Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

download Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

of 18

Transcript of Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

  • 7/27/2019 Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

    1/18

    Daikin Altherma Selection Software

    A Guide To using The Selection Software

  • 7/27/2019 Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

    2/18

    www.altherma.co.uk

    Using The Selection Software Program

    Page 2

    Select a location as this will

    automatically insert weather conditions,

  • 7/27/2019 Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

    3/18

    www.altherma.co.uk Page 3

    Select preferences

    Select what units you prefer

  • 7/27/2019 Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

    4/18

    www.altherma.co.uk Page 4

    Equipment prices (can be omitted)

    Currency used

  • 7/27/2019 Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

    5/18

    www.altherma.co.uk Page 5

    You will need to input Heat pump electricity cost and electric heating

    cost. You need to input a high and low electricity costing i.e. economy7, for this you can add and remove the stars depending when your

    price changes activate. If your not on economy 7 then you will have to

    average your KW/H cost into one figure and add this to both fields

  • 7/27/2019 Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

    6/18

    www.altherma.co.uk Page 6

    Input fields when zero heating will be

    required due to ambient conditions and

    minimum heat pump coverage

  • 7/27/2019 Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

    7/18www.altherma.co.uk Page 7

    For a price comparison to gas thenthese fields will need to be

    accurately inputted

  • 7/27/2019 Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

    8/18www.altherma.co.uk Page 8

    For a fuel comparison to Daikin

    Altherma and gas then these fields

    will need to be accurately inputted

  • 7/27/2019 Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

    9/18www.altherma.co.uk Page 9

    System drawing settings

  • 7/27/2019 Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

    10/18www.altherma.co.uk Page 10

    If no unit price has been

    entered then you will see this

    box click on yes

  • 7/27/2019 Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

    11/18www.altherma.co.uk Page 11

    Left click of the mouse to add and

    remove operating monthsRight click of the mouse to add and

    remove operating months

    Results are now activated

  • 7/27/2019 Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

    12/18www.altherma.co.uk Page 12

    Choose which system you require

    Right click on the mouse

    on the dotted outline to

    select the specific

    equipment required

    Once all selections have been done a list of all

    available systems will appear

  • 7/27/2019 Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

    13/18www.altherma.co.uk Page 13

    You will require the Equilibrium point to

    insert in the commissioning stage

    The solution can be refined

    by changing the required

    temperatures

  • 7/27/2019 Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

    14/18

    www.altherma.co.uk Page 14

    You will require the Equilibrium point to

    insert in the commissioning stage

  • 7/27/2019 Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

    15/18

    www.altherma.co.uk Page 15

    Costing graphs then can be obtained

  • 7/27/2019 Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

    16/18

    www.altherma.co.uk Page 16

    Make a field settings report

  • 7/27/2019 Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

    17/18

    www.altherma.co.uk Page 17

    1st

    code

    2nd

    code

    Setting name Date

    (*)

    Value

    (*)

    Date

    (*)

    Value

    (*)

    Default

    value

    Range Step Unit

    0 User permission level

    00 User permission level 3 2-3 1 -

    1 Weather dependent set point

    00 Low ambient temperature (Lo_A) -4 -10 -20-5 1 C

    01 High ambient temperature (Hi_A) 16 15 10-20 1 C

    02 Set point at low ambient temperature

    (Lo_TI)

    35 40 25-55 1 C

    03 Set point at high ambient temperature

    (Hi_TI)

    30 25 25-55 1 C

    2 Disinfection function

    00 Operation interval Fri Mon-Sun,

    All

    - -

    01 Status 1 (ON) 1 (ON) 0/1 - -

    02 Start time 23:00 0:00-23:00 1:00 hour

    03 Set point 70 40-80 5 C

    04 Interval 10 5-60 5 min

    3 Auto restart

    00 Status 0 (ON) 0 (ON) 0/1 - -

    4 Backup heater operation

    00 Status 1 (ON) 1 (ON) 0/1 - -

    01 Priority 0 (OFF) 0 (OFF) 0/1 - -

  • 7/27/2019 Daikin Altherma-Using Selection Software Program_UKEAUTSSP 0510_tcm219-168626

    18/18

    www.altherma.co.uk Page 18

    1st

    code

    2nd

    code

    Setting name Date

    (*)

    Value

    (*)

    Date

    (*)

    Value

    (*)

    Default

    value

    Range Step Unit

    5 Equilibrium temperature and space heating

    priority temperature

    00 Equilibrium temperature status 1 (ON) 1 (ON) 0/1 - -

    01 Equilibrium temperature -4 0 -15-20 1 C

    02 Space heating priority status 1 (ON) 0 (OFF) 0/1 - -

    03 Space heating priority temperatures -2 0 -15-20 1 C

    04 Set point correction for sanitary water temperature 10 10 0-20 1 C

    6 DT for sanitary water heating

    00 Start 5 5 1-20 1 C

    01 Stop 0 0 0-10 1 C

    7 Sanitary water step length

    00 Sanitary water step length 3 3 2-4 1 C

    8 Sanitary water heating mode timer

    00 Minimum running time 5 5 0-20 1 min

    01 Maximum running time 45 30 20-95 5 min

    02 Anti-recycling time 1.5 3 0-10 0.5 hour

    03 Booster heating delay time 60 20 20-95 5 min

    9 Cooling and heating set point ranges

    00 Heating set point upper limit 35 55 37-55 1 C

    01 Heating set point lower limit 30 25 25-37 1 C

    02 Cooling set point upper limit - - - - 20 18-20 1 C

    03 Cooling set point lower limit - - - - 5 5-18 1 C