DECEMBER 2012
Elevator QEI / Maintenance
Performance Report
LENOX PLACE APARTMENTS
701 WEST SUPERIOR STREET
DULUTH, MN 55802
PASSENGER ELEVATORS 1 AND 2
FOR: BIGOS MANAGEMENT, INC.
8325 WAYZATA BLVD, SUITE 200
GOLDEN VALLEY, MN 55426
BY: ELEVATOR CONSULTING SERVICES, INC.
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 2 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
KEY
UNSAT Unsatisfactory NW Not Working
NC Not Checked NA Not Applicable
OK Satisfactory NI Needs Improvement
INDUSTRY STANDARDS
Rated Speed: 125 f. p.m. Limits 115-135 (+/- 10%)
Performance: 16.0 sec. Doors start to close, doors 3/4 open on next floor
Door Open: 2. 8 sec. Doors start to open until fully open.
Door Close: 3. 4 sec. Doors start to close until fully closed.
Long Dwell: 5 - 8 sec. Time doors are fully open until doors start to
close, in response to a corridor call.
Short Dwell: 3 - 5 sec. Time doors are fully open until doors start to
close, in response to a car call.
Dwell/Int.: 1 sec. Time allowed for second passenger to exit the car,
prior to the doors starting to close.
Nudging: 20 sec. Time allowed for the photo eye to be interrupted
prior to door closing at reduced speed.
Door Pressure: 30# The force necessary to prevent closing of the doors
shall not be more than 30 pounds.
ITEMS IN RED ARE THE RESPONSIBILITY OF THE ELEVATOR CONTRACTOR
ITEMS IN BLUE ARE THE RESPONSIBILITY OF THE BUILDING OWNER
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 3 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Equipment Inventory
Control Type: DUPLEX SELECTIVE COLLECTIVE
Contract Speed: 200 FPM
Machine Type: WESTINGHOUSE GEARED 28 OVERHEAD
Door Equipment: WESTINGHOUSE SINGLE SLIDE OPENING
WESTINGHOUSE E2 OPERATOR
Door Size/Type: 42” WIDE X 84” HIGH
Number of Openings: FOURTEEN (14) FRONT IN LINE ONLY
Travel: 16’3” OH
#2 – 13 FLOOR TO FLOOR 8’6”
Floors Served: G, *1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13
City/State Number: ELEVATOR 1 – NONE (STATE ELECTRICAL STICKER 1-24-80)
MN ELEVATOR 2 – NONE (STATE ELECTRICAL STICKER 1-24-80)
Capacity: 2500 LBS
Fire Service Log: NI
EXISTS BUT THERE ARE NO ENTRIES
Maintenance Log: OK
Oil Monitoring Log: N/A
MSDS Documentation: NI
NONE
Inspector’s Key Box: NI
Inspector’s Keys: NI
Service Vendors: SEC
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 4 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
PERFORMANCE
ELEVATOR 1 2 Speed Up: 180 FPM 180 FPM
Speed Down: 180 FPM 180 FPM
Perform Up: 18.5 SEC 20.1 SEC
Perform Down: 19.0 SEC 21.4 SEC
Door Open: 4.0 SEC 3.9 SEC
Door Close: 5.6 SEC 5.7 SEC
Car Call Dwell: 7.5 SEC 7.5 SEC
Hall Call Dwell 7.5 SEC 7.5 SEC
Nudging: 80 SEC 80 SEC
Door Torque: 25 LBS 30 LBS
*ALL + .2 SEC
Ride Quality
Ride: GOOD OK
Deceleration Up: OK OK
Deceleration Down: OK OK
Noise: OK OK
Acceleration Up: OK OK
Acceleration Down: OK OK
Leveling: OK OK
Stop: OK OK
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 5 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Equipment Room
Access: OK
Headroom: OK
Enclosure: OK
Lighting: NI
NEEDS ADDITIONAL LIGHTS IN FRONT OF CONTROLLER
Cleanliness: OK
Air Circulation, Ventilation: NI
POOR
NEEDS AC
Pipes, Ducts, Non Elevator: NONE
Parts: MINOR PARTS ON SITE
LOCKED UP
GFIC Receptacle: NI
EXISTING RECEPTACLES NEED UPGRADE
Fire Extinguisher: NI
06/2011
Guarding: NI
NEED CABLE GUARDS
Self-Closing, Locking Labeled Door: OK
Numbering of units: OK
Sprinkler in room: NO
Lockable, fused disconnect: OK
110 Volt Disconnect: YES
ONE FOR BOTH CARS
Earth Ground: NO
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 6 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Equipment Room Continued
Shunt Trip Protected: N/A
Shunt Trip Monitored: N/A
Signage on door: OK
Smoke Detector: NC
Emergency Evacuation Guides: NC
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 7 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Control Panel
ELEVATOR 1 2 Type of Control: 2C-2BC-ERL 2C-2BC-ERL
RELAY W-ERL RELAY W-ERL
Manufacturer: WESTINGHOUSE WESTINGHOUSE
Installation Date: 1980 1980
Installation Code: 1977 1977
Controller Data Tag: NI NI
Cleanliness: FAIR FAIR
Identification: OK OK
GO-18248 GO-18248
Software Version: N/A N/A
Grounded: YES YES
U. L. /CSA Label: NO NO
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 8 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Components
ELEVATOR 1 2 Relays: OK OK
(60 RELAY)
Enclosed / Open Style: OPEN OPEN
Contacts: OK OK
Resistors: OK OK
P.C. Boards/Timers: OK OK
Capacitors: OK OK
Wiring: OK OK
Performance: OK OK
Camera Wire: NO NO
Telephone: OK OK
Phone Number: N/A N/A
Programmed Site: SEC SEC
Starts: N/A
Main Relay
Size: 2
Manufacturer: WESTINGHOUSE
Contacts: OK
Wiring: OK
Mounting: OK
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 9 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
MG SET
ELEVATOR 1 2 Type: WESTINGHOUSE LIFELINE WESTINGHOUSE LIFELINE
Cleanliness: OK OK
Lubrication: OK OK
Bearings: OK OK
Isolation: OK OK
Noise: OK OK
Grounding: OK OK
Arcing: NO NO
Brushes: OK OK
Brush Rigging: CHECK CHECK
DC End
KW: 7.5 7.5
RPM: 1750 1750
Frame: 284T 284T
AMPS: 22.5 / 45 19.3 / 38.6
Line Voltage: 230 230
AC End
AC END / HP: 15 15
AC AMPS: 32.5 32.5
Frame: 286 286A
Volts: 400 / 200 230
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 10 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Machine
ELEVATOR 1 2 Type: GEARED – 28 GEARED – 28
Cleanliness: OK OK
Leaks: YES MINOR ONLY
LEAKING
OUT ONTO FLOOR
Noise: OK OK
Sheave: OK OK
Spider Shaft Bearings: OK OK
Worm Shaft Seal: NI OK
LEAKING
PAN ¾ FULL
Thrust Bearing: OK OK
Gear Condition: FAIR FAIR
Motor
Type: SK/A SK/A
Horsepower: 15 15
AMPS: 55 55
RPM: 1660/1800 1660/1800
Frame: 286-A1 286-A1
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 11 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Rope Gripper / Ascending Protection
Manufacturer: N/A
Model: N/A
Mounting: N/A
Jaws: N/A
Tagged: N/A
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 12 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Brake
ELEVATOR 1 2 Type: DRUM DRUM
Cleanliness: OK OK
Lubrication: OK OK
Contacts: OK OK
Sleeve: OK OK
Core: OK OK
VISUAL INSPECTIO ONLY-BOTH
Lining (Visual Only): CHECK CHECK
Grommets: BOTH APPEAR TO BE OK-VISUAL CHECK ONLY
Pins: OK OK
Drum: OK OK
Tagged: NI NI
Tape
Tape Guides: N/A
Magnets: N/A
Car top box: N/A
Sensors: N/A
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 13 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
GOVERNOR
ELEVATOR 1 2 Type: WH B5 WH B5
Manufacturer: WESTINGHOUSE WESTINGHOUSE
Cleanliness: OK OK
Lubrication: OK OK
Seals: OK OK
Bearings: OK OK
Jaws: OK OK
Gears: N/A N/A
Collars: OK OK
Switches: OK OK
Switch Trip Speed: 277 FPM 277 FPM
Data Plate/Tripping Speed: 277 FPM 277 FPM
Over Speed: 249 FPM 249 FPM
Pull Through: 400 LBS 400 LBS
Five Year Test: OK OK
Tagged: 01/2009 01/2009
Annual No Load Test: OK OK
Tagged: 09/13/2012 09/13/2012
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 14 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Selector / Encoder
ELEVATOR 1 2 Cleanliness: OK OK
Wiring: OK OK
Tape Guides: OK OK
Tape: N/A N/A
Contacts: OK OK
Relays: OK OK
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 15 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Hoistway
ELEVATOR 1 2 Deflector Sheaves
Cleanliness: OK OK
Lubrication: OK OK
Bearings: OK OK
Grooves: OK OK
Noise: OK OK
Limit Switches
Noise, Rollers: OK OK
Operation: OK OK
Type: WEST STND WEST STND
Rails
Cleanliness: OK OK
Type: T-16 T-16
Lubrication: N/A N/A
Fastening: OK OK
Solid Shoes / Roller Guide: ROLLER GUIDE ROLLER GUIDE
Penetrations: NUMEROUS NUMEROUS
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 16 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Cable Condition
ELEVATOR 1 2 Hoist: 5-1/2” 5-1/2”
Roping: 1:1 1:1
Installation Date: 06/2011 06/2011
Cable Tag Present: YES YES
Governor: 3/8 3/8
Compensating: NONE NONE
Shackle Type Car: WEDGE WEDGE
Shackle Type Counter Weight: WEDGE WEDGE
Cable Ties – Car: OK OK
- Counter weight: OK OK
Traveling Cables
Suspension: OK OK
Type: CLOTH CLOTH
Kellums Grips: OK OK
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 17 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Hoistway Equipment
ELEVATOR 1 2 Car Top
Cleanliness: OK OK
Maintenance Station: OK OK
Stop Switch: OK OK
Data Plate: YES YES
Light: OK OK
Light Guard: OK OK
Solid Shoes / Roller Guides: ROLLER GUIDES ROLLER GUIDES
GFIC Receptacles: NI NI
Escape Hatch Locked: YES YES
Windows in Hoistway: NONE NONE
Multiple Hoistways: N/A N/A
Stenciled: YES YES
Car Top Railing: NO NO
Counterweight
Cleanliness: OK OK
Noise: OK OK
Slide Guides: OK OK
Roller Guides: OK OK
Weight Containment: OK OK
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 18 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Hoistway Venting/ Hoistway
Existing: YES (NORTH)
REAR HOISTWAY OF ELEV 1
Motorized: YES
Key Switch: UNKNOWN
Safety Bars: NO
Size (3%): OK
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 19 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Door Operator
ELEVATOR 1 2 Type: E2 E2
Cleanliness: OK OK
Door Protection: SAFETY EDGE/ SAFETY EDGE/
PHOTO EYE PHOTO EYE
9 ½ & 39 9 ½ & 39
Lubrication: OK OK
Relating Cables: N/A N/A
Sheaves: OK OK
Belts: OK OK
Chains: N/A N/A
Door Arms: N/A N/A
Bearings: OK OK
Car Sill: OK OK
Hangers: OK OK
Noise: OK OK
Tracks: OK OK
Upthrusts: OK OK
Restrictor Device: OK OK
Gibs: OK OK
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 20 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Car Enclosure
ELEVATOR 1 2 Ventilation: OK OK
FAN
Walls: OK OK
STAND OFF PANELS – 3 WALLS
FRONT – SS #4 FRONT – SS #4
Returns: STAINLESS STEEL STAINLESS STEEL
Transom: STAINLESS STEEL STAINLESS STEEL
Car Lighting: OK OK
FLORESCENT FLORESCENT
Ceiling: OK OK
SUSPENDED WITH MILK PLASTIC & EGG CRATE
Position Indicators: OK OK
PER LINE / ANALOG STYLE IN TRANSOM
Handrails/Bumpers: OK OK
1 REAR WALL AT 31”
2” TO TOP, BARSTOCK STAINLESS
Flooring: OK OK
CARPET CARPET
Car Doors: OK OK
STAINLESS STEEL STAINLESS STEEL
Sills: OK OK
ALUMINUM ALUMINUM
Certificate Frame: NO NO
Car Riding Lantern: NC NC
Camera: N/A N/A
Card Reader: N/A N/A
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 21 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Entrance Equipment
ELEVATOR 1 2 Cleanliness: OK OK
Lubrication: OK OK
Tracks: OK OK
(Intragal / 3 ¾ pocket)
Hangers: NI OK
FLOORS 1 AND 7
Relating Cables: N/A N/A
Gibs: OK OK
Interlocks: OK OK
Clutch Release Rollers: NC NC
Clutch Release Assemblies: NC NC
Noise: NI OK
Upthrust: OK OK
Closers: ADJUST FLOORS: ADJUST FLOORS:
*1, 6, 7 AND 10 *1 & 9
Braille: NI NI
ONE SIDE ONLY AT 60” ONE SIDE ONLY AT 60”
Sills: OK OK
Star of Life: NO NO
Elevator ID Tactile: NO NO
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 22 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Emergency Fire Box
Main Egress Landing: 1st FLOOR
Existing in lobby: YES
Machine room key: YES
Phase I, II keys: YES
Lunar Key: YES
Keys Tagged: YES
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 23 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Fixtures
ELEVATOR 1 2 Car Operating Panel
Type: WESTINGHOUSE WESTINGHOUSE
Style: WESTINGHOUSE WESTINGHOUSE
Condition: OK OK
Illumination OK OK
Height compliance: NI NI
ALARM BUTTON – TOO HIGH
CURRENT-54”/CODE-35”
Braille Identification: YES YES
EXCEPT DOOR OPEN EXCEPT DOOR OPEN
Buttons: OK OK
Phone: 218-722-6416 218-722-5292
A. D. A. A. D. A.
COMPLIANT COMPLIANT
Phone Monitored: YES YES
Call Back Number: 218-722-6416 218-722-5292
Alarm Button: TOO HIGH TOO HIGH
PER CODE PER CODE
53.5” TO CENTER
Stop Switch: KEYED KEYED
Directional Lanterns: OK OK
Emergency Light: OK OK
Capacity Plate / Engraved: OK OK
Fire Hat: NO NO
Certificate Frame: NO NO
Certificate: NO NO
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 24 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
ELEVATOR 1 2
Service Cabinet
Light Switch: OK OK
Fan Switch: OK OK
Independent Service: OK OK
Access Enable: YES YES
Emergency light test button: NO NO
Inspection: OK OK
Stop Switch: NO NO
GFI Outlet: NO NO
Fire Service Cabinet
Fire Fighters Instruction: NONE NONE
Phase II key switch: YES YES
OFF / ON OFF / ON
Call Cancel Button: NO NO
Stop Switch: KEYED KEYED
Fire Hat: NO NO
Phone Jacks: NO NO
Door Open Front: YES YES
Door Open Rear: N/A N/A
Door Close Front: NO NO
Door Close Rear: N/A N/A
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 25 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Hall Buttons
Type: WESTINGHOUSE
Condition: OK
Buttons: OK
Illuminated: YES
Height: 37” TO CENTER
CODE IS 42 INCHES TO CENTER
Mechanical: OK
Lanterns: NONE
CAR ONLY
Fire Signage: NON APPENDIX H SIGN
Phase I Key Switch: YES
BYPASS / OFF / ON
Phase I Instructions: NO
Fire Hat/Indicator Light: NO
Vent Key: NC
Vent Light: NC
Main Lobby Panel: OK
Concealed Riser: ONE
Card Reader(s): N/A
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 26 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Main Lobby Panel
Existing: OK
Location: 1ST
FLOOR
Position Indicators: YES
Emergency Power Key Switch: NO
Emergency Power Independent Light: NO
Fire Service Key Switch: YES
Selection Switch: N/A
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 27 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Pit Equipment
ELEVATOR 1 2 Bottom Access: YES YES
Run by: OK OK
Cleanliness: OK OK
Comp guides: N/A N/A
Car Buffer/Spring: OK OK
Counter Weight Buffer/Spring: OK OK
Counter Weight Guard/Protection: OK OK
Governor Tension Sheave: OK OK
Light Switch: OK OK
Lights Fixtures: OK OK
Light Guards: OK OK
Stop Switch: OK OK
Ladder: NI NI
30” TO TOP RUNG 30” TO TOP RUNG
TOO LOW TOO LOW
GFIC Receptacle: NI NI
Sump Hole: YES YES
Sump Hole Grated/Protected: YES YES
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 28 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Bottom of Car
ELEVATOR 1 2 Cleanliness: NI NI
Safeties: (Visual Only) OK OK
Light Fixture: OK OK
Light Guard: OK OK
Solid Shoes / Roller Guides: ROLLER GUIDES ROLLER GUIDES
Toe Guard: OK OK
Traveling Cable Suspension: OK OK
GFI Receptacles: NI NI
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 29 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
LENOX PLACE
PASSENGER ELEVATORS 1 AND 2
MAINTENANCE CORRECTIVE ITEMS
The following minimum items need corrective action taken:
5 YEAR TESTS 01-2009 ANLT-ELEVATOR 1: 09/13/2012
ELEVATOR 2: 09/13/2012
GENERAL
NONE
ELEVATOR ONE
1. Adjust car door running clearance. It is too close and rubbing toward top by the directional
lantern.
Completion Date____________ Initial_____
2. Check noisy door operating belt. Lube belt, adjust belt, or replace. 4TH
REQUEST
Completion Date____________ Initial_____
3. Adjust hoistway door closures.
Completion Date____________ Initial_____
4. Clean pit of debris.
Completion Date____________ Initial_____
5. Adjust door hanger rollers floor 1 it is squeaking loudly.
Completion Date____________ Initial_____
ELEVATOR TWO
1. Check door operator. Noisy belts?
Completion Date____________ Initial_____
2. Adjust hoistway door closures.
Completion Date____________ Initial_____
3. Adjust car door running closures, rubbing against return jamb.
Completion Date____________ Initial_____
4. Clean pit of debris.
Completion Date____________ Initial_____
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 30 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
LENOX PLACE
PASSENGER ELEVATORS 1 AND 2
RECOMMENDATIONS
The following can be mandated in a 30 day order by prevailing code authority:
1. Replace controls for code compliance to the 1987 version of fire fighters service. Regard by
December 29th
, 2014. All other recommendations would be included and mandated as a result
of this improvement. Budget $490,000
2. Upgrade the existing receptacles in the machine room, pit area, car bottom and car top with a
GFIC receptacle. Budget $80.00 per receptacle including parts and labor. NEC 620-85,
Minnesota State Building Code Chapter 1307 / Conditions for Continued Operations for
Existing Elevators
3. Upgrade and improve the lighting in the machine room to comply with the required foot
candles by code. Requires additional florescent fixtures to meet the 10 foot candles. ASME
17.1 Rule 101.5a, Minnesota State Building Code Chapter 1307
4. Install new pit ladders top rung needs to be at 48” currently it is at 30”.
5. A. D. A. Recommendations.
6. Install Phase I Fire Fighters Service instruction signage at the main floor key switch.
ASME 17.1 Rule 211, Minnesota State Building Code Chapter 1307, Phase II signage in
each elevator.
7. ASME 17.3 Report, see detail report.
8. Upgrade the existing safety edge with an infra red scanner per code.
9. Provide and install a Group II security key box in the machine room. Includes providing a
key for all access items for the elevator. Includes access, lunar key, fire service, fan, light,
inspection, etc. Properly label each. One required per machine room per facility.
(Inspector’s key box).
10. Machine room Climate Control ASME 17.3 Rule 2.2.4 Temperature Control. Machine
rooms shall be provided with natural or mechanical means to avoid overheating of the
electrical equipment and to ensure safe and normal operation of the elevator.
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 31 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
Provide a dedicated air conditioning unit to maintain the machine room temperature between
55 and 90 degrees at 85 per cent relative humidity. Includes all ducting, panning, wiring,
thermostat control.
ITEMS IN BLUE SHOULD RECEIVE A HIGHER CONSIDERATION OF ADOPTION EITHER
FOR RELIABILITY OR LIFE SAFETY.
BIGOS MANAGEMENT INC.
OK- SATISFACTORY 32 LENOX PLACE-ELEVATORS 1 & 2
NI- NEEDS IMPROVEMENT DECEMBER 2012 QEI / MAINTENANCE REVIEW
LENOX PLACE
PASSENGER ELEVATORS 1 AND 2
A. D. A. RECOMMENDATIONS
RULE 4.10.3 HALL CALL BUTTON EXISTING DOES NOT MEET NOMINAL HEIGHT REQUIREMENTS
NEEDS TO BE 42 INCHES TO CENTER / CURRENTLY AT 37 INCHES
BUDGET $ 1,125.00 PER LANDING
RULE 4.10.4 HALL LANTERNS EXISTING DOES NOT MEET REQUIREMENTS
NEEDS TO HAVE 1 UP / 2 DOWN MODULE
BUDGET $ 400.00
RULE 4.10.5 BRAILLE EXISTING DOES NOT MEET REQUIREMENTS
ONLY ON ONE SIDE, CODE REQUIRES BOTH SIDE HAVE THEM
BUDGET $ 150.00
RULE 4.10.6 DOOR PROTECTION & REOPENING EXISTING DOES NOT MEET THE HEIGHT REQUIREMENT
PHOTOS EYES NEED TO BE AT 5 AND 29 INCHES
CURRENTLY ARE AT 9 ½ AND 39 INCHES
RECOMMEND DOOR SCANNER
BUDGET $ 2,150.00 PER UNIT
RULE 4.10.10 FLOOR SURFACE EXISTING DOES MEET REQUIREMENTS
RULE 4.10.11 LIGHT LEVEL IN CAB EXISTING DOES MEET REQUIREMENTS FOR LUMENS
RULE 4.10.12 CAR CONTROLS EXISTING DOES NOT MEET REQUIREMENTS FOR HEIGHT
ALARM BELL NEEDS TO BE AT 35 INCHES TO CENTER
CURRENTLY AT 54 INCHES
BUDGET $ 5,500.00 PER ELEVATOR FOR A NEW COP
RULE 4.10.13 CAR POSITION INDICATORS EXISTING DOES NOT MEET ALL REQUIREMENTS
NEEDS TO HAVE A PASSING FLOOR GONG
BUDGET $ 550.00 PER ELEVATOR