CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

download CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

of 221

Transcript of CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    1/221

    CSC-121

    Breaker Protection IEDEngineering and Operation

    Manual

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    2/221

    VersionV1.00Doc. Code: 0SF.465.020(E)

    Issued Date2012.8Copyright owner: Beijing Sifang Automation Co., Ltd

    Note: The company keeps the right to perfect the instruction. If equipments do

    not agree with the instruction at anywhere, please contact our company in time.We will provide you with corresponding service.

    is registered trademark of Beijing Sifang Automation Co., Ltd.

    We reserve all rights to this document, even in the event that a patent is issued and a differentcommercial proprietary right is registered. Improper use, in particular reproduction anddissemination to third parties, is not permitted.

    This document has been carefully checked. If the user nevertheless detects any errors, he isasked to notify us as soon as possible.

    The data contained in this manual is intended solely for the IED description and is not to bedeemed to be a statement of guaranteed properties. In the interests of our customers, weconstantly seek to ensure that our products are developed to the latest technological standardsas a result it is possible that there may be some differences between the hardware/softwareproduct and this information product.

    Manufacturer:Beijing Sifang Automation Co., Ltd.

    Tel: +86 10 62962554, +86 10 62961515 ext. 8998Fax: +86 10 82783625Email: [email protected]: http://www.sf-auto.com

    Add: No.9, Shangdi 4th Street, Haidian District, Beijing, P.R.C.100085

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    3/221

    Preface

    Purpose of this manual

    This manual describes operation, installation, commissioning, protection test

    and putting the IED into service. The manual includes the following chapters:

    Introduction, this chapter presents the basic content and have a brief

    introduction of this manual

    Local human machine interface, this chapter presents the configuration

    of HMI interface and how to use the HMI

    Installing the IED, this chapter introduces the procedure to install IED and

    how to check that the IED is properly connected to the protection system

    Read and change setting, this chapter introduces how to read and

    change the setting value via LHMI or software tool, and switch the setting

    value group

    Testing the communication connection and time synchronization, this

    chapter presents how to test the communication port connection and

    introduces how to test time synchronization

    IED testing, this chapter contains that what should be tested and how to

    test the IED

    Operating maintenance, this chaper describes the items for maintenance

    and how to maintain the IED when operating

    Transportion and storage, this chapter presents how to transport andstore the IED

    Appendix, this chapter presents the significant data and diagram of the

    IED

    Target audience

    This manual mainly face to installation engineer, commissioning engineer and

    operation engineer with perfessional electric and electrical knowledge, rich

    experience in protection function, using protection IED, test IED, responsible

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    4/221

    for the installation, commissioning, maintenance and taking the protection

    IED in and out of normal service.

    Applicability of this manual

    This manual is valid for CSC-121 Breaker Protection IED.

    Technical support

    In case of further questions concerning the CSC family, please contact Sifang

    compay or your local Sifang representative.

    Safety information

    Strictly follow the company and international safety regulations.

    Working in a high voltage environment requires serious approch to

    aviod human injuries and damage to equipment

    Do not touch any circuitry during operation. Potentially lethal

    voltages and currents are present

    Avoid to touching the circuitry when covers are removed. The IED

    contains electirc circuits which can be damaged if exposed to static

    electricity. Lethal high voltage circuits are also exposed when covers

    are removed

    Using the isolated test pins when measuring signals in open circuitry.Potentially lethal voltages and currents are present

    Never connect or disconnect wire and/or connector to or from IED

    during normal operation. Dangerous voltages and currents are

    present. Operation may be interrupted and IED and measuring

    circuitry may be damaged

    Always connect the IED to protective earth regardless of the

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    5/221

    operating conditions. Operating the IED without proper earthing may

    damage both IED and measuring circuitry and may cause injuries in

    case of an accident.

    Do not disconnect the secondary connection of current transformer

    without short-circuiting the transformers secondary winding.

    Operating a current transformer with the secondary winding open will

    cause a high voltage that may damage the transformer and may

    cause injuries to humans.

    Do not remove the screw from a powered IED or from an IED

    connected to power circuitry. Potentially lethal voltages and currents

    are present

    Using the certified conductive bags to transport PCBs (modules).

    Handling modules with a conductive wrist strap connected to

    protective earth and on an antistatic surface. Electrostatic discharge

    may cause damage to the module due to electronic circuits are

    sensitive to this phenomenon

    Do not connect live wires to the IED, internal circuitry may be

    damaged

    When replacing modules using a conductive wrist strap connected to

    protective earth. Electrostatic discharge may damage the modules

    and IED circuitry

    When installing and commissioning, take care to avoid electricalshock if accessing wiring and connection IEDs

    Changing the setting value group will inevitably change the IEDs

    operation. Be careful and check regulations before making the

    change

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    6/221

    Contents

    Chapter 1 IED introduction............................................................................................................... 1

    Chapter 2 Local human machine interface.................................................................................... 3

    1 Introduction....................................................................................................................................... 4

    2 Liquid crystal display (LCD)........................................................................................................... 6

    3 Keyboard........................................................................................................................................... 7

    4 IED menu.......................................................................................................................................... 8

    4.1 Menu construction........................................................................................................... 8

    4.2 Operation status............................................................................................................... 9

    4.3 Query reports................................................................................................................. 10

    4.4 Set time........................................................................................................................... 10

    4.5 Contrast........................................................................................................................... 104.6 Settings........................................................................................................................... 10

    4.7 IED setting...................................................................................................................... 12

    4.8 Test binary output.......................................................................................................... 12

    4.9 Testing operation........................................................................................................... 12

    Chapter 3 Installing IED.................................................................................................................. 15

    1 Unpacking and checking the IED................................................................................................ 16

    2 Installing the IED............................................................................................................................ 17

    3 IED connection............................................................................................................................... 18

    3.1 IED connector................................................................................................................. 18

    3.1.1 Introduction............................................................................................................. 18

    3.1.2 Terminals of Analogue Input Module (AIM)........................................................ 19

    3.1.3 Terminals of Binary Input Module (BIM)............................................................. 21

    3.1.4 Terminals of Binary Output Module (BOM)........................................................ 22

    3.1.5 Terminals of Communication module (COM).................................................... 26

    3.1.6 Terminals of Power Supply Module (PSM)........................................................ 27

    3.1.7 RS232 port.............................................................................................................. 28

    3.2 Connecting to protective earth..................................................................................... 28

    3.3 Connecting the power supply module........................................................................ 28

    3.4 Connecting to CT and VT circuits............................................................................... 283.5 Connecting the binary inputs and outputs.................................................................. 28

    3.6 Making the screen connection..................................................................................... 30

    3.7 RS485 and RS232 ports connection.......................................................................... 30

    3.7.1 RS485 port connection......................................................................................... 30

    3.7.2 RS232 port connection......................................................................................... 31

    3.8 Connecting the GPS...................................................................................................... 31

    4 Checking before energizing......................................................................................................... 33

    4.1 Introduction..................................................................................................................... 33

    4.2 Checking the protective earth connection.................................................................. 33

    4.3 Checking the power supply connection...................................................................... 33

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    7/221

    4.4 Checking the CT and VT circuits connection............................................................ 33

    4.4.1 Checking the CT circuits connection.................................................................. 33

    4.4.2 Checking the VT connection................................................................................ 34

    4.5 Checking the binary input and output connection.................................................... 34

    4.5.1 Checking the binary input connection................................................................ 34

    4.5.2 Checking the binary output connection.............................................................. 35

    4.6 Checking the screened cables connection................................................................ 35

    4.7 Checking the RS485 and RS232 port connectios.................................................... 35

    4.7.1 Checking the RS485 port connection................................................................. 35

    4.7.2 Checking RS232 port connection....................................................................... 35

    4.8 Checking GPS connection........................................................................................... 35

    4.9 Checking the insulation voltage and insulation resistance..................................... 35

    4.9.1 Checking the insulation voltage.......................................................................... 35

    4.9.2 Checking the insulation resistance..................................................................... 36

    5 Checking after energizing............................................................................................................ 37

    5.1 Introduction..................................................................................................................... 37

    5.2 Test LCD......................................................................................................................... 37

    5.3 Test the keyboard.......................................................................................................... 37

    5.4 Setting the IED time...................................................................................................... 37

    5.5 Self-supervision HMI data............................................................................................ 38

    5.6 Checking the software and hardware version........................................................... 38

    Chapter 4 Read and change setting............................................................................................. 39

    1 Read and change the setting vaule............................................................................................ 40

    1.1 Read and change the setting value via LHMI........................................................... 40

    1.1.1 Introduction............................................................................................................. 40

    1.1.2 Communication parameter................................................................................... 40

    1.1.3 Equipment parameter........................................................................................... 41

    1.1.4 Setting values and binary settings for protection function............................... 41

    2 Switching the setting group.......................................................................................................... 49

    2.1 Introduction..................................................................................................................... 49

    2.2 Method for switching setting group via LHMI............................................................ 49

    2.3 Method for switching setting group via binary input................................................. 49

    Chapter 5 Testing the communication connection and time synchronization......................... 51

    1 Testing the communication connection...................................................................................... 52

    1.1 Testing the Ethernet communication.......................................................................... 52

    1.1.1 Testing the electrical Ethernet communication................................................. 52

    1.1.2 Testing the optical Ethernet communication...................................................... 52

    1.2 Testing the RS485 port................................................................................................. 52

    1.3 Testing the RS232 port................................................................................................. 52

    2 Testing the time synchronization................................................................................................. 54

    2.1 Network mode................................................................................................................ 54

    2.2 Pulse mode.................................................................................................................... 54

    2.3 IRIG-B mode.................................................................................................................. 54

    Chapter 6 IED testing...................................................................................................................... 55

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    8/221

    1 Introduction..................................................................................................................................... 56

    2 Points for attention during testing................................................................................................ 58

    3 Preparing for test........................................................................................................................... 60

    3.1 Introduction..................................................................................................................... 60

    3.2 Connecting test equipment to IED.............................................................................. 60

    4 Testing the power supply.............................................................................................................. 62

    4.1 Checking the self-startup performance...................................................................... 62

    4.2 DC power on and power off testing............................................................................. 62

    4.3 Checking the expiry date of power supply................................................................. 62

    5 Checking the analog channel...................................................................................................... 63

    5.1 Checking the zero drift.................................................................................................. 63

    5.2 Calibrating....................................................................................................................... 63

    5.3 Checking the accuracy and the linearity of analog quantitis................................... 63

    5.4 Checking the polarity of analog quantities................................................................. 64

    6 Testing binary input....................................................................................................................... 65

    7 Testing binary output..................................................................................................................... 66

    8 Verifying the IED functions........................................................................................................... 67

    8.1 Overcurrent protection.................................................................................................. 67

    8.1.1 Verifying the settings............................................................................................. 67

    8.1.2 Completing the test................................................................................................ 75

    8.1.3 Reference setting list for test............................................................................... 75

    8.2 Earth fault protection..................................................................................................... 77

    8.2.1 Verifying the settings............................................................................................. 77

    8.2.2 Completing the test................................................................................................ 85

    8.2.3 Reference setting list for test............................................................................... 85

    8.3 Neutral earth fault protection........................................................................................ 88

    8.3.1 Verifying the settings............................................................................................. 88

    8.3.2 Completing the test................................................................................................ 94

    8.3.3 Reference setting list for test............................................................................... 94

    8.4 Sensitive earth fault protection.................................................................................... 96

    8.4.1 Verifying the settings............................................................................................. 96

    8.4.2 Completing the test.............................................................................................. 102

    8.4.3 Reference setting list for test............................................................................. 102

    8.5 Negative sequence overcurrent protection.............................................................. 104

    8.5.1 Verifying the settings........................................................................................... 104

    8.5.2 Completing the test.............................................................................................. 107

    8.5.3 Reference setting list for test............................................................................. 107

    8.6 Thermal overload protection...................................................................................... 108

    8.6.1 Verifying the settings........................................................................................... 108

    8.6.2 Completing the test.............................................................................................. 112

    8.6.3 Reference setting list for test............................................................................. 112

    8.7 Overload protection..................................................................................................... 112

    8.7.1 Verifying the settings........................................................................................... 112

    8.7.2 Completing the test.............................................................................................. 114

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    9/221

    8.7.3 Reference setting list for test............................................................................. 114

    8.8 Overvoltage protection............................................................................................... 115

    8.8.1 Verifying the settings........................................................................................... 115

    8.8.2 Completing the test............................................................................................. 121

    8.8.3 Reference setting list for test............................................................................. 122

    8.9 Undervoltage protection............................................................................................. 122

    8.9.1 Verifying the settings........................................................................................... 122

    8.9.2 Completing the test............................................................................................. 130

    8.9.3 Reference setting list for test............................................................................. 130

    8.10 Displacement voltage protection............................................................................... 131

    8.10.1 Verifying the settings........................................................................................... 131

    8.10.2 Completing the test............................................................................................. 133

    8.10.3 Reference setting list for test............................................................................. 133

    8.11 Circuit breaker failure protection............................................................................... 134

    8.11.1 Verifying the settings of stage 1 of CBF protection........................................ 134

    8.11.2 Completing the test............................................................................................. 142

    8.11.3 Reference setting list for test............................................................................. 142

    8.12 Dead zone protection.................................................................................................. 143

    8.12.1 Verifying the settings........................................................................................... 143

    8.12.2 Completing the test............................................................................................. 145

    8.12.3 Reference setting list for test............................................................................. 145

    8.13 STUB protection.......................................................................................................... 146

    8.13.1 Verifying the settings........................................................................................... 146

    8.13.2 Completing the test............................................................................................. 149

    8.13.3 Reference setting list for test............................................................................. 149

    8.14 Poles discordance protection.................................................................................... 149

    8.14.1 Verifying the settings........................................................................................... 149

    8.14.2 Completing the test............................................................................................. 154

    8.14.3 Reference setting list for test............................................................................. 155

    8.15 Synchro-check and energizing check function....................................................... 155

    8.15.1 Verifying the settings........................................................................................... 155

    8.15.2 Completing the test............................................................................................. 170

    8.15.3 Reference setting list for test............................................................................. 170

    8.16 Auto-reclosing function............................................................................................... 171

    8.16.1 Verifying the settings........................................................................................... 171

    8.16.2 Completing the test............................................................................................. 174

    8.16.3 Reference setting list for test............................................................................. 175

    8.17 Current transformer secondary circuit supervision................................................. 176

    8.17.1 Verifying the settings........................................................................................... 176

    8.17.2 Completing the test............................................................................................. 178

    8.17.3 Reference setting list for test............................................................................. 178

    8.18 Voltage transformer secondary circuit supervision................................................ 178

    8.18.1 Verifying the settings........................................................................................... 178

    8.18.2 Completing the test............................................................................................. 187

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    10/221

    8.18.3 Reference setting list for test............................................................................. 187

    8.19 Monitoring function...................................................................................................... 188

    8.19.1 Reference voltage monitoring............................................................................ 188

    8.19.2 Auxiliary contact of circuit breaker monitoring................................................. 188

    9 Checking before operation......................................................................................................... 190

    9.1 Checking the LED........................................................................................................ 190

    9.2 Checking the display on LCD..................................................................................... 190

    9.3 Checking the clock...................................................................................................... 190

    9.4 Checking the voltage and current............................................................................. 190

    9.5 Checking the setting group........................................................................................ 190

    9.6 Checking the setting.................................................................................................... 190

    9.7 Checking the binary input........................................................................................... 191

    9.8 Checking the normal operation mode....................................................................... 191

    9.8.1 Trip and close test with the circuit breaker....................................................... 191

    9.9 Put into operation......................................................................................................... 191

    Chapter 7 Operating maintenance.............................................................................................. 193

    1 Attentions during operating........................................................................................................ 194

    2 Routine checking......................................................................................................................... 196

    3 Periodical checking..................................................................................................................... 197

    4 Operation after updating software or replacing modules....................................................... 198

    4.1 Operation after updating software or replacing CPU module............................... 198

    4.2 Operation after updating software or replacing communication module............. 198

    4.3 Operation after replacing the binary input or output module................................. 199

    4.4 Operation after replacing the analog input module................................................ 199

    4.5 Operation after replacing power supply module..................................................... 199

    5 The alarm information and measure......................................................................................... 200

    5.1 Alarm information class I and the measure............................................................. 200

    5.2 Alarm information class II and the measure............................................................ 200

    Chapter 8 Transportation and storage........................................................................................ 203

    1 Transportion.................................................................................................................................. 204

    2 Storage.......................................................................................................................................... 205

    Chapter 9 Appendix....................................................................................................................... 207

    1 Arrangement diagram of modules............................................................................................. 208

    2 Typical diagram............................................................................................................................ 209

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    11/221

    Chapter 1 IED Introduction

    1

    Chapter 1 IED Introduction

    About this chapter

    This chapter presents the overview of the operation and

    engineering about the IED.

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    12/221

    Chapter 1 IED Introduction

    2

    The Human Machine Interface (HMI) on the IED provides an ideal

    mechanism for the day to day operation and even advanced use of the IED.

    The keyboard, LCD and LEDs on the front of the IED are what constitute the

    HMI. Troubleshooting, monitoring, setting and configuring are all possible via

    this interface. Through the screens and menu elements available, as well as

    the keypad, the user is able to navigate throughout the menu structure and

    move from screen to screen.

    The IED is unpacked and visually checked. The connection to the protection

    system has to be checked in order to verify that the installation is successful.

    The settings for each function must be calculated before the commissioning

    task. The functions setting menu have been listed in detail so that the user

    can find and change the required settings directly and correctly. For the

    different application, the IED can be performed conveniently throughswitching the setting group.

    For the functions included in the IED can be tested by users, the testing

    procedure have been listed as reference to verify that protection function

    operate correctly.

    After the IED is in service, some checking items also need to be done for

    maintenance in order to ensure that the IED is in good condition during

    operation, some suggestions have been preset as reference and the user can

    perform some other checking items according to the relevant regulations.

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    13/221

    Chapter 2 Local human machine interface

    3

    Chapter 2 Local human machine

    interface

    About this chapter

    This chapter describes the structure of human-machine

    interface (HMI), LCD, LED, keyboard, RS232 and IED menu.Instruction on how to operate with keys, how to configure the

    LED and menu information introduction.

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    14/221

    Chapter 2 Local human machine interface

    4

    1 Introduction

    The HMI is simple and easy to be used for routine operation, the front panel

    of the HMI consists of LCD, LED and keyboard. As shown in the following

    picture, the setting, configuration, monitoring, maintenance and fault analysiscan be performed in HMI.

    2

    1

    3

    45

    68

    7

    CSC-121

    Figure 1 Front plate with 8 LEDs

    2

    1

    3

    45

    68

    7

    CSC-121

    Figure 2 Front plate with 20 LEDs

    1. Liquid crystal display (LCD)

    2. LEDs

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    15/221

    Chapter 2 Local human machine interface

    5

    3. Shortcut function keys

    4. Arrow keys

    5. Reset key

    6. Quit key

    7. Set key

    8. RS232 communication port

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    16/221

    Chapter 2 Local human machine interface

    6

    2 Liquid crystal display (LCD)

    The LCD background of HMI is blue, 8 lines with up to 28 characteristics per

    line can be displayed.

    When operating keys are pressed or in the case of IED alarming or operating

    report appearance, the back light will turn on automatically until the preset

    time delay elapse after the latest operation or alarm.

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    17/221

    Chapter 2 Local human machine interface

    7

    3 Keyboard

    The keyboard is used to monitor and operate IED. The keyboard has the

    same look and feel in CSC family. As shown inFigure 1andFigure 2,

    keyboard is divided into Arrow keys, Reset key, Quit key, Set key and shorcutfunction keys. The specific instructions on the keys as the following table

    described:

    Table 1 Keys on the front of the IED

    Key Function

    Up arrow key Move up in menu

    Page up between screens

    Increase value in setting

    Down arrow key Move down in menu

    Page down between screens

    Decrease value in setting

    Left arrow key Move left in menu

    Right arrow key Move Right in menu

    Reset key Reset the LEDs

    Return to normal scrolling display state directly

    Set key Enter main menu or submenu

    Confirm the setting change

    Quit key Back to previous menu

    Cancel the current operation and back to previous menu

    Return to scrolling display state

    Lock or unlock current display in the scrolling display state (the

    lock state is indicated by a key type icon on the upright corner of

    the LCD)

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    18/221

    Chapter 2 Local human machine interface

    8

    4 IED menu

    4.1 Menu construction

    OpStatus

    QueryRpt

    SetTime

    Contrast

    Settings

    Setup

    TestBO

    Testing

    AI Version

    BIEquipCode

    Measure

    EventRpt Log

    CurTime SetTime

    TestEffect

    Protocol

    ModifyPW

    SOEReset

    SetPrint

    103Type

    ProtSet

    EquipPara

    SimuReSig SwSetGr

    ViewDrift AdjDrift

    ViewScale AdjScale

    PrtSample

    CommuPara

    ProtContWdMainMenu

    AIDisplaySet

    StartRpt

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    19/221

    Chapter 2 Local human machine interface

    9

    Table 2 Full name for the menu

    Sub-menu Full name Sub-sub menu Full name

    OpStatus Operation status

    AI Analog input

    EquipCode Equipment codeMeasure Measurement quantity

    Version IED version

    BI Binary input

    QueryRpt Query reports

    EventRpt Event reports

    AlarmRpt Alarm reports

    Log Operation logging

    Set time Setting timeCur Time Current time

    Set Time Set time

    Contrast LCD contrast TestEffect Test effect

    Settings Setting value

    CommuPara Communication parameter

    ProtSet Protection setting

    EquipPara Equipment parameter

    PortContwd Protection binary setting

    Setup IED setting

    SOEReset SOE reset selection

    ModifyPW Modify password

    SetPrint Setting the print

    Protocol Protocol selection

    103Type 103 function type

    Test BO Test binary output

    Testing Testing operation

    SimuReSig Simulation remote signalization

    ViewDrift View zero drift

    ViewScale View scale

    PrtSample Print sample value

    SwSetGr Switch setting group

    AdjDrift Adjust zero drift

    AdjScale Calibrating

    4.2 Operation status

    Sub menu Sub-sub menu Explanation

    OpStatus

    AI Read the secondary analogue of the selected CPU

    module

    EquipCode Read the versions, released time and CSC code of all

    modules

    Measure Read the analogue value and calculation value

    Version Read the IED type, date and CPU version

    BI Read the current status of binary inputs, Offor On

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    20/221

    Chapter 2 Local human machine interface

    10

    4.3 Query reports

    Sub

    menu

    Sub-sub menu Sub-sub-sub

    menu

    Explanation

    QueryRpt

    EventRpt Latest Rpt Query the latest event report, press the Set

    key to see the report

    Last 6 Rpts Query the latest six event reports, press the

    Set key to see the report

    QueryRpt by

    DateQuery the reports by date

    AlarmRpt Last 6 Rpts Query the latest six alarm reports, press the

    Set key to see the report

    QueryRpt by

    Date Query the reports by date

    Log Last 6 Rpts Query the latest six operation reports, press

    the Set key to see the report

    QueryRpt by

    DateQuery the reports by date

    4.4 Set time

    Sub menu Sub-sub menu Explanation

    Set timeCur Time

    Modify the time with arrow keysSet Time

    4.5 Contrast

    Sub menu Sub-sub menu Explanation

    Contrast TestEffect Modify the contrast with arrow keys

    4.6 Settings

    Sub

    menu

    Sub-sub menu Sub-sub-sub

    menu

    Explanation

    Settings CommuPara

    BayName Enter into the line name

    TimeMode NetworkTimeMode

    PulseTimeMode

    IRIG-B TimeMode

    CommAddr Enter into the LON and RS485 address, and

    the Ethernet 1 and Ethernet 2 address

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    21/221

    Chapter 2 Local human machine interface

    11

    Sub

    menu

    Sub-sub menu Sub-sub-sub

    menu

    Explanation

    BaudR485 Selection with up or down buttons

    ProtSet

    Common Common protection setting in this menu

    EF Protection setting relation with earth faultprotection

    SEF Protection setting relation with sensitive

    earth fault protection

    STUB Protection setting relation with STUB

    protection

    3V0 Protection setting relation with displacement

    voltage protection

    CBF_PD_DZ Protection setting relation with circuit

    breaker failure, pole discordance and dead

    zone protection

    OC Protection setting relation with overcurrent

    protection

    NOC Protection setting relation with neutral

    overcurrent protection

    NSOC Protection setting relation with negative

    sequence protection

    Thermal OL Protection setting relation with thermal

    overload protection

    OV_UV Protection setting relation with overvoltageand undervoltage protection

    AR Protection setting relation with

    auto-reclosuing protection

    EquipPara

    PortContwd

    Common Common binary setting in this menu

    EF Protection binary setting relation with earth

    fault protection

    SEF Protection binary setting relation with

    sensitive earth fault protection

    STUB Protection binary setting relation with STUB

    protection

    3V0 Protection binary setting relation with

    displacement voltage protection

    CBF_PD_DZ Protection binary setting relation with circuit

    breaker failure, pole discordance and dead

    zone protection

    OC Protection binary setting relation with

    overcurrent protection

    NOC Protection binary setting relation with neutral

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    22/221

    Chapter 2 Local human machine interface

    12

    Sub

    menu

    Sub-sub menu Sub-sub-sub

    menu

    Explanation

    overcurrent protection

    NSOC Protection binary setting relation with

    negative sequence protectionThermal OL Protection binary setting relation with

    thermal overload protection

    OV_UV Protection binary setting relation with

    overvoltage and undervoltage protection

    AR Protection binary setting relation with

    auto-reclosuing protection

    4.7 IED setting

    Sub

    menu

    Sub-sub menu Sub-sub-sub

    menu

    Explanation

    Setup

    SOEReset

    Manual Reset

    Automatic

    Reset

    Really Reset

    ModifyPW The fatory password: 8888

    103Type IEC60870-5-103 code

    Protocol If communication with automation systemvia RS485 port, this item can be ignored

    AI DisplaySetDisplay Sec Ai Display secondary analog input quantity

    Display Pri Ai Display primary analog input quantity

    4.8 Test binary output

    Sub

    menu

    Sub-sub menu Sub-sub-sub

    menu

    Explanation

    Test BO

    4.9 Testing operation

    Sub

    menu

    Sub-sub menu Sub-sub-sub

    menu

    Explanation

    Testing SimuReSig

    Simu Alarm

    Usingor Xto select the simulation pointSimu Connt

    TransRecData

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    23/221

    Chapter 2 Local human machine interface

    13

    Sub

    menu

    Sub-sub menu Sub-sub-sub

    menu

    Explanation

    Simu Trip

    Simu BI

    Simu MSTAlarm

    ViewDrift

    Enter into the CPU number

    ViewScale

    PrtSample

    SwSetGr

    AdjDrift

    AdjScale

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    24/221

    Chapter 2 Local human machine interface

    14

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    25/221

    Chapter 3 Installing IED

    15

    Chapter 3 Installing IED

    About this chapter

    This chapter describes how to install the protection IED,

    introduces connection of the contactor, analogue quantities,

    binary inputs and outputs and power supply, and what should todo before and after energizing.

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    26/221

    Chapter 3 Installing IED

    16

    1 Unpacking and checking the IED

    Procedure:

    1. Remove the transporting case

    2. Visually inspect the IED

    3. Check all items included in accordace with the delivery documents. Once

    the IED has been started make sure that the software functions ordered

    have been included in the delivery

    4. Check for transport damages

    If transport damage is discovered appropriate action must be taken

    against the latest carrier and the latest SiFang office or representative

    should be informed. If there are any discrepancies in relation to the

    delivery documents, the SiFang company should be notified immediately

    5. If the protection IED is repacked for transport again, the storage packing

    of the IED must provide proper degree of protection against possible

    damage, in accordance with the standard of IEC 60255-21-1 class 1 and

    IEC 60255-21-2 class 1

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    27/221

    Chapter 3 Installing IED

    17

    2 Installing the IED

    Procedure:

    1. Insert the IED into cabinet and the bottom of the IED should be supportedon the frame of cabinet

    2. Fix the IED by tightening all screws against the cabinet. The IED should

    be fixed in the cabinet and each screw should be firmed

    3. Connect the earthing screw on the rear panel to the nearest protective

    earthing point in the cubicle. The protective earth cables should be green

    or yellow conductors with cross-sectional area 2.5mm2according to

    electrical regulations and electrical standards requirement

    The cubicle must be properly connected to station earthing system, using

    the conductor with cross-sectional area of at least 4mm2.

    4. Power supply module connection

    The wiring from the cubicle terminal block to the IED terminals must be

    connected in accordance with the established guidelines for this type of

    IED. The wires from binary inputs and outputs and the auxiliary power

    supply must be routed separated from the current transformer cablesbetween the terminal blocks of the cubicle and the IEDs connections.

    5. Connection to CT and VT circuits

    CT and VT are connected to the analogue input module on the rear side

    of the IED.

    Using solid conductor with cross-sectional 2.5-6mm2(AWG14-10) or

    stranded conductor with cross-sectional 2.5-4mm2(AWG14-12). The

    screws used for fixation conductor should be tightened.

    6. Connecting the binary input and output signals

    Auxiliary power supply and binary input and output signals are connected

    using female connectors. Signal wires are connected to a female

    connector, which is then plugged into the corresponding male connector,

    located at the rear of the IED.

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    28/221

    Chapter 3 Installing IED

    18

    3 IED connection

    3.1 IED connector

    3.1.1 Introduction

    The quantity and designation of connectors depend upon the ordering

    information and application. The rear cover plates are prepared with enough

    space for each configuration in ordering information and the cut-outs that are

    not in use are covered with a plate from factory.

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    29/221

    Chapter 3 Installing IED

    19

    3.1.2 Terminals of Analogue Input Module (AIM)

    Terminals of Analogue InputModule B

    b01 a01

    b02 a02

    b03 a03

    a04b04

    a05b05

    a06b06

    a07b07

    a08b08

    a09b09

    a10b10

    a11b11

    ab

    a12b12

    Figure 3 Terminals arrangement of AIM B

    Table 3 Description of terminals of AIM B

    Terminal Analogue

    Input

    Remark

    a01 IA Star point

    b01 IA

    a02 IB Star point

    b02 IB

    a03 IC Star point

    b03 IC

    a04 IN

    b04 IN Star point

    a05 Null

    b05 Null

    a06 Null

    b06 Null

    a07 Null

    b07 Null

    a08 Null

    b08 Null

    a09 Null

    b09 Null

    a10 Null

    b10 Null

    a11 Null

    b11 Null

    a12 Null

    b12 Null

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    30/221

    Chapter 3 Installing IED

    20

    Terminals of Analogue InputModule E

    b01 a01

    b02 a02

    b03 a03

    a04b04

    a05b05

    a06b06

    a07b07

    a08b08

    a09b09

    a10b10

    a11b11

    ab

    a12b12

    Figure 4 Terminals arrangement of AIM E

    Table 4 Description of terminals of AIM E

    Terminal Analogue

    Input

    Remark

    a01 IA Star point

    b01 IA

    a02 IB Star point

    b02 IB

    a03 IC Star point

    b03 IC

    a04 IN

    b04 IN Star point

    a05 I5

    b05 I5 Star point

    a06 Null

    b06 Null

    a07 Null

    b07 Null

    a08 Null

    b08 Null

    a09 Null

    b09 Null

    a10 U4 Star point

    b10 U4

    a11 UB Star point

    b11 UC Star point

    a12 UA Star point

    b12 UN

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    31/221

    Chapter 3 Installing IED

    21

    3.1.3 Terminals of Binary Input Module (BIM)

    c02 a02

    c04 a04

    c06 a06

    a08c08

    a10c10

    a12c12

    a14c14

    a16c16

    a18c18

    a20c20

    a22c22

    a24c24

    a26c26

    a28c28

    a30c30

    a32c32

    ac

    DC -DC -

    Figure 5 Terminals arrangement of BIM

    Table 5 Description of terminals of BIM

    Terminal Definition Remark

    a02 BI1 BI group 1

    c02 BI2 BI group 2

    a04 BI3 BI group 1

    c04 BI4 BI group 2

    a06 BI5 BI group 1

    c06 BI6 BI group 2

    a08 BI7 BI group 1

    c08 BI8 BI group 2

    a10 BI9 BI group 1

    c10 BI10 BI group 2

    a12 BI11 BI group 1

    c12 BI12 BI group 2

    a14 BI13 BI group 1

    c14 BI14 BI group 2

    a16 BI15 BI group 1

    c16 BI16 BI group 2

    a18 BI17 BI group 1

    c18 BI18 BI group 2

    a20 BI19 BI group 1

    c20 BI20 BI group 2

    a22 BI21 BI group 1

    c22 BI22 BI group 2

    a24 BI23 BI group 1

    c24 BI24 BI group 2

    a26 BI25 BI group 1

    c26 BI26 BI group 2

    a28 BI27 BI group 1

    c28 BI28 BI group 2

    a30 BI29 BI group 1

    c30 BI30 BI group 2

    a32 DC - InputCommon

    terminal of BI

    group 1

    c32 DC - Input

    Common

    terminal of BI

    group 2

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    32/221

    Chapter 3 Installing IED

    22

    3.1.4 Terminals of Binary Output Module (BOM)

    Binary Output Module A

    The module provides 16 output relays for tripping or initiating, with total 16contacts.

    a02

    R

    1

    a04

    a06

    a08

    a10

    a12

    a14

    a16

    a18

    a20

    a22

    a24

    a26

    a28

    a30

    a32

    ac

    c02

    c04

    c06

    c08

    c10

    c12

    c14

    c16

    c18

    c20

    c22

    c24

    c26

    c28

    c30

    c32

    R

    3

    R

    5

    R

    7

    R

    9

    R

    11

    R

    13

    R

    15

    R

    16

    R

    2

    R

    4

    R

    6

    R

    8

    R

    10

    R

    12

    R

    14

    Figure 6 Terminals arrangement of BOM A

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    33/221

    Chapter 3 Installing IED

    23

    Table 6 Description of terminals of BOM A

    Terminal Definition Related relay

    a02 Trip contact 1-0 Output relay 1

    c02 Trip contact 1-1 Output relay 1

    a04 Trip contact 2-0 Output relay 2

    c04 Trip contact 2-1 Output relay 2

    a06 Trip contact 3-0 Output relay 3

    c06 Trip contact 3-1 Output relay 3

    a08 Trip contact 4-0 Output relay 4

    c08 Trip contact 4-1 Output relay 4

    a10 Trip contact 5-0 Output relay 5

    c10 Trip contact 5-1 Output relay 5

    a12 Trip contact 6-0 Output relay 6

    c12 Trip contact 6-1 Output relay 6

    a14 Trip contact 7-0 Output relay 7

    c14 Trip contact 7-1 Output relay 7

    a16 Trip contact 8-0 Output relay 8

    c16 Trip contact 8-1 Output relay 8

    a18 Trip contact 9-0 Output relay 9

    c18 Trip contact 9-1 Output relay 9

    a20 Trip contact 10-0 Output relay 10

    c20 Trip contact 10-1 Output relay 10

    a22 Trip contact 11-0 Output relay 11

    c22 Trip contact 11-1 Output relay 11

    a24 Trip contact 12-0 Output relay 12

    c24 Trip contact 12-1 Output relay 12

    a26 Trip contact 13-0 Output relay 13

    c26 Trip contact 13-1 Output relay 13

    a28 Trip contact 14-0 Output relay 14

    c28 Trip contact 14-1 Output relay 14

    a30 Trip contact 15-0 Output relay 15

    c30 Trip contact 15-1 Output relay 15

    a32 Trip contact 16-0 Output relay 16

    c32 Trip contact 16-1 Output relay 16

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    34/221

    Chapter 3 Installing IED

    24

    Binary Output Module C

    The module provides 16 output relays for signal, with total 19 contacts.

    a02

    a04

    a06

    a08

    a10

    a12

    a14

    a16

    a18

    a20

    a22

    a24

    a26

    a28

    a30

    a32

    ac

    c02

    c04

    c06

    c08

    c10

    c12

    c14

    c16

    c18

    c20

    c22

    c24

    c26

    c28

    c30

    c32

    R4

    R5

    R1

    R2

    R3

    R6

    R7

    R

    16

    R

    9

    R

    10

    R

    11

    R

    12

    R

    13

    R

    14

    R

    15

    R

    8

    Figure 7 Terminals arrangement of BOM C

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    35/221

    Chapter 3 Installing IED

    25

    Table 7 Description of terminals of BOM C

    Terminal Definition Related relay

    a02 Signal 1-0, Common terminal of signal contact group 1

    c02 Signal 2-0, Common terminal of signal contact group 2

    a04 Signal contact 1-1 Output relay 1

    c04 Signal contact 2-1 Output relay 1

    a06 Signal contact 1-2 Output relay 2

    c06 Signal contact 2-2 Output relay 2

    a08 Signal contact 1-3 Output relay 3

    c08 Signal contact 2-3 Output relay 3

    a10 Signal 3-0, Common terminal of signal contact group 3

    c10 Signal 4-0, Common terminal of signal contact group 4

    a12 Signal contact 3-1 Output relay 4

    c12 Signal contact 4-1 Output relay 7

    a14 Signal contact 3-2 Output relay 5

    c14 Signal contact 4-2 Output relay 6

    a16 Signal contact 5-0 Output relay 8

    c16 Signal contact 5-1 Output relay 8

    a18 Signal contact 6-0 Output relay 9

    c18 Signal contact 6-1 Output relay 9

    a20 Signal contact 7-0 Output relay 10

    c20 Signal contact 7-1 Output relay 10

    a22 Signal contact 8-0 Output relay 11

    c22 Signal contact 8-1 Output relay 11

    a24 Signal contact 9-0 Output relay 12

    c24 Signal contact 9-1 Output relay 12

    a26 Signal contact 10-0 Output relay 13

    c26 Signal contact 10-1 Output relay 13

    a28 Signal contact 11-0 Output relay 14

    c28 Signal contact 11-1 Output relay 14

    a30 Signal contact 12-0 Output relay 15

    c30 Signal contact 12-1 Output relay 15

    a32 Signal contact 13-0 Output relay 16

    c32 Signal contact 13-1 Output relay 16

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    36/221

    Chapter 3 Installing IED

    26

    3.1.5 Terminals of Communication module (COM)

    0102

    03

    04

    05

    06

    07

    08

    09

    10

    11

    12

    13

    14

    15

    16

    EthernetportB

    EthernetportA

    EthernetportC

    Figure 8 Terminals arrangement of COM

    5

    6

    7

    8

    9

    10Ethernet

    port

    Figure 9 Examples of COM module

    Table 8 Description of terminals of COM

    Terminal Definition

    01 Null

    02 Null

    03 Null

    04 Null

    05 Optional RS485 port - 2B

    06 Optional RS485 port - 2A

    07 Optional RS485 port - 1B

    08 Optional RS485 port - 1A

    09 Time synchronization

    10 Time synchronization GND

    11 Null

    12 Null

    13 Null

    14 Null

    15 Null

    16 Null

    Ethernet

    Port A

    Optional optical fiber or RJ45

    port for station automation

    system

    Ethernet

    Port B

    Optional optical fiber or RJ45

    port for station automationsystem

    Ethernet

    Port C

    Optional optical fiber or RJ45

    port for station automation

    system

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    37/221

    Chapter 3 Installing IED

    27

    3.1.6 Terminals of Power Supply Module (PSM)

    c02 a02

    c04 a04

    c06 a06

    a08c08

    a10c10

    a12c12

    a14c14

    a16c16

    a18c18

    a20c20

    a22c22

    a24c24

    a26c26

    a28c28

    a30c30

    a32c32

    ac

    DC 24V +

    OUTPUTS

    DC 24V -

    OUTPUTS

    AUX.DC +

    INPUT

    AUX. DC -

    INPUT

    Figure 10 Terminals arrangement of PSM

    Table 9 Description of terminals of PSM

    Terminal Definition

    a02 AUX.DC 24V+ output 1

    c02 AUX.DC 24V+ output 2

    a04 AUX.DC 24V+ output 3

    c04 AUX.DC 24V+ output 4

    a06 Isolated terminal, not wired

    c06 Isolated terminal, not wired

    a08 AUX.DC 24V- output 1

    c08 AUX.DC 24V- output 2

    a10 AUX.DC 24V- output 3

    c10 AUX.DC 24V- output 4

    a12 AUX.DC 24V- output 5

    c12 AUX.DC 24V- output 6

    a14 Alarm contact A1, for

    AUX.DC power input failure

    c14 Alarm contact A0, for

    AUX.DC power input failure

    a16 Alarm contact B1, for

    AUX.DC power input failure

    c16 Alarm contact B0, for

    AUX.DC power input failure

    a18 Isolated terminal, not wired

    c18 Isolated terminal, not wired

    a20 AUX. power input 1, DC +

    c20 AUX. power input 2, DC +a22 AUX. power input 3, DC +

    c22 AUX. power input 4, DC +

    a24 Isolated terminal, not wired

    c24 Isolated terminal, not wired

    a26 AUX. power input 1, DC -

    c26 AUX. power input 2, DC -

    a28 AUX. power input 3, DC -

    c28 AUX. power input 4, DC -

    a30 Isolated terminal, not wired

    c30 Isolated terminal, not wired

    a32 Terminal for earthing

    c32 Terminal for earthing

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    38/221

    Chapter 3 Installing IED

    28

    3.1.7 RS232 port

    RS232 serial port is located on front panel, the software tool in PC can be

    connected with the IED via this port to make setting, testing and cofiguration,

    etc.

    3.2 Connecting to protective earth

    Connect the earthing screw on the rear panel to the nearest protective

    earthing point in the cubicle. The protective earth cables should be green or

    yellow conductors with cross-sectional area 2.5mm2according to electrical

    regulations and electrical standards requirement.

    The cubicle must be properly connected to station earthing system, using the

    conductor with cross-sectional area of at least 4mm2.

    3.3 Connecting the power supply module

    The wiring from the cubicle terminal block to the IED terminals must be

    connected in accordance with the established guidelines for this type of IED.

    The wires from binary inputs and outputs and the auxiliary power supply must

    be routed separated from the current transformer cables between the terminal

    blocks of the cubicle and the IEDs connections.

    3.4 Connecting to CT and VT circuits

    CT and VT are connected to the analogue input module on the rear side of

    the IED.

    Using solid conductor with cross-sectional 2.5-6mm2(AWG14-10) or stranded

    conductor with cross-sectional 2.5-4mm2(AWG14-12). The screws used for

    fixation conductor should be tightened.

    3.5 Connecting the binary inputs and outputs

    Auxiliary power supply and binary input and output signals are connected

    using female connectors. Signal wires are connected to a female connector,

    which is then plugged into the corresponding male connector, located at the

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    39/221

    Chapter 3 Installing IED

    29

    rear of the IED.

    Procedure:

    1. Connect wire to the female connector

    All wiring to the female connector should be done before it is plugged into

    the male part and screwed to the case. The conductors can be of rigid

    type (solid, stranded) or of flexible type.

    The female connectors accept conductors with a cross section area of

    0.2-1.5 mm2 (AWG 24-15). If two conductors are used in the same

    terminal, the maximum permissible cross section area is 0.2-0.8 mm2

    (AWG 24-18, each conductor corresponding to one cross section area).

    If two conductors, each with area 1.5 mm2(AWG 15) need to be

    connected to the same terminal, a ferrule must be used to combine the

    two conductors, no soldering is needed.

    Press the locking button by screwdriver to insert the wiring with ferrule

    into the connector, move away the screwdriver after the ferrule has been

    inserted into the connector completely to lock the wiring tightly. The follow

    picture illustrates this process.

    Figure 11 Connection illustration without inserting the connector

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    40/221

    Chapter 3 Installing IED

    30

    Figure 12 Connection illustration with inserting the connector

    2. Plug the connector to the corresponding back-side mounted male

    connector

    3. Lock the connector by fastening the lock screws

    3.6 Making the screen connection

    When using screened cables always make sure screens are earthed and

    connected according to applicable engineering methods. This may include

    checking for appropriate earth points near the IED, for instance, in the cubicle

    and/or near the source of measuring. Ensure that earth connections are

    made with short conductors of an adequate cross section, at least 6 mm2(AWG10) for single screen connections.

    3.7 RS485 and RS232 ports connection

    3.7.1 RS485 port connection

    The RS485 interface is capable of half-duplex service with the signals A/A'

    and B/B' to transmit signals.

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    41/221

    Chapter 3 Installing IED

    31

    The network topology of RS485 adopts bus type of terminal matched, do not

    support ring or star network. Use the single and continuous channel as bus.

    The terminating resistance is located on beginning and terminal of the bus

    cable. The other ports do not need the terminating resistance.

    As shown inFigure 8andFigure 9,RS485 port located on the rear side of

    communication module. The IED provides two electrical isolation RS485

    ports, the two ports can work at the same time with IEC60870-5-103 protocol

    supported.

    3.7.2 RS232 port connection

    One RS232 serial port is provided and located on front panel, which is used to

    connect personal computer. The RS232 port adopts half-dupexcommunication mode, usually which is connected with 9-pin D-subminiature

    female connectors

    Connection method: direction connection cable for serial port, the IED

    terminal is pins and the PC termianl is female connector. The terminal of 2, 3,

    4 and 5 is connected directly. As shown in the following picture:

    Figure 13 Example for serial port connection

    The line 4 must be connected directly

    3.8 Connecting the GPS

    Mount the GPS antenna on the building roof or the place of visibility to all

    direction is obtained, top of the antenna should be horizontal. Mount the

    antenna to console and fix the console on the building roof with expansion

    bolts. The turning radius should not be too small when laying the cables. The

    length of antenna cables is designed strictly based on antenna gain, so, it is

    not allowed to lengthen, shorten or add connectors that will affect signal

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    42/221

    Chapter 3 Installing IED

    32

    reception or can't receive any signals.

    The principle for mounting GPS antenna is that the position is visible

    completely to all directions in 360, however, for some special conditions,

    mount the antenna at the place with best visibility as far as possible.

    The GPS port is located on the rear side of communication module, as shown

    inFigure 8andFigure 9,which can be connected with screened twist-pair

    cable.

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    43/221

    Chapter 3 Installing IED

    33

    4 Checking before energizing

    4.1 Introduction

    After completing the IED connections, the related connections need to be

    checked, this section descirbes what should be checked before energizing.

    This is done with IED and all connected circuits de-energized.

    4.2 Checking the protective earth connection

    Check the protective earthing connection of IED is connected reliably in

    accordance with the related electrical regulations and standards.

    4.3 Checking the power supply connection

    Check that the auxiliary power supply voltage remains within the permissible

    input voltage range under all operating conditions. Check that the polarity is

    correct.

    4.4 Checking the CT and VT circuits connection

    4.4.1 Checking the CT circuits connection

    Check that the wiring is in strict accordance with the supplied connection

    diagram. If any errors appearance, do not continue before any errors are

    corrected. The following tests shall be performed on every primary CT

    connected to IED:

    Primary injection test to verify the current change ratio of the CT, the

    correct wiring up to the protection IED and correct phase sequence

    connection (i.e. A, B, C)

    Polarity checking to prove that the predicted direction of secondary

    current flow is correct for a given direction of primary current flow

    CT secondary loop resistance measurement in order to confirm that the

    current transformer secondary loop DC resistance is within specification

    and that there are no high resistance joints in the CT winding or wiring

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    44/221

    Chapter 3 Installing IED

    34

    CT excitation test in order to confirm that the current transformer is of the

    correct accuracy rating and that there are no shorted turns in the current

    transformer windings. Manufacturer's design curves should be available

    for the current transformer in order to compare the actual results

    Check the earthing of the individual CT secondary circuits to verify that

    each three-phase set of main CTs is properly connected to the station

    earth and only at one electrical point

    Checking the insulation resistance

    Phase identification of CT shall be made

    Both primary and secondary sides must be disconnected from theline and IED when plotting the excitation characteristics

    If the CT secondary circuit earth connection is removed without the

    current transformer primary being de-energized, dangerous voltages

    may result in the secondary CT circuits

    4.4.2 Checking the VT connection

    Check that the wiring is in strict accordance with the supplied connection

    diagram. If any errors appearance, do not continue before any errors are

    corrected.

    The following tests are recommended:

    Polarity check

    VT circuit voltage measurement (primary injection test)

    Grounding check

    Phase relationship

    Insulation resistance check

    4.5 Checking the binary input and output connection

    4.5.1 Checking the binary input connection

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    45/221

    Chapter 3 Installing IED

    35

    When checking the binary inputs, it's better to disconnect the binary input

    connector from binary input module. Check all connected signals in order to

    make sure that both the input level and polarity of voltage are in accordance

    with the IEDs specifications.

    4.5.2 Checking the binary output connection

    When checking the binary outputs, it's better to disconnect the binary output

    connector from binary output module. Check all connected signals in order to

    make sure that both the input level and polarity of voltage are in accordance

    with the IEDs specifications.

    4.6 Checking the screened cables connection

    Check that the screened cables are connected correctly.

    4.7 Checking the RS485 and RS232 port connectios

    4.7.1 Checking the RS485 port connection

    Check that the RS485 port connections are correct.

    4.7.2 Checking RS232 port connection

    Check that the RS232 serial port connections are correct.

    4.8 Checking GPS connection

    Check that the GPS connections are correct.

    4.9 Checking the insulation voltage and insulationresistance

    4.9.1 Checking the insulation voltage

    Using the withstand voltage tester to apply correspondung level voltagebetween tested circuit and earth, and between circuits (e.g. 2000VAC

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    46/221

    Chapter 3 Installing IED

    36

    /2800VDC), lasting 1 min. No flashover and breakdown apperance, the

    leakage current is less than 10mA.

    4.9.2 Checking the insulation resistance

    Using a rotating meter with 500V to test insulation resistance in turn between

    analog circuits and earth, and the circuits to each other. Every resistance

    must not be less than 100 M. And the lasting time for resistance test is not

    less than 5s to ensure that the value of insulation resistance is read in a

    steady state.

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    47/221

    Chapter 3 Installing IED

    37

    5 Checking after energizing

    5.1 Introduction

    After completing of the external circuits connection, checking all connections

    and energizing the IED, LCD and keyboard should be tested. Check that the

    software version, serial number and the installed modules are in accordance

    with ordering information. The IED time need to be set to ensure that the IED

    time is synchronized with local time. The self-supervision function should also

    be checked to verify that the IED operates properly.

    5.2 Test LCD

    After energizing the IED, the blue background of LCD light up, operate the

    keys to turn pages to check that the LCD display is correct.

    5.3 Test the keyboard

    All the keys on front panel including Arrow keys, Reset key, Set key, Quit key

    and shortcut key can be operated to check that these keys satisfy with the

    correpsonding function, the detail functions of each key are described inTable 1.

    5.4 Setting the IED time

    This procedure describes how to set the IED time from the local HMI.

    1. Enter into the time setting menu: Set Time, press the Set button to enter

    into the setting menu

    2. Set the date and time

    Use the Left and Right arrow buttons to move between the time and date

    values (year, month, day, hours, minutes and seconds). Use the Up and

    Down arrow buttons to change the value.

    3. Confirm the setting

    Press the Set button to set the data and clock to the new values.

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    48/221

    Chapter 3 Installing IED

    38

    5.5 Self-supervision HMI data

    Table 10 Self-supervision HMI data

    Information Detail information Possible reason and solutions

    Communication

    Fail

    Communication

    Failure

    Communication fails between CPU and COM module.

    In this condition either the CPU is working abnormal or

    the CAN (Controller Area Network) network

    communication has been interrupted. Check each CPU

    working state or CAN network on backboard.

    Write Set Fail Write setting failure Write setting again

    Write DevPara FailWrite Device

    parameter failureWrite device parameter again

    No response for calling CPU configuration

    Maybe the address of two CPU modules are same,

    one of the two modules is not inserted or connected

    badly

    Alarming code XX The CPU modules is disabled

    5.6 Checking the software and hardware version

    Enter into menu: OpStatus/EquipCode

    Checking the software version: In this menu, to check the protection

    programm version.

    Checking the hardware version: In this menu, to check the equipment code,

    the version of binary input and output module, communication module and

    HMI.

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    49/221

    Chapter 4 Read and change setting

    39

    Chapter 4 Read and change setting

    About this chapter

    This chapter describes how to set and read the setting values

    and parameters either through LHMI or software tool, and how

    to switch the setting value group.

    This chapter does not contain instructions on how to calculate

    the setting value, for the detail setting calculation information

    please refers to the Technical application manual.

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    50/221

    Chapter 4 Read and change setting

    40

    1 Read and change the setting vaule

    1.1 Read and change the setting value via LHMI

    1.1.1 Introduction

    All the function settings and binary settings can be read and set through LHMI.

    The user can browse to the desired settings and enter into the appropriate

    vaules, The parameters for each function can be found in the LHMI. See the

    Technical applciation manual for a complete list of setting parameters for

    each function.

    1.1.2 Communication parameter

    1.1.2.1 Bay name

    Enter into menu: Settings/CommPara/BayName

    Check and change bay name.

    1.1.2.2 Time synchronization mode

    SNTP mode

    Enter into menu: Settings/CommuPara/TimeMode/NetworkTimeMode

    The time synchronization mode can be changed into network time mode via

    this setting.

    PulseTimeMode

    Enter into menu: Settings/CommuPara/TimeMode/PulesTimeMode

    The time synchronization mode can be changed into pulse time mode via this

    setting.

    IRIG-BTimeMode

    Enter into menu: Settings/CommuPara/TimeMode/IRIG-BTimeMode

    The time synchronization mode can be changed into IRIG-B time mode via

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    51/221

    Chapter 4 Read and change setting

    41

    this setting.

    1.1.2.3 Communication address

    Enter into menu: Settings/CommuPara/CommAddr

    The address of Lon network, RS485 port, Ethernet port 1and Ethernet 2 can

    be modified in this setting .

    1.1.2.4 485 baud rate

    Enter into menu: Settings/CommuPara/BaudR485

    485 baud rate is displayed and modified here.

    1.1.3 Equipment parameter

    Enter into menu: Settings/EquipPara

    In this menu, the following items is displayed and can be modified: sampling

    frequency for recording, rising or falling edge selection for each function.

    All the functions are enabled or disabled via 1 or 0, 1 means enable, 0 means

    disable.

    Left or right keys are used to select value for pre-recording time and the up

    and down keys are used to change value.

    Note: when the cursor move to this item, at the bottom of screen,

    displays the time limit for pre-recording time.

    Left or right keys are used to select value for post-recording time and the up

    and down keys are used to change value.

    Note: when the cursor move to this item, at the bottom of screen,

    displays the time limit for post-recording time.

    1.1.4 Setting values and binary settings for protectionfunction

    1.1.4.1 Introduction

    Protection setting

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    52/221

    Chapter 4 Read and change setting

    42

    The menu of protection setting is used to check and modify every function

    setting, using left and right button to chose the vaule and the up and down

    buttons are used to modify the value, the upper and lower limits of setting

    value will be displayed when the cursor move to corresponding setting items.

    Protection binary setting

    The protection binary settings are used to enable or disable each function,

    1means enable and 0 means disable.

    1.1.4.2 Common setting

    1.1.4.2.1 Time for relay reset

    Enter into menu: Settings/ProtSet/Pls Input SetGrNo/Common

    Check and set the time for relay reset.

    1.1.4.2.2 Rated value of line voltage

    Enter into menu: Settings/ProtSet/Pls Input SetGrNo/Common

    Check and set the primary and secondary rated value of line voltage.

    1.1.4.2.3 Rated current value

    Enter into menu: Settings/ProtSet/Pls Input SetGrNo/Common

    Check and set the primary and secondary rated current value.

    1.1.4.3 Common binary setting

    1.1.4.3.1 VT conneted from line side

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/Common

    Enable or disable the VT connected from line side or bus side.

    1.1.4.3.2 Switch setting group by binary input

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/Common

    Enable or disable the setting group is switched by binary input.

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    53/221

    Chapter 4 Read and change setting

    43

    1.1.4.3.3 Test mode

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/Common

    Enable or disable the test mode

    1.1.4.3.4 Block remote access

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/Common

    Enable or disable the function of block remote access.

    1.1.4.3.5 I5 for SEF

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/Common

    Enable or disable the the I5 current channel is appiled for SEF function or

    NOC function.

    1.1.4.4 Overload function

    Enter into menu: Settings/Test Menu/Pls Input SetGrNo/Common

    Enable or disable the binary setting for overload function.

    1.1.4.5 Overcurrent protection

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/OC

    Enable or disable the definite time stage and inverse time stage of

    overcurrent protection function, and the features related with overcurrent

    protection.

    Enter into menu: Settings/ProtSet/Pls Input SetGrNo/OC

    Check and set the various settings of overcurrent protection.

    1.1.4.6 Earth fault protection

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/EF

    Enable or disable the definite time stage and inverse time stage of earth fault

    protection function, and the features related with earth fault protection.

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    54/221

    Chapter 4 Read and change setting

    44

    Enter into menu: Settings/ProtSet/Pls Input SetGrNo/EF

    Check and set the various settings of earth fault protection.

    1.1.4.7 Neutral earth fault protection

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/NOC

    Enable or disable the definite time stage and inverse time stage of neutral

    earth fault protection function, and the features related with neutral earth fault

    protection.

    Enter into menu: Settings/ProtSet/Pls Input SetGrNo/ NOC

    Check and set the various settings of neutral earth fault protection.

    1.1.4.8 Sensitive earth fault protection

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/SEF

    Enable or disable the definite time stage and inverse time stage of sensitive

    earth fault protection function, and the features related with sensitive earth

    fault protection.

    Enter into menu: Settings/ProtSet/Pls Input SetGrNo/SEF

    Check and set the various settings of sensitive earth fault protection.

    1.1.4.9 Negative sequence overcurrent protection

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/NSOC

    Enable or disable the definite time stage and inverse time stage of negative

    sequence overcurrent protection function, and the features related withsensitive earth fault protection.

    Enter into menu: Settings/ProtSet/Pls Input SetGrNo/NSOC

    Check and set the various settings of negative sequence overcurrent

    protection.

    1.1.4.10 STUB protection

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/STUB

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    55/221

    Chapter 4 Read and change setting

    45

    Enable or disable the STUB proteciton.

    Enter into menu: Settings/ProtSet/Pls Input SetGrNo/STUB

    Check and set the various settings of STUB protection.

    1.1.4.11 Thermal overload protection

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/Thermal OL

    Enable or disable the thermal overload proteciton and relevant functions.

    Enter into menu: Settings/ProtSet/Pls Input SetGrNo/Thermal OL

    Check and set the various settings of thermal overload protection.

    1.1.4.12 Displacement voltage protection

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/3V0

    Enable or disable the displacement voltage protection and relevant functions.

    Enter into menu: Settings/ProtSet/Pls Input SetGrNo/3V0

    Check and set the various settings of displacement voltage protection.

    1.1.4.13 Overvoltage protection

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/OV_UV

    Enable or disable the overvoltage protection and relevant functions.

    Enter into menu: Settings/ProtSet/Pls Input SetGrNo/OV_UV

    Check and set the various settings of overvoltage protection.

    1.1.4.14 Undervoltage protection

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/OV_UV

    Enable or disable the undervoltage protection and functions related with

    voltage protection.

    Enter into menu: Settings/ProtSet/Pls Input SetGrNo/OV_UV

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    56/221

    Chapter 4 Read and change setting

    46

    Check and set the various settings of undervoltage protection.

    1.1.4.15 Circuit breaker failre protection

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/CBF_PD_DZ

    Enable or disable the circuit breaker failure protection and functions related

    with circuit breaker failure protection.

    Enter into menu: Settings/ProtSet/Pls Input SetGrNo/CBF_PD_DZ

    Check and set the relevant settings of circuit breaker failure protection.

    1.1.4.16 Poles discordance protection

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/CBF_PD_DZ

    Enable or disable the poles discordance protection and functions related with

    poles discordance protection.

    Enter into menu: Settings/ProtSet/Pls Input SetGrNo/CBF_PD_DZ

    Check and set the relevant settings of poles discordance protection.

    1.1.4.17 Dead zone protection

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/CBF_PD_DZ

    Enable or disable the dead zone portection.

    Enter into menu: Settings/ProtSet/Pls Input SetGrNo/CBF_PD_DZ

    Check and set the relevant settings of dead zone protection.

    1.1.4.18 Auto-reclosing function

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/AR

    Enable or disable the modes of auto-reclosing and the relevant discrimination

    and functions for auto-reclosing funtion.

    Enter into menu: Settings/ProtSet/Pls Input SetGrNo/AR

    Check and set the the relevant settings for each shot and the disrimination

  • 7/27/2019 CSC-121 Breaker Protection IED Engineering and Operation Manual_V1.00

    57/221

    Chapter 4 Read and change setting

    47

    setting.

    1.1.4.19 Synchro-check and energizing check function

    Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/AR

    Enable or disable the modes for synchro-check and energizing check

    function.

    Enter into menu: Settings/ProtSet/Pls Input SetGrNo/AR

    Check and set the the various settings fo