kip
Minimum Vertical Reinforcemnt Required
Design Required
8
10
12
Design Required
Design Required
#5 @ 16"
D12 @ 8"
#5 @ 16"
6
Wall Height per Story (ft)
Design Required#5 @ 16"
D12 @ 8"
REBAR
1000[39.4"]
40
[1 1
2"]
40
[1 1
2"] 400
[16"]
200[8"]
40
[1 1
2"]
40
[1 1
2"]
300
[12"]
300
[12"]
For Horizontal Reinforcement – Refer to Min. Reinforcement Requirements, of ACI 318-99
50 Design Guide
Armopanel™ Concrete Wall System
k (effective length factor) =1 f' c = 25 MPa fy = 400 MPa
VERTICAL REINFORCEMENT: 15M @ 400 mm EF (10M @ 200 mm EF )THICKNESS OF CONCRETECORE
FACTORED SHEAR CAPACITY V (factored) 20,48, tn /m ( 204.8 kN /m )
Armopanel™ Concrete Wall. Interaction Diagram
300 mmFLEXURE AND AXIAL FACTORED LOAD STRENGTH IN VERTICAL DIRECTION per linear meter
FLEXURE FACTORED LOAD STRENGTH IN HORIZONTAL 2,22, tn-m /m ( 22.2 kN·m /m )DIRECTION per linear meter
M vs. P (factored)
0
40
80
120
160
200
240
280
320
0 5 10 15 20 25M, tn-m /mP, t
n / m
H=122cm H=203cm H=244cm H=305cm H=345cm H=386cm
HEIGHT OF WALL
M, kN·m / m 50 100 150 200 250P, k
N /
m
3200 2800 2400 2000 1600 1200 800 400
NOTE: FIG. B-6.2.15 Vertical reinforcement should be covered by 40 mm thick concrete
Design Guide 51
Armopanel™ Concrete Wall System
Concrete Strength = 25 MPaSteel Strength = 400 MPa
Clear concrete cover = 40 mm.
560 1360 1760 2160 2470 2640 2740 280092
160191151120103908592
160182143111958392
160163125978092
15513310075
Loads are given per liner meter. FIG. B-2.16
Design Required
Design Required
D12@200
Design Required
Supplementary table to 300 mm Concrete Wall Interaction Diagram
Minimum Vertical Reinforcement Required
Reinforcing steel must be placed on the each side of the wall.
2,03
Wall Height
per
P , kN
D12@200
Design Required
M, kN·m
15M@400
3,86
D12@200
15M@400
15M@4002,44
3,05D12@200
15M@400
REBAR
1000[39.4"]
40
[1 1
2"]
40
[1 1
2"] 400
[16"]
200[8"]
40
[1 1
2"]
40
[1 1
2"]
300
[12"]
300
[12"]
For Horizontal Reinforcement – Refer to Min. Reinforcement Requirements, of CSA A23.3-94
52 Design Guide
Armopanel™ Concrete Wall System
k (effective length factor) =1 f'c=3,500 psi fy=60,000 psi
VERTICAL REINFORCEMENT: # 5 @ 16" EFTHICKNESS OF CONCRETECORE
FACTORED SHEAR CAPACITY V (factored) 16.62 , kips / lin. Ft.
FLEXURE FACTORED LOAD STRENGTH IN HORIZONTAL DIRECTION per linear foot 5.93 , ft-kip / lin. Ft.
FLEXURE AND AXIAL FACTORED LOAD STRENGTH IN VERTICAL DIRECTION per linear foot
Armopanel™ Concrete Wall. Interaction Diagram
14"
M vs. P (factored)
0
40
80
120
160
200
240
0 10 20 30 40 50 60 70
M , ft-kip / lin. Ft.
P ,
kip
/ lin
. Ft.
H=48 in. H=80 in. H=96 in. H=120 in. H=136 in. H=152 in.
HEIGHT OF WALL
NOTE: FIG. B-6.2.17 Vertical reinforcement should be covered by 1 ½” thick concrete
Design Guide 53
Armopanel™ Concrete Wall System
Concrete Strength = 3,500 psiSteel Strength = 60,000 psi
Clear concrete cover = 1 1/2"
40 120 144 176 203 213 219 222255057453430
27,8262550
55,8433228
25,62550
51,539,529,524,925504433
23,7Loads are given per liner foot. FIG. B-2.18
6
Wall Height
per
Design Required#5 @ 16"
D12 @ 8"
Design Required
8
10
12
Design Required
Design Required
#5 @ 16"
D12 @ 8"
#5 @ 16"
D12 @ 8"
#5 @ 16"
D12 @ 8"
Supplementary table to 14" Concrete Wall Interaction Diagram
Reinforcing steel must be placed on the each side of the wall.
M, kip·ft
P , kip
Minimum Vertical Reinfocement Required
1000[39.4"]
40
[1 1
2"]
40
[1 1
2"]
40
[1 1
2"]
40
[1 1
2"] REBAR
400[16"]
200[8"]
350
[12"]
350
[12"]
For Horizontal Reinforcement – Refer to Min. Reinforcement Requirements, of ACI 318-99
54 Design Guide
Armopanel™ Concrete Wall System
Vertical reinforcement should be covered by 40 mm thick concrete
k (effective length factor) =1 f'c = 25 MPa fy = 400 Mpa
VERTICAL REINFORCEMENT 15M @ 400 mm EF ( 10M @ 200 mm EF )THICKNESS OF CONCRETECORE
FACTORED SHEAR CAPACITY V (factored) 24,73 tn /m ( 247.3 kN /m )NOTE: FIG. B-2-19
FLEXURE FACTORED LOAD STRENGTH IN HORIZONTAL 2,69 tn-m /m ( 26.9 kN·m /m )DIRECTION per linear meter
Armopanel™ Concrete Wall. Interaction Diagram
350 mmFLEXURE AND AXIAL FACTORED LOAD STRENGTH IN VERTICAL DIRECTION per linear
meter
M vs. P (factored)
0
40
80
120
160
200
240
280
320
360
0 5 10 15 20 25 30M, tn-m /m
P, t
n / m
H=122cm H=203cm H=244cm H=305cm H=345cm H=386cm HEIGHT OF WALL
( M, kN·m /m) 50 100 150 200 250 300
P, k
N /
m
3600 3200 2800 2400 2000 1600 1200 800 400
Design Guide 55
Armopanel™ Concrete Wall System
Concrete Strength = 25 MPaSteel Strength = 400 MPa
Clear concrete cover = 40 mm.
560 1840 2160 2560 3020 3170 3260 3310110230262213152134122117110230251204145127116110230232185130113110233200155107
Loads are given per liner meter. FIG. B-2.20
3,86
D12@200
15M@400
15M@4002,44
3,05D12@200
15M@400
2,03
Wall Height
per
P , kN
D12@200
Design Required
M, kN·m
15M@400
Supplementary table to 350 mm Concrete Wall Interaction Diagram
Minimum Vertical Reinforcement Required
Reinforcing steel must be placed on the each side of the wall.
Design Required
Design Required
D12@200
Design Required
1000[39.4"]
40
[1 1
2"]
40
[1 1
2"]
40
[1 1
2"]
40
[1 1
2"] REBAR
400[16"]
200[8"]
350
[12"]
350
[12"]
For Horizontal Reinforcement – Refer to Min. Reinforcement Requirements, of CSA A23.3-94