Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de...

42
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide Applications The TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers are stand-alone and field- selectable BACnet® MS/TP or N2 networked devices. Wireless networked models of the TEC3000 Series Thermostat Controller are also available. Series Single- or Two-Stage Economizer Thermostat Controllers provide control of the following: Unitary rooftop units (RTUs) Unitary RTUs with economizers Unitary heat pumps Unitary heat pumps with economizers Unitary RTUs with hot gas reheat Unitary RTUs with hot gas reheat and economizers The networked models feature a field-selectable Building Automation System (BAS) BACnet MS/TP or N2 communication capability that enables remote monitoring and programming for efficient space temperature control. The wireless models are compatible with the WNC1800/ ZFR182x Pro Series Wireless Field Bus System that enables communication with a building automation system (BAS). The wireless models (TEC30xx-xx-000) are compatible only with the WNC1800/ZFR182x Pro Series Wireless Field Bus System that enables communication with a building automation system (BAS). The new wireless models (TEC31xx-14-000) are compatible only with WRG1830/ ZFR183x Pro Series Wireless Field Bus System. All models include a USB port configuration that reduces installation time to allow simple backup and restore features from a USB drive, which enables rapid cloning of configuration between similar units. Some models have occupancy sensing capability built into the device. These thermostat controllers maximize up to 30% energy savings in high-energy usage commercial buildings, such as schools and hotels, during occupied times by using additional standby setpoints. All models feature an intuitive onboard touchscreen UI with backlit display that makes setup and operation quick and easy. Only the single-speed fan configuration is supported for fan coil equipment types. All models contain a build-in humidity sensor to support dehumidification on RTUs with hot gas reheat and RTUs with auxiliary dehumidifier installed. When no heating is required, the thermostat controller monitors the space humidity and activates dehumidification control as necessary. Heat, reheat or both are used as required to prevent over-cooling while achieving humidity setpoint and maintain the space temperature. Important: The TEC3000 Series Thermostat Controller is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the thermostat controller. Important: Le TEC3000 Series Thermostat Controller est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du thermostat controller risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du thermostat controller. North American emissions compliance United States This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference ina residential installation. This equipment generates, uses and can radiate radio frequency energy and, if notinstalled and used in accordance with the instructions, may cause harmful interference to radio communications.However, there is no guarantee that interference will not occur in a particular installation. If this equipment doescause harmful interference to radio or television reception, which can be determined by turning the equipment offand on, the user is encouraged to try to correct the interference by one or more of the following measures: Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. LIT-12013163 2020-07-06 TEC3330-1x-xxx, TEC3331-1x-xxx, TEC3630-1x-xxx, TEC3631-1x-xxx, TEC3030-1x-xxx, TEC3031-1x-xxx, TEC313x-14-xxx

Transcript of Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de...

Page 1: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

TEC3000 Series Networked and WirelessSingle- or Two-Stage Economizer Thermostat

Controllers Installation Guide

ApplicationsThe TEC3000 Series Single- or Two-Stage EconomizerThermostat Controllers are stand-alone and field-selectable BACnet® MS/TP or N2 networked devices.Wireless networked models of the TEC3000 SeriesThermostat Controller are also available. Series Single- orTwo-Stage Economizer Thermostat Controllers providecontrol of the following:• Unitary rooftop units (RTUs)• Unitary RTUs with economizers• Unitary heat pumps• Unitary heat pumps with economizers• Unitary RTUs with hot gas reheat• Unitary RTUs with hot gas reheat and economizersThe networked models feature a field-selectableBuilding Automation System (BAS) BACnet MS/TP or N2communication capability that enables remote monitoringand programming for efficient space temperature control.The wireless models are compatible with the WNC1800/ZFR182x Pro Series Wireless Field Bus System that enablescommunication with a building automation system (BAS).The wireless models (TEC30xx-xx-000) are compatibleonly with the WNC1800/ZFR182x Pro Series Wireless FieldBus System that enables communication with a buildingautomation system (BAS). The new wireless models(TEC31xx-14-000) are compatible only with WRG1830/ZFR183x Pro Series Wireless Field Bus System. All modelsinclude a USB port configuration that reduces installationtime to allow simple backup and restore features from aUSB drive, which enables rapid cloning of configurationbetween similar units.Some models have occupancy sensing capability built intothe device. These thermostat controllers maximize up to30% energy savings in high-energy usage commercialbuildings, such as schools and hotels, during occupiedtimes by using additional standby setpoints.All models feature an intuitive onboard touchscreenUI with backlit display that makes setup and operationquick and easy. Only the single-speed fan configuration issupported for fan coil equipment types.All models contain a build-in humidity sensor to supportdehumidification on RTUs with hot gas reheat and RTUswith auxiliary dehumidifier installed. When no heatingis required, the thermostat controller monitors thespace humidity and activates dehumidification control asnecessary. Heat, reheat or both are used as required toprevent over-cooling while achieving humidity setpointand maintain the space temperature.

Important: The TEC3000 Series ThermostatController is intended to provide an input toequipment under normal operating conditions.Where failure or malfunction of the thermostatcontroller could lead to personal injury or propertydamage to the controlled equipment or otherproperty, additional precautions must be designedinto the control system. Incorporate and maintainother devices, such as supervisory or alarm systemsor safety or limit controls, intended to warn ofor protect against failure or malfunction of thethermostat controller.Important: Le TEC3000 Series ThermostatController est destiné à transmettre des donnéesentrantes à un équipement dans des conditionsnormales de fonctionnement. Lorsqu'unedéfaillance ou un dysfonctionnement duthermostat controller risque de provoquer desblessures ou d'endommager l'équipementcontrôlé ou un autre équipement, la conception dusystème de contrôle doit intégrer des dispositifs deprotection supplémentaires. Veiller dans ce cas àintégrer de façon permanente d'autres dispositifs,tels que des systèmes de supervision ou d'alarme,ou des dispositifs de sécurité ou de limitation, ayantune fonction d'avertissement ou de protection encas de défaillance ou de dysfonctionnement duthermostat controller.

North American emissionscomplianceUnited StatesThis equipment has been tested and found to comply withthe limits for a Class B digital device, pursuant to Part15of the FCC Rules. These limits are designed to providereasonable protection against harmful interference inaresidential installation. This equipment generates, usesand can radiate radio frequency energy and, if notinstalledand used in accordance with the instructions, may causeharmful interference to radio communications.However,there is no guarantee that interference will not occurin a particular installation. If this equipment doescauseharmful interference to radio or television reception,which can be determined by turning the equipmentoffand on, the user is encouraged to try to correct theinterference by one or more of the following measures:• Reorient or relocate the receiving antenna.• Increase the separation between the equipment and

receiver.• Connect the equipment into an outlet on a circuit

different from that to which the receiver is connected.

LIT-12013163

2020-07-06

TEC3330-1x-xxx, TEC3331-1x-xxx, TEC3630-1x-xxx,TEC3631-1x-xxx, TEC3030-1x-xxx, TEC3031-1x-xxx,

TEC313x-14-xxx

Page 2: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

• Consult the dealer or an experienced radio/TVtechnician for help.

CanadaThis Class (B) digital apparatus meets all the requirementsof the Canadian Interference-Causing EquipmentRegulations.Cet appareil numérique de la Classe (B) respecte toutesles exigences du Réglement sur le matériel brouilleurduCanada.

InstallationParts included• One TEC3000 Series Thermostat Controller with integral

mounting base• One installation instructions sheet

Location considerationsFor networked models, locate the TEC3000 SeriesThermostat Controller:• On a partitioning wall, approximately 5 ft (1.5 m) above

the floor in a location of average temperature, to allowfor vertical air circulation to the TEC

• Away from direct sunlight, radiant heat, outside walls,outside doors, air discharge grills, stairwells, and frombehind doors

• Away from steam or water pipes, warm air stacks,unconditioned areas (not heated or cooled), or sourcesof electrical interference

• In a clear path between the integrated passive infrared(PIR) occupancy sensor, if equipped, and the space itmonitors

For wireless models, also locate the thermostat controller:• Outside of a recessed area, metal enclosure, or shelving

unit• On the same building level as the other wireless devices

on the same personal area network (PAN)• At least 2 in. (51 mm) away from any metal obstruction• In the direct line of sight to other wireless devices on

the same PAN. Signal transmission is best if the pathbetween the TEC3000 and other wireless devices isdirect as possible. Line of sight is desirable but notrequired. See Table 1 and Table 2 for the recommendedand maximum distances.

• Away from metal and large solid obstructions, thatincludes equipment rooms and elevator shafts andconcrete or brick walls, between the TEC3000 andthe ZFR182x or ZFR183x Router/Repeater or ZFR ProCoordinator Radio

• Within range of two or more wireless devices on thesame PAN. Redundancy in the layout provides the bestreliability in wireless installations

• At least 20 ft (6 m) from a microwave ovenFor integrated PIR models, make sure that the thermostatcontroller is located centrally, where occupant movementis frequent. Ensure that the unit is not blocked by a plastictamper resistant enclosure (such as the GRD10A-608). Theplastic enclosure blocks the occupancy sensing capability.

The use of insulating foam pads is necessary forinstallations where wiring passes through the wall to thethermostat.For wireless models, the effective transmission range anddistance for indoor applications vary because of wirelesssignal absorption and reflection due to metal obstructions,walls or floors, and furniture that is found in buildinginteriors.Table 1: Indoor line-of-sight transmission rangesZFR182x

Range type Transmission distanceWNC CoordinatorRadio, ZFR ProRepeater

TEC3000 WirelessThermostatController

Recommended 50 ft (15.2 m) 50 ft (15.2 m)Line of sight,maximum

250 ft (76.2 m) 100 ft (30 m)

Note:• Allow for sufficient clearance to insert a USB drive

into the USB port• For more details about using ZFR Pro Series

communication devices, refer to the WNC1800/ZFR182x Pro Series Wireless Field Bus SystemTechnical Bulletin (LIT-12012356).

Important: Only connect memory devicesto the USB port. Do not use it for chargingexternal devices.

Table 2: Indoor line-of-sight transmission rangesZFR183x

Range type Transmission distanceWNC CoordinatorRadio, ZFR ProRepeater

TEC3000 WirelessThermostatController

Recommended 250 ft (76.2 m) 50 ft (15.2 m)Line of sight,maximum

4000 ft (1219.2 m) 100 ft (30 m)

Note:• Actual range depends on the site and installation

conditions. See Technical Documentation for moreinformation.

• For more details about using ZFR Pro Seriescommunication devices, refer to the WNC1800/ZFR183x Pro Series Wireless Field Bus SystemTechnical Bulletin (LIT-12013553).

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide2

Page 3: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Figure 1: Thermostat controller shown withoutoccupancy sensor, dimensions, in. (mm)

Table 3: Thermostat controller features

Callout Description1 Security screw2 Display3 USB port

Installing the thermostat controller1. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson

Controls® T-4000-119 Allen-Head Adjustment Tool(order separately) to remove the security screw if itis installed on the top of the thermostat controllercover as illustrated in Figure 2.

2. Pull the top edge of the cover and open thethermostat controller as illustrated in Figure 2.

Important: The cover is not secured on thebottom. Do not drop the cover.Important: If you are installing more than onethermostat controller, keep track of which coverattaches to which base. The controller versionand the base version must match to ensurecorrect operation.Important: Use correct Electrostatic Discharge(ESD) precautions during installation andservicing to avoid damage to the electroniccircuits of the thermostat controller.

Figure 2: Removing the security screw from the thermostatcontroller cover, shown without occupancy sensor, andremoving the thermostat controller cover

3. Align the thermostat controller mounting base onthe wall with the security screw on the top and usethe base as a template to mark the two mountinghole locations. See Figure 3.

- If you need to install the thermostat controlleron an electrical junction box, use 2-1/2 in. x4 in. (63 mm x 101 mm) square boxes withmud ring covers and avoid smaller 1-1/2 in.x 4 in. (38 mm x 101 mm) square or 3 in. x 2in. (76 mm x 51 mm) boxes. This procedureensures that you have enough space forcabling, if needed.

- For surface-mounted applications, use durablemounting hardware, such as wall anchors, thatcannot be easily pulled out of the mountingsurface.

4. Pull approximately 6 in. (152 mm) of wire from thewall and insert the wire through the center holein the thermostat controller mounting base. SeeFigure 3.

5. Secure the mounting base to the wall surface usingtwo mounting screws (user supplied) as illustratedin Figure 3.

Note: Do not overtighten the mounting screws.

Figure 3: Mounting hole locations, dimensions, in. (mm)and securing the thermostat controller mounting base tothe wall

Note: When you mount the unit on the wall, youcan hang the front cover on the end of the backcover as illustrated in Figure 4.

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 3

Page 4: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Figure 4: Hanging the thermostat controller front cover

WiringAbout this task:When you replace an existing thermostat controller,remove and label the wires to identify the terminalfunctions.

 WARNING

Risk of Electric ShockDisconnect the power supply before making electricalconnections to avoid electric shock.

 AVERTISSEMENT

Risque de décharge électriqueDébrancher l'alimentation avant de réaliser toutraccordement électrique afin d'éviter tout risque dedécharge électrique.

 CAUTION

Risk of Property DamageDo not apply power to the system before checkingall wiring connections. Short circuited or improperlyconnected wires may result in permanent damage tothe equipment.

 ATTENTION

Risque de dégâts matérielsNe pas mettre le système sous tension avantd'avoir vérifié tous les raccords de câblage. Desfils formant un court-circuit ou connectés de façonincorrecte risquent d'endommager irrémédiablementl'équipement.

Important: Make all wiring connections inaccordance with local, national, and regionalregulations. Do not exceed the electrical ratings ofthe TEC3000 Series Thermostat Controller.Important: Use correct ESD precautions duringinstallation and servicing to avoid damage to theelectronic circuits of the thermostat controller.To wire the thermostat controller, complete thefollowing steps:

1. Strip the ends of each wire 1/4 in. (6 mm) andconnect them to the appropriate screw terminals asindicated in Table 5.

Note: For more details on wiring the MS/TP Communications Bus, refer to the MS/TP Communications Bus Technical Bulletin(LIT-12011034).

2. Attach the communication wires to the terminalblock.

Note: If multiple wires are inserted into theterminals, make sure to twist the wires togetherbefore you insert them into the terminalconnectors.

3. Carefully push any excess wire back into the wall.Note: Seal the hole in the wall with fireproofmaterial to prevent drafts from affecting theambient temperature readings.

4. For networked models, set the bus end-of-line (EOL)termination switch to the desired location.

You can designate the thermostat controller asthe end of the Field Controller (FC) Bus and N2Bus through the bus EOL termination switch.The default position is OFF. If the thermostatcontroller is at the end of a daisy chain of

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide4

Page 5: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

devices on the FC Bus and N2 Bus, set the EOLswitch to the ON position. See Figure 5.

Figure 5: EOL switch position (left) and installing thethermostat controller cover (right)

5. Reattach the thermostat controller cover to themounting base, bottom side first.

Important: Make sure you reattach the coverthat corresponds to its correct base. The CPUboard number needs to match the base boardnumber. Otherwise, an operation error occursafter you reattach a cover and base that donot belong together. The example in Figure 6indicates that a TEC3612-16 is mounted on thebase of a TEC3312-16. See Table 4 for TEC3000model names and code numbers.

Figure 6: Error code indicating mismatched boards

Table 4: TEC3000 model names and code numbers

Name 1Codenumber1

Name Codenumber1

TEC3012-13 30 TEC3313-14 05TEC3012-14 31 TEC3322-13 08TEC3012-16 33 TEC3322-14 09TEC3013-14 35 TEC3322-16 0BTEC3022-13 38 TEC3323-14 0DTEC3022-14 39 TEC3330-13 10TEC3022-16 3B TEC3330-14 11TEC3023-14 3D TEC3330-16 13

Table 4: TEC3000 model names and code numbers

Name 1Codenumber1

Name Codenumber1

TEC3030-13 40 TEC3331-14 15TEC3030-14 41 TEC3612-13 18TEC3030-16 43 TEC3612-14 19TEC3031-14 45 TEC3612-16 1BTEC3112-14 49 TEC3613-14 1DTEC3113-14 4D TEC3622-13 20TEC3122-14 51 TEC3622-14 21TEC3123-14 55 TEC3622-16 23TEC3130-14 59 TEC3623-14 25TEC3131-14 5D TEC3630-13 28TEC3312-13 00 TEC3630-14 29TEC3312-14 01 TEC3630-16 2BTEC3312-16 03 TEC3631-14 2D

1 The two-character code number is listed within the errorcode to indicate that the CPU board and base board do notbelong together.

6. Use a 1/16 in. (1.5 mm) Allen wrench or JohnsonControls T-4000-119 Allen-Head Adjustment Tool(order separately) to reinstall the security screwon the top of the thermostat controller cover. SeeFigure 2 for security screw placement.

7. Remove the protective plastic cover sheet from thedisplay.

Important: If the display is dirty, gently wipeit clean with isopropyl alcohol or ethyl alcohol.Do not scrub hard as to avoid damaging thesurface. Do not use other cleaners such aswater, ketones, and aromatic solvents, sincethey may damage the polarizer.Note:

- For VAV and two-pipe systems, connectthe valve to the heating output.

- Only one transformer is required for eachTEC.

- Power to the AUX contact comes fromthe reheat coil.

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 5

Page 6: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Terminal identificationTable 5: Terminal identification (See Wiring diagrams for details)

FunctionTerminal labelTEC3030, TEC3031, TEC313x TEC3330, TEC3331 TEC3630, TEC3631

24 V 24 VAC hot from the sensorY1 Cooling stage 1Y2 Cooling stage 2AUX Auxiliary binary outputAUX Auxiliary power inputW1 OB Heating 1 (RTU mode)/Reversing valve (O/B) (Heat Pump mode)1RH1 Power for W1 and W2

W2 SUP Heating 2 (RTU mode)/Supplemental heat (Heat Pump mode)OAD Outdoor air damper, 0 VDC - 10 VDC2COM2 Common

COM2 Common

G FanBI-2 Configurable binary input 2BI-1 Configurable binary input 1RSEN Configurable analog input 1OAT Configurable analog input 3SAT Configurable analog input 2NET+ n/a Not connected Field bus+/N2+NET- n/a Not connected Field bus-/N2-NET COM n/a Not connected Isolated common for field bus

1 RH needs to be connected for W1 and W2 to energize. For heating systems with an isolated power supply, connect RH to the Rterminal of the heating system. For systems that switch the hot supply to the heating commands, connect the jumper to 24 V. Forsystems that switch the neutral supply to the heating commands, connect the jumper to COM.

2 For the networked models, the common terminals, which do not include NET COM, are internally connected and can be used for allinputs and outputs. For the wireless models, the common terminals are connected and can be used for all inputs, outputs, and 24VAC ground or common.

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide6

Page 7: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Wiring diagramsSee Table 5 for terminal identification.

Figure 7: Staged wiring diagram - Rooftop Unit

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 7

Page 8: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Figure 8: Staged wiring digram - Heat Pump

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide8

Page 9: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Figure 9: Staged wiring diagram - Rooftop Unit with Auxiliary DehumidifierNote: See Figure 12 for auxiliary contact wiring

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 9

Page 10: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Figure 10: Staged wiring digram - Heat Pump with Auxiliary DehumidifierNote: See Figure 12 for auxiliary contact wiring

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide10

Page 11: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Figure 11: Staged wiring diagram - Rooftop Unit with Hot Gas Reheat

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 11

Page 12: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Figure 12: AUX contact wiring

Figure 13: Binary input wiring

Setup and adjustmentsImportant: Table 14 provides a full list of TEC3000menu settings. In the upcoming sections, step-by-step instructions are included on how to access andadjust the more commonly used menus.

OverviewAbout this task:Figure 14 shows the thermostat controller home screenin both the light and dark themes. You can customizeit to show or hide various elements from the occupant.See Table 6 for a listing of the touchscreen icons andTable 14 to identify the home screen settings under theDisplay Settings. When screen customization is used inconjunction with a passcode, the building owner cancontrol which options the occupant can access and adjust.

Important: If lockout levels are used, some iconsare hidden. Table 7 provides details of these levels.

Figure 14: Thermostat controller home screen (shownwith light and dark themes)

To switch between the modern, classic, light, anddark themes, complete the following steps:

1. Press the Menu icon.2. Press Settings.3. Press Display Settings.4. Press Change Color Theme.5. Select one of the four options available.

Result

Multiple pages are available on the display. The page thatyou currently view is emphasized with a filled dot. Theother available page displays as an empty dot.In the modern theme, the cooling, or blue, and heating, ororange, circles show whether the cooling or heating modeis active.

Figure 15: Thermostat controller home screen incooling mode (left) and heating mode (right)

Customizing the home screenAbout this task:Customizing the Home screen settings include:• Brightness• Enable Backlight• Units• Time• Time Zone• Time Format• Date• Date FormatYou can also show or hide these items on the Homescreen:• Fan Button• Temperature• Humidity• Off Button• Hold Button• Setpoint• Alarms• Occupancy Status• Unit Status• Date/TimeTo customize the Home screen, complete the followingsteps:

1. Press the Menu icon.2. Press Display Settings.3. Enable or disable elements of the home screen as

appropriate for the building owner and occupants.4. Set the passcode on the thermostat controller to

prevent the occupants from changing settings thatthey should not have access to change.

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide12

Page 13: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Touchscreen iconsTable 6 describes the touchscreen icons on the home screen. Press and release a touchscreen icon to activate the TEC.Additional touchscreen icons appear based on the menu, and those icons are also described in Table 6.Table 6: Touchscreen icons

Icon Icon name DescriptionMenu Displays the configuration screens where various settings may be

adjusted.

Alarm Indicates that the thermostat controller has triggered an alarm.

On

Standby

Unit Power Powers the thermostat controller on or off.• This icon disables all equipment control but does not physically

power down the unit.• On the modern home screen, if the Unit Power icon is in standby

mode, the temperature and humidity also display in standby modeto indicate that control off or standby mode is active.

On

Standby

Humidity Indicates the humidity reading.

On

Standby

Degree Indicates that the unit is set to degrees.

Network Communication(for Networked Models)No Signal

Indicates that the thermostat controller detected a supervisorycontroller and both are online.Indicates that the thermostat controller did not detect a supervisorycontroller.

No Signal

Low Signal

MediumSignal

High Signal

Radio Signal (for WirelessModels)

Indicates the strength of the radio signal.

Arrow UpArrow Down

Increases or decreases the cooling value on the home screen.

Arrow UpArrow Down

Increases or decreases the heating value on the home screen.

Cooling Hold Indicates that cooling hold mode is enabled. To disable Hold mode,press the button.

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 13

Page 14: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Table 6: Touchscreen icons

Icon Icon name DescriptionHeating Hold Indicates that heating hold mode is enabled. To disable Hold mode,

press the button.Cooling Setpoint Displays the current cooling setpoint. Indicates that Hold mode is

disabled. To enable Hold mode, press the button.Heating Setpoint Displays the current heating setpoint. Indicates that Hold mode is

disabled. To enable Hold mode, press the button.Setpoint Temperature Displays the current setpoint temperature. Indicates that the Show

Hold button is set to No.

Heating Mode Indicates that heating mode is selected.

Cooling Mode Indicates that cooling mode is selected.

Auto Mode Indicates that Auto mode is selected.

On

Auto

Quiet

Fan Overrides for Single-speed Fans

Adjusts the fan override between On, Auto, and Quiet for single-speedfans.

Unoccupied

Occupied

TemporarilyOccupied

Standby

Override -Occupied

Override -Unnoccupied

Occupancy Status Adjusts the occupancy between Unoccupied, Occupied, TemporarilyOccupied, Standby, Occupancy Override, Unoccupancy Override.

Back Moves the display to the previous screen.

Forward Moves the display to the next screen.

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide14

Page 15: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Table 6: Touchscreen icons

Icon Icon name DescriptionHome Returns the display to the main home screen.

Save Saves the current configuration and parameter settings.

Delete Deletes the scheduled event.

Clear Clears the password entry on the keypad screen.

Exclamation point Indicates that an error has occurred.

User lockoutYou can select from three different levels of access atthe local display to manage functionality through thesupervisory controller. This lockout is independent ofany display or passcode settings. The existing temporaryoccupancy capability is unaffected by this feature. Userlockout hides the icons that are not operable. The lockoutlevels are described in Table 7.Table 7: User lockout levels

Lockoutlevel

Capability

State 0 Provides full access to Home ScreenDisplay Adjustments and icons (default).

State 1 Hides the Menu icon.State 2 Only allows the screen to trigger

temporary occupancy. Menu, Unit Power,the Up and Down arrows, and Run/Holdare hidden.

Using the USB portUse the USB port to quickly and easily load firmwareupgrades, back up the current settings, and restoresettings to the TEC3000 by using a USB drive. The TEC3000can recognize eight configuration files or firmwarepackage files. The USB drive format must be FAT or FAT32.The drive cannot be NTFS format or USB 3.0. If you areupgrading firmware or copying configuration files, youneed the passcode if one has been set up. Do not removethe USB drive until the firmware upgrade is complete.The TEC3000 may restart and go offline to the NAE aftera firmware upgrade. The upgrade takes approximatelythree minutes.Configurations are copied, except for the Communicationmode. See Choosing the Communication mode (TEC3630,TEC3631 Models) to configure the networked devices.

Loading the firmware1. Ensure that the TEC screen is on.2. Insert the USB drive into the right side of the TEC.

See Figure 1 for the USB port location.3. Press the Menu icon.4. Scroll down the menu and press Update.5. Press Load Firmware.6. Select the correct firmware version. The correct file

name has the .pkg extension.7. Press Confirm if you have the correct firmware

version.The firmware is loaded from the USB drive into theTEC3000 operating system. The TEC3000 locates thenew firmware only if the new firmware is on the rootdrive of the USB drive. See Table 16 if the firmware isnot loaded correctly.

8. Remove the USB drive from the TEC3000 controllerwhen the update is complete.

The TEC3000 firmware update is complete when theTEC3000 restarts and returns to the home screen.

Backing up the settingsAbout this task:

Note: When you back up the settings, the networksettings are not backed up or restored.

1. Ensure that the TEC screen is on.2. Insert the USB drive into the right side of the TEC.

See Figure 1 for the USB port location.3. Press the Menu icon.4. Scroll down the menu and press Update.5. Press Backup.

A message appears stating that the file is savedlocally and on a USB drive.

6. Press Confirm to save locally and on USB.The setting files are named based on the TEC3000model name, date, and time stamp. For example,

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 15

Page 16: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

TEC3xx1-00_2018-07-01T1. The files are saved locallyand on the USB drive’s root directory. See Table 16 ifthe settings are not backed up correctly.

7. After the settings are saved onto the USB drive,remove the USB drive from the TEC3000.

Restoring the settingsAbout this task:If the TEC3000 is connected to a network (for example,MS/TP or wireless), you must manually set or verify theBACnet® Instance ID and BACnet Address, or both, inthe Network Setup page after the restore so they do notconflict with other devices on the same network.

1. Ensure that the TEC screen is on.2. Insert the USB drive into the right side of the TEC.

See Figure 1 for the USB port location.3. Press the Menu icon.4. Press Update.5. Press Restore.6. Select Local Storage or the correct configuration

file created from a previous backup operation.The setting files are named based on the TEC3000model name, date, and time stamp (for example,TEC3xx1-00_2018-07-01T1). The files are saved locallyand on the USB drive’s root directory.

7. Press Confirm if you have the correct file name.The settings are loaded from the USB drive.

8. After the settings are loaded from the USB drive,remove the USB drive from the TEC3000.

Choosing the Communication mode(TEC3630, TEC3631 Models)

1. Ensure the TEC screen is on.2. Press the Menu icon.3. Press Setup.4. Press Network Setup.5. Press FC Comm Mode.6. Select BACnet or N2 by pressing the up and down

arrows.Proceed to Step 7 to perform BACnet communicationand Step 15 to perform N2 communication.

7. Press the back arrow to return to the previousscreen.

8. Press BACnet Instance ID.9. Enter the unique BACnet® instance ID using the

keypad. This value should be different to the othercontrollers on the site.

10. Press Save.11. Press the back arrow to return to the previous

screen.12. Press BACnet Address.13. Enter the BACnet MS/TP address through the

keypad.14. Press Save.

15. After selecting N2 in Step 6, press Save.16. Press the back arrow to return to the previous

screen.17. Press N2 Address.18. Enter the N2 address through the keypad.19. Press Save.

Configuring the network settings forwireless models

1. Ensure the TEC screen is on.2. Press the Menu icon.3. Press Setup.4. Press Network Setup.5. Press FC Comm Mode and the Wireless Field Bus

appears. This setting cannot be changed.6. Press the back arrow to return to the previous

screen.7. Press BACnet Instance ID.8. Enter the BACnet® instance ID using the keypad.

This value should be different to the othercontrollers on the site.

9. Press Save.10. Press the back arrow to return to the previous

screen.11. Press BACnet Address.12. Enter the BACnet address using the keypad. This

value should be different to the other controllerson the PAN.

13. Press Save.14. Press the back arrow to return to the previous

screen.15. Press PAN ID.16. Enter the PAN ID using the keypad. This value

needs to be the same as set in the associatedZFR182x or ZFR183x Coordinator Radio.

17. Press Save.Once the PAN is set, the TEC attempts to connect tothe wireless network. Provided that other devices onthe PAN are in radio range, the connection shouldoccur within one minute. It can then take up to 10minutes for the WNC gateway to display that thedevice is online.

Configuring the thermostat controllerUse the Menu icon on the home screen to access andchange the basic operating parameters of the thermostatcontroller. During normal operation, press the Menu icononce to access the following parameters:• Fault Status• Setpoints• Schedule• Display Settings• Setup• Trend• Status• Update

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide16

Page 17: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Installer configuration menuThe thermostat controller comes from the factory withdefault settings for all configuration parameters. TheUI menu navigation and default settings are shown inTable 14. Before any outputs turn on, the controller mustbe configured for the equipment connected. You needto start from the home screen to perform any of thefollowing tasks.

Screen resetThe current screen returns to the home screen and turnsoff if the current screen is not touched for 3 minutes.Touch the screen to turn it on again. To disable thescreensaving option, press Display Settings and setEnable Display Timeout to No.

Selecting Rooftop or Heat Pump modeAbout this task:By default, the thermostat controller is configured forRooftop mode. This mode is used for up to two discretestages of heating (W1, W2) and up to two discrete stagesof cooling (Y1, Y2). Certain heat pumps do not require anO/B input and instead take standard W and Y commandsas heat or cool commands, internally sequencing theequipment. For these type of heat pump units, leave thecontroller in Rooftop mode.When in heat pump mode, the TEC controls up to twostages of compressors (Y1, Y2) for both heating andcooling. O/B is controlled through the W1/OB output andone stage of supplemental heat is controlled through theW2/SUP output. To configure heat pump mode, completethe following steps:

1. Press the Menu icon.2. Press Setup.3. Press Equipment Setup.4. Press Heat Pump.5. Press Heat Pump Supported and select Yes.6. If supplemental heating is installed, press Supp

Heating Installed and select Yes.7. Press Reversing Valve Polarity and set

appropriately for the O/B input on the equipmentbased on if the equipment is normally cooling untilthe thermostat output is activated or normallyheating (typically, Normally Heat for O andNormally Cool for B).

8. Press Save and the back arrow to return to theprevious screen.

Configuring heating and cooling stages1. Press the Menu icon.2. Press Setup.3. Press Equipment Setup.4. Press General.5. Press Number of Compressors and adjust the

number of compressor inputs on the equipmentbeing controlled.

6. If the thermostat controller is in rooftop mode,press Number of Heating Stages and adjust thenumber of heating inputs on the equipment beingcontrolled.

7. Press Save and the back arrow to return to theprevious screen.

Configuring economizerAbout this task:If the equipment has an analog (between 0 VDC to10 VDC) input for an economizer damper command,configure the economizer as follows:1. Press the Menu icon.2. Press Setup.3. Press Equipment Setup.4. Press Economizer.5. Press Economizer Installed and select Yes.6. Press Min Position and set to the percentage that

the damper must be kept open to ensure fresh airflow in the zone.

7. Press Closed Voltage and set to the voltage outputat which the damper is fully closed.

8. Press Opened Voltage and set to the voltage outputat which the damper is fully opened.

9. Press Save and the back arrow to return to theprevious screen.

The TEC supports three methods of determiningeconomizer availability. These are Dry Bulb, SingleEnthalpy, and Dual Enthalpy, in increasing order ofaccuracy. To run an economizer, outdoor air temperature(OAT) is required to run in Dry Bulb mode. This can beprovided by connecting a sensor to the OAT input on theTEC. It also can be provided by writing to NET-OAT froma Building Automation System (BAS), which overridesthe internal sensor. If Outdoor Air Humidity (OAH) isalso provided by writing to NET-OAH, the dual enthalpymethod is used to determine if economizer cooling shouldbe used.All network overrides to the TEC work on a timeout basis.If the value is written to, it remains active as long as theBAS writes a new value within 15 minutes of the first one.If the 15-minute timeout occurs without getting any datawritten, the TEC stops using the network data.When operating in Dry Bulb or Single Enthalpy mode,it is necessary to provide a Dry Bulb Setpoint or an OAEnthalpy Setpoint, respectively. The TEC ships with defaultvalues set, but depending on climate it may be necessaryto change these. To access these values, complete thefollowing steps:

1. Press the Menu icon.2. Press Setup.3. Press Equipment Setup.4. Press Economizer.5. Press Dry Bulb Setpoint or Outdoor Enthalpy

Setpoint and adjust according.6. Press Save and the back arrow to return to the

previous screen.

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 17

Page 18: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Setting the Control modeAbout this task:The Control Mode informs the controller to run in Coolingonly, Heating only, or Automatic mode, based on thetemperature in the zone relative to the heating andcooling setpoints. Control Mode does not overrideequipment lockouts or changeover. To set the ControlMode, complete the following steps:

1. Press the Menu icon.2. Press Setup.3. Press General Setup.4. Press Control Mode and select Cooling, Heating,

or Auto as preferred.5. Press Save and the back arrow to return to the

previous screen.

Setting the Fan modeAbout this task:The Fan Mode informs the controller how to handlethe fan. There are two options for fan configuration: aFan Mode available to the installer through the menusystem, and a fan override available as an option to theend user from the Fan icon on the home screen. SeeCustomizing the home screen for information on enablingand disabling end-user controls. The Fan Mode availableto the installer depends on the fan type. The followingoptions are provided for single-speed fans:• On—Fan is continuously on• Auto—Fan cycles on demand with the controller

entering cooling, heating, or dehumidification modes• Smart—Fan cycles on demand with the controller

entering cooling or heating modes during unoccupiedperiods but is continuously running during occupiedand standby periods

The Fan Override icon on the home screen dependson the fan type. The following options are provided forsingle-speed fans:• On—Overrides the fan to be continuously on• Auto—Follows the behavior set as Fan Mode• Quiet—Follows the behavior set as Fan Mode, but

prevents the fan from ever going above minimumspeed. The Quiet option has no effect on equipmentwith single-speed fans.

To set the Fan Mode, complete the following steps:

1. Press the Menu icon.2. Press Setup.3. Press General Setup.4. Press Fan Mode and select On, Auto, or Smart.5. Press Save and the back arrow to return to the

previous screen.

Configuring the zone space orequipment sizeAbout this task:With non-binary outputs, the TEC3000 defaultconfiguration is to have a slower temperature responsefor larger zones with normal-sized equipment. Ininstallations with small zones and oversized equipment,set the Equipment Size parameter to Oversized.To set the Equipment Size parameter, complete thefollowing steps:

1. Press the Menu icon.2. Press Control Setup.3. Press Tuning.4. Use the up and down arrows to navigate to

Equipment Size.5. Press Equipment Setup and select Oversized.6. Press Save and the back arrow to return to the

previous screen.

Temperature setpointsAbout this task:The thermostat controller provides a flexible setpointconfiguration to give power to the building owner whilebeing easy to use by the occupant. In addition to a simpleup/down offset adjustment on the home screen for theoccupant, there are six temperature setpoints on the TEC.The six temperature setpoints are Cooling and Heatingsetpoints for Occupied, Unoccupied, and Standby modes.To set these setpoints, complete the following steps:

1. Press the Menu icon.2. Press Setpoints and then Temperature.3. Select the setpoint to adjust and change as

preferred.4. Press Save and the back arrow to return to the

previous screen.Note: The TEC enforces a 2-degree deadbandbetween heating and cooling setpoints. If asetpoint violates this standard (for example,cooling setpoint is set to 70 with a heatingsetpoint already set to 70), the opposingsetpoint is modified to comply with thisdeadband (in the previous example, theheating setpoint would automatically change to68).

ResultThe occupant has access to an up/down adjustment fromthe home screen. This adjustment applies a fixed offset(+/-) to the currently active setpoint, and this offset holdsuntil the occupancy state of the controller changes. Ifthe user taps the setpoint on the home screen, the iconinverts and displays white text on a black icon. The offsetis held throughout all occupancy periods. For example,if the TEC is cooling in Occupied mode to an occupiedcooling setpoint of 72 and you raise the setpoint 2degrees to 74 from the home screen and then select hold,then the +2 degree offset persists through an occupancychange. If the occupancy then changes to unoccupied,

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide18

Page 19: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

with a setpoint of 80 degrees, the effective setpoint is 82degrees. This allows the occupant to have a small amountof control over raising or lowering the temperature, butthe building owner can still set back setpoints duringstandby and unoccupied periods. When the setpoint is inHold mode, pressing the icon again releases the hold andimmediately sets the setpoint offset back to 0.When the TEC is in Min/Max mode (Setpoints/OccSetpoint Select are equal to Min and Max Setpoint), theTEC rejects any attempts to change the present valueoutside of the valid range. If the present value is outsideof the valid range (for example, if the Occ Setpoint Selectis switched from Setpoint Offset to Min and Max Setpoint),the present value is reset to be in the center of the validrange.The four modes of setpoint operation are described inTable 8.

Table 8: Setpoint operation

Mode ofsetpointoperation

Details

Occ SetpointSelect =SetpointOffset andHeat CoolSetpointMode =IndividualSetpoints

This is the default mode and the originalmode of operation that the TEC wasreleased with (the next three modes arenew). In this mode, the TEC has a heatingsetpoint and a cooling setpoint. There is acommon Setpoint Offset (warmer/cooleradjust) that applies to each setpointsimultaneously. The range of setpointadjustment is two-fold:• There are large constant ranges

bounding the individual heating andcooling setpoints.

• There is also a smaller configurablerange limit set to the Setpoint Offsetpoint (Control Setup > General > MaxSetpoint Offset).

Occ SetpointSelect = Minand MaxSetpointsand HeatCoolSetpointMode =IndividualSetpoints

In this mode, the TEC has a heatingsetpoint and a cooling setpoint. Eachsetpoint has a configurable range(Setpoints > Temperature > Min CoolingSetpoint, Max Cooling Setpoint, MinHeating Setpoint, and Max HeatingSetpoint). The configurable range valuesare bounded by the larger constantbounds used in Setpoint Offset mode andare constrained in the following manner:Min must be below Max and Heatingmust be below Cooling, so in order fromleast to greatest, the values are: MinHeating Setpoint, Max Heating Setpoint,Min Cooling Setpoint, and Max CoolingSetpoint.

Occ SetpointSelect =SetpointOffset andHeat CoolSetpointMode =CommonSetpoint

In this mode, the TEC has one setpoint,Common Setpoint, for heating andcooling. There is also a common SetpointOffset (warmer/cooler adjust) that onlyapplies to Common Setpoint. Otherwise,this setting works the same as when OccSetpoint Select = Setpoint Offset and HeatCool Setpoint Mode = Individual Setpoints.

Occ SetpointSelect = Minand MaxSetpointsand HeatCoolSetpointMode =CommonSetpoint

In this mode, the TEC has one setpoint,Common Setpoint, for heating andcooling. There is a configurable range forCommon Setpoint, Min Setpoint, and MaxSetpoint.

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 19

Page 20: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Configuring occupancyTo adapt to nearly any application, the TEC3000 controllersupports a wide variety of occupancy sources, such as:• Local stand-alone weekly scheduler• Remote schedule from BAS• Occupancy sensor (internal or remote)• Occupancy binary input (configurable)• Manual occupancy override• Temporary occupancy (by interacting with the screen

while in unoccupied mode)

• Temporary occupancy binary inputOccupancy is determined using a top-down decisionmatrix as shown in Table 9.Enumerations may not match the TEC3000 SeriesNetworked and Wireless Single- or Two-Stage EconomizerThermostat Controllers Installation Guide (LIT-12013163)and the TEC3000 Series Field-Selectable BACnet MS/TP orN2 Networked Thermostat Controllers Technical Bulletin(LIT-12011956) for NAE releases prior to 7.x.

Table 9: Occupancy determination

Sequence of operation (highest to lowest priority) Status indicatedManualOccupancyMode(OCCOVRD-MODE)

1Occupancy BI(BI1-S, BI2-S)1

2, 3TemporaryOccupancy2,3

OccupancySchedule(External orSchedule)(OCC-CONFIG, NET-OCC)

4MotionSensor4

EffectiveOccupancy(EFF-OCC)

Occupancy Source(OCCSOURCE-S)

Occupied Occupied-Override

Unoccupied

Unoccupied-Override

Occ Override

Closed1 Occupied

Open1

– –

Unoccupied

Occupancy BI

True2 NOT Occupied TempOccupancy

Temp Occ

True3 NOT Occupied

TempOccupancy

Temp Occ BI

True OccupiedFalse Standby

Occupancy SensorOccupied

Disabled OccupiedUnoccupied UnoccupiedStandby

–Standby

Occupancy Schedule

True OccupiedFalse Unoccupied

Occupancy Sensor

No Override

NotConfigured1

False

5 Not Set5

Disabled Occupied Occupancy Schedule1 Not Configured means that neither BI1 Config nor BI2 Config is set to Occupancy BI. Open and Closed refer to the current state of

the BI when configured as Occupancy.2 True is triggered by interacting with the screen during a scheduled unoccupied period. A value of True can only occur when the

schedule is not Occupied.3 When triggered by a BI configured for Temp Occ, the input is ignored when the schedule is Occupied, the Manual Occupancy Mode

is not No Override, or an Occupancy BI is configured.4 Built-in occupancy sensing (PIR) or BI configured for Motion NO or Motion NC.5 Not Set occurs when no events are scheduled through the local scheduler, or the schedule source is set to Schedule and the

Schedule is writing Not Set as the schedule.

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide20

Page 21: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Selecting schedule sourceScheduling (for networked models)The TEC3000 Thermostat Controller can operate as astand-alone unit with an internal schedule or scheduledwith an external schedule. The OCC-CONFIG object setsthe method used for scheduling.If the OCC-CONFIG is set to External, the NET-OCC objectis used to control the unit externally.If the OCC-CONFIG is set to Schedule, the internalschedule commands the LOCAL-OCC object, which setsthe Occupancy Schedule command.

Note: If you do not have a schedule in theSchedule object and you have the OCC-CONFIGset to Schedule, you can control the unit with theLOCAL-OCC object externally; however, we donot recommend this method. See Table 10 forscheduling information.

Once the Occupancy Schedule command is set, thesettings shown in the occupancy determination tabledetermine the effective occupancy. See Table 9.Table 10: BAS objects for schedulingOCC-CONFIG LOCAL-OCC

(commandedby internalschedule)

NET-OCC 1Occupancyschedulecommand1

Occupied OccupiedUnoccupied UnoccupiedStandby Standby

External Any State(InternalSchedule inControl) Not Set Not SetOccupied OccupiedUnoccupied UnoccupiedStandby Standby

Schedule

Not Set

Not Applicable

Not Set1 The effective occupancy can be affected by other factors

listed in Table 9.

Scheduling (for all models)About this task:The occupancy schedule comes from either the weeklyscheduler built into the TEC or as an input from theBAS. The Schedule Source must be selected to tell thecontroller where to read the occupancy source from. Toselect the schedule source, complete the following steps:

1. Press the Menu icon.2. Press Scheduling.3. Press Schedule Options.4. Press Schedule Source and select Schedule (Local)

or External (BAS).5. Press Save and the back arrow to return to the

previous screen.This option is also exposed to the BAS through the pointOCC-CONFIG. If BAS is configured as the occupancysource, map the point NET-OCC in and write to thatpoint to control the schedule remotely. If the supervisorgoes offline (as identified by the network icon goingaway on the home screen of the TEC), the control logic

automatically falls back to the local schedule as theoccupancy source. If that schedule is not set, the defaultoccupancy is continuously occupied.

Setting the local scheduleAbout this task:A weekly occupancy schedule with up to four occupancyevents for each day can be set locally on the TEC andoperate independently of a supervisor. To set theschedule, complete the following steps:

1. See Selecting schedule source to ensure theschedule source is set to Local.

2. Press the Menu icon.3. Press Scheduling.4. Press Set Schedule.5. Select the days to which the schedule should apply.

If events are already set for the selected days,they appear in the corresponding event box. If anyevents conflict between selected days, an asteriskappears in the event box. See Figure 16.

6. Select the Occupancy Status icon for the event. SeeFigure 17.

Important: Internally, the TEC3000 uses aBACnet schedule where daily schedules areindependent of the previous and next days.The default occupancy of the TEC3000 fromthe factory is set to Occupied. As a result, adaily event at 12:00 AM must be scheduled ifyou do not want the controller to transition toOccupied Mode at midnight.

Figure 16: Selecting the days

Figure 17: Setting the Room Occupancy mode

7. Select the Time Set button. See Figure 18.

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 21

Page 22: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

8. Set the time to the time at which the event willoccur and press Save. The screen resets to theEvent Set Schedule screen.

Figure 18: Selecting the Time Set button (left) and settingthe event time (right)

9. Press Save to save the completed event or Trashto delete the completed event. See Figure 19. Thescreen resets to the Event 1 Set Schedule screen.

Note: If you do not select Save at this point,the event is not saved and you must repeat theevent selection sequence.

Figure 19: Saving the event

10. Select Event 2. See Figure 20. The screen resetsto the Event 2 Set Schedule screen. The days arepreselected to match Event 1.

11. Select the Occupancy Status button for Event 2.Figure 20: Selecting event 2 (left) and setting theoccupancy status (right)

12. Select the Time Set button.13. Set the time for Event 2 and press Save.14. Press the back arrow to return to the Scheduling

screen.

Overriding the Occupancy modeAbout this task:The TEC supports a manual override of all other schedulesources (for example, Schedule, Occupancy BI, andtemporary occupancy). To override the Occupancy Mode,complete the following steps:

1. Press the Menu icon.2. Press Scheduling3. Press Schedule Options.

4. Press Manual Occ Mode and select Occupied,Unoccupied, or No Override.

5. Press Save and the back arrow to return to theprevious screen.

This option is also exposed to the BAS through the pointOCCOVRD-MODE.

Enabling optimal startAbout this task:The TEC supports an advanced optimal start algorithm.The algorithm works in conjunction with a local scheduleto pre-heat or pre-cool the zone before scheduledoccupancy periods begin, in order to bring the zoneto the required occupied setpoint when the scheduledoccupancy period begins. Occupant comfort is ensuredwhile automatically minimizing energy usage. Thisalgorithm creates a model of the zone being controlledand automatically determines when to start theequipment before the scheduled transition to Occupied.The start time automatically adjusts daily to minimize thetime between reaching setpoint and entering Occupiedstate.

Note: Optimal Start does not work when theschedule source is set to External.To enable this feature, complete the following steps:

1. Press the Menu icon.2. Press Scheduling.3. Press Schedule Options.4. Press Optimal Start Enable and select Yes.5. Press Save and the back arrow to return to the

previous screen.

Enabling the motion sensor (TEC3x31Models)About this task:On models with integral motion sensing capability, themotion sensor is enabled with a default timeout of 15minutes from the last detection of motion in the zone.On models without an integrated sensor, the defaulttimeout is still 15 minutes, but it only is applied when oneof the two configurable binary inputs is set to be a motionsensor. See Configurable binary inputs for information onconfiguring the binary inputs. To disable motion sensingcapabilities, set the Motion Sensor Timeout to 0 minutes.See Table 9 to view the available setpoints. See Table 14to view the setpoint values. To adjust the motion sensortimeout, complete the following steps:

1. Press the Menu icon.2. Press Scheduling.3. Press Schedule Options.4. Press Motion Sensor Timeout and adjust

accordingly.5. Press Save and the back arrow to return to the

previous screen.

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide22

Page 23: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

PID/PRAC+ automatic control tuningAbout this task:The TEC3000 features advanced proportional-integral-derivative (PID) control algorithms to maximize controlperformance while minimizing excessive cycling andwear on the equipment. PID is used in conjunction with aMulti-Stage Controller (MSC) for all occupied and standbycontrol.Additionally, the PID features Johnson Controlsproprietary Pattern Recognition Adaptive Control (PRAC+) automatic tuning, which continuously tunes thecontroller parameters to automatically optimize thecontrol performance to match the equipment and zone.By default, PRAC+ is enabled and immediately begins totune. To reset tuning at any time to the factory defaults,complete the following steps:1. Press the Menu icon.2. Press Setup.3. Press General Setup.4. Press Tuning.5. Press Reset PID Tuning and select Yes.6. Press Save and the back arrow to return to the

previous screen.PRAC+ automatic tuning can also be disabled. Whendisabled, the controller parameters remain at their lastvalues until automatic tuning is re-enabled. To disableautomatic tuning, complete the following steps:

1. Press the Menu icon.2. Press Setup.3. Press General Setup.4. Press Tuning.5. Press Temp Control Setup.6. Select Manual PID Tuning (or any option listed in

Table 11). PID tuning is active with the AutomaticPID Tuning and Deadband Override parameters.

7. Press Save and the back arrow to return to theprevious screen.

ResultAs a result of disabling PRAC+ Automatic Tuning, you haveaccess to different types of manual tuning that allowsmodifications of tuning parameters listed under ControlSetup > General in Table 14.

Table 11: TEC3000 tuning types

Tuning type DescriptionAutomatic PIDtuning

Automatic tuning in an existingTEC3000

Deadbandoverride

Overrides the deadband that PRAC+ would normally use. DecouplesDeadband control from PRAC+Automatic Tuning and Min On OffEquipment Setting.

Manual PIDtuning

Manual tuning of Heating and CoolingPIDs. The manual tuning parametersare listed under Setup > General Setup> Tuning in Table 14.

On/off control(for TEC3x1xand TEC3x3xmodels)

Binary control

Note: For more details on PID/PRAC+ AutomaticControl Tuning, refer to the Controller Tool Help(LIT-12011147).

Configurable binary inputsThe thermostat controller supports up to twoconfigurable binary inputs (BIs) that can be used to addadditional features to the system. Configurable BinaryInputs are accessed through Setup > Inputs. Both BIs canbe configured to support the following options:• Disabled—Sets the binary input to an unused state.

When disabled, you can use the binary input formonitoring-only without affecting the thermostatfunctionality.

• Open Window—Sensor to shut down control if awindow is opened. The controller disables control 60seconds after detecting an opened window.

• Open Door—Works in conjunction with the Motion NO/Motion NC sensor to control occupancy

• Fan Lock—Air Proof switch input to shut down controlif no airflow is detected within 10 seconds of turningthe fan on. Fan Lock must be manually reset from theFaults menu.

• Service—Input from the equipment to display a servicewarning on the thermostat

• Dirty Filter—Input from the equipment to display adirty filter fault on the thermostat

• Motion NC—External motion sensor with a closedcontact output when no motion is detected

• Motion NO—External motion sensor with an opencontact output when no motion is detected

• Temp Occ—Trigger to place controller into TemporaryOccupancy mode

• Occupancy—Direct override of Occupied andUnoccupied

• Supply Fan Status—Input from the equipment todisplay a Supply Fan Fault. When Fan Alarm Action isset to Shutdown and the Supply Fan Fault is active, theTEC3000 disables the fan, heating, and cooling. Whenthe Fan Alarm Action is set to Enable and the SupplyFan Fault is active, the TEC3000 allows the fan, heating,and cooling to operate during the Supply Fan Fault.

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 23

Page 24: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Setting both BIs to the same function is not supported forOccupancy, Fan Lock, Open Door, and Open Window. Ifboth BIs are set the same for those four, BI2 is ignoredand only BI1 is used.The Open Door option works in conjunction with a motionsensor, either built into the TEC or connected to anotherBI configured for Motion NO/NC mode. When the dooris open, the sensor ignores detected motion. Openingthe door does not stop an Occupied period started by themotion sensor prior to opening the door.The polarity of the inputs are provided in Table 12.Table 12: Input polaritiesBIconfiguration

Contact open Contact closed

Occupancy Unoccupied OccupiedTemp Occ No Trigger Active Temporary Occupancy

Trigger1

Motion NO No Motion Detected,Standby

Motion Detected,Occupied1

Motion NC 1Motion Detected,Occupied1

No Motion Detected,Standby

Dirty Filter Dirty Filter AlarmInactive

Dirty Filter Alarm1

Service Service Alarm Inactive Service Alarm1

Fan Lock No Airflow AirflowOpen Door Door Open, Unoccupied Door Closed, OccupiedOpen Window Window Open, Control

Shut DownWindow Closed, ControlRunning

Supply FanStatus

Supply Fan Off Supply Fan On

1 Configurations that support both BIs configured for thesame feature of the action that occurs when either of the BIsenter that state.

Commissioning modeAbout this task:The thermostat controller has a built-in commissioningmode, which is designed to allow you to quickly testequipment wiring and functionality. Commissioning modetemporarily disables the control logic, and allows you tomanually command any individual output. Commissioningis designed to be the last step of the installation processafter configuring the controller for the equipment beingcontrolled, and the available options in commissioningmode are dependent on the controller configuration. Toenter commissioning mode, complete the following steps:1. Press the Menu icon.2. Press Setup.3. Select Commissioning.4. Confirm that the selection was intentional. (The

control is overridden upon selecting Confirm).Individual outputs can be commanded through thisinterface. For binary outputs, the options are Off or On;for analog outputs, they can be commanded from 0 to100%. Whenever a control output is turned on, the fan

is engaged for safety purposes. To command an outputfrom the Commissioning menu, complete the followingsteps:

1. Select the output to command. Adjust the value tothe preferred output and press Save. The outputimmediately changes to that value.

2. Restore the value to the original setting and pressSave once again to complete testing that output.

Pressing the back icon from the main commissioningmenu or allowing the menu system to time out and returnto the home screen ends commissioning and puts thecontrol logic back in control of the outputs.

Dehumidification controlAbout this task:Dehumidification operates when the zone humidityincreases above the humidity setpoint and the controlleris in a satisfied state with no active call for cooling orheating. When dehumidification is active, the coolingdevice controls to the humidity setpoint, and the heatingdevice reheats the zone in order to keep the temperatureat setpoint.The TEC3000 controller supports dehumidification controlunder the following configurations:• RTU with an auxiliary dehumidifier wired to Aux output• Heat pump with an auxiliary dehumidifier wired to Aux

output• RTU with hot gas reheat installed and wired to AUX

outputTo enable dehumidification control, complete thefollowing steps:1. Press the Menu icon.2. Press Setup.3. Press General Setup.4. Press Dehum Enable and select Yes.5. Press Save and the back arrow to return to the

previous screen.6. Press Dehumidification Sequence Mode and select

the applicable dehumidification sequence optionbased on the type of equipment.

Dehumidification Sequence Modes:• Simple dehimidification—select this option if you

use an external or auxiliary dehumidifier wired to thethermostat’s Aux output.

• Hot gas reheat dehumidification—select this option ifthe equipment type is RTU with hot gas reheat and theHGR valve is wired to the thermostat’s Aux output.

• None—select this option if no dehumidificationequipment is present.

Only one dehumidification process is active at a time.To adjust the dehumidification setpoint, complete thefollowing steps:

1. Press the Menu icon.2. Press Setpoints.3. Press Dehumidification

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide24

Page 25: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

4. Press Dehumidification and use the up and downarrows to set the value of Humidity Setpoint.

5. Press Save and the back arrow to return to theprevious screen.

After you select the Dehumidification Sequence Mode,perform the Aux Control configuration as described inSetting the Aux mode when dehimidification is enabled.These options are also exposed to BAS through the pointsDEHUM-ENABLE, UNOCC DEHUM ENABLE, and DEHUM-SEQ-MODE.

Aux controlThe TEC features an auxiliary output that you canconfigure to operate in a few different ways. The availableAux Mode options depend on whether the auxiliaryoutput is used for dehumidification control or not.When Dehumidification is disabled, the Aux Modesupports the following options:• Not Used—Output is always off• Occupied NO—Output is normally open, but closes

when occupied• Occupied NC—Output is normally closed, but opens

when occupied• Occupied Fan NO—Output is normally open, but is

closed when occupied with the fan running• Occupied Fan NC—Output is normally closed, but is

open when occupied with the fan running• On—Output is turned on (relay closed), used by a BAS

to directly control the AUX output• Off—Output is turned off (relay open), used by a BAS to

directly control the AUX outputWhen Dehumidification is enabled, the Aux Modesupports the following options:• Dehumidifier—select when external or auxiliary

dehumidifier is connected to Aux BO. See Figure 9 andFigure 10.

• Hot Gas Reheat—select when HGR valve is connectedto Aux BO. See Figure 11.

Setting the Aux mode whendehimidification is disabledAbout this task:To set the Aux Mode when Dehumidification is disabled,complete the following steps:

1. Press the Menu icon.2. Press Setup.3. Press General Setup.4. Press Aux Mode and set accordingly.5. Press Save and the back arrow to return to the

previous screen.This option is also exposed to the BAS through the pointAUX-MODE.

Setting the Aux mode whendehimidification is enabledAbout this task:

To set the Aux Mode when Dehumidification is enabled,complete the following steps:

1. Press the Menu icon.2. Press Setup.3. Press General Setup.4. Press Aux Mode and set to Not Used.5. Press Dehumidification Aux Mode and select

according to the equipment installed.6. Press Save and the back arrow to return to the

previous screen.This option is also exposed to the BAS through the pointDEHUM-AUX-MODE.

Scheduled circulationAbout this task:You can schedule to run your fan for a minimum durationper hour during occupied or unoccupied hours. If theminimum hourly fan runtime is not exceeded, the fanturns on at the end of the hour for the length of timerequired to fulfill the minimum run time. The fan runtimecalculation includes runtime initiated when the Fan Modeis set to On and other overrides. The fan does not turnon if the fan runtime is already longer than the minimumhourly fan runtime. When you enabled the ScheduledCirculation Only When Occupied setting, the fan doesnot turn on at the end of the hour to fulfill the minimumruntime unless the occupancy state is set to Occupied.To set the Scheduled circulation, complete the followingsteps:

1. Press the Menu icon.2. Press Setup.3. Press General Setup.4. Press Scheduled Circulation and select Enable5. Press Minimum Hourly Fan Runtime and set the

time in a range of 5 to 30 minutes.6. Press Fan Circulation Speed and set the fan speed.7. Press Scheduled Circulation Only When

Occupied and select Disable or Enable as desired.8. Press Save and the back arrow to return to the

previous screen.This option is also exposed to the BAS through the pointsSCH-CIR-EN, SCH-CIR-ONLYOCC, and MIN-HR-FAN. IfScheduled Circulation is disabled, the other two objectsshow unreliable.

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 25

Page 26: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Configurable analog inputs (AIs)The thermostat controller supports up to threeconfigurable AIs that can be used to add differentfeatures to the system. The configuration menu can beaccessed through Setup > Input Setup. All three AIs canbe configured tosupport the following options:• Relative Humidity—Sets up the AI to accept a 0 VDC-10

VDC input when connected to a humidity sensor.• Remote Zone Temperature—Sets up the AI to accept

a resistive input when connected to one of the sixsupported types of temperature sensors.

• Carbon Dioxide—Sets up the AI to accept a 0 VDC-10VDC input when connected to a CO2 sensor.

• Damper Feedback—Sets up the AI to accept a 0 VDC-10VDC input when connected.

• Outdoor Air Temperature—Sets up the AI to accepta resistive input when connected to one of the sixsupported types of temperature sensors.

• Supply Air Temperature—Sets up the AI to accepta resistive input when connected to one of the sixsupported types of temperature sensors.

Configuring the AIs1. Connect the required sensors to the analog inputs.2. Press the Menu icon.3. Press Setup.4. Press Input Setup.5. Press AI1 Input Selection and select the sensor

that is connected to RSEN. If the selected sensoris a Remote Zone Temperature, Outdoor AirTemperature, or Supply Air Temperature sensor,the thermostat restarts.

6. Do one of the following after the restart based onthe type of sensor you are configuring:

- If the selected sensor is a temperature sensor,do the following:

i. Press Menu > Setup > Input Setup> AI1 Input Setup and selectthe temperature sensor that isconnected to RSEN.

ii. Press Menu > Setup > InputSetup > AI1 Offset and select thetemperature offset as needed forthesensor connected to RSEN. Theoptions are -5°F to 5°F or -2.8°C to2.8°C.

- If the selected sensor is a Relative Humidity,Carbon Dioxide, or Damper feedback sensor,the Input Setup is automatically set to 0VDC-10 VDC. Press Menu > Setup > InputSetup > AI1 Offset and select the offsetneeded for the sensor connected to RSEN. Theoptions are -15% to 15% for Relative Humidity,-200 ppm to 200 ppm for Carbon Dioxide, and-15% to 15% for Damper Feedback.

7. Configure the analog inputs SAT and OAT byfollowing the same steps to set up AI2 InputSelection, AI2 Input Setup, AI2 Offset, AI3 InputSelection, AI3 Setup, and AI3 Offset.

8. Complete steps 1 to 7 to re-configure therespective AI if you have to change the sensorconnected to any of the AIs. When the setup of AI1Input Selection, AI2 Input Selection, and AI3 InputSelection changes from resistive type (RemoteZone Temperature, Outdoor Air Temperature, andSupply Air Temperature) to 0 VDC-10 VDC type(Relative Humidity, Carbon Dioxide, and DamperFeedback) or the other way around, the thermostatrestarts.

Networked sensorsThe TEC3000 supports sensor values supplied over anetwork connection. For the TEC3000 to consider thevalue as reliable, the value must be written to the NET-Override network point at least every 15 minutes. Table13 provides a list of point descriptions and the suggestedwrite interval ranges.Table 13: Point descriptions and suggested writeinterval ranges

Name Description Suggested writeinterval range

NET-OAT

Network Override OutdoorAir Temperature

15 minutes atmaximum

NET-OAH

Network Override OutdoorAir Humidity

15 minutes atmaximum

NET-SAT

Network Override SupplyAir Temperature

30 seconds to 2minutes

NET-ZNH

Network Override ZoneHumidity

5 minutes to15 minutes atmaximum

NET-ZNT

Network Override ZoneTemperature

15 seconds to 2minutes

NET-OCC

Network Override ZoneOccupancy

15 minutes atmaximum

Availability of AIsFor TEC3x3x-1x-xxxx models, RSEN, SAT, and OAT inputsare available for connection.

Priority for configurable AIsYou cannot set any two AIs to the same function orsensor type for any of the inputs. If two or more AIs areconfigured as the same, the first configured input is usedand the others are ignored. For example, if RSEN, SAT, andOAT are all configured as Relative Humidity, only RSEN isused and SAT and OAT are ignored.

Priority for overall sensors data sourcesThe TEC3000 supports various sources of sensor datafor use in control or display, including internal sensors,remote sensors that connect using an analog input, ornetwork commanded sensors. The TEC uses the highestpriority connected input, which consists of networkcommands followed by remote sensors and then internalsensors, for control and display. Not all sources areavailable for all sensors.

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide26

Page 27: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Network commands operate on a timeout basis. Whena network point is written to by a supervisor, the pointbecomes the highest priority for 15 minutes. If thesupervisor writes a new update within 15 minutes, thetimer restarts for another 15 minutes.

Available fault diagnostics• Supply Fan Faults—The TEC3000 supports a

configurable Supply Fan Status feedback input thatturns on when the Supply Fan Status does not matchthe Supply Fan Command, and that you can configureto disable heating, cooling, and fan commands. Youcan adjust the alarm delay with the Fan Alarm delaysetting. If the delay is set to 0 or if you do not definethe binary input, this feature becomes disabled.

• Supply Fan Runtime—The TEC3000 supports settingruntime limits on the supply fan command. Whenthe limit is exceeded, an alarm turns on. This featureis intended to be used as a maintenance reminder.Setting the runtime limit to 0 disables this feature.

• Supply Air Temperature Diagnostics—The TEC3000supports diagnostics when you have a Supply AirTemperature installed. The TEC3000 monitors thesupply air. If you call for cooling or heating and thetemperature does not fall or rise by at least the supplyair temperature alarm offset value within the supplyair temperature alarm delay, an alarm generates.If the monitoring occurs while cooling, a coolingineffective alarm generates. If the monitoring occurswhile heating, a heating ineffective alarm generates. Ifyou set the supply air temperature offset value set to 0,this alarm disables.

• Zone Temperature Alarm—When enabled, the user canset a low and high temperature alarm; and if the zonetemperature rises or falls below those limits, an alarmgenerates.

• Trends—Built-in trends exist for many of the inputs andoutputs for the TEC3000. These trends are viewable atthe TEC. The analog graph displays data in 15-minuteincrements over the previous 24 hours or a tablewith the last 25 data points. Binary trends display 25samples taken at every change of state.

Menus and submenusIn Table 14, the * indicates that the menus depend on your configuration.Table 14: Menus and submenus

Level 1 Level 2 Level 3Dehumidification Dehumidification

Occupied CoolingOccupied HeatingUnoccupied CoolingUnoccupied HeatingStandby CoolingStandby HeatingOcc Setpoint SelectHeat Cool Setpoint ModeMax Heating Setpoint*Min Heating Setpoint*Max Cooling Setpoint*Min Cooling Setpoint*Max Setpoint*

SetpointsTemperature

Min Setpoint*Set ScheduleOptimal Start EnableTemp Occ DurationMotion Sensor TimeoutManual Occupancy Mode

Scheduling Schedule Options

Schedule Source

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 27

Page 28: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Table 14: Menus and submenus

Level 1 Level 2 Level 3Passcode EnabledPasscode*Brightness SettingEnable Backlight TimeoutUnitsTimeTime ZoneSet Time FormatDateSet Date FormatLanguageShow Fan Button on HomeShow Temp on HomeShow Humidity on HomeShow Off Button on HomeShow Hold ButtonShow Setpoint on HomeShow Alarms on HomeShow Occ StatusShow Unit Status

Display Settings

Show Date/Time

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide28

Page 29: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Table 14: Menus and submenus

Level 1 Level 2 Level 3Control ModeUnit EnableFan Mode*Max Setpoint OffsetFan On Delay*Fan Off DelayFrost ProtectionDehum EnableUnocc Dehum EnableDehumidification Sequence Mode*Aux ModeDehumidification Aux Mode*Load Shed Rate LimitLoad Shed AdjustFan Alarm DelayFan Alarm Action*Fan Alarm Reset*Fan Runtime LimitFan Runtime Reset*Supply Air Temperature Alarm OffsetSupply Air Temperature Alarm Delay*Scheduled Circulation EnableScheduled Circulation Only when Occupied

General Setup

Mininum Hourly Fan RuntimeBI1 ConfigBI2 ConfigSupply Temp SensorSupply Temp Offset*Zone Temp SensorZone Temp OffsetReset SensorsFor networked models:Zone Temp Alarm Enabled

For networked models:Zone Temp Low Limit

Setup

Input Setup

For networked models:Zone Temp High Limit

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 29

Page 30: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Table 14: Menus and submenus

Level 1 Level 2 Level 3Temp Control SetupReset PID TuningDeadband*Auto Economizer TuningHeat Prop Band*Heat Integral Time*Heat Process Range*Heat Saturation Time*Heat Time Constant*Heat Process Dead Time*Heat Period*Cool Prop Band*Cool Integral Time*Cool Process Range*Cool Saturation Time*Cool Time Constant*Cool Process Dead Time*Cool Period*Econ Prop Band*Econ Integral Time*Econ Process Range*Econ Saturation Time*Econ Time Constant*Econ Process Dead Time*Econ Period*

Tuning Setup

Equipment SizeFC Comm ModeBACnet Instance ID*For networked models:N2 Address*

BACnet Address*For networked models:MSTP Baud Rate*

BACnet Encoding TypeBACnet/MSTP Communication Mode

Setup (Cont)

Network Setup

For wireless models:Pan ID

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide30

Page 31: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Table 14: Menus and submenus

Level 1 Level 2 Level 3Number of CompressorsLead/Lag Equalize RuntimeNumber of Heating Stages*Compressor Min On TimeCompressor Min Off TimeHeating Min On TimeHeating Min Off TimeSupp Min On TimeSupp Min Off TimeCooling Lockout TempHeating Lockout Temp

General

Unoccupied Off DelayEconomizer InstalledMinimum Position*Closed Voltage*Open Voltage*Dry Bulb Setpoint

Economizer

Outdoor Enthalpy SetpointHeat Pump SupportedSupp Heating Installed*Comp Low Lockout Temp*Supp High OA Lockout Temp*

Equipment Setup

Heat Pump

Reversing Valve Polarity*EFF-ZNTEFF-SETPOINTEFF-ZNHB1 StatusB2 StatusEFF-OATEFF-SATFANSPD-SCLG1-CCLG2-CHTG1-CHTG2-COAD-OHTG-O

Trend

CLG-O

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 31

Page 32: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Table 14: Menus and submenus

Level 1 Level 2 Level 3Occupancy SourceUnit StatusSupply Air TemperatureCooling OAT LockoutHeating OAT LockoutComp Low OAT LockoutSupp High Lockout Temp

System Status

Zone Temp SourceCooling % CommandHeating % CommandSupplemental Heat CommandFanDehumidifier Command*

Control Status

Hot Gas Reheat Command*Model NameSoftware VersionUnit NameDevice Name

Controller Info

Device DescriptionSupply Air TemperatureHeat CommandCool CommandSupply Fan

Commissioning

AuxView VersionLoad FirmwareRestore*

Update

Backup*Radio Code VersionRadio PAN IDActive ChannelSignal StrengthConnection StatusNetwork StateIEEE Address

For wireless models:Network Status

Short Address

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide32

Page 33: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Table 15: TE-6300 Series Temperature Sensors (order separately)

Sensor type Mounting style Probe length Product code number

Adjustable1 8 in. (203 mm) TE-6311A-1

TE-6315M-18 ft (2.4 m)1 TE-6315V-21

TE-6316M-1

Averaging

17 ft (5.2 m)

TE-6316V-21

4 in. (102 mm) TE-631GM-1TE-6311M-18 in. (203 mm)TE-6311P-1

Duct

18 in. (457 mm) TE-631JM-14 in. (102 mm) TE-631GV-2Flange8 in. (203 mm) TE-6311V-2

TE-6310F-0Flush n/aTE-6310F-1

Outside air 3 in. (76 mm) TE-6313P-1Strap-mount 3 in. (76 mm) TE-631S-12Wall2 n/a TE-6314P-1

6 in. (152 mm) TE-631AM-2

Nickel (1k ohm)

Well8 in. (203 mm) TE-6312M-1

Adjustable 8 in. (203 mm) TE-6351-A4 in. (102 mm) TE-635GM-1

TE-6351M-18 in. (203 mm)TE-6351P-1

Duct

18 in. (457 mm) TE-635JM-14 in. (102 mm) TE-635GV-2Flange8 in. (203 mm) TE-6351V-2

TE-6350F-0Flush n/aTE-6350F-1

Strap-mount 3 in. (76 mm) TE-635S-1Outside air 3 in. (76 mm) TE-6353P-1

Wall2 n/a TE-6324P-1

6 in. (152 mm) TE-635AM-2

Platinum (1k ohm)

Well8 in. (203 mm) TE-6352M-110 ft (3 m) TE-6327P-11k ohm averaging1

20 ft (6.1 m) TE-6328P-110 ft (3 m) TE-6337P-1

Platinum equivalent

100 ohm averaging1

20 ft (6.1 m) TE-6338P-1

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 33

Page 34: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Table 15: TE-6300 Series Temperature Sensors (order separately)

Sensor type Mounting style Probe length Product code numberAdjustable 8 in. (203 mm) TE-6341A-1Duct 8 in. (203 mm) TE-6341P-1

4 in. (102 mm) TE-634GV-2Flange8 in. (203 mm) TE-6341V-2

Outside air 3 in. (76 mm) TE-6343P-1

Wall2 n/a TE-6344P-1

8 in. (203 mm) TE-6342M-1

Thermistor (2.2k ohm)

Well6 in. (152 mm) TE-634AM-2

Adjustable 8 in. (203 mm) TE-6361A-14 in. (102 mm) TE-636GM-1

TE-6361M-18 in. (203 mm)TE-6361P-1

Duct

18 in. (457 mm) TE-636JM-14 in. (102 mm) TE-636GV-2Flange8 in. (203 mm) TE-6361V-2

TE-6360F-0Flush n/aTE-6360F-1

Outside air 3 in. (76 mm) TE-6363P-1Strap-mount 3 in. (76 mm) TE-636S-1

6 in. (152 mm) TE-636AM-2

Thermistor (10k ohm)Type II

Well8 in. (203 mm) TE-6362M-1

1 Two TE-6001-8 Element Holders come with the platinum-equivalent averaging sensors. Order separately to use with a nickelaveraging sensor.

2 Order the TE-1800-9600 Mounting Hardware separately to mount the wall unit to a wallbox.

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide34

Page 35: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

TroubleshootingTable 16: Fault list

Faults Probable causes SolutionsRemote Zone Temp Fail The External Zone Temperature

sensor has been disconnected or hasfailed.

1. Check the wiring of the sensor.2. If intentionally disconnected, reset sensors

through the menu.3. If the problem persists, order replacement

units and return the affected devices toJohnson Controls under the RMA program.

Supply Temp Fail The External Supply Temperaturesensor has been disconnected or hasfailed.

1. Check the wiring of the sensor.2. If intentionally disconnected, result fault

by entering the menu, enter Control Setup,and select Inputs to reset the sensors.

3. If the problem persists, order replacementunits and return the affected devices toJohnson Controls under the RMA program.

Outdoor Temp Fail The External Outdoor AirTemperature sensor has beendisconnected or has failed.

1. Check the wiring of the sensor.2. If intentionally disconnected, reset sensors

through the menu.3. If problems persist, order replacement

units and return the affected devices toJohnson Controls under the RMA program.

Internal Sensor Fail An internal sensor has failed on theTEC.

Order replacement units and return theaffected devices to Johnson Controls under theRMA program.

OA Lockouts Disabled The Local Outdoor Air Temperaturesensor has become disconnectedor failed or a network Outdoor AirTemperature sensor has timed out,and the TEC is no longer shuttingdown equipment based on the OAlockout setpoints.

1. If the source of outdoor air temperaturewas a locally connected sensor, follow thesteps for the Outdoor Temp Fail alarm.

2. If the source of outdoor air temperaturewas a BAS, check the BAS to ensure thatit is still online and is providing the TECwith the temperature reading. If removalof the BAS mapping was intentional, resetsensors through the menu.

Econ Unavailable The Outdoor Air Temperature sensoris not installed, has failed, or has beendisconnected and the TEC can nolonger control the economizer.

Follow the same steps as Outdoor Temp Failalarm.

Dehum Unavailable Dehumidification is unavailablebecause the zone humidity sensor hasfailed or the humidity reading is notreliable.

Order replacement units and return theaffected devices to Johnson Controls under theRMA program.

Service Equipment connected to the BIconfigured for a Service alarmtriggers the alarm.

Service the equipment by way of themanufacturer's recommendation.

Dirty Filter Equipment connected to the BIconfigured for a Dirty Filter alarmtriggers the alarm.

Replace the filter in the equipment as explainedin the manufacturer's instructions.

Calibration Corrupt Factory calibration data is lost or isnot installed.

Order replacement units and return theaffected devices to Johnson Controls under theRMA program.

Zone Temp Unreliable All sources of zone temperature areunreliable, including the onboardsensor.

Order replacement units and return theaffected devices to Johnson Controls under theRMA program.

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 35

Page 36: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Table 16: Fault list

Faults Probable causes SolutionsOpen Window The switch connected to the BI

configured for Open Window sensesthat the window is opened, andcontrol has shut down.

1. Close the window to resume control.2. Check sensor functionality with an

ohmmeter, and verify the wiring to theTEC.

3. Order replacement units and return theaffected devices to Johnson Controls underthe RMA program.

Fan Lock The switch connected to the BIconfigured for Fan Lock did not senseairflow within 10 seconds of startingthe fan, and control has been shutdown.

1. Inspect equipment to ensure fanfunctions.

2. Check sensor functionality with anohmmeter, and verify wiring to the TEC.

3. Reset fault by entering the menu, selectingFault Status, and selecting the Fan Lock.

4. Order replacement units and return theaffected devices to Johnson Controls underthe RMA program.

Humidity Unreliable The zone humidity reading wasreliable and has now failed.

1. If the source of zone humidity was theonboard sensor, contact Johnson Controlsproduct sales and support.

2. If the source of zone humidity was a BAS,check the BAS to ensure that it is stillonline and providing the TEC with thehumidity reading. If removal of the BASmapping was intentional, reset sensorsthrough the menu.

The controller has detected aninternal fault that it cannot recover.

Order replacement units and return theaffected devices to Johnson Controls under theRMA program.

Controller Fault

An unknown error has prevented thecontroller from turning on.

Order replacement units and return theaffected devices to Johnson Controls under theRMA program.

Touchscreen Unavailable The touchscreen components fail toinitialize.

1. Reboot the controller.2. If problems persist, order replacement

units and return the affected devices toJohnson Controls under the RMA program.

Board Mismatch The baseboard and CPU board arepaired incorrectly. An error messageappears on the TEC indicating themodel number of the baseboard andCPU board.

Match the baseboard to its corresponding CPUboard. See Figure 6 and Table 4 for informationon ensuring that you have the CPU board andbase board paired correctly.

The previous upgrade did notcomplete.

1. Upgrade the TEC3000 to the latest releasedversion.

2. Upgrade the TEC3000 to the currentversion again.

Firmware Mismatch

The previous downgrade has notcompleted because the previousversion is no longer supported.

Reboot the TEC3000 to clear the fault.

USB Malfunction A USB drive has malfunctioned anddrawn more than the maximumallowed current.

1. Attempt to insert and use the USB driveagain.

2. Try a new USB drive.3. If problems persist, order replacement

units and return the affected devices toJohnson Controls under the RMA program.

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide36

Page 37: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Table 16: Fault list

Faults Probable causes SolutionsSupply Fan Runtime LimitExtended

The Supply Fan Runtime exceeds theconfigured Supply Fan Runtime Limit.

1. Service the Supply Fan.2. Reset the Supply Fan runtime.

Heating Ineffective The Supply Air Temperature hasnot increased above the configuredSupply Air Temperature Alarm Offsetwhile heating has been active forat least the Supply Air TemperatureAlarm Delay.

Verify that the heating elements on the rooftopare functioning correctly.

Cooling Ineffective The Supply Air Temperature has notdecreased below the configuredSupply Air Temperature Alarm Offsetwhile cooling has been active for atleast the Supply Air TemperatureAlarm Delay.

Verify that the cooling elements on the rooftopare functioning correctly.

Supply Fan Fault The Supply Fan Status configuredfor either BI1 or BI2 has not provedwithin the configured Fan AlarmDelay.

1. Verify that the Supply Fan is operatingwhen turned on.

2. Verify that the Supply Fan Status wiring isconnected correctly.

Zone Temperature Too Cold The Zone Temperature decreasedbelow the configured Zone Temp LowLimit.

Verify that the TEC and the RTU heating areenabled and functioning.

Zone Temperature Too Hot The Zone Temperature increasedabove the configured Zone TempHigh Limit.

Verify that the TEC and the RTU cooling areenabled and functioning.

Table 17: Troubleshooting details

Symptom Probable causes SolutionsThe controller displays Idlewith a Unit Status of CoolingUnavailable due to OA Tempdespite being above coolingsetpoint, or with a status ofHeating Unavailable due toOA Temp despite being below thesetpoint.

The outdoor air temperature istoo warm for heating or too coldfor cooling.

1. If Cooling and Heating Lockout Setpointsare inadequate, adjust the setpoints.

2. Wait for the outdoor conditions to befavorable for heating or cooling.

The Control Mode is set toCooling Mode, but the controllerrequests heating.

Change the Control Mode to Auto or Heating.The controller displays Idlewith a Unit Status of CoolingUnavailable due to ControlMode despite being above coolingsetpoint, or with a status ofHeating Unavailable due toControl Mode despite beingbelow the setpoint.

The Control Mode is set toHeating Mode, but the controllerrequests cooling.

Change the Control Mode to Auto or Cooling.

The controller displays Idlewith a Unit Status of CoolingUnavailable despite beingabove cooling setpoint, or with astatus of Heating Unavailabledespite being below the setpoint.

The Number of Compressors setto Not Used and the controller isrequesting cooling, or Numberof Heating Stages is set to NotUsed.

Adjust the number of compressors and numberof heating stages to match the configuration ofthe unit.

The staged equipment shuts offabove the cooling setpoint orbelow the heating setpoint whenthe PID runs on the TEC. If theunit is in On/Off Control mode,this does not apply.

The PID control algorithmminimizes overshoot andenergy usage for the particularequipment and zone, and maycycle the equipment prior toreaching setpoint.

Expected behavior.

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 37

Page 38: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Table 17: Troubleshooting details

Symptom Probable causes SolutionsThe heat pump requirestraditional wiring (Y1, Y2, W1,W2, and G) and handles thereversing valve internally, butHeat Pump Supported is set toYes.

Consult the equipment documentation toverify wiring configuration, then set Heat PumpSupported to No.

The heat pump does notsequence properly.

The heat pump requiresthermostat to control thereversing valve (Y1, Y2,O/B,and G) but the Heat PumpSupported is set to No.

Consult the equipment documentation to verifywiring configuration, then set Heat PumpSupported to Yes.

The heat pump heats when itshould be cooling, and cools whenit should heat.

Reversing Valve polarity isincorrectly set.

Consult the equipment documentation toverify reversing valve polarity, then adjustthe Reversing Valve Polarity menu optionaccordingly.

The staged equipment cycles toorapidly or too slowly when the PIDis running on the TEC.

The control band around thesetpoint is determined by theminimum on/off times and is setincorrectly for the equipment,zone, or user preference. Thereis a tradeoff between reducedcontrol band size and increasedenergy usage and equipmentwear from increased cycling.

1. Verify that equipment minimum on/offtimes are set correctly.

2. If the default deadband around thesetpoint does not provide the requiredtemperature control, set Temp ControlSetup to Deadband Override and set theDeadband parameter to the preferredvalue.

The controller provides an errorwhen trying to upgrade firmware.

The firmware on the USB driveis below the minimum requiredversion. Error code 1025.

Please use firmware version 3.0.2.xxxx (fornetworked models) or 2.0.2.xxxx (for wirelessmodels) or higher. A reboot is required to clearthe Firmware Mismatch fault that occurs.

The TEC3000 zone temperaturedoes not change fast enoughcompared to the measured zonetemperature from a verificationdevice, such as a calibratedsensor.

The TEC3000 is configured bydefault for larger spaces withnormal-sized equipment when aproportional device is active.

Select Control Setup >Tuning > Equipment Size> Oversized.

The zone space temperatureincreases or decreases toomuch when the unit is active inunoccupied mode.

The heating and coolingequipment are too big for theunoccupied space.

Decrease the Unoccupied Off Delay parameterfrom 10 minutes to a more appropriate time forthe equipment configuration.

The controller provides an errorwhen trying to back up settings.

The USB drive is defective. Try a different USB drive.

The USB drive is defective. Try a different USB drive.The Restore file is corrupt. Try restoring a different backup file.

The controller provides an errorwhen trying to restore settingsfrom a backup.

The Restore file is from anincompatible model TEC.

Ensure that the backup file being restored wasfrom the same model TEC.

The drive is formatted as NTFSor another unsupported format.The TEC supports file allocationtable (FAT) (for networkedmodels), FAT16 (for wirelessmodels), and FAT32 (for allmodels) formats only.

Reformat the USB drive, or try a different USBdrive with a supported format.

The controller is unable to accessa USB drive.

The USB drive is defective. Try a different USB drive.

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide38

Page 39: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Table 17: Troubleshooting details

Symptom Probable causes SolutionsThe I/O board that the displayboard is currently attached todoes not match the one thatinitially shipped with the displayboard.

Attach the display board to the correct I/Oboard.

The controller displays BoardMismatch.

A hardware failure causesthe two boards to incorrectlyidentify themselves.

Order replacement units and return the affecteddevices to Johnson Controls under the RMAprogram.

The controller displaysController Fault.

An internal fault was detectedand the controller was unable torecover.

Order replacement units and return the affecteddevices to Johnson Controls under the RMAprogram.

The Bell icon displays on the TEChome page.

The fault has been detected onthe TEC.

See Table 16 for TEC fault causes and resolution.

Partial Restore Complete isdisplayed when trying to restoresettings from a backup file.

Not all of the items in thebackup file have been restored.This error can occur when avalue is out of the minimum ormaximum range in the backupfile. It may also occur if there areinconsistencies in the reliabilityof a setting in the backup fileand on the TEC device.

1. Create a Backup file on a USB drive for theTEC that is showing the issue.

2. Edit the backup file created in the previousstep on a PC to reflect the preferredsettings.

3. Verify that the modified values are withinminimum and maximum range in thebackup file.

4. Restore the settings from the newly editedbackup file on the TEC.

Cold air drafts enter the back ofthe TEC.

Seal any holes behind the TEC to reduce drafts.The temperature displayed islower than the actual roomtemperature. Air is being forced through the

TEC from a nearby vent.Move the location of the TEC or change theventing to prevent air from being forced throughthe TEC.

For networked models, theOnline icon does not appear for anetworked controller.

There is incorrect field buswiring.

Refer to the MS/TP Communications Bus TechnicalBulletin (LIT-12011034).

For wireless models, SupervisoryStatus = Offline

The supervisory controller is notcommunicating with the TEC.The TEC is not mapped to a JCISupervisory System. The WNCGateway is not communicatingwith the TEC.

1. Map the TEC into a JCI Supervisory system.2. Verify that the PAN’s WNC Gateway is

online.3. Add ZFR182x or ZFR183x Routers/Repeaters

into the wireless system.

Some icons are hidden. Lockout levels are used or theicons are hidden due to thedisplay settings.

See Table 7 for lockout levels and access details.

The touchscreen is unresponsive.You do not tap the touchscreen,but the display acts as if it istapped, which causes the displayto blink or toggle betweenscreens.You need to tap the display atan offset from a touch point toactivate the display.

You tap the display or touch thecontroller within 5 mm of thedisplay when power is applied tothe controller.

Reboot the controller. Do not interact with thecontroller until the home screen displays.

Note: For common MS/TP troubleshootinginformation, refer to the MS/TP Communications BusTechnical Bulletin (LIT-12011034).

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 39

Page 40: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

TEC3000 Series Networked and Wireless Single- or Two-Stage EconomizerThermostat Controllers technical specificationsTable 18: TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllerstechnical specifications

Specification DescriptionPower requirements 19 VAC to 30 VAC, 50/60 Hz, 4 VA at 24 VAC nominal, Class 2 or safety extra-low

voltage (SELV)USB port power rating 120 mA to 250 mA current draw supportedRelay contact rating 19 VAC to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush, Class 2 or SELVBinary inputs Dry contact across terminal COM to terminals BI1 or BI2Analog inputs Nickel, platinum, A99B, 2.25k ohm NTC, 10k ohm NTC, 10k ohm NTC Type 3 across

terminal COM to terminals R SENTemperature sensor type Local digital sensorWire size 18 AWG (1.0 mm diameter) maximum, 22 AWG (0.6 mm diameter) recommended

For wired models: Up to 100 devices maximum for each Network AutomationEngine (NAE); 4,000 ft (1,219 m) maximum cable length. Refer to the MS/TPTechnical Bulletin for the Metasys, FX, or Verasys® system installed.

MS/TP network guidelines

For wireless models: Up to 100 devices maximum for each Network AutomationEngine (NAE)

Wireless band (for wireless models) Direct-sequence spread-spectrum 2.4 GHz ISM bandsZFR 10 mW maximumTransmission

power (forwirelessmodels)

ZFR Pro2 100 mW maximum

50 ft (15.2 m) recommended indoorTransmission range (for wirelessmodels) 250 ft (76.2 m) line of sight, maximum

Backlit display -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° incrementsHeating control 40.0°F/4.5°C to 90.0°F/32.0°C

Temperaturerange

Cooling control 54.0°F/12.0°C to 100.0°F/38.0°CAccuracy Temperature ±0.9F°/±0.5C° at 70.0°F/21.0°C typical calibratedMinimum deadband 2F°/1C° between heating and coolingoccupancy sensor motion detection(occupancy sensing models)

Minimum of 94 angular degrees up to a distance of 15 ft (4.6 m); based on a clearline of sight

Operating 32°F to 122°F (0°C to 50°C); 95% RH maximum, noncondensingAmbientconditions Storage -22°F to 122°F (-30°C to 50°C); 95% RH maximum, noncondensing

BACnetInternational

BACnet Testing Laboratories™ (BTL) 135-2001 Listed BACnet Advanced ApplicationController (B-AAC)UL Listed, File E27734, CCN XAPX, Under UL60730Networked models: FCC Compliant to CFR 47, Part 15, Subpart B, Class B

United States

Wireless models: Transmission complies with FCC Part 15.247 regulations for lowpower unlicensed transmitters; transmitter identification FCC: OEJ-WRZRADIO.ZFR183x: Contains FCC ID: OEJZFRPRO2

UL Listed, File E27734, CCN XAPX7, Under E60730Networked models: Industry Canada, ICES-003

Compliance

Canada

Wireless models: Industry Canada (IC) RSS-210; Transmitter identificationZFR1810-1: IC: 279A-WRZRADIO.ZFR183x: Contains IC: 279A-ZFRPRO2

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide40

Page 41: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

Table 18: TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllerstechnical specifications

Specification DescriptionEurope (fornetworkedmodels only)

CE Mark – Johnson Controls declares that this product is in compliance with theessential requirements and other relevant provisions of the EMC Directive and theRoHS Directive.

Australia and NewZealand

RCM Mark, Australia/NZ Emissions Compliant

Models withoutoccupancy sensor

0.75 lb (0.34 kg)Shippingweight

Models withoccupancy sensor

0.77 lb (0.35 kg)

Repair informationIf the TEC3000 Series Thermostat Controller fails tooperate within its specifications, replace the unit. For areplacement thermostat controller, contact the nearestJohnson Controls representative.

Product warrantyThis product is covered by a limited warranty, detailsof which can be found at www.johnsoncontrols.com/buildingswarranty.

Software termsUse of the software that is in (or constitutes)this product, or access to the cloud, or hostedservices applicable to this product, if any,is subject to applicable terms set forth atwww.johnsoncontrols.com/techterms. Your use of thisproduct constitutes an agreement to such terms.

PatentsPatents: https://jcipat.com

Single point of contactAPAC Europe NA/SAJOHNSON CONTROLS

C/O CONTROLS PRODUCTMANAGEMENT

NO. 32 CHANGJIJANG RD NEWDISTRICT

WUXI JIANGSU PROVINCE 214028

CHINA

JOHNSON CONTROLS

WESTENDHOF 3

45143 ESSEN

GERMANY

JOHNSON CONTROLS

507 E MICHIGAN ST

MILWAUKEE WI 53202

USA

Contact informationContact your local branch office:www.johnsoncontrols.com/locationsContact Johnson Controls: www.johnsoncontrols.com/contact-us

TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 41

Page 42: Controllers Installation Guide · protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou

© 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision andare subject to change without notice.

www.johnsoncontrols.com