Customer Service VICTRIX 90 Central heating only, wall hung condensing boiler.
-
Upload
merilyn-miles -
Category
Documents
-
view
217 -
download
3
Transcript of Customer Service VICTRIX 90 Central heating only, wall hung condensing boiler.
Customer Service
VICTRIX 90VICTRIX 90Central heating only, wall hung condensing boiler
Customer Service
90 kW output (77400 kcal/h) Outdoor installation ready (IPX5D protection rating) Modulating range from 25% a 100% (22,5-90 kW) Fully pre-mix system (natural gas-G20 e G31-propane) AISI 304L stainless steel condensing module Electronic board and NTC probes (12 kohm) 4 bar safety valve “Green Series” dedicated flue system Ready for:
- Cascade operation (max 8 boilers )
- Connection to external cylinder
- Connection to Immergas accessories for thermoregulation
(external probe, zone managing devices, etc..)
Caratteristiche principaliCaratteristiche principali
Customer Service
Height = 1086 mm Length = 600 mm Depth = 610 mm
Dimensions and connectionsDimensions and connections
Key:V – Electric supplyG – Gas supply R – System returnM – System flowSC = Condensate drain
(Ø 13 mm min. internal)
Connections
GAS System
G R M
¾” 1” ½ 1” ½
Customer Service
Main componentsMain components
1. Flue hood
2. Condensing module
3. Air intake pipe
4. Fun
5. Gas valve
6. Discharge funnel
7. Sample points (air A) (flue F)
8. Air vent
9. Burner
10.Pump
1
2
9
3
7
5
6
104
8
Customer Service
Casing groupCasing group
IPX5D cover thermoformed
Ø80 exhaust flue discharge
The boiler leaves the factory in B23 type configuration, air is drawn directly from the place where the boiler is installed
Customer Service
Hydraulic circuitHydraulic circuit
M - FlowSC – Condensate discargeG - GasR - Return
Air vent valve
Flow NTC probe
Return NTC probe
Overheating thermostat (Klixson)
Circulator
4 bar safety valve
Customer Service
CirculatorCirculatorHigh head 25-105 Grundfos pump (10 m H2O)
Head (
kPa)
Head (
m H
2O
)
Flow rate (l/h)
A = Head available to the system on the individual boiler maximum speed.B = Head available to the system on maximum speed with the non-return valve for boilers in cascade (battery)
Customer Service
Condensation moduleCondensation module
AISI 304L stainless steel overlapped module
16 element assembly: flue side 10+6, water side 8+8
Customer Service
Combustion circuitCombustion circuit
1. Flue hood
2. Condensation chamber
3. Delivery coils
4. Siphon
5. Cylindrical burner
6. Combustion chamber
7. Return coils
Customer Service
Venturi pipe
Gas manifold
Metalfibre burner
Condensing moduleFlue hood
Fan
Air intake unit Gas valve
Combustion circuitCombustion circuit
Customer Service
1 - Valve inlet pressure check2 – Valve outlet pressure check (P3)
3 - Off-set adjusting screw12 - Outlet gas flow rate adjuster
Valve coils are 24 V dc supplied
GB-ND 057 GB-ND 057 DungsDungs
1:1 pneumatic gas valve1:1 pneumatic gas valve
Customer Service
ON-OFF main switch Adjusting buttons
Manometer
Digital display
Control panelControl panel
Customer Service
RESET Manual boiler block reset
MODE Display menu selection button
STEP Parameter selection
STORE Data confirmation and memory
+ Increasing of set value
- Decreasing of set value
End user interfaceEnd user interfaceIt is equipped with a 4 digit display and 6 buttons for programming and adjustment
Customer Service
Integrated ignition and modulation microprocessor board
Temperature modulation via two 12 k ohm NTC probes (flow and return)
Parameter adjustment via buttons
Operation status display, temperature and error codes
Output modulation from 25 to 100 %
Printed circuit boardPrinted circuit board
Customer Service
Printed circuit boardPrinted circuit board
End user adjustments(free access menu)
Max central heating temperature Central heating and/or domestic hot water mode operation Domestic hot water temperature (optional external cylinder)
Qualified technician main adjustments(code protected menu)
Timer controlled pump post-circulation Timer controlled central heating Fan rotations per minute External probe reading correction
Customer Service
Printed circuit board safetiesPrinted circuit board safeties
Ignition block
Overheating (105ºC)
Fan speed check (fault and revolutions)
NTC probe faults
Low circulation
Low water pressure
Anti-frost protection as low as -5°C
Pump anti-blocking function
Flow overheating (95ºC)
Customer Service
Q-P = External pumpG-J = External probe M-O = Thermoregulation deviceR-H = External cylinder probe
F-E = ON-OFF thermostat T-S-K = 3-way valveV-U = Summer switchY-Z = Analogic input (0-10V)
Available connections Available connections on the printed circuit boardon the printed circuit board
Customer Service
Cascade manager
Modulating room thermostat
Zone manager
External probe
Thermoregulation optionsThermoregulation options
Customer Service
Hydraulic optionsHydraulic options
Single boiler safety device kit 3-way valve kit for connection
to external cylinder Hydraulic collector kit for
single boiler
Customer Service
Thermometer trap
Gas interceptingvalve trap
Pressuregauge cock
Manual resetpressure switch
Manual resetthermostat
Thermometer
Expansion tankconnection
Single boiler safety device kitSingle boiler safety device kit
The devices included in the kit are homologatedby the Italian authority for the job safety (ISPESL)
Customer Service
External storage tank 3-way valve
Storage tank probe
3-way kit for external tank3-way kit for external tank
The probe replaces the one supplied as standard with the boiler
An optional kit is available for installation of two external cylinder in parallel
Customer Service
Hydraulic collector kitHydraulic collector kit
Includes mud filter on system return pipe
Customer Service
Vertical kitHorizontal kit:
- through-wall discharge
- chimney discharge
(Max length= 17m)
(Max length = 17 m)
Ø 80 flue system kitØ 80 flue system kitOpen chamber, fan assisted installationOpen chamber, fan assisted installation
Customer Service
Vertical coaxial kit
Horizontal coaxial kit(Max length = 12 m)
(Max length = 10m)
Ø80-125 Ø80-125 flue system kitflue system kitSealed chamber, fan assisted installationSealed chamber, fan assisted installation
Customer Service
Max vertical length: 17 m.
Composite material
80mm nominal diameter
(89,5 mm externally )
Engineered to be implemented inside chimneys or existing flue exhaust systems
Ø80 flexible ducting kitØ80 flexible ducting kit
Customer Service
3-way valve kit for external cylinder
Solar panelON-OFF room thermostat
Installation sampleInstallation sampleSingle installation with 200 liter boiler and solar panelsSingle installation with 200 liter boiler and solar panels
Customer Service
Zone manager
Room managers
Modulating thermostat
Installation sampleInstallation sampleSingle installation with 3 central heating zones and external tankSingle installation with 3 central heating zones and external tank
Customer Service
Installation warningsInstallation warnings
Clean the system (pipes, heating elements, etc…) employing specific products
Install a filter on the system in order to recover mud and impurities
Fill the system with correct hardness water (12-15°f) in order to prevent calcium deposits
Employ protective additives in order to prevent corrosion and ensure system efficiency
Connect the safety valve funnel to the drain network system (sewer)
Discharge condensate in compliance with local laws and regulations