DALLAS VA MEDICAL CENTER
INSTALL EMERGENCY POWER FOR BUILDING 2J
MEDICAL EQUIPMENT
4500 S. LANCASTER RD., DALLAS, TX
VA PROJECT #549-15-509 CANNON DESIGN PROJECT #003640.55
100% CONSTRUCTION DOCUMENTS 09/08/2017
1100 Clark Avenue
St. Louis, Missouri 63102 T: 314.241.6250 F: 314.241.2570
BOSTON NEW YORK BALTIMORE WASHINGTON DC BUFFALO TORONTO MONTREAL PITTSBURGH CHICAGO ST. LOUIS VANCOUVER SAN FRANCISCO LOS ANGELES PHOENIX MUMBAI ABU DHABI
Consultants:
12
/2/2
016
3:0
1:1
9 P
M
MOTOR CONNECTION. REFER TO EQUIPMENT CONNECTION MOTOR CONTROLLER SCHEDULE FORSPECIFIC REQUIREMENTS
WIRING TERMINATIONS
## CIRCUIT NUMBER (AND PANELBOARD IF SPECIFICALLY DESIGNATED)
POWER BRANCH CIRCUITS
GROUNDING AND BONDINGG GROUND/ELECTRODE CONDUCTOR
GROUND ROD
GROUND TEST STATION
MECHANICAL CONNECTION
GROUND CONNECTION (MOLDED FUSION WELD OR IRREVERSIBLE)
GROUND EQUIP ROOM GROUND TERMINAL BAR OF LENGTH INDICATED, 1'-6" AFF
GROUND
RACEWAY AND PATHWAYCONDUIT TURNED UP
CONDUIT TURNED DOWN
CAPPED CONDUIT
CONDUIT STUBBED AND BUSHED INTO ACCESSIBLE CEILING CAVITY
SERVICE WEATHERHEAD
SINGLE CHANNEL SURFACE RACEWAY
DUAL CHANNEL SURFACE RACEWAY
TRIPLE CHANNEL SURFACE RACEWAY
RACEWAY ROUTED DOWN FROM CEILING TO HORIZONTAL
RACEWAY ROUTED UP FROM FLOOR TO HORIZONTAL
CABLE TRAY, HUNG ABOVE CEILING OR AS NOTED
WIRE BASKET, HUNG ABOVE CEILING OR AS NOTED
MULTI-OUTLET ASSEMBLY, 6" ABOVE COUNTER BACKSPLASH OR AS NOTED
WALL DUCTWD
BOXES AND CABINETSJUNCTION BOXJ
PULL BOXPB
CABINET, TOP OF TRIM 6'-2" AFF
UNDERGROUND CONSTRUCTION
TM TRANSFORMER MANHOLE OR VAULT
H HANDHOLE
M MANHOLE
DBC* CABLE (DBC-DIRECT BURIED CABLE, DB-DUCT BANK) (* = NUMBER)
MULTI-SERVICE BOXES AND RACEWAYSCEILING CONCEALED, REGRESSED BACKBOXCCR*
FLOOR BOX, EXPOSED, WITH PROVISIONS FOR WHIPFEW*
FLOOR BOX, EXPOSED, FLUSHFEF*
FLOOR BOX, EXPOSED, WITH TOMBSTONE DEVICEFET*
FLOOR BOX, CONCEALED, WITH REGRESSED DEVICESFCR*
POKE-THRU ASSEMBLY, EXPOSED, WITH PROVISIONS FOR WHIPPEW*
POKE-THRU ASSEMBLY, EXPOSED, FLUSHPEF*
POKE-THRU ASSEMBLY, EXPOSED, WITH TOMBSTONE DEVICEPET*
POKE-THRU ASSEMBLY, CONCEALED, WITH REGRESSED DEVICESPCR*
RAISED FLOOR BOX, CONCEALED, WITH REGRESSED DEVICESRCR*
RAISED FLOOR BOX, EXPOSED, WITH PROVISIONS FOR WHIPREW*
STAGE BOX, CONCEALED, WITH REGRESSED DEVICESSCR*
TABLE BOX, EXPOSED, FLUSHTEF*
TABLE BOX, EXPOSED, WITH TOMBSTONE DEVICETET*
TABLE BOX, CONCEALED, WITH REGRESSED DEVICESTCR*
UNDER FLOOR DUCT, EXPOSED, FLUSHUEF*
UNDER FLOOR DUCT, EXPOSED, WITH TOMBSTONE DEVICEUET*
WALL BOX, EXPOSED, WITH PROVISIONS FOR WHIPWEW*
WALL BOX, CONCEALED, WITH REGRESSED DEVICESWCR*
IDENTIFICATION CHART
ACCESSC - CONCEALEDE - EXPOSED
LOCATIONF - FLOORP - POKE-THRUR - RAISED FLOORS - STAGET - TABLEU - UNDER FLOOR DUCTW - WALL
SERVICE COVER/DEVICE FITTINGB - BLANKF - FLUSHR - REGRESSEDS - SEMI FLUSHT - TOMBSTONEW - WHIP
SEQUENTIAL NUMBER
_ _ _ _
REFER TO MULTI-SERVICE BOX SCHEDULE FOR ADDITIONAL INFORMATION REGARDING THEFOLLOWING BOXES.
INDOOR SERVICE POLEISP
INDOOR MULTI-SERVICE COLUMNISC
ELECTRIC POWER MANAGMENT SYSTEMLOAD/ EQUIPMENT MONITOR UNITM11
INTEGRAL BREAKER MONITOR UNITM12
INDIVIDUAL LOAD DISPLAY UNITM21
ASSEMBLY DISPLAY UNITM22
COMPUTER WORKSTATION, DESK OR SHELF MOUNTEDMPC
PRINTER, DESK OR SHELF MOUNTEDMPR
NOTE: SPEC REFERENCES ARE GENERAL AND MAY NOT BE SPECIFIC
DIVISION 26: LEGEND
POWER DISTRIBUTION
METER SOCKETM
PROTECTIVE RELAY (*INDICATES ANSI FUNCTION, NUMBER INDICATES QUANTITY)*
AMMETERAM
VOLTMETERVM
AMMETER SWITCHAM
VOLTMETER SWITCHVM
DIGITAL METERING MONITORDM
MEDIUM VOLTAGE DRAWOUT POWER CIRCUIT BREAKER
LOW VOLTAGE INTERRUPTER SWITCH
MEDIUM VOLTAGE INTERRUPTER SWITCH
POTENTIAL TRANSFORMER (NUMBER INDICATES QUANTITY)
CURRENT TRANSFORMER (NUMBER INDICATES QUANTITY)
PROGRAMMABLE LOGIC CONTROLLERPLC
LIGHTNING ARRESTOR
SWITCHGEAR, SWITCHBOARD, INTEGRATED POWER CENTER OR MOTOR CONTROL CENTER, DASHEDLINES INDICATE FUTURE SECTIONS, DOUBLE LINE INDICATES FRONT
NETWORK PROTECTOR
CABLE LUGS
PROVISIONS FOR FUTURE EXPANSIONS
HARMONIC FILTERHF
HC HARMONIC CONDITIONING TRANSFORMER (SINGLE LINE DENOTATION)
HFT HARMONIC FILTER TRANSFORMER (SINGLE LINE DENOTATION)
TRANSFORMER (SINGLE LINE DENOTATION)
TRANSFORMERST TRANSFORMER (PLAN DENOTATION)
3-PHASE, 3-WIRE DELTA CONNECTION
3-PHASE WYE, NEUTRAL UNGROUNDED CONNECTION
WYE CONNECTION
PANELBOARDS
SHADING INDICATES BRANCH TYPE
TEXT INDICATES LUG / BREAKER TYPE
PANELBOARD (SINGLE LINE DENOTATION)
ELECTRONIC PANELBOARD
NORMAL BRANCH PANELBOARD
(LIFE SAFETY / NEC 517) - (EMERGENCY/ NEC 700) BRANCH PANELBOARD
(CRITICAL / NEC 517) - (STANDBY - NEC 701) BRANCH PANELBOARD
(EQUIPMENT / NEC 517) - (OPTIONAL - NEC 702) BRANCH PANEL BOARD
PROTECTIVE DEVICESSEPARATELY ENCLOSED CIRCUIT BREAKER, FLUSH MOUNTED 3'-8" AFFCB
UNFUSED DISCONNECT SWITCH, SURFACE 3'-8" AFF, (5-0" AFF IN EQ ROOMS)
XXAS/XXAF
FUSED DISCONNECT SWITCH, SURFACE MOUNTED 3'-8" AFF, (5'-0" AFF IN EQ ROOMS). FUSEDDISCONNECT SWITCH, "AS" INDICATES AMPERE RATING OF SWITCH AND "AF" INDICATES AMPERERATING OF FUSE.
BOLTED PRESSURE CONTACT SWITCHBPS
XXASXXAT# POLES
CIRCUIT BREAKER (SINGLE LINE DENOTATION)
XXAFFUSE (SINGLE LINE DENOTATION)
LOW VOLTAGE DRAWOUT POWER CIRCUIT BREAKER
KEY INTERLOCK SYSTEM (* INDICATES LINK)K*
MOLDED CASE SWITCHMCS
T FRACTIONAL HORSEPOWER MOTOR CONTROLLER, RECESSED 3'-8" AFF OR ABOVE CEILING (MANUALTHERMAL SWITCH)
MOTOR CONTROLLERS
MOTOR CONTROLLER/DISCONNECT, 3'-8" AFF (5'-0" AFF IN EQ ROOMS)
VARIABLE SPEED DRIVEVSD
ENGINE GENERATOR SETS
XXASXXAT# POLES LSIA LSIG
G
ENGINE- GENERATOR SET (SINGLE LINE DENOTATION)
EGS ALARM ANNUNCIATOR, TOP OF TRIM 6'-2" AFFEAA
TRANSFER SWITCH
TRANSFER SWITCHES
ISOLATION BYPASS TRANSFER SWITCH
CLOSED TRANSITION TRANSFER SWITCH
GENERALNEW EQUIPMENT
EXISTING WORK
DEVICE TO BE REMOVED (DEMO PLANS) UNDERFLOOR CONDUIT (NEW PLANS)
MATCH LINE REFERENCING CONTINUATION ON OTHER DRAWINGS
BRANCH CIRCUIT BOUNDARY
WIRE AND/OR CONDUIT RUN CONTINUED ON REFERENCED DETAIL
DETAIL AND/OR SECTION REFERENCE
FUTURE WORK
'E' SERIES GENERAL NOTES1. FOR EXACT LOCATIONS OF DUCT MOUNTED SMOKE DETECTORS, WATER FLOW SWITCHES ANDTAMPER SWITCHES REFER TO HVAC / FP DRAWINGS.
2. VERIFY EXACT LOCATION OF CONNECTION POINTS PRIOR TO CONNECTION.
3. MOUNTING HEIGHTS ARE TO CENTER OF DEVICE OR EQUIPMENT, UNO.
4. PROVIDE RACEWAY, WIRE AND CABLE, ASSOCIATED FITTINGS AND CONNECTORS, ANDCOMPLETE CONNECTIONS REQUIRED FOR DESIGNATED BRANCH CIRCUITS FROM DEVICE(S) TO FINALOVERCURRENT DEVICE AND TO LOCAL CONTROL DEVICE(S) PER SPECIFICATIONS.
5. MINIMUM BRANCH CIRCUIT WIRE SIZE SHALL BE #12 AWG EXCEPT LIFE SAFETY BRANCH CIRCUITWIRING WHICH SHALL BE MINIMUM #10 AWG. MAINTAIN MAXIMUM BRANCH CIRCUIT CONDUCTORLENGTHS AS PER SPECIFICATIONS AND SCHEDULED ON THIS DRAWING. INCLUDE GROUNDCONDUCTOR DERATINGS.
6. PULL A SEPARATE NEUTRAL CONDUCTOR FROM PANELBOARD FOR EACH BRANCH CIRCUITSERVING NEMA 5 RECEPTACLES WITHIN SIX (6) FEET OF COMPUTER DEVICE JACKS, AND EACHBRANCH CIRCUIT PROTECTED BY A GROUND FAULT CIRCUIT INTERRUPTER. DERATE CONDUCTORSPER NEC ACCORDINGLY.
7. PROVIDE GROUNDING PER NEC. ALSO PROVIDE GREEN GROUND WIRE IN ALL BRANCH ANDFEEDER CIRCUITS SIZED PER NEC.
8. THE SPACE ABOVE THE CEILING IS LIMITED AND THE INSTALLATION OF WORK WILL BE TIGHT. DUETO THIS, IT IS IMPORTANT THAT THE TRADE CONTRACTOR SHALL COORDINATE THE INSTALLATION OFTHEIR WORK (IE: DUCTWORK, TERMINAL UNITS, PIPING, ETC) WITH THE EXISTING CEILING SYSTEMHEIGHT AND CONSTRUCTION, THE STRUCTURAL SYSTEM, THE LIGHTING FIXTURES, THE SPRINKLERHEADS/MAINS, AND THE PLUMBING PIPES. ROUTE DUCTWORK AND PIPING AS HIGH AS POSSIBLE.LOCATE TERMINAL UNITS BETWEEN STRUCTURAL BEAMS AND MAINTAIN PROPER SERVICE ACCESSCLEARANCES.
9. DO NOT INSTALL ANY NEW WORK DIRECTLY ABOVE ANY ELECTRICAL PANELS ANDTRANSFORMERS.
10. CIRCUIT NUMBERS SHOWN FOR EQUIPMENT WIRED TO EXISTING PANELBOARD(S) IS SHOWN FORDESIGN INTENT ONLY AND MAY NOT CORRESPOND TO ACTUAL CIRCUIT BREAKER MOUNTING POSITIONIN THE PANEL. UPDATE THE AS-BUILT DRAWINGS WITH THE ACTUAL CIRCUIT NUMBERS USED TOCORRESPOND TO THE PANEL DIRECTORY.
13. CONFIRM ALL LABELS AND ROOM NUMBERS WITH OWNER PRIOR TO FINALIZING LABELING ANDPROGRAMMING.
14. CONNECT TO EXISTING POWER MONITORING SYSTEM FOR EACH NEW GENERATOR, UPS,SWITCHBOARD, AND PSG SECTION.
ABBREVIATIONSA AMPEREAC ARMOR CLAD CABLEAFCI ARC-FAULT CIRCUIT INTERRUPTINGAFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEAHJ AUTHORITY HAVING JURISDICTIONAHU AIR HANDLING UNITAIC AMPERE INTERRUPTING CAPACITYAL ALUMINUMAM AMMETERANN ANNUNCIATORANSI AMERICAN NATIONAL STANDARDS INSTITUTEATS AUTOMATIC TRANSFER SWITCHAV AUDIO VISUALAWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEMBDF BUILDING DISTRIBUTION FRAMEBFC BELOW FINISHED CEILINGBFG BELOW FINISHED GRADEBKBD BACKBOARDBKR BREAKERBPS BOLTED PRESSURE SWITCH
C CONDUITCAT CATALOGCATV CABLE ANTENNA TELEVISIONCB CIRCUIT BREAKERCCTV CLOSED CIRCUIT TELEVISIONCEC CHICAGO ELECTRICAL CODECKT CIRCUITCLG CEILINGCM CONSTRUCTION MANAGERCO COMPANYCOAX COAXIALCT CURRENT TRANSFORMERCTTS CLOSE TRANSITION TRANSFER SWITCHCU COPPER
DC DIRECT CURRENTDHCP DYNAMIC HOST CONFIGURATION PROTOCOL
DEVICE SUBSCRIPTSII ROMAN NUMERAL INDICATES QUANTITY OF GANGED DEVICES UNDER COMMON FACEPLATEa LOWER CASE LETTER(S) INDICATES MULTI SWITCH CONTROL ARRANGEMENT7 NUMERAL INDICATES BRANCH CIRCUIT NUMBERA WITH AUXILIARY CONTACTSB REMOVE DEVICE AND INSTALL BLANK COVERPLATEBF BLANK FACE GFCIBS ITEM CONTROLLED BY BED STOP RELAYC ITEM INSTALLED FLUSH IN CEILINGC* CONTROL POINT IDENTIFIER (*INDICATES CONTROL NUMBER)D 120 VOLT DISCONNECT SWITCH ARRANGEMENTE EXISTING BACKBOX TO REMAIN AND BE REUSEDEN EXISTING LOCATION NEW DEVICEEO EQUIPMENT SUPPLIED BY OWNEREQ ITEM INSTALLED IN EQUIPMENTER EXISTING TO BE REMOVEDERL EXISTING TO BE RELOCATEDEX EXISTINGFL ITEM INSTALLED FLUSH IN FLOORGFCI GROUND FAULT CIRCUIT INTERRUPTING RECEPTACLEGFI GROUND FAULT CIRCUIT INTERRUPTING BREAKER PROTECTEDGFP FEED THROUGH GROUND FAULT CIRCUIT INTERRUPTING PROTECTEDH HORIZONTALLY MOUNTEDHA HIGH ABUSE COVERPLATEHG HOSPITAL GRADEIG ISOLATED GROUND RECEPTACLEK KEY OPERATEDL LOCATOR STYLE SWITCH OPERATING HANDLELV LOW VOLTAGEM MULLION MOUNTEDM* MONITORING POINT IDENTIFIER (*INDICATES MONITORING POINT)NL NIGHT LIGHT RECEPTACLENLG NIGHT LIGHT GFCI RECEPTACLEP PILOT TYPE SWITCH OPERATING HANDLEPP FOR AUTO DOOR PUSH PLATEQ QUAD (DOUBLE DUPLEX) DEVICES SURFACE MOUNTEDSG SAFETY GROUNDING RECEPTACLESP SURGE PROTECTOR RECEPTACLESW SPLIT WIRED RECEPTACLE FOR REMOTE SWITCHINGTR TAMPER RESISTANTUSB USB PORT CHARGING RECEPTACLEW ITEM INSTALLED 3'-8" AFF OR AS DETAILEDWG WIRE GUARDWP WEATHERPROOFWPS WEATHERPROOF SPRING COVERZ* DEVICE ZONE IDENTIFIER (* INDICATES ZONE NUMBER)
DRAWING NOTES AND DESIGNATIONS
EQUIPMENT DESIGNATIONSEQUIPMENT NAME
TYPE
BRANCH
SEQUENCE NUMBER
NUMBERS IN SEQUENCE - 1,2,3, ETC.
ATSF AUTOMATIC TRANSFER SWITCH, FIRE PUMPATSS AUTOMATIC TRANSFER SWITCH, LIFE SAFETY (NEC 517)ATSC AUTOMATIC TRANSFER SWITCH, CRITICAL (NEC 517)ATSE AUTOMATIC TRANSFER SWITCH, EQUIPMENT (NEC 517)ATSX AUTOMATIC TRANSFER SWITCH, X-RAYATSM AUTOMATIC TRANSFER SWITCH, MIXED EXISTINGATSS AUTOMATIC TRANSFER SWITCH, STANDBY (NEC 701)ATSO AUTOMATIC TRANSFER SWITCH, OPTIONAL (NEC 702)BPS BOLTED PRESSURE SWITCHCB CIRCUIT BREAKERCRT FIRE ALARM CRT ANNUNCIATORDS UNFUSED DISCONNECT SWITCHDT DAY TANKEC ELEVATOR CONTACTORFAP FIRE ALARM ANNUNCIATORFATC FIRE ALARM TERMINAL CABINETFDS FUSED DISCONNECT SWITCHFPU FIELD PROCESSING UNITGC GENERAL PURPOSE CONTACTORIDRS INTEGRATED DATA CENTER RACK SYSTEMIEC INTERCOM EQUIPMENT CABINETIPC INTEGRATED POWER CENTERLC LIGHTING CONTACTORLRC LIGHTING RELAY CABINETLVS LOW VOLTAGE POWER SWITCHGEARMCCE MOTOR CONTROL CONTER, EQUIPMENT (NEC 517)MCCN MOTOR CONTROL CENTER, NORMALMCCO MOTOR CONTROL CENTER, OPTIONAL (NEC 702)MCCS MOTOR CONTROL CENTER, STANDBY (NEC 701)MMC MODULAR METER CENTERMS METER SOCKETMTSS MANUAL TRANSFER SWITCH, STANDBY (NEC 701)MTSO MANUAL TRANSFER SWITCH, OPTIONAL (NEC 702)MVR MEDIUM VOLTAGE REGULATORMVS MEDIUM VOLTAGE SWITCHGEARNEC NURSE CALL EQUIPMENT CABINETPBL PLUG-IN BUSWAY LIGHTINGPBP PLUG-IN BUSWAY POWERPSS PRIMARY SUBSTATIONPSU PATIENT SERVING UNITPSWGR PARALLELING SWITCHGEARRUPS ROTARY HYBRID UNINTERRUPTIBLE POWER SUPPLYSFP SURGICAL FACILITY PANELT TRANSFORMERTBTP TELECOMMUNICATION BACKBONE TERMINATION PANELTDTP TELECOMMUNICATION DEVICE TERMINATION PANELTMGR TELECOMMUNICATION MAIN GROUND BUSTMGB TELECOMMUNICATION ROOM GROUND BUSTC TIME CLOCKTVSS TRANSIENT VOLTAGE SURGE SUPPRESSORUPS UNINTERRUPTIBLE POWER SUPPLYUSSHV UNIT SUBSTATION AT 480Y/277 SECONDARY VOLTAGEUSSLV UNIT SUBSTATION AT 208Y/120 SECONDARY VOLTAGE
R RADIOLOGY
SWBD
SWBD-R UPS 2
PANELBOARDS DESIGNATIONS
LEVEL
AREA
TYPE
BRANCH
SEQUENCE NUMBER
NUMBERS IN SEQUENCE - 1,2,3, ETC.
UPS
R RADIOLOGY
I ISOLATED PANELBOARDK KITCHEN PANELBOARDL LIGHTING AND APPLIANCE PANELBOARDO OPERATING ROOM PANELBOARDP POWER DISTRIBUTION PANELBOARDX X-RAY PANELBOARD
B BASEMENT LEVEL1 LEVEL 012 LEVEL 023 LEVEL 03
4 P E L 1
BRANCH VOLTAGE DROP
CONDUCTOR AWG #12 #10 #8
MAXIMUM CONDUCTOR LENGTH AT 120V 95 160 245MAXIMUM CONDUCTOR LENGTH AT 277V 225 375 565MAXIMUM CONDUCTOR LENGTH AT 208V 1 PH. 170 280 425MAXIMUM CONDUCTOR LENGTH AT 480V 1 PH. 390 650 985GROUND CONDUCTOR AWG #12 #10 #8
NOTES:
1. INCREASE BRANCH CIRCUIT CONDUCTOR AS INDICATED.
2. BASED ON 20A CIRCUIT LOADED TO 10A USING SINGLE PHASE, 2 WIRE CIRCUITS.
3. SCHEDULE REPRESENTS MINIMUM CONDUCTOR SIZE BASED ON LENGTH OF BRANCHCIRCUIT CONDUCTOR FROM PANEL TO PHYSICAL CENTER OF LOAD TO OVERCOMEVOLTAGE DROP. 3% VOLTAGE DROP ASSUMED.
4. TRANSITION FROM LARGER CONDUCTOR SIZE TO #12 FOR FINAL TERMINATION TOOUTLET DEVICE. PROVIDE JUNCTION BOX WITHIN 10' OF OUTLET. EXTEND #12CONDUCTOR TO OUTLET.
CABLE ROUTING NOTESX
DRAWING KEYED NOTESX
LAB EQUIPMENT TAGXXX
SYMBOL WITH TAIL INDICATES WALL INSTALLATION, HEIGHT AS INDICATED
SYMBOL WITH DASHED OUTLINE INDICATES INSTALLATION AT CEILING
FEEDER DESIGNATION300/4
EXISTING EQUIPMENT DESIGNATION(E) XXX
X
NEW EQUIPMENT DESIGNATION
EQUIPMENT DESIGNATION NUMBER
X
ABBREVIATIONSUPS UNINTERRUPTIBLE POWER SUPPLYUSS UNIT SUBSTATIONUTP UNSHIELDED TWISTED PAIR
V VOLTVAV VARIABLE AIR VOLUMEVM VOLTMETERVolP VOICE OVER INTERNET PROTOCOLVPI VACUUM-PRESSURE IMPREGNATEDVSD VARIABLE SPEED DRIVE
W WATTWAN WIDE AREA NETWORKWAP WIRELESS ACCESS POINTWLAN WIRELESS LOCAL AREA NETWORKWP WEATHERPROOF
XFMR TRANSFORMER
TERM TERMINALTEL TELEPHONETGB TELECOMMUNICATIONS GROUNDING
BUS BARTHD TOTAL HARMONIC DISTORTIONTMGB TELECOMMUNICATIONS MAIN GROUNDING BUS BARTR TELECOM ROOMTRANS TRANSITIONTSER TELECOMMUNICATIONS SERVICE ENTRANCE
ROOMTTC TELEPHONE TERMINAL CABINETTV TELEVISIONTVSS TRANSIENT VOLTAGE SURGE SUPPRESSIONTYP TYPICAL
UC UNDER COUNTERUG UNDERGROUNDUNO UNLESS NOTED OTHERWISE
GEN GENERATORGFCI GROUND FAULT CIRCUIT INTERRUPTINGGFI GROUND FAULT INTERRUPTINGGFR GROUND FAULT RELAYGFRT GROUND FAULT RELAY TEST PANELGND GROUND
HCT HARMONIC CONDITIONING TRANSFORMERHF HARMONIC FILTERHFT HARMONIC FILTER WITH INTEGRAL
TRANSFORMERHID HIGH INTENSITY DISCHARGEHOA HAND OFF AUTOHP HORSEPOWERHST HARMONIC SUPPRESSION TRANSFORMERHSKPG HOUSEKEEPINGHTR HEATERHV HIGH VOLTAGEHZ HERTZ (CYCLES/SECOND)
ICC INTERMEDIATE CROSS CONNECTID INSIDE DIAMETERIDF INTERMEDIATE DISTRIBUTION FRAMEIMC INTERMEDIATE METAL CONDUITIP INTERNET PROTOCOLIPS IMAGES PER SECONDiSCSI INTERNET SMALL COMPUTER SYSTEM
INTERFACEIR INFRARED
JB JUNCTION BOX
KO KNOCK OUTKV KILOVOLTKVA KILOVOLT AMPEREKW KILOWATTKWH KILOWATT HOUR
LA LIGHTNING ARRESTORLAN LOCAL AREA NETWORKLCD LIQUID CRYSTAL DISPLAYLED LIGHT EMITTING DIODELS LIFE SAFETYLTD LONG TIME DELAYLTG LIGHTINGLV LOW VOLTAGE
MAG MAGNETICMAN MANUALMAX MAXIMUMMATV MASTER ANTENNA TELEVISIONMb MEGABITMC METAL CLAD CABLE
MCA MINIMUM CIRCUIT AMPERESMCB MAIN CIRCUIT BREAKERMCC MOTOR CONTROL CENTERMCS MOLDED CASE SWITCHMCP MOTOR CIRCUIT PROTECTORMDF MAIN DISTRIBUTION FRAMEMDP MAIN DISTRIBUTION PANELBOARDMECH MECHANICALMER MAIN EQUIPMENT ROOMMFGR MANUFACTURERMFS MAIN FUSED SWITCHMGP MEDICAL GAS PANELMH MANHOLEMI MINERAL INSULATED CABLEMIC MICROPHONEMIN MINIMUMMLO MAIN LUGS ONLYMM MULTIMODEMOCP MAXIMUM OVERCURRENT PROTECTIONMTD MOUNTEDMTS MANUAL TRANSFER SWITCHMV MEDIUM VOLTAGE
N NEUTRALNA NOT APPLICABLENC NORMALLY CLOSEDNEC NATIONAL ELECTRICAL CODENEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATIONNFPA NATIONAL FIRE PROTECTION ASSOCIATIONNIC NOT IN CONTRACTNO NORMALLY OPENNOC NETWORK OPERATIONS CENTERNTS NOT TO SCALE
OA OUTSIDE AIROC ON CENTEROCPD OVERCURRENT PROTECTIVE DEVICEOD OUTSIDE DIAMETEROH OVERHEAD
P POLEPA PUBLIC ANNOUNCEMENTPB PULLBOX/PUSHBUTTONPC PHOTO CELLPCU PACKAGED CONTROL UNITP/E PNEUMATIC- ELECTRICPH PHASEPNL PANELBOARDPLC PROGRAMMABLE LOGIC CONTROLLERPoE POWER OVER ETHERNETPRI PRIMARYPSU PATIENT SERVING UNITPT POTENTIAL TRANSFORMERPTZ PAN TILT ZOOMPVC POLYVINYL CHLORIDEPWR POWER
RAID REDUNDANT ARRAY OF INDEPENDENT DISKSRCP REFLECTED CEILING PLANSRCPT RECEPTACLERE REFER TOREF REFRIGERATORRF RADIO FREQUENCYRF RETURN FANRFID RADIO FREQUENCY IDENTIFICATION DEVICERGS RIGID GALVANIZED STEELRM ROOMRTLS REAL TIME LOCATION SYSTEMRUPS ROTARY HYBRID UNINTERRUPTIBLE POWER
SUPPLYSCHED SCHEDULESEC SECONDARYSF SUPPLY FANSFL SUB FEED LUGSSFP SURGICAL FACILITY PANELSH SHEETSM SINGLE MODESP SINGLE POLESPDT SINGLE POLE DOUBLE THROWSPST SINGLE POLE SINGLE THROWSPC SPACESPEC SPECIFICATIONSPKR SPEAKERSPR SPARESS STAINLESS STEELST SHUNT TRIPSTD SHORT TIME DELAYSTP SHIELDED TWISTED PAIRSTR STARTERSWBD SWITCHBOARDSWGR SWITCHGEARSYM SYMMETRICAL
TB TERRA BYTESTBB TELECOMMUNICATIONS BONDING BACKBONETC TERMINAL CABINET
UPS UNINTERRUPTIBLE POWER SUPPLYUSS UNIT SUBSTATIONUTP UNSHIELDED TWISTED PAIR
V VOLTVAV VARIABLE AIR VOLUMEVM VOLTMETERVolP VOICE OVER INTERNET PROTOCOLVPI VACUUM-PRESSURE IMPREGNATEDVSD VARIABLE SPEED DRIVE
W WATTWAN WIDE AREA NETWORKWAP WIRELESS ACCESS POINTWLAN WIRELESS LOCAL AREA NETWORKWP WEATHERPROOF
XFMR TRANSFORMER
ABBREVIATIONS
DIA DIAMETERDIV DIVISIONDN DOWNDO DRAWOUTDPDT DOUBLE POLE DOUBLE THROWDPST DOUBLE POLE SINGLE THROWDS DISCONNECT SWITCHDSP DIGITAL SIGNAL PROCESSORDWG DRAWINGDVD DIGITAL VERSATILE DISCDVR DIGITAL VIDEO RECORDERDVS DIGITAL VIDEO SURVEILLANCEDWG DRAWING
EA EACHEF EXHAUST FANEGS ENGINE-GENERATOR SETELEC ELECTRICELEV ELEVATOREMT ELECTRICAL METALLIC TUBINGEO EQUIPMENT BY OWNEREOL END OF LINE DEVICEEPMS ELECTRIC POWER METER SYSTEMEQUIP EQUIPMENTEWC ELECTRIC WATER COOLEREXH EXHAUSTEXP EXPLOSION PROOF
FA FIRE ALARMFACU FIRE ALARM CONTROL UNITFBO FURNISHED BY OWNERFI FILM ILLUMINATORFLR FLOORFLUOR FLUORESCENTFPS FRAMES PER SECONDFPU FIELD PROCESSING UNITFS FUSED SWITCHFTL FEED THRU LUGS
GA GAUGEGb GIGABITGE GROUNDING EQUALIZER CONDUCTOR
POWER QUALITY MONITOR
UPS-UNINTERRUPTIBLE POWER SUPPLY (SINGLE LINE DENOTATION)
PQM
EQUIPMENT CLEARANCE SPACE
UNINTERRUPTIBLE POWER SUPPLY
UPS REMOTE STATUS PANELRSP
SURGE PROTECTIVE DEVICESPD
LIGHTING/LIGHTING CONTROLS
LINE VOLTAGE, PHOTOELECTRIC CONTROL, 1'-0" ABOVE ROOF, AIMED NORTHPC
SINGLE POLE SWITCH, 3'-8" AFF
EMERGENCY LIGHTING BATTERY UNIT
LED FLOOD LIGHT
EMERGENCY POWER OUT STATIONEPO
LIGHTING BRANCH CIRCUITS
LOWER CASE LETTER(S) INDICATE MULTI-SWITCH CONTROL ARRANGEMENT.a
WIRING DEVICESNEMA 5-20R GFCI DUPLEX RECEPTACLE IN WP BOX WITH WP COVER, 1'-6" AG
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EMPOWER FOR BUILDING 2JMEDICAL EQUIPMENT
of 20
2J
NOTES, LEGENDS, SYMBOLS ANDABBREVIATIONS
E0001TZ TCI
ROOM "E"
ROOM "D"
VUTSRQPO
7
6
5
APPROXIMATE ROUTE FROMNEW SWITCHBOARD FEEDERTO NEW PANELS
8
UP TO LEVEL 3
PB
E0200CE0200A
E0200B
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EMPOWER FOR BUILDING 2JMEDICAL EQUIPMENT
of 20
2J
PIPE BASEMENT LEVEL POWER ANDSYSTEMS PLAN AREA A
E0200ATZ TCI
1/8" = 1'-0"1
PIPE BASEMENT LEVEL POWER AND SYSTEMS PLAN AREA A
GENERAL NOTES:A.FEEDER ROUTING IS SHOWN FOR DESIGN INTENT PURPOSES ONLYAND SHALL BE FIELD COORDINATED AND ADJUSTED AS REQUIRED.
B.PULL BOX SIZES AND LOCATIONS ARE SHOWN FOR DESIGN INTENTPURPOSE ONLY AND SHALL BE FIELD COORDINATED AND ADJUSTED ASREQUIRED. PULL BOXES ARE TO BE DETERMINED IN THE FIELD.
C.FEEDER SHALL FOLLOW ALONG BUSDUCT IN STACKED ELECTRICALROOMS UP THROUGH CEILING.
ROOM "G"
ROOM "F"
APPROXIMATE ROUTE FROMNEW PARALLELINGSWITCHGEAR FEEDER TOTHE ATS-RUPS2
APPROXIMATE ROUTEFROM NEW SWITCHBOARDFEEDER TO NEW PANELS
VUTSRQPO
4
3
2
1.6
1.3
UP TO ATS-RUPS2
UP TO SWBD-REC3
UP TO LEVEL 3
PB
PB
PB
TRANSITION FROMFUNCTIONAL BASEMENTLEVEL
STACKEDVERTICALLY
1
TO ATS 2-CP-16
E0200CE0200A
E0200B
PB
PB
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EMPOWER FOR BUILDING 2JMEDICAL EQUIPMENT
of 20
2J
PIPE BASEMENT LEVEL POWER ANDSYSTEMS PLAN AREA B
E0200BTZ TCI
1/8" = 1'-0"1
PIPE BASEMENT LEVEL POWER AND SYSTEMS PLAN AREA B
GENERAL NOTES:A.FEEDER ROUTING IS SHOWN FOR DESIGN INTENT PURPOSESONLY AND SHALL BE FIELD COORDINATED AND ADJUSTED ASREQUIRED.
B.PULL BOX SIZES AND LOCATIONS ARE SHOWN FOR DESIGNINTENT PURPOSE ONLY AND SHALL BE FIELD COORDINATED ANDADJUSTED AS REQUIRED. PULL BOXES ARE TO BE DETERMINEDIN THE FIELD.
C.FEEDER SHALL FOLLOW ALONG BUSDUCT IN STACKEDELECTRICAL ROOMS UP THROUGH CEILING.
KEYED NOTES :1.VLAN NETWORK PATCH PANEL LOCATED IN FIRST FLOORTELECOMMUNICATION ROOM IN THIS LOCATION ABOVE.ROUTE NEW EPMS CABLES TO THIS LOCATION, TEST ANDTERMINATE AT SPARE PORTS ON THE PATCH PANEL.
NMLKJ
7
6
5
4
3
2
1.6
1.3
8
9
HGFEDCBA
PB
STACKEDVERTICALLY
TO ATS 2-CP-16
E0200A
E0200BE0200C
UP TO ATS 2-CP-16
1
PB
PBPBPB
2 APPROXIMATE ROUTE FROM NEWPARALLELING SWITCHGEAR TO ATS 2-CP-16
APPROXIMATE ROUTE OF EXISTINGCHILLED WATER PUMP FEEDER.
E0403
1
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EMPOWER FOR BUILDING 2JMEDICAL EQUIPMENT
of 20
2J
PIPE BASEMENT LEVEL POWER ANDSYSTEMS PLAN AREA C
E0200CTZ TCI
1/16" = 1'-0"1
PIPE BASEMENT LEVEL POWER AND SYSTEMS PLAN AREA C
GENERAL NOTES:A.FEEDER ROUTING IS SHOWN FOR DESIGN INTENT PURPOSES ONLY AND SHALL BEFIELD COORDINATED AND ADJUSTED AS REQUIRED.
B.PULL BOX SIZES AND LOCATIONS ARE SHOWN FOR DESIGN INTENT PURPOSE ONLYAND SHALL BE FIELD COORDINATED AND ADJUSTED AS REQUIRED. PULL BOXESARE TO BE DETERMINED IN THE FIELD.
KEYED NOTES :1.INTERCEPT AND SPLICE EXISTING CHILLED WATER PUMP FEEDER. PROVIDENEW PULL BOX.
2.DEMOLISH EXISTING CHILLED WATER PUMP FEEDER BACK TO SUBSTATIONA.
E0401
1
E0402
3
E0401
2
UTSRQPONMLKJ
7
6
5
4
3
2
1.6
1.3
0
8
9
1
955 SF
ROOM BB
250A
2355 SF
ROOM BB
250
2936 SF
ROOM BB
260
HGFE
5660 SF
ELECTRICALSUBSTATION
BA-140
DCBA
10503 SF
NORTH MAINMECHANICAL
ROOM
E0403
2
1
1
E0403
E0403
3
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EMPOWER FOR BUILDING 2JMEDICAL EQUIPMENT
of 20
2J
FUNCTIONAL BASEMENT LEVELPOWER AND SYSTEMS PLAN
E0201TZ TCI
1" = 20'-0"1
FUNCTIONAL BASEMENT LEVEL POWER AND SYSTEMS PLAN
KEYED NOTES :1.VLAN NETWORK PANEL LOCATED IN THISTELECOMMUNICATION ROOM.
UP
UP
UP
UP
242 SF
ELECTRICALRM.
3-4B
254 SF
ELECTRICALRM.
3-5B
252 SF
ELECTRICALRM
3-7B
262 SF
ELECTRICALRM.
3-6B
E0402
1
E0402
2
WV
UTSRQ
7
6
5
4
3
2
1.6
1.3
8
9
1
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EMPOWER FOR BUILDING 2JMEDICAL EQUIPMENT
of 20
2J
LEVEL 03 POWER AND SYSTEMS PLAN
E0203TZ TCI
1/16" = 1'-0"1
LEVEL 03 POWER AND SYSTEMS PLAN
J
J
PC
J
NEW DIESELGENERATORLOCATION
DT DT DTDTDTEX EX EX EX EX
EX EX
EX
EX EX
EX EX EXEX
EX
EX
EX
EX
EXEXEXEXEX
EX EX
EX EX EX EX
GEN 2 GEN 3 GEN 4 GEN 5
CAT GEN 1MODEL 3508700KW/875KVA(TYPICAL)
QPO
1.6
1.3
0
APPROXIMATE ROUTE FORGENERATOR FEEDER,GROUNDING ELECTRODE, ANDCONTROL CONDUITS TO THEEXISTING PARALLELINGSWITCHGEAR
1
EX
EX
EX
EX
EX
BGLEC EX
BGHEC EX
BGTEC2
BGTEC
BGLECBRK#2
BGLECBRK#4
BGLECBRK#6
BGLECBRK#8
BGLECBRK#10
GENERATORFUELCONTROL
PUMP 1 & 2MOTORSTARTER
MCB11 EXP01
2
6
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
GROUND
2RAD2
2RAD1
2RAD3
2RAD5
2RAD4
COMMUNICATION CONDUIT
BAT
JWH
LOH
STACKEDVERTICALLY
12
14
19,21
NEW PIPE RACK. SEE STRUCTURAL DRAWING S0102 FORDETAILS.
7
PB
10
G
G
G G
3
E0401
11
EXISTING PIPING SUPPORT
BAS
EX
1515
14 14
EPO WP
a
12
WP
1
1
1
1 a
a
a
1
1 1616
17
1818
19
NEW SWITCHGEARLOCATIONASCO 4000 AMP480Y/277V, 3 PHASE,4W,
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
2
1.6
1
LSDP
5
4
RELOCATE GEN-5 WATER ANDOIL SENSOR AND 1"C TOACCOMMODATE NEW SECTION
TRANSITIONDOWN TO PIPEBASEMENT
TOP HAT
TO
P H
AT
EX
4
4
4
4
(3) STACKEDVERTICALLY
24V DCBATTERY
8
(4) STACKEDVERTICALLY
3
3
16,18BATTERYCHARGER
9
13
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EMPOWER FOR BUILDING 2JMEDICAL EQUIPMENT
of 20
2J
ENLARGED PLANS
E0401TZ TCI
1/4" = 1'-0"1
GENERATOR ROOM 250 AND AREA WAY
1/4" = 1'-0"2
SWITCHGEAR ROOM 250A
KEYED NOTES :1.NEW SWITCHGEAR SECTION AS EXTENSION TO EXISTING PARALLELING SWITCHGEAR. SEEE0521. EXTEND EXISTING CONCRETE PAD.
2.PROVIDE NEW GENERATOR TO MATCH PITCH OF EXISTING GENERATORS. NEW GENERATORTO BE IN WEATHER PROOF, SOUND ATTENUATED ENCLOSURE WITH SUB BASE BELLY FUELTANK.
3.PROVIDE NEW STEEL SUPPORTS FOR THE FEEDER AND COMMUNICATION CONDUIT.
4.USE EXISTING RACK FOR SUPPORT OF NEW FEEDER AND COMMUNICATION CONDUIT.
5.NEW TOP HAT TO MATCH HEIGHT OF EXISTING TOP HAT.
6.FEEDER AND COMMUNICATION CONDUIT TO FOLLOW NEXT TO EXISTING GENERATOR FEEDERFOR ROOM TRANSITION.
7.RELOCATE EXISTING FA BOX, FA CABLES AND CONDUIT AS NEEDED.
8.NEW STATION BATTERY SYSTEM INCLUDING BATTERY CHARGER. WIRE FROM THE STATIONBATTERY INTO THE EXISTING CONTROL POWER CIRCUIT WITHIN THE PARALLELINGSWITCHGEAR. 2#6 AWG 1"C.
9.PROVIDE CORE TO PIPE BASEMENT. PROVIDE FEEDER TO RUPS2, ATS 2-CHP-16 AND FIVEADDITIONAL 4" RGS STUBS. CAP FOR FUTURE USE.
10.BOND NEW GENERATOR GROUNDING ELECTRODE TO EXISTING BUILDING GROUNDINGELECTRODE SYSTEM AT THE CEILING.
11.CONTRACTOR TO PROVIDE TEMPORARY SUPPORT FOR DISCONNECT SWITCH ANDASSOCIATED CONDUITS, ETC WHILE STEEL SUPPORT STRUCTURE IS BEING REPLACED.ATTACH DISCONNECT SWITCH TO NEW STEEL SUPPORT STRUCTURE.
12.NEW GENERATOR EPO.
13.TIE BATTERY CHARGER GENERAL TROUBLE ALARM INTO THE PARALLELING SWITCHGEARALARM SYSTEM.
14.WEATHER PROOF DOUBLEHEAD LED FLOOD LIGHT MOUNTED TO STEEL SUPPORT AT 10'.WIRE TO 120V CIRCUIT SHOWN. CONTROL BY NEW SWITCH AND PHOTOCELL SHOWN.COORDINATE EXACT LOCATION AND MOUNTING OF FLOOD LIGHTS, PHOTOCELL AND SWITCHIN THE FIELD. SUBMIT PRODUCT FOR APPROVAL PRIOR TO RELEASE.
15.WEATHER PROOF LED EMERGENCY BATTERY UNIT MOUNTED TO EXTERIOR OF GENERATORENCLOSURE AND WIRED AHEAD OF SWITCH LEG TO 120V CIRCUIT SHOWN. SUBMIT PRODUCTFOR APPROVAL PRIOR TO RELEASE.
16.GFCI RECEPTACLE IN A WEATHER PROOF ENCLOSURE MOUNTED TO EXTERIOR OFGENERATOR ENCLOSURE AND WIRED AHEAD OF SWITCH LEG TO 120V CIRCUIT SHOWN.RECEPTACLE TO HAVE WHILE IN USE ENCLOSURE.
17.CONCRETE BELOW GENERATOR TO BE REMOVED AND REPLACED REFER TO STRUCTURALDETAIL 3/S0001. CONTRACTOR TO COORDINATE GENERATOR ANCHORING DETAILS ANDLOCATION WITH MANUFACTURER.
18.GENERATOR TO BE SECURED IN PLACE BEFORE NEW STRUCTURAL SUPPORT IS INSTALLED.TEMPORARY SUPPORT ANY EXISTING SYSTEMS UNTIL NEW STRUCTURAL SUPPORT IS INPLACE. REFER TO DETAIL 3/E0403.
19.GENERATOR MANUFACTURER TO PROVIDE DAY TANK. DAY TANK TO BE WITHIN GENERATORFOOT PRINT WITH MINUMUM 4 HOUR RUN TIME. MANUFACTURER'S RESPONSIBILITY TO MEETLOCAL UL REQUIREMENTS.
1.EXTEND BRANCH CIRCUITS IN THIS AREA TO THE FOLLOWING BRANCH PANELBOARDS, UNLESSOTHERWISE NOTED:
120 / 208V PANELBOARDSBGLEC - NORMAL POWER
277 / 480V PANELBOARDSBGHEC - NORMAL POWER
BRANCH CIRCUIT NOTES :
1
1
GENERATOR ROOM TRANSITION OVERVIEW3
NTS
7
6
GENERAL NOTES:A.FEEDER ROUTING IS SHOWN FOR DESIGN INTENT PURPOSES ONLY AND SHALL BE FIELDCOORDINATED AND ADJUSTED AS REQUIRED.
B.PULL BOX SIZES AND LOCATIONS ARE SHOWN FOR DESIGN INTENT PURPOSE ONLYAND SHALL BE FIELD COORDINATED AND ADJUSTED AS REQUIRED. PULL BOXES ARETO BE DETERMINED IN THE FIELD.
C.ALL CONDUIT ROUTES THIS SHEET ARE OVERHEAD ROUTES UNLESS OTHERWISENOTED.
PB
SBSBSB
3DLP
3DTP 3DTEQ 3DTEC3DLEC
3DTR3DLR3DHL
LV LIGHTING PANEL
3DHES
242 SF
ELECTRICALRM.
3-4B
ROOM "D"EX
EX
EX
EX
EX
EX EX
EX
EX
EX
EX
EX
S
3DRUPS2 3ERUPS2
3FLR
3FTR 3FHR3FHES 3FLEQ
3FTEQ
3FTP3FLP 3FLP23FHL3FLEC
3FTECRP-3F
262 SF
ELECTRICALRM.
3-6B
ROOM "F"
EX
EXEX EX
EX
EX
EX
EX
EX
EX
EXEX
EX
EX
EX
3GRUPS2
3FRUPS2
6
E0402
DPREQ REQ REC2 FESDFEC
FEQDFEQ
GEQ
GEC
RUPS1
NEW UPS AND ATS'S LOCATION
EX EX EX
EX EX EX
EX
EX
EX
EX EX
EX
EX
EX
EX
EX
EXEXEX
EXEXEX
EX
EX
EX EX
EX EXEX EX
EX
EXEX
EXFEC
USR 2000KVA
USF 2500KVA
LOA
D F
-7
LOA
D F
-14
3000A MCB D
IST
.
DIS
T.
LOA
D F
-7
LOA
D F
-14
4000A MCB
DIS
T.
DIS
T.
DIS
T.
UPS
CO
NT
RO
LLIX
CA
PA
CIT
OR
S
UTS
2
1.6
1.3
SWBD-RUPS2
ATS-RUPS2
TRANSITION DOWN TOPIPE BASEMENT LEVEL
RUPS2
UPS
PB
1
1
1
EPO3
RSP3FRUPS2 3GRUPS2
JB
JB
ERL
ERL
JB
ERL
JBERL
2
2
(4)#2/0, (1)#6G-2"C
(3)#1,1#8G,1-1/2"C
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EMPOWER FOR BUILDING 2JMEDICAL EQUIPMENT
of 20
2J
ENLARGED PLANS
E0402TZ TCI
1/4" = 1'-0"1
LEVEL 03 ELECTRICAL ROOM 3-4B 1/4" = 1'-0"
2LEVEL 03 ELECTRICAL ROOM 3-6B
1/4" = 1'-0"3
FUNCTIONAL BASEMENT LEVEL ELECTRICAL ROOM 260
1/4" = 1'-0"6
ROOM 3-6B WALL SECTION VIEW NEW 1/4" = 1'-0"
5ROOM 3-6B WALL SECTION VIEW DEMO
KEYED NOTES :1.RELABEL ALL INSTANCES OF 'RUPS' TO RUPS1.
2.JUNCTION BOX TO BE REMOVED AND RELOCATED AS NECESSARY TOALLOW SPACE FOR NEW PANELS. EXTEND EXISTING FEEDERS TO ANDFROM THE ADJACENT PANEL AND TRANSFORMER AS REQUIRED. VERIFYSIZES OF CONDUCTORS AND CONDUIT PRIOR TO WORK.
3.NEW UPS EPO.
ROOM 3-6B OVERVIEW7
NTS
2
2
A.FEEDER ROUTING IS SHOWN FOR DESIGN INTENT PURPOSESONLY AND SHALL BE FIELD COORDINATED AND ADJUSTED ASREQUIRED.
B.ALL CONDUIT ROUTES THIS SHEET ARE OVERHEAD ROUTESUNLESS OTHERWISE NOTED.
GENERAL NOTES:
4
3
G
UNITSUBSTATION
"USA"
ATS-AES
ATS-AEC
ATS-AEQ
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
ATS 2-CHP-16
1
TRANSITION DOWNTO PIPE BASEMENT
7
D
2-CHP-16
2-CHP-16VSD
EX EX
PO
0
1
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EMPOWER FOR BUILDING 2JMEDICAL EQUIPMENT
of 20
2J
ENLARGED PLANS
E0403TZ TCI
1/4" = 1'-0"2
PARTIAL ELECTRICAL SUBSTATION ROOM BA-140
GENERAL NOTES:A.FEEDER ROUTING IS SHOWN FOR DESIGN INTENT PURPOSES ONLY AND SHALL BEFIELD COORDINATED AND ADJUSTED AS REQUIRED.
B.PULL BOX SIZES AND LOCATIONS ARE SHOWN FOR DESIGN INTENT PURPOSE ONLYAND SHALL BE FIELD COORDINATED AND ADJUSTED AS REQUIRED. PULL BOXES ARETO BE DETERMINED IN THE FIELD.
C.ALL CONDUIT ROUTES THIS SHEET ARE OVERHEAD ROUTES UNLESS OTHERWISENOTED.
KEYED NOTES :1.VLAN NETWORK PATCH PANEL LOCATED IN THISTELECOMMUNICATION AREA.
1/4" = 1'-0"1
PARTIAL NORTH MAIN MECH ROOM
1/4" = 1'-0"3
PROPOSED GENERATOR INSTALLATION PATH
FUNCTIONAL BASEMENT LEVEL
LEVEL 01
LEVEL 02
LEVEL 04
LEVEL 01
LEVEL 02
LEVEL 04
INTERIOREXTERIOR INTERIOR EXTERIOR
PIPE BASEMENT LEVEL
LEVEL 03 LEVEL 03
LEVEL 05 LEVEL 05
FUNCTIONAL BASEMENT LEVEL
PIPE BASEMENT LEVEL
LEVEL 06 LEVEL 06
LEVEL 07 LEVEL 07
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24G1 G2 G3 G4 G5 G6 METERING1 2 3 4 5 6
200A 200A 300A 200A 100A 100A
SP
AR
E
G
LSIA
G
LSIA
G
LSIA
G
LSIA
G
LSIA
G
LSIA
1600AF
1600AT
(0.9) 6.0P
SP
AR
E
2-RAD1 2-RAD2 2-RAD3 2-RAD4 2-RAD5
2-G1 2-G2 2-G3 2-G4 2-G5
AE
SR
E:
E05
25
AE
CR
E:
E05
25
AE
QR
E:E
0525
FIR
E P
UM
PR
E:
E05
25
7HA
RE
: E
0525
BE
CR
E:
E05
26
BE
QR
E:
E05
26
7HB
RE
: E
0526
CE
CR
E:
E05
27
CE
QR
E:
E05
27
7HC
RE
: E
0527
UP
SR
E:
E05
27
DE
CR
E:
E05
22
DE
QR
E:
E05
22
BE
SR
E:
E05
26
CE
SR
E:
E05
27
DE
SR
E:
E05
22
CH
1R
E:
E05
23
CH
2R
E:
E05
23
FE
CR
E:
E05
23
FE
QR
E:
E05
23
GE
CR
E:
E05
23
GE
QR
E:
E05
23
RE
CR
E:
E05
24
FE
SR
E:
E05
23
RE
C2
RE
: E
0524
RE
QR
E:
E05
24
FIRE PUMP
AEQ
AEC
LSDP
7HB
BEQ
BEC
7HA
UPS
7HC
CEQ
CEC
GENERATOR 1 CH2 GEQ SPARE
CH1 GEC REQ
DEQ FEQ REC2
DEC FEC RECGENERATOR 1
GENERATOR 2
GENERATOR 2
GENERATOR 3
GENERATOR 3
GENERATOR 4
GENERATOR 4
GENERATOR 5
GENERATOR 5
GENERATOR 6
GENERATOR 6
RUPS2
MASTERCONTROLCUBICLE
RU
PS
2R
E:
E05
24
1600
A M
.C.B
.
1600
A M
.C.B
.
1600
A M
.C.B
.
1600
A M
.C.B
.
1600
A M
.C.B
.
1600
A M
.C.B
.
1
1
2
3
800AF 800AF
800AF800AT(0.5)LSI5.0P
800AF800AT(1.0)LSI5.0P
800AF800AT
800AF800AT
800AF800AT
800AF800AT
800AF800AT
400AF300AT
800AF600AT
200AF150AT
800AF800AT
800AF800AT
400AF300AT
800AF400AT
1600AF1200AT
1600AF1200AT
1600AF1200AT
1600AF1200AT
1600AF1200AT
800AF600AT
800AF800AT
800AF600AT
1000AF850AT
1000AF850AT
800AF500AT
400AF200AT
800AF800AT
800AF800AT
800AF800AT
800AF600AT
800AF600AT
PR
EP
AR
ED
SP
AC
E
PR
EP
AR
ED
SP
AC
E
750KW/938KVA
PREPAREDSPACE
PREPAREDSPACE
ATS CHP-16
GENERATOR PARALLELING SWITCHGEAR "ESW"480/277 VOLT, 3 PHASE, 4 WIRE WITH 100% GROUND,4000 AMP BUS
HMI
PM800
EPO
GENERATORALARM
TOUCH PANEL
PARALLELCONTROLLER
PM800 PM800 PM800 PM800 PM800
GENERATORALARM
TOUCH PANEL
GENERATORALARM
TOUCH PANEL
GENERATORALARM
TOUCH PANEL
GENERATORALARM
TOUCH PANEL
GENERATORALARM
TOUCH PANEL
PARALLELCONTROLLER
PARALLELCONTROLLER
PARALLELCONTROLLER
PARALLELCONTROLLER
PARALLELCONTROLLER
EPO EPO EPO EPO EPO
5
5
EXISTING TOP HAT TOP HAT
4
3 SETS(TYP).
250KCMIL, 2"CRGS CONDUIT
NEW HOUSEKEEPING PAD EXTENSION
4
3 6
7 7 7 7 7
4Z
RGSA
TS
2-C
P-1
6R
E:
E05
25
1600AF1600AT(0.9)LSIA6.0P
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EMPOWER FOR BUILDING 2JMEDICAL EQUIPMENT
of 20
2J
POWER RISER DIAGRAMSPARALLELING SWITCHGEAR "ESW"
E0521TZ TCI
NTS1
SWITCHGEAR "ESW" ELEVATION
KEYED NOTES :1.PROVIDE NEW CIRCUIT BREAKER, METER, GENERATOR CONTROLS/TOUCH PANEL AND EPO WITHIN EXISTING PREPARED SPACE.
2.SOLIDLY GROUND GENERATOR. TIE INTO EXISTING BUILDINGGROUNDING ELECTRODE SYSTEM.
3.NEW VERTICAL SWITCHGEAR SECTION. MODIFY AND EXTEND EXISTINGBUS.
4.RELABEL SWITCHGEAR SECTION TO BE RUPS1.
5.CONNECT MONITORING INFORMATION FROM NEW EQUIPMENT. UPDATEHMI TO INCLUDE NEW ATS, PSG BREAKERS AND GENERATOR. PROVIDEALL HARDWARE AND SOFTWARE AS REQUIRED.
6.TIE NEW GENERATOR INTO THE EXISTING EPMS (SCHNEIDER) THRU THEVLAN NETWORK. ROUTE CAT 6 TO NEAREST TELECOMMUNICATIONROOM.
7.UPGRADE EXISTING PARALLELING SYSTEM CONTROLS AND HMI'S ASREQUIRED TO INCORPORATE THE NEW GENERATOR SET CONTROLS.
FEEDER DESIGNATIONS - COPPER CONDUCTOR EXISTING
FEEDER ID AMPS PHASE WIRES
(AWG) NEUTRAL WIRES
(AWG) GND (AWG) MIN. CONDUIT
SIZELEGACY FEEDER
DESIGNATION
20/4 20 (3)#12 (1)#12 #12 3/4 4A
30/4 30 (3)#10 (1)#10 #10 3/4 4B
50/4 50 (3)#8 (1)#8 #10 1 4C
65/4 65 (3)#6 (1)#6 #8 1-1/4 4D
85/4 85 (3)#4 (1)#4 #8 1-1/4 4E
115/4 115 (3)#2 (1)#2 #6 1-1/2 4F
130/4 130 (3)#1 (1)#1 #6 2 4G
150/4 150 (3)#1/0 (1)#1/0 #6 2 4H
175/4 175 (3)#2/0 (1)#2/0 #6 2 4J
200/4 200 (3)#3/0 (1)#3/0 #4 2-1/2 4K
230/4 230 (3)#4/0 (1)#4/0 #4 2-1/2 4L
255/4 255 (3)#250KCMIL (1)#250KCMIL #4 3 4M
285/4 285 (3)#300KCMIL (1)#300KCMIL #3 3 4N
310/4 310 (3)#350KCMIL (1)#350KCMIL #3 3-1/2 4P
335/3 335 (3)#400KCMIL #3 3-1/2 3R
335/4 335 (3)#400KCMIL (1)#400KCMIL #3 3-1/2 4R
380/4 380 (3)#500KCMIL (1)#500KCMIL #3 4 4S
400/4 400 (6)#3/0 (2)#3/0 (2)#3 (2)3 -1/2 4T
620/4 620 (6)#350KCMIL (2)#350KCMIL (2)#1 (2)3 -1/2 4U
780/4 780 (6)#500KCMIL (2)#500KCMIL (2)#1/0 (2)4 4V
800/4 800 (9)#300KCMIL (3)#300KCMIL (3)#1/0 (3)3 4W
1200/3 930 (12)#350KCMIL (3)#1/0 (3)3 4X
1500/3 1200 (12)#500KCMIL (3)#3/0 (3)4 4Y
1600/4 1500 (12)#500KCMIL (4)500KCMIL (4)#4/0 (4)4 4Z
FUNCTIONAL BASEMENT LEVEL
LEVEL 01
LEVEL 02
LEVEL 04
LEVEL 01
LEVEL 02
LEVEL 04
INTERIOREXTERIOR INTERIOR EXTERIOR
PIPE BASEMENT LEVEL
LEVEL 03 LEVEL 03
LEVEL 05 LEVEL 05
FUNCTIONAL BASEMENT LEVEL
PIPE BASEMENT LEVEL
LEVEL 06 LEVEL 06
LEVEL 07 LEVEL 07
300A 150A
ATS-REQ
1AHR 1ALR
ATS-REC1
1AHRE 1ALRE
5ALRE 5BLRE 5CHR
5CHRE 5CLRE
7HLRE
5DHRE 5DLRE
3DLR
5ELRE
3EHR 3ELR 3EHRE
PANEL INROOM 3B-344
3FHR 3FLR 3GHR 3GLR 3GHRE 3GLRE
5GLRE IPUD IPUE IPUF IPUG IPUA IPUB IPUC
TO PANEL 3EHRE
70A 300A
ATS-REC2
400AF400AT
600AF600AT
800AF800AT
600AF600AT
600AF600AT
800AF800AT
225AF175AT
800AF800AT
800AF800AT
800AF800AT
RE: E0521RE: E0521RE: E0521
800AF800AT(1.0)LSIG6.0P
800AF800AT(1.0)LSI5.0PNC
800AF800AT(1.0)LSI5.0PNO
400AF400AT(1.0)LSI5.0P
ATS-RUPS2800A4P, OT
RE: E0521 TO PSG 'ESW'
500KW480Y/277V
3DRUPS2 3ERUPS2 3FRUPS2 3GRUPS2
UNIT SUBSTATION USR (SquareD QED2)3000A, 480Y/277V, 3 PHASE, 4W65KAIC
K
13.2KVFEEDER #7
13.2KV FEEDER #12
3000A
2000KVA
600A15KV
2
1 1SWBD-RUPS2800A, 480/277V 3 PHASE 4W65 KAIC
4U4P
4S4V4V 4P 4V 4X 4W
4X
4X
4X
4X
4V
4X
K1 K1
800ASPACE
800ASPACE
3 3
3 3 3 3 3 3 3 3
3 3
4 4PQM
3SPD
4W
4W
4T 4T 4T 4T
4W
5
SEE DETAIL 1/E0800 FOR MOREINFORMATION.
800AS4PNO
6
4W
4W
4W
RGS
RGS
RGS
RGS
RGS#2/0G, 1-1/2"C
800AF800AT(1.0)LSIG6.0P
7
400AF400AT(1.0)LSI5.0P
400AF400AT(1.0)LSI5.0P
400AF400AT(1.0)LSI5.0P
400AF400AT(1.0)LSI5.0PSPARE
400AF400AT(1.0)LSI5.0PSPARE
400AF400AT(1.0)LSI5.0PSPARE
400AF400AT(1.0)LSI5.0PSPARE
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EMPOWER FOR BUILDING 2JMEDICAL EQUIPMENT
of 20
2J
POWER RISER DIAGRAM R
E0524TZ TCI
KEYED NOTES :1.PROVIDE NEW CIRCUIT BREAKER WITHIN EXISTING SPACE.
2.NEW GENERATOR START CIRCUIT TO EXISTING PARALLELSWITCHGEAR MASTER CONTROL PANEL.
3.TIE THE CIRCUIT BREAKER TRIP UNITS AND THE SWITCHBOARDPOWER QUALITY METER INTO THE EPMS (SCHNEIDER) THRU THE VLANNETWORK. ROUTE CAT 6 TO NEAREST TELECOMMUNICATION ROOM.
4.KEY INTERLOCK K1 SHALL BE TWO LOCKS, ONE KEY.
5.ATS TO HAVE ASCO 72E COMMUNICATION MODULE. CAT 6 TO RUN TONEAREST TELECOMMUNICATION ROOM TO CONNECT TO THE EXISTINGEPMS (SCHNEIDER).
6.TIE UPS INTO THE EXISTING SCHNEIDER SYSTEM THRU THE VLANNETWORK. ROUTE CAT 6 TO NEAREST TELECOMMUNICATION ROOM.
7.SOLIDLY GROUND UPS SYSTEM. TIE INTO THE EXISTING GROUNDELECTRODE SYSTEM WITHIN ELECTRICAL ROOM 260.
FEEDER DESIGNATIONS - COPPER CONDUCTOR EXISTING
FEEDER ID AMPS PHASE WIRES
(AWG) NEUTRAL WIRES
(AWG) GND (AWG) MIN. CONDUIT
SIZELEGACY FEEDER
DESIGNATION
20/4 20 (3)#12 (1)#12 #12 3/4 4A
30/4 30 (3)#10 (1)#10 #10 3/4 4B
50/4 50 (3)#8 (1)#8 #10 1 4C
65/4 65 (3)#6 (1)#6 #8 1-1/4 4D
85/4 85 (3)#4 (1)#4 #8 1-1/4 4E
115/4 115 (3)#2 (1)#2 #6 1-1/2 4F
130/4 130 (3)#1 (1)#1 #6 2 4G
150/4 150 (3)#1/0 (1)#1/0 #6 2 4H
175/4 175 (3)#2/0 (1)#2/0 #6 2 4J
200/4 200 (3)#3/0 (1)#3/0 #4 2-1/2 4K
230/4 230 (3)#4/0 (1)#4/0 #4 2-1/2 4L
255/4 255 (3)#250KCMIL (1)#250KCMIL #4 3 4M
285/4 285 (3)#300KCMIL (1)#300KCMIL #3 3 4N
310/4 310 (3)#350KCMIL (1)#350KCMIL #3 3-1/2 4P
335/3 335 (3)#400KCMIL #3 3-1/2 3R
335/4 335 (3)#400KCMIL (1)#400KCMIL #3 3-1/2 4R
380/4 380 (3)#500KCMIL (1)#500KCMIL #3 4 4S
400/4 400 (6)#3/0 (2)#3/0 (2)#3 (2)3 -1/2 4T
620/4 620 (6)#350KCMIL (2)#350KCMIL (2)#1 (2)3 -1/2 4U
780/4 780 (6)#500KCMIL (2)#500KCMIL (2)#1/0 (2)4 4V
800/4 800 (9)#300KCMIL (3)#300KCMIL (3)#1/0 (3)3 4W
1200/3 930 (12)#350KCMIL (3)#1/0 (3)3 4X
1500/3 1200 (12)#500KCMIL (3)#3/0 (3)4 4Y
1600/4 1500 (12)#500KCMIL (4)500KCMIL (4)#4/0 (4)4 4Z
FUNCTIONAL BASEMENT LEVEL
LEVEL 01
LEVEL 02
LEVEL 04
LEVEL 01
LEVEL 02
LEVEL 04
INTERIOREXTERIOR INTERIOR EXTERIOR
PIPE BASEMENT LEVEL
LEVEL 03 LEVEL 03
LEVEL 05 LEVEL 05
FUNCTIONAL BASEMENT LEVEL
PIPE BASEMENT LEVEL
LEVEL 06 LEVEL 06
LEVEL 07 LEVEL 07
BALMBAHM BAHS
1AHL
3AHL
5AHL
1ALP
3ALP
5ALP
CTBCENTRAL TAP BOX
CTBCENTRAL TAP BOX
CTBCENTRAL TAP BOX
5AHEC 5ALEC
3ALEQ
CTBCENTRAL TAP BOX
5AHEQ 5ALEQ
BAHDM BALSBALP
CTBCENTRAL TAP BOX
1AHES 1ALES
BFHES
3AHES
5AHES 5ALES
600A 125A
ATS-AEQ
CTBCENTRAL TAP BOX
J
7HA
ELEV S8 ELEV S10 ELEV S12
ELEV S9 ELEV S11
ATS 7HA
1ALP1
3ALP1
5ALP1
1AHEC 1ALEC 1ALEC1
3AHEC 3ALEC 3ALEC1
1AHEQ 1ALEQ
ATS-AES ATS-AEC
400A 125A
TO CHP7 TO CHP8
BAHEQ BALEQ
800A 400A 100A 150A 800A 400A 800A 600A 1000A 800A 200A
800AT600AT(0.66)LSIG6.0P
RE
: E
0521
RE
: E
0521
RE: E0521
RE: E0521
4F
4F
4F
4X 4X
4P
4X
4F4H
4U
4D
4K
4K
4K
4Y
4Y
4Y
4Y
4Y
4Y
4K
4Y
4U
ATS 2-CP-16400A, 3POT
TO PSG 'ESW'RE: E0521
UNIT SUBSTATION USA4000A, 480Y/277V, 3 PHASE,4W
K
13.2KV FEEDER #13
4000A
2500KVA
600A15KV
13.2KV FEEDER #6
3R
2-CHP-16VSD
3R
3R
3 4
1
5
2
SPLICE
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EMPOWER FOR BUILDING 2JMEDICAL EQUIPMENT
of 20
2J
POWER RISER DIAGRAM A
E0525TZ TCI
FEEDER DESIGNATIONS - COPPER CONDUCTOR EXISTING
FEEDER ID AMPS PHASE WIRES
(AWG) NEUTRAL WIRES
(AWG) GND (AWG) MIN. CONDUIT
SIZELEGACY FEEDER
DESIGNATION
20/4 20 (3)#12 (1)#12 #12 3/4 4A
30/4 30 (3)#10 (1)#10 #10 3/4 4B
50/4 50 (3)#8 (1)#8 #10 1 4C
65/4 65 (3)#6 (1)#6 #8 1-1/4 4D
85/4 85 (3)#4 (1)#4 #8 1-1/4 4E
115/4 115 (3)#2 (1)#2 #6 1-1/2 4F
130/4 130 (3)#1 (1)#1 #6 2 4G
150/4 150 (3)#1/0 (1)#1/0 #6 2 4H
175/4 175 (3)#2/0 (1)#2/0 #6 2 4J
200/4 200 (3)#3/0 (1)#3/0 #4 2-1/2 4K
230/4 230 (3)#4/0 (1)#4/0 #4 2-1/2 4L
255/4 255 (3)#250KCMIL (1)#250KCMIL #4 3 4M
285/4 285 (3)#300KCMIL (1)#300KCMIL #3 3 4N
310/4 310 (3)#350KCMIL (1)#350KCMIL #3 3-1/2 4P
335/3 335 (3)#400KCMIL #3 3-1/2 3R
335/4 335 (3)#400KCMIL (1)#400KCMIL #3 3-1/2 4R
380/4 380 (3)#500KCMIL (1)#500KCMIL #3 4 4S
400/4 400 (6)#3/0 (2)#3/0 (2)#3 (2)3 -1/2 4T
620/4 620 (6)#350KCMIL (2)#350KCMIL (2)#1 (2)3 -1/2 4U
780/4 780 (6)#500KCMIL (2)#500KCMIL (2)#1/0 (2)4 4V
800/4 800 (9)#300KCMIL (3)#300KCMIL (3)#1/0 (3)3 4W
1200/3 930 (12)#350KCMIL (3)#1/0 (3)3 4X
1500/3 1200 (12)#500KCMIL (3)#3/0 (3)4 4Y
1600/4 1500 (12)#500KCMIL (4)500KCMIL (4)#4/0 (4)4 4Z
KEYED NOTES :1.UTILIZE EXISTING CIRCUIT BREAKER TO FEED NEW LOAD.
2.REMOVE EXISTING CHILLED WATER PUMP FEEDER FROM POINT OFSPLICE TO USA.
3.PROVIDE NEW GENERATOR START CIRCUIT TO EXISTINGPARALLELING SWITCHGEAR MASTER CONTROL PANEL.
4.ATS TO HAVE ASCO 72E COMMUNICATION MODULE. CAT6 TO RUN TONEAREST TELECOMMUNICATION ROOM TO CONNECT TO THEEXISTING EPMS (SCHNEIDER).
5.CONTRACTOR TO VERIFY SIZE OF EXISTING CONDUCTORS ANDCONDUIT PRIOR TO WORK.
GENERATOR 6
MASTERCONTROLCUBICLE
HMI
TOP HAT
STATIONBATTERY
2#6-1"C
SPARE 2"C40#14-2"C
2CAT5-1"C2#8AWG-1"C
CA
T6 3
/4"C
3 C
AT
6 3
/4"C
VLAN PATCHPANEL
NEW GENERATOR ATS-RUPS2 RUPS2SWBD-RUPS2
6#14-1"C INHIBIT, START, 2 SPARE
EPMS
VLAN PATCHPANEL
EPMS11
ATS 2-CHP-16
VLAN PATCHPANEL
EPMS
RGS
3 C
AT
6 3
/4"C
1
6#14-1"C INHIBIT, START, 2 SPARE
BAS PANELGENERATOR
ROOM 250
2
4#14-1"C
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EMPOWER FOR BUILDING 2JMEDICAL EQUIPMENT
of 20
2J
COMMUNICATIONS SCHEMATIC
E0721TZ TCI
NTS1
COMMUNICATIONS SCHEMATIC
KEYED NOTES :1.THE CONTRACTOR SHALL COMMISSION SCHNEIDER ELECTRIC TOINCORPORATE ALL NEW DATA POINTS INTO THE EXISTING EPMS SYSTEM.SCOPE SHALL INCLUDE TERMINATION, PROGRAMMING, TESTING ANDCOMMISSIONING, INCLUDING ANY AND ALL HARDWARE, SOFTWARE ANDCOMPONENT UPGRADES.
2.AHU FAN SHUTDOWN SIGNAL. PROGRAMMED TO IMMEDIATELY SHUT DOWNFANS UPON RECEIPT OF GENERATOR START SIGNAL. SEE M0101 FORADDITIONAL INFORMATION.
TYPICAL
DISTRIBUTION PANELBOARD FRONT VIEW
2 1 3
4
KEYED NOTES :
1.EQUIPMENT IDENTIFICATION LABEL.
2.VOLTAGE LABEL.
3.ARC FLASH WARNING LABEL.
4.TESTING LABEL.
5.TOTAL 99" MINIMUM BREAKER/DEVICE MOUNTINGSPACE. (49.5" EACH SIDE)
49.5
".
80/3
60/3
80/3
100/3
150/3
225/3
6.4
".
80/3
60/3
80/3
100/3
150/3
400A MLO, 480Y/277V, 3 PHASE, 4W, 35 KAIC
GENERAL NOTES:
A.PROVIDE BREAKERS AS SHOWN. BREAKERSTO BE MOLDED CASE BREAKERS WITHELECTRONIC TRIP. LSI
6.4
".6.4
".7.5
".7.5
".7.5
".
SPD
225/3
13.5
".
7.5
".
5
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EMPOWER FOR BUILDING 2JMEDICAL EQUIPMENT
of 20
2J
PANEL SCHEDULES
E0800TZ TCI
* NEW LOAD AND CIRCUIT BREAKER
Notes:
Total Est. Demand: 14 A
Total Conn.: 16 A
Total Est. Demand: 11500 VA
Total Conn. Load: 13000 VA
Receptacle 13000 VA 88.46% 11500 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 18 A 18 A 12 A
Total Load: 4833 VA 4833 VA 3333 VA
41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42
39 -- -- -- 500 VA 500 VA -- -- -- 40
37 JACKET WATER HEATER EM GEN #1 30 A 2 500 VA 500 VA 2 30 A JACKET WATER HEATER EM GEN #2 38
35 Spare 20 A 1 0 VA 333 VA -- -- -- 36
33 Spare 20 A 1 0 VA 333 VA -- -- -- 34
31 Spare 20 A 1 0 VA 333 VA 3 50 A TRANSFORMER BGTEC 32
29 -- -- -- 333 VA 333 VA -- -- -- 30
27 -- -- -- 333 VA 333 VA -- -- -- 28
25 TRANS FOR PANEL TELE CLOSET 20 A 3 333 VA 333 VA 3 15 A VENT FAN 2-VF18 26
23 Space -- -- 0 VA 333 VA -- -- -- 24
21 -- -- -- 500 VA 333 VA -- -- -- 22
19 JACKET WATER HEATER EM GEN #6* 20 A 2 500 VA 333 VA 3 15 A VENT FAN 2-VF17 20
17 -- -- -- 0 VA 333 VA -- -- -- 18
15 -- -- -- 0 VA 333 VA -- -- -- 16
13 Spare 15 A 3 0 VA 333 VA 3 15 A VENT FAN 2-VF16 14
11 -- -- -- 500 VA 333 VA -- -- -- 12
9 JACKET WATER HEATER EM GEN #5 30 A 2 500 VA 333 VA -- -- -- 10
7 -- -- -- 500 VA 333 VA 3 15 A VENT FAN 2-VF15 8
5 JACKET WATER HEATER EM GEN #4 30 A 2 500 VA 333 VA -- -- -- 6
3 -- -- -- 500 VA 333 VA -- -- -- 4
1 JACKET WATER HEATER EM GEN #3 30 A 2 500 VA 333 VA 3 15 A VENT FAN 2-VF14 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating:
Mounting: Surface Wires: 4 Mains Rating: 400 A
Supply From: Phases: 3 Mains Type:
Location: ROOM BB 250 Volts: 480/277 Wye A.I.C. Rating: 25000
Branch Panel: BGHEC EX
* NEW LOAD AND CIRCUIT BREAKER
Notes:
Total Est. Demand: 26 A
Total Conn.: 26 A
Receptacle 6800 VA 100.00% 6800 VA Total Est. Demand: 9300 VA
Other 2000 VA 100.00% 2000 VA Total Conn. Load: 9200 VA
Lighting 400 VA 125.00% 500 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 34 A 23 A 23 A
Total Load: 4123 VA 2733 VA 2733 VA
41 Space -- -- 0 VA 0 VA -- -- Space 42
39 Space -- -- 0 VA 0 VA -- -- Space 40
37 Space -- -- 0 VA 0 VA -- -- Space 38
35 -- -- -- 0 VA 0 VA -- -- Space 36
33 -- -- -- 0 VA 0 VA -- -- Space 34
31 Spare 20 A 3 0 VA 0 VA -- -- Space 32
29 -- -- -- 0 VA 0 VA -- -- -- 30
27 Spare 20 A 2 0 VA 0 VA 2 20 A Spare 28
25 -- -- -- 0 VA 0 VA 1 20 A Spare 26
23 Spare 20 A 2 0 VA 333 VA -- -- -- 24
21 Spare 20 A 1 0 VA 333 VA -- -- -- 22
19 Spare 20 A 1 0 VA 333 VA 3 30 A FIRE PUMP & CONTROL 20
17 Spare 20 A 1 0 VA 400 VA -- -- -- 18
15 Spare 20 A 1 0 VA 400 VA 2 20 A SWITCHGEAR BATTERY CHARGER* 16
13 Spare 20 A 1 0 VA 1000... 1 20 A LUBE OIL HEATER (LOH)* 14
11 Spare 20 A 1 0 VA 1000... 1 20 A BATTERY CHARGER (BAT)* 12
9 Spare 20 A 1 0 VA 1000... 1 20 A BATTERY CHARGER 10
7 Spare 20 A 1 0 VA 1000... 1 20 A BATTERY CHARGER 8
5 Spare 20 A 1 0 VA 1000... 1 20 A BATTERY CHARGER 6
3 Spare 20 A 1 0 VA 1000... 1 20 A BATTERY CHARGER 4
1 EXTERIOR FLOOD LIGHTS* 20 A 1 790 VA 1000... 1 20 A BATTERY CHARGER 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating:
Mounting: Surface Wires: 4 Mains Rating: 400 A
Supply From: Phases: 3 Mains Type:
Location: ROOM BB 250 Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: BGLEC EX
1DISTRIBUTION PANELBOARD (TYP)
UTSRQPON
2
1.6
1.3
0
1
20,000 GALLONUNDERGROUNDDIESEL TANK
EXISTING 3" FUELOIL RETURN
2" FOS
FUEL OIL VENT TOATMOSPHERE
REMOTE GENERATORCOOLING UNIT
DEMOLISH EXISTINGSTAINLESS STEELFLUE VENTS TOATMOSPHERE
FUEL OIL VENT TOATMOSPHERE
6" GWS/R
6" GWS/R
CONDENSERFOR IT ROOM
REMOTEGENERATORCOOLING UNIT
12"Ø
12"Ø
12"Ø
12"Ø
12"Ø
12"Ø
12"Ø
12"Ø
12"Ø
12"Ø
EXISTING STRUCTURALSUPPORT TO BE REMOVED.
FOR NEW STRUCTURALSUPPORTS SEE STRUCTURAL
PLANS
EXISTING STRUCTURALSUPPORT TO BE REMOVED.FOR NEW STRUCTRUALSUPPORTS SEE STRUCTURALPLANS.
3" UNDERGROUNDFUEL OIL RETURN
700 kWGENERATOR
700 kWGENERATOR
700 kWGENERATOR
700 kWGENERATOR
700 kWGENERATOR
DAYTANK
DAYTANK
DAYTANK
DAYTANK
DAYTANK
6" GWS/R
EXISTING REF. LINES
EXISTING STRUCTURALSUPPORT TO BE REMOVED.
FOR NEW STRUCTRUALSUPPORTS SEE
STRUCTURAL PLANS.
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EM
POWER FOR BUILDING 2J
MEDICAL EQUIPMENT
of 20
2J
FUNCTIONAL BASEMENT LEVEL HVAC
DEMOLITION PLAN
D0601MB BRM
1/8" = 1'-0"1
D0601 - FUNCTIONAL BASEMENT LEVEL HVAC DEMOLITION PLAN
A/C AIR CONDITIONINGA/E ARCHITECT/ENGINEERAAV AUTOMATIC AIR VENT (VALVE)ABV ABOVEACCU AIR-COOLED CONDENSING UNITACH AIR CHANGES PER HOURACU AIR CURTAINAD ACCESS DOORAF AIR FOIL FANAFF ABOVE FINISHED FLOORAFMS AIR FLOW MEASURING STATIONAHU AIR HANDLING UNITALT ALTERNATEALUM ALUMINUMAMP AMPEREAP ACCESS PANELAPD AIR PRESSURE DROPAPPROX APPROXIMATEARCH ARCHITECT/ARCHITECTURALAS AIR SEPARATORATD AIR TRANSFER DUCTAUTO AUTOMATICAVG AVERAGEAWT AVERAGE WATER TEMPERATUREAXF AXIAL FAN
BB BASEBOARD RADIATIONBDD BACK DRAFT DAMPERBF BOILER FEED WATERBG BOTTOM GRILLE (3"-12" ABOVE FLOOR)BHP BRAKE HORSEPOWERBLDG BUILDINGBMS BUILDING MANAGEMENT SYSTEMBOD BOTTOM OF DUCTBR BOTTOM REGISTER (3"-12" ABOVE FLOOR)BSMT BASEMENTBTU BRITISH THERMAL UNITBTUH BRITISH THERMAL UNIT PER HOUR
CA COMPRESSED AIRCAP CAPACITYCC COOLING COILCCW COUNTER CLOCKWISECD CONDENSATE DRAINCENTRIF CENTRIFUGALCF CUBIC FEETCFH CUBIC FEET PER HOURCFM CUBIC FEET PER MINUTECH CABINET HEATERCHR CHILLERCHWR CHILLED WATER RETURNCHWS CHILLED WATER SUPPLYCI CAST IRONCL CENTER LINECLG COOLINGCO CLEAN OUTCO2 CARBON DIOXIDE COMP COMPRESSORCONC CONCRETECONN CONNECTIONCONST CONSTRUCTIONCONT CONTINUOUS, CONTINUATIONCONTR CONTRACTORCONV CONVECTORCP CONTROL PANELCT COOLING TOWERCU CONDENSING/ER UNITCU FT CUBIC FEETCV CONSTANT VOLUME CV CONSTANT VOLUMECWR CONDENSER WATER RETURNCWS CONDENSER WATER SUPPLY
D DRAIN OR DRYERDB DECIBEL OR DRY BULB TEMPERATUREDDC DIRECT DIGITAL CONTROLDEG.F DEGREE FAHRENHEITDEMO DEMOLISHDG DOOR GRILLEDIA DIAMETERDIAG DIAGONALDIFF DIFFUSERDIM DIMENSIONDISCH DISCHARGEDN DOWNDP DIFFERENTIAL PRESSUREDPDT DOUBLE POLE, DOUBLE THROWDPST DOUBLE POLE, SINGLE THROWDTR DUAL TEMPERATURE RETURNDTS DUAL TEMPERATURE SUPPLYDWDI DOUBLE WIDTH, DOUBLE INLETDWG DRAWINGDX DIRECT EXPANSION
E/P ELECTRIC-PNEUMATICEA EXHAUST AIREAT ENTERING AIR TEMPERATUREEBB ELECTRIC BASEBOARD HEATEREC EXPANSION COMPENSATOR/JOINTECWR EQUIPMENT COOLING WATER RETURNECWS EQUIPMENT COOLING WATER SUPPLYEDB ENTERING DRY BULB TEMPERATUREEER ENERGY EFFICIENCY RATIOEF EXHAUST FANEFF EFFICIENCYEHC ELECTRIC HEATING COILEL/ELEV ELEVATIONELEC ELECTRIC/ELECTRICALELEM ELEMENTELEV ELEVATOREMD END OF MAIN DRIP (STEAM)EMER EMERGENCYENG ENGINEERENT ENTERINGERP ELECTRIC RADIANT PANELESP EXTERNAL STATIC PRESSUREEST ESTIMATEET EXPANSION TANKETO ETHYLENE OXIDEEUH ELECTRIC UNIT HEATEREV EXHAUST AIR VALVEEVAP EVAPORATOREVF FUME HOOD EXHAUST AIR VALVEEVL LAB EXHAUST AIR VALVE
H HUMIDISTAT OR HUMIDIFIERHC HEATING COILHEPA HIGH EFFICIENCY PARTICULATE AIR FILTERHG HOT GASHL HIGH LIMITHORIZ HORIZONTALHP HORSEPOWER OR HEAT PUMPHPR HIGH PRESSURE CONDENSATE RETURNHPS HIGH PRESSURE STEAMHR HOURHRC HEAT RECOVERY COILHT HEIGHTHTG HEATINGHTWR HIGH TEMPERATURE WATER RETURNHTWS HIGH TEMPERATURE WATER SUPPLYHUM HUMIDIFIERHVAC HEAT, VENTILATION, & AIR CONDITIONINGHVU HEATING & VENTILATING UNITHWR HOT WATER RETURNHWS HOT WATER SUPPLYHX HEAT EXCHANGERHZ HERTZ
ID INSIDE DIAMETERIN OR " INCHESIN W.C. INCHES WATER COLUMNIN W.G. INCHES WATER GAUGEINSUL INSULATIONINT INTERNAL
KW KILOWATTKWH KILOWATT HOUR
LAT LEAVING AIR TEMPERATURELBS POUNDSLDB LEAVING DRY BULB TEMPERATURELF LINEAR FEETLPG LIQUID PETROLEUM GASLPR LOW PRESSURE CONDENSATE RETURNLPS LOW PRESSURE STEAMLRA LOCKED ROTOR AMPERESLVG LEAVINGLVR LOUVERLWB LEAVING WET BULB TEMPERATURELWT LEAVING WATER TEMPERATURE
M MOTOR OPERATORMAINT MAINTENANCEMAU MAKE-UP AIR UNITMAX MAXIMUMMBH THOUSAND BTU PER HOURMCC MOTOR CONTROL CENTERMECH MECHANICALMERV MINIMUM EFFICIENCY REPORTING VALUEMEZZ MEZZANINEMFR MANUFACTURERMIN MINIMUMMISC MISCELLANEOUSMPR MEDIUM PRESSURE CONDENSATE RETURNMPS MEDIUM PRESSURE STEAMMTD MOUNTED
N.C. NORMALLY CLOSEDN.O. NORMALLY OPENNC NOISE CRITERIANIC NOT IN CONTRACTNO. OR # NUMBERNR NOT REQUIREDNTS NOT TO SCALENV NATURAL VENTILATION
OA OUTSIDE AIROAI OUTSIDE AIR INTAKEOBD OPPOSED BLADE DAMPEROED OPEN END DUCTOFCI OWNER FURNISHED/CONTRACTOR INSTALLEDOFOI OWNER FURNISHED/OWNER INSTALLEDOH OVERHEADOPNG OPENING
∆P/DP DIFFERENTIAL PRESSUREP PUMPP/E PNEUMATIC-ELECTRIC SWITCHPA PASCALPCD PUMPED CONDENSATE DISCHARGE/RETURNPCF POUNDS PER CUBIC FOOTPCWR PROCESSED CHILLED WATER RETURNPCWS PROCESSED CHILLED WATER SUPPLYPD PRESSURE DROPPF PROPELLER FANPG PRESSURE GAUGE
PH PHASEPLBG PLUMBINGPRESS PRESSUREPROP PROPELLERPRV PRESSURE REDUCING VALVEPSF POUNDS PER SQUARE FOOTPSI POUNDS PER SQUARE INCHPSIA POUNDS PER SQUARE IN ABSOLUTEPSIG POUNDS PER SQUARE IN GAUGE
QTY QUANTITY
R RETURNRA RETURN AIRRAD RADIATIONRAF RETURN AIR FANREBAL REBALANCEREG REGISTERREV REVISEDRH RELATIVE HUMIDITYRHC REHEAT COILRHG REFRIGERANT HOT GASRL REFRIGERANT LIQUIDRM ROOMRO RELIEF OPENINGRP RADIANT PANELRPM REVOLUTIONS PER MINUTERS REFRIGERANT SUCTIONRTU ROOF TOP UNITRV REFRIGERANT VENT OR RELIEF VALVE (VENT)RV RETURN AIR VALVE
S/W SUMMER-WINTERSA SUPPLY AIR OR SOUND ATTENUATORSCR SILICON CONTROLLED RECTIFIERSD SMOKE DETECTORSENS SENSIBLE LOADSF SMOKE-FIRE DAMPERSHT SHEETSM SMOKE DAMPERSOL SOLENOIDSP STATIC PRESSURESQ SQUARESQ. FT. SQUARE FEETSS STAINLESS STEELSTD STANDARDSTL STEELSTM STEAMSTRUC STRUCTURE/STRUCTURALSV SUPPLY AIR VALVESWSI SINGLE WIDTH, SINGLE INLET
3SF 3 HOUR SMOKE FIRE DAMPERTC TEMPERATURE CONTROLTD TRANSFER DUCTTEMP TEMPERATURETL TOTAL LOADTO TRANSFER OPENINGTSP TOTAL STATIC PRESSURETSTAT THERMOSTATTU TERMINAL UNITTYP TYPICAL
UGRD UNDERGROUNDUH UNIT HEATER (HYDRONIC OR STEAM)UNO UNLESS NOTED OTHERWISEUPS UNINTERUPTIBLE POWER SUPPLYUV UNIT VENTILATOR
V VOLT OR VENTVAV VARIABLE AIR VOLUMEVD VOLUME DAMPERVEL VELOCITYVERT VERTICALVI VIBRATION ISOLATIONVIF VERIFY IN FIELDVOL VOLUMEVR VACUUM RETURNVRV VARIABLE REFRIGERANT VOLUMEVSD VARIABLE SPEED DRIVEVTR VENT THROUGH ROOF
W WATTW.G. WATER GAGEW/ WITHW/O WITHOUTWB WET BULB TEMPERATUREWC WATER COLUMNWMS WIRE MESH SCREENWPD WATER PRESSURE DROPWT WEIGHTWTR WATER
EWB ENTERING WET BULB TEMPERATUREEWT ENTERING WATER TEMPERATUREEXH EXHAUSTEX EXISTINGEXIST EXISTINGEXT EXTERNAL
F FAHRENHEITF&T FLOAT & THERMOSTATIC STEAM TRAPF.D. FLOOR DRAINFA FREE AREAFC FORWARD CURVEDFCU FAN COIL UNITFD FIRE DAMPERFF FINAL FILTERFH FUME HOODFLA FULL LOAD AMPERESFLEX FLEXIBLEFLR FLOORFLT FLASH TANKFM FLOW METERFOG FUEL OIL GAUGEFOR FUEL OIL RETURNFOS FUEL OIL SUPPLYFOV FUEL OIL VENTFP FIRE PROTECTIONFPB FAN POWERED TERMINAL UNITFPM FEET PER MINUTEFPS FEET PER SECONDFR FINNED RADIATIONFSTAT FREEZESTATFT FEETFV FACE VELOCITY
G NATURAL GASGA GAUGEGAL GALLONGCWR GEOTHERMAL CONDENSER WATER RETURNGCWS GEOTHERMAL CONDENSER WATER SUPPLYGD GRAVITY DAMPERGPH GALLONS PER HOURGPM GALLONS PER MINUTEGR GLYCOL RETURNGRL GRILLEGRV GRAVITY RELIEF VENTGS GLYCOL SUPPLYGV GRAVITY VENTILOR OR NATURAL GAS VENT
UH Sx x
x x
UNIT HEATER
AIR FLOW CFM
MODEL {
MOTOR HP @ 120/1/60
S-HORIZONTALP-VERTICAL
TOTAL MBHAT 180º F EWT160º F LWT65º F EAT
GPM
HOT WATERUNIT HEATER
CH Fx x
x x
CABINETHEATER
AIR FLOW CFM@ MEDIUMSPEED
MODEL
MOTOR HP @ 120/1/60
N=INVERTED RECESSED WALL HUNGB=VERTICAL CABINETF=VERTICAL WALL HUNG CABINETH=VERTICAL FULLY RECESSEDE=HORIZONTAL FULLY RECESSEDD=HORIZONTAL CABINET
TOTAL MBHAT 180º F EWT160º F LWT65º F EAT
GPM
HOT WATERCABINET HEATER
FR Ax x
x x
FINNEDRADIATION
SIZE (MBH/FT.)
TYPE
ACTIVE LENGTH (FT.)
TOTAL MBHAT 180º F EWT160º F LWT65º F EAT
GPM
HOT WATERFINNED TUBE
C W
L x W x Dx x
CONVECTOR
DIMENSIONS:LENGTH x WIDTH x DEPTHTOTAL MBH
AT 180º F EWT160º F LWT65º F EAT
GPM
HOT WATERCONVECTOR
MODEL {W=WALL HUNGR=FULLY RECESSED
RP Xx x
HOT WATERRADIANT PANEL
LENGTH
TOTAL MBHAT 180º F EWT160º F LWT65º F EAT
GPM
HOT WATERRADIANT PANEL
EUH Sx x
x x
UNIT HEATER
AIR FLOW CFM
MODEL {
MOTOR HP @ 120/1/60
S-HORIZONTALP-VERTICAL
TOTAL MBH KW
ELECTRICUNIT HEATER
ECH Fx x
x x
CABINETHEATER
AIR FLOW CFM@ MEDIUMSPEED
MODEL
MOTOR HP @ 120/1/60
N=INVERTED RECESSED WALL HUNGB=VERTICAL CABINETF=VERTICAL WALL HUNG CABINETH=VERTICAL FULLY RECESSEDE=HORIZONTAL FULLY RECESSEDD=HORIZONTAL CABINET
TOTAL MBHAT 180º F EWT160º F LWT65º F EAT
KW
ELECTRICCABINET HEATER
TP
T
1
M0101
SUPPLY DUCT RISE
RETURN DUCT RISE
SECTION INDICATOR TOP INDICATESSECTION NUMBER BOTTOMINDICATES SHEET NUMBER
VARIABLE SPEED DRIVE
EXHAUST DUCT RISE
OPPOSED BLADE VOLUMEDAMPERS
SAFETY/RELIEF VALVE
PRESSURE REDUCING VALVE
CHECK VALVE (SHOWN W/FLOW)
CONTROL VALVE (3-WAY)
CONTROL VALVE (2-WAY)
BALANCING VALVE
SOLENOID VALVE
DIRECTION OF FLOW
UNION
PIPE ANCHOR
PIPE GUIDE
OR FLEXIBLE DUCT
SINGLE LINE DUCT RISE OR DROP
SINGLE LINE EXHAUST DUCT
ELBOW WITH TURNING VANES
SINGLE LINE RETURN DUCT
SINGLE LINE SUPPLY DUCT
T
R
S
ELECTRICAL CONNECTION (BY DIVISION 23)
ROOM PRESSURIZATION MONITOR
FREEZESTAT
FLOW SWITCH
RELAY
HUMIDITY SENSOR
SWITCH
STRAINER W/BLOWDOWN VALVE
SENSING ELEMENT - AIR STREAM
SENSING ELEMENT - LIQUID SEPARABLE WELL
FLEXIBLE CONNECTION
ROUND (DIAMETER)
TRAP
EXPANSION LOOP
EXPANSION JOINT
PIPING FLOW METER ANALOG OUTPUT
DIGITAL OUTPUT
DIGITAL INPUT
ELECTRICAL CONNECTION (BY DIVISION 26)
PILOT LIGHT-LETTER INDICATESCOLOR:
ANALOG OUTPUT, PNEUMATIC
ELECTRIC-PNEUMATIC SWITCH
PNEUMATIC-ELECTRIC SWITCH
SMOKE
ANALOG INPUT, PRESSURE
ANALOG INPUT, TEMPERATURE
FIRESTAT
SMOKE DETECTOR
DUCT SMOKE DETECTOR
G - GREENY - YELLOWR - RED
THERMOSTAT WITH LOCKINGCOVER
VOLUME DAMPER
CURRENT SENSOR
BACKDRAFT DAMPER
PUMP
FIRE, SMOKE/FIRE, OR SMOKE DAMPER
SUPPLY DUCT DROP
RETURN DUCT DROP
EXHAUST DUCT DROP
EXISTING SINGLE LINE DUCT
CAPPED DUCTWORK
CAPPED PIPING OR SINGLE DUCTWORK
OR
FD,SF, OR SM
EXISTING ITEM TO BE REMOVED
VALVE
"ØDUCT OFF-SET DN (IN DIRECTION OF FLOW)
DUCT OFF-SET UP (IN DIRECTION OF FLOW)
RECTANGULAR DUCT DIMENSIONS(SIZE IN INCHES, FIRST DIMENSION IS SHOWN)
ROUND DUCT DIMENSIONS (DIAMETER)
OVAL DUCT DIMENSIONS(SIZE IN INCHES, FIRST DIMENSION IS SHOWN)
MOTORIZED DAMPER
T TEMPERATURE SENSOR (IN DUCT OR PIPE)
CARBON DIOXIDE SENSOR
P PRESSURE GAGE
OR
PUSH BUTTONPB
200-5
200-2SUPPLY AIR DEVICE -(REFER TO SCHEDULE FOR SIZE)FIRST NO. CFM, SECOND NO. TYPE(REFER TO SPECIFICATION FOR AIR DEVICE TYPE)
LINEAR DIFFUSER
200-1410x8
SUPPLY/ RETURN/EXHAUST SIDEWALL GRILLE-FIRST NO. CFM, SECOND NO. TYPEBOTTOM NO. WIDTH BY HEIGHT OF GRILLE(REFER TO SPECIFICATION FOR AIR DEVICE TYPE)
RETURN AIR DEVICE -(REFER TO SCHEDULE FOR SIZE)FIRST NO. CFM, SECOND NO. TYPE(REFER TO SPECIFICATION FOR AIR DEVICE TYPE)
EXHAUST AIR DEVICE -(REFER TO SCHEDULE FOR SIZE)FIRST NO. CFM, SECOND NO. TYPE(REFER TO SPECIFICATION FOR AIR DEVICE TYPE)
VSD
RECTANGULAR WYE DUCT FITTING
AIR FLOW MEASURING STATION
OCCUPANCY SENSOR
EXISTING HVAC PIPE
NEW HVAC PIPE
EXISTING HVAC PIPE TO BE REMOVED
PIPE ELBOW DOWN
PIPE ELBOW UP
POINT OF CONNECTION (NEW TO EXISTING)
PIPE BOTTOM DROP
CLEANOUT (CO)
PIPE RISE OR DROP
ANALOG INPUT
TEMPERATURE SENSOR
OXYGEN SENSOR
OFF
ONAUTOSTARTER
HOSE DRAIN VALVE WITH CAP
MANUAL AIR VENT
PRESSURE/TEMPERATURE TEST PORT
-ADAPT TO PROJECT CONDITIONS
ANALOG INPUT, FLOW
FIRE, SMOKE/FIRE, OR SMOKE DAMPERIN RISER
FD,SF, OR SM
NEW EQUIPMENT
EXISTING EQUIPMENT
CALLOUT INDICATOR TOP INDICATESNUMBER ON THE SHEET BOTTOMINDICATES SHEET NUMBER
NEW DUCT
EXISTING DUCT
DEMOED DUCT
TRIPLE DUTY VALVE
FM26
AI
AIF
AIP
AIT
AO
AOP
BDD
1
M0101
CO
CO²
CS
DI
DO
24x12 OV
24x12
24"Ø
DN
UP
DE
PE
200-5
EX-XXX
EXISTING
EQUIPMENT TYPE
FIRE
OR
FM
FS
F
H
250-7
CFM
TYPE
LENGTH
NO. OF SLOTS
SLOT WIDTH (INCHES)4LF-2-1
XXX-1
TYPE NO.
EQUIPMENT TYPE
OS
O²
EP
G
1. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR ALLCEILING AIR DEVICE LOCATIONS.
2. REFER TO ARCHITECTURAL ELEVATION DRAWINGS FOR LOCATION OFWALL MOUNTED MECHANICAL ITEMS.
3. LOCATE ALL DUCT BALANCING DAMPERS ABOVE ACCESSIBLECEILINGS, OR PROVIDE ACCESS DOORS. MINIMUM ACCESS DOOR SIZESHALL BE 18x18 UNLESS OTHERWISE APPROVED BY ENGINEER.
4. DUCTWORK NOT SIZED IS GENERALLY SMALLER BRANCH ZONEDUCTS. COORDINATE ELEVATIONS AND PROVIDE NECESSARY OFFSETS.DUCTWORK SHALL BE SIZED PER THE BRANCH DUCTWORK SCHEDULE.
5. PROVIDE VOLUME DAMPERS AT ALL SUPPLY, RETURN AND EXHAUSTDUCT BRANCH TAKE-OFFS. SEE DUCT CONSTRUCTION DETAILS.
6. BLANK-OFF AREAS OF LOUVERS NOT USED WITH 20 GAGE SHEETMETAL DOUBLE WALL BLANK-OFF PANEL INSULATED WITH 2" RIGIDFIBERBOARD. SEAL AIR TIGHT.
7. INSTALL RIGID 1"x1" GALVANIZED STEEL WIRE MESH AT ALL OPENENDED DUCTS IN OCCUPIED AREAS OR EXPOSED TO VIEW.
8. ALL HWS AND HWR PIPING SERVING RADIATION SHALL BECONCEALED IN WALLS OR FLOOR UNLESS OTHERWISE NOTED.
9. COORDINATE SCHEDULE FOR HOOKUPS TO EXISTING SYSTEM ANDREMOVAL OR RELOCATION OF EQUIPMENT WITH THE OWNER. PERFORMTHIS WORK AT SUCH TIMES TO ENSURE THAT PERIODS OF SHUTDOWNWILL BE ACCEPTABLE TO THE OWNER.
10. FILL HEATING GLYCOL SYSTEM WITH 40% PROPYLENEGLYCOL/WATER SOLUTION.
11. VERIFY EXACT LOCATION OF CONNECTION POINTS (NEW TO EXISTING)IN FIELD PRIOR TO CONSTRUCTION.
12. COORDINATE INSTALLATION OF NEW DUCTWORK AND PIPING WITHEXISTING BUILDING STRUCTURE, DUCTWORK, PIPING, ELECTRICAL CONDUIT,LIGHTING, ETC.
13. RELOCATE EXISTING DUCTWORK AND/OR PIPEWORK IN EXISTINGCEILING SPACES TO ACCOMMODATE ALL RENOVATIONS AND ADDITIONS.
14. TAKE DOWN AND REINSTALL EXISTING CEILINGS IN ALL AREASWHERE MECHANICAL WORK IS INDICATED AND EXISTING CEILINGS REMAIN.REFER TO ARCHITECTURAL REFLECTED CEILING PLAN DRAWINGS FORLOCATIONS WHERE EXISTING CEILINGS REMAIN. REPLACE CEILING TILESDAMAGED DURING WORK.
15. INSTALL ALL FLOOR MOUNTED HVAC EQUIPMENT, INCLUDING AHUS,PUMPS, CHILLERS, ETC. ON 4" MINIMUM HEIGHT CONCRETE HOUSEKEEPINGPAD. EXTEND PAD MINIMUM 4" BEYOND EQUIPMENT AT ALL SIDES.
16. PATCH ALL WALLS, FLOORS, CEILINGS, AND ROOFS TO MATCHEXISTING IN ALL CASES WHERE EXISTING WALLS, FLOORS, CEILINGS ANDROOFS REMAIN AND HVAC DEMOLITION IS INDICATED.
17. THIS PROJECT CONSISTS OF MULTIPLE PHASES OF CONSTRUCTIONOVER A SPECIFIED TIME PERIOD. PROVIDE ALL WORK NECESSARY TO KEEPEXISTING SYSTEMS IN SAFE OPERATION. PROVIDE ISOLATION (SHUT-OFF)VALVES AT ALL CONNECTION POINTS TO EXISTING SYSTEMS.
18. ALL HYDRONIC BRANCH PIPING SHALL BE 3/4" UNLESS NOTEDOTHERWISE.
19. PROVIDE POSITIVE DRAINAGE OF ALL PLENUMS CONNECTED TOOUTSIDE LOUVERS. WATERPROOF BOTTOM OF PLENUMS. SLOPE PLENUMBOTTOM TO LOUVER OR PROVIDE DRAIN POINTS WITH DISCHARGE TO DRAIN.
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EM
POWER FOR BUILDING 2J
MEDICAL EQUIPMENT
of 20
2J
SYMBOLS, ABBREVIATIONS, AND
GENERAL NOTES
M0001MB BRM
ABBREVIATIONS
LEGENDS
SYMBOLS GENERAL NOTES
UTSR
QPO
N
2
1.6
1.3
0
1
20,000 GALLONUNDERGROUND
DIESEL TANK
EXISTING 3" DIESELFUEL RETURN
6" GWS/R
2" FOS
EXISTINGSTAINLESS STEELFLUE VENTS TOATMOSPHERE
EXISTING FUEL OILVENT TOATMOSPHERE
EXISTING FUEL OILVENT TO ATMOSPHERE
6" GWS/R
6" GWS/R
NEW STAINLESS STEEL FLUEVENTS TO ATMOSPHERE;SEE 2 / M0401
EXISTING REMOTEGENERATOR COOLING UNIT
SAW CUT CONCRETE DRIVEWAYTO CONNECT NEW 1" FUEL OILRETURN LINE TO EXISTING 3" FUELOIL RETURN LINE UNDERGROUND.PATCH CONCRETE DRIVEWAY TOMATCH EXISTING.
NEW 1" FUEL OILSUPPLY LINE
CONNECTED TOEXISTING EXISTING
CONDENSERFOR IT ROOM
EXISTINGREMOTEGENERATORCOOLING UNIT
16"Ø
16"Ø
16"Ø
16"Ø 16"Ø
16"Ø
12"Ø
12"Ø
12"Ø
12"Ø
12"Ø
700 kWGENERATOR
700 kWGENERATOR
700 kWGENERATOR
700 kWGENERATOR
700 kWGENERATOR
DAYTANK
DAYTANK
DAYTANK
DAYTANK
DAYTANK
NEW GENERATOR
3" UNDERGROUNDFUEL OIL RETURN
EXISTING BAS PANEL; PROVIDE NEW BAS POINT ANDEND ANY AND ALL PROGRAMMING AS REQUIREDFROM THE PARALLELING SWITCHGEAR MASTERCONTROL TO THE BAS PANEL TO SIGNAL AHU FANSHUTDOWN PRIOR TO GENERATOR START.
EXISTING REF. LINES
TEMPORARILY SUPPORTALL SERVICES ASREQUIRED TO REPLACESTEEL SUPPORTS
1" FUEL OILRETURN LINE
1" FUEL OILSUPPLY LINE
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EM
POWER FOR BUILDING 2J
MEDICAL EQUIPMENT
of 20
2J
FUNCTIONAL BASEMENT LEVEL
PIPING PLAN
M0101MB BRM
1/8" = 1'-0"1
M-HP01 - FUNCTIONAL BASEMENT LEVEL PIPING PLAN
TO EXISTINGGENERATORDAY TANKS
EXISTINGUNDERGROUND FUEL
TANK
NEW GENERATORDAY TANK
TO NEWGENERATORDAY TANK
PUMPED RETURN
53.6 GAL/HR
NEW CONNECTIONTO EXISTING FUELOIL RETURN LINEEXISTING FUEL OIL
PUMPING PACKAG
3 HP PUMP
3 HP PUMP
TERMINATE DUCTWITH 45° CUTOFF
EXISTING OUTDOORCONCRETE WALL
CAP EXHAUST ANDINCLUDE DRAIN
TEE EXHAUSTAT WALL
FLUE EXHAUSTFROM GENERATOR
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EM
POWER FOR BUILDING 2J
MEDICAL EQUIPMENT
of 20
2J
RISER DIAGRAMS & DETAILS
M0401MB BRM
NTS1
FUEL RISER DIAGRAMNTS
2GENERATOR FLUE EXHAUST TEE DETAIL
BUILDING CODE: INTERNATIONAL BUILDING CODE (IBC2009)
OCCUPANCY CATEGORY II
SUPERIMPOSED DEAD LOADS
CEILINGS, MECHANICAL ITEMS SUSPENDED FROM STRUCTURAL FRAMING:10 PSF
SUPERIMPOSED LIVE LOADS (INCLUDING PARTITION LOADS)
MECHANICAL ELECTRICAL AND TELECOM ROOMS: 150 PSF
SNOW LOADS
1. GROUND SNOW LOAD, Pg = 5 PSF
2. SNOW EXPOSURE FACTOR, Ce = 0.9
3. THERMAL FACTOR, Ct = 1.0
4. SNOW IMPORTANCE FACTOR, I = 1.2
5. FLAT ROOF SNOW LOAD, Pf = 3.8 PSF
WIND LOADS
1. BASIC WIND SPEED = 90 MPH
2. WIND IMPORTANCE FACTOR = 1.15
3. WIND EXPOSURE CATEGORY = B
4. INTERNAL PRESSURE COEFFICIENT = ±0.18
5. WIND PRESSURE COMPONENTS AND CLADDING:INTERIOR ZONE: P = +6.9 PSF, P = -16.8 PSFEND ZONE: P = +6.9 PSF, P = -42.3 PSF
(PLUS AND MINUS SIGNS SIGNIFY PRESSURES ACTING TOWARD AND AWAY FROM THESURFACES, RESPECTIVELY. END ZONES EXTEND FROM CORNERS OF BUILDING ADISTANCE EQUAL TO 10% OF LEAST HORIZONTAL BUILDING DIMENSION, BUT NOT LESSTHAN 3 FT.)
6. WIND LOADS ARE BASED ON ASCE 7-05, METHOD 2
EARTHQUAKE DESIGN DATA
1. SEISMIC IMPORTANCE FACTOR, I = 1.5
2. SPECTRAL RESPONSE ACCELERATIONSSs = 0.092S1 = 0.051
3. SITE CLASSIFICATION = D
4. DESIGN SPECTRAL RESPONSE ACCELERATIONSSDS = 0.098SD1 = 0.051
5. SEISMIC DESIGN CATEGORY = C
SEISMIC BRACING OF ARCHITECTURAL, MECHANICAL AND ELECTRICAL COMPONENTS
1. FOR SEISMIC DESIGN CATEGORY C COMPONENT BRACING REQUIREMENTS AREAS FOLLOWS:
MECHANICAL/ELECTRICAL COMPONENTS:
Ip = 1.5 REQUIRED
M1EMPLOY A LICENSED SURVEYOR TO VERIFY EXISTING DIMENSIONS, FLOOR ELEVATIONS, AND FLOOR-TO-FLOORHEIGHTS BEFORE ORDERING, DETAILING, FABRICATING, OR ERECTING STRUCTURAL STEEL. THIS INFORMATION MUST BECONFIRMED AT LOCATIONS WHERE NEW FLOORS AND ROOFS MEET EXISTING CONSTRUCTION.
M2CONSULT THE ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR LOCATION AND SIZE OFCHASES, INSERTS, OPENINGS, SLEEVES, WASHES, DRIPS, REVEALS, DEPRESSIONS, EQUIPMENT PADS AND OTHERPROJECT REQUIREMENTS. COMBINE THE REQUIREMENTS INTO THE SHOP DRAWINGS AND THE WORK. PROVIDESTRUCTURAL FRAMING PER TYPICAL DETAILS AS REQUIRED AT FLOOR AND ROOF OPENINGS WHERE STRUCTURALFRAMING IS NOT SHOWN.
M3THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION OF CONSTRUCTION OF THE PROJECT ANDTHEN, ONLY TO SUPPORT THE DESIGN LOADS INDICATED. THE CONTRACTOR IS RESPONSIBLE FOR MEANS, METHODSAND SEQUENCE OF CONSTRUCTION AND FOR THE ADEQUACY OF THE STRUCTURE TO SUPPORT LOADS OCCURRINGDURING CONSTRUCTION. FURNISH TEMPORARY BRACING, SHORING, AND/OR SUPPORT AS REQUIRED.
M4CHECK DIMENSIONS AGAINST THE REQUIREMENTS OF OTHER CONTRACT DOCUMENTS. RESOLVE APPARENTINCONSISTENCIES IN THE CONTRACT DOCUMENTS WITH THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH WORK.
M5DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE NOT SPECIFICALLYSHOWN, USE DETAILS OF SIMILAR CONSTRUCTION, SUBJECT TO APPROVAL BY THE ENGINEER.
M6WHEREVER THERE IS CONFLICT BETWEEN DETAILS OR TWO DETAILS APPLYING TO THE SAME CONDITION, THEENGINEER WILL HAVE SOLE AUTHORITY TO DETERMINE WHICH DETAIL IS THE MOST APPROPRIATE FOR THE CONDITION.
M7PROMPTLY NOTIFY THE ENGINEER OF ANY STRUCTURAL MEMBER CALLED OUT ON THE ARCHITECTURAL, MECHANICAL,PLUMBING OR ELECTRICAL DRAWINGS THAT IS NOT IDENTIFIED ON THE STRUCTURAL DRAWINGS. DESIGN OF THESEMEMBERS WILL BE PROVIDED AS NECESSARY BY THE STRUCTURAL ENGINEER UPON NOTIFICATION.
M8THE GENERAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE LOCATION AND PLACEMENT OF INSERTS,HANGERS AND OTHER MISCELLANEOUS ITEMS REQUIRED FOR THE SUPPORT OF MECHANICAL, ELECTRICAL ANDPLUMBING ITEMS SUSPENDED FROM THE STRUCTURE.
M9DO NOT MAKE MODIFICATIONS, ALTERATIONS OR REPAIRS TO THE STRUCTURE WITHOUT PRIOR REVIEW BY THESTRUCTURAL ENGINEER. SUBMIT DETAILS AND CALCULATIONS PREPARED BY A PROFESSIONAL ENGINEER REGISTEREDIN STATE WHERE PROJECT IS LOCATED AND EMPLOYED BY CONTRACTOR.
S1A QUALITY CONTROL PROGRAM OF SHOP AND FIELD TESTING AND INSPECTION WILL BE PERFORMED ONSTRUCTURAL STEEL FABRICATION, ERECTION, AND CONNECTIONS IN ACCORDANCE WITH THESPECIFICATIONS. SCHEDULE WORK AND PROVIDE ACCESS TO ALLOW THE TESTING REQUIREMENTS TOBE COMPLETED.
S2DETAIL, FABRICATE AND ERECT STRUCTURAL STEEL IN CONFORMANCE WITH THE AISC SPECIFICATIONSAND CODES, LATEST EDITIONS.
S3PERFORM WELDING USING CERTIFIED WELDERS AND IN ACCORDANCE WITH THE AWS "STRUCTURALWELDING CODE - STEEL", LATEST EDITION. COMPLY WITH AISC SPECIFICATION FOR MINIMUM FILLETWELD SIZES, BUT DO NOT USE LESS THAN A 3/16 INCH FILLET UNLESS SPECIFICALLY NOTED ON THEDRAWINGS.
S4SUBMIT ENGINEERED AND CHECKED SHOP DRAWINGS TO THE ARCHITECT/ ENGINEER FOR REVIEW.SHOW SHOP FABRICATION DETAILS, FIELD ASSEMBLY DETAILS, AND ERECTION DIAGRAMS FORSTRUCTURAL STEEL. SCHEDULE SUBMISSIONS TO ALLOW ADEQUATE TIME FOR REVIEW PRIOR TOFABRICATION.
S5DETAIL BEAMS FRAMING INTO CONCRETE WALLS, BEAMS OR COLUMNS TO ALLOW FOR HORIZONTALFIELD TOLERANCES AND THERMAL MOVEMENT. PROVIDE CONNECTION DETAILS REQUIRED BY THESPECIFIC CONSTRUCTION SEQUENCES.
S6AFTER FABRICATION, CLEAN STEEL OF RUST, LOOSE MILL SCALE, DIRT, OIL, GREASE OR OTHERFOREIGN MATERIALS.
S7REFER TO THE ARCHITECTURAL DRAWINGS FOR THE REQUIRED FIRE RATINGS AND UL ASSEMBLYNUMBERS.
S8DO NOT FIELD CUT STRUCTURAL STEEL UNLESS REVIEWED AND APPROVED BY THEARCHITECT/ENGINEER IN WRITING. CLEARLY INDICATE STEEL MEMBER OPENINGS REQUIRED ON THESHOP DRAWINGS. ALL COSTS FOR PROVIDING PENETRATIONS IN THE FIELD, INCLUDING MEMBERREINFORCING, IS THE RESPONSIBILITY OF THE CONTRACTOR.
S9ERECTION PROCEDURES, SEQUENCES AND COORDINATION OF WORK WITH OTHER TRADES IS THERESPONSIBILITY OF THE CONTRACTOR. PROVIDE ADDITIONAL STEEL REQUIRED FOR ERECTIONPURPOSES AT NO COST TO THE OWNER. REMOVE THIS ADDITIONAL STEEL UNLESS DIRECTEDOTHERWISE BY THE OWNER IN WRITING.
S10PROVIDE TEMPORARY BRACING AND SHORING AS REQUIRED FOR THE SAFETY, STABILITY ANDALIGNMENT OF THE STRUCTURE. LEAVE TEMPORARY BRACING IN PLACE UNTIL THE PERMANENTSTRUCTURAL LATERAL LOAD RESISTING SYSTEM IS COMPLETE, INCLUDING FLOOR AND ROOFDIAPHRAGMS. PERFORM FINAL BOLTING AND WELDING ONLY ON THOSE PORTIONS OF THE STRUCTURETHAT HAVE BEEN ALIGNED AND PLUMBED WITHIN THE SPECIFIED TOLERANCES.
S11THE TESTING AGENCY SHALL PROVIDE QUALITY CONTROL CONFORMING TO THE FOLLOWINGREQUIREMENTS:a. PERFORM FULL TIME VISUAL INSPECTION OF THE FIELD ERECTION OF 100% OF THE STRUCTURAL
ELEMENTS.b. VISUALLY INSPECT ALL ANCHOR-BOLT NUT INSTALLATION AND TIGHTENING.c. ROUTINELY MONITOR FIELD BOLTING PROCEDURES DURING BOLT INSTALLATION. VERIFY THAT
ALL BOLTS IN ALL CONNECTIONS ARE BROUGHT TO A "SNUG TIGHT" CONDITION WITH ALL POLIESOF THE CONNECTION IN FIRM CONTACT.
d. CHECK THAT ALL BOLTED CONNECTIONS ARE BEING INSTALLED IN ACCORDANCE WITH THEPROCEDURES OUTLINED IN THE RCSC "SPECIFICATION".
e. OBTAIN QUALIFICATIONS OF ALL WELDERS AND VERIFY ALL WELDING PROCEDURES, INCLUDINGTHE CONTRACTOR'S COMPLIANCE WITH PREHEAT, HWEATHER-PROTECTION, ELECTRODES, ANDWELDING SURFACE PREPARATION REQUIREMENTS.
f. VISUALLY INSPECT ALL FIELD WELDING OPERATIONS AND WELDS.g. MAGNETIC PARTICLE TESTING SHALL BE IN ACCORDANCE WITH ASTM E709 FOR A MINIMUM OF
20 PERCENT OF THE LENGTH OF ALL FIELD WELDS, AT RANDOM, FINAL PASS ONLY.
S12PROVIDE NEW MATERIAL CONFORMING TO THE FOLLOWING REQUIREMENTS FOR STRUCTURAL STEEL:
MEMBER GRADE
HOLLOW STRUCTURAL SECTIONS(RECTANGULAR AND ROUND) ASTM A500 GRADE B
BASE PLATES ASTM A36 UNO
ALL OTHER STEEL MEMBERS ASTM A36 UNO
HIGH STRENGTH BOLTS, ASTM A-325 OR A-490NUTS AND WASHERS (MIN. 3/4" DIAMETER)
ANCHOR RODS ASTM F1554 GRADE 36 UNO
STEEL SHAPE WELDING ELECTRODE E70XX
ADDL ADDITIONALADJ ADJACENTALT ALTERNATEALUM ALUMINUMAPPROX APPROXIMATEAR ANCHOR RODARCH ARCHITECTURALB PL BASE PLATEB/ BOTTOM OFBFR BLENDED FIBER REINFORCINGBLDG BUILDINGBLKG BLOCK (ING)BOT BOTTOMBRG BEARINGBSMT BASEMENTBTWN BETWEENCIP CAST-IN-PLACECJ CONTROL JOINTCL CENTER LINECLR CLEARCMU CONCRETE MASONRY UNITCO CLEAN OUTCOL COLUMNCONC CONCRETECONN CONNECT (ION)CONST JT CONSTRUCTION JOINTCONT CONTINUOUS OR CONTINUECS COLUMN STRIPCU YD CUBIC YARDDET DETAILDIA DIAMETERDIAG DIAGONALDIM DIMENSIONDL DEAD LOADDWG DRAWINGEA EACHEE EACH ENDEF EACH FACEEJ EXPANSION JOINTEL ELEVATIONELEC ELECTRICALELEV ELEVATOREOD EDGE OF DECKEOS EDGE OF SLABEQ EQUALES EACH SIDEEW EACH WAYEXIST EXISTINGEXP EXPANSIONEXT EXTERIORFD FLOOR DRAINFDTN FOUNDATIONFLR FLOORFP FULL PENETRATIONFS FAR SIDEFT FOOT/FEETFTG FOOTINGGA GAGEGALV GALVANIZEDGB GRADE BEAMGC GENERAL CONTRACTORHORIZ HORIZONTALHP HIGH POINTHS HIGH STRENGTHHSS HOLLOW STRUCTURAL SECTIONHT HEIGHTID INSIDE DIAMETERIF INSIDE FACEINFO INFORMATIONINSUL INSULATED (ION)INV INVERTJT JOINTk KIPSL ANGLELBS POUNDSLL LIVE LOADLLH LONG LEG HORIZONTALLLV LONG LEG VERTICALLP LOW POINTLSH LONG SIDE HORIZONTALLSV LONG SIDE VERTICALLTWT LIGHT WEIGHTLW LONG WAYMATL MATERIALMAX MAXIMUMMECH MECHANICALMEP MECHANICAL ELECTRICAL & PLUMBINGMFR MANUFACTURERMIN MINIMUMMISC MISCELLANEOUSMO MASONRY OPENINGMS MIDDLE STRIPNIC NOT IN CONTRACTNO NUMBERNOM NOMINALNS NEAR SIDENTS NOT TO SCALEOC ON CENTEROD OUTSIDE DIAMETEROF OUTSIDE FACEOPNG OPENINGPC PILE CAPPCC PRECAST CONCRETEPCF POUNDS PER CUBIC FOOTPEN PENETRATIONPL PLATEPSF POUNDS PER SQUARE FOOTPSI POUNDS PER SQUARE INCHPT POST TENSIONQTY QUANTITYR RADIUSRD ROOF DRAINREF REFERENCEREINF REINFORCE (D) (ING)REQD REQUIREDREV REVISIONRO ROUGH OPENINGSC SLIP CRITICALSECT SECTIONSIM SIMILARSJ SEISMIC JOINTSOG SLAB-ON-GRADESPEC SPECIFICATIONSSQ SQUARESST STAINLESS STEELSTD STANDARDSTIFF STIFFENERSTL STEELSTRUCT STRUCTURALSW SHORT WAYSYMM SYMMETRICALT/ TOP OFT&B TOP AND BOTTOMTHK THICK (NESS)TRANS TRANSVERSETYP TYPICALUNO UNLESS NOTED OTHERWISEVERT VERTICALVIF VERIFY IN FIELDW WIDE FLANGE SECTIONW/ WITHW/O WITHOUTWD WOODWP WORK POINTWT TEE SECTIONWWF WELDED WIRE FABRIC
C1A QUALITY CONTROL PROGRAM OF FIELD TESTING AND INSPECTION WILL BEPERFORMED BY THE TESTING AGENCY ON STRUCTURAL CONCRETE WORK.SCHEDULE WORK AND PROVIDE ACCESS TO ALLOW THE TESTING REQUIREMENTS TOBE COMPLETED. PROVIDE ADEQUATE NOTICE TO ALLOW THE TESTING AGENCY TOREVIEW PLACEMENT OF REINFORCEMENTS PRIOR TO PLACING CONCRETE.
C2SUBMIT ENGINEERED CONCRETE MIX DESIGNS, INCLUDING REQUIRED BACKUP DATA,FOR EACH TYPE OF CONCRETE PROPOSED FOR USE TO THE ARCHITECT/ ENGINEERFOR REVIEW. ALLOW ADEQUATE TIME FOR REVIEW PRIOR TO PERFORMING CONCRETEWORK.
C3DETAIL, FABRICATE, LABEL, SUPPORT AND PLACE CONCRETE REINFORCEMENT INACCORDANCE WITH ACI 315 "DETAILS AND DETAILING OF CONCRETE REINFORCEMENT"AND ACI 318 "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE", LATESTEDITIONS.
C4SUBMIT DETAILED SHOP DRAWINGS INDICATING REINFORCEMENT SIZE, SPACING ANDPLACEMENT TO THE ARCHITECT/ENGINEER FOR REVIEW PRIOR TO FABRICATION.INCLUDE DETAILS AND LOCATIONS OF CURBS, CONSTRUCTION JOINTS, SLABDEPRESSIONS, SLEEVES, OPENINGS, ETC.
C5PERFORM CONCRETE COMPRESSION STRENGTH TESTING PER ASTM C31 AND C39.SAMPLE CONCRETE FOR TESTING SPECIMENTS AT THE POINT OF DEPOSIT INACCORDANCE WITH ASTM C172. TESTING SHALL CONSIST OF ONE SET OF 3 CYLINDERSMADE FROM A SINGLE SAMPLING FOR EACH TRUCK OR EACH 50 CUBIC YARDS OFCONCRETE PLACED EACH DAY. ALL TEST SPECIMENS ARE TO BE LABORATORY-CURED.TEST AS FOLLOWS:a. ONE (1) 7-DAY BREAK.b. TWO (2) 28-DAY BREAK
C6CLEAN AND MOISTEN CONSTRUCTION JOINTS IMMEDIATELY PRIOR TO PLACING FRESHCONCRETE.
C7COORDINATE THE LOCATION OF INSERTS, EMBEDDED PLATES, ANCHORS, REGLETSAND SIMILAR ITEMS REQUIRED BY OTHER TRADES TO BE PLACED IN CONCRETE.MAINTAIN CORRECT LOCATION OF REINFORCING BARS WHEN PLACING THESE ITEMS.
C8UNLESS NOTED OTHERWISE, PROVIDE DOWELS TO MATCH MAIN REINFORCEMENT SIZEAND SPACING. PROVIDE TENSION LAP SPLICE UNLESS NOTED OTHERWISE.
C9DO NOT USE CALCIUM CHLORIDE IN CONCRETE.
C10REFER TO THE ARCHITECTURAL, MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGSFOR CURBS, PADS, DEPRESSIONS, WALL/SLAB OPENINGS, SPECIAL FLOOR FINISHES,ETC.
C11PROVIDE AIR-ENTRAINING IN CONCRETE AS SET FORTH IN ACI 318-11, TABLE 4.4.1.
C12REFER TO ACI 318, CHAPTER 7.7 FOR MINIMUM CONCRETE COVER REQUIREMENTS,UNO.
C13REFER TO ACI 305 FOR REQUIREMENTS FOR PLACING CONCRETE IN HOT WEATHERAND TO ACI 306 FOR REQUIREMENTS FOR PLACING CONCRETE IN COLD WEATHER.
C14PROVIDE ONLY CONCRETE AND REINFORCING MATERIALS OF THE TYPES AND GRADESLISTED IN THE TABLE BELOW, UNLESS NOTED OTHERWISE.
CONCRETE F'C (PSI) UNIT WEIGHT (PCF)
FOOTINGS 4000 145ALL OTHER CONCRETE 4000 145
REINFORCING GRADETYPICAL BARS ASTM A615, GRADE 60
1/2" ISOLATION JT (TYP)
STEEL COL
NOTES:1. T = FOOTING THICKNESS.2. EVENLY SPACE FOOTING REINFORCEMENT.3. TOP OF FOOTING MATCH EXISTING T/ SLAB.
FTG - SEE PLAN
SEE 3/S0001 FORSUBGRADE REQUIREMENTS.
EXISTING SOGPATCH AS REQ'D
COL AND FTG
T/SLAB
VIF
W OR L SEE PLAN
6"
T
EMULSIFIED ASPHALT SEAL
NOTE:LEVELING SCREWS, LEVELING NUTS OR STEELSHIMS ARE ACCEPTABLE PLUMBING ALTERNATIVES
HSS COLUMN
ANCHOR ROD
(1) HEAVY HEX NUT
1/4" LEVELING PLATE(SEE NOTE)
LEVELING SCREWS(ALTERNATE)
L DIMENSION
T/FDTN
SEE PLAN
FINISH WHEN LEVELINGPLATE IS USED
FINISH
TH
ICK
NE
SS
T=
FIN
ISH
EQ EQ
GR
OU
T1"N
ON
-SH
RIN
K
EQ
EQW D
IME
NS
ION
TY
P2"
EM
BE
DM
EN
T
F1NOTE REQUIREMENTS ON PLANS. DO NOT UNDERMINE EXISTING CONSTRUCTION.
F2BEAR FOOTINGS ON UNDISTURBED SOILS OR ENGINEERED FILL HAVING A MINIMUM NET ALLOWABLEBEARING CAPACITY OF 1500 POUNDS PER SQUARE FOOT. EXTEND EXTERIOR CONSTRUCTION DOWN AMINIMUM OF 1 FOOT BELOW EXTERIOR GRADE. ELEVATIONS GIVEN ARE MINIMUM DEPTHS.
F3PROVIDE POSITIVE PROTECTION FOR EXCAVATION SLOPES AGAINST INSTABILITY AND DETERIORATIONDUE TO RAIN, WIND, SNOW OR ICE.
F4THE EXPOSED SUBGRADE SOILS MAY BE SENSITIVE TO DISTURBANCE AND STRENGTH DEGRADATIONWHEN HIGH MOISTURE CONTENTS ARE PRESENT. MINIMIZE CONSTRUCTION TRAFFIC OVER EXPOSEDSUBGRADES. DO NOT POND WATER ON THE SUBGRADES. CONTROL SURFACE AND GROUND WATER BYPROPER SITE GRADING, PERIMETER CUTOFF TRENCHES, AND SUMP AND PUMP METHODS OFDEWATERING. CONSTRUCT CUTOFF TRENCHES AND SUMPS OUTSIDE THE INFLUENCE OF PROPOSEDFOUNDATIONS.
F5THE OWNER'S GEOTECHNICAL CONSULTANT MUST REVIEW AND APPROVE FINISHED EXCAVATIONS ANDBEARING SUBGRADES BEFORE PLACING CONCRETE. PROVIDE ADDITIONAL EXCAVATION AS NECESSARYTO ACHIEVE THE REQUIRED BEARING CAPACITY.
F6CLEAN REINFORCEMENT IMMEDIATELY PRIOR TO PLACING CONCRETE.
F7DO NOT PLACE CONCRETE IN AN EXCAVATION CONTAINING FREE WATER, FROST, ICE OR FROZENGROUND. PROVIDE NECESSARY MEASURES TO PREVENT FROST OR ICE FROM PENETRATING FOOTINGOR SLAB SUBGRADE, BOTH BEFORE AND AFTER CONCRETE PLACEMENT AND UNTIL SUBGRADES AREFULLY PROTECTED BY THE PERMANENT BUILDING STRUCTURE.
F8PLACE THE CONCRETE FOR EACH FOOTING IN ONE CONTINUOUS POUR.
LIME STABILIZED SUBGRADE
#4@12"T&B EW
RAW SUBGRADE
1'-0"
6"
.
EXIST SOGPATCH AS REQ'D
NOTES:1. SAW CUT EXIST SLAB ON GRADE. COORDINATE WITH SITE UTILITIES
BEFORE DEMOLITION OF EXISTING SLAB ON GRADE.2. RAW SUBGRADE: TOP 6" COMPACTED TO 95% STANDARD PROCTOR3. LIME STABILIZED SUBGRADE: HYDRATED LIME SLURRY (THD TYPE B).
4% LIME BY SOIL DRY. TOP 6" COMPACTED TO 98% STANDARD PROCTOR.4. CONCRETE: 4000 PSI @ 28 DAYS & AIR ENTRAINED TO 5% | 1%.5. MONOLITHIC POUR WHERE SITE PAD AND COLUMN FOOTING OVERLAP.
PORTLAND CEMENT CONCRETE
2"
CLR
EMULSIFIED ASPHALT SEAL
O.F. OF GENERATORENCLOSURE
1/2" ISOLATION JT (TYP)
MIN
1'-0"
3"
CLR
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EMPOWER FOR BUILDING 2JMEDICAL EQUIPMENT
of 20
2J
GENERAL NOTES ANDABBREVIATIONS
S0001RS TB
STRUCTURAL DESIGN LOADS
MISCELLANEOUS
STRUCTURAL STEEL NOTESABBREVIATIONS
STRUCTURAL CONCRETE NOTES
1/2" = 1'-0"1
TYPICAL COLUMN FOOTING
1" = 1'-0"2
TYPICAL STEELCOLUMN BASE DETAIL
FOUNDATION NOTES
1/2" = 1'-0"3
TYPICAL SITE PAD DETAIL
QO P
1.3
13
S0102
2'-0" x 2'-0" x 12"(WxLxT) FTG W/ (3)#5 EW TOP ANDBOT, TYP UNO
3'-0" x 3'-0" x 12" FTGW/ (4) #5 EW EF
HSS4x4x5/16 POST WITH 1'-0" x1'-0" x 3/4" (WxLxT) BASE PLATEAND (4) 3/4" Ø HEAVY HEXHEAD ANCHOR BOLTS W/ 9"MIN EMBEDMENT, TYP
5'-5"
4'-0"
VIF
5'-5" 4'-8"
VIF
4'-9"
1'-3"
8'-1"
13'-4"
4'-0"
14'-4"
1'-3"
17'-4"
45°
15'-8"
6'-7"
8'-10"
6'-4
"
10'-6
"
8
S0102
VIF
3'-11 1/2"
VIF2'-1
1/2
"
4'-10"
VIF
2'-9 3/4" 10'-0"
QO P
1.3
13
S0102
VIF
HSS6x4x5/16
HS
S6x4x5/1
6
HSS POST, VERIFY SIZEAND LOCATION
5
S0102
HSS4x4x5/16
HSS4x4x5/16
HS
S6x4x5/1
6
.
3 9/
16" (
VIF)
1'-1
0"
10'-6
"
5'-6"
5'-6"
8
S0102
6
S0102
HSS6x4x5/16
HSS4x4x5/16
HSS4x4x5/16
HSS6x4x5/16
HSS6x4x5/16
HS
S6x4x5/1
6
HS
S6x4x5/1
6
HSS6x4x5/16
HSS4x4x5/16
HSS6x4x5/16
HS
S6x4x5/1
6
HS
S6x4x5/1
6
HSS4x4x5/16
HSS6x4x5/16
HSS6x4x5/16
HSS6x4x5/16
HSS6x4x5/16
HSS6x4x5/16
HSS6x4x5/16
HSS6x4x5/16
HSS4x4x5/16 (-5'-8")
HSS4x4x5/16 (-5'-8")
HSS4x4x5/16 (-5'-8")
7
S0102
TYP
HSS4x4x5/16 (-5'-8")
HSS4x4x5/16 (-5'-8")
HSS4x4x5/16 (-5'-8")
HSS4x4x5/16 (-5'-8")
HSS6x4x5/16 (-5'-8")
0".
0".
0".
0".
0".
0".
0".
0".
0".
HSS4x4x5/16 (-5'-8")
HSS4x4x5/16 (-5'-8")
0".
0".
8
S0102
SIM
8
S0102
SIM
HSS4x4x5/16 (-5'-8")
TYP
HSS6x4x5/16
45°3
S0102
SIM
8
S0102
SIM
8
S0102
SIM
HS
S4x4
HS
S4x4
HSS4
HSS4
5'-8"
1/4" CAP PL, TYP
T/ EXIST SOG
3 SIDES
TYP
T/STL
MATCH EXIST ELEVATIONS
PJP
HSS4x4x5/16
HSS4x
4x5/
16
1
1
TYP
TYP
8"
B/ EXIST CONC BEAM
B/ EXIST PRECAST PANEL
VIF
3 SIDES, TYPHSS6x4x5/16 PENETRATIONTHROUGH EXIST PRECAST
EXIST COL EXIST COL
TYP
1. FOR GENERAL NOTES AND ABBREVIATIONS, SEE DRAWING S0001.2. MATCH EXISTING SOG ELEVATION (517'-6"), VIF.3. FIELD VERIFY DIMENSIONS BEFORE FABRICATION
1. FOR GENERAL NOTES AND ABBREVIATIONS, SEE DRAWING S0001.2. T/ STL ELEVATION 530'-2", UNLESS NOTED OTHERWISE (+ OR -) FROM
ELEV 530'-2", VIF.3. FIELD VERIFY DIMENSIONS BEFORE FABRICATION.4. INDICATES BRACE LOCATION
HSS4 - SEE PLAN
HSS 6x4 - SEE PLAN
1
1
TYP
3 SIDES,TYP
PJP
HSS6x4 - SEE PLAN
HSS4x4 COLUMN
HSS4x4x5/16 BRACE, TYP
2'-6"
1/4" CAP PL
6
S0102
1/4" CAP PL
EXISTING CONC WALL
1'-10"
TYP
3 SIDES,TYP
PJP
HSS4x
4x5/
16HSS4x4x5/16
HSS4
HS
S4x4
HSS6x4
HS
S4x4
5'-8"
1
1
T/STL
MATCH EXIST ELEVATIONS
T/ EXIST SOG1
11" 1"
TYP
HSS BEAM - SEE PLAN
HSS4x4 BRACE
1
1
NOTE:ALL STEEL SHALL BEHOT-DIP GALVANIZED
1100 Clark AvenueSt. Louis, Missouri 63102
T: 314.241.6250F: 314.241.2570
DALLAS, TX
CANNON DESIGN PROJECT NO. 03640.55
© CannonDesign 2016All rights reserved. No part of this document may be reproduced or utilized in any form, without prior written authorization by the Cannon Corporation
SEPT 8, 2017
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement
one eighth inch = one foot 16
84
0
B
A
C
D
E
F
three inches = one foot
6"
10
6"
one and one half inches = one foot
one inch = one foot
20
6"
6"
02
three quarters inch = one foot
one half inch = one foot
40
three eighths inch = one foot
40
04
8
one quarter inch = one foot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
DALLAS VAMC INSTALL EMPOWER FOR BUILDING 2JMEDICAL EQUIPMENT
of 20
2J
FRAMING PLANS
S0102RS TB
1/8" = 1'-0"1
FOUNDATION PLAN 1/8" = 1'-0"
2LEVEL 01
1/2" = 1'-0"3
SECTION
1/2" = 1'-0"5
SECTION
1 1/2" = 1'-0"7
SECTION
3/4" = 1'-0"6
SECTION 1/2" = 1'-0"
8SECTION
1 1/2" = 1'-0"4
BRACE CONNECTION